citylink manual revd

153
Section I : Eqp. Description Section II : Installation Section III : Commissioning Section IV : Configuration Section V : Trouble Shooting Section VI : Appendices User Manual B1089 Rev. D © Nera ASA

Upload: vassiliy-pevnev

Post on 29-Oct-2014

129 views

Category:

Documents


9 download

TRANSCRIPT

Page 1: Citylink Manual RevD

Section I : Eqp. Description

Section II : Installation

Section III : Commissioning

Section IV : Configuration

Section V : Trouble Shooting

Section VI : Appendices

User Manual

B1089 Rev. D

© Nera ASA

Page 2: Citylink Manual RevD

2 B1089 Rev. D

This page is intentionally left blank.

Page 3: Citylink Manual RevD

B1088 Rev. D 3

List of Revisions

Rev. Date What is changed

B 98-12-21 Section II: Changed Figure II-7, New Figure II-8Section V: New menu on IDU display + minor correctionsin Chapter 2.0.Section VI: Changed signal description intables IV-1, -3 & -7.Appendix IV: Added info about limitations compared toTechnical Specification L29059 Rev. D.

C 99-03-25 Grounding cable for Branching Unit described inSection II and Appendix II.Revisions and complementory text in Sections III, IV andV (NEW Configurator related.)Appendix III; updated Alarm-list.Changes in App.IV (Tech. Spec. and amendments)

D 99-06-26 Section I & III updatedNew: Hot Standby intoduced. (Sections I-IV and VI)New: Bracket for Wall/ Roof mounting of ODU/Antenna(Section II Chapter 3.1.8)Appendix IV; Tech Spec. removed, Requirementsconcerning rev. of units used in HSB config. introduced

Page 4: Citylink Manual RevD

4 B1089 Rev. D

This page is intentionally left blank.

Page 5: Citylink Manual RevD

B1088 Rev. D 5

WARNING!

r DO NOT remove or insert theTransmitter Unit with DC power on.

r Power to the OutDoor Unit (ODU) is carried onthe coaxial cable between the InDoor Unit(IDU) and the ODU. Before connecting orremoving the cable, ensure that the primarypower to the IDU has been switched off.

WARNING!

This equipment contains components which aresensitive to "ESD" (Electro Static Discharge).

It is therefore essential that whenever disassem-bling the equipment and/or handling PCboards, special precautions to avoid ESD haveto be made.

These precautions include personnel ground-ing, grounding of work bench, grounding oftools and instruments as well as transport andstorage in special antistatic bags and boxes.

C L A S S 1 L A S E R P R O D U C T

IEC82 5-2: 1993

CAUTION!

The Optical Interface must only be serviced byqualified personnel, who are aware of thehazards involved to repair Laser products.

When handling Laser products the followingprecautions must be taken:

r Never look directly into an open connectoror optical cable

r Before disconnecting an optical cable, thepower should be switched off. If this is notpossible, the cable must be disconnectedfrom the STM-1 output before it is discon-nected from the STM-1 input.

r When the cable is reconnected it must beconnected to the STM-1 input before it isconnected to the STM-1 output.

CAUTION!Exposure to strong high frequency electromag-netic fields may cause thermal damage topersonnel . The eye (Cornea and lens) is easilyexposed.

Any unnecessary exposure is undesirable andshould be avoided.

In Radio-Relay communication installations,orderly setup for normal operation, the generalRF radiation level will be well below the safetylimit.

In the antennas and directly in front of them theRF intensity normally will exceed the dangerlevel, within limited portions of space.

Dangerous radiation may be found in theneighbourhood of open waveguide flanges orhorns where the power is radiated into space.

To avoid dangerous radiation the followingprecautions must be taken:

r During work within and close to the frontof the antenna; make sure that transmitterswill remain turned off.

r Before opening coaxial - or waveguideconnectors carrying RF power, turn offtransmitters.

r Consider any incidentally open RFconnector as carrying power, untilotherwise proved. Do not look into coaxialconnectors at closer than reading distance(30 cm). Do not look into an open wave-guide unless you are absolutely sure thatthe power is turned off.

Use of controls or adjustments or perform-ance of procedures other than those specifiedherein may result in hazardous radiationexposure .

Page 6: Citylink Manual RevD

6 B1089 Rev. D

This page is intentionally left blank.

Page 7: Citylink Manual RevD

B1088 Rev. D 7

Table of Contents

SECTION I Equipment Description .................. 13

1.0 Introduction ................................................................. 14

2.0 IDU Description ........................................................... 15

3.0 ODU Description ......................................................... 17

4.0 Management ................................................................ 19

5.0 Hot Standby ................................................................. 19

SECTION II Installation ...................................... 21

1.0 General ........................................................................ 221.1 Packing ................................................................ 221.2 Marking................................................................. 221.3 Transportation ...................................................... 221.4 Radio Equipment Inventory Check ....................... 231.5 Preparation for Installation .................................... 231.6 Handling & Storing ............................................... 23

2.0 Installation Equipment required................................ 242.1 Tools .................................................................... 242.1.1 Tools for Antenna Installation ............................... 242.1.2 Tools for IDU- ODU Cable /Connector Mounting . 242.2 Equipment external to the Radio Equipment ........ 25

3.0 ODU / Antenna Installation ......................................... 263.1 Installation of 0.6m and 0.45m Antenna .............. 263.1.1 Attachment of Plate and Turnbuckle .................... 263.1.2 Mounting Lower Clamp ........................................ 273.1.3 Assembly of Branching Support Bracket ............. 27

Page 8: Citylink Manual RevD

8 B1089 Rev. D

3.1.4 Installation of Branching Unit,Sun-shield and Flexible Waveguide ..................... 28

3.1.5 Assembly of Upper Column Interface .................. 293.1.6 Assembly of Lower Column Clamp and Threaded Rod.

Attachment of Reflector to Column. ..................... 293.1.7 Installation of Transceiver ................................... 303.1.8 Installing the ODU/Antenna on a Wall or a Roof .. 313.2 Installation of 1.2m Antenna ................................ 333.2.1 Assembly of Branching Support Bracket ............. 333.2.3 Installation of Branching Unit,

Sun-shield and Flexible Waveguide ..................... 34

4.0 IDU Installation ............................................................ 354.1. Mounting the IDU in a 19” Rack ............................ 354.2 Mounting the IDU in an ETSI Rack ....................... 354.3 Mounting the IDU for Freestanding ....................... 364.4 Mounting the IDU on a Wall .................................. 374.5 Cable Installation .................................................. 38

5.0 Installation of Hot Standby Equipment ..................... 395.1 Installation of ODU / Antenna ............................... 395.1.1 0.45m and 0.6m Antenna ..................................... 395.1.2 1.2m Antenna ....................................................... 425.2 Hot Standby IDU Installation ................................. 445.2.1 Mounting the Hot Standby IDUs in a 19” Rack ..... 445.2.2 Mounting the Hot Standby IDUs in an ETSI Rack. 44

6.0 IDU/ODU Cable Installation........................................ 45

SECTION III Commissioning ............................ 49

1.0 General ........................................................................ 501.1 Tools required ...................................................... 501.2 Connections ......................................................... 50

Page 9: Citylink Manual RevD

B1088 Rev. D 9

2.0 Power on ...................................................................... 512.1 NEW-NMS/NEW-Configurator Startup and

connecting to Network Elements ......................... 512.1.1 Starting NEW-NMS/NEW-Configurator with

Serial Connection (RS-232/ LCT). ....................... 512.1.2 Starting NEW-NMS/NEW-Configurator with

TCP/IP Connection. ............................................. 522.2 Initial configuration ................................................ 52

3.0 Antenna Alignment ...................................................... 533.1 Procedure for Coarse-alignment .......................... 543.2 Procedure for Fine-alignment .............................. 543.3 Cross Polarization Adjustment ............................ 553.4 Final Control ......................................................... 55

SECTION IV Configuration ............................... 57

1.0 General ........................................................................ 58

2.0 Element Node .............................................................. 602.1 Element Id ............................................................ 602.2 Available Functions .............................................. 612.3 Notification Mask .................................................. 622.4 NE Clock Page ..................................................... 642.5 Software Download .............................................. 652.6 Software Versions ................................................ 66

3.0 Transmission Node..................................................... 683.1 Section Termination ............................................. 683.2 Alarm Indication Signal Insert ............................... 693.3 Path Trace ........................................................... 72

4.0 Equipment Node ......................................................... 744.1 Network Routing ................................................... 744.2 Communication Ports .......................................... 764.2.1 DCC (Data Communication Channel) ................. 764.2.2 NI (Network Interface) ........................................... 78

Page 10: Citylink Manual RevD

10 B1089 Rev. D

4.2.3 LCT ...................................................................... 804.2.4 Ethernet ............................................................... 814.2.5 IP Settings ............................................................ 824.2.6 IP Tunneling ......................................................... 834.2.7 OSI TP4 Tunneling ............................................... 844.3 Looping ................................................................ 854.3.1 Main Looping ........................................................ 854.3.2 64 Kbit/s Looping ................................................. 874.3.3 Wayside Looping ................................................. 884.3.4 Advanced Looping ................................................ 904.3.5 CityLink IDU-Switch Looping ................................ 914.4 In Door Unit (IDU) ................................................. 924.4.1 IDU Production Data ............................................ 924.4.2 64 kbit/s Channels ............................................... 944.4.3 2 Mbit/s Wayside Channel ................................... 964.4.4 X-Connect ............................................................ 974.4.5 Pulse Output ........................................................ 984.4.6 Diagnose .............................................................. 994.4.7 Self Test ............................................................... 1004.4.8 BER Thresholds .................................................. 1004.4.9 Laser Control ....................................................... 1024.5 Out Door Unit (ODU) ........................................... 1044.5.1 ODU Transceiver - Configuration Frequency....... 1044.5.2 ODU Transceiver - Power Configuration ............. 1064.5.3 ODU Production Data .......................................... 1084.5.4 Antenna Data ....................................................... 109

5.0 Hot Standby ................................................................. 1105.1 General ................................................................ 1105.1.1 The Element Node Configuration ......................... 1115.1.2 The Equipment Node Configuration ..................... 1125.2 Combining the HSB Elements ............................. 1135.3 Hot Standby Element ID ....................................... 1145.3.1 Splitting a Hot Standby System ............................ 1165.4 Switching Criteria ................................................. 1175.5 Hot Standby Configuration ................................... 1185.6 CityLink IDU-Switch Production Data - Main Card 1205.7 Replacing Units .................................................... 122

Page 11: Citylink Manual RevD

B1088 Rev. D 11

SECTION V Trouble Shooting .......................... 123

1.0 General ........................................................................ 124

2.0 Troubleshooting by means ofLEDs and Display ........................................................ 1242.1 Description of Alarm LEDs .................................. 1252.2 Use of Keypad and Display .................................. 1252.3 Other alarms that will be shown on

the LEDs on the IDU-Switch ................................ 127

3.0 Troubleshooting by NEW-NMS Configurator .......... 1283.1 Introduction .......................................................... 1283.2 Information Acquisition ......................................... 1283.2.1 Polling .................................................................. 1283.2.2 Event Notification ................................................. 1283.3 Alarm Presentation .............................................. 1293.4 Visual Alarm Notification ....................................... 1293.4.1 Alarms on a Tree node/leaf in the Explorer view .. 1303.4.2 Alarms on a Node symbol in the Map view........... 1313.4.3 Alarms on a Block component in

the Physical/ Schematic view .............................. 1323.4.4 Viewing Alarms in the Current Alarms View ......... 134

4.0 Cable Fault ................................................................... 135

SECTION VI Appendices ................................. 137

Appendix I: IDU Interface Description .................................. 138Power Connector .................................................. 142LAN (TP) Connector Detail ................................... 142LAN (AUI) Connector Detail ................................... 143NI1 and NI2 Connector Detail ................................ 14464Kb/s Connector Detail ....................................... 145ALM & AUX Connector Detail ................................ 146LCT Connector Detail ........................................... 147

Page 12: Citylink Manual RevD

12 B1089 Rev. D

Appendix II: ODU Interface Description ............................... 148ODU/IDU Interface ............................................... 148Branching / Antenna Interface .............................. 148

Appendix III: Alarm List & Alarm Description......................... 149

Appendix IV: Requirements concerning Revisions of Unitsused in Hot Standby Configuration ................. 153

Page 13: Citylink Manual RevD

B1089 Rev. D 13

I E

qp. D

escr

iptio

n

EquipmentDescription

SECTION I

Page 14: Citylink Manual RevD

14 B1089 Rev. D

I Eqp. D

escription

1.0 IntroductionCityLink is a super compact SDH radio-relay transmission system for the 18,23 and 25 GHz frequency bands with STM-1 capacity. The equipment is splitmounted with one single coaxial cable between the InDoor Unit (IDU) andthe OutDoor Unit (ODU). The ODU and antenna can be located up to 300meter apart from the IDU. The equipment is available in 1+0 (single) or hotstandby configurations.

The network applications foreseen for this equipment are mainly for in-creased connectivity in urban areas as well as closure of fibre optical rings.

Built-in supervision enables easy installation and configuration, and systemstatus and availability data may be recorded. Advanced management withstandardised use of the Embedded Control Channel (ECC) allows for easyremote access to this equipment. Broadband RF design enables easychannel selection.

Key features• Easy installation• Frequency agility (selectable from the management system)• Optical or electrical STM-1 interface• 64kbit/s and 2Mb/s insert channels• Built-in diagnostics with local and remote loopback• Extended temperature range• 1+0 or Hot Standby Configuration• High system gain• Automatic/Manual Transmitter Power Control (ATPC/MTPC)• Standardized use of the ECC• Embedded SNMP• 55 (56) MHz channel arrangement• 2MHz synchronization interface (SETS)• Interface for local and subnetwork management (LAN or RS-232)

Page 15: Citylink Manual RevD

B1089 Rev. D 15

I E

qp. D

escr

iptio

n

2.0 IDU Description

Fig. I-1 IDU Front Layout

Figure I-1 shows the IDU front layout. All the connectors are located on thefront for easy operation. In addition to the STM-1 data interface, 2Mbit/swayside and 64kbit/s data channels are available. The IDU is equipped withan integrated supervisory system for local and remote configuration andcontrol. The supervisory system communicates with the ODU by use of anFSK modulated channel on the coaxial cable. The same coaxial cable alsocarries power to the ODU. An integrated 2 lines LCD is available for alarmview and RF input and output level monitoring (see Section V; TroubleShooting). For configuration and management purposes the IDU is equippedwith two LCT interfaces for connection to the PC, one with RS-232 interfaceand one LAN TP interface. In addition NI interfaces for connection to otherIDU’s or other Nera equipment are provided. The IDU has a connector foralarm input/output functionality (ALM & AUX).

Figure I-2 shows a block schematic view of the IDU with STM-1 NetworkNode Interface. In radio transmit direction the STM-1 input is CMI decodedand fed to the SORP ASIC. It performs all the SOH processing and radioscrambling. The FIR ASIC encodes the signal by use of a convolution codeand maps it to the 32CROSS constellation. It also performs the necessarypulse shaping. The signal is then I/Q modulated, and the 350MHz IF signalis fed to the ODU interface and applied to the IF coaxial connector. In radioreceive direction the 140MHz IF from the ODU will interface the IDU on thesame connector. The necessary equalising functions are provided in theODU interface before the IF signal is presented to the coherent demodulator.From the demodulator the signal is fed to the adaptive time domain equaliser.The equalised signal is then decoded in the TRELLIS decoder, by use of softdecision and the Viterbi algorithm for error correction. The signal then goesto the SORP for radio descrambling and SOH processing, and is finally CMIencoded in the CMI interface.

CRIT ICALM A J O RM I N O RW A R N I N G

P O W E R O N

A

B

CSTM-12Mb/s Wayside

IN OUT IN OUT

2MHz Sync

IN OUT

L C T

NI 2NI 1

G.703 V.11

64kb/s

A L M & A U X

LAN ( AUI )LAN (TP)- 4 8 V D C

FUSE 1.0A

ODU

Page 16: Citylink Manual RevD

16B

1089

Rev

. D

I Eqp. Description

Fig

. I-2

Blo

ck s

chem

atic

vie

w o

f the

IDU

ADAPTIVE

TIMEDOM.

EQUALIZER

TRELLIS

DECODER

ANALOGDEMOD-ULATOR-

ODU

INTERFACE

ANALOGMODULATOR

FIR FILTER

&

ENCODER

S DH

OVERHEAD &

R ADIO

PROCESSOR

SORP

SUPER-

VISORY

SYSTEM and

NETWORKELEMENTAGENTS

CMI

INTERFACE

or

OPT. TX/RX

LCD &

KEYPAD

STM-1

electrical

or optical

2x64kb/s

2Mb/sWAYSIDE

LCT

2 x NI

LAN

ALM/AUX

DC/DC

TO/FROM

ODU

REGULATED

OUTPUTS

MODEM TRANSCEIVER

COMMUNICATION

48V DC

DCC

Page 17: Citylink Manual RevD

B1089 Rev. D 17

I E

qp. D

escr

iptio

n

3.0 ODU DescriptionThe ODU is an assembly of branching unit and transceiver unit. The ODUis connected to the IDU with a single coaxial cable. The coaxial cable providesTx-IF, Rx-IF, signalling and power supply. For flexibility and easy installa-tion, the coaxial cable is connected to the transceiver through the branchingunit. The transceiver is attached to the branching with a snap on system.With this solution, the coaxial cable may remain connected during transceiv-er replacement. The ODU and the antenna are assembled very closelytogether making it very compact. Nevertheless the antenna can be separatedfrom the ODU by use of a flexible waveguide.

The branching unit contains RF channel filters, circulators and overvoltage-protection.

The transceiver unit contains a microwave Tx/Rx module, a synthesised localoscillator and a transceiver main board, all in a waterproof housing. Thetransceiver is based on dual frequency conversion in the transmitter andtriple conversion in the receiver. This radio architecture with high IFfrequencies allows for use of wide band branching filters while still maintain-ing excellent spectrum purity in transmitter and high selectivity in receiver.The use of wide band branching filters allows for a wide choice of remotechannel frequency selection without changing hardware.

The microwave module is an integrated multi-chip module with GaAs HEMTMMICs for Power Amplifier and Low Noise Amplifier. The necessary LOfrequencies for the frequency converters are generated in a low phase noisesynthesiser unit. The channel frequency is remotely programmed from theindoor unit. Transmit/receive IF-chain, control-circuits, signalling andpower supply are integrated on the transceiver main board.

Page 18: Citylink Manual RevD

18B

1089

Rev

. D

I Eqp. Description

TRANSCEIVER UNIT

140 MHz

UHF UPCONVERTER

IF IN / OUTM / T COMDC PWR

BRANCHINGUNIT

TRANSCEIVER MAIN BOARD MICROWAVE MODULE

PRE-DIST

350MHz

XN

ANTENNAUNIT

PWR

SYNTHESIZER

UHF LO

DUPLEXFREQ.

UHF LO

FIXEDFREQ.

