condensing boiler technology

29
Issue 2015-01 Condensing boiler technology

Upload: phungdiep

Post on 01-Jan-2017

273 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Condensing boiler technology

Issue 2015-01

Condensing boiler technology

Page 2: Condensing boiler technology

2 3

About ebm-papst 4

Laboratory equipment 8

Systems for condensing boiler technology 10

Radial blowers 16

Gas valves 34

Burner controls 42

ebm-papst representatives & subsidiaries 48

Content

Page 3: Condensing boiler technology

4 5

ebm-papst Landshut is the ideal partner for developing heating units.

ebm�papst Landshut is THE ideal partner for developing heating

systems.

Condensing boiler technology has been advancing steadily since the

1990s. ebm-papst Landshut has been the top supplier for premix

blowers for just as long. We were there from the start. We developed

and supplied the world’s first blower for condensing boiler technology.

However, we also developed ourselves, evolving from the largest

supplier of premix blowers to a developer of complete systems for

condensing boiler technology consisting of a blower, venturi, valve and

burner control. That, too, remains unmatched anywhere in the world.

Page 4: Condensing boiler technology

6 7

Sustainability is at the centre of ourthoughts and actions. Out of conviction!

Eco-friendliness and sustainability have always been at the core of our thoughts and actions. For decades, we have worked according to the

simple but strict creed of our co-founder Gerhard Sturm: “Each new product we develop has to be better than the last one in terms of economy

and ecology.” GreenTech is the ultimate expression of our corporate philosophy.

GreenTech is pro-active development.

Even in the design phase, the materials and processes we use are

optimised for the greatest possible eco-friendliness, energy balance

and – wherever possible – recyclability. We continually improve the

material and performance of our products, as well as the flow and

noise characteristics. At the same time, we significantly reduce ener-

gy conumption. Close co-operation with universities and scientific

institutes and the professorship we endow in the area of power engi-

neering and regenerative energies allows us to profit from the latest

research findings in these fields – and at the same time ensures

highly qualified young academics.

GreenTech is eco-friendly production.

GreenTech also stands for maximum energy efficiency in our produc-

tion processes. There, the intelligent use of industrial waste heat and

groundwater cooling, photovoltaics and, of course, our own cooling

and ventilation technology are of the utmost importance. Our most

modern plant, for instance, consumes 91% less energy than currently

specified and required. In this way, our products contribute to protect-

ing the environment, from their origin to their recyclable packaging.

GreenTech is acknowledged and certified.

Every step in our chain of production meets the stringent standards

of environmental specialists and the public.

This supports our position as Germany’s most sustainable company

2013, as does the DEKRA Award 2012 we received in the category

“Umwelt – Herausforderung Energiewende / Environment – Chal-

lenge: Transition to more sustainable energy systems”, to name only

a few of a large number of examples. The environmental advantage

gained in the performance of the products developed from our

GreenTech philosophy can also be measured in the fulfillment of the

most stringent energy and environmental standards. In many instanc-

es, our products are already well below the thresholds energy legisla-

tion will impose a few years from now – several times over.

Our customers profit from this every day.

The heart of GreenTech is future-oriented EC technology from ebm-

papst. The EC technology at the core of our most efficient motors and

fans allows efficiency of up to 90%, saves energy at a very high level,

significantly extends service life and makes our products mainte-

nance-free. These values pay off not only for the environment, but

every cent also pays off for the user! All ebm-papst products – even

those for which GreenTech EC technology does not (yet) make sense

from an application viewpoint – feature the greatest possible connec-

tion of economy and ecology.

GreenTech isacknowledgedand certified.

GreenTech ispro-active

development.

GreenTech iseco-friendlyproduction.

GreenTechfollows a firmphilosophy.

GreenTechpays offfor our

customers.

Page 5: Condensing boiler technology

8 9

Air performance test rig

Multiple air performance test rigs are available. They test the operat-

ing performance of the blowers and plot the air performance curves.

Spectrum analyser

The spectrum analyser can be used to measure line-bound interfer-

ence. Since our devices are used for further processing in expert

industrial companies, we are not actually required to test their elec-

tromagnetic compatibility (EMC measurement). Nevertheless, we

would like to offer this service to our customers. This tests whether

the motors fulfill the requirements of EN-55014-1, thus ensuring that

there is no interference with devices in the environment.

