christenson corporation€¦  · web viewclosing fire and smoke doors normally held open by...

43
SECTION 16721 FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. EXTENT: Provide equipment, wiring, conduit or approved Fire Alarm Cable, (Fire Alarm Cable used in areas dedicated as Assembly must use MC Type Fire Alarm Cable) special wall boxes and cabinets to make a complete and functioning system as hereinafter specified and shown on the plans. Provide equipment and materials compatible to the system supplied. Equipment shall be located as shown on the drawings. Equipment not specifically specified or shown on the drawings, but required for the operation of a completely functional system shall be provided. B. Related Sections: The following Sections may contain requirements that relate to this Section: 1. Division 15 Section "Fire Protection" for water-flow, pressure, tamper switches and/or fire pump connected to fire alarm system. 2. Division 15 Section "Pneumatic Control Systems" for duct smoke detectors. 3. Division 15 Section "Electric Control Systems" for duct smoke detectors. 4. Division 16 Section "Intrusion Detection Systems" for Security monitoring. 1.2 MANUFACTURER'S QUALIFICATIONS A. THE SYSTEM shall be produced by one of the approved manufacturers who shall have produced similar systems for a period of at least ten years. The local factory representative shall have been established locally providing sales and service for a minimum of the last four years. B. REFERENCE LIST shall be provided with a minimum of (5) five projects of similar size and operation. Reference list shall be for projects completed within the last (3) years and 16721-1 LK 00000

Upload: others

Post on 23-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

SECTION 16721

FIRE ALARM SYSTEM

PART 1 - GENERAL

1.1 DESCRIPTION

A. EXTENT: Provide equipment, wiring, conduit or approved Fire Alarm Cable, (Fire Alarm Cable used in areas dedicated as Assembly must use MC Type Fire Alarm Cable) special wall boxes and cabinets to make a complete and functioning system as hereinafter specified and shown on the plans. Provide equipment and materials compatible to the system supplied. Equipment shall be located as shown on the drawings. Equipment not specifically specified or shown on the drawings, but required for the operation of a completely functional system shall be provided.

B. Related Sections: The following Sections may contain requirements that relate to this Section:1. Division 15 Section "Fire Protection" for water-flow, pressure, tamper

switches and/or fire pump connected to fire alarm system. 2. Division 15 Section "Pneumatic Control Systems" for duct smoke

detectors. 3. Division 15 Section "Electric Control Systems" for duct smoke detectors. 4. Division 16 Section "Intrusion Detection Systems" for Security monitoring.

1.2 MANUFACTURER'S QUALIFICATIONS

A. THE SYSTEM shall be produced by one of the approved manufacturers who shall have produced similar systems for a period of at least ten years. The local factory representative shall have been established locally providing sales and service for a minimum of the last four years.

B. REFERENCE LIST shall be provided with a minimum of (5) five projects of similar size and operation. Reference list shall be for projects completed within the last (3) years and include the following items for EACH reference:1. Name/Address/Owner of Project2. Contact Person/Title/Phone Number3. Completion Date of Project4. Complete Equipment List (BOM)5. Length of Time Local Supplier has been a Dealer for the Brand of

Equipment Installed AND if Dealership is currently active. 6. Manufacturer's Factory Training and Certifications Received on this Type

Equipment by Sales/Service Personnel, (include copies of Certificates)a. Detailed Project Description

C. THE LOCAL SYSTEM manufacturer/supplier shall be licensed and certified in accordance with the City Jurisdiction, The State Jurisdiction and any other applicable agency. The local manufacturer/supplier shall provide applicable "Certificates" and/or "Licenses" upon demand of the building owner, architect or

16721-1 LK 00000

Page 2: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

engineer. The local manufacturer/supplier shall co-ordinate and provide a test of the system in the presence of the Fire Department - Fire Prevention Division in accordance with the Fire Departments Testing requirements. The supervising technician shall be minimum NICET Level II certified under the field of Fire Protection Engineering Technology subfield of Fire Alarm Systems and at least one of the system suppliers local management personnel shall be NICET Level III certified under the field of Fire Protection Engineering Technology subfield of Fire Alarm Systems.

D. BEFORE SUBMITTALS are reviewed by the Engineer, System Supplier shall submit completely wired drawings and SUBMITTALS indicating all connections and devices to the Authority Having Jurisdiction (AHJ) for approval. This approval must accompany the submittals in writing to the Engineer by the System Supplier for the Engineer's review. The Engineer will furnish AutoCad files of the Architectural Plans for the System Supplier's use in preparation of these documents on request.

E. UPON COMPLETION of the installation, the system manufacturer shall send factory trained personnel to perform all necessary final electrical tests and adjustments at the jobsite and who shall then submit a "Letter of Certification" stating that: The system was tested and functions properly and that the system conforms to the requirements of these specifications. Tests to be performed and reports to be submitted shall be a specified hereinafter. The system manufacturer shall notify the Owners' Representative at least one week prior to final testing. All test reports shall be certified and sent to the Owners' Representative for review. Tests shall be performed in the presence of the Owners' Representative.

F. ALL EQUIPMENT furnished under this specification shall be installed under the direct supervision of technically qualified full-time employees of the manufacturer of the specific equipment.

G. APPROVED MANUFACTURERS:

Simplex Time RecorderEdwards System Technology

H. THE FACT THAT a manufacturer is an APPROVED MANUFACTURER does not diminish their responsibility to meet all the criteria as directed in this specification including but not limited to the manufacturer's local representation requirements.

I. FOR THE basis of establishing a criteria for the required equipment, the specifications refer to Simplex equipment and model numbers.

J. SUBSTITUTIONS of products proposed to be equal to those specified herein will be considered only when the following requirements have been met:

1. A COMPLETE LIST of such substituted products, with drawings and data sheets, shall be submitted to and approved by the consulting engineer, not less than ten (10) calendar days prior to scheduled date of opening of bids.

16721-2 LK 00000

Page 3: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

2. IT SHALL CONFORM to the standards herein and the manufacturer must supply proof of having produced similar equipment for at least ten years with a written history of system now rendering satisfactory service provided. Supplier of this equipment must also have had service and sales of the same equipment for the past four (4) years. Substitute equipment and its capabilities must be a standard part of that systems current product line and must meet or exceed the capabilities of the equipment specified. Contractors are cautioned to conform to this specification so that the system provided will insure future options and priorities of the owner with regard to the systems use. If the alternate system fails to provide all the requireme nts specified in this documen t, the Contractor shall be responsi ble for all costs associated with the removal and replacement of said equipment.

3. A BIDDER INTENDING to use acceptable substitute products shall submit two price quotations: one based on the use of products specified herein; the other shall define the use of substitute products and list cost differentials as related to the base quotation.

4. THE CONTRACTOR shall submit a point-by-point statement of compliance for All Sections.

5. THE STATEMENT of compliance shall consist of a list of all numbered paragraphs within these sections.

6. WHERE THE PROPOSED system complies fully with the numbered paragraphs as written, such shall be indicated by placing the word "comply" opposite the paragraph number.

7. WHERE THE PROPOSED system does not comply with the paragraph as written, but the Contractor feels it will accomplish the intent of the paragraph in a manner different from that described, a full description of the intent perceived by the Contractor shall be provided as well as a full description of how its proposal will meet its perceived intent.

8. WHERE A FULL DESCRIPTION is not provided, it shall be assumed that the proposed system does not comply with the paragraph in question.

9. ANY SUBMISSION which does not include a point-by-point statement of compliance as described herein shall be disqualified.

1.3 SYSTEM

A. EQUIPMENT: 4010 Life Alarm System by Simplex Time Recorder Co., unless otherwise indicated, shall be the standard product of one manufacturer and shall be factory coordinated. The system shall use addressable device circuits with individual supervision, individual notification appliance circuit supervision, incoming and standby power supervision. Include a control unit, signal circuit expander (if required), manual pull stations (fire alarm boxes), automatic fire detectors, horns, strobes, remote control devices, all wiring, connections to devices, outlet boxes, junction boxes, and all other necessary material for a complete operating system.

B. APPLICATION: 4010 system sized as required based on number of addressable devices required and number audio/visual circuits. The Handicap Suites shall contain UL 1971/ADA acceptable Audio/Visual Alarm Indicating Units. The fire alarm control unit shall allow for loading or editing special instructions and

16721-3 LK 00000

Page 4: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

operating sequences as required. The system is to be capable of on-site programming to accommodate facilitate expansion, building parameter changes, or changes as required by local codes. All software operations are to be stored in a non-volatile programming memory within the fire alarm control unit.  Loss of primary and secondary power shall not erase the instructions stored in memory. The ability for selective input/output control functions based on ANDing, Oring, NOTing, timing and special coded operations is to also be incorporated in the resident software programming of the system.The FACU shall utilize TrueWare File Comparison Software to copy/analyze/compare and provide a detailed report to the system programmer indicating in detail any system operations which should be tested after changes are made to a system configuration. This utility shall report the differences between the two created database files (before and after).

C. EQUIPMENT: U.L. approved and installed in accordance with the requirements of the National Electric Code, Local Codes and these specifications with the stricter requirement governing in case of possible variance. Systems equipment shall be jointly guaranteed by the Contractor and the Systems' Manufacturer for a period of one year from date of acceptance.

1.4 OPERATION

A. FIRE ALARM CONTROL UNIT (FACU): Shall monitor and control all addressable devices and each initiating device shall be individually addressable within the building as follows. All wiring shall be Class A as follows:1. Style 6 - Signaling Line Circuits (Addressable Circuits)2. Style D - Initiating Device Circuits

(Wiring between Monitor Zams and/or IAMs & the device being monitored)

3. Style Z - Notification Appliance Circuits (Horn/Strobe Circuits)4. IF REQUIRED ON DRAWINGS: Elevator Machine Room shall be

furnished with a rate of rise heat detector to disconnect the elevator equipment prior to the sprinkler head discharge per ASTM 17. Verify local requirements and comply with all codes.

5. The FACU shall also provide power and monitor carbon monoxide detectors.

B. The FACU shall be 24VDC operation with 120 VAC operating power. Twenty Four hours of standby power shall be provided by internally mounted properly sized, sealed gelyte lead acid batteries.

C. ALARM INITIATION: Provided from Manual Stations, Sprinkler Waterflow Switches located one per floor and System Smoke Detectors and Heat Detectors as indicated. Provide Audio/Visual Alarm Indicating Devices inside each Handicap Suite and Audio Alarm Indicating Devices inside each Non-Handicap Suite. Provide Audio/Visual Alarm Indicating Devices on the interior of the building. Devices shall be located as shown on the drawings. The control panel shall also provide dedicated audible alarm circuits for carbon monoxide alarms, audible alarms for carbon monoxide shall be different and distinct from fire alarms.

16721-4 LK 00000

Page 5: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

D. GENERAL ALARM INDICATION: Provide a general alarm when any initiating device described is activated. A system general alarm shall include:1. Indicating the general alarm condition at the FACU and the annunciator. 2. Identifying the device that is the source of the alarm at the FACU and the

annunciator. 3. Displaying the alarm on an 80 character LCD display. The system alarm

LED shall flash on the control unit and the annunciator until the alarm has been acknowledged. Once acknowledged, this same LED shall latch on. A subsequent alarm received from another zone shall flash the system alarm LED on the control unit and annunciator. The display shall show the new alarm information.

4. A pulsing alarm tone shall occur within the control unit and the annunciator until the event has been acknowledged.

5. Operating audible and visible alarm notification signals throughout the building.

6. Sounding a continuous fire alarm signal until silenced by the alarm silence switch at the control unit or at the annunciator.

7. All visible alarm notification appliances shall flash continuously until the Alarm Silence Switch is operated.

8. Any subsequent zone alarm shall reactivate the alarm notification appliances.

9. Closing fire and smoke doors normally held open by magnetic door holders. All doors normally held open by 24 VDC door control devices shall release after a [15] second time delay.

10. Unlocking designated doors. 11. Stopping supply and return fans serving zone where alarm is initiated. 12. Closing smoke dampers on system serving zone where alarm is initiated.13. Initiating smoke control sequence through a signal to the building

automatic temperature control system. 14. Activating any and all FACUs programmed for control of dedicated supply

and exhaust fans in an alarm situation. Provide dedicated override control points located near the fan control centers. If the building HVAC controls are used for smoke exhaust, the designated fire alarm control unit shall be programmed to override the HVAC controls and put all fan and dampers into the appropriate fire mode.

15. Activating the air handling systems per life safety code, NFPA 90A and NFPA 101.

E. REMOTE FIRE ALARM ANNUNCIATOR operation shall be as follows:1. There shall be a minimum of (1) 4606-9101 LCD Digital Remote

Annunciators in addition to the FACU, at the designated Fire Dept. Entrance.

2. Each Remote Annunciator shall be capable of displaying in English alpha/numeric text via an 80 character (2 line x 40 character) display any or all alarms from the FACU.

3. Each Remote Annunciator shall be capable of the following once the "Key Enable" Switch is activated:a. Alarm, Supervisory and Trouble Acknowledgeb. Alarm Silencec. Silencing the internal trouble buzzerd. Resetting the Fire Alarm system

16721-5 LK 00000

Page 6: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

4. Annunciator and FACU shall display the alarm by first indicating the known area of the building:a. Type of Alarm (Alarm, Trouble, Supervisory).b. Then by a custom label indicating floor, corridor, room number

indicating the exact device.

F. INITIATING AUTOMATIC elevator recall per ASME/ANSI A17. 1 and A17. 3. 1. The alarm activation of any elevator lobby smoke detector shall, in

addition to the operations listed above, cause the elevator cabs to be recalled according to the following sequence:a. If the alarmed device is on any floor other than the main level of

egress, the elevator cabs shall be recalled to the main level of egress.

b. If the alarmed device is on the main egress level, the elevator cabs shall be recalled to the predetermined alternate recall level as determined by the local authority having jurisdiction.

G. ENTIRE SYSTEM: May be reset only following the resetting of individual alarm

initiation devices and a resetting procedure within the FACU. System trouble indication devices shall continue to operate until this operation is complete, with a system trouble bell being mounted directly adjacent to the FACU.

H. CITY CONNECTION: Provide the connection from the Main FACU to an off-site Central Monitoring Facility via telephone line connection in order to provide automatic summons of the Fire Department in case of alarm. THIS CONNECTION SHALL BE OF THE TYPE REQUIRED BY THE CITY AND SHALL BE PREAPPROVED BY THE AHJ. (Telephone lines as required to be provided by Owner). System Supplier shall provide the equipment for this function. Electrical Contractor shall install and wire equipment per the suppliers and city's instruction.

I. ALARM VERIFICATION: The activation of any system smoke detector shall initiate an Alarm Verification operation whereby the unit will reset the activated detector and wait for a second alarm activation.  If, within one (1) minute after resetting, a second alarm is reported to the FACU it shall process the alarm as described previously.  If no second alarm occurs within one minute the system is to resume normal operation.  The Alarm Verification is to operate only on smoke detector alarms. Other activated initiating devices shall be processed immediately. The alarm verification operation is to be selectable by device.1. The control unit shall have the capability to display the number of times

(tally) a zone or device has gone into a verification mode. Should this smoke verification tally reach a pre-programmed number, a trouble condition shall occur.

2. Alarm verification devices shall have the capability of being divided into eight different groups whereby only two verification zones from a group will confirm the first activation and cause the unit to follow programmed alarm sequence.

J. SPRINKLER SUPERVISORY SIGNAL: The control unit is to have a dedicated supervisory service LED and a dedicated supervisory service acknowledge switch.

16721-6 LK 00000

Page 7: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

1. The activation of any standpipe or sprinkler valve tamper switch shall activate the system supervisory service audible signal and illuminate the LED at the control unit.  Differentiation between valve tamper activation and opens and/or grounds on fire alarm initiation circuit wiring shall be provided.

2. Activating the Supervisory Service Acknowledge Switch will silence the supervisory audible signal while maintaining the Supervisory Service LED on indication that the tamper contact is still in the off-normal state.

3. Restoring the valve to the normal position shall cause the supervisory service audible signal to pulse, thus indicating restoration to normal position. Activating the Supervisory Service Acknowledge Switch will silence the audible signal and restore the system to normal.

4. Low-air pressure switch operation on a dry pipe or preaction sprinkler system shall cause or initiate the following:a. Activate the system supervisory service audible signal and

illuminate the LED at the control unit and the annunciator. Differentiation between low-air pressure activation and opens and/or grounds on the initiation circuit wiring shall be clearly identified in plain-language on the FACU Alphanumeric display.

b. Pressing the Supervisory Service Acknowledge Key shall silence the supervisory audible signal while maintaining the Supervisory Service LED "on" indicating the off-normal condition.

c. A record of the event in the FACU historical LOG. d. Transmission of supervisory signal to remote central station. e. Restoring the air pressure to normal shall cause the Supervisory

Service LED to extinguish, indicating restoration to normal.

K. MANUAL EVACUATION: Within the Control Unit a manual evacuation switch shall be provided to operate the systems alarm notification appliances. Other control circuits shall not be activated. However, a true alarm shall be processed as described previously.

L. ACTIVATION of an auxiliary bypass switch shall override the automatic functions either selectively or throughout the system.

M. ALARM AND TROUBLE CONDITIONS: Shall be immediately displayed on the control unit front alphanumeric display.  If more alarms or troubles are in the system, the operator may scroll to display new alarms.

N. THE SYSTEM: Shall have an alarm list key that will allow the operator to display all alarms, troubles, and supervisory service conditions with the time of occurrence. This shall allow for the determination of not only the most recent alarm but also may indicate the path that the fire is taking.

O. ALL DOORS normally held open by door control devices shall release upon AC power failure. All magnetic door holders whether furnished by the system supplier or the door hardware supplier shall be 24vdc and shall be powered by the FACU. Door holder/closers furnished by the hardware supplier shall be wired by the electrical contractor. Door lock system on doors as supplied by another vendor shall be connected to the FACU for the purpose of releasing doors upon a fire alarm. The fire alarm system supplier shall provide one form "c" dry contact

16721-7 LK 00000

Page 8: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

in the FACU for this purpose.

P. THE CONTROL UNIT shall be capable of supplying up to 8 Amps @ 24VDC power output for external system use.

Q. WHEN PRINTER IS INDICATED ON THE PLANS: Recording of Events: Record all alarm, supervisory, and trouble events by means of system printer. Printouts are by zone, device, and function. When the FACU receives a signal, the alarm, supervisory & trouble] conditions are printed. The printout shall include the type of signal (e.g. alarm, supervisory, or trouble) the device or zone identification, date, and the time of the occurrence. The printout differentiates alarm signals from all other printed indications. When the system is reset, this event is also printed, including the same information concerning location, date, and time.

R. ONE PERSON WALK TEST: The actuation of the "enable one person test" program at the control unit shall activate the "One Person Testing" mode of the system which shall cause the following to occur:1. The city circuit connection shall be bypassed. 2. Control relay functions shall be bypassed. 3. The control unit shall show a trouble condition. 4. The alarm activation of any initiation device shall cause the audible

notification appliances to code a number of pulses to match the zone or device number.

5. The unit shall automatically reset itself after signaling is complete. 6. Any momentary opening of an initiating or notification appliance circuit

wiring shall cause the audible signals to sound for 4 seconds indicating the trouble condition.

7. Auxiliary manual controls shall be supervised so that an "off normal" position of any switch shall cause an "off normal" system trouble. The Aoff normal@ status shall be clearly identified in plain-language on the FACU alphanumeric display.

S. SUPERVISION: Each independently supervised circuit shall include a discrete readout to indicate disarrangement conditions per circuit. The System Modules shall be electrically supervised for module placement. Should a module become disconnected the system trouble indicator shall illuminate and the audible trouble signal shall sound. The system shall have provisions for disabling and enabling all circuits individually for maintenance or testing purposes.

T. POWER REQUIREMENTS:

1. The control unit shall receive 120 VAC power via a dedicated fused disconnect circuit.

2. The system shall be provided with sufficient battery capacity to operate the entire system upon loss of normal 120 VAC power in a normal supervisory mode for a period of [24] hours with [5] minutes of alarm operation at the end of this period. The system shall automatically transfer to battery standby upon power failure. All battery charging and recharging operations shall be automatic.

3. All circuits requiring system operating power shall be 24 VDC and shall be individually fused or equivalently protected at the control unit.

4. The incoming power to the system shall be supervised so that any power

16721-8 LK 00000

Page 9: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

failure must be audibly and visibly indicated at the control unit and the annunciator. A green "power on" LED shall be displayed continuously while incoming power is present.

5. The system batteries shall be supervised so that a low battery condition or disconnection of the battery shall be audibly and visibly indicated at the control unit and the annunciator.

6. If ALOW BATTERY@ condition is left unattended a second stage ADEPLETED BATTERY@ trouble condition shall be audibly and visibly reported at the control unit indicating the batteries are below the listed system operating voltage. Systems that completely shut down and fail to indicate ADEPLETED BATTERY@ condition shall be unacceptable.

PART 2 - PRODUCTS

2.1 SYSTEM

A. FIRE ALARM CONTROL UNIT (FACU)

1. General: Comply with UL 864, "Control Units for Fire-Protective Signaling Systems" and shall be Year 2000 compliant.

2. Cabinet: Lockable steel enclosure. Arrange unit so all operations required for testing or for normal care and maintenance of the system are performed from the front of the enclosure. If more than a single unit is required to form a complete control unit, provide exactly matching modular unit enclosures. Accommodate all components and allow ample gutter space for interconnection of units as well as field wiring. Identify each enclosure by an engraved, red-laminated, phenolic resin nameplate. Lettering on the enclosure nameplate shall not be less than 1-inch] high. This nameplate shall be provided by the electrical contractor.

3. Systems: Alarm and supervisory systems are separate and independent in the FACU. All modules shall be installed on a single piece chassis to facilitate easy installation and removal. All circuit connections shall be up front and easily accessible.

4. Control Modules: Types and capacities required to perform all functions of the fire alarm systems [plus 20% for future expansion]. Local, visible, and audible signals notify of alarm, supervisory, and trouble conditions

5. Zones: Provide for all alarm and supervisory zones indicated including addressable zones.

6. Alphanumeric Display and System Controls: Arrange to provide the basic interface between human operator at FACU and addressable system components, including annunciation, supervision, and control. A display with a minimum of 80 characters displays alarm, supervisory, and component status messages and indicates control commands to be entered into the system for control of smoke sensor sensitivity and other parameters. Arrange keypad for use in entering and executing control commands.

7. Instructions: Printed or typewritten instruction card mounted behind a LEXAN plastic or glass cover in a painted steel or aluminum frame. Install the frame in a location observable from the FACU. Include interpretation and appropriate response for displays and signals, and briefly describe the functional operation of the system under normal, alarm, and trouble

16721-9 LK 00000

Page 10: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

conditions.

B. FIRE ALARM CONTROL UNIT (FACU)1. Control Unit construction shall be modular with solid state,

microprocessor based electronics. It shall display only those primary controls and displays essential to operation during a fire alarm condition. Keyboards or keypads shall not be required to operate the system during fire alarm conditions. A local audible device shall sound during Alarm, Trouble or Supervisory conditions. This audible device shall also sound during each keypress to provide an audible feedback to ensure that the key has been pressed properly.

2. The following control unit hardware shall be provided;a. 1 base panel with beige cabinet and door, 120VAC input power.b. 250 Addressable point capacity PER PAIR OF WIRES. c. Addressable Annunciator Circuitd. 4 Notification Appliance Circuits - Class Ae. 2 Auxiliary Control Relaysf. Sufficient power to operate the control unit and minimum of 4

amps power for Notification Appliances (but sufficient enough for the entire system).

g. Battery Voltage and Amp Metersh. 1 Municipal City Circuiti. 1 RS-232 Port and 1 Modem Portj. Common Event DACT or Point Reporting DACT (as required by

AHJ)3. The following primary controls shall be visible through a front access Unit:

a. Individual red fire alarm LEDb. Individual yellow supervisory service LEDc. Eighty character liquid crystal displayd. Individual yellow trouble LEDe. Green "power on" LEDf. Yellow signals silenced LEDg. Fire alarm acknowledge keyh. Supervisory service acknowledge keyi. Trouble acknowledge keyj. Alarm silence keyk. System reset keyl. 3 Status indicators for [Waterflow] [Sprinkler Supervisory] [Ground

Fault] [future use]4. The FACU shall provide the following bypass controls:

a. Manual Evacuationb. City Circuit Bypassc. Control Point Bypassd. Elevator Bypasse. Door Holder Bypassf. Lamp Testg. Earth Fault Latchh. Display Time & Datei. [2 spares for future use]

5. The control Unit shall provide the following operational features:a. Setting of time and date

16721-10 LK 00000

Page 11: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

b. Front Panel and PC Programming capabilityc. Automatic device level general alarm programming with default

label generationd. Alarm, trouble, and abnormal condition listinge. Enabling and disabling of each monitor point separately with abort

warning when circuits are enabledf. Activation and deactivation of each control point separatelyg. Changing operator access levelsh. One Person test enablei. Running diagnostic functions including ADevice Level@ Ground

Fault Searchj. Displaying software revision levelk. Displaying historical logsl. Displaying card statusm. Point listingn. Software Verification (simulate mode)o. Ground Fault Latch capabilityp. English language reports with analog sensor current value, peak

value, alarm sensitivity, and almost dirty data 6. For additional maintenance purposes the following lists shall be available

from the point lists menu:a. All points list by addressb. Monitor point listc. Signal listd. Auxiliary control liste. Feedback point listf. Pseudo point listg. LED/switch status list

7. Scrolling through menu options or lists shall be accomplished in a self-directing manner in which prompting messages shall direct the user. These controls shall be located behind an access door. a. Primary Keys, LED's and LCD Display

8. The Control Unit shall have a 80 character liquid crystal display which shall be backlit for enhanced readability. So as to conserve battery standby power, it shall not be lit during an AC power failure unless an alarm condition occurs or there is keypad activity.

9. Under normal conditions the front unit shall display a "System is Normal" message and the current time and date. System shall be Year 2000 Compliant.

10. Should an abnormal condition be detected the appropriate LED (Alarm, Supervisory or Trouble) shall flash. The unit audible signal shall pulse for alarm conditions and sound steady for trouble and supervisory conditions.

11. The LCD shall display the following information relative to the abnormal condition of a point in the system:a. 40 character custom location labelb. Type of device (i.e. smoke, pull station, waterflow)c. Point status (i.e. alarm, trouble)

12. Acknowledge functions may be passcode protected if the user has insufficient privilege to acknowledge such conditions. A message shall indicate insufficient privilege but allow the user to view the points without acknowledging them. Should the user have sufficient privilege to

16721-11 LK 00000

Page 12: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

acknowledge, a message will be displayed informing the user that the condition has been acknowledged.

13. After all points have been acknowledged, the LEDs shall glow steady and the tone alert will be silenced. The total number of alarms, supervisory and trouble conditions shall be displayed along with a prompt to review each list chronologically. The end of the list shall be indicated by an end of list message "END of LIST".

14. Alarm Silencing:a. Should the "Alarm Silence" button be pressed all alarm signals

shall cease operation and a signals silenced LED will illuminate. b. Signals shall not be silenced during alarm silence inhibit mode.

15. System Reset:a. The SYSTEM RESET button shall be used to return the system to

its normal state after an alarm condition has been remedied. The LCD display shall step the user through the reset process with simple English Language messages. Messages, "SYSTEM RESET IN PROGRESS", will first be displayed followed by the message, "SYSTEM RESET COMPLETED", and finally, "SYSTEM IS NORMAL", should all alarm conditions be cleared.

b. Should an alarm condition continue to exist the message, "SYSTEM RESET IN PROGRESS", will be followed by the message, "SYSTEM RESET ABORTED", and the system will remain in an abnormal state. System control relays shall not reset. The tone alert and the Alarm LED will be on. The display will indicate the total number of alarms and troubles present in the system along with a prompt to use the ACK keys to review the points. These points will not require acknowledgment if they were previously acknowledged.

c. Should the Alarm Silence Inhibit function be active, the (SYSTEM RESET) key press will be ignored. The message, "SYSTEM RESET INHIBITED", will be displayed for a short time to indicate the action was not taken. As feedback to the operator, the message "SYSTEM RESET NO LONGER INHIBITED" will be displayed when the inhibit function times out.

16. Viewing Point Statusa. The FACU shall provide access to status data for the following

points:(1) Initiating device circuits(2) Indicating appliance circuits(3) Auxiliary relays(4) Feedback points(5) All other input/output points

b. The following status data shall be available:(1) Primary state of point(2) Zone, Point ID and card type information(3) Class "A" status(4) Current priority of outputs(5) Disable/Enable status(6) Verification tallies of initiating devices(7) Automatic/Manual control status of output points(8) Acknowledge status

16721-12 LK 00000

Page 13: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

(9) Relay status17. The system shall be capable of logging and storing events in separate

alarm, supervisory, and trouble history logs. Each recorded event shall include the time and date of that event's occurrence. In addition, all events shall be capable of being displayed in a single combined log.a. The following Historical Alarm log events shall be stored:

(1) Alarms(2) Alarm acknowledgment(3) Alarm Silence(4) System reset(5) Alarm historical log cleared

b. The following Historical Supervisory log events shall be stored:(1) Supervisory alarms(2) Supervisory acknowledgment

c. The following Historical Trouble log events shall be stored:(1) Trouble conditions(2) Supervisory alarms(3) Trouble acknowledgment(4) Supervisory acknowledgment(5) Alarm verification tallies(6) One Person test results(7) Trouble historical log cleared

18. Silent One Person Testing with History Logginga. The system shall be capable of being tested by one person. While

in testing mode the alarm activation of an initiating device circuit shall be silently logged as an alarm condition in the historical data file. The unit shall automatically reset itself after logging of the alarm.

b. The momentary disconnection of an initiating or indicating device circuit shall be silently logged as a trouble condition in the historical data file. The unit shall automatically reset itself after logging of the trouble condition.

c. Should the one person test feature be on for an inappropriate amount of time it shall revert to the normal mode automatically. After testing is considered completed, testing data may be retrieved from the system in chronological order to ensure device/circuit activation.

19. LED Supervision. All control module LEDs shall be supervised for burnout or disarrangement. Should a problem occur the LCD shall display the module and LED location numbers to facilitate location of the LED.

20. System Active Status Reminder. Should an active alarm, supervisory, or trouble condition be present within the system and the audible tone alert signal silenced, the tone alert signal shall resound at preprogrammed time intervals to act as a reminder that the fire alarm system is not 100% operational. Both the time interval and the reminder signal shall be programmable to suit the owner's application.

21. Access Levelsa. There shall be four (4) access levels with level 4 being the highest

level. Level 1 actions shall not require a passcode. Passcodes shall consist of up to ten (10) digits. Changes to passcodes shall only be made by authorized personnel.

16721-13 LK 00000

Page 14: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

b. In order to maintain security when entering a passcode the digits entered will not be displayed but a cursor will move along filling the position with an x to indicate that the digit has been accepted. All key presses will be acknowledged by a local audible sound.

c. When a correct passcode is entered, the message "Access Granted" shall be displayed. The new access level shall be in effect until the operator manually logs out or the keypad has been inactive for ten 10 minutes.

d. Should an invalid code be input, the operator shall be notified with the message, "ERROR. . . INCORRECT PASSCODE", and shall be allowed up to three chances to enter a valid code. After three unsuccessful tries, the message, "ACCESS DENIED", shall be displayed. The level shall not be altered, and the operator shall no longer be in the menu option.

e. Access to a level will only allow the operator to perform all actions within that level plus all actions of lower levels, not higher levels.

f. The following keys/controls shall have access levels associated with them:(1) Alarm silence(2) System reset(3) Set time/date(4) Manual control(5) On/off/auto control(6) Disable/enable(7) Clear

historical alarm log

(8) Clear historical trouble log(9) One person testing(10) Change alarm verification

g. Acknowledge keys shall also require privileged access to acknowledge points. If the operator presses an (ACK) key with insufficient access, an error message will be displayed. The points will scroll with (ACK) key presses to view the points on the list, but the points will not get acknowledged in the database.

h. Fire Alarm Control Unit shall be capable of operating a remote maintenance terminal and/or printers; output shall be ASCII from an EIA RS-232-C connection with an adjustable baud rate.

i. Each RS-232-C port shall be capable of supporting and supervising a remote Printer or a remote maintenance terminal. Each port shall be field configurable for supervised operation (to be used when the remote maintenance terminal or printer is permanently installed as part of the system) or for unsupervised operation (for use with portable remote devices that are temporarily connected for testing reports or diagnostic analysis).

22. SMOKE SENSOR SENSITIVITY ADJUSTMENT:a. SMOKE SENSORS SHALL be smoke density measuring devices

having no self contained alarm set point (fixed threshold). The alarm decision for each sensor shall be determined by the control unit. The control unit shall determine the condition of each sensor

16721-14 LK 00000

Page 15: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

by comparing the sensor value to the stored values.b. AUTHORIZED OPERATION of controls at the FACU shall cause

the selection of specific addressable smoke sensors for adjustment, display of their current status and sensitivity settings, and control of changes in those settings.

c. REMOTE CONTROLLABILITY: Individually monitor sensors at the FACU for calibration, sensitivity, and alarm condition, and individually adjust for sensitivity from the FACU. The alarm decision for each sensor shall be determined by the control unit. The control unit shall determine the condition of each sensor by comparing the sensor value to the stored values.

d. SMOKE SENSOR SENSITIVITY: The sensitivity of each sensor will be as high as it can possibly be for its location without being so sensitive that it will be nuisance alarm-prone. It shall be possible to adjust True Alarm Sensor Sensitivity from .2% to 3.7% per foot obscuration. The ENTIRE sensitivity range shall be U.L. Listed and shall be documented and verified by submission of U.L. Listing cards with the submittal package. The FACU shall be capable of analyzing the environment over a period of time to determine the optimum setting. This shall be done by analyzation of the peak values and the average values stored in the FACU history log. Obscuration values shall be expressed directly in percentage of smoke obscuration on all reports and displays (similar to NFPA and UL).

e. AN OPERATOR at the control unit, having a proper access level, shall have the capability to manually access the following information for each sensor:

- primary status - device type

- present average value * - present sensitivity selected * - peak detection values - sensor range (normal, dirty, etc.)

* Values shall be in "percent of smoke obscuration" format so that no interpretation is required by the operator.

f. THE CONTROL UNIT shall maintain a moving average of the sensors smoke chamber value to automatically compensate (move the threshold) for dust, dirt, and component degradation conditions that could affect detection operations. The control unit shall automatically maintain a constant smoke obscuration sensitivity for each sensor (via the floating threshold) by compensating for environmental factors.

g. IT SHALL BE POSSIBLE to program the control unit to automat-ically change the sensitivity settings of each sensor based on time-of-day and day-of-week (for example, to be more sensitive during unoccupied times and less sensitive during occupied periods).  There shall be a minimum of seven (7) sensitivity settings available for each True Alarm sensor and a minimum of three (3) sensitivity settings available for each "Quick Connect" True Alarm sensor.

h. THE CONTROL UNIT shall have the capability of being program-

16721-15 LK 00000

Page 16: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

med for a pre-alarm or two-stage function.  This function allows an indication to occur when, for example, a 3% sensor reaches a threshold of 1.5% smoke obscuration.

i. THE CONTROL UNIT shall automatically indicate when an individual sensor needs cleaning.

j. WHEN A SENSORS average value reaches a predetermined value, a ADIRTY SENSOR@ trouble condition shall be audibly and visually indicated at the control unit for the individual sensor. Additionally, the LED on the sensor base shall glow steady giving a visible indication at the sensor location.

k. IF A ADIRTY SENSOR@ is left unattended, and its average value increases to a second predetermined value, an AEXCESSIVELY DIRTY SENSOR@ trouble condition shall be indicated at the control unit for the individual sensor.

l. TO PREVENT FALSE alarms, these ADIRTY@ conditions shall in no way decrease the amount of smoke obscuration necessary for system activation.

m. THE CONTROL UNIT shall continuously perform an automatic self-test routine on each sensor which will functionally check sensor electronics and ensure the accuracy of the values being transmitted to the control unit. Any sensor that fails this test shall indicate a ASELF TEST ABNORMAL@ trouble condition.

n. THE FACU SHALL be listed for automatic compliance with NFPA 72 Sensitivity Testing requirement.

o. IF THE PROPOSED system does not have the capabilities defined in [22.] a maintenance and testing service providing the following shall be included with the base bid:(1) Bi-annual sensitivity reading and logging for each smoke

sensor. This is to be accomplished by use of a UL listed calibration device per the requirement of NFPA 72.

(2) Scheduled biannual threshold adjustments to maintain proper sensitivity for each smoke sensor.

(3) Threshold adjustment to any smoke sensor that has alarmed the system without the presence of particles of combustion. This service shall be performed within 4 hours of any such occurrence.

(4) Scheduled biannual cleaning or replacement of each smoke detector or sensor within the system.

(5) If any device alarms the system without the presence of particles of combustion twice within 30 days, it shall be cleaned or replaced.

(6) Semi-annual functional testing of each smoke detector or sensor using the manufacturer=s calibrated test tool. Unmeasured smoke or aerosol injection shall not be permitted.

(7) Written documentation of all testing, cleaning, replacing, threshold adjustment, and sensitivity reading for each smoke detector or sensor device within the system.

(8) The initial service included in the bid price shall provide the above listed procedures for a period of five years after owner acceptance of the system.

16721-16 LK 00000

Page 17: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

p. Smoke Sensor shall have mini horn built in smoke sensor base for each room. Both handicap and non-handicap room sensors when in alarm shall alarm just room in alarm and front desk only. During general alarm all room sensors shall go into alarm.

23. INDIVIDUAL DEVICE NETWORK (IDNET)a. Communication with addressable devices:  The system must

provide communication with all initiating and control devices individually.  All of these devices are to be individually annunciated at the control unit.  Annunciation shall include the following conditions for each point:a.  Alarmb.  Troublec.  Opend.  Shorte.  Groundf.  Device Fail/or Incorrect Device

b. The system shall support 100% of addressable devices in alarm or operated at the same time, under both primary (AC) and secondary (battery) power conditions. Systems which cannot support 100% of their points in alarm simultaneously cannot assure appropriate system response and are not acceptable.

c. All addressable devices are to have the capability of being disabled or enabled individually.

d. Up to 250 addressable devices may be multi - dropped from a single pair of wires. Systems that require factory reprogramming to add or delete devices are unacceptable. Systems which require a special tool and/or programming unit shall provide the special tool and/or programming unit to the owner upon project completion and provide a minimum of (8) hours training to the owners representative.

e. Format -The communication format must be a poll/response protocol to allow t-tapping of the wire to addressable devices and be completely digital.  A high degree of communication reliability must be obtained by using parity data bit error checking routines for address codes and check sum routines for the data transmission protocol. Systems that do not utilize full digital transmission protocol (i.e. - that may use time pulse width methods to transmit data, etc.) will not be acceptable since they are considered unreliable and prone to errors.

f. Identification of Addressable Devices -Each addressable device must be uniquely identified by an address code entered on each device at time of installation. The use of jumpers to set address will not be acceptable due to the potential of vibration and poor contact.

g. Wiring Type, Distance, Survivability and Configuration - Wiring types will be approved by the equipment manufacturer. The system must allow up to 2,500 feet wire length to the furthest addressable device. T-tapping of the communications channel will be supported except where Class A wiring is required.

16721-17 LK 00000

Page 18: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

C. FIRE ALARM CONTROL UNIT1. Where shown on the plans, provide and install a Simplex Type 4010 Fire

Alarm Control Unit. Construction shall be modular with solid state, microprocessor based electronics. An 80 character LCD display shall indicate alarms, supervisory service conditions and any troubles. It shall display only those primary controls and displays essential to operation during a fire alarm condition.  Although the keypad/keyboard can be used for control (fire fighter/emergency) of the entire system, it shall only be used for maintenance purposes.  Keyboards or keypads shall not be visible or required to operate the system during fire alarm conditions.

2. A local audible device shall sound during Alarm, Trouble or Supervisory conditions. This audible device distinguish one condition from another without having to view the panel. This audible device shall also sound differently during each key press to provide an audible feedback (chirp) to ensure that the key has been pressed properly.

3. Primary Keys & Panel Display -The Control Unit's display shall be backlit for enhanced readability. So as to conserve battery standby power, it shall not be lit during an AC power failure unless an alarm condition occurs or there should be keypad activity. The display shall support both upper and lower case letters. Lower case letters shall be used for soft key titles and prompting the user.  Upper case letters shall be used for System Status Information.  A cursor shall be visible when entering information.

4. Equipment Enclosures - Provide cabinet(s) of sufficient size to accommodate the aforementioned equipment.  The cabinet(s) shall be equipped with locks and transparent door panel(s) providing freedom from tampering yet allowing full view of the various lights and controls.

5. The system shall be provided with a 4009-9001 signal circuit expander (if required) to provide 4 additional Style Z signal circuits with 8 amp power supply and charger for 10 ah battery set.

2.2 FIRE ALARM PERIPHERAL EQUIPMENT

A. ADDRESSABLE MANUAL FIRE ALARM STATIONS: Manual fire alarm stations, Type 4099-9001 single action, plainly marked to "Pull Lever" to sound alarm, located as shown on the plans at a height of 48" from finished floor; circuit shall be 4-wire addressable loop supervision. Provide 2975-9178 backbox for surface mount or mount on a 4" square box with single gang trim ring for semiflush mount. When Manual Stations are to be mounted on the exterior of the building, provide each unit with (1) 2099-9817 Weatherproof, Clear, "Lift to Activate" Cover and (1) 2099-9818 Surface Weatherproof Adapter Kit.

B. True Alarm Quick Connect Sensors shall be 4098-9710 and shall not require a base. True Alarm Standard Sensors and Addressable Sensor Bases shall be Simplex Type 4098-9714 Sensor with a 4098-9792 Base. For locations requiring a relay base it shall be a 4098-9791 Base with a supervised relay driver output and a 2098-9737. For locations requiring a sounder in the base it shall be a 4098-9791 Base with a supervised relay driver output and a 2098-9737. The addressable smoke sensors shall be of the photoelectric type and shall communicate actual smoke chamber values to the system control unit. The

16721-18 LK 00000

Page 19: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

sensors shall be listed to UL Standard 268 and shall be documented as compatible with the control equipment to which they are connected. The sensors shall be listed for both ceiling and wall mount applications. Each sensor and/or base shall contain a LED that will flash each time it is scanned by the control unit (once every 4 seconds). When the control unit determines that a sensor is in the alarm or a trouble condition, the control unit shall command the LED on that sensor's base to turn on steady indicating the abnormal condition. Sensors which do not provide a visible indication of an abnormal condition at the sensor location shall not be acceptable. Each sensor shall contain a magnetically actuated test switch to provide for easy alarm testing at the sensor location. Each sensor shall be scanned by the control panel for its type identification to prevent inadvertent substitution of another sensor type. The control unit shall operate with the installed device but shall initiate a "Wrong Device" trouble condition until the proper type is installed or the programmed sensor type is changed. The sensor's electronics shall be immune from false alarms caused by EMI and RFI. All Sensor Bases shall mount on a 4" Octagon 2 1/8" deep box. Relay Bases shall require a 4" Octagon 2 1/8" deep box with a 1 1/2" deep extension ring.

C. Addressable Heat Sensors for rooms as indicated on the plans shall be 4098-9733 True Alarm Heat Sensor. True Alarm Heat Sensors shall be self restoring for both rate of rise and fixed temperature set points and rate of rise shall be selectable at 15 degree or 20 degree per minute. Fixed temperature set point shall be 135 degrees for alarm. True Alarm Heat Sensors shall be capable of being programmed as a utility device to monitor for temperature extremes in the range from 32 degrees F to 158 degrees F (0 to 70 degrees C). Heat Sensors shall utilize the same Bases as other True Alarm Sensors. All Sensor Bases shall mount on a 4" Octagon 2 1/8" deep box. Relay Bases shall require a 4" Octagon 2 1/8" deep box with a 1 1/2" deep extension ring.

D. True Alarm Duct Sensors shall be Simplex Type 4098-9714 sensor with a 4098-9751 In-Duct Duct Sensor Housing with Relay Output or 4098-9750 In-Duct Duct Sensor Housing without Relay Output. Shall be of tubeless design for square ducts 8" to 36" wide or round ducts 6" or 8" diameter. In the case of round ducts larger than 8" or square ducts wider than 36", a 4098-9714 with a 4098-9753 Housing with Relay Output or 4098-9752 Housing without Relay Output and Sampling Tubes designed to detect the presence of smoke within the A.H.U. duct work, installed where indicated on the electrical drawings. Sensors shall operate as described under True Alarm Sensors above. Sensors shall be equipped with a functional test device circuit capable of simulating a maximum acceptable amount of smoke for alarm. The test device circuit shall provide individual local tests of all components of the smoke detector and shall not require generation of actual smoke within the A.H.U. Provide Two (2) sampling tubes for the 4098-9752 or 40 98-9753 of the proper length to accommodate accurate sampling of air within the duct work for each detector location. Intake sampling tube shall penetrate the duct a minimum 75% of its diameter. Provide each duct sensor with a 2098-9806 Remote Alarm Indicator/Test Switch, mount on outlet box within easy reach, near the duct detector.

E. Zone Adapter Module - Zone Adapter Modules shall be used for monitoring of waterflow, valve tamper, non-addressable detectors, and for control of evacuation indicating appliances and AHU systems.

16721-19 LK 00000

Page 20: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

1. An addressable interface module shall be provided for interfacing normally open direct contact devices to an addressable signaling line circuit. The device shall be a Simplex Type Zone Adapter Module (ZAM).

2. ZAM's shall be capable of mounting in a standard 4" square, 2 1/8" deep electric box. Electrical Contractor shall furnish boxes and 2 gang cover plates to allow surface or flush mounting. Zam's shall receive their 24VDC power from a separate two wire pair running from an appropriate power supply.

3. There shall be three types of devices:Type 1: 4090-9101 Class B & 4090-9106 Class A Monitor ZAMType 2: 4090-9002 Relay IAMType 3: 4090-9001 Monitor IAM

4. For Type 1 and/or Type 3 above:a. For conventional 2-wire smoke detector and/or contact device

monitoring with Style D (NFPA-72 initiating device circuit) wiring supervision.

b. Type 1 only: This type of addressable device module shall provide power to, and monitor the status of a zone consisting of conventional 2-wire smoke detectors and/or N/O contact devices as specified elsewhere and identified on the plans. The supervision of the initiating device circuit wiring shall be Style D. These ZAM's shall communicate the zone's status (normal, alarm, trouble) to the control unit. This device does require separate 24VDC power. It does require the addressable IDNET circuit. This device can power 2-wire smoke detectors.

c. Type 3 only: This type of addressable device IAM (Individually Addressable Module) shall monitor the status of a zone consisting of conventional N/O contact devices as specified elsewhere and identified on the plans.  The supervision of the initiating device circuit wiring shall be Style D. These ZAM's shall communicate the zone's status (normal, alarm, trouble) to the control unit. This device does not require separate 24VDC power. It does require the addressable IDNET circuit. This device cannot power 2-wire smoke detectors.

5. For Type 2 above:a. For non-supervised control.

This type of addressable device IAM (Individually Addressable Module) shall provide single pole, double throw relay switching for loads up to 120VAC. Power Limited Rating: 2A @ 24VDC, 1A @ 24VDC Inductive. Non-Power Rating: 1/2A @ 120VAC. This device does not require separate 24VDC power. It does require the addressable IDNET circuit.

6. The ZAM shall be supervised and uniquely identified by the control unit.  Device identification shall be transmitted to the control unit for processing according to the program instructions.  Should the ZAM become non-operational, tampered with, or removed, a discrete trouble signal, unique to the device, shall be transmitted to, and annunciated at, the control unit.

7. The ZAM shall be capable of being programmed for its "address" location on the addressable device signaling ling circuit. The ZAM shall be compatible with addressable manual stations and addressable detectors

16721-20 LK 00000

Page 21: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

on the same addressable circuit.8. All devices shall be supervised for trouble conditions. The system control

unit shall be capable of indicating the type of trouble condition (open, short, device missing/failed). Should a device fail, it shall not hinder the operation of other system devices. Should a problem occur on a particular wire run, it should not affect other wire runs.

F. RESIDENTIAL SMOKE DETECTORS FOR HANDICAPPED GUEST rooms shall be Simplex 4098-9714 Photoelectric type. Detectors shall be 24VAC operation and shall be UL Listed to UL Standard 217 and 1971. Detectors shall incorporate a built in piezo horn rated at 90db @ 10 feet, red LED alarm/power on indicator, test button and 177 candela ADA strobe light for hearing impaired individuals.

G. RESIDENTIAL SMOKE DETECTORS FOR NON-HANDICAPPED GUEST rooms shall be Simplex 4098-9714 (with built in piezo horn) Photoelectric type. Detectors shall be 24VAC operation and shall be UL Listed to UL Standard 217. Detectors shall incorporate a built in piezo horn rated at 90db @ 10 feet, red LED alarm/power on indicator, test button and temper proof locking base. Detector shall contain no radioactive material.

H. AIR HANDLING UNIT SHUTDOWN RELAYS shall be Type 2088-9010 series fan shutdown relay, 24VDC operation, mounted in surface cabinet with LED indicator indicating when relay is energized. These relays shall be controlled and powered from the 4010 control unit. Contacts shall be 2P D.T. rated at 10 amps resistive 28 VDC/120VAC.

I. SPRINKLER WATERFLOW AND VALVE TAMPER SWITCHES: Waterflow Switch shall be Type 2097 waterflow switch, with two normally open alarm contacts and tamper switch and equipped with adjustable retard feature. Provide proper unit to fit water pipe size required. This device shall be installed by the sprinkler contractor and wired by the electrical contractor. Gate Valve Switch shall be Type 2097 gate valve switch with two normally closed trouble contacts, to be mounted on gate valves as directed. This device shall be installed by the sprinkler contractor and wired by the electrical contractor.

J. INTERIOR AUDIO/VISUAL fire alarm signal device shall be Model 4903-9236 Red Horizontal Wall Mount w/ UL 1971/ADA Strobe unit and horn, 24VDC, 0.138 amp with diodes for electrical supervision of wiring and 24VDC, 15 candela, xenon flasher, mounted on a 4" square flush mounted box. Selected locations as shown on the plans shall utilize Model 4903-9238 UL 1971/ADA Strobe unit and horn, 24VDC, 0.238 amp with diodes for electrical supervision of wiring and 24VDC, 110 candela, xenon flasher, mounted on a 4" square flush mounted box. Surface mounted units shall use a 2975-9145 back box with a 4905-9903 adapter plate.

K. INTERIOR VISUAL ONLY fire alarm signal device shall be Model 4904-9137 Red Vertical Wall Mount w/ UL 1971/ADA Strobe unit, 24VDC, 0.100 amp with diodes for electrical supervision of wiring and 24VDC, 15 candela, xenon flasher, mounted on a 1-gang flush mounted box. Selected locations as shown on the plans shall utilize Model 4904-9136 UL 1971/ADA Strobe unit, 24VDC, 0.200 amp with diodes for electrical supervision of wiring and 24VDC, 110 candela,

16721-21 LK 00000

Page 22: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

xenon flasher, mounted on a 1-gang flush mounted box. Surface mounted units shall use a single gang Wiremold box #5744S or equal. Exterior areas shall use a 4905-9907 High Humidity Gasket Kit and a 4905-9910 Surface Adapter Plate mounted on a weatherproof box (RACO #5324 single gang or equal).

L. INTERIOR SYNCHRONIZED STROBE AUDIO/VISUAL fire alarm signal device shall be Model 4903-9422 Red Horizontal Wall Mount w/ UL 1971/ADA Strobe unit and horn, 24VDC, 0.138 amp with diodes for electrical supervision of wiring and 24VDC, 15 candela, xenon flasher, mounted on a 4" square flush mounted box. Selected locations as shown on the plans shall utilize Model 4903-9424 UL 1971/ADA Strobe unit and horn, 24VDC, 0.238 amp with diodes for electrical supervision of wiring and 24VDC, 110 candela, xenon flasher, mounted on a 4" square flush mounted box. Surface mounted units shall use a 2975-9145 back box with a 4905-9903 adapter plate.

M. INTERIOR SYNCHRONIZED VISUAL ONLY fire alarm signal device shall be Model 4904-9305 Red Vertical Wall Mount w/ UL 1971/ADA Strobe unit, 24VDC, 0.100 amp with diodes for electrical supervision of wiring and 24VDC, 15 candela, xenon flasher, mounted on a 1-gang flush mounted box. Selected locations as shown on the plans shall utilize Model 4904-9309 UL 1971/ADA Strobe unit, 24VDC, 0.200 amp with diodes for electrical supervision of wiring and 24VDC, 110 candela, xenon flasher, mounted on a 1-gang flush mounted box. Surface mounted units shall use a single gang Wiremold box #5744S or equal. Exterior areas shall use a 4905-9907 High Humidity Gasket Kit and a 4905-9910 Surface Adapter Plate mounted on a weatherproof box (RACO #5324 single gang or equal).

N. STROBES REQUIRING SYNCHRONIZATION shall be connected to an Indicating Appliance Circuit (horn circuit) which has a 4905-9914 Synchronized Flash Module inserted on it. Synchronized Flash Module shall be installed in a 4" square deep box. It shall be possible to connect Synchronized and Non-Synchronized Strobes on the same circuit so as not to waste horn circuit capacity.

O. INTERIOR ADA MINIHORN/STROBE fire alarm signal device shall be Model GX90S-4-110-1WR Red Wall Mount UL 1971/ADA Strobe unit and piezo mini horn. This unit shall be 24VDC, 0.250 amp with diodes for electrical supervision of wiring with a 24VDC, 110 candela, 1Hz, xenon flasher with a polar distribution of the light and 90 db @ 10 feet mini horn both mounted on a single gang flush mounted box. Sleeping room mounting shall be within 16 feet of the pillow measured horizontally and mounting height to the top of the lens shall be greater than or equal to 24" from the finished ceiling.

P. INTERIOR MINIHORN ONLY fire alarm signal device shall be Model 2901-9836 Red Wall Mount, 24VDC, 0.015 amp with diodes for electrical supervision of wiring, 90 db @ 10 feet, mounted on a single gang flush mounted box. Surface mounted units shall use a single gang Wiremold box #5744S or equal. These units shall have their tops at heights above the finished floors of not less than 90' and below the finished ceiling of not less than 6".

Q. EXTERIOR AUDIO ALARM device shall be Model 4901-9805H vibrating type horn, with a 4905-9909 Adapter Plate and a 4905-9907 Gasket Kit, mounted on a

16721-22 LK 00000

Page 23: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

weatherproof 2-gang surface box (RACO #5333) provided by Contractor.

R. EXTERIOR STROBE ONLY fire alarm signal device shall be Model 4904-9136 Red Vertical Wall Mount w/ UL 1971/ADA Strobe unit, 24VDC, 0.200 amp with diodes for electrical supervision of wiring and 24VDC, 110 candela, xenon flasher. Exterior areas shall use a 4905-9907 High Humidity Gasket Kit and a 4905-9910 Surface Adapter Plate mounted on a weatherproof box (RACO #5324 single gang or equal).

S. EXTERIOR SPRINKLER BELL shall be Model 2901-9333 vibrating type 10" bell with a 2975-9009 weatherproof gasketed surface box.

T. OFF-SITE DIGITAL COMMUNICATOR: Connection from the Main FACU to the Local Fire Department or an approved central station (as required by Local Codes). U.L. Listed Dual Line Communicator shall be Simplex Type 4010-9810 Common Event Reporting or 4010-9816 Point Reporting Fire Communicator included in FACU cabinet, (2) 2080-9022 Connector Cords. Communicator type shall be as required by the local AHJ and shall be U.L. Listed to U.L. 864 conforming to the requirements of NFPA 72. Communicator shall transmit all alarms and be capable of supervising two telephone lines, if one line fails for more than 45 seconds a built in trouble alert shall be activated and a trouble signal automatically transmitted to the central station on the remaining line. The Communicator shall also send a test signal to the central station every 24 hours at a programmed time of day or night. Communicator shall be capable of remote off site programming to provide more economical changes to the owner. Communicator shall be monitored by a U.L. Listed Monitoring Company. First year Annual Monitoring fee shall be included (if applicable). Telephone Company charges are the owners responsi bility and are not to be included in the bid . Communicator shall be installed and wired by the Electrical Contractor. Provide the required device for city connection, verify with AHJ prior to purchase.

U. MASTER BOX, (if required by AHJ in lieu of digital communicator) shall be one of the following to match the existing Master Box system:1. 2095-9000 Shunt Trip, Surface Mount2. 2095-9001 Local Energy Trip, Surface Mount3. 2095-9011 Local Energy Trip, Flush Mount, ExteriorIf required provide the following options:1. 2095-9010 Fire Box Pendant Lamp2. 2095-9022 Cottage Shell Pedestal3. 2975-9174 Backbox for 2095-9011Always provide a 2095-9041 Three Element Gas Tube Arrestor

V. FIRE ALARM ANNUNCIATOR where shown on the plans, provide and install a Simplex Alpha/Numeric Fire Alarm Annunciator, Simplex Type 4606-9101, with a two line by 40 character (80 character total) LCD display. Annunciator shall Display all Alpha/Numeric messages as displayed at the FACU, Annunciator shall also contain an alarm, trouble and supervisory service LED and acknowledgment switches, system reset and alarm silence switch, display time key, (3) programmable indicating LED's, alarmed silence LED and a key switch to activate or deactivate all other switches. Annunciator shall mount on a six gang box and be connected to the FACU with one BSCC #S1802SLC10 (.210"

16721-23 LK 00000

Page 24: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

OD) twisted shielded pair of 18's and two #14 power wires. Capabilities shall exist for a maximum of (6) 4606-9101's per 4010 FACU.

16721-24 LK 00000

Page 25: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

PART 3 - EXECUTION

3.1 FIRE ALARM INSTALLATION AND WIRING

A. FURNISH AND INSTALL wiring, conduit, junction boxes and outlet boxes required for the installation of a complete system. Wiring shall be installed in power limited, U.L. Listed Fire Alarm Cable in conduit. All wiring shall be #14 gauge solid copper, with the exception of the IDNET addressable cable which shall be equal to BSCC #S1802SLC10 (.210" OD) and ADA Audio/Visual signals shall be wired with BSCC #S1402S10 (.211" OD). Shall be color coded throughout and shall test free and clear of opens, grounds and shorts between conductors. Equipment shall be grounded with an approved earth ground wire being supplied at the control unit. Wiring shall be in conformance with Article 760 of the National Electric Code. Verify all wiring with system manufacturer prior to installation.

B. DEVICE INSTALLATION1. Smoke Detectors: Install ceiling-mounted detectors not less than 4 inches

from a sidewall to the near edge. Install detectors located on the wall at least 4 inches but not more than 12 inches below the ceiling. For exposed solid joist construction, mount detectors on the bottoms of the joists. On smooth ceilings, install detectors not over 30 feet apart in any direction. Install detectors no closer than 5 feet from air registers.

2. Audible Notification Appliances: Install not less than 80 inches above the finished floor nor less than 6 inches below the ceiling. Install bells and horns on flush-mounted back boxes with the device-operating mechanism concealed behind a grille or as indicated. Combine audible and visual notification appliances at the same location into a single unit.

3. Visual Notification Appliances: Install adjacent to each alarm bell or alarm horn and not less than 80 inches above the finished floor and at least 6 inches below the ceiling.

4. Device Location-Indicating Lights: Locate in the public space immediately adjacent to the device they monitor.

5. Fire Alarm Control Unit (FACU): Surface mount with tops of cabinets not more than 6 feet above the finished floor.

6. Annunciator: Arrange as indicated, with the top of the Unit no more than 6 feet above the finished floor.

C. INSTALLATION OF equipment and devices that pertain to other work in the contract shall be closely coordinated with the appropriate subcontractors.

D. CONTRACTOR SHALL NOT remove protective covers from smoke or heat sensors until all construction work and cleanup has been performed. If this is not adhered to all cleaning costs to clean dirty smoke detectors shall be paid for by the contractor.

E. CONTRACTOR WIRING INSTALLATION1. Wiring Method: Install wiring in metal raceway according to Division 16

Section "Raceways. " Conceal raceway except in unfinished spaces and as indicated.

2. Wiring Within Enclosures: Install conductors parallel with or at right

16721-25 LK 00000

Page 26: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

angles to the sides and back of the enclosure. Bundle, lace, and train the conductors to terminal points with no excess. Connect conductors that are terminated, spliced, or interrupted in any enclosure associated with the fire alarm system to terminal blocks. Mark each terminal according to the wiring diagrams of the system. Make all connections with approved crimp-on terminal spade lugs, pressure-type terminal blocks, or plug connectors.

3. Cable Taps: Use numbered terminal strips in junction, pull or outlet boxes, cabinets, or equipment enclosures where any circuit tap is made.

4. System Wiring: Wire and cable shall be a type listed for its intended use by an approval agency acceptable to the Authority Having Jurisdiction (AHJ) and shall be installed in accordance with the appropriate articles from the current approved edition of the National Electric Code (NEC)(NFPA 70). It is the Contractor=s responsibility to obtain from the Fire Alarm System Manufacturer written instruction regarding the appropriate wire/cable to be used for this installation. No deviation from the written instruction shall be made by the Contractor without the prior written approval of the Fire Alarm System Manufacturer.

5. Color Coding: Color-code fire alarm conductors differently from the normal building power wiring. Use one color code for alarm initiating device circuits wiring and a different color code for supervisory circuits. Color-code notification appliance circuits differently from alarm-initiating circuits. Paint fire alarm system junction boxes and covers red.

6. Risers: Install at least 2 vertical cable risers to serve the fire alarm system. Separate risers in close proximity to each other with a minimum one-hour-rated wall, so the loss of one riser does not prevent the receipt or transmission of signal from other floors or zones.

7. Wiring to Central Station Transmitter: 1-inch conduit between the FACU and the central station transmitter connection as indicated. Install number of conductors and electrical supervision for connecting wiring as required to suit central-station monitoring function.

F. GROUNDING: Ground equipment and conductor and cable shields as specified by the equipment manufacturer. For audio circuits, minimize to the greatest extent possible ground loops, common mode returns, noise pickup, cross talk, and other impairments. Provide 5-ohm ground at main equipment location. Measure, record, and report ground resistance.

G. FIELD QUALITY CONTROL: 1. Manufacturer's Field Services: Provide services of a factory-authorized

service representative to supervise the field assembly and connection of components and the pretesting, testing, and adjustment of the system.

2. Pretesting: Upon completing installation of the system, align, adjust, and balance the system and perform complete pretesting. Determine, through pretesting, the conformance of the system to the requirements of the Drawings and Specifications. Correct deficiencies observed in pretesting. Replace malfunctioning or damaged items with new and retest until satisfactory performance and conditions are achieved. Prepare forms for systematic recording of acceptance test results.

3. Report of Pretesting: After pretesting is complete, provide a letter certifying the installation is complete and fully operable, including the

16721-26 LK 00000

Page 27: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

names and titles of the witnesses to the preliminary tests. 4. Final Test Notice: Provide a 10-day minimum notice in writing when the

system is ready for final acceptance testing. 5. Minimum System Tests: Test the system according to the procedures

outlined in NFPA 72. Minimum required tests are as follows:a. Contractor shall verify the absence of unwanted voltages between

circuit conductors and ground. b. Contractor shall Megger test all conductors other than those

intentionally and permanently grounded with electronic components disconnected (prior to connecting equipment). Test for resistance to ground. Report readings less than 1 megohm for evaluation.

c. Contractor shall test all conductors for short circuits utilizing an insulation-testing device.

d. With each circuit pair, short circuit at the far end of the circuit and measure the circuit resistance with an ohmmeter. Record the circuit resistance of each circuit on the record drawings.

e. Verify the control unit is in the normal condition as detailed in the manufacturer's operating and maintenance manual.

f. Test initiating, notification, and signaling circuits for proper signal transmission under open circuit conditions. One connection each should be opened at not less than 10 percent of the initiating and notification devices. Observe proper signal transmission according to class of wiring used.

g. Test each initiating device and notification appliance for alarm operation and proper response at the control unit. Test smoke detectors with actual products of combustion.

h. Measure and record the actual current draw of each Notification Appliance Circuit.

i. Test the system for all specified functions according to the manufacturer's operating and maintenance manual. Systematically initiate specified functional performance items at each station including making all possible alarm and monitoring initiations and using all communications options. For each item, observe related performance at all devices required to be affected by the item under all system sequences. Observe indicating lights, displays, signal tones, and annunciator indications.

j. Test both primary power and secondary power. Verify, by test, the secondary power system is capable of operating the system for the period and in the manner specified.

k. Retesting: Correct deficiencies indicated by tests and completely retest work affected by such deficiencies. Verify by the system test that the total system meets the Specifications and complies with applicable standards.

l. Report of Tests and Inspections: Provide a written record of inspections, tests, and detailed test results in the form of a test log. Submit log upon the satisfactory completion of tests.

m. Tag all equipment, stations, and other components at which tests have been satisfactorily completed.

n. In order to obtain a certificate of occupancy. Demonstrate that the system meets the Specifications and complies with applicable

16721-27 LK 00000

Page 28: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

standards. This final test shall be witnessed by a representative of the Authority Having Jurisdiction and a factory-authorized service representative.

H. CLEANING AND ADJUSTING1. Cleaning: Remove paint splatters and other spots, dirt, and debris. Touch

up scratches and mars of finish to match original finish. Clean unit internally using methods and materials recommended by manufacturer.

2. Occupancy Adjustments: When requested within one year of date of Substantial Completion, provide on-site assistance in adjusting sound levels and adjusting controls and sensitivities to suit actual occupied conditions. Provide at least one visit to the site for this purpose.

3.2 SERVICE AND TESTING

A. MANUFACTURER: Provide supervision of the project during installation, supervision of final connections and testing of all devices, demonstrate system operation following checkout in the presence of the Architect, Engineer and Owner, and shall after completion of the project and acceptance, provide service incidental to the proper performance of the system during the guarantee period. After the guarantee period, the manufacturer shall provide upon request and at standard rates, the service necessary for the future proper performance of this system. To provide this service, the manufacturer shall have an intrastate service organization consisting of at least five direct full time factory trained employees under the supervision of a qualified service manager. Service availability shall be local. The prime function of this organization shall be prompt efficient service. Upon project completion, the equipment supplier shall present a full coverage preventative maintenance agreement to the Owner for his purchase approval covering all service and instructions to the customer, with a minimum of two inspections per year with no additional charge for emergency calls between inspections during normal working hours.

B. TRAINING: Provide the services of a factory-authorized service representative to demonstrate the system and train Owner's maintenance personnel as specified below. Train Owner's maintenance personnel in the procedures and schedules involved in operating, troubleshooting, servicing, and preventive maintaining of the system. Provide a minimum of [4] hours' training. Schedule training with the Owner at least seven days in advance.

3.3 GUARANTEE

A. AFTER COMPLETION: Guarantee work to be free from defects for a period of one year. Such defects shall apply to faulty materials or workmanship. In the event of the development of defects, remedy the failures without additional expense to Owner, within a reasonable time after notice. System equipment shall be guaranteed by the manufacturer for one year.

3.4 MAINTENANCE SERVICE

A. Maintenance Service Contract: Provide a maintenance contract to owner (for his purchase approval) at the start of the warranty period. THIS CONTRACT SHALL

16721-28 LK 00000

Page 29: Christenson Corporation€¦  · Web viewClosing fire and smoke doors normally held open by magnetic door holders. ... minute after resetting, a second alarm is reported to the FACU

NOT BE INCLUDED IN THE BID. This contract shall cover the fire alarm systems and equipment for a period of 12 months commencing with Substantial Completion, using factory-authorized service representatives:

1. Basic Services: Systematic, routine maintenance visits on a [quarterly] basis at times coordinated with the Owner. In addition, respond to service calls within 24 hours of notification of system trouble. Adjust and replace defective parts and components with original manufacturer's replacement parts, components, and supplies.

2. Additional Services: Perform services within the above 12-month period not classified as routine maintenance or as warranty work as described in Division 1 Section "Warranties and Bonds" when authorized in writing. Compensation for additional services must be agreed upon in writing prior to performing services.

3. Renewal of Maintenance Service Contract: No later than 60 days prior to the expiration of the maintenance services contract, deliver to the Owner a proposal to provide contract maintenance and repair services for an additional one-year term. Owner will be under no obligation to accept maintenance service contract renewal proposal.

3.5 EXTRA MATERIALS

A. General: Furnish extra materials, matching products installed (as described below), packaging with protective covering for storage, and identifying with labels clearly describing contents.

1. Glass Rods for Manual Stations: Furnish quantity equal to 15 percent of the number of manual stations installed; minimum of 6 rods.

2. Lamps for Remote Indicating Lamp Panels: Furnish quantity equal to 10

percent of the number of units installed, but not less than one. 3. Lamps for Strobe Units: Furnish quantity equal to 10

percent of the number of units installed, but not less than one. 4. Smoke Detectors, Fire Detectors, and Flame Detectors:

Furnish quantity equal to 10 percent of the number of units of each type installed but not less than one of each type.

5. Detector Bases: Furnish quantity equal to 2 percent of the number of units of each type installed but not less than one of each type.

END OF SECTION

16721-29 LK 00000