210 MHz

2 GHzSYNTH

UHF DOWNCONVERTER

350 MHz CAB.EQ.

IF LOOP

CTRL / M/T COM POWER

IFIN /OUT

Fig

. I-3

Blo

ck s

che

ma

tic v

iew

of t

he

OD

U, 1

8G

Hz,

in 1

+0

co

nfig

ura

tion

Page 19: Citylink Manual RevD

B1089 Rev. D 19

I E

qp. D

escr

iptio

n

4.0 ManagementAn integrated supervision system makes the CityLink capable of function-ing as a Network Element (NE) in a managed SDH transmission network.Management and supervision of the CityLink can be performed in variousways from very simple alarm monitoring to standardised managementthrough optional built-in NE agents. Standardised use of Q

ECC, according

to ITU-T Rec. G.784, is provided.

The CityLink also supports embedded SNMP agent that can be controlledby SNMP based manager supplied by the service provider.

For element and network management the NEW-NMS (Nera Element vieW- Network Management System) software provides the full range of manage-ment functionality; Fault, Performance, Security and Configuration.

The integrated SNMP agent provides interface to higher level NetworkManagement Systems.

The alternative interfaces available at the IDU are described in Appendix I;IDU Interface Description.

5.0 Hot StandbyIn Hot Standby configuration, the IDU, the transceiver unit and the coaxialcable between IDU and ODU are duplicated. The two transceivers share acommon branching unit. A switch and a hybrid at radio frequency, includedin the branching unit, allow for switching between the two transmitters andprovides signal to the two receivers respectively. An IDU-switch unit isplaced between the two IDUs. Figure I-4 shows the IDU switch front layout.

The following user interfaces are protected in hot standby configuration:• STM-1 interface• 2 Mbit/s wayside interface• 2 MHz synchronisation interface

CRITICALMAJORMINORWARNINGPOWER ON

A

B

C

STM-12Mb/s Wayside

CALL

PHONE

IDU-A IDU-B

64kb/s, G.703SVCE INTFC

IDU-B-48VDC

FUSE 0.5A

IDU-AACCESSORY CONTROL

OUT IN

2MHz Sync

OUT IN OUT INIDU-A IDU-BUSER

IDU-A

IDU-B

ODU-A

ODU-B

OUT INOUT IN OUT INIDU-A IDU-BUSER

OUT INOUT IN OUT INIDU-A IDU-BUSER

Fig. I-4 Hot Standby IDU Switch, Front Layout

Page 20: Citylink Manual RevD

20B

1089

Rev

. D

I Eqp. Description

BRANCHINGUNIT

ANTENNAUNIT

PWR

TRANSCEIVER A

IDU B

HOT STBY IDU SWITCH

NON PROTECTEDUSER

INTERFACES(64 kb/s, NI, LAN)

PROTECTEDUSER

INTERFACES(STM-1, 2 MHz Sync,

2 Mb/s Wayside)

NON PROTECTEDUSER

INTERFACES(64 kb/s, NI, LAN)

TRANSCEIVER B

IDU A

Fig

. I-5

Blo

ck s

che

ma

tic v

iew

, C

ityL

ink

Ho

t S

tan

db

y co

nfig

ura

tion

Page 21: Citylink Manual RevD

B1089 Rev. D 21

II In

stal

latio

n

Installation

SECTION II

Page 22: Citylink Manual RevD

22 B1089 Rev. D

II Installation

1.0 GeneralThis section assumes that pre-planning of the link has occurred, i.e. pathbudgeting & survey to ensure good line-of sight between the two link ends.

1.1 PackingAny sensitive product, i.e. IDU and Printed Circuit Boards, are packed inspecial antistatic handling bags or boxes.

It is therefore essential that whenever unpacking or disassembling theequipment and or handling printed circuit boards etc., special precautionsto avoid ESD (Electro Static Discharge) should be taken, such as using wristgrounding or corresponding protection.

The equipment is packed in sealed plastic bags which are equipped withrequired moisture protection.

All equipment is further packed in special designed cases prepared fortransportation.

Dimensions and weight of each case are specified in the "Packing specifi-cations" issued for the respective shipment.

1.2 MarkingMarking is done according to customers requirements. If such informationis unavailable, the equipment is marked in the following way:

Customer addressContract No.Site Name (if known)Case No.

1.3 TransportationThe transport containers are prepared for shipment by air, truck, railway andsea, suitable for handling by fork-lift trucks and slings.

The cargo must be kept dry during transport and storage.For sea-transport, deck-side shipment is not permitted and carrier-ownedcargo containers should be used.

Page 23: Citylink Manual RevD

B1089 Rev. D 23

II In

stal

latio

n

1.4 Radio Equipment Inventory CheckLook for damage on the cases. Ensure that correct quantities of goods havearrived, according to the packing list in each package/unit.

Check also that the part description on the outside of each box correspondsto the components required for the installation, i.e. correct antenna andfrequency, ODU frequency band and sub-band, IDU configuration.

Report any damages or missing items to Nera ASA by telex or fax. A shortdescription of damages, preferably including photographs, should be sentas soon as possible.

1.5 Preparation for InstallationComplete the required civil works. Transport all the equipment to site.Unpack the equipment and inspect for damage during transit to site and makesure that the correct quantities of goods have arrived.

Units with static discharge protection should not be unpacked until insertioninto its place (slot) in the equipment takes place. Discharge yourself beforeinsertion of the unit.

1.6 Handling & StoringIt is recommended that components are stored and transported to theinstallation site in their original packing cases. If items are unpacked forstorage, they should be handled with care and protected during transpor-tation by similar protective materials.

The equipment is an electronic device which should be handled with care.It should be stored in dry, cool conditions, out of direct sunlight. A moistureabsorbing bag is taped inside the transportation unit to minimise conden-sation during transportation. This is to be removed at installation.

No maintenance is required when stored according to particulars above.

Page 24: Citylink Manual RevD

24 B1089 Rev. D

II Installation

2.0 Installation Equipment required

2.1 ToolsThe tools needed to install the equipment are listed in the following sub-chapters.

2.1.1 Tools for Antenna Installation• 2 pcs Combination Wrench 13 mm• 2 pcs Combination Wrench 16 mm• 2 pcs Combination Wrench 17 mm• 1 pc Torque Wrench 16 mm, 40 - 50 Nm

2.1.2 Tools for IDU- ODU Cable /Connector Mounting• 1 Hacksaw, fine-toothed• 1 Soldering Iron, min. 150W• Solder 36/37 RMA flux core• Cloth• 1 Knife• 1 Flat file, fine• 1 Wire brush• 1 Tape rule (or caliper)

• 1 Heat gun, 1000W

for hexagon coupling nut :• 1 Wrench 1/2" (13mm)• 1 Wrench 9/16" (15mm)• 1 Wrench 11/16" (18mm)• 1 Wrench 13/16" (21mm)

Page 25: Citylink Manual RevD

B1089 Rev. D 25

II In

stal

latio

n

2.2 Equipment external to the Radio EquipmentIn addition to the necessary radio equipment & antenna the following itemsare needed:

• Coaxial cable between IDU and ODU. See chapter 6 (this Section) foradvise on which cable to use.

• At least two crimpable N-type connectors suitable for termination ofthe coaxial cable.

• Suitable waveguide & flanges between antenna and branching unitif remote mount option is used.

• Cable to ground the ODU.• Cable to ground the IDU.• Cable to power the IDU.• Cable to connect the PC, running the configuration & set-up program,

to the IDU.• Cable ties to secure cable runs.

Page 26: Citylink Manual RevD

26 B1089 Rev. D

II Installation

3.0 ODU / Antenna Installation

3.1 Installation of 0.6m and 0.45m AntennaThe following installation procedure contains drawings that describe onlythe 0.6m antenna. However, the procedure is the same for the 0.45m antennaas only the reflector's diameter is different.

3.1.1 Attachment of Plate and Turnbuckle

PLATE

TURNBUCKLE

M8x40

Page 27: Citylink Manual RevD

B1089 Rev. D 27

II In

stal

latio

n

M10x35

BRANCHINGSUPPORTBRACKET

M10x150(FOR Ø75MMCOLUMN: M10x130)

3.1.2 Mounting Lower Clamp

3.1.3 Assembly of Branching Support Bracket

Page 28: Citylink Manual RevD

28 B1089 Rev. D

II Installation

3.1.4 Installation of Branching Unit,Sun-shield and FlexIble Waveguide

M4 M8

BRANCHING UNIT

SUN-SHIELD

FLEXIBLEWAVEGUIDE

NOTE!Most antennas are delivered with a bimetallic shim. This MUSTNOT be mounted for CityLink installations as the ODU, theflexible waveguide and the antenna all have aluminiumwaveguide connectors.

Mount two gaskets between the antenna feed and the flexiblewaveguide and also two gaskets between the flexible waveguideand the branching unit. If the installation is placed in a verycorrosive environment, further protection can be achieved byadding silicon rubber.

Grounding pointsee Chapter 6.0 Fig. II-11

Page 29: Citylink Manual RevD

B1089 Rev. D 29

II In

stal

latio

n

3.1.6 Assembly of Lower Column Clamp and Threaded Rod.Attachment of Reflector to Column.

M10x150(FOR Ø75 COLUMN:M10x130)TORQUE 40-50 NM

THREADED ROD

3.1.5 Assembly of Upper Column Interface

DIRECTION OFTRANSMISSION

M10x150(FOR Ø75 COLUMN:M10x130)TORQUE 40-50 NM

Threaded Rod mounted tothe plate

Page 30: Citylink Manual RevD

30 B1089 Rev. D

II Installation

3.1.7 Installation of Transceiver

NOTE!To avoid damage to the waveguide components, remember toremove the transportation protection lid mounted on the trans-ceiver's waveguide output.

Page 31: Citylink Manual RevD

B1089 Rev. D 31

II In

stal

latio

n

3.1.8 Installing the ODU / Antenna on a Wall or a Roof

3.1.8.1 Assembly the Bracket for Wall / Roof Mount

SPLITSECTIONBUSHING

BRACKETSECTION

M10

M10

EXPANSION NUT FOR CON-CRETE WALL OR ROOF.DRILL A 40mm DEEP Ø12mmHOLE FOR EACH NUT PRIORTO MOUNTING

M10 BOLT OR SCREW.USE THE M10 BOLT IF THEWALL IS MADE OUT OF WOODAND THE SCREW (AND EXPAN-SION NUT) IF IT IS A CON-CRETE WALL.

LET THE SECTIONBUSHING REST ONTHIS BOLTHEAD

Page 32: Citylink Manual RevD

32 B1089 Rev. D

II Installation

3.1.8.2 Attachment of ODU / Antenna to the Mount BracketFollow the same procedure as for regular column mounting (ref Chapters3.1.1 through 3.1.6).

Page 33: Citylink Manual RevD

B1089 Rev. D 33

II In

stal

latio

n

105m

m ±

5

3.2 Installation of 1.2m AntennaThis chapter only descibes how to install the CityLink branching supportbracket and the branching unit. For further instructions please refer to thehandbook supplied with the antenna (H2602; Installation Procedure for 1.2mAntenna).

For installation of the transceiver, see Chapter 3.1.7.

3.2.1 Assembly of Branching Support Bracket

BRANCHINGSUPPORTBRACKET

HORIZONTALGIRDER

VERTICALGIRDER

HORIZONTALGIRDER

BRANCHINGSUPPORTBRACKET

Make sure that the distance between the top of the branching supportbracket and the horizontal girder is 105mm ±5mm.

Page 34: Citylink Manual RevD

34 B1089 Rev. D

II Installation

3.2.3 Installation of Branching Unit,Sun-shield and Flexible Waveguide

NOTE!Most antennas are delivered with a bimetallic shim. This MUSTNOT be mounted for CityLink installations as the ODU, theflexible waveguide and the antenna all have aluminiumwaveguide connectors.

Mount two gaskets between the antenna feed and the flexiblewaveguide and also two gaskets between the flexible waveguideand the branching unit. If the installation is placed in a verycorrosive environment, further protection can be achieved byadding silicon rubber.

M4 M8

BRANCHING UNIT

SUN-SHIELD

FLEXIBLEWAVEGUIDE

ANTENNAFEED

FLEXIBLEWAVEGUIDE

Page 35: Citylink Manual RevD

B1089 Rev. D 35

II In

stal

latio

n

4.0 IDU Installation

4.1. Mounting the IDU in a 19” RackPosition the IDU in the rack and secure it by using the four M6 - 16mm screwsprovided in the IDU package (see Figure II-1) . Allow min 10mm space aboveand below the IDU for ventilation purposes.

Figure II-1 Mounting the IDU in a 19” Rack

Figure II-3 Mounting the IDU in an ETSI Rack

4.2 Mounting the IDU in an ETSI RackMount the adapters provided in the IDU package by using the M6 - 20mmscrews provided in the IDU package. See Figure II-2.Position the IDU in the rack and secure it by using the four M6 - 6mm screwsprovided in the IDU package. Allow min 10mm space above and below theIDU for ventilation purposes. See Figure II-3.

Figure II-2 Mounting the Adapters for ETSI Rack

Page 36: Citylink Manual RevD

36 B1089 Rev. D

II Installation

4.3 Mounting the IDU for FreestandingIn case the IDU shall be placed on a table, on a shelf or on top of another IDUthe table studs provided in the IDU package must be mounted. See FigureII-4and II-5. Ensure minimum 10mm space above and below the IDU forventilation purposes. Do not cover the ventilation holes on the top of theIDU.

After putting the table studs into the bottom holes of the IDU, press thecenter pin through the stud so that it is firmly locked to the IDU. See below.

Figure II-4 Mounting the IDU table studs for freestanding

Figure II-5 Locking the IDU table studs to the IDU.

Page 37: Citylink Manual RevD

B1089 Rev. D 37

II In

stal

latio

n

4.4 Mounting the IDU on a WallMount the feet provided in the IDU package. See Figure II-4 and II-5. Hookup the IDU as indicated in Figure II-6. Ensure minimum 10mm space betweenthe wall and the bottom of the IDU.

Figure II-6 Mounting the IDU on a wall

Detail

Detail

Page 38: Citylink Manual RevD

38 B1089 Rev. D

II Installation

4.5 Cable Installation Route, secure if necessary with cable ties, and terminate ground cable

between the IDU chassis ground post and a nearby local earth point. Usemin. 10mm2 cable. Refer to Appendix 1, Figures VI-1 and VI-2 for the IDUchassis ground post location.

Route, secure if necessary with cable ties, the terminated IDU/ODU andconnect to the ODU port of the IDU. See Chapter 5.0 (this Section) forfurther details.

Dependent on the purchased configuration of the IDU, route and attachall cables except the power cable. Refer to Appendix 1 for wiring details.

The CityLink requires DC power (-40,5 to -57V) via a 2-pin connector.Refer to Figure VI-3 for a pinout of the connectors. It is recommendedto use the supplied power cable (UWMK3101).This cable is left unconnected in one end. The white inner conductormust be connected to 0V (station ground) and the black inner conductormust be connected to - 48V. After connecting the cable to the powersupply, measure polarity on power connector terminals before applyingpower to the IDU.

Attach the power cable to the IDU.

Page 39: Citylink Manual RevD

B1089 Rev. D 39

II In

stal

latio

n

5.0 Installation of Hot Standby Equipment

5.1 Installation of ODU / Antenna

5.1.1 0.45m and 0.6m Antenna

5.1.1.1 Attachment of Plate, Turnbuckle and Lower ClampPlease refer to Chapter 3.1.1 and 3.1.2 (this Section).

5.1.1.2 Assembly of Branching Support Bracket

M8x35THREADED STUD

BRANCHINGSUPPORTBRACKET

Page 40: Citylink Manual RevD

40 B1089 Rev. D

II Installation

5.1.1.3 Installation of Hot Standby Branching Unit,Sun-shield and Flexible Waveguide

NOTE!Most antennas are delivered with a bimetallic shim. This MUSTNOT be mounted for CityLink installations as the ODU, theflexible waveguide and the antenna all have aluminiumwaveguide connectors.

Mount two gaskets between the antenna feed and the flexiblewaveguide and also two gaskets between the flexible waveguideand the branching unit. If the installation is placed in a verycorrosive environment, further protection can be achieved byadding silicon rubber.

M4 M8

BRANCHING UNIT

SUN-SHIELD

FLEXIBLEWAVEGUIDE

Grounding pointsee Chapter 6.0 Fig. II-12

Page 41: Citylink Manual RevD

B1089 Rev. D 41

II In

stal

latio

n

5.1.1.4 Assembly of Column Interface, Lower Column Clampand Threaded Rod. Attachment of Reflector to ColumnPlease refer to Chapters 3.1.5 and 3.1.6 (this Section)

5.1.1.5 Installation of Transceiver

NOTE!To avoid damage to the waveguide components, remember toremove the transportation protection lid mounted on the trans-ceiver's waveguide output.

Page 42: Citylink Manual RevD

42 B1089 Rev. D

II Installation

5.1.2 1.2m AntennaThis chapter only descibes how to install the CityLink branching supportbracket and the branching unit. For further instructions please refer to thehandbook supplied with the antenna (H2602; Installation Procedure for 1.2mAntenna).

For installation of the transceiver, see Chapter 5.1.1.5.

5.1.1.2.1 Assembly of Branching Support Bracket

87m

m ±

5

BRANCHINGSUPPORTBRACKET

HORIZONTALGIRDER

VERTICALGIRDER

HORIZONTALGIRDER

BRANCHINGSUPPORTBRACKET

Make sure that the distance between the top of the branching supportbracket and the horizontal girder is 87mm ±5mm.

Page 43: Citylink Manual RevD

B1089 Rev. D 43

II In

stal

latio

n

5.1.2.2 Installation of Branching Unit,Sun-shield and Flexible Waveguide

FLEXIBLEWAVEGUIDE

BRANCHING UNIT

M4 M8

SUN-SHIELD

Page 44: Citylink Manual RevD

44 B1089 Rev. D

II Installation

5.2 Hot Standby IDU Installation

5.2.1 Mounting the Hot Standby IDUs in a 19” RackPosition the IDUs in the rack and secure them by using the four M6 - 16mmscrews provided in each IDU package (see Figure II-7) . Allow min 10mmspace above and below the IDUs for ventilation purposes.

Figure II-7 Mounting the Hot Standby IDUs in a 19” Rack

IDU A

IDU B

IDU SWITCH

Figure II-8 Mounting the Hot Standby IDUs in an ETSI Rack

5.2.2 Mounting the Hot Standby IDUs in an ETSI RackMount the adapters provided in each IDU package by using the M6 - 20mmscrews provided in the IDU package. See Figure II-2 (Chapter 4.2).Position the IDUs in the rack and secure them by using the four M6 - 6mmscrews provided in each IDU package. Allow min 10mm space above andbelow the IDUs for ventilation purposes and 25mm between the IDUs. SeeFigure II-8.

IDU A

IDU B

IDU SWITCH

Page 45: Citylink Manual RevD

B1089 Rev. D 45

II In

stal

latio

n

6.0 IDU/ODU Cable InstallationBoth ends of the cable must be terminated with N-male connectors. Werecommend using flexible tube coaxial cable FSJ1-50 (CF 1/4"). If this cableis requested by the purchaser, the N-male connectors and the installationmaterial may also be supplied.

For other cable types the cable and all necessary installation materials mustbe arranged by the purchaser.

Cable length limitations are dependent upon cable type used. The tablebelow shows some examples.

Cable type Maximum cable length Minimum supply voltagewith minimum with 300 meter cablesupply voltage

FSJ1-50 90 m 47VCF ¼" Cu 2Y, 50Ω 200 m 42VLCF 3/8" Cu 2Y, 50Ω 300 m 40.5VRG214/U 150 m 300m cable is not

applicable. Max. cablelenght is 250m with supplyvoltage > 43V

• Avoid excessive bending. Run the cable where it is reasonable wellprotected and will not rub against sharp edges or overly abrasivesurfaces.

• Avoid generic crimp tools for the cable connectors. Use the crimp tooldesigned for the connectors and cable being used.

• The N-connectors should be tightened to the IDU and ODU by hand.Using a tool may cause damage.

• Leave enough slack in the cable termination to the ODU to allowantenna re-positioning.

• The cable connection to the ODU should be made weatherproofusing the cable connector weatherproof sleeve provided in theinstallation kit.

See Figure II-9 for Coax Cable Arrangement for FSJ1-50 cable type.

Page 46: Citylink Manual RevD

46 B1089 Rev. D

II Installation

1a 1b 1c

1d 2

3 4 5

6

CABLE KIT 100 mCABLE KIT 200 mCABLE KIT 300 m

CABLE ( x) mCABLE TIE

CONNECTOR, IDUCONNECTOR,ODUGROUNDING KIT

CABLE GLAND

FSJ1-50A+ 241630-3FSJ1-50A+ 241630-3FSJ1-50A+ 241630-3

FSJ1-50A40417

F1PNR-HCF1PNM-H 223158

--

ITEM PART NO. (ANDREW)

85W99-10085W99-20085W99-300

85W99-1A87B1-4

87K64-22*87K64-23*87K97-19* --

REMARKSQTY

100 m200 m300 m

(x) m 2/m

1 1 1 1

OUTDOORCONNECTORASSEMBLYINSTRUCTIONS 237336(PACKED WITH CONNECTOR)

INDOORCONNECTORASSEMBLYINSTRUCTIONS 237316(PACKED WITH CONNECTOR)

4

HANGER SPACING

0.5 m

2

INDOOR UNIT, IDU

51

2

6

1

MINIMUM BENDING

RADIUS: 25 mm

2 (x2)

DESCRIPTION

INCLUDING 200 TIES (40417)INCLUDING 400 TIES (40417)INCLUDING 600 TIES (40417)

Length more than 300 m 2 Ties per meter cable

= * CONNECTOR KIT CODE : AZBZ130

TO BE SPECIFIED

ORDERINGCODE (NERA)

4

1

3

OUTDOOR UNIT, ODU

ANTENNA

3

INSTALLATIONINSTRUCTIONS 237196

(PACKED WITH GND KIT)

NOTE 1

WEATHER PROTECTIONKIT ABZ278 IS INCLUDEDIN ODU (OUTDOOR UNIT).(See Figure II-10)

NOTE 1

NOTE 1

REEL

241630-3

Figure II-9 Coax Cable (FSJ1-50) Arrangement

Page 47: Citylink Manual RevD

B1089 Rev. D 47

II In

stal

latio

n

CABLE CONNECTION

1. Slide the Protection Sleeve and the Clamp Hose over the connector and onto the cable.

2. Connect the cable to the ODU. Press the protection sleeve over the connector and tighten the connector by hand (using the sleeve gives a good hand-grip when tightening).

3. Pull the protection sleeve backwards and apply Sealing Compound (Plast 2000) onto the top end of the sleeve. Press the sleeve upwards and over the connector until it stops into the groove around the ODU connector`s nut and washer.

4. Adjust the clamp diameter with a screwdriver and slide in the clamp between the sleeve and the ODU`s cooling ribs and place it over the connector head.Tighten the clamp with a screwdriver.

OUTDOOR UNIT ODU

BOTTOM OFBRANCHING UNIT

PROTECTION SLEEVE97E12A-1

N - CONNECTOR

SEALING75N06D-1

HOSE CLAMP 97Z6A-5

BOTTOM OFBRANCHING UNIT

PROTECTIONSLEEVE

N - CONNECTORfemale, chassis

N - CONNECTORmale, cable

HOSE CLAMP

APPLY SEALING COMPOUND HERE

CONNECTOR ATTACHMENT

SEE INSTALLATION INSTRUCTIONS ANDREW 327336

ADDITIONAL SEALING :

1. USE O- RING 97G1A-6 HERE

2. USE SEALING COMPOUND 75N06D-1 HERE

(NOTE 1)

NOTE 1 :

ALL CODED ITEMS AREINCLUDED IN KIT ABZ278(PACKED WITH ODU BRANCHING UNIT)

(NOTE 1)

Figure II-10 Coax Cable (FSJ1-50) Connection

Page 48: Citylink Manual RevD

48 B1089 Rev. D

II Installation

Figure II-11 Branching Unit Grounding Point

Attach grounding cable (10mm 2) to thispoint with the M8 nut and washers.

Figure II-12 Hot Standby Branching Unit Grounding Point

Attach grounding cable (10mm 2) to thispoint with the M8 nut and washers.

Page 49: Citylink Manual RevD

B1089 Rev. D 49

III C

omm

issi

onin

g

Commissioning

SECTION III

Page 50: Citylink Manual RevD

50 B1089 Rev. D

III Com

missioning

1.0 GeneralThis section assumes that the radio terminal has been installed according tothe guidelines in Section II; Installation.

1.1 Tools required• Voltmeter to monitor AGC voltage• Cable for connection between AGC monitoring point and voltmeter.

1.2 ConnectionsSee Appendix I for a more detailed description of connectors.

Before connecting power apply the following cables:• Cable for main traffic, i.e. STM-1 electrical or optical, up to

3 x 34Mb/s or up to 21 x 2Mb/s.• IDU chassis ground. Use min. 10 mm2 cable.• Coaxial cable between IDU and ODU.• Cable to connect the PC, running the configuration & set-up program,

to the IDU.

Optionally the following connections may be used:• ALM/AUX connector for parallel alarm inputs and outputs.• 2x64kb/s connector for 64kb/s serial channels utilising bytes in the

Section Overhead.• NI-1 and/or NI-2 connectors for interface to other Nera equipment.• 2Mb/s WAYSIDE connectors for interface to 2Mb/s wayside traffic

channel utilising bytes in the Section Overhead.• 2MHz SYNC connectors for synchronisation purposes.

Page 51: Citylink Manual RevD

B1089 Rev. D 51

III C

omm

issi

onin

g

2.0 Power onApply power to the IDU by connecting the power cable. The radio link’sstart-up procedure and self-diagnostics will start to execute.

When power is applied to the IDU the system will perform self test, this willtake a few seconds. The message “* PWR On Boot * Please wait...” will bedisplayed on the LCD during the test period. If no fatal errors are found theactive SW version will start. The message “Starting Application” will bedisplayed for a few seconds while the application SW is starting.

Error messages and how to correct them are described in Section V TroubleShooting.

2.1 NEW-NMS/NEW-Configurator Startup andconnecting to Network ElementsThe NEW-NMS/NEW-Configurator (Nera Element vieW-Network Manage-ment System/ -Configurator) program must be installed on a PC satisfyingthe requirements depicted in the program manual. Follow carefully theprogram installation instructions to make sure the program is successfullyinstalled.

The element viewer can monitor the network elements using a serial connec-tion (RS-232) or a TCP/IP connection (or both for different network elements).Apply all external connections to the PC before the program is started.

A serial connection must be used the first time the network manager/configurator is connected to the CityLink, because the IP address must beset in the CityLink, before a TCP/IP connection can be established.

2.1.1 Starting NEW-NMS/NEW-Configurator withSerial Connection (RS-232/ LCT).Apply the serial cable to one of the serial ports of the PC and the LCT portof the CityLink.

Start the program. A Log on dialog box pops up. Log on to the network withyour user id and password. The program has an auto discover function whichautomatically discovers network elements connected to the serial ports ofthe PC when starting. If some network elements are connected to the serialports of the PC, the network topology is automatically discovered and

Page 52: Citylink Manual RevD

52 B1089 Rev. D

III Com

missioning

presented in the Explorer view. Press Add to include discovered elements inthe network topology of the program. The auto discover function can alsobe manually executed by selecting Discover from the File menu. Whendiscovering the network manually the program looks for network elementsat the open ports listed in the Communication dialog box (select Communi-cation from the Configuration menu).

2.1.2 Starting NEW-NMS/NEW-Configurator withTCP/IP Connection.(Assumes the TCP/IP address is configured in the CityLink )

Apply Ethernet connections to both the CityLink and PC. Start the program.A Log on dialog box pops up. Log on to the network with your user id andpassword. The program does not know the IP-address of the networkelement so the connection must be manually established. To configure aTCP/IP connection to the network element, select Communication from theConfiguration menu. Press the Add button and type the IP address of the NEin the address field of the dialog box which pops up. Press OK to save thechanges, and OK to close the Communication Configuration dialog box.Select Discover from the File menu. Press Add to include discovered elementsin the network topology of the program. The accepted network elements willbe discovered and presented in the Explorer view.

2.2 Initial configurationWhen the program has established contact with the CityLink, some config-urations must be set before antenna alignment can be performed.

A Configuration Wizard will guide you through the initial configurations.Start the Wizard by selecting the network element in the Explorer view. Thenselect Configuration > Wizard from the right mousebutton context menu.Follow the Wizard instructions.

All the configuration settings are described in Section IV; Configuration.

You are now ready to proceed with antenna alignment.

Page 53: Citylink Manual RevD

B1089 Rev. D 53

III C

omm

issi

onin

g

3.0 Antenna AlignmentIf an antenna other than Nera 0.45m or Nera 0.6m is used, follow themanufacturer's mechanical alignment instructions. Proceed to Chapter 3.2for details on fine-aligning the antenna.

TURNBUCKLE FORAZIMUTH ADJUSTMENT

AA

THREADED ROD FORELEVATION ADJUSTMENT

A

Bolt connections marked with an "A" are not to be too tight duringadjustment.

Page 54: Citylink Manual RevD

54 B1089 Rev. D

III Com

missioning

The purpose of the alignment procedure is to obtain maximum signal leveland cross polarization discrimination by aligning two antennas in oppositedirections.

The antennas should be properly mounted and polarized in the same way.It must be possible to transmit from one antenna and receive on the other.The best way is to have a transmitter and a receiver connected to both antennas.

3.1 Procedure for Coarse-alignmentAdjust both antennas to correct directions as precisely as possible by usingmagnetic compass or optical sight.

3.2 Procedure for Fine-alignmentFine adjustment is achieved by sending a signal from one of the antennas.On the receive side various methods may be used.

a) Measure the AGC voltage from the transceiverb) Read the received level on a spectrum analyzerc) Measure the received power with a Power Meterd) Use the audio signal to adjust for maximum input power. The audio

signal is activated by removing the cap from the AGC connector.

Mute the transmitter at the receive station to exclude interference from thissource.

It is recommended that the person adjusting the antenna can read theinstrument while adjusting. It is very easy to be misled if the signal is fading.

If the AGC voltage is used, a voltmeter should be connected and monitoredby the person who is adjusting the antenna. Adjust alternatively in azimuthand elevation till the received signal is at maximum level. Try a few times ineach direction.

The antenna should be turned enough that the first sidelobes are seen,thereby ensuring that the antenna is aligned on the main lobe.

When the antenna is correctly adjusted, secure all bolts. Monitor theinstrument during this operation and if necessary realign the antenna.

When adjustments are completed on the first antenna, this should be usedfor transmitting while the same procedure is performed on the oppositeantenna.

Page 55: Citylink Manual RevD

B1089 Rev. D 55

III C

omm

issi

onin

g

3.3 Cross Polarization AdjustmentAfter alignment of the antenna, the antenna feed should be adjustedhorizontally and vertically. Loosen the flange which secures the feed to thereflector. Align the feed by using a spirit level. Secure the flange.

3.4 Final ControlWhen all adjustments are performed check that the input level agrees withthe one theoretically calculated. If the input level is too low, adjust theantennas once more. Finally, ensure that all bolts and nuts are properlymounted and secured.

Page 56: Citylink Manual RevD

56 B1089 Rev. D

III Com

missioning

This page is intentionally left blank.

Page 57: Citylink Manual RevD

B1089 Rev. D 57

IV C

onfig

urat

ion

Configuration

SECTION IV

Page 58: Citylink Manual RevD

58 B1089 Rev. D

IV C

onfiguration

1.0 GeneralThis section assumes that the Commissioning described in Section III hasbeen performed for the complete radio link hop.

Configuration of the Network Elements is done from the Explorer View whichcan be launched by selecting Explore Net from the View menu.

Configuration of Network Elements is achieved using a set of property-sheets. The property-sheets are modeless, so configuration of severaldifferent modules can be displayed simultaneously.

To open the configuration property-sheets:Press the Right mouse-button on the Network Element node/leaf you wantto view/change the current configurations. A dynamic menu pops up. Openthe Configuration sub-menu and select the configuration-specific menuitem.

The configuration property sheets can also be launched by selecting/marking an NE node/leaf in the Explorer View and then selecting theconfiguration-specific menu item under the Edit sub menu in the Configu-ration menu.

The property-sheets are divided into two categories by means of function-ality:

Configuration Property sheets with Multiple Settings:The program retrieves the current settings from the NE when the property-sheet is opened. No message is sent to the element and no data is modifiedin NEW’s data structure before the user presses one of the property-sheetbuttons:

Figure IV-1 Buttons on Configuration property sheets withmultiple settings

Button descriptions:Set: Sets the current settings in the Network Element.Get: Retrieves the current settings of the Network Element.Close: Closes the property-sheet without saving or setting any dataHelp: Displays help for the active property-page.

.

Page 59: Citylink Manual RevD

B1089 Rev. D 59

IV C

onfig

urat

ion

To change the settings:1 First, get the current settings from the Network element by pressing Get.

The current NE settings are automatically retrieved when the property-sheet is opened.

2 Alter the settings.3 Press Set to send the changes to the network element.

Configuration Property sheets with Single Interactive Settings:The program retrieves the current NE settings when the property-sheet isopened. Has no Get, Set or Save buttons; All functional buttons are placedin the property-pages. A message is sent to the Network Element immediatelywhen a control is changed or a button is pressed.

Property-sheet buttons:

Figure IV-3 Configuration property sheet information field

Figure IV-2 Buttons on Configuration property sheets withsingle interactive settings

Button descriptions:Close: Closes the property-sheet.Help: Displays help for the active property-page.

All property-pages have an information field at the bottom reflecting thecurrent status of the data shown in the property-page and the date and timethe property sheet data was retrieved from the network element.

Page 60: Citylink Manual RevD

60 B1089 Rev. D

IV C

onfiguration

2.0 Element Node

2.1 Element IdThe CityLink Element Id property sheet shows some main information aboutthe Network Element (NE) like name, type, serial number and differentaddresses. The fields with white background can be altered by users withproper user privileges. The gray fields are non editable.

The Element Id configuration sheet can be opened from the Configurationcontext menu of the Element node in the Explorer view. The sheet can alsobe invoked by selecting (highlighting) the Element node in the Explorer viewand then selecting Edit Element Id from the Configuration menu.

Fields: Description:Serial Number: The serial number of the NE. (Not editable)NE Type: The type of NE. (Not editable)Name: The name of the NE (max. 32 characters)Section Address: The section address of the NE. (1-254)NE Address: The NE address (1-128). Used for identification of

NEs within a section.MAC Address: The Media Access Control address of the NE.

Used for OSI-Management. (Not editable)NSAP Address: The Network Service Access Point address of

the NE. Used for OSI-Management.IP Address The Internet Protocol address of the NE.Hot Standby: Check this to change type to Hot Standby

Figure IV-4 Element ID Configuration Sheet

Page 61: Citylink Manual RevD

B1089 Rev. D 61

IV C

onfig

urat

ion

2.2 Available FunctionsThe available functions property sheet shows the functions available at thenetwork element. All these functions are additional CityLink functions. Theuser has paid extra to get these functions. Contact your Nera equipmentsupplier to order functions. You will get an encrypted authentication stringin return.The Available Functions configuration sheet can be opened from theConfiguration context menu of the Element node in the Explorer view. Thesheet can also be invoked by selecting (highlighting) the Element node inthe Explorer view and then selecting Edit Available Functions from theConfiguration menu.

Fields: Description:Automatic Transmitted ATPC is a function for effectively reducingPower Control (ATPC) interference probabilities..IP Stack The NE has an integrated IP stack.

Synchronous Equipment Synchronous Equipment Timing Source isTiming Source (SETS) available.Simple Network Management An SNMP management agent is available.Protocol (SNMP)

64 Kbit/s Channels Two 64 Kbit/s channels can be inserted intothe STM-1 Section Overhead (SOH ).

2 Mbit/s Wayside Channel One 2 Mbit/s wayside channel can be insertedinto the STM-1 Section Overhead (SOH ).

Alarm Auxiliary Function A unit containing an auxiliary alarm unitand an auxiliary output unit is available.

Q3-Agent The NE supports Q3 network management.

Figure IV-5 Available Functions Configuration Sheet

Page 62: Citylink Manual RevD

62 B1089 Rev. D

IV C

onfiguration

2.3 Notification MaskWhen an event (of any kind) occurs at a CityLink Network Element, a ServiceRequest is sent to the program. A service request is an event notification.The event notifications can be masked out for some or all events. Hence, theradio will not send out event notifications when a masked event occurs. Bymasking out certain, or all event notifications, the spontaneous communi-cation traffic will be reduced.

The Alarm Events can be masked out for different severity levels. Maskmeans that when a checkbox is checked( ), no event notifications will besent.

The Notification Mask configuration sheet can be opened from theConfiguration context menu of the Element node in the Explorer view. Thesheet can also be invoked by selecting (highlighting) the Element node inthe Explorer view and then selecting Edit Notification Mask from theConfiguration menu.

Figure IV-6 Notification Mask Configuration Sheet

Page 63: Citylink Manual RevD

B1089 Rev. D 63

IV C

onfig

urat

ion

Fields: Choices: Description:

Event Mask Alarm Mark this and no Alarm Service Requests

will be sent from the NE to the program. Security Mark this and no Security Service Requests

will be sent from the NE to the program. Switching Mark this and no Switching Service Requests

will be sent from the NE to the program.

Alarm Severity Mask (When the Alarm Event Mask is marked thesefunctions are inactive)

Critical Mark this and no Alarm Service Requests willbe sent from the NE to the program whenCritical alarms occur.

Major Mark this and no Alarm Service Requests willbe sent from the NE to the program whenMajor alarms occur.

Minor Mark this and no Alarm Service Requests willbe sent from the NE to the program whenMinor alarms occur.

Warning Mark this and no Alarm Service Requests willbe sent from the NE to the program whenWarnings occur.

Page 64: Citylink Manual RevD

64 B1089 Rev. D

IV C

onfiguration

2.4 NE Clock PageThe NE Clock sheet lets you synchronize the Network Element Date/Timewith the NEW-NMS / PC Date/Time. (The NE Clock is set to the same date/time as the PC Clock).

The NE Clock configuration sheet can be opened from the Configurationcontext menu of the Element node in the Explorer view. The sheet can alsobe invoked by selecting (highlighting) the Element node in the Explorer viewand then selecting Edit NE Clock from the Configuration menu.

Fields: Description:The Element's Clock: The Date and Time retrieved from the

Network Element.Difference from The difference between the PC clockNEW-NMS (your PC): and the Network Element Clock.

Figure IV-7 NE Clock Configuration Sheet

Page 65: Citylink Manual RevD

B1089 Rev. D 65

IV C

onfig

urat

ion

2.5 Software DownloadCityLink Application software can be downloaded through the NEW-NMS/NEW-Configurator program.

The SW Download configuration can be started from the Configurationcontext menu of the Element node in the Explorer view. The sheet can alsobe invoked by selecting (highlighting) the Element node in the Explorer viewand then selecting Edit SW Download from the Configuration menu.

To download new NE application code:1. The process of downloading starts with selecting the file containing the

application code. The file has extension: .bin. When a .bin-file is selected,a dialog box showing some information about the file will appear.

2. Verify that the correct version of the code file is chosen. Press Cancelif wrong code file is chosen.

3. Press Start Download4. Wait until the download is finished.

New application software is now downloaded at the NE. Now the NE muststart to use the new software. The new software will not start to execute untilit is activated. This is done from the SW Version property sheet.

Page 66: Citylink Manual RevD

66 B1089 Rev. D

IV C

onfiguration

2.6 Software VersionsThe SW versions property sheet shows the software revisions and theirstatus. The IDU contains two application code memory banks for both theSU (IDU) and the Transceiver (ODU). Both the IDU and the ODU useapplication code from one bank, while the other bank is available for SWdownload. New software can be downloaded (see Chapter 2.5 SW Down-load) in the unused bank while the IDU or ODU is executing the code of theother bank. The user may also select which bank to execute the applicationfrom if both banks contain valid software.

The ODU contains an application code software bank in addition to the twobanks in the IDU. The ODU software is copied from the active IDU bank tothe ODU bank during the ODU boot process.

The SW Versions configuration sheet can be opened from the Configura-tion context menu of the Element node in the Explorer view. The sheet canalso be invoked by selecting (highlighting) the Element node in the Explorerview and then selecting Edit SW Versions from the Configuration menu.

Figure IV-8 SW Version Configuration Sheet

Page 67: Citylink Manual RevD

B1089 Rev. D 67

IV C

onfig

urat

ion

Fields: Description:SW Component Name of the softwareBank Software locationRevision Software revisionStatus Idle:Software is not being executed.

Active:Software is being executed.Loading: SW is downloading to this bank.Invalid: Incomplete or invalid SW; SW bankhas not been used or a SW download hasfailed.Not contact with unit: The IDU does not havecontact with the unit containing this SW.

To activate a memory bank:1 Select the unused bank (status: Idle) by clicking the left mouse button.2 Press the Set Active button

The NE will be reset and when it starts, the application code of the chosenbank will be executed.

Page 68: Citylink Manual RevD

68 B1089 Rev. D

IV C

onfiguration

3.0 Transmission Node

3.1 Section TerminationThe CityLink Section Termination sheet shows the channel configuration ofthe network element. For CityLink systems, the number of the differentchannel settings is fixed.Only the Channel Termination can be changed.

The Section Termination configuration sheet can be opened from theConfiguration context menu of the Transmission node in the Explorer view.The sheet can also be invoked by selecting (highlighting) the Transmissionnode in the Explorer view and then selecting Edit Section Termination fromthe Configuration menu.

Fields: Description:Regular Channels: The Number of Regular Channels.Protection Channels: The Number of Protection Channels.Regular Co. Channels: The Number of Regular Co. Channels.Protection Co. Channels: The Number of Protection Co. Channels.Channels: List of NE Channels with the channel properties.

Channel Name of the channel.Termination MS (Multiplexer section) or RS (Regenerator

Section) (Double-click the field to edit).The MS and RS are parts of the STM-1 Sectionoverhead. Together MS and RS form the totalSOH.

Figure IV-9 Section Termination Configuration Sheet

Page 69: Citylink Manual RevD

B1089 Rev. D 69

IV C

onfig

urat

ion

To change the settings:1. Get the current settings from the network element by pressing Get.

(The settings are automatically retrieved from the NE when the property-sheet is opened).

2. Alter the settings you want to change. To change the Terminationsettings, double-click in the appropriate cell in the list. A Combo-boxwhere you can select RS or MS is then displayed

3. Press Set to send the changes to the network element.

3.2 Alarm Indication Signal Insert(For advanced users)The Path Trace functionality and the AIS (Alarm Indicator Signal) function-ality are used for verifying that the received STM-1 frames are the frames wewant to receive (correct routing, frequency alignment...). This is done byeither inserting a fixed byte or a user defined ASCII string in the J0 slot in theRSOH, or a two bit RF ID symbol at the transmit end. This is done from thepath trace sheet. The RF ID functionality is only available at the Radio side.The radio that receives the STM-1 frames must have the same Trace string(J0) or RF ID defined in the AIS insert sheet. If there is a mismatch, an AIScan be inserted. An AIS can also be inserted if the HBER threshold isexceeded.

The AIS Insert configuration sheet can be opened from the Configurationcontext menu of both the Transmission Radio and Line Rx nodes in theExplorer view. The sheet can also be invoked by selecting (highlighting) oneof the Transmission Radio and Line Rx nodes in the Explorer view and thenselecting Edit AIS Insert from the Configuration menu.

Page 70: Citylink Manual RevD

70 B1089 Rev. D

IV C

onfiguration

Fields: Subfields: Description:

Insert AIS when An AIS is inserted when the Viterbi HBERViterbi HBER threshold is exceeded. (See Chapter 4.4.8 forthreshold exceeded setting of BER threshold.)

Insert AIS when An AIS is inserted when there is a mismatchtrace mismatch match between the Trace String set in the Path

Trace sheet and Trace String set on this sheet.

Insert AIS when An AIS is inserted when there is a mismatchRF ID mismatch between the RF ID set in the Path Trace sheet

and RF ID bit set on this sheet.The RF ID functionality is only available atthe Radio node.

AIS remove delay 1 - 200 seconds

RegeneratorSectionTrace (J0) Not Used The Regenerator Section Trace String is not

used.Fixed Byte The Regenerator Section Trace String is one

byte ( =8 bit) long.

Figure IV-10 AIS Insert Configuration Sheet

Page 71: Citylink Manual RevD

B1089 Rev. D 71

IV C

onfig

urat

ion

Fields: Subfields: Description:

User Message The Regenerator Section Trace String is a user de- (ASCII) fined message ASCII (sixteen bytes =128bits long)Expected: The ASCII string or fixed byte to be compared with

received J0 in RSOH. If mismatch, AIS will beinserted if the Insert AIS when trace mismatch boxis checked. The Expected field normally containsthe same values as the Trace string in the Pathtrace property sheet at the transmit end of the path.

Received: The ASCII string or fixed byte in received J0 inRSOH.

Status: The status of the Regenerator Section Trace:• OK: Expected and received Regenerator

Section Trace are identical.• RS-TIM alarm: (Regenerator Section Trace

Identifier Mismatch) Mismath betweenexpected and received RS Trace.

• LOF error: Loss of frame alarm on receivedSTM-1 signal. Thus, J0 is not available. Alarmstatus, OK or RS-TIM alarm will be latched.

• CRC error: CRC error in received RegeneratorSection Trace. (Only in User Message mode)

• Invalid: Not valid User Message received.

RF ID: (The RF ID functionality is only available at theRadio node)

Not Used/Used: RF_ID MS3 bit on/offExpected: The value to be compared with the RF ID byte

in the received SOH. If mismatch, AIS will beinserted if the Insert AIS when RF ID mismatchbox is checked. The Expected field normally con-tains the same values as the RF ID value in thePath Trace property sheet at the transmit end ofthe path.

Received: The received RF ID value.Status: The status of the RF ID:

• OK: Expected and received RF ID values areidentical.

• RF-ID alarm: Mismatch between expected andreceived RF ID values.

• Invalid: Not valid RF ID value received.

Page 72: Citylink Manual RevD

72 B1089 Rev. D

IV C

onfiguration

Figure IV-11 Path Trace Configuration Sheet

3.3 Path Trace(For advanced users)The Path Trace functionality and the AIS (Alarm Indicator Signal) function-ality are used to test that the received STM-1 frames are the frames we wantto receive (correct routing, frequency alignment. . . . ). This is done by eitherinserting a fixed byte or an user defined ASCII sting in the J0 slot in the RSOH,or a two bit RF ID symbol at the transmit end. This is done from the path tracesheet. The RF ID functionality is only available at the Radio side. The radiothat receives the STM-1 frames must have the same Trace string (J0) or RFID defined in the AIS insert sheet. If there is a mismatch, an AIS can beinserted. An AIS can also be inserted if the HBER threshold is exceeded.

The Path Trace configuration sheet can be opened from the Configurationcontext menu of both the Transmission Radio and Line Tx nodes in theExplorer view. The sheet can also be invoked by selecting (highlighting) theone of the Transmission Radio and Line Tx nodes in the Explorer view andthen selecting Edit Path Trace from the Configuration menu.

Page 73: Citylink Manual RevD

B1089 Rev. D 73

IV C

onfig

urat

ion

Fields: Subfields Description:Regenerator SectionTrace String

Enabled When checked the specific TraceString is sent in the J0 byte.

Fixed Byte The Regenerator Section TraceString is one byte ( =8bit) long.

User MessageThe Regenerator Section Trace (ASCII) String is a user defined message

ASCII (sixteen bytes =128bits long)Trace String Specifies the data (Fixed byte or User

Message) to be inserted into the J0byte.

RF IDNot Used/UsedRF_ID MS3 bit on/off

Two bit combination.

Page 74: Citylink Manual RevD

74 B1089 Rev. D

IV C

onfiguration

Figure IV-12 Routing Table Configuration Sheet

4.0 Equipment Node

4.1 Network RoutingEvery CityLink Network Element has a static and a dynamic routing tablewhich relates incoming messages, addressed to other NEs, to different ports.The NE evolves a Dynamic Routing Table, while the Static Routing Table isset by the user.

The dynamic routing table evolves towards the optimal routing table. Whenthe NE is reset, the dynamic routing table is reset too, so when the NE is turnedon again the NE has to evolve the routing table from “scratch”.

The static routing table is only used after the IDU has been booted. It is usedas a starting point for the dynamic routing mechanism, and will thus, ifproperly set, decrease the time the NE uses to create a sufficient routing table.Static entries can be manually added and dynamic entries can be copied tothe static table.

The Routing Table configuration sheet can be opened from the Configura-tion context menu of the Equipment node in the Explorer view. The sheet canalso be invoked by selecting (highlighting) the Equipment node in theExplorer view and then selecting Edit Routing Table from the Configura-tion menu.

Page 75: Citylink Manual RevD

B1089 Rev. D 75

IV C

onfig

urat

ion

Fields: Description:Auto The router may update the entry automatically.Manual The entry is never changed by the router.Section The Section number of the addressed NE.NE The SU number of the addressed NE.Port Tells which port the message should be routed

through. Can be:NI 1NI2DCC LineDCC RadioOSI TP4 Tunnel 1OSI TP4 Tunnel 2IP Tunnel 1IP Tunnel 2

Weight A computed weight which gives an idea of thedistance to the network element.

Buttons:Add: Adds a routingEdit: Edit an existing routingDelete: Delete a routingInsert Dynamic: Insert a dynamic routing

Page 76: Citylink Manual RevD

76 B1089 Rev. D

IV C

onfiguration

4.2 Communication Ports

4.2.1 DCC (Data Communication Channel)The CityLink DCC (Data Communication Channel) is used to communicatebetween the Supervisory Unit of the Network Element and Supervisory Unitsof other Network Elements through the SOH of the STM-1 traffic.

There are two DCC ports. DCC Line at the line side and DCC Radio at the radioside. The DCC Radio is always enabled. Nera Stack will always be enabledat DCC Radio.

The Communication Ports configuration sheet can be opened from theConfiguration context menu of the Equipment node in the Explorer view.Press the DCC tab to view/change the DCC settings. The sheet can also beinvoked by selecting (highlighting) the Equipment node in the Explorer viewand then selecting Edit Communication Ports from the Configurationmenu.

Figure IV-13 DCC Tab in Communication Ports Configuration Sheet

Page 77: Citylink Manual RevD

B1089 Rev. D 77

IV C

onfig

urat

ion

Fields: Choices: Description:Enabled Switches the DCC communication ports

on/off.Channel: The Channel where the DCC are inserted

in the SOH.Ch. 1-Ch XX CityLink has only one channel. This field

will always be ‘Ch. 1’ at CityLink.Direction

Line DCC Line is inserted the line side of theradio.

Radio DCC Radio is inserted the radio side ofthe radio.

Timeslot: Shows which timeslot in the SOH theDCC channels use. The user can changethe used timeslot by pressing SOH. TheSDH Frame Section Overhead Dialogbox will appear.

StackNera NERA Stack.

Nera stack is always enabled on the radioside (DCC Radio).

QECC QECC StackTCP/IP TCP/IP Stack

LAPD Data link layer for the QECC protocol. Formore information refer to ITU-T G.784and ITU-T Q.921.

Network side Server for the LAPD requests.User Side Client for the LAPD requests.

PPP: (Point to Point Protocol) Data link layerfor the TCP/IP protocol. (currently notimplemented)

Active mode (currently not implemented)Demand dial (currently not implemented)Direct mode (currently not implemented)Passive mode (currently not implemented)

Page 78: Citylink Manual RevD

78 B1089 Rev. D

IV C

onfiguration

4.2.2 NI (Network Interface)The CityLink NI (Network Interface) ports (NI-1 and NI-2) are used to connectthe Supervisory Unit of the Network Element to Supervisory Units of otherNetwork Elements. The NI ports on the front panel of the CityLink IDU areused to connect the Network Elements. The NI ports can be set to a varietyof different configurations.

The NI 2 port, in the CityLink Radio, can be Enabled only if the Ethernetfunction is Disabled, and vice versa.

The Communication Ports configuration sheet can be opened from theConfiguration context menu of the Equipment node in the Explorer view.Press the NI tab to view/change the NI settings. The sheet can also beinvoked by selecting (highlighting) the Equipment node in the Explorer viewand then selecting Edit Communication Ports from the Configurationmenu.

Figure IV-14 NI Tab in Communication Ports Configuration Sheet

Page 79: Citylink Manual RevD

B1089 Rev. D 79

IV C

onfig

urat

ion

Fields: Choices: Description:Enabled Enables the NI portFunction The functionality of the NI port.

The baud rate and stack aregrayed/whitened to indicate whichsettings are necessary for thedifferent functionalities.

CityLinkNL 29x NINL29x QxPDH SynchronousPDH AsynchronousV.11 contra dir masterV.11 contra dir slaveV.11 co dirQ1 V.11NL29x V.11 contradir slave

Baudrate The baud rate (symbols pr. second)of the NI port. If the field is grayed,no baud rate is necessary to set.

1200 to 200000 BaudStack

Nera NERA Stack.OSI OSI Stack

LAPD Data link layer for the QECC protocol.For more information refer to ITU-TG.784 and ITU-T Q.921.

Network side Server for the LAPD requests.User Side Client for the LAPD requests.

PPP: (Point to Point Protocol) Data linklayer for the TCP/IP protocol.(currently not implemented)

Active mode (currently not implemented)Demand dial (currently not implemented)Direct mode (currently not implemented)Passive mode (currently not implemented)

Page 80: Citylink Manual RevD

80 B1089 Rev. D

IV C

onfiguration

Fields: Choices: Description:Baudrate: 1200 - 115200 Baudrate. The default baudrate is 115200.

4.2.3 LCTThe LCT port is the serial port (RS-232) that can be used to communicate witha PC executing NEW-NMS. In this sheet the baud rate of the LCT port canbe changed.

WARNING!If you are communicating with the NE through the LCT (Serial) port and youchange the LCT baud rate you will loose contact with the NE until youconfigure the NEW-NMS communication settings to the same baud rate asthe NE baud rate.

The Communication Ports configuration sheet can be opened from theConfiguration context menu of the Equipment node in the Explorer view.Press the LCT tab to view/change the LCT settings. The sheet can also beinvoked by selecting (highlighting) the Equipment node in the Explorer viewand then selecting Edit Communication Ports from the Configurationmenu.

Figure IV-15 LCT Tab in Communication Ports Configuration Sheet

Page 81: Citylink Manual RevD

B1089 Rev. D 81

IV C

onfig

urat

ion

4.2.4 EthernetIn the CityLink Radio the Ethernet port can be Enabled only if the NI 2 portis Disabled, and vice versa. See chapter 4.2.2.

The Communication Ports configuration sheet can be opened from theConfiguration context menu of the Equipment node in the Explorer view.Press the Ethernet tab to view/change the Ethernet settings. The sheet canalso be invoked by selecting (highlighting) the Equipment node in theExplorer view and then selecting Edit Communication Ports from theConfiguration menu.

Fields: Choices: Description:Enabled Toggles Ethernet on/offStack Nera Nera Stack

OSI TP4 OSI StackTCP/IP TCP/IP Stack. Must be selected if IP

Tunneling is enabled.

Figure IV-16 Ethernet Tab in Communication Ports Configuration Sheet

Page 82: Citylink Manual RevD

82 B1089 Rev. D

IV C

onfiguration

4.2.5 IP SettingsThe IP Settings sheet lets you view the IP address of the NE and configurethe subnet mask and default gateway. The IP Address can be set in theElement Id property sheet.

Fields: Description:IP Address Shows the Internet Protocol (IP) address of the NE.Subnet Mask Type the Subnet Mask number obtained from your

network administrator. This number, combined with theIP address, identifies which network your NE is on.

Default Gateway For each adapter, type the correct IP address of thedefault gateway used for forwarding packets to othernetworks or subnets. This address should be providedby the network administrator and is required for nodeson internetworks. If this is not provided, IP functionalitywill be limited to the local subnet unless a route isspecified with the TCP/IP route command.

Figure IV-17 IP Settings Tab in Communication Ports Configuration Sheet

The Communication Ports configuration sheet can be opened from theConfiguration context menu of the Equipment node in the Explorer view.Press the IP Settings tab to view/change the NI settings. The sheet can alsobe invoked by selecting (highlighting) the Equipment node in the Explorerview and then selecting Edit Communication Ports from the Configura-tion menu.

Page 83: Citylink Manual RevD

B1089 Rev. D 83

IV C

onfig

urat

ion

4.2.6 IP TunnelingA connection can be set up between two NEs through another network,using the Internet Protocol. This is called IP Tunneling. Two connections,IP Tunnel 1 and IP Tunnel 2, can be configured. Ethernet must be enabledwith TCP/IP Stack in order to use IP tunnels. Internet Protocol (IP)- address,Section address and NE address are used for set up of IP tunnels to otherNEs. The IP tunnel must only be set up at one side of the tunnel.

The Communication Ports configuration sheet can be opened from theConfiguration context menu of the Equipment node in the Explorer view.Press the IP Tunneling tab to view/change the IP Tunneling settings. Thesheet can also be invoked by selecting (highlighting) the Equipment nodein the Explorer view and then selecting Edit Communication Ports fromthe Configuration menu.

Fields: Choices:Description:Enabled On/Off Toggles IP Tunneling on/off.Remote section address The section address of the NE addressed

through the IP tunnel.Remote NE address The NE address of the Network Element

addressed through the IP tunnel.Remote IP address The Internet Protocol (IP) address of the

NE addressed through the IP tunnel.

Figure IV-18 IP Tunneling Tab in Comm. Ports Configuration Sheet

Page 84: Citylink Manual RevD

84 B1089 Rev. D

IV C

onfiguration

4.2.7 OSI TP4 TunnelingA connection can be set up between two NEs through another network,using the OSI protocol. This is called OSI Tunneling. Two connections, OSITP4 Tunnel 1 and OSI TP4 Tunnel 2, can be configured. Ethernet must beenabled with OSI Stack in order to use OSI TP4 Tunneling.Network Service Access Point (NSAP)- address, Section address and NEaddress are used for set up of IP tunnels to other NEs.

The Communication Ports configuration sheet can be opened from theConfiguration context menu of the Equipment node in the Explorer view.Press the OSI TP4 Tunneling tab to view/change the OSI TP4 Tunnelingsettings. The sheet can also be invoked by selecting (highlighting) theEquipment node in the Explorer view and then selecting Edit Communi-cation Ports from the Configuration menu.

Fields: Choices: Description:Enabled: On/Off Toggles OSI Tunneling on/offRemote section address: Shows the section address of the NE

addressed though OSI TP4 TunnelRemote NE address: Shows the SU address of the NE

addressed though OSI TP4 TunnelRemote NSAP address: 0 to 20 bytes

Figure IV-19 OSI TP4 Tunneling Tab in Comm. Ports Configuration Sheet

Page 85: Citylink Manual RevD

B1089 Rev. D 85

IV C

onfig

urat

ion

4.3 LoopingThe loop settings are divided into four categories: Main traffic looping,2Mbit/s Wayside traffic looping, 64Kbit/s looping and IDU-Switch looping.Additional advanced loop settings are available for Nera users only.

4.3.1 Main LoopingThe Looping configuration sheet can be opened from the Configurationcontext menu of the Equipment node in the Explorer view. Press the Main tabto view/change the Main looping settings. The sheet can also be invokedby selecting (highlighting) the Equipment node in the Explorer view and thenselecting Edit Looping from the Configuration menu.

Actions:Loops can be toggled on/off by pressing the loop-buttons placed on top ofa schematic bitmap. Only one loop of the same category can be on at the time.

When a loop button is pressed, but no response from the NE is received, theloop button is blue. When a loop is confirmed on, it is colored red.

If the Looping configuration sheet is closed while a loop is active, the loopwill be terminated after 30 seconds.

Figure IV-20 Looping Configuration Sheet

Page 86: Citylink Manual RevD

86 B1089 Rev. D

IV C

onfiguration

The different main traffic loops : (Figure IV-20 describes the loops)

Baseband Loop (far end) - Outgoing line traffic to incoming line traffic. Baseband Loop (near end) - Incoming line traffic to outgoing line traffic. IF Loop IDU IF Loop Transceiver RF Loop Transceiver

Buttons:Close: Closes the property sheet.Help: Press this button to get help on the current property sheet page.

For help on an item, click at the top of the dialog box, then clickthe item.

Page 87: Citylink Manual RevD

B1089 Rev. D 87

IV C

onfig

urat

ion

4.3.2 64 Kbit/s LoopingThe Looping configuration sheet can be opened from the Configurationcontext menu of the Equipment node in the Explorer view. Press the 64 Kbit/s Looping tab to view/change the looping settings. The sheet can also beinvoked by selecting (highlighting) the Equipment node in the Explorer viewand then selecting Edit Looping from the Configuration menu.

Actions:Loops can be toggled on/off by pressing the loop-buttons placed on top ofa schematic bitmap. Only one loop of the same category can be on at the time.When a loop button is pressed, but no response from the NE is received, theloop button is blue. When a loop is confirmed on, it is colored red.If the Looping configuration sheet is closed while a loop is active, the loopwill be terminated after 30 seconds.

The different 64Kbit/s loops: (Figure IV-21 describes the loops)

64Kbit/s Channel 1 Loop (far end) 64Kbit/s Channel 1 Loop (near end) 64Kbit/s Channel 2 Loop (far end) 64Kbit/s Channel 2 Loop (near end)

Buttons:Close: Closes the property sheet.Help: Press this button to get help on the current property sheet page.

For help on an item, click at the top of the dialog box, then clickthe item.

Figure IV-21 Looping Configuration Sheet. 64kbit/s Tab

Page 88: Citylink Manual RevD

88 B1089 Rev. D

IV C

onfiguration

4.3.3 Wayside LoopingThe Looping configuration sheet can be opened from the Configurationcontext menu of the Equipment node in the Explorer view. Press the 2 Mbit/s Wayside tab to view/change the looping settings. The sheet can also beinvoked by selecting (highlighting) the Equipment node in the Explorer viewand then selecting Edit Looping from the Configuration menu.

Figure IV-22 Looping Configuration Sheet, Wayside Tab

Actions:Loops can be toggled on/off by pressing the loop-buttons placed on top ofa schematic bitmap. Only one loop of the same category can be on at the time.

When a loop button is pressed, but no response from the NE is received, theloop button is blue. When a loop is confirmed on, it is colored red.

If the Looping configuration sheet is closed while a loop is active, the loopwill be terminated after 30 seconds.

Page 89: Citylink Manual RevD

B1089 Rev. D 89

IV C

onfig

urat

ion

The different wayside loops : (Figure IV-22 describes the loops)

Wayside Loop (far end) Wayside Loop (near end)

A PRBS sequence can be inserted at the transmit end (TX) of the waysidechannel instead of the regular wayside traffic. A PRBS error counter is placedon the receive end (RX) of the wayside channel. This is a powerful way totest the quality of the radio connection. The PRBS used is a 215-1 maximum-length sequence.

Note that the direction of the Wayside channel (Line or Radio) can beconfigured in the 2 Mbit/s Wayside Channel property sheet. (See chapter4.4.3).

Additional fields for PRBS Settings:TX PRBS Insert: Inserts PRBS traffic into the wayside transmitter.

Modes: None, Not Inverted and Inverted.RX PRBS Counter: Enable the PRBS Counter at the RX end. Modes.

Modes: Disabled, Not Inverted and Inverted.RX PRBS Counter: Displays the current number of PRBS errors at the

wayside receive endRX PRBS Rate: Displays the current number of PRBS errors per

second at the wayside receive end.

Buttons:Reset: Resets the PRBS Counter (includes the PRBS Rate)Close: Closes the property sheet.Help: Press this button to get help on the current property sheet page.

For help on an item, click at the top of the dialog box, then clickthe item.

Page 90: Citylink Manual RevD

90 B1089 Rev. D

IV C

onfiguration

4.3.4 Advanced LoopingNera User OnlyThe Looping configuration sheet can be opened from the Configurationcontext menu of the Equipment node in the Explorer view. Press the AdvancedLooping tab to view/change the Main looping settings. The sheet can alsobe invoked by selecting (highlighting) the Equipment node in the Explorerview and then selecting Edit Looping from the Configuration menu.

Figure IV-23 Looping Configuration Sheet, Advanced Looping Tab

Actions:Loops can be toggled on/off by pressing the loop-buttons placed on top ofa schematic bitmap. Only one loop of the same category can be on at the time.When a loop button is pressed, but no response from the NE is received, theloop button is blue. When a loop is confirmed on, it is colored red.If the Looping configuration sheet is closed while a loop is active, the loopwill be terminated after 30 seconds.

The different SORP loops: (Figure IV-23 describes the loops)

Line RX SORP Line Transmit Output To Line Receive Input Loop Radio TX SORP Radio Receive Output To Radio Transmit Input Loop Radio RX SORP Radio Transmit Output To Radio Receive Input Loop Radio TX SORP Radio Receive Input To Radio Transmit Output Loop Radio RX FIR (Finite Impulse Response Filter) To VITERBI

Decoder Loop

Buttons:Close: Closes the property sheet.Help: Press this button to get help on the current property sheet page .For

help on an item, click at the top of the dialog box, then click the item.

Page 91: Citylink Manual RevD

B1089 Rev. D 91

IV C

onfig

urat

ion

4.3.5 CityLink IDU-Switch LoopingThe Looping configuration sheet can be opened from the Configurationcontext menu of the Equipment node in the Explorer view. Press the IDU-Switch Looping tab to view/change the Main looping settings. The sheetcan also be invoked by selecting (highlighting) the Equipment node in theExplorer view and then selecting Edit Looping from the Configurationmenu.

Figure IV-24 Looping Configuration Sheet, IDU-Switch Looping Tab

Actions:Loops can be toggled on/off by pressing the loop-buttons placed on top ofa schematic bitmap. Only one loop of the same category can be on at the time.When a loop button is pressed, but no response from the NE is received, theloop button is blue. When a loop is confirmed on, it is colored red.If the Looping configuration sheet is closed while a loop is active, the loopwill be terminated after 30 seconds.

The different IDU-Switch loops: (Figure IV-24 describes the loops)

CMI Loop 2Mbit/s Loop 2MHz Loop

Buttons:Close: Closes the property sheet.Help: Press this button to get help on the current property sheet page .For

help on an item, click at the top of the dialog box, then click the item.

Page 92: Citylink Manual RevD

92 B1089 Rev. D

IV C

onfiguration

4.4 In Door Unit (IDU)

4.4.1 IDU Production DataThe IDU production data property sheet shows the production serialnumbers and the production and test dates of the IDU. Only an administratorcan change the settings.This sheet is also used for calibrating the Optical Line interface. Calibrationis only needed when the optical unit is beginning to get old.

The IDU Production Data configuration sheet can be opened from theConfiguration context menu of the IDU node in the Explorer view. The sheetcan also be invoked by selecting (highlighting) the IDU node in the Explorerview and then selecting Edit Production Data from the Configurationmenu.

Figure IV-25 IDU Production Data Configuration Sheet

Page 93: Citylink Manual RevD

B1089 Rev. D 93

IV C

onfig

urat

ion

Fields: Description:Article Code: The Article CodeSerial No: The Serial number.HW Revision: Hardware revisionPurchase Order: The Purchase OrderMAC Address: The Media Access Control address of

the NE.Production Date: The date when the article was produced.Test Date: The date when the article was tested.FAT Date: The date when the Factory Acceptance

Test was found to be satisfactory.SAT Date: The date when the Site Acceptance Test

was found to be satisfactory.Laser calibration constant: Constant used in empirical relationship to

determine Laser Bias Out of Limitswarning, i.e. BIAS.

Laser threshold Current (mA): If the laser bias current exceeds this value,the Laser Bias Out of Limits warnining,i.e. BIAS is generated. A laser bias currentexceeding the threshold is a sign of ageand degradation.

64K G.703 present: Checked if the IDU contains hardware forthe G.703 64kbit/s channel. Note that thisfunction has to be software enabled inorder to be used. (See chapter 2.2,Available Functions)

SETS input present: Checked if the IDU contains hardware forthe SETS functionality. Note that thisfunction has to be software enabled inorder to be used. (See chapter 2.2,Available Functions)

Page 94: Citylink Manual RevD

94 B1089 Rev. D

IV C

onfiguration

4.4.2 64 kbit/s ChannelsTwo 64 kbit/s channels can be inserted into the SOH. Each of the 64 kbit/schannel will occupy one byte of the SOH frame. Press the SOH Frame buttonto select which bytes of the SOH that are used by the 64 kbit/s Channels.One channel is the V.1l. This channel has to be of type V.11 Contra. Theother is the G.703 Channel. This channel can be either G.703 Co or G.703Contra . Both channels can be retrieved from and inserted into the line andradio side independently.

The 64 kbit/s Channels configuration sheet can be opened from theConfiguration context menu of the IDU node in the Explorer view. The sheetcan also be invoked by selecting (highlighting) the IDU node in the Explorerview and then selecting Edit 64 kbit/s Channels from the Configurationmenu.

Figure IV-26 64 kbit/s Channels Configuration Sheet

Page 95: Citylink Manual RevD

B1089 Rev. D 95

IV C

onfig

urat

ion

Fields: Choices: Description

Status:Enabled Enables the 64 kbit/s Channel.Disabled Disables the 64 kbit/s Channel.

Type: Choose linecode for 64 kbit/s channel.V.11 Contra (Channel V.11)G.703 Co (Channel G.703)G.703 Contra (Channel G.703)

Direction: Choose the direction the 64 kbit/s Rx channelshould be extracted from.

Line 64 kbit/s Rx is inserted from line SOH frames.Radio 64 kbit/s Rx is inserted from radio SOH frames.

Timeslot: Shows which timeslot in the SOH the64 kbit/s Rx channel occupy.

Page 96: Citylink Manual RevD

96 B1089 Rev. D

IV C

onfiguration Fields: Options: Description:Status Enabled Enables the 2 Mbit/s Wayside Channel

Disabled Disables the 2 Mbit/s Wayside ChannelDirection Choose the direction the 2 Mbit/s Wayside

Rx channel should be extracted from.Line 2 Mbit/s Rx is extracted from line SOH

. Radio Rx is extracted from radio SOH.

4.4.3 2 Mbit/s Wayside ChannelA 2 Mbit/s channel can be inserted in the SOH in either line-direction or radio-direction. The 2 Mbit/s channel will occupy 33 bytes (32 bytes data + 1 bytealignment information) of the SOH. Press the SOH Frame button to viewwhich bytes of the SOH that are used by the 2 Mbit/s Wayside Channel.The 2 Mbit/s channel uses the Rx and Tx connection at the front panel of theIDU. Rx is received data and Tx is sent data.

The 2 Mbit/s Wayside configuration sheet can be opened from the Config-uration context menu of the IDU node in the Explorer view. The sheet can alsobe invoked by selecting (highlighting) the IDU node in the Explorer view and

then selecting Edit 2 Mbit/s Wayside from the Configuration menu.

Figure IV-272 Mbit/s Wayside Channel Configuration Sheet

Buttons: SOH Frame Press this button to view which timeslots in the SOH

the 2 Mbit/s channel occupies.

Page 97: Citylink Manual RevD

B1089 Rev. D 97

IV C

onfig

urat

ion

4.4.4 X-Connect(For advanced users)Two 64kbit/s (one SOH timeslot) cross-connections can be set up. Thecross-connections bypass the SORP so that the SOH time-slots are sent fromthe Line receive unit directly to the Radio transmit unit.

The X-Connect configuration sheet can be opened from the Configurationcontext menu of the IDU node in the Explorer view. The sheet can also beinvoked by selecting (highlighting) the IDU node in the Explorer view andthen selecting Edit X-Connect from the Configuration menu.

Figure IV-28X-Connect Configuration Sheet

Fields: Description:Enabled/Disabled Switches X-Connect on/offLine timeslot The time slot to bypass the SORP.Radio timeslot The destination time slot.

Page 98: Citylink Manual RevD

98 B1089 Rev. D

IV C

onfigurationFields: Choices: Description:Enabled/Disabled Toggles Pulse Output On/OffSource Only one source at a time.

FEC Radio The output pin reflects the FEC onthe Viterbi asic.

B1 Line The output pin reflects the B1 on theLine Receive side of the SORP.

B2 Line The output pin reflects the B2 on theLine Receive side of the SORP.

B1 Radio The output pin reflects the B1 on theRadio Receive side of the SORP.

B2 Radio The output pin reflects the B2 on theRadio Receive side of the SORP.

4.4.5 Pulse OutputFor test purposes.The SORP and Viterbi asics give pulses when they recognize errors. Thenumber of pulses per second is a measurement of the quality of the receivedsignals. These pulses can be sent out on the ALM/AUX port.

The Pulse Output configuration sheet can be opened from the Configurationcontext menu of the IDU node in the Explorer view. The sheet can also beinvoked by selecting (highlighting) the IDU node in the Explorer view andthen selecting Edit Pulse Output from the Configuration menu.

Figure IV-29Pulse Output Configuration Sheet

Page 99: Citylink Manual RevD

B1089 Rev. D 99

IV C

onfig

urat

ion

4.4.6 DiagnoseThe Diagnose function retrieves data about memory, boot errors andwarnings, boot version and number of resets of the SU of the NE. Press Getto retrieve the data from the NE. The diagnose tests are performed at IDUreset. (Note that the Viterbi decoder and SORP1 are only tested at cold reset)

The Diagnose configuration sheet can be opened from the Configurationcontext menu of the IDU node in the Explorer view. The sheet can also beinvoked by selecting (highlighting) the IDU node in the Explorer view andthen selecting Edit Diagnose from the Configuration menu.

Figure IV-30 Diagnose Configuration Sheet

Module Status CommentsCPLD OK/Not OK A write/read test sequence was performed

at last reset/startup.RTC OK/Low bat/ A write/read test sequence was performed

Not running at last reset/startup.LCD OK/Not OK A write/read test sequence was performed

at last reset/startup.DRAM OK/Not OK A write/read test sequence was performed

at last reset/startup.SRAM OK/Not OK A write/read test sequence was performed

at last reset/startup.Code FLASH OK/Not OK A write/read test sequence was performed

at last reset/startup.Boot FLASH OK/Not OK A write/read test sequence was performed

at last reset/startup.Viterbi Decoder OK/Not OK A write/read test sequence was performed

at last startup.SORP OK/Not OK A write/read test sequence was performed

at last startup.

Page 100: Citylink Manual RevD

100 B1089 Rev. D

IV C

onfiguration

4.4.7 Self TestThe Self Test function uses a two step procedure for testing the IDU. Thefirst test sets a CMI loop, while the second test sets an IF loop. For both loops,a PRBS is created in the SORP and errors are counted and synchronizationlosses are registered as the signal returns from the loops. Press Test to startthe Self Test.

WARNING !When performing a Self Test the STM-1 traffic will be destroyed.

The Self Test dialog box can be opened from the Configuration context menuof the IDU node in the Explorer view. The dialog box can also be invoked byselecting (highlighting) the IDU node in the Explorer view and then selectingEdit Self Test from the Configuration menu.

Figure IV-31 Selt Test Dialog Box

4.4.8 BER ThresholdsThe Viterbi decoder is a component using a Viterbi low complexity algorithmfor decoding/error correcting the received bit-sequence in the NE. TheViterbi error rate is used as a quality measurement for the radio hop.

When the Viterbi error rate exceeds certain values, alarms are generated. Thethreshold values decide when alarms are generated. The threshold valuescan be changed by the user.

Alarm Id Default value Alarm severityHBER Indicator for BER > 1e-3 MAJORLBER Indicator for LBER > 1e-6 MINOREW-BER Indicator for EW-BER > 1e-10 WARNING

Page 101: Citylink Manual RevD

B1089 Rev. D 101

IV C

onfig

urat

ionFields: Choices: Description:

HBER A Major alarm is generated when the Viterbierror rate exceeds the HBER threshold value.AIS is inserted when the HBER thresholdvalue is exceeded.

1.0·10-3 - 1.0·10-10 Error bit rateLBER A Minor alarm is generated when the Viterbi

error rate exceeds the LBER threshold value.1.0·10-3 - 1.0·10-11 Error bit rate

EW A Warning is generated when the Viterbierror rate exceeds the Error Warningthreshold value.

1.0·10-3 - 1.0·10-12 Error bit rate.

Figure IV-32BER Threshold Configuration Sheet

Internal proportions: HBER > LBER > EW

The BER Threshold configuration sheet can be opened from the Configu-ration context menu of the Radio node under the IDU node in the Explorer view.The sheet can also be invoked by selecting (highlighting) the Radio nodeunder the IDU node in the Explorer view and then selecting Edit BERThreshold from the Configuration menu.

Page 102: Citylink Manual RevD

102 B1089 Rev. D

IV C

onfiguration

Figure IV-33 Laser Control Configuration Sheet

4.4.9 Laser ControlThe optical port may or may not have implemented Automatic LaserShutdown (ALS). This is a function designed for eye safety purposes,according to ITU-T rec. G.958. When implemented, ALS may be enabled ordisabled.

When ALS is not implemented or enabled the laser must be turned on/offmanually.

When ALS is enabled, the laser automatically will restart after a waiting timeperiod (selectable), when having previously been turned off. (If the sectionof operation is not connected or Loss Of Optical Signal from far end isdetected, the laser will again be turned off after 2 sec.) The waiting period isby default set to 1 minute.

The Laser Control configuration sheet can be opened from the Configura-tion context menu of the Optical Line node under the IDU node in the Explorerview. The sheet can also be invoked by selecting (highlighting) the OpticalLine node under the IDU node in the Explorer view and then selecting Edit

Laser Control from the Configuration menu.

Page 103: Citylink Manual RevD

B1089 Rev. D 103

IV C

onfig

urat

ion

Fields: Buttons: Description:

ALS:Enabled/Disabled Toggles ALS On/OffWaiting Time (1.0 - 5.0 minutes ) Specifies waiting

time before the laser is turned on. Ifsection of operation is connectedand optical signal from far end ispresent, laser will remain on, if notlaser will be turned off after2 seconds.

Get Retrieves Laser Control settingsfrom NE.

Set Sets Laser Control settings to NE.Restart (2 Seconds) Manually restart the laser for

2 secondsRestart (90 Seconds)Manually restart the laser for 90

seconds for testing purposes

ManualControl: (ALS disabled or not implemented)

On Manually turn the laser onOff Manually turn the laser offStatus: Shows the status of the Laser Unit

Page 104: Citylink Manual RevD

104 B1089 Rev. D

IV C

onfiguration

4.5 Out Door Unit (ODU)

4.5.1 ODU Transceiver - Configuration FrequencyThe Duplex Distance between the Rx and Tx band is fixed. The user can setthe Tx frequency by clicking on the frequency slots. Since the duplexdistance is fixed the Rx frequency will be automatically set. The correspond-ing Tx and Rx frequency must be set in the opposite NE.

NEW NMS/Configurator receives the frequency plan from the NE. Whenno NE is connected (off-line), no frequency plan will be shown.

The output power is automatically muted when the frequency setting isexecuted.

The Frequency/Power configuration sheet can be opened from the Config-uration context menu of the ODU node in the Explorer view. The sheet canalso be invoked by selecting (highlighting) the ODU node in the Explorer viewand then selecting Edit Frequency from the Configuration menu.

Figure IV-34 Frequency/Power Configuration Sheet, Frequency Tab

Page 105: Citylink Manual RevD

B1089 Rev. D 105

IV C

onfig

urat

ion

Fields: Denomination:Description:Frequency plan Choose the wanted frequency plan.

The frequency plan must correspondto your tranceiver.

TX Frequency MHz The Tx Carrier frequencyRX Frequency MHz The Rx Carrier frequencyDuplex Distance MHz The distance between the Tx and the

Rx carrier frequency.Channel distance MHz The distance between the channels

in this frequency planModulation The modulation scheme used with

this frequency planTX Frequency Band, MHz Tx Lower sideband frequencyMin for this frequency planTX Frequency Band, MHz Tx Upper sideband frequencyMax for this frequency planRX Frequency Band, MHz Rx Lower sideband frequencyMin for this frequency planRX Frequency Band, MHz Rx Upper sideband frequencyMax for this frequency plan

••••• To change the settings:1. Get the current settings from the Network element by pressing Get.

(The settings are automatically retrieved from the NE when the property-sheet is opened).

2. Alter the settings by clicking the frequency band you want to transmityour Tx data. The Rx frequency is automatically updated since the duplexDistance is fixed.

3. Press Set to send the changes to the network element.A dialog box pops up. Press YES if you want to change the frequency onthe remote terminal

Buttons:Get: Press this button to retrieve the current settings from the NE.Set: Press this button to send the settings to the NE.Close: Closes the property sheet.Help: Press this button to get help on the current property sheet. For

help on an item, click at the top of the dialog box, then click theitem.

Page 106: Citylink Manual RevD

106 B1089 Rev. D

IV C

onfiguration

4.5.2 ODU Transceiver - Power ConfigurationThe Transceiver Power Configuration sheet lets the user set some OutputPower settings, some RF Input warning thresholds and ATPC settings.

ATPC (Automatic Transceiver Power Control) is a function for effectivelyreducing the interference probability in your network. The output powerfrom the transceiver is automatic controlled. If the regulation loop for theATPC stops functioning, an alarm is generated. This alarm can be delayed.

The output power should be muted when the frequency setting is changed.

The Power configuration sheet can be opened from the Configurationcontext menu of the ODU node in the Explorer view. The sheet can also beinvoked by selecting (highlighting) the ODU node in the Explorer view andthen selecting Edit Power from the Configuration menu.

Figure IV-35 Power Configuration Sheet

Page 107: Citylink Manual RevD

B1089 Rev. D 107

IV C

onfig

urat

ion

Fields: Denomination:Description:

Transceiver Type: Shows the frequency range of thetransceiver.

RF Input Level dBm The upper threshold value for whenWarning, High to generate an RF Input Level

Warning (Alarm no. 1504)

RF Input Level dBm The lower threshold value for whenWarning, Low to generate an RF Input Level

Warning (Alarm no. 1504)

ATPC Alarm Level dBm Set the Power Level to use when anATPC alarm occurs.

ATPC dBm The wanted input level when ATPCReference Level is activated.

Mute output power Mutes the output power. No outputpower is sent.

Maximum dBm Maximum output power forOutput Power transmitting

Manual dBm The output power level used whenOutput Level ATPC is not activated

ATPC Status ATPC Disabled/ Enabled

ATPC mode ATPC can operate in four different modes:Automatic Regulation: The trans-ceiver automatically regulates thetransmitter powerMinimum Output: A min. amount ofpower is used for transmitting.Maximum Output: A max. amount ofpower is used for transmitting.Freeze Output Power: A fixed amountof power is used for transmitting.

ATPC alarm delay seconds The ATPC alarm can be delayed from1 to 15 seconds.

Page 108: Citylink Manual RevD

108 B1089 Rev. D

IV C

onfiguration

4.5.3 ODU Production DataThe ODU production data property sheet shows the production serialnumbers and the production and test dates of the ODU. Only an administra-tor can change the settings.

The ODU Production Data configuration sheet can be opened from theConfiguration context menu of the ODU node in the Explorer view. The sheetcan also be invoked by selecting (highlighting) the ODU node in the Explorerview and then selecting Edit Production Data from the Configurationmenu.

Figure IV-36ODU Production Data Configuration Sheet

Fields: Description:Article Code: The Article CodeSerial No: The Serial number.HW Revision: Hardware revisionPurchase Order: The Purchase OrderProduction Date: The date when the article was produced.Test Date: The date when the article was tested.FAT Date: The date when the Factory Acceptance Test was

found to be satisfactory.SAT Date: The date when the Site Acceptance Test was found

to be satisfactory.

Page 109: Citylink Manual RevD

B1089 Rev. D 109

IV C

onfig

urat

ion

Figure IV-37 Antenna Configuration Sheet

4.5.4 Antenna DataThis sheet shows some main characteristics of the antenna. Only theAntenna code can be altered. The antenna data are stored in a database file.

The Antenna Data configuration sheet can be opened from the Configura-tion context menu of the Antenna node in the Explorer view. The sheet canalso be invoked by selecting (highlighting) the Antenna node in the Explorerview and then selecting Edit Antenna from the Configuration menu.

Fields: Description:Antenna code The antenna code.

Page 110: Citylink Manual RevD

110 B1089 Rev. D

IV C

onfiguration

5.0 Hot Standby

5.1 GeneralHot Standby systems on CityLink consists of two InDoor Units connectedto an IDU-Switch and two OutDoor Units connected to the same branchingunit. The branching unit has an RF-switch in the Tx direction.The two IDUs with the connected ODUs are independent systems. In theNEW-NMS the two systems will appear as one Network Element with oneTransmission- and one Equipment node. If NEW-NMS has contact with bothNEs, the equipment node will have two IDU nodes, two ODU nodes and anIDU-Switch node. The Transmission node will have two Channels.

Figure IV-38 Hot Standby Explorer view

If NEW only has contact with one HSB NE, one can experience that only partof the tree is built. If this happens, check the Network Configuration of thesystem.

Page 111: Citylink Manual RevD

B1089 Rev. D 111

IV C

onfig

urat

ion

5.1 5.1.1 The Element Node ConfigurationThe element node configurations will be different for the two HSB NetworkElements. If NEW has contact with both NEs, the configuration sheets forthe Element node will have one page for each HSB NE. An example of thisis the Notification Mask configuration sheet.

Figure IV-39 Notification Mask

The settings will be collected from both NEs. If the settings are changed andset, the set message are sent to both NEs with data according to therespective pages.

Page 112: Citylink Manual RevD

112 B1089 Rev. D

IV C

onfiguration

5.1.2 The Equipment Node ConfigurationOn the Equipment node the configuration sheets consist of several pages.In the configuration menu for this node, there is one menu Item for each NE.If only one NE is connected the menu item for the other NE is disabled.

Figure IV-40 The Equipment Node Context Menu

5.1.2.1 The Looping ConfigurationWhen opening the Looping Sheet on a HSB NE, the pages for main, waysideand 64Kbit looping will apply for both IDUs. If a loop is set on the IDU andthe system switches, the signal will still be looped.

Page 113: Citylink Manual RevD

B1089 Rev. D 113

IV C

onfig

urat

ion

5.2 Combining the HSB ElementsIf the two Network Elements in a Hot Standby system are not configured asHot Standby, these NEs need to be configured as HSB. To do this open theElement Id configuration sheet, mark the Hot Standby checkbox. At thismoment the Combine Hot Standby Elements dialog box should appear.

Figure IV-41 Combine Hot Standby Elements Dialog Box

The name of the current element will be shown in the NE A textbox, andbefore the configuration is set the corresponding NE B has to be chosenin the NE B combo-box.Press the OK-button and the new configuration will be set.After approximately 30 seconds the two NEs will merge into one Hot StandbyNE.

Page 114: Citylink Manual RevD

114 B1089 Rev. D

IV C

onfiguration

5.3 Hot Standby Element IDThe CityLink Element Id property sheet shows some main information aboutthe Network Element like name, type, serial number and different addresses.The fields with white background can be altered by users with proper userprivileges. The gray fields are non-editable.

The Element Id configuration sheet can be opened from the Configurationcontext menu of the Element node in the Explorer view. The sheet can alsobe invoked by selecting (highlighting) the Element node in the Explorer viewand then selecting Edit Element Id from the Configuration menu.

For a Hot Standby system the Name, Section address, NE address and HotStandby part of the Element Id configuration is common for the two HSB NEs.Hence this is put in a single page called Common.

The data on this page is set in both NEs.

Figure IV-42 Common Tab in Element ID Configuration Sheet

Page 115: Citylink Manual RevD

B1089 Rev. D 115

IV C

onfig

urat

ion

The rest of the information in the Element Id configuration is unique to therespective NEs. Hence this information is displayed in two pages and thedata is collected / set in the respective NEs.

Figure IV-43 NE A Tab in Element ID Configuration Sheet

Fields: DescriptionSerial Number: The serial number of the NE (not nditable).NE Type: The type of NE (not editable).Name: The name of the NE (max. 32 characters).Section Address:The section address of the NE (1-254).NE Address: The Network Element address (1-128).

Used for identification of NEs within a section.MAC Address: The Media Access Control address of the NE

(not editable).NSAP Address: The Network Service Access Point address of the NE,

used for OSI-Management.IP Address: The Internet Protocol address of the NE.

Page 116: Citylink Manual RevD

116 B1089 Rev. D

IV C

onfiguration

To change the settings:1 Get the current settings from the NE by pressing Get. (The settings are

automatically retrieved from the NE when the property-sheet is opened)2 Alter the settings you want to change.3 Press Set to send the changes to the NE.

Buttons:Get: Press this button to retrieve the current settings from the NE.Set: Press this button to send the settings to the NE.Close: Closes the property sheet.Help: Press this button to get help on the current property sheet. For help

on an item, click at the top of the dialog box, then click the item.

5.3.1 Splitting a Hot Standby SystemIf a hot standby system is to be reconfigured into a standard CityLink system,uncheck the Hot Standby checkbox on the common page and press Set. TheSplit Hot Standby Elements dialog will now appear. Choose a new addressfor at least one of the NEs, and press OK.

After approximately 30 seconds the two NEs will be split into two standardCityLink NEs.

Figure IV-44 Split Hot Standby Elements Dialog Box

Page 117: Citylink Manual RevD

B1089 Rev. D 117

IV C

onfig

urat

ion

5.4 Switching CriteriaThe Hot Standby system operates in two modes, manual and automatic.In manual mode the Rx-switch and the Tx-switch are controlled by NEW. Noalarms in the system will cause the system to switch. The system is switchingthe Rx-switch and the Tx-switch at the same time (bidirectional).In automatic mode the switching is based on alarms in the system. Inautomatic mode the Rx-switch and Tx-switch can operate either bidirectionalor unidirectional.

Unidirectional mode: The system will only switch the transmission directionwhere the alarm has occured.

Bidirectional mode: The system will switch in both directions when an alarmoccurs. The traffic will go through the same IDU and ODU in both directions.Hence, the other IDU or ODU can be removed without disturbing traffic.Exception: When an alarm occurs in IDU-A, the system tries to switch to IDU-B/ODU-B. If ODU-Bis not able to take over the traffic, the system will thentry to keep the traffic running by only switching to IDU-B and continue usingODU-A. The system has switched to unidirectional mode to try to keep thetraffic running. The system will resume bidirectional mode next time an alarmoccurs.

Switching criteria in receive direction:• RF-INPUT The RF input signal is missing (ODU)• LO Local oscillator alarm (ODU)• IF-DEM Loss of incoming 140MHz IF to demodulator (IDU)• LOF Loss of frame (i.e. sync loss in demodulator) (IDU)• HBER User defined bit error threshold.• LT-PLL Line Transmit PLL alarm (IDU)• ACCESSORY

CONTROL Cable removed between IDU and IDUSwitch• Loss of comunications between IDU and IDU-Switch for more then

30 s.

Switching criteria in transmit direction:• RF-OUT RF output power alarm (ODU)• LO Local oscillator alarm (ODU)• IF-INP Loss of 350 MHz IF input to transceiver (ODU)• IF-MOD Loss of IF output from modulator (IDU)• LOF-LR Loss of frame at STM-1 input signal to IDU• LOS-LR Loss of STM-1 input signal to IDU• RT-PLL Radio Transmit PLL alarm (IDU)• TRELLIS PLL Trellis coder out of lock

Page 118: Citylink Manual RevD

118 B1089 Rev. D

IV C

onfiguration

5.5 Hot Standby ConfigurationThe Hot Standby configuration sheet shows the switching configurationsfor the IDU-Switch.

The Hot Standby configuration sheet can be opened from the Configurationcontext menu of the IDU-Switch node in the Explorer view. The sheet can alsobe invoked by selecting (highlighting) the IDU-Switch node in the Explorerview and then selecting Edit Hot Standby from the Configuration menu.

Figure IV-45 Hot Standby Configuration Sheet

Fields: Description:

Auto / manual: Auto or Manual hot standby switching

Switching mode: In Bidirectional mode, both Tx and Rx direction switchesat the same time. In Unidirectional mode, Tx and Rx canswitch independent of each other.Switching mode is available in Auto only. In Manual themode is always Bidirectional.

Active channel: Set which channel is active.Active Channel is available in Manual only

Page 119: Citylink Manual RevD

B1089 Rev. D 119

IV C

onfig

urat

ion

Fields: Description:

Status: The status of the IDU-Switch received from Both NEsIf Status Is Not Available, NEW did not receive themessage from this NE.Attribute Description StatusODU Describes which ODU ODU A ActiveSwitch Status is used as transmitter ODU B Active

IDU Describes which IDU IDU A ActiveSwitch Status is used as receiver IDU B Active

Status NE A Data OK when configur- Data OKation has been confirmed Data Not OKfrom the IDU-Switch andTransceiver

ODU A Status received from OKTransceiver transceiver Not OKStatus

ODU A Status on alarms related No AlarmsAlarms to switching in the Alarms present

IDU A Status received from IDU OKSwitch Status received from IDU- Not OKStatus Switch

IDU A Alarms Status on alarms related No Alarmsto switching in the IDU Alarms present

Status on NE B is the same as above for messages receivedfrom NE B.

Buttons:Get: Press this button to retrieve the current settings from the NE.Set: Press this button to send the settings to the NE.Close: Closes the property sheet without saving or setting any data.Help: Press this button to get help on the current property sheet. For

help on an item, click at the top of the dialog box, then click theitem.

Page 120: Citylink Manual RevD

120 B1089 Rev. D

IV C

onfiguration

5.6 CityLink IDU-Switch Production Data - Main CardThe IDU-Switch production data property sheet shows the production serialnumbers and the production and test dates of the IDU-Switch. Only anadministrator can change the settings.This sheet also is used for calibrating the Optical Line interface. Calibrationis only done when the optical unit is beginning to get old.The IDU-Switch Production Data configuration sheet can be opened fromthe Configuration context menu of the IDU-Switch node in the Explorer view.The sheet can also be invoked by selecting (highlighting) the IDU node inthe Explorer view and then selecting Edit Production Data from theConfiguration menu.

Figure IV-46 IDU-Switch Production Data Configuration Sheet

Page 121: Citylink Manual RevD

B1089 Rev. D 121

IV C

onfig

urat

ion

Fields: Description:Article Code: The Article CodeSerial No: The Serial number.HW Revision: Hardware revisionSales Order: The Purchase OrderProduction Date:The date when the article was produced.Test Date: The date when the article was tested.FAT Date: The date when the Factory Acceptance Test was found

to be satisfactory.SAT Date: The date when the Site Acceptance Test was found to be

satisfactory.Laser calibration Constant used for calibrating the laser. Default value is 47.constant:Laser threshold If the laser bias current exceeds this value, the opticalCurrent (mA): interface’s “BIAS” alarm is generated. A laser bias current

exceeding the threshold is a sign of age and degradation.

To change the settings (Only an administrator can change the settings):1. Get the current settings from the NE by pressing Get. (The settings

are automatically retrieved from the NE when the property-sheet isopened).

2. Alter the settings you want to change.3. Press Set to send the changes to the network element.

Buttons:Get: Press this button to retrieve the current settings from the NE.Set: Press this button to send the settings to the NE.Close: Closes the property sheet.Help: Press this button to get help on the current property sheet. For help

on an item, click bmc bitmaps\question_mark.bmp at the top ofthe dialog box, then click the item.

Page 122: Citylink Manual RevD

122 B1089 Rev. D

IV C

onfiguration

5.7 Replacing UnitsSet system in manual mode before removing either IDU or ODU.

Page 123: Citylink Manual RevD

B1089 Rev. D 123

V T

roub

le S

hoot

ing

Trouble Shooting

SECTION v

Page 124: Citylink Manual RevD

124 B1089 Rev. D

V T

rouble Shooting

1.0 General

2.0 Troubleshooting by means ofLEDs and Display

Some information is available to the user from the 16x2 lines Liquid CrystalDisplay and the four alarm LEDs, all located at the right side of the IDU frontpanel. The LCD display is not intended to give detailed information aboutthe system, but will enable the user to quickly, and without the need of a PC,get the alarm status.

If an alarm LED is lit, use the keypads & display to see the active specificalarm. See alarm list in Appendix III for corrective actions.

There are three fatal errors that will prevent the IDU from starting the softwareafter performing self test:

No legal Application SW.The message “No Legal SW Please download” will be displayed inthe LCD. To correct this error download new application SW

DIMM module not mounted, or not working.The message “Errors During Boot: DRAM DIMM” will be displayedon the LCD. To correct this error remove power and check if DIMM ismounted correctly.

SIMM module not mounted or not working.The message “Errors During Boot: CODE SIMM” will be displayedon the LCD. To correct this error remove power and check if SIMM ismounted correctly

N E R A C i t y L i n k N o A l a r m s L

ABC

CriticalMajor/minor

Power onWarning

HOME

Figure V-1 LEDs Keypad and Display

Page 125: Citylink Manual RevD

B1089 Rev. D 125

V T

roub

le S

hoot

ing

2.1 Description of Alarm LEDsThe functions of the four alarm LEDs are as follows:

CRITICAL Red Will be activated when one or morecritical alarms are activated

MAJOR/MINOR Red Will be activated when one or moremajor or minor alarms are activated

WARNING Orange Will be activated when one or morewarnings are activated

POWER ON Green Will be on when main power is > 36V

2.2 Use of Keypad and DisplayThe Menu tree is organised as shown in fig V-4. Five menus are available:

Home menu. Levels menu Alarms menu (only displayed if active alarms.) Set men At Work menu LCD Contrast menu SU and Section addresses

The up and down arrow keys are used for moving from one menu to another.

HOME

Figure V-2 Use of Keypad.

Used for returning to the top menu.

Used for displaying previous / next menu item.In the LCD Contrast menu, the keys are used forincrementing / decrementing the LCD contrast.

In Alarm Menu:Used for toggling between Local and Remote side.Press for more than 1sec. to display alarm ID number.

In Set Men At Work Menu:Used for toggling the MEN_AT_WORK alarm on/off.

In LCD CONTRAST Menu:Used for toggling the function of the up/down keys.Either Menu or Adjust

Page 126: Citylink Manual RevD

126 B1089 Rev. D

V T

rouble Shooting

Home Menu:The top menu, or home menu will display the current alarm status. This menucan be accessed at any time by pressing the HOME key. The HOME menuwill always be activated 5 minutes after last key was pressed.

Levels Menu:The levels menu will be used for displaying the Rx and Tx levels of the ODU.

Alarms menu.Used for displaying status of the filtered alarms. This menu will only beavailable if there are active alarms. The alarms displayed on the display aresorted by critical alarms first followed by major, minor and warnings.

Set Men At Work menu.Used for setting or resetting the MEN_AT_WORK alarm. The alarm statuscan be toggled by the left/right key.

LCD Contrast menu.Used for adjusting the LCD contrast. Adjusting the LCD contrast can behelpful for changing the best viewing angle of the LCD. To change thecontrast while in the LCD Contrast menu, select the adjust mode by pressingthe left/right key. When the second line of the display displays "Adjust ", theup and down keys can be used for increasing and decreasing the contrast.

Reset µProcessor:

Press the HOME key and the UP-ARROW ( ) simultanously until thedisplay indicates that the microprocessor has been reset (approx. 3 seconds).

R a d i o T x I f C L R T _ P L L 1

Alarm Node name

Alarm Severity, one of:C - CriticalM - Majorm - MinorW - Warning

Alarm name.By depressing the Left/rightkey more than 1s the alarmID will be displayed.

Alarm status:0 - Alarm is off.1 - Alarm is on.

Local(L) or Remote(R) side of the Radio. Togled by the lefth/right key

Figure V-3 Display messages and use of Keypad.

Page 127: Citylink Manual RevD

B1089 Rev. D 127

V T

roub

le S

hoot

ing

N E R A C i t y L i n k N o A l a r m s L

T x L e v e l xxxdBmR x L e v e l xxxdBm

S e t M e n A t W o r kO F F

L C D C o n t r a s tM e n u

If pressedmore than 1s, or no alarms.

Last active alarm, if any

From any menu

If pressedmore than 1s,or no alarms

First active alarm, if any

SU address: xxxSec address: xxx

Figure V-4 The Menu Tree and Keypad/Display use.

2.3 Other alarms that will be shown onthe LEDs on the IDU-SwitchDROP-IN+48VBELOW+3.3VBELOW+5VBELOW+12VBELOW-5VTX-OUTLASER-OFFBIAS

For further details; see Appendix III Alarm List & Alarm Description

Page 128: Citylink Manual RevD

128 B1089 Rev. D

V T

rouble Shooting

3.0 Troubleshooting by NEW-NMS Configurator

3.1 IntroductionFault management is the process of locating and correcting network prob-lems or faults. Fault management is possibly the most important task innetwork management. It consists of identifying the occurrence of a fault,isolating the cause of the fault and correcting it if possible. The faultmanagement increases the network reliability by giving the network operatora tool that quickly detects problems and initiates recovery procedures.

NEW contains functions for acquisition, presentation and storage of alarmsand events from the network to be managed.

3.2 Information AcquisitionIn order to detect faults, information must be gathered from the network. Thestate of the network is monitored using two different methods.

3.2.1 PollingThe various network elements should be polled on a regular basis, so thatchanges in Network Elements (NE) are detected and network connectivityis checked. Which NE to poll, the polling rate and what to be polled for aspecific NE is user definable.

3.2.2 Event NotificationIn addition to polling, some NEs have the ability to spontaneously reportevents. The NEW will gather this information in addition to polling. Thisfeature will decrease the managers response time to network events consid-erably.

Page 129: Citylink Manual RevD

B1089 Rev. D 129

V T

roub

le S

hoot

ing

3.3 Alarm PresentationIn all views, where network information is presented, colors are used toindicate the alarm severity status of the network elements. To easily identifythe status of the network elements, all alarms are classified according to theirseverity. Each alarm severity class has a color. In the different views, thenetwork elements change colors according to the color of their most severealarm. The alarm classifications are described in the table below.

Severity Colour Description(default)

Normal Green No alarms or warning have been reported fromthe network element

Warning Yellow Indicates the detection of a potential orimpending service-affecting fault, before anysignificant affects have been felt. Action shouldbe taken to further diagnose and correct theproblem in order to prevent it from becoming amore serious service-affecting fault.

Minor alarm Dark Yellow Indicates the existence of a non-service-affecting fault condition and that correctiveaction should be taken in order to prevent amore serious fault.

Major alarm Orange Signifies that a service-affecting conditionhas occurred and urgent corrective action isrequired.

Critical alarm Red The most severe alarm. It signifies that aservice-affecting condition has occurred andan immediate corrective action is required.

No contact Blue Indicates that no contact is achieved with thenetwork element. The communication settingsshould be checked in order to obtain contactwith the element.

Misconfigured Magenta The network element has not been properlyconfigured.

3.4 Visual Alarm NotificationThere are four different ways of monitoring alarms in NEW. These methodsare described in the following subchapters. The NEW context sensitive helpsystem offers a more comprehensive support on all features in the NEWprogram.

ytireveS roloC)tluafed(

noitpircseD

lamroN neerG morfdetroperneebevahgninrawrosmralaoNtnemelekrowteneht

gninraW wolleY gnidnepmirolaitnetopafonoitcetedehtsetacidnItnacifingisynaerofeb,tluafgnitceffa-ecivres

otnekatebdluohsnoitcA.tlefneebevahstceffaredronimelborpehttcerrocdnaesongaidrehtruf

suoireseromagnimocebmorftitneverpot.tluafgnitceffa-ecivres

mralaroniM wolleYkraD gnitceffaecivres-nonafoecnetsixeehtsetacidnIebdluohsnoitcaevitcerroctahtdnanoitidnoctluaf

.tluafsuoireseromatneverpotredroninekat

mralarojaM egnarO sahnoitidnocgnitceffaecivresatahtseifingiS.deriuqersinoitcaevitcerroctnegrudnaderrucco

mralalacitirC deR ecivresatahtseifingistI.mralaerevestsomehTetaidemminadnaderruccosahnoitidnocgnitceffa

.deriuqersinoitcaevitcerroc

tcatnocoN eulB ehthtiwdeveihcasitcatnocontahtsetacidnIsgnittesnoitacinummocehT.tnemelekrowten

htiwtcatnocniatbootredronidekcehcebdluohs.tnemeleeht

derugifnocsiM atnegaM ylreporpneebtonsahtnemelekrowtenehT.derugifnoc

Page 130: Citylink Manual RevD

130 B1089 Rev. D

V T

rouble Shooting

3.4.1 Alarms on a Tree node/leaf in the Explorer viewThe Explorer View is opened by selecting Explore Net from the View Menu.Figure V-5 shows an example of the Explorer view.

The Explorer View shows the Network information in a logical manner. EachNE is divided into two main branches; A Transmission branch and anEquipment branch. The sub-branches and leaves under the Transmissionsbranch concern the transmission aspects of the NE. The sub-branches andleaves under the Equipment branch concern the physical equipment of theNE.

Figure V-5 Example of Explorer View

The Explorer view use the severity colours to indicate alarm events. Thealarms are presented in a hierarchical manner. The colour of the most severealarm is inherited from the leaf where the alarm was identified, to all branchleaves up to the section symbol. E.g. the section and NE symbols will alwaysshow the alarm colour of the most severe alarm identified in the sub-branchesin the Explorer view.

Page 131: Citylink Manual RevD

B1089 Rev. D 131

V T

roub

le S

hoot

ing

By pressing the right mouse button on any nodes/leaves in the Explorer Viewand selecting Current Alarms from the context menu, a Current Alarm List(ref. Appendix III) is opened showing all alarms Hierarchical below theselected leaf.

3.4.2 Alarms on a Node symbol in the Map viewThe Map View is opened by selecting Map Navigator from the View Menu.Follow the instructions in the Help file to create a map. Figure V-6 shows anexample of the view.

The Map View shows the Network information in a physical manner. EachNE is showed as an NE icon. Graphic-files can be added as backgroundimages in the view. NE icons grouped together with bindings form networks.The NE icons change their severity colours according to the current mostsevere alarm of the NE.

Figure V-6 Example of Map View

By pressing the right mouse button on a NE icon in the Map View andselecting Alarms from the context menu, a Current Alarm List (ref. AppendixIII) is opened showing all alarms of the NE.

Page 132: Citylink Manual RevD

132 B1089 Rev. D

V T

rouble Shooting

3.4.3 Alarms on a Block component inthe Physical/ Schematic viewA Block Schematic presentation of CityLink IDU and ODU can be openedby selecting Physical View from the context menu in the map view. APhysical view of the IDU and ODU will appear in a window (Figure V-7). Thecolor of the border around the IDU and the ODU reflects the most severealarm event of the units.

Figure V-7 CityLink Physical view

Page 133: Citylink Manual RevD

B1089 Rev. D 133

V T

roub

le S

hoot

ing

By double-clicking either the IDU or the ODU block schematic views (FigureV-8) of the units appear.

Figure V-8 Schematic views of CityLink ODU & IDU

The colors of the blocks reflect the most severe alarm identified in thedifferent parts of the units. This makes the schematic views a very powerfultool for identifying the locations of alarms.

Page 134: Citylink Manual RevD

134 B1089 Rev. D

V T

rouble Shooting

3.4.4 Viewing Alarms in the Current Alarms ViewThe Current Alarm View can be opened by selecting Current Alarms fromthe Fault Menu. Figure V-9 shows an example of the Current Alarms List.Each alarm is listed as a row in the list as shown in Table V-1.

The Current Alarms List can also be opened from both the Explorer Viewand the Map View by selecting Current Alarms from the right-mouse-button-click context menu. The filter is then automatically set up to showonly the alarms hierarchically below the node/leaf the alarm list was openedfrom.

Figure V-9 Example of Current Alarms

Different Fields DescriptionSeverity The severity of the alarmAlarm text A short description of the alarmNode The name of the node where the alarm occurred

sdleiFtnereffiD noitpircseD

ytireveS mralaehtfoytirevesehT

txetmralA mralaehtfonoitpircsedtrohsA

edoN derruccomralaehterehwedonehtfoemanehT

Table V-1 Fields in the Current Alarms List

Alarms can also be logged to files. Consult the NEW NMS Manual or theNEW NMS Help system for further information.

Page 135: Citylink Manual RevD

B1089 Rev. D 135

V T

roub

le S

hoot

ing

4.0 Cable FaultIf a cable fault is indicated, it indicates that microprocessor communicationsbetween the IDU and ODU have failed. The fault is most probably with thecable connection. It may be open or shorted. Disconnect the cable connec-tion to the IDU and leave the connection to the ODU connected. Measurethe DC cable resistance between the centre pin and the outer of the N-typeconnector terminating the cable by means of a multi-meter.

If resistance is in the order of some hundreds kΩΩΩΩΩ to a few MΩΩΩΩΩ:Probably no cable fault.Replace IDU or ODU, one at the time. If alarm persists, swap the replacedunit for the original and replace the other unit.

If resistance is less than some hundreds kΩΩΩΩΩ:Probably cable or connector damage. Check the cable and connectors atboth ends for defects or for reasons that would cause the problem. Remeas-ure DC resistance, now with both cable ends disconnected. The resistanceshould be “open circuit” and if not replace the entire cable run, terminatingwith new N-type connectors.

If resistance is immeasurable (high impedance):Typically reasons are connectors not terminated correctly or cable cut.Check the cable and connectors at both ends for defects or for reasons thatwould cause the problem. Remeasure DC resistance, with the outer end stillconnected to the ODU. If still immeasurable impedance, replace the entirecable run, terminating with new N-type connectors.

Page 136: Citylink Manual RevD

136 B1089 Rev. D

V T

rouble Shooting

This page is intentionally left blank

Page 137: Citylink Manual RevD

B1089 Rev. D 137

VI A

ppen

dice

s

Appendices

SECTION VI

Page 138: Citylink Manual RevD

138B

1089 Rev. D

VI Appendices

Appendix I:

IDU

Interface Description

POWERConnector : PO WER D-SUB 2-PINCable : UWMK3101

LAN (AUI)Connector : D-SUB 15-PIN FEMALECable : UWMK3092

LAN (TP)Connector : RJ45 8-PINCable : Off the shelf TP cable

NETWORK INTERFACE (RS485)Connector : D-SUB 9-PIN FEMALECable : UWMK3078 , UWMK3079

64KBIT/S SERVICE CHANNEL (G.703)Connector : RJ45 8-PINCable : UWMK3077

LOCAL CRAFT TERMINAL (RS232)Connector : D-SUB 9-PIN MALECable : UWMK3123

2MHz SYNCHRONISATION (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable (1+0) : UWMH3080Cable (HSB): UWMH3242

2Mb/s WAYSIDE (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable (1+0) : UWMH3080Cable (HSB): UWMH3242

155Mb/s STM-1 (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable (1+0): UWMH3080Cable (HSB): UWMH3242

CHASSISGROUND

ODU INTERFACEN-TYPE FEMALE

ALARM & AUXILLARY FUNCTIONSConnector : D-SUB 25-PINCable (1+0): UWMK3076Cable (HSB): UWMH3187 & UWMK3076

FUSE1.0 A SLOW-BLOW

64KBIT/S SERVICE CHANNEL (V.11)Connector : RJ45 8-PINCable : UWMK3077

Fig

ure

VI-1

: CityL

ink ID

U w

ith E

lectrica

l ST

M-1

Inte

rface

Page 139: Citylink Manual RevD

B1089 R

ev. D139

VI Appendices

POWERConnector : POWER D-SUB 2-PINCable : UWMK3101

LAN (AUI)Connector : D-SUB 15-PIN FEMALECable : UWMK3092

LAN (TP)Connector : RJ45 8-PINCable : Off the shelf TP cable

NETWORK INTERFACE (RS485)Connector : D-SUB 9-PIN FEMALECable : UWMK3078 , UWMK3079

64KBIT/S SERVICE CHANNEL (G.703)Connector : RJ45 8-PINCable : UWMK3077

LOCAL CRAFT TERMINAL (RS232)Connector : D-SUB 9-PIN MALECable : UWMK3123

CHASSISGROUND

ODU INTERFACEN-TYPE FEMALE

ALARM & AUXILLARY FUNCTIONSConnector : D-SUB 25-PINCable (1+0): UWMK3076Cable (HSB): UWMH3187 & UWMK3076

FUSE1.0 A SLOW-BLOW

64KBIT/S SERVICE CHANNEL (V.11)Connector : RJ45 8-PINCable : UWMK3077

2MHz SYNCHRONISATION (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable (1+0) : UWMH3080Cable (HSB): UWMH3242

2Mb/s WAYSIDE (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable (1+0) : UWMH3080Cable (HSB): UWMH3242

155Mb/s STM-1 (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable (1+0): UWMH3080Cable (HSB): UWMH3242

Fig

ure

VI-2

: CityL

ink ID

U w

ith O

ptica

l ST

M-1

Inte

rface

Page 140: Citylink Manual RevD

140B

1089 Rev. D

VI Appendices

Fig

ure

VI-3

: Ho

t Sta

nd

by ID

U S

witch

with

Ele

ctrical S

TM

-1 In

terfa

ce

POWERConnector : POWER D-SUB 2-PINCable : UWMK3101

ACCESSORY CONTROLConnector : RJ45 8-PIN Cable : UWMK3187

64KBIT/S SERVICE CHANNEL (G.703)Connector : RJ45 8-PINCable : UWMK3243

PHONEConnector : 4-PIN Cable : Off the shelf handset cable

2MHz SYNCHRONISATION (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3242

155Mb/s STM-1 (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3080

155Mb/s STM-1 (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3242

CHASSISGROUND

SVCE INTFCConnector : D-SUB 15-PIN (female)Cable : UWMK3244

FUSE 0.5 ASLOW-BLOW

64KBIT/S SERVICE CHANNEL (G.703)Connector : RJ45 8-PINCable : UWMK3243

2MHz SYNCHRONISATION (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3080

2MHz WAYSIDE (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3080

2MHz WAYSIDE (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3242

CRITICALMAJORMINORWARNINGPOWER ON

A

B

C

STM-12Mb/s Wayside

CALL

PHONE

IDU-A IDU-B

64kb/s , G.703

SVCE INTFC

IDU-B-48VDC

FUSE 0.5A

IDU-AACCESSORY CONTROL

OUT IN

2MHz Sync

OUT IN OUT INIDU-A IDU-BUSER

IDU-A

IDU-B

ODU-A

ODU-B

OUT INOUT IN OUT INIDU-A IDU-BUSER

OUT INOUT IN OUT INIDU-A IDU-BUSER

Page 141: Citylink Manual RevD

B1089 R

ev. D141

VI Appendices

Fig

ure

VI-4

: Ho

t Sta

nd

by ID

U S

witch

with

Op

tical S

TM

-1 In

terfa

ce

POWERConnector : POWER D-SUB 2-PINCable : UWMK3101

ACCESSORY CONTROLConnector : RJ45 8-PIN Cable : UWMK3187

64KBIT/S SERVICE CHANNEL (G.703)Connector : RJ45 8-PINCable : UWMK3243

PHONEConnector : 4-PIN Cable : Off the shelf handset cable

2MHz SYNCHRONISATION (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3242

155Mb/s STM-1 (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3242

CHASSISGROUND

SVCE INTFCConnector : D-SUB 15-PIN (female)Cable : UWMK3244

FUSE 0.5 ASLOW-BLOW

64KBIT/S SERVICE CHANNEL (G.703)Connector : RJ45 8-PINCable : UWMK3243

2MHz SYNCHRONISATION (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3080

2MHz WAYSIDE (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3080

2MHz WAYSIDE (G.703, 75OHM)Connector : DIN47297, 1.0/2.3mmCable : UWMH3242

155Mb/s STM-1 (G.957, S.1-1)Connector : SCCable : 87K237-A6

CRITICALMAJORMINORWARNINGPOWER ON

A

B

C

STM-12Mb/s Wayside

CALL

PHONE

IDU-A IDU-B

64kb/s , G.703

SVCE INTFC

IDU-B-48VDC

FUSE 0.5A

IDU-AACCESSORY CONTROL

OUT IN

2MHz Sync

OUT IN OUT INIDU-A IDU-BUSER

IDU-A

IDU-B

ODU-A

ODU-B

OUT INOUT IN OUT INIDU-A IDU-BUSER

OUT INOUT IN OUT INIDU-A IDU-B

USER

Page 142: Citylink Manual RevD

142 B1089 Rev. D

VI A

ppendices

Power Connector

0V S TAT IO N G RO UND

-48VD C

Figure VI-5 : IDU power Connector Pin Out

LAN (TP) Connector Detail

PIN 1 PIN 8

Figure VI-6: RJ-45 LAN(TP) Socket Pin Numbering

LAN (TP) RJ-45 8-PIN Signal Name Signal Description1 TPTX+ Data Output2 TPTX- Data Output3 TPRX+ Data Input4 NC Not Connected5 NC Not Connected6 TPRX- Data Input7 NC Not Connected8 NC Not Connected

Table VI-1 : “LAN(TP)” RJ-45 8-PIN Pinout

IDUFRONTVIEW

Page 143: Citylink Manual RevD

B1089 Rev. D 143

VI A

ppen

dice

s

LAN (AUI) Connector Detail

PIN 1PIN 8

PIN 15 PIN 9

Figure VI-7: “LAN(AUI)” D-SUB 15-PIN Pin Numbering

LAN (AUI) D-SUB Signal Name Signal Description15-PIN FEMALE1 GND2 AUI_CX+ AUI Collision Input3 AUI_TX+ AUI Transmit Output4 GND5 AUI_RX+ AUI Receiver Input6 GND7 NC Not Connected8 GND9 AUI_CX- AUI Collision Input10 AUI_TX- AUI Transmit Output11 GND12 AUI_RX- AUI Receiver Input13 +12V14 GND15 NC Not Connected

Table VI-2 : “LAN (AUI)” D-SUB 15-PIN Female Pinout

IDUFRONTVIEW

Page 144: Citylink Manual RevD

144 B1089 Rev. D

VI A

ppendices

NI1 and NI2 Connector Detail

PIN 1P IN 5

P IN 9 P IN 6

Figure VI-8: “NI1” and “NI2” D-SUB 9 PIN Pin Numbering

NI1 and NI2 D-SUB Signal Name Signal Description9-PIN FEMALE1 RxD- Data Input2 RxD+ Data Input3 GND Signal Ground.

Normally this pin shallnot be connected.

4 TxD+ Data Output5 TxD- Data Output6 RxC- Clock Input7 RxC+ Clock Input8 TxC+ Clock Output9 TxC- Clock Output

Table VI-3 : “NI1” and “NI2” D-SUB 9-PIN Pinout

IDUFRONTVIEW

Page 145: Citylink Manual RevD

B1089 Rev. D 145

VI A

ppen

dice

s

64Kb/s Connector Detail

P IN 1 P IN 8

Figure VI-9: “64Kb/s” RJ-45 8-PIN Socket Pin Numbering

64Kb/s (G.703) Signal Signal DescriptionRJ-45 8-PIN Name1 TxD- Data input ; Neg. pulse ; Co- or Contra dir.2 TxD+ Data input ; Pos. pulse ; Co- or Contra dir.3 TxC+ Clock output ; Pos. pulse ;

Contra dir. ; for data input4 TxC- Clock output ; Neg. pulse

Contra dir. ; for data input5 RxD+ Data output ; Pos. pulse ;

Co- or Contra dir.6 RxD- Data output ; Neg. pulse ;

Co- or Contra dir.7 RxC+ Clock output ; Pos. pulse ;

Contra dir. ; for data output8 RxC- Clock output ; Neg. pulse ;

Contra dir. ; for data output

Table VI-5 : “64Kb/s(V.11)” RJ-45 8-PIN Pinout

Table VI-4 : “64Kb/s(G.703)” RJ-45 8-PIN Pinout

64Kb/s (V.11) Signal Signal DescriptionRJ-45 8-PIN Name1 TxD-(v11) Data input ; Neg. pulse ; Contra dir.2 TxD+(v11) Data input ; Pos. pulse ; Contra dir.3 TxC-(v11) Clock output ; Neg. pulse ;

Contra dir. ; for data input4 TxC+(v11) Clock output ; Pos. pulse ;

Contra dir. ; for data input5 RxD-(v11) Data output ; Neg. pulse ; Contra dir.6 RxD+(v11) Data output ; Pos. pulse ; Contra dir.7 RxC-(v11) Clock output ; Neg. pulse ;

Contra dir. ; for data output8 RxC+(v11) Clock output ; Pos. pulse ;

Contra dir. ; for data output

IDUFRONTVIEW

Page 146: Citylink Manual RevD

146 B1089 Rev. D

VI A

ppendices

ALM & AUX Connector Detail

Figure VI-10: “ALM & AUX” D-SUB 25-PIN Pin Numbering

IDUFRONTVIEW

P IN 13 P IN 1

P IN 14P IN 25

ALM & AUX Signal Name Signal DescriptionD-SUB25-PIN FEMALE1 USER1A Relay output 1A2 USER1B Relay output 1B3 USER2A Relay output 2A4 USER2B Relay output 2B5 USER3A Relay output 3A6 USER3B Relay output 3B7 USER4A Relay output 4A8 USER4B Relay output 4B9 ALM1 Alarm input 1 (TTL level)10* I2CSDA Data I2c bus11 ALM2 Alarm input 2 (TTL level)12 ALM3 Alarm input 3 (TTL level)13 AGND Analog GND14 AGND Analog GND15 ALM4 Alarm input 4 (TTL level)16* I2CSCL Clock I2C bus17 ALM5 Alarm input 5 (relay input)18* I2C_GND I2C GND19 ALM6 Alarm input 6 (relay input)20 ALM7 Alarm input 7 (relay input)21 ALM8 Alarm input 8 (relay input)22 B1_V11+ B1 error pulses (V.11 output)23 B1_V11- B1 error pulses (V.11 output)24 B1_OC B1 error pulses

open collector output25 B1_OPTO B1 error pulses opto

coupler driver outputTable VI-6 : “ALM & AUX” D-SUB 15-PIN Female Pinout* For IDUs w/code 3MDK103A-EL and 3MDK103A-F, these signal namesare AGND (analog GND)

Page 147: Citylink Manual RevD

B1089 Rev. D 147

VI A

ppen

dice

s

LCT Connector Detail

IDUFRONTVIEW

Figure VI-11 : “LCT” D-SUB 9 PIN Pin Numbering

LCT D-SUB Signal Name Signal Description9-PIN MALE1 NC Not Connected2 RxD City Link Data Input3 TxD City Link Data Output4 - Internally connected to pin 65 GND Signal ground6 - Internally connected to pin 47 - Internally connected to pin 88 - Internally connected to pin 79 NC Not connected

Table VI-7 : “LCT” D-SUB 9-PIN Pinout

PIN 5P IN 1

P IN 6 PIN 9

Page 148: Citylink Manual RevD

148 B1089 Rev. D

VI A

ppendices

Appendix II: ODU Interface Description

ODU/IDU Interface N-connector female for: Transmit and Receive IF, Modem/Transceiver

communication and power supply.

Branching / Antenna Interface PBR220 waveguide. Grounding cable for Branching Unit.

Page 149: Citylink Manual RevD

B1089 Rev. D 149

VI A

ppen

dice

s

Appendix III:Alarm List & Alarm Description

Alarm Name Description Id Severity

BASEBAND

LOS Loss Of Signal: 1000 MAJORLOF Loss of Frame 1001 MAJORMS-AIS Alarm indication signal detected. 1002 MINORMS-AIS-INS Alarm indication signal is inserted. 1003 MAJORMS-RDI Remote defect indicator detected. 1004 WARNING2M-WAYSIDE-INP 2Mbit wayside input is missing. 1005 MINOR2M-WAYSIDE-AIS-INP 2Mbit wayside input AIS detected. 1006 WARNINGTRELLIS-PLL Indicates that the Trellis coder is out of 1007 CRITICAL

lock.(CNF35C Asic)RT-PLL The Sorp 38,88 MHz PLL is out of lock. 1008 CRITICAL

2M-SYNC Selected synchronisation for Line Transmit 1009 MINORdirection is missing.

RS-TRACE-MISMATCH Mismatch between configured string and 1010 MAJORreceived string

LOC Loss of clock (SORP) 1011 CRITICAL

BASEBANDDIRECTION RADIO TOLINE

LT-PLL The Line Transmit 155MHz PLL is out of lock. 1100 CRITICAL2M-WAYSIDE-OUTP-AIS AIS is detected on the Wayside traffic output. 1101 WARNINGHBER Indicator for BER > 1e-3 1102 MAJORLBER Indicator for BER > 1e-6 1103 MINOREW-BER Indicator for BER > 1e-10 1104 WARNINGRF-ID Wrong RF-ID received compared 1105 MAJOR

to configuration.

MODULATOR

IF-MOD Loss of IF 350MHz 1200 CRITICAL

DEMODULATOR

IF-DEM Loss of INCOMING 140MHz. 1300 CRITICAL

OPTICAL INTERFACE

TX-OUT The output power has increased 2dB. 1400 CRITICALLASER-OFF The laser is off. It could be manual shutdown 1401 WARNINGBIAS The laser bias is out of limits. Sign of age and 1402 WARNING

degradation.

TRANSCEIVER

LOS The RF input signal is missing. Loss of signal 1000 MAJORin transmission sense.

IF-INP IF input to the transceiver is missing 1500 CRITICALRF-OUT The output power is low 1501 MAJORRF-OUTPUT-WARNING The RF level is either above the threshold or 1503

The RF level is below the threshold.

Page 150: Citylink Manual RevD

150 B1089 Rev. D

VI A

ppendices

Alarm Name Description Id Severity

RF-INPUT-WARNING The RF level is either above the upward 1504 WARNINGfading threshold or The RF level is below thedown fading threshold.

LO Local Oscillator is out of lock. 1505 MAJORUNIT-ALM The transceiver is not responding 1506 MAJORATPC The regulation loop for the ATPC is not 1507 MINOR

working. Software generated alarm based onalarm condition on local LOF on Rx andremote LOF on Rx .

RF-MUTE The RF transmitter is muted. 1508 WARNINGLOOPING-IF-EN The transceiver looping on IF is enabled 1509 WARNINGLOOPING-RF-EN The transceiver looping on RF is enabled. 1510 WARNING

OTHER ALM

MEN-AT-WORK Software generated. Operator set men at 2000 WARNINGwork before doing repairs.

DROP-IN+48V The battery supply voltage is dropped below 2001 WARNINGacceptable limit

BELOW+3.3V Voltage from the DC-DC converter below limit 2002 WARNING

BELOW+5V Voltage from the DC-DC converter below limit 2003 WARNING

BELOW+12V Voltage from the DC-DC converter below limit 2004 WARNING

BELOW-5V Voltage from the DC-DC converter below limit 2005 WARNINGOVER-CURRENT Detects short current on ODU cable. 2006 MAJORWAYSIDE-LOOP FE Wayside looping Far End 2007 WARNINGWAYSIDE-LOOP NE Wayside looping Near End 2008 WARNINGPRBS-INSERTED PRBS inserted in wayside 2009 WARNINGLOOPING_EN Looping enabled 2010 WARNINGEVENT-LOG-EXC-LIMIT Event log has exceeded the capacity threshold 2011 WARNINGDOWNLOAD-IN- Download of software is under progress. 2012 WARNINGPROGRESSNEED_FREQUENCY An RF unit needs to be configured with Tx and 2013 MAJOR

Rx frequency.SECURITY-LOG-EXC- Security log has exceeded the capacity threshold2014 WARNINGLIMIT64K-LOOP 1 64 kb channel looping Channel 1 2015 WARNING64K-LOOP 2 64 kb channel looping Channel 2 2016 WARNINGRTC-LOW BATTERY The battery that powers the Real Time Clock is low2017 WARNING

HOT STANDBY ALARMS Alarms marked with * are not implemented inHot Standby IDU-Switches with equipmentcodes: 3SYZ251A-EL, 3SYZ251A-F,3SYZ251B-EL and 3SYZ251B-F

HSB_RELAY IDU-Switch relay mismatch 2200 CRITICALIDUA-ACTIVE IDU A is active in receiving direction 2201 INFOIDUB-ACTIVE IDU B is active in receiving direction 2202 INFOHSB-MANUAL The IDU-Switch and the RF-switch is 2203 WARNING

operated manuallyHSB-LOOP-CMI CMI loop enabled 2204 WARNINGHSB-LOOP-WAY Wayside loop enabled 2205 WARNINGHSB-LOOP_SYNC SYNC loop enabled 2206 WARNINGHSB-LOS No CMI/optical input from lineside 2207 MAJOR2M-WAYSIDE-INP No 2Mb/s input from lineside 2208 MAJOR2M-SYNC_INP No sync input from lineside 2209 WARNING

Page 151: Citylink Manual RevD

B1089 Rev. D 151

VI A

ppen

dice

s

Alarm Name Description Id Severity

*LOS-CMI-IDUA No CMI input from IDU-A 2210 MAJOR*WAYSIDE-IDUA No 2Mb/s input from IDU-A 2211 MINOR*SYNC-IDUA No sync input from IDU-A 2212 WARNING*LOS-CMI-IDUB No CMI input from IDU-B 2213 MAJOR*WAYSIDE-IDUB No 2Mb/s input from IDU-B 2214 MINOR*SYNC-IDUB No sync input from IDU-B 2215 WARNINGCHANNEL-ACTIVE This ODU is active 2216 INFOUNIT-ALARM-A IDU-A has no contact with IDU-Switch 2217 MAJORUNIT-ALARM-B IDU-B has no contact with IDU-Switch 2218 MAJOR

AUXILIARY ALARMS

EXTERN-ALARM-1 Multipurpose port. Configured as 2500 WARNINGAlarm Output, Alarm Input or Remote Control.External alarm reported if port configured asalarm input.Alarm name configurable from management system.

EXTERN-ALARM-2 ref External alarm 1 2501 WARNINGEXTERN-ALARM-3 ref External alarm 1 2502 WARNINGEXTERN-ALARM-4 ref External alarm 1 2503 WARNINGEXTERN-ALARM-5 ref External alarm 1 2504 WARNINGEXTERN-ALARM-6 ref External alarm 1 2505 WARNINGEXTERN-ALARM-7 ref External alarm 1 2506 WARNINGEXTERN-ALARM-8 ref External alarm 1 2507 WARNINGOUTPUT-ALARM-1 Output alarm reported if auxiliary output port 2550 NORMAL

configured as alarm output.OUTPUT-ALARM-2 ref Output alarm 1 2551 NORMALOUTPUT-ALARM-3 ref Output alarm 1 2552 NORMALOUTPUT-ALARM-4 ref Output alarm 1 2553 NORMAL

PERFORMANCE All software generatedALARMS

G826-THRESHOLD- If the current 15 minute period exceeds the 3000 WARNING15MIN-B1 set threshold for B1, this alarm is set. Cleared

when new period starts.

G826-THRESHOLD- If the current 15 minute period exceeds the 3001 WARNING15MIN-B2 set threshold for B2, this alarm is set.

Cleared when new period starts.Blocked by default.

G826-THRESHOLD- If the current 15 minute period exceeds 3002 WARNING15MIN-REI the set threshold for REI, this alarm is set.

Cleared when new period starts.Blocked by default.

G826-THRESHOLD- If the current 24 hour period exceeds the set 3003 WARNING24Hour-B1 threshold for B1, this alarm is set.

Blocked by default.

G826-THRESHOLD- If the current 24 hour period exceeds the set 3004 WARNING24HOUR-B2 threshold for B2, this alarm is set.

Cleared when new period starts.Blocked by default.

Page 152: Citylink Manual RevD

152 B1089 Rev. D

VI A

ppendices

Alarm Name Description Id Severity

G826-THRESHOLD- If the current 24 hour period exceeds the set 3005 WARNING24HOUR-REI threshold for REI, this alarm is set.

Cleared when new period starts.Blocked by default.

G826-THRESHOLD- If the current month period exceeds the set 3006 WARNINGMONTH-B1 threshold for month, this alarm is set.

Cleared when new period starts.

G826-THRESHOLD- If the current month period exceeds the set 3007 WARNINGMONTH_B2 threshold for month, this alarm is set.

Cleared when new period starts.Only for MS termination.

G826-THRESHOLD- If the current month period exceeds the set 3008 WARNINGMONTH-REI threshold for REI, this alarm is set.

Cleared when new period starts.Only for MS termination.

Page 153: Citylink Manual RevD

B1089 Rev. D 153

VI A

ppen

dice

s

Appendix IV:Requirements concerning Revisions ofUnits used in Hot Standby Configuration

IDU Code: 3MDK103B-EL, rev. R2A or higher(i.e. R2B, R3A, R4C etc.).

Transceiver Code: 10L18L1010A, rev. R2F or higher.10L18U1010A, rev. R2F or higher.10L25L1008A, rev. R2F or higher.10L25U1008A, rev. R2F or higher.(Higher revision than R2F is for example R2G,R3A and R3B.)