Climate chamber

Multiple climate chambers are available in various sizes. They enable

endurance tests to be carried out in a variety of ambient conditions

(temperature, humidity, air pressure). This also makes it possible to

determine the service life of the devices.

We have the research and development expertise needed for

continuous improvement in today’s world: Dedicated, intelligent engi-

neers and technicians who work to further develop products, co-op-

erating with our customers’ development teams. The range of analy-

ses is not limited to harmful emissions. We also analyse and optimise

EMC and noise emissions.

We support our customers in the development of applications from

the very beginning. Only when all of the necessary characteristics are

present does the product go into production. The tests required for

this purpose include both inspections for complying with legal man-

dates and specific customer requirements. Numerous measuring de-

vices are available directly at the Landshut location for this purpose.

For example, we also test for design effects, such as changes to the

gas-air manifold, check valves or the venturi. All of these factors can

influence the efficiency – as well as the noise level and function –

of a condensing boiler and must be taken into account when match-

ing the individual components to each other.

Gas laboratory

ebm-papst Landshut has a gas laboratory with state-of-the art

measuring devices. The laboratory can also take into account coun-

try-specific differences, as each country has its own legislation for

the composition of the gases and the minimum and maximum supply

pressure. The inlet pressure in the supply line can be varied to show

the effects of various supply networks. In addition, all testing and limit

gases commonly used in Europe, America and Asia are available.

We carry out exhaust gas measurements (CO2, CO, lambda) and

measurements with variable aerodynamic parameters (venturi pres-

sure, modulation range, mass flow). The climate chamber also allows

both short-term and endurance testing of external variables such

as temperature and humidity. Wind and turbulence at the air-intake

area can also be simulated. The volume of condensate produced by

the condensing effect can be determined to measure the efficiency of

the system.

Noise measurement laboratory

The noise behaviour of our blowers and systems is tested in our

soundproof noise measurement laboratory featuring state-of-the-art,

high-precision sound measuring systems. By the way, these are the

same real-world conditions in which they are built into our custom-

ers’ products.

Additional equipment

Our equipment also includes a high-resolution 3D microscope and

a 3D plotter for rapid prototyping, which can be used to fabricate

plastic parts for tests on short notice.

We can also carry out vibration tests to simulate mechanical loads,

such as those that occur during transport of the blowers. Equipment

for testing the type of protection is also available. They allow ambient

influences to be tested based on DIN EN 60529.

Laboratory equipment

Page 6: Condensing boiler technology

10 11

Systems for condensing boiler technology

Page 7: Condensing boiler technology

12 13

Gas blowerState-of-the-art blower technology for modulating operation with low noise and a long service life.

Condensing boiler versus conventional heating.

The difference is that in condensing boiler systems, the water vapour

present in the exhaust is condensed before exiting the fl ue and is used

to extract additional heat. Relative to conventional heating systems,

which do not use this effect, this allows a signifi cantly higher effi cien-

cy of up to 111% to be attained relative to the lower heating value.

Burner control with displayIn co-operation with ebm-papst Heating Systems, the electronic control is matched precisely to the system. Signals from the burner con-trols can be read out in the lab using LabVision software.

VenturiThe pressure generated by the venturi effect provides an optimum mixture of gas and air in the pneumatic gas-air ratio control.

Gas valveThe part required for the correct gas quan-tity has a particularly compact design.

Systems for condensing boiler technology

In times of increasingly scarce raw materials, existing energy sources

have to be used as effi ciently as possible. Therefore, it is important

to replace the old conventional heating units with high-effi ciency con-

densing boiler systems.

Design of a condensing boiler heating unit.

What can we supply you with? And what do you get out of it?

System gas-air assembly

Air Gas

GasVenturi

Blower

Burner Control with display

Burner

Gas-

air m

ixtu

reGa

s-ai

r mix

ture

on/o

ff

Valve

Perfectly matched components of a condensing boiler.

The mixture ratio of gas to air is critical for the energy yield during

combustion. If the gas content is too high, we refer to the mixture as

being too rich. Since there is not enough oxygen available, the gas is

not completely burned off and it is dissipated with the exhaust gas.

This not only wastes a lot of energy, the exhaust gases also contain

undesirable products such as carbon monoxide (CO) and carbon par-

ticulate matter. The opposite situation – when the gas content is too

low – can, in extreme cases, cause the fl ame in the burner to go out.

Therefore, having the correct mixture is of critical importance. This

is attained only if the system is optimally matched for premixing gas

and air or oxygen. This is not so easy in practice. Just one example

of a problem is the different gas qualities. Natural gas has a high

methane content and thus a lower gross calorifi c value than liquid

gas, which consists primarily of propane and butane mixtures. Bio-

gas is also being used more and more frequently. The mixture ratio

must be adjusted exactly to the gross calorifi c value of the different

gas families – as must the air pressure and the temperature of the

intake air and the supply pressure in the gas line.

Another challenge is the fl exibility of the heat output. The greater

the modulation range of a heating system, the better the heat output

can be adjusted to the current demand. The limits of the modulation

degree are determined by the minimum and maximum output of the

premix blower. Even at a low heat output, the system has to have the

ability to set the optimum mixture ratio. For this purpose, the compo-

nents – blower, venturi, valve and burner control – have to be ideally

matched to each other.

If these components are purchased from different manufacturers,

confi guring the interfaces and the operating performance optimally

is an arduous task. Therefore, it is only logical for us to supply all

four components as a fi nished system for premixing from a single

source. This enables our customers to focus entirely on their core

skills.

The following illustration shows the function of these

components.

Figure 1: Schematic design of a system

on/offSpeed control

Page 8: Condensing boiler technology

14 15

Heating range [kW] Part number

Venturi 1 2 – 15 55734.33000

Venturi 2 5 – 28 55734.33010

Venturi 3 7 – 35 55734.33020

204 mm

178 mm

157 mm

253 mm

213 mm

234 mm

224 mm

175 mm

163 mm

Heating range [kW] Part number

Venturi 1 3 – 23 55734.32010

Venturi 2 5 – 28 55734.32020

Venturi 3 7 – 42 55734.32030

Heating range [kW] Part number

Venturi 1 15 – 90 55724.10000

Venturi 2 24 – 145 55724.10010

Our system solutions at a glance

In heating engineering, it is essential that all components are perfect-

ly co-ordinated in order to attain optimum output and efficiency.

Therefore, we offer you complete heating systems from a single

source, including gas blower, venturi and gas valve.

A substantial advantage of our venturi tubes is their optimum mixture

ratio with simultaneously high modulation ranges. To achieve this

high efficiency, we offer a variety of venturi inserts for the multi-

venturi tubes tailored to specific heating capacity ranges. In addition,

solutions with a multi-venturi offer a wide variety of options for ar-

ranging our systems in your devices. This gives you the advantage of

having the most flexible and space-saving integration possible.

For potential mounting positions, please refer to page 18. For addi-

tional potential attachment positions for a valve or specific attach-

ments for air conduction, please contact us.

A burner control perfectly matched to the system is also possible

thanks to our system partnership with ebm-papst Heating Systems,

the Netherlands-based specialist for intelligent control technology.

This can be mounted directly on the system or remotely.

We supply our systems as completely tested and fine-tuned units

with optimised interfaces to save you time and money.

Systems at a glance

NRV 77 The system for heat outputs from 2 to 35 kW

NRV 118 The system for heat outputs from 3 to 42 kW

NRV 137 The system for heat outputs from 15 to 145 kW

Consisting of:

– Gas blower NRG 77 with multi-venturi

– Gas valve GB-ND 055 E01

Sample on request.

Consisting of:

– Gas blower NRG 118 with multi-venturi

– Gas valve GB-ND 055 E01

Consisting of:

– Gas blower NRG 137 with multi-venturi

– Gas valve GB-ND 057 D01

Sample on request.Sample on request.

Page 9: Condensing boiler technology

16 17

Radial blowers

Page 10: Condensing boiler technology

18 19

Mounting positions

Mounting positions 1 to 5 are possible in general. For vibration-

cushioned motor installation, the motor weight is also supported by

an elastic element. Therefore, the mounting position must be speci-

fi ed. Consultation is required in conjunction with our systems and for

mounting position 6.

Venturi tubes

Venturi tubes provide for the correct ratio of air fl ow to gas fl ow.

In addition to this, the venturi’s effi ciency determines the maximum

possible modulation degree of the heating system.

Here you see the possible rotation between venturi and blower –

the gas valve is also pictured for clarifi cation:

Potential mounting positions for the multi-venturi

You can obtain further details on the available venturi variants from

your contact person on-site.

Commutation electronics

The motor electronics are integrated into the blower unit. This en-

sures that the commutation electronