compressor manual 2009
TRANSCRIPT
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
CONTENT
1、General ………………………………………………………… 2
1.1 Working principal ……………..……………………………………… 2
1.2 System control ………….…………………………………………… 2
1.3 Manipulation Temperature ……………. …………………………………… 3
1.4 Lubricant features …………………………………………………… 4
2、Installation requirements and inspection before running …………. 4
2.1 Hoist and transportation … ……………………………………… 4
2.2 Field requirements ……………………………………………… 5
2.3 Requirements for quality of cooling water …………….…………………… 6
2.4 Connection requirements for air pipe …………………………………… 6
2.5 Electric installation requirements .…………………………………… 7
2.6 Machine inspection ……………………………………………… 8
3、Daily operation ………………………………………………… 8
3.1 Preparations before running ………………………………………… 8
3.2 Start-up procedure for the first time …………………………………… 9
3.3 Start-up procedure for the daily time .……………………………………… 9
3.4 Turn-off procedure …………………………………………… 9
4、 Control panel operation(for pack series 4-15kw)…….……….… 10
4.1 Basic operation ……………………………………………… 11
4.2 Customer parameters …………………….…………………………. 12
4.3 Factory parameters ………………………………………… 15
4.4 Pressure Switch (for pa ck series with pressure gauge)……………………………… 16
4.5 Circuit diagram ………………………………………………… 17
5、 Control panel operation(for sc series 18-250kw)…………… 19
5.1 Basic operation …………………………………………………… 20
5.2 PLC functions and technical parameters ……………………………… 26
5.3 Control principle ………………………………………… 28
5.4 Alarm and notices …………………………………… 30
5.5 Safety protection ………………………………………………… 31
5.6 Histroy failure record check ……………………………………………… 32
5.7 Circuit diagram ………………………………………………… 33
6、 Maintenance ………………………………………………... 34
7、 Explored drawing ……………………………………… 39
8、 Troubleshooting ……………………………………………… 42
- 1 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
1、General
DMC screw air compressor adapts up-to-date structure design from Italy. Its key parts such as screw
air end, control valves are of European origin. It which falls into the category of products of
intellect-type and environments-protecting-type is microcomputer -controlled feathering compact
structure, high efficiency, low noise, long life period and so on. And it is the ideal air source equipment
popularly applied to textile, machinery, chemicals, electric, mining and other industrial areas. It runs
intelligently, and realizes long-range control and chain control.
1.1Working principle
Compression: the screw air end sucks air through air intake filter and intake control valve. Then the
rotary double shafts compress the air . At the same time, oil is put into the air compressing cavity making
the screw and bearing cool and lubricant.
Separation: The mixed gas of air and oil generated by compressing is exhausted into air and oil
separation cartridge. Most of oil is separated from the mixed gas under the influence of gravity and
mechanical centrifugal force. Almost all oil mist is separated out after the gas of air and oil is through
separation cartridge core. So then the oil amount of the mixed gas is below 3PPM. The oil separated
through separation cartridge core is back to screw principal machine through oil return tube. A throttle is
mounted on the oil return tube in order to keep the loss of compressed air in the lowest extent. The clean
oil flows into air end internal cavity after being filtered.
Cooling: After oil is separated, compressed air flows out of separation element through minimum
pressure valve then into after-cooler. Then cool the compressed air into a temperature towering above
environmental temperature by 7-10 degrees centigrade before it is discharged. Minimum pressure valve
guarantees the minimum pressure needed to keep up circulation of oil when the screw air compressor is
started or when it is running normally. Due to the check valve on minimum pressure valve, the
compressed air can’t flow backwards into separation element.
1.2 System control
The aim of having a control system is how to control the intake valve correctly to let air in normally. The
system is comprised of intake valve, work piston, magnet valve and pressure gauge.
Start-up: the intake valve shuts up under the influence of spring force. Hence only little air is sucked
through single-direct valve of intake valve to generate cartridge pressure to keep up circulation of oil
when screw air compressor is started up from no-load state.
Load: when compressor is running to a load state, it’s vacuum within compressor. And there is pressure
in intake filter. So, due to the difference of pressure, which makes the piston of intake valve work, intake
valve opens. Vacuum of one side lets air in then be compressed, which makes intake valve open fully.
After that, system pressure increases.
Full load: when the pressure of oil separation cartridge reaches 0.4MPa, minimum valve opens to let
- 2 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
compressed air flow out. (When the system pressure is lower than the rated pressure, intake valve will be
open all the time.)
No-load: when the pressure of empty pipeline reaches the maximum pressure rated by pressure switch,
the switch turns off the magnet valve’s power. Then there is no pressure difference. Intake valve shuts up
under the influence of spring force. Discharge magnet valve releases pressure and the pressure of
separation element goes down. All these make backpressure of frame end of screw air compressor low
down. When compressor is in the no-load condition, a little air goes in to keep certain pressure. It is
needed as working pressure of lubricant system to make rotors and bearing lubricant. When the pressure
of pipeline goes down to the rated load pressure, compressor is back to load state. Then magnet valve
gets power. Intake valve opens. Accordingly, the system pressure goes up. As per requirement to
compressed air, make the process be in a cycle.
Stop: when the compressor is stopped, all magnet valves’ power will be turned off. Then intake valve
will close up. Last the discharge magnet valve will release the cartridge pressure.
1.3Manipulation temperature
Screw air compressor’s environment temperature ranges from 5 degrees centigrade to 40 degrees
centigrade. Intake point is the measure point.
Condensation---low temperature
When the manipulation temperature is lower, water would concentrate in oil on the location of higher
degree of moisture. Compressor is equipped with a thermostatic valve. And the temperature is set to 70℃.
(Upon reaching the temperature, water vapors.) Oil won’t pass through the oil cooler until it reaches the
rated temperature.In the area of temperature below 5 ℃, anti-condensation apparatus should be mounted. And a heater should be installed under the separation element too.
Overheat---high temperature
The air sucked under this condition (environmental temperature is above 40℃ or the compressor is
installed in a house where there is a boiler) when the compressor is in full load state may be excessively
hot and above the cooling requirement. The air for cooling use had better be input from outdoors. When
the load rate is below 100% load, a higher environmental temperature can also meet the cooling
requirements. The maximum of working temperature of compressor is 105℃. If the temperature is above105℃, the compressor will be overheat and cease to work.
Discharge temperature
The measure point of discharge temperature is located in the vent of frame end of compressor. Discharge
would vary according to environmental temperature, load percentage, cleanliness of cooler, cleanliness
of intake filter and the cleanliness of oil filter. The normal manipulation temperature is between 70℃ and90℃.When the compressor is started up from a cool condition, the discharge temperature will go up
- 3 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
quickly to 85℃. Then thermostatic valve open fully. (it sets to open when the temperature is 70℃)If it is with down loads, oil temperature will be back to 70℃. At this time a little oil will pass through thermostatic valve in case the oil temperature be too low. With the increase of load, thermostatic valve
adjusts discharge temperature by control the oil amount through oil cooler.
1.4 Lubricant features
The feathers of DMC screw air compressor is as follow:
• Low degree of blister, not easy to volatilize
• High degree of anti-emulsification, high degree of anti-oxidation
• Motion viscosity (40℃) ㎟/s 32
• Pour point temperature -35℃ anti-solidification, low energy-consumption
• Flash temperature 230℃, anti-carbon-deposit, and low-energy-
consumption
Oil for bearing of motor:
Commended: Shell Alvania RL 3
2. Installation requirements and inspection before running machine
Examine in details whether there is damage due to transportation or not before accepting the compressor.
If any, please request the shipping company to confirm it by signing and contact us immediately.
2.1Hoist and transportation
• Guide rope should be used when compressor is being hoisted lest it be damaged. Check if welding
crack and bolt become loose after it is lifted up.As figure shows, a supporting board is needed when
compressor is being hoisted.
• If use a platform trailer to transport the compressor, make sure the trailer has enough driving-power.
• If use a forklift to transport the compressor, also make sure it has enough driving-power. Specific
requirement is subject to the local regulation.
The length of fork should not be less than the length of the base of compressor.
- 4 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
2.2Field requirements
• Compressor should be located in a clean, no-dust, well-ventilated place (discharge the heat wind from
upside, input air from bottom) with air excluding toxic gas, inflammable gas and explosive gas. Where it is
easy to maintain the compressor.
• Compressor mustn’t be used outdoors. Because there is a bad condition. That is, there is a great quantity
of dust. A filter screen should be mounted in the air intake of house in order to reduce the quantity of dust.
• Environmental temperature should be above 5℃ to guarantee lubricant a normal cycle.
• Some space (1m between compressor and wall is perfect) must be set aside in order to make daily
maintenance work convenient. See figure3.
• Compressor should be placed in a solid level surface. There is no using nut to fasten it.
Tip: D on’t put it in a place where the hot wind can be sucked circularly. (P ut it in a well-ventilated place)
If compressor is mounted in an enclosed room, an exhaust fan must be mounted in this room with a view to
keep the room temperature. The exhausting quantity must be more than air volume of circulating fan or
cooling fan. There should be enough area of entrance of cool air. The minimum of maintenance space should
be 500mm or above. If air entrance for cooling is in this direction, the minimum of maintenance space
should be 1000mm and above.
- 5 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
2.3 Requirement for cooling water and water-cooling set
• General hardness expressed by CaCo3 should be less than 100PPM (100 milligram/liter)
• PH value varies from 6-8
• Suspended material should be less than 50PPM (50 milligram/liter)
T i p: t he t e m pe r a t u r e of c o o li ng w a t er i s s et t o 32 ℃ . A nd t he w a t er qua lit y m u s t be i n con f o r m i t y w i t h
gene r al i ndu stri al w a t e r . A vo i d u si ng g r ound w a t e r . I f t he w a t er qua li t y i s not good, u s e pu ri f y i ng agent t o
c l ean depo siti ng d ir t pe ri od i ca l l y . I f t he co m p r e ss or co m es i n t o d is u s e f or a l ong tim e, d r a i n out a l l coo li ng
w a t e r .
2.4 Connection requirements for air pipe
• The diameter of discharge pipe should be at least the same as that of compressor. All pipes and connectors
should be able to bear the rated pressure. The configuration should meet the requirements for flowing
velocity of compressed air. And the pressure drop of pipeline mustn’t exceed the set pressure by 5% or more.
Try to use elements with a bent or high drag coefficient as little as may be. If the pipeline is relatively long,
adopt pipes with a diameter bigger than rated one.
• Don’t let this matter occur. That is, don’t let condensation water flow into working machine or elements
driven by air along the pipeline. An oil/water separation apparatus and a dirt-draining apparatus should be
mounted on front end of pipeline. Install the main pipe with a slope of 1-2 degrees, and then the condensate
water can be easily drained out.
• One-way valve, stop valve are mounted at the exit of compressor. And a sample connection of pressure and
a stop valve for maintenance and pipe-connecting use are mounted after them.
• Because there is an anti-vibration mat and not supporting things for fixing, all external pipelines should
have its individual supporting things. In order not to let condensate water flow back into compressor when it
stops, make pipeline lower than the air gate of compressor.
• When compressor is used with drier, an air reservoir should be installed in between compressor and drier.
In this case, it can low down the temperature of discharged air and separate a part of condensate water. At the
same time, compressed air of lower temperature and less amount of water is transported into the drier
through air reservoir. In such way, it can lessen the load of drier and save energy.
- 6 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
• Main pipeline going around the whole air-use house is the ideal plan. In this case, compressed air from
direction can be got anywhere. If there is a sudden increase of air-use quantity on some branch pipe, it can
reduce pressure drop. Moreover, mounting proper valves on main pipeline can insure convenience for
maintenance. Because we can cut it off, if necessary.
2.5 Electric installation requirements
All internal wires of compressor are through test by factory. All external wires linked to compressor must be
manufactured by qualified factory. According to the input working power required by compressor set, choose
right wire specification. If the wire is too long, line loss should be taken into consideration. Under this
circumstance, diameter of wire should be made bigger so as to meet the requirements for starting-up and
running.
Compressor of a big quantity of discharging air needs an individual power-supply system; otherwise it will
have bad influence on normal working of other equipment.
Make sure that power voltage meets rated working voltage of compressor before running it.
Reliable grounding of compressor set is needed to avoid dangers resulted in by power leaking.
Power supply
Standard requirements:
230V, 3 phase, 60Hz grounding
460V, 3 phase, 60Hz grounding
380V, 3 phase, 50Hz grounding
415V, 3 phase, 50Hz grounding
Other
Make special requirements on placing the order
Turning of motors
Power must be linked to compressor correctly to guarantee the right turning of motor. DMC screw air
compressor is equipped with a special apparatus to avoid contra-rotation of motor. (If the sequence of 3
phases is not correct, motor stops automatically to protect the motor.)
Particularized methods as follow: First, switch on power. Second, unloose the scram button. Third, press the
stop button. Then the machine will check itself. Finally, press the start button. If the machine is running
normally, that means the sequence of 3 phases is correct.
If the motor stops automatically, that means the sequence of 3 phases is not. Then exchange the two phases
of power input. (Instead of exchanging the wire ring of motor or the wire ring of starter, all these wire rings
are set to optimize the performance of motor.) Men with electrician certification should finish wire-linking
work.
- 7 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
2.6 Machine inspection
Inspection for screw air end
• Revolve the belt pulley or shaft coupling of gear end by hands from two different directions. Check if the
screw end is not locked.
• When compressor is not in use for more than two months or stored for a period of time, intake valve should
be opened. Then fill half-kilolitre of oil into compressor through it. Revolve the belt pulley or shaft coupling
of air end by hands from two different directions. Make sure all oil enters airr end.
• When reconnect inlet pipe, make sure nozzle is sealed.
Inspection for oil level
When open the side door, you can see the oil inspection mirror. The maximum oil level must not be higher
than the upper part of oil inspection mirror and the minimum oil level must not be lower than the bottom of
oil inspection mirror. The requirements also holds true when compressor is running.
Charge the rated amount of oil. Make sure the lid to the nozzle is screwed on well and seal ring is in good
condition.
T i p s : C ha r ge o i l acco r d i ng t o t he a m ount sti pu l a t ed. T o o m uch o i l wil l m ake t he co m p r e ss ed a i r con t a i n t oo
much oil. A nd too little oil will lead to high temperature of compressor.
Inspection for transmission system
• Inspection for belt
Check if all belts are in the groove. Adjust the tightness of belts through the adjusting bolt on motor.
• Inspection for flexible shaft coupling
Check if the bolt of the flexible shaft coupling is in fixed state.
Inspection for all valves of system
Check if stop valve is open.
3、Daily operation
The procedure below is for starting up for the first time or compressor being not in use for more than two
months.
3.1 Preparations before runningDMC screw air compressor is with an advanced delay-start/delay-stop function. This function can protect
motor, air end and electromagnetic starter so as to optimize operating performance.
Delay-start: This function is to avoid starting up continuously after power cut or emergency shut down.
During this period, compressor can’t be started up. Make sure the pressure is cut down to avoid starting up
the compressor when there is backpressure. Press the start button. And this signal will be put down
- 8 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
automatically by system. When the delaying time has elapsed, compressor will start up automatically.
Delay-stop: This is a soft stop function. This function makes compressor unload and cease to work. First,
press the stop button to unload compressor. Then it will be running for a while until the preset time and stop.
(This will contribute to reducing the pressure of oil separation cartridge.) During the delaying time, if press
the start button, the delaying time will be finished automatically. If the system pressure needs loading, the
compressor will load or unload normally.
3.2 Start-up procedure for the first time
• Check if the stop valve on outlet is open. (If the stop valve is open, this pressure is the pressure of
compressor system)
• Turn on power, and then power indicator light will be on. Compressor begins its delay-start. Starting
instantly is forbidden.
• Press start button to run the compressor, and then compressor is in the normal delay-start condition. Once it
reaches the preset time, compressor will start up automatically. (During the delaying time, press the stop
button, and then compressor will stop)
• Watch the manipulating temperature and system pressure on control pane to manipulate the compressor
correctly.
• When it reaches the pressure stipulated, Compressor goes on running. But it is running in a un-load state.
• Compressor supplies compressed air through loading and unloading. Pay attention to pressure, temperature
and power flux when manipulating it. Make sure there is no accidental vibration and compressor is running
smoothly.
3.3Start-up procedure for the daily time
• Check if oil level is correct. The oil level must be in the center of oil gage.
• Drain out the condensate water in the air-storing tank.
• Confirm that stop valve is open.
• Press start button. (Compressor does not start up automatically. But run light is flashing, it means
compressor is in a delay-start state.)
A tt en ti on: D o not st a r t up i t wit h i n 60 s econds a ft er co m p r e ss or i s st opped. R e l ea s e a l l p r e ss u r e wit h i n
s epa r a ti on e l e m en t . ( A v o i d t hat co m p r e ss or i s st a r t ed up w hen t he r e i s backp r e ss u r e.)
3.4Turn-off procedure
Press the stop button, and then the compressor will be in delay-stop state. Meanwhile, the stand-by indicator
light is flashing. After some time, the compressor stops.
If the compressor is start stopping, press the stop button to make it stop thoroughly.
Attention: when compressor is in stand-by state, it may stop and may start up at some time. So don’t take it
for granted that compressor has been stopped when the motor is not in motion. Check if the stand-by light is
on.
Tip: emergency shut down button is generally pressed on emergency.
- 9 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
4、 Control Panel (for PACK series 4-15kw without pressure gauge)
Type: M A M - 2 2 0 ( B ) - T
Attention
Please read this manual carefully before operation.
Only Authorized technicians are allowed to install MAM—KY.
Please take into fully consideration of the installation position during the mechanical installation to
ensure good vent condition and to minimize the electromagnetic interference.
During the wiring procedure, please separate the Strong current and light current lines to reduce the
electromagnetic interference.
A surging absorber must be applied to the inductive load such as the AC contactor of the relay output.
Check carefully for the wiring of the input/output before power applying.
Correctly grounding of the ground terminals of the unit (Third grounding) can improve the anti-noise
capability of the unit.
The presetting of the rating current of the motor (skip current) is set to Rated Current on the name plate
X Motor overload factor/1.2.
- 10
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Features:
LCD English display
• Full protections for motor in terms of short-circuit, locked rotor, lack of phase, overload and unbalance.
• Start/Stop and operation control of the Motor
• Anti- reverse protection for Air Compressor
• Measuring, protecting and controlling multi-points temperatures
• Automatic adjust load rating to balance pressure
• Stable, reliable, competitive price with high value
• Remote / nearby control
• Block / independent operation
• RS-485 communication
4.1. Basic OperationButtons Description
MAM-220
GAS T:80℃STATE NORMAL STOP
POWER RUN
FALT
S RT ON
Figure 1
ON——Start Button: Press this button to start the compressor
OFF——Stop Button: Press this button to stop the compressor
S—— Set Button: users press this button to confirm the data inputted and save it after modification.
When compressor is running press this button will switch to load run / unload run.
▲——Up button: Press this button to move upward during data modification. Press this button to
select menu during the menu selection
▼——Down Button: Press this button to move downward during data modification. Press this button
to select menu during the menu selection
►——Cursor / Confirm Button: This button can be used as cursor during the data modification and as
confirm button during the menu selection
RT——Return / reset Button: Press this button to return to upper menu during the menu operation.
Press this button for 5 seconds to reset the machine when the unit is stopped in failure.
- 11
-
THIS RUNNING TIME FAILURE 1 CUSTOMER PARAMETER
THIS LOADING TIME FAILURE 2 FACTORY PARAMETER
OIL FILTER FAILURE 3
AIR FILTER FAILURE 4
O-A SEPERATOR FAILURE 5
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Status Display and Operation
The display interface is as follow when the units are POWER ON:
SCREW
COMPRESSOR
The main display after 5 seconds will be the following:
P:0.8Mpa
S: NORMAL STOP
Attention: press“►” the position of “P:0.8 Mpa” change to display “T:080‡” .
Press “▼” Enter the following Menu Selection Interface:
TOTAL RUN TIME:******H*
*M
Run the Parameter Review
Press ‘▼’button, parameters and status are as follows
LOADING TIME LUBE TIME PRODUCE DATE
MAIN MOTOR CURRENT LUBE GREASE PRODUCE NO.
4.2 Customer Parameters
T ip : T h e C us t o m e r P a r a m e t e r s a nd t h e F a c t o r y P r e s e t P a r a m e t e r s c a nn o t b e m od i f i e d du r i n g t h e R unn i ng S t a t e a nd S t op D e l a y i ng p er i od
Press the ‘▼’ button, the last page is the ‘CUSTOMER SET’ and ‘FACTORY SET’. Or on the main menu,
your can press the ‘▲’button, immediacy turn to the ‘CUSTOMER SET’ and ‘FACTORY SET’. Interface.
CUSTOMER SET
FACTORY SET
- 12
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
At this time, press “▼” button or “▲”button, the black cursor will move to select “CUSTOMER SET” Or “FACTORY SET”,when the black cursor is on the “CUSTOMER SET ”, press “►” button ,
the following interface will appeared
LOADING P: 00.65MPa
The CUSTOMER PARAMETER is being showed now without press the CONFIRM button ‘ ’.
Press the CONFIRM button ‘ ’ again to pop up the following interface where the password input
is needed:
PASSWORD
****
A tte n t i o n : The C us t o m e r P a sswo r d ca n m e m od i f i e d i n t he C U S T OMER P A R AM ETE R , t he F AC T O R Y P A SS W O R D i s ****
The ‘▼’ or ‘▲’ button return to be black cursor and the button ‘►’ return to be the CONFIRM
button. Press the CONFIRM button ‘►’ when the cursor is over the menu ‘LOADING P’, now the
blinking appears and the button ‘▼’ and ‘▲’ are Page-Up and Page-Down button for changing the
current value. The button ‘►’ is now the move button to move the position where the modification
is needed; Press ‘S’ to confirm and the blinking will disappear. The ‘▼’ or ‘▲’ return to be black
cursor move button and the button ’ ►’ change back to be CONFIRM button to continue to modify
the other CUSTOMER SET. If there are no other parameters needed to be modified, press the button
‘RT’ to return to the upper menu or the main menu. The other CUSTOMER Set could be modified
with the same method as above.
Customer Parameters Fuctions
Parameter Preset Value Functions
LOADING P *.**MPa Loading pressure value
UNLOADING P. *.**Mpa Unload pressure value
FAN START T ***℃Control the fan starting. This value will be set to‘120℃' if there is no fan present or the fan is not required to be protected.”
FAN STOP T ***℃ Control the stopping of the fan
MOT START TIME 0008s
When using the controller to protect the motor, it
is required that the time here defined will not
meet the impulse starting current of the motor, the
value here must be longer than the STAR DELAY
TIME plus LOAD DELAY TIME
- 13
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
STAR DELAY TIME 0006S Star pressure release starting delay time.
LOAD DELAY TIME 0002SThe loading delay time after star contactor
releasing.
EMPTY RUN TIME 0020MLoad free continuous running time, the machine
will automatically stop after this time
STOP DELAY TIME 0010SThe machine will not stop until this time passed
the load free state when stop the machine
BLOWDOWN TIME 0100SMachine can not be restarted before this set time
after stopped or over time operation
ON/OFF MODE Machine side
When the remote mode is set, both the buttons at
machine side and the remote control button can
turn on and off the machines
LOAD MODE AutoWhen the manual mode is set, the Load/Unload
function can only be executed by pressing buttons
CLR OIL FILTER 0000 HOURS Reset time for the duration of oil filter changing
CLR O/A SEP 0000Hours Reset time for O/A Separator changing
CLR AIR FILTER 0000Hours Reset time for air filter changing
CLR LUBE 0000Hours Reset time for Lubricate Oil Changing
CLR GREASE 0000Hours Reset time for Lubricate Grease Changing
MAX OIL FILTER 9999HoursSet this value to ‘0’ will make the oil filter alarm
not available
MAX O/A SEP 9999HoursSet this value to ‘0’ to disable the O/G separator
alarm function
MAX AIR FILTER 9999HoursSet this value to ‘0’ to disable the alarm function
of gas filter
MAX LUBE 9999HoursSet this value to ‘0’ to disable the time alarm of
lub. oil
MAX GREASE 9999HoursSet this value to ‘0’ to disable the time alarm of
Lub. Grease
COM MODECOMPUTER/BLOCK
/PROHIBITSelect communications mode
COM ADD 0001-0255
BLOCK STATEMAIN
Act as Host or Secondary Machine
when there are more than one machines
The HOSTcontrols the others
BLOCK NUMBER 0016
BLOCK LOAD P*.**MPa
BLOCK UNLOAD P *.**MPa
- 14
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
BLOCK DELAY 0000S Blocking delay time
LANGUAGE SEL ENGLISH/CHINESE Select language
POWER FREQ 50Hz/60Hz Select power frequency
PHASE PROT INACTIVE/ACTIVE Active or inactive phase sequence protect
4.3 Factory ParametersThe difference between the ‘CUSTOMER SET’ and the ‘FACTORY SET’ is that the ‘FACTORY SET’
can not be modified unless you have the factory password from the manufacturer. The main functions of
the
‘FACTORY SET’ are as the following table.
Factory Parameter Initial Value Functions
MANI MOTOR
CURR.
MAXIMUM
OVERLOAD VAULE
OF THE MOTOR /1.2
After the starting delay time, when the motor
current is greater than 1.2 times of the set value
and less than 4 times of the set value, the unit will
jump as per overload feature.
PRE-ALARM T 105℃ Alarm when the temperature reaches this set value
STOP T. 110℃ Alarm when the air exhausting temperature
reaches this set value.
STOP P. 1.00MPaAlarm and stop machine when the air supply
pressure reaches this set value
MAX UNLOAP 0.80MPaThe Unload Limit Pressure in the Customer
Parameter must be set lower than this value.
CLR LOAD TIME ****Hours The factory can modify the load running time
CLR TOTAL TIME ****Hours The factory can modify the total running time
CLR ALM RECORD **** Input password to clear all the history failures.
UNBALANCE
SCOPE0006
When unbalance is not greater than (1+set value),
the unbalance protection will stop the machine. If
the set value is greater than 15, the unbalance
protection will be disabled.
LACK PHASE
STOP0005S
Set the LACK PHASE TIME ≥20S, the Lack
phase protection will be disabled, if the unbalance
protection is active, it will be started.
PROD. DATE ****Y**M**D The factory input the product date of the unit.
PROD. NO. ****** The factory input the product No.
- 15
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
4.4 Pressure Switch (for PACK series with pressure gauge)
T i p s : wo r k i ng p r e ssu r e ca n b e a d j us t e d on l y b y p r e ssu r e sw it c h a nd i nd i c a t e d i n p re ssu r e
g a u g e f or t h i s m od e l
Pressure switch is used to controls compressor operation within the set switching limits. If the supply pressure drops to the Switch-on pressure( Pmin), the compressor will switches on, if the supply pressure increases to the switch–off pressure (Pmax),the compressor will switches off.There are two adjusting screws on the top of pressure switch.
1(DIFF)—is to adjust difference of Pmax / Pmin.2(RANGE)—is to adjust Pmax .In normal, Diff value is between 1.0-1.5bar, Max Pressure value is 7-10bar.
W ARNI N G : Do n ot a d j u st P m ax u p t h an s ett in g va lu e o f c o m p r e sso r p r e ss u r e o p t i o n a ll y .
- 16
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
4.5 Circuit diagram
- 17
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
- 18
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
5、 Control Panel (for SC series 18.5-250kw)
T Y P E : M A M - K Y 0 2 S( B
)-( Ⅷ )
Attention
Please read this manual carefully before operation.
Only Authorized technicians are allowed to install MAM—KY.
Please take into fully consideration of the installation position during the mechanical installation to
ensure good vent condition and to minimize the electromagnetic interference.
During the wiring procedure, please separate the Strong current and light current lines to reduce the
electromagnetic interference.
A surging absorber must be applied to the inductive load such as the AC contactor of the relay output.
Checking carefully for the wiring of the input/output before power applying.
Correctly grounding of the ground terminals of the unit (Third grounding) can improve the anti-noise
capability of the unit.
The presetting of the rating current of the motor (skip current) is set to Rated Current on the name plate
X Motor overload factor/1.2.
- 19
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Features:● LCD English display
● Full protection function for the motor in short circuit, locked rotor, phase lost, overload or unbalance.
● StartIStop and operating control of the Motor
● Anti- reversing protection of Air Compressor
● Measuring and protection controlling to multi-points temperatures
● Automatic adjusting load rating to balance pressure
● High Integrity, Stable reliability and excellent value-ability
● Optional remote I machine side control
● Optional interactiveI independent operation
● RS-485 communication interface function
5.1 Basic Operation
Buttons Description
GAS T:80℃ GAS P:0.8MPaSTATE NORMAL STOP
0S REMOTE
ON M
Figure 1
ON——Start Button: Press this button to start the motor
OFF——Stop Button: Press this button to stop the motor
M——Set Button: Press this button to confirm the input data to be saved after modification of the data.
——Up button: Press this button to move upward during modification data. Press this button to select
menu during the menu selection
——Down Button: Press this button to move downward during modification data. Press this button to
select menu during the menu selection
——Cursor I Confirm Button: This button can be used as cursor during the data modification and as
confirm button during the menu selection
RT——ReturnIPreset Button: Press this button to return to upper menu during the menu operation.
Press this button to reset the machine when the unit is stopped in failure.
- 20
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Status Display and Operation
The display interface is as following when POWER ON:
Welcome to use
***Screw Air Compressor
The main display after 5 seconds will be the following:
GAS T:20℃
GAS P:0.60Mpa
STATE:NORMAL STOP
NEAR
Press “1” Enter the following Menu Selection Interface:
RUN PARAMETER
CALENDAR
CUSTOMER PARAMETER
FACTORY PRAMETER
Run the Parameter Review
Press ‘1’or ‘f’ to move the black cursor over the menu ‘RUN
PARAMETER’and then press ‘ W to popup the submenu:
HOST、FAN CURRENT
TOTAL RUN TIME
CURRENT RUN TIME
MAINTENANCE PARAMETER
Press ‘ W to pop up another menu:
CUR(A):R S T
HOST: 56.1 56.2 56.0
FAN: 4.1 4.1 4.1
If the menu pop up is the last menu level, the black cursor will disappeared, press the RETURN button ‘ RT’ and return to the upper menu or the main interface. If the operation is stopped in a certain interface, it will automatically return to the main interface after several seconds.
Using the moving buttons ‘1W , ‘fW ,CONFIRM button ‘ W return button ‘ RT’ to view the
RUN PARAMETERS such as the CURRENT RUN TIME MAINTENANCE
PARAMETER,
- 21
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
HISTORY FAILURE, PRODUCING DATE and CURRENT FAILURES and then return to the
upper menu with the similar method of the above.
Calendar and Time
Press ‘1’ or ‘f’ to move the black cursor to the menu ‘CALENDAR’ and then press ‘ ’ , the following
menu will be pop up:
DATE AND TIME
2004 Y 2 M 22 D
SUNDAY
12 H 46 M 59 S
At the stop status of the unit, the date and time could be adjusted according to the following steps: Press
‘1’ or ‘f’ to move the black cursor to the parameters you want to modify and then press ‘ ’ to reach the
blinking position. Now the button ‘1’ and ‘f’ are changed to ‘Pageup’ and ‘Pagedown’ button. Press
‘M’ button to confirm and save the data after finish the modification. The buttons ‘1’ or ‘f’ return
to black cursor move button and the button ’ ’ change back to its Return function.
CUSTOMER PARAMETERS
T ip s: T h e C us t o m e r P a r a m e t er s a nd t he F a c t o r y P ara m e t e r s ca nnot b e m od i f i e d du r i ng t he R unn i ng S t a t e a nd S t op D e l a y i ng p er i od
The Customer Parameters could be read and modified with the same method of running the
Parameter Review mentioned above. For example, to modify the parameter BLOCK UNLOAD
PRESSURE, the steps will be as the following:
Press ‘1’ or ‘f‘ to move the black cursor to ‘CUSTOMER PARAMETER’ menu and then press
the CONFIRM button ‘ ’ to pop up the following menu:
SET P、T
ONIOFF DELAY PRESET
OP. MODE PRESET
BLOCK PARA PRESET
Press the CONFIRM button ‘ ’ again to reach the following menu:
LOADING P 0.8MPa
UNLOADING P 0.6MPa
FAN START T
80℃
FAN STOP T:
70℃
The CUSTOMER PARAMETERS can be read now when the CONFIRM button ‘ ’ is not
pressed now. Press the CONFIRM button ‘ ’ again to pop up the following interface where the
password input is needed:
- 22
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
ENTER
A tte n t i o n : The C us t o m e r P a sswo r d ca n be m od i f i e d i n t he C U S T OMER P A R AM ETE R , t he F A C T O R Y P A SS W O R D i s ****
The Blinking Position will appear after this interface displayed. The button ‘1’ and ‘f’ have been
changed to PgUp and PgDown button that could be used to change the current value. The button
‘ ’ is changed to move button to move the position where the modification is needed, Press ‘M’
to confirm and the following interface will be displayed:
BLOCK LOAD P: 0.8MPa *
BLOCK UNLOAD P: 0.6MPa
FAN START T:
80℃ FAN
STOP T:
70℃
When there is a ‘*’
displayed at the up right
corner, it means it is at the
CUSTOMER
PARAMETER set status.
The ‘1’ or ‘f’ button return to black cursor and the button ‘ ’ return to be the CONFIRM button.
Press the CONFIRM button ‘ ’ when the cursor is over the menu ‘ BLOCK UNLOAD PRESSURE’,
now the blinking position appears and the button ‘1’ and ‘f’ have been changed to PgUp and PgDwn
button that could be used to change the current value. The button ‘ ’ is changed to move button to move
the position where the modification is needed, Press ‘M’ to confirm and the blinking position will
disappear. The ‘1’ or
‘f’ return to black cursor move button and the button ’ ’ change back to its CONFIRM button
to continue to modify the other CUSTOMER PARAMETERS. If there are no other parameters needed to
be modified, press the button ‘RT’ to return to the upper menu or the main menu. The other CUSTOMER
PARAMETERS could be modified with the same method above.
The CUSTOMER PARAMETERS menu list
First Submenu Second submenu Preset Value Functions
SET P. T.
UNLOAD P. *.**Mpa Unload pressure value
LOAD P. *.**MPa Load pressure value
FAN START T. ***℃
Control the fan starting. This value will be set to ‘120℃' if there is no fan present or the fan is not required to be protected.‛
FAN STOP T. ***℃
Control the stopping of the fan
- 23
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
HOST START TIME 0008s
FAN START TIME 0006s
When using the controller to protect the motor,
it is required that the time here defined will not
meet the impulse starting current of the motor,
the value here must be longer than the STAR
DELAY TIME plus LOAD DELAY TIME
When using the controller to protect the motor,
it is required that the time here defined will not
meet the impulse starting current of the motor.
STAR DELAY TIME 0006S Star contactor release starting delay time.
The loading delay time after star contactor
ONIOFF DELAY
TIME PRESET
LOAD DELAY TIME 0002S
EMPTY DELAY 0020M
STOP DELAY TIME 0010S
START DELAY TIME 0100S
releasing.
Load free continuous running time, the machine
will automatically stop after this time
The machine will not stop until this time passed
the load free state when stop the machine
Machine can not be restarted before this set time
after stopped or over time operation at load free
state
STANDBY DELAY TIME 0000S Additional functions
The continuous draining time during the
OPERATION
MODE PRESET
DRAIN OPEN TIME 0002S
DRAIN CLOSE TIME 0010M
MachineONIOFF MODE
side
LOAD MODE Auto
COM MODE Prohibited
automatic draining control.
The Draining Gap duration during the
automatic Draining control
When the remote mode is set, both the buttons
at machine side and the remote control button
can turn on and off the machines
When the manual mode is set, the LoadIUnload
function can only be executed by pressing
buttons
When this is set to ‘PROHIBIT’ the
communication function is not available
COM CODE 0255 Communication address
Act as Host or Secondary Machine when there
are more than one machines running in
BLOCKING
PARAMETERS
PRESET
MAINTENANCE
PARAMETER
BLOCKING MODE HOST
BLOCKING ONIOFF Sequence
SWITCHING TIME 9999 Hours
BLOCK NUMBER 0016
BLOCK LOAD P *.**MPa
BLOCK UNLOAD P *.**MPa
BLOCK DELAY TIME 0000S
0000OIL FILTER RESET
HOURS
blocking mode. The HOST controls the
SECONDARY
Reset time for the duration of oil filter changing
- 24
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
PRESET OIA RESET 0000Hours Reset time for OIG Separator changing
AIR FILTER RESET 0000Hours Reset time for gas filter changing
LUB OIL RESET 0000Hours Reset time for Lubricate Oil Changing
LUB GREASE RESET 0000Hours Reset time for Lubricate Grease Changing
Set this value to ‘0’ will make the oil filter
MAX LIFE
TIME PRESET
LANGUAGE
SELECT
NEW USER
PASSWORD
OIL FILTER 9999Hours
OIG SEPARATOR 9999Hours
GAS FILTER 9999Hours
LUB. OIL 9999Hours
LUB GREASE 9999Hours
English
****
alarm not available
Set this value to ‘0’ to disable the OIG separator
alarm function
Set this value to ‘0’ to disable the alarm
function of gas filter
Set this value to ‘0’ to disable the time alarm of
lub. oil
Set this value to ‘0’ to disable the time alarm of
Lub. Grease
Set to ‘ENGLISH’ will change the interface to
be English display.
Customer could modify the user password
FACTORY PARAMETERS
The difference of the FACTORY PARAMETERS and the CUSTOMER PARAMETERS is that
the FACTORY PARAMETERS cannot be modified unless you have the initial password from the
factory. The modification method of the FACTORY PARAMETER is the same as that of the
CUSTOMER PARAMETER. The main functions of the parameters are as the following table.
PARAMETER Initial Value Functions
HOST RATED
CURR.
MAXIMUM
OVERLOAD VALUE
OF THE MOTOR I1.2
After the starting delay time, when the motor current
is greater than 1.2 times of the set value and less than
4 times of the set value, the unit will jump as per
overload feature.
FAN RATED CURR.
MAXIMUM
OVERLOAD VALUE
OF FAN MOTOR I1.2
Same as above
PRE-ALARM T 105℃
Alarm when the temperature reaches this set value
STOP T. 110℃
Alarm when the air exhausting temperature reaches
this set value.
STOP P. 1.00MPaAlarm and stop machine when the air supply
temperature reaches this set value
UNLOAD LIM P 0.80MPaThe Unload Limit Pressure in the Customer
Parameter must be set lower than this value.
MODI LOAD TIME ****Hours The factory can modify the load running time
MODI TOTAL TIME ****Hours The factory can modify the total running time
- 25
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
HISTORY FAULT
RESET****
Input the history failure password to clear all the
history failures.
UNBALANCE
SCOPE0006
When (the max. phase currentImin. phase current) is
greater than (1+set value), the unbalance protection
will stop the machine. If the set value is greater than
15, the unbalance protection will be disabled.
LACK PHASE
STOP0005
Set the LACK PHASE TIME ≥20S, the Lack phase
protection will be disabled.
0000 M
PROD. DATE ****Y**M**D The factory input the product date of the unit.
PROD. NO. ****** The factory input the product No. of the unit
5.2. PLC Functions and Technical Parameters• Switching value:8 ways of switching value input; 10 ways of relay switching value input.
• Analog quantity:2 Pt100 temperature input; 2 ways of 4~20mA transferred input; 2 groups of 3
phase current input (Match with CT)
• Input voltage of phase sequence: 3 phase 460VI230V.
• Working Power of the controller: 100V-220V, 50HzI60Hz, 20VA.
• Display measuring Range:
Oil Temperature of Oil: —20~150℃;
Accuracy: ±1℃. Air Temperature: —20~150℃ Accuracy: ±1℃. Running
Time: 0~999999Hours.
Current Display Measuring Range: 0~999.9A.
Pressure: 0~1.60Mpa, Accuracy: 0.01Mpa.
• Phase sequence Protection: When the protector detects the wrong phase sequence, it activate for the
time≤2s.
• Motor Protection: This control unit has the following 5 basic protection functions.
-Rotor Lock protection: After the starting of the motor, if the working current reaches 4 or 8 times
of the set value, the protection activates. The activate time is less than 0.2s.
-Short-Circuit Protection: if the detected current reaches 8 times or more above the set value,
the protection activates, the activate time is less than 0.2s.
-Lack phase protection: Any of the phase lack, the protection activates and the activate time is
the setting time.
-Unbalance Protection: the current difference between any of the two phases reaches the percentage
of the setting value, the protection activates and the activate time is less than 5s.
-Overload anti-time limitation protection (time unit: s): See the following table. The multiple=I Actual value/I Set Value.
When the running current of the motor is in 1.2 ~3.0 times of the set value, the overload multiple and
action delay time will be accordance with the following table.
IactII set
Time Para≥1.2 ≥1.3 ≥1.5 ≥1.6 ≥2.0 ≥3.0
Action time 60 48 24 8 5 1
-Temperature Protection: When the actual detected temperature is higher than the set temperature,
- 26
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
the protection activates and the activate time≤2s.
-The output relay contactor capacity:250V5A. The life time of the contactors: 500000 times of running.
-The current display tolerance <1.0%.
-RS—485 communications.
Controller installation
The Controller will be installed in the control cabinet. There must be enough spaces around
the controller for the accessibility when making the wiring. The recommended sizes are as below:
1. Input LCD ( IN):00, 01, 02, 03, 04, 05, 06 and 07 is relatively
correspond to the input switching value
terminals of 20, 19, 18, 17, 16, 15, 14 and 13.
2. Output LCD(OUT)00, 01, 02, 03, 04, 05, 06, 07, 08 and 09 is
relatively corresponded to the output
switching value terminals of 27, 28, 29, 30,
31, 35, 36, 37, 38 and 39.
3. Power LCD:PWR 灯4. Running LCD: RUN LCD
5. FAILURE LCD: ERR LCD
Diagram 6:
Main Control Unit
Structure Size
2. The Basic
Wiring diagram of
the
electronic
Installation.
- 27
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Text Display connector terminals:
There are five connect terminals and one D type display cabal connector which are relatively used for the
display connector, Rs—485 communication interface and 24V Power input
Controller Connect Terminals:
The display panel is connected with the controller using communication cabals. 23, 24 and 25 are the
phase sequence input terminals; 7 and 9 are the Air Exhaust Temperature Input terminals; CT1 is the host
mutual inductor; CT2 is the fan mutual Inductor. 32 is the common port COM1 of the relay output; 27
controls the main contactor; 28 controls the star contactor; 29 controls the angel contactor; 30 is the
loading magnetic valve; 31 controls the Fan; 34 controls the Load release valve: 37 is the running
indicator; 38 is the Failure indicator; 39 is the Alarm indicator; 40 is COM2; 42 is the simulated ground
(Earth); 43 and 44 are the 220V power source.
A tte n t i o n : t h e m a g n e ti c c o i l m us t b e c onn ec t e d t o t h e su r g i ng a bso r b e r wh e n w i r i ng
5.3 Control Principle
Individual Control-Local Automatic control (ONIOFF mode: Beside Machine; Loading method: Automatic)
• Press ‘I’ to start:˄Y— Starting When the controller is powered on, it will perform a 3S self-checking. Press the ‘I’ button cannot
start the machine until the self-checking is completed. The starting process of the host will be as the
following: KM3 is powered on, KM2 is Powered on - Y type Starting Status - Time Delay
finish
˄Y— converting time , KM3 loss power (KM1 and KM3 interlocked) ,KM1 is powered on -
Motor runs in type and the Starting is completed. The load magnetic Valves are without
power during the whole starting process to ensure the load free starting.
• Automatic Running Control:
When the motor is started to running in state and load the magnetic valve with power applied
after a certain period of delay. Then the air compressor will be applied with air pressure to increase
- 28
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
the pressure in the air tank. When the air pressure reaches the value over the set unload pressure
(unload pressure value), the loading magnetic valve will loss power and the release magnetic valve is
applied with power to run the air compressor with load free. If in the specified time (load free
running period) the air pressure turns to be lower than the set load pressure (LOAD PRESSURE
VALUE), the load magnetic valve obtains power and the release magnetic valve losses power, the air
compressor will apply normal pressure to increase the pressure in the air tank. If the pressure in the
air tank is not drop down to the load pressure limit within the empty free running time, the controller
will automatically stop the running of the motor to perform the automatic stop of machine for over
time empty free running. Only when the pressure drops to the load pressure limit, the motor could
restart according to the normal starting process and it runs repeat in this way.
• Manual LoadIunload at the automatic status
At the automatic status, the unit will stay in the unload state, press the button ‘1f’ to load, if the
pressure is higher than the unload pressure, the load magnetic valve will inch once and then return to
the unload status; if the pressure is lower than the unload pressure, the load magnetic valve will be
applied with power and will not stop running and return to the unload state until the air supply
pressure becomes higher than the unload pressure. When the unit is at the load state, press the button
‘1f’ to unload. If the pressure is higher than the load pressure, the load magnetic valve will loss the
power and return to the load state till the air supply pressure becomes lower than the load pressure. If
the pressure is lower than the load pressure, the unload function is disable.
• Normal Stopping:
Press the button ‘O’, the load magnetic valve will loss power and the unload magnetic will be
applied with power, after a while of delay (stop delay), the motor contactor will loss power, the host
and fan will stop running, after the restarting delay completed, the unload magnetic will loss power.
Only pressing the button ‘I’ could restart the motor.
• Frequency starting prevents control
The motor can not be started immediately unless after a while of time delay after stopped by pressing
‘O’ button or stopped due to failure. Whenever the situation is, this controller will display the
remaining count down of the time delaying (such as 90s). The motor can only be started when the
time display is 0.
-Remote Automatic Control (ONIOFF mode: Remote; Load mode: Automatic)The remote automatic control is almost the same as the local automatic control, the only difference is
that the start and stop of the unit is controlled by remote control.
-Local Manual Control (OnIOff mode: beside machine; Load mode: Manual)The Starting and stopping control is the same as the automatic control, the only difference is that
when the starting procedure finished in this mode, the machine is at the load free state and will be
loaded by pressing the button ‘1f’. When the air supply pressure is higher than the unload pressure,
the unit will load automatically, if the button ‘1f’ is not pressed to load, the unit will be running at
the load free state till load free stop. During the unload process, press the button ‘1f’ to load and
during the process of loading, press the button ‘1f’ to unload
-Remote Manual Control (OnIOff Mode: Remote; Load mode: Manual)The remote automatic control is almost the same as the local manual control, the only difference is
that the start and stop of the unit is controlled by remote control.
- 29
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Network controlWhen the control network is set to ‘COMPUTER’, it could perform the computer network control
of the units
Set the controller communication to ‘BLOCKING’ could perform the network control between the
controllers but the host must be 1# controller.
Fan Temperature controlWhen the air Exhausting temperature is higher than the fan starting temperature, the Fan motor will
run; when the air exhausting temperature is lower than the fan stop temperature, the fan motor will
stop running. If there is no fan or the fan is not necessary to be protected, set the starting
temperature of the fan to ‘120℃’ and the stop temperature to be ‘70℃’.
Failure stop and Emergency stopWhen there is any electronic failure or high air temperature failures occurred during the running
process, the controller would stop the motor immediately. The motor can only be restarted after the
failures are cleared. Any emergency situation occurred, please press down the emergency stop
button to cut off the power supply of the controller and contactor power.
5.4 Alarm and Notices
Text Display tipsAir filter Alarm tips
• Check the alarm using the switch signal
The controller can display the message on the text display to remind the operator that ‘ the air
filter is blocked’ by checking the pressure difference switch operating state.
• Set the running time alarm of the air filter
The Text displays ‘Air filter life terminated’ when the using time of the air filter terminates.
Oil Filter alarm tips
• Check the alarm using the switch signal
The controller can display the message on the text display to remind the operator that ‘ the oil
filter is blocked’ by checking the pressure difference switch operating state.
• Set the running time alarm of the oil filter
The Text displays ‘Oil filter life terminated’ when the using time of the oil filter terminates.
Oil separator alarm tips
• Check the alarm using the switch signal
The controller can display the message on the text display to remind the operator that ‘ the oil
separator is blocked’ by checking the pressure difference switch operating state.
• Set the running time alarm of the oil separator
The Text displays ‘Oil separator life terminated’ when the reach using time of the oil separator.
Lubricate Oil alarm tips
• The Text displays ‘Lubricate Oil life terminated’ when reach the using time of the lubricate oil .
- 30
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Lubricate Grease alarm tips
• The Text displays ‘Lubricate Grease life terminated’ when reach the using time of the lubricate.
Main Controller Tips
Item Meaning and Functions Lights Status
POWER Controller Power on PWR Lights
RUN Controller run RUN Lights
Failure Detect failure and Stop the unit ERR Blinking
Input Switching
Value
Terminal 20~12 Input switching
value activate
IN00~08 lights, but if there is no function at the
input point, no light lighting
Output Switching
Value
Terminals 27,28,29,30,31,35,36,37,38
and 39 output switching value activateOUT00~09 lights
Data Save Set Data and save time PWR blinking once
5.5 SAFETY PROTECTION
Motor Protection
• MAM — KY02S air compressor controller can perform the short-circuit protection, rotor
lock protection, overload protection, Phase Lacking Protection and Unbalance Protections to the motor.
Electronic
failureFailure Display Possible Causes
Short-CircuitLocal Failure display ‘Host or Fan
short-circuited’
Short-circuited or the rated current is
wrongly set
Rotor lockLocal Failure display ‘Host or Fan Rotor
Locked’
Overloaded, Bearing wear off or other
mechanic Failures
OVERLOADLocal Failure display ‘Host or Fan
Overloaded’
Overloaded, Bearing wear off or other
mechanic Failures
Phase LackLocal Failure display ‘ Host or Fan
Phase Lacking’
Phase lacking occurred to the Power or the
connectors
UnbalanceLocal Failure display ‘ Host or Fan
current unbalance’.
Contactors are not contacted correctly or
the motor inner parts open.
Air Exhaust overheat protection
• When the air exhaust temperature is higher than the set limited unload temperature, the controller will
alarm and stop the machine. Local Failure display ‘Air Exhaust High Temperature’.
• Reverse running protection of the air compressor
- 31
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
A t t e n t i o n : W h e n t h e ph a s e s e qu e n c e of t h e p ow e r c onn e c t e d t o t h e a i r c o m p r e ssor i s not c on f o r m t o t h e s e t of t he c on t r o ll e r , t h e l o ca l f a i l u r e d i sp l a y s ‘ W r o n g ph a s e s e qu e n c e ’ a nd
a s a r e su l t t h e c on t r o ll e r ca n no t s t a r t t h e m o t o r . I t i s n ee d e d t o c h e c k a nd a lt e r n a t e a n y t wo of
t he phase sequence and i nvesti gat e t he m ot or rot at ion di recti on.
Over Pressure protection
When the pressure of the air exhaust is higher than the set stop pressure of the controller, the controller
will alarm and stop the machine, the local failure displays ‘Pressure too high’.
Sensor Failure Protection
When the cable of the pressure sensor or the temperature sensor is broken, the controller will alarm and
stop the machine and the local failure displays ‘** sensor failure’.
5.6 History failure record check
The failures caused by the peripheral equipments of the controller could be investigated by
queering from the local failure record or the history failure record to find out the failure causes and
solves the relative problem.
- 32
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
5.7 Circuit diagram
- 33
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
6. Maintenance
6.1Maintenance items and maintenance periodCompressor will not be in a good motion, unless it gets adequate maintenance. Right maintenance can
prolong its service life and greatly cut down the time of stopping due to failure.
Daily manipulation
Before starting up: drain out the condensate water in the bottom of oil separation until some oil flows out.
And check if the oil level is in correct position.
Attention: Don’t open oil-discharging ball valve until five minutes later after stopping
After starting up: Watch the pressure on the control panel. Check manipulating temperature and the general
conditions inside compressor. Check if there is leakage on the outer surface of cooler or on bolts.
Maintenance plan
Check the running temperature and working pressure. (Every day)
Put down the current, voltage, temperature and pressure. (Every day)
Clean compressor. (Only after stopping). (Every week)
Blew wash the ail filter. (Every week)
Check oil level. (Every month) Check the bolts on the belt pulley (shaft coupling). (Only after compressor
stopping)
Blew wash cooler. (Every month)
Make maintenance every 500 hours
Check the quality of oil. If it is qualified, it can be used again after be filtered cleanly. Otherwise, replace it.
Replace the core of oil filter
Replace the core of intake filter
Replace the core of oil separation
Replace the filtering net of oil return pipe
Check the fatness of belt pulley or the labiality of the shaft coupling.
Attention: Reduce the replacing time, if the environment is spoiled excessively.
Every 2000 hours
Replace the core of oil filter
Replace the core of intake filter or intake filter
Check and adjust the fatness of belt pulley or the labiality of shaft coupling.
Check intake-controlling valve
Every 4000 hours
Replace lubricant
Replace the core of oil separation or oil separation
Replace the minimum-pressure control valve
Check thermostatic valve
Check if the electronic lead is tight
Check if main bolts, main nuts and connectors are tight.
Check the security apparatus
- 34
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
G u a r d f o r m a i n t e n a n ce
D on ’ t r epa i r and m a i n t a i n co m p r e ss or i f co m p r e ss or i s i n m o ti on or t he r e i s p r e ss u r e i n it . F irst , st op it , and
t hen m a i n t a i n i t a ft er i nner p r e ss u r e i s r e l ea s ed.
A ft er fi n is h i ng t he r epa i r and m a i n t enance w o r k, check f u l l y i f c o m p r e ss or i s a ss e m b l ed and s et w e l l and i f
all fixing parts and sealing parts are installed well.
Maintenance method for intake filter
1. Open the end cover
2. Take out the filter core
3. Check the condition of intake filter (if it is not good, replace it)
4. Clean out the dust accumulating on the bottom cover
5. Replace it with a new filter core
6. Fix the end cover well.
Maintenance method for oil filter
1. Screw out the old filter with pliers
2. Clean the touching surface
3. Lay a thin film of oil on the seal ring of new filter
4. Press the filter with handle until the washer is sealed
5. Check if there is leakage after starting up
- 35
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Maintenance method for cartridge of oil separator
The method of external type is the same as the oil filter
The method of built-in type is as follow:
1. Open the service wicket door
2. Loosen the connector between pipe and minimum-pressure valve
3. Loosen the pipeline on the cover of oil separation. Make sure it can be reinstalled.
4. Loosen the fixing bolts on the oil separation
5. Lift up the cover board slightly, and then clean the oil return pipe
6. Take out the oil separation cartridge
7. Replace the oil separation cartridge and washer
8. Install it according the reverse procedure. Check the length of oil return pipe (Refer to the maintenance
method for oil return pipe)
9. Screw down every bolt with torque spanner.
10. When compressor is started up and reaches the manipulating temperature, screw down the bolts of cover
board of oil separation cartridge
- 36 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Features of intake valve, solenoids valve and its maintenance method
Intake-controlling valve is mainly composed of valve body, valve gate, piston, cylinder, spring and seal ring
and so on. And there is a controlling plate and an electromagnetic control valve on its side. They are with the
functions such as load shedding, noise elimination, depressurizing, stopping to release thoroughly,
adjustment of on or off, and so on. A small part of air is output through the vintage of intake-controlling
valve to balance the amount of sucked air through the vintage. This can keep the pressure in the separation
element in the range of 0.2-0.3 Mpa. So that lubricant can be in a normal cycle. The pressure sensor and the
electromagnetic valve of adjusting system control the action of on or off of intake-controlling valve
automatically. The agility of the action of on or off is very important for the reliability of compressor. So
compressor must be maintained periodically, and then it will be in a good motion. When maintaining is being
done, parts should be dismantled to check the worn condition on every friction surface. Special attention
should be paid to the surface of rubber seal ring. If there is damage or crack on it, it must be replaced. On
reinstalling then, every part should be cleaned up and lubricant should be laid on the friction surface of every
metal part.
Maintenance method for minimum-pressure valve and temperature control valve
1. Screw out the lid, pay attention to the spring force of the valve.
2. Take down the lid,
3. Check if there is abrasion on the O-type ring of the piston. If so, replace the ring.
4. Check if there is abrasion on the seal ring. If so, replace it.
5. Lubricate them with high temperature grease. Reinstall them according the revere direction.
- 37
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Exchanging method for lubricant
1. Stop compressor
2. Connect up oil-discharging pipe, then open the ball valve, and then drain the oil into the oil-recycling
can.
3. Close the oil-discharging ball valve, then open the oil filling cover, and then refill new oil until the
oil level is in the center of oil gauge.
4. Fix the oil filling cover, and then check if the O-type ring is in the correct position.
5. Start up the compressor. Check the oil level after compressor running for a while. If oil lever is lower,
properly fill oil again.
A tt en ti on: s ho r t d o w n t he r e p l ac i ng pe ri od w h e n t he r e i s t oo m uch du s t or t he m an i pu l a ti ng t e m pe r a t u r e
is too high.
Oil level:
Maximum oil level: oil level is in the center of oil gauge, after compressor stopping for 30 minutes.
Minimum oil level: oil level is in the lower part of oil gauge when compressor is running.
Adjusting method for tightness of belt
1. Stop
2. Shift out wicket door
3. Loosen the fixing bolt for security under motor base. (Three-fourths ring tightness is always kept)
4. Rotate the adjusting bolt, then adjust the tightness of belt until getting the right tightness
5. Screw down the fixing bolt of gear end
Method for replacing belt
The method is the same as the method of the adjusting method for tightness of belt. First, adjust the belt
loose enough, then replace it with a new one, and then adjust the tightness.
Attention: After replacing it, adjust the new belt once 5 minutes later after starting up, and then adjust it
once again 10 minutes later after starting up again
T i p : f u l l g r oup of be lt s s hou l d be r ep l aced at one ti m e. I t i s not a ll o w ed t hat r ep l ace one or s o m e be lt s of
them at one time.
Adjustment of belt pulley
The parallelism of belt pulley should be adjusted again when the motor or air end is moved or reinstalled.
Poor parallelism of belt pulley will cause belts be abraded quickly, thus reduce the service life of belts
and belt pulley. Insure the two belt pulleys in the same plane. First, fix the belt pulley of gear end in the
right position, and then adjust the belt pulley of motor to let them be in the same plane.
Centering of flexible shaft coupling
The flexible shaft coupling must be centered when the motor or gear end is moved or reinstalled. And
parallelism and axiality must fall into the range of 0-0.05mm
Maintenance method for motor
A lubricant should be applied on the motor bearing every 1500 hours. (Use shell Alvania RL3, if not
specified.) Clean up the grease with a clean duster cloth. Run the motor in a unload state after belt pulley
being dismantled. Don’t stop applying new lubricant when motor is running, until all original oil is
drained out through the oil-discharging ventage (Oil-discharging ventage is under the bearing cavity).
Finally, Wipe away the excessive grease. (Excessive grease does harm to bearing)
- 38
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
7. Explored drawing
PACK SERIES (4-15kw)
- 39 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
- 40
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
SC SERIES (18.5-250KW)
- 41 -
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
8. Troubleshooting:
FAULT POSSIBLE REASON SOLUTION
Compressor does not start
1、 no electric power to
compressor, switch or emergency stop button does not closed
2、sequence of phases is not correct or phase lacking
3、overload protection relay does not reset
4、fuses or electrical contactor are defective
check electrical connection
check or interchange two phases
(L1,L2 or L3) in the power cable
reset it with hand
check it, replace if necessary
Compressor is difficult to start and stop automatically in
start process due to high current
1、under- voltage or three phasevoltage is not balance
2、electrical connection is flexible
ensure constant voltage in accordance with IEC Standard
check and tighten connection
3、compressor can not vented perfectly
check intake valve and replace if necessary
4、compressor oil is very
viscous due to low ambient temperature
5、minimum pressure valve does not closed perfectly
heat up the compressor before startup
check the valve spring and replace if necessary
Compressor stop automatically in working process due to over load
1、exhaust pressure is exceed
rated valuecheck and adjust unloading pressure value
2、setting value of overload
protection current is not correct
3、oilIair separator is jam
check and adjust setting current value of main motor or fan motor
check it, replace if necessary
4、pressure control or sensorfault
check pressure sensor, switch or computer controller
- 42
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
5、screw air end or main motor is defective
simple examine through rotate it with hand, repair or replace if necessary
Compressor stop automatically in working process due to over heat
1、insufficient oil quantity or use
incorrect type oil
2、cooling unit soiled or internal jam
3、ambient temperature too high˄≥40
fill oil and ensure oil level is not below than “minimum level” mark, use original manufacture oil only
clean cooling unit
improve air ventilation of compressor room
4、insufficient vent cooling air clean and keep air inlet vent opening
5、oil filter or thermostatic valve cartridge jam
clean it , replace if necessary
6、cooling fan fault check and replace if necessary
7、temperature sensor PT100 defective or wire break
check and replace if necessary
8、oil pipe leakage fasten and seal oil pipe coupling
Excessive oil consumption
1、oilIair separator element is
defective
2、excessive oil filling
3、oil-return line jam
check and replace if necessary
drain off some oil, ensure oil level is not higher than “maximum level” mark
check and replace one-way valve if necessary
4、working pressure is too low for long time˄≤0.6MPA
5、use incorrect oil, more foam and low viscous
user should reduce compressed air consume to let pressure increase
use original manufacture oil only
- 43
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
6、too many condense water in
internal system due to high humidity climate
drain condensation water from oil tank promptly
No compressed air exhaust , no pressure build up
1、intake valve does not open intake controller or solenoid valve is defective, or air pipe connected to controller is leakage, check and replace if necessary
2、discharge solenoid valve is defective
check electric supply and clean valve holes, replace if need
3、minimum pressure valve does not open
check minimum pressure valve spring , replace if necessary
4、components in compressor are leaking
check oil and air lines in compressor, tighten and reseal screw coupling connections
5、V-belts are slipped or torn check and replace if necessary
System pressure does not decrease when reach rated pressure value
1、intake valve does not closeintake controller or solenoid valve is defective, or air pipe connected to controller is leakage, check and replace if necessary
2、discharge solenoid valve is defective
check electric supply and clean valve holes, replace if necessary
3、system pressure control faultcheck pressure sensor, pressure switch or computer controller, replace if necessary
Oil or oil smoking in intake filter when sto
Exhause volume decrease
1、intake valve is leaking check and replace if necessary
2、press Emergency Stop
p Button when compressor is in loading
switch off compressor using OFF Button, only use the Emergency Stop Button in emergencies
3、minimum pressure non-return valve is leaking
check and replace if necessary
4、Excessive oil in air
1、air vent, intake filter or oilIair separator jam
see the reasons of excessive oil consumption
clean and replace if necessary
2、intake valve does not move perfectly
check and replace if necessary
- 44
-
DMC SCREW COMPRESSOR SHANGHAI DAVEY MACHINERY CO., LTD
Compressor load/ unload very frequently
Abnormally noise and vibration in compressor
3、components in compressor are leaking
1、pressure difference value incorrectly set
2、air consumptions is not steady
3、external units of the
compressed air treatment jam
4、ball valve at compressor outlet closed
1、fixed screw on the base is released
2、V-belts are slipped
3、friction with fan vane and edge
4、compressor install improperly
5、screw air end or motor is defective
check air lines in compressor, tighten and reseal screw coupling connections if necessary
adjust pressure difference value, not smaller than 0.15MPA usually
use a bigger volume receiver tank
clean external air pipeline ,air dryer or air filter , replace if necessary
open ball valve
tighten screw
adjust v-belts tension, replace if necessary
adjust fan vane
mounted compressor in flat ground
check air end or main motor and fan
motor, repair if necessary
Safety valve blows
1、operating pressure has been misadjusted
2、safety valve is defective
3. System internal pressure has exceed over setting pressure of safety valve
set operating pressure to the maximum permissible pressure range of compressor(see value in nameplate)
replace safety valve
Check and replace airIoil separator if necessary
- 45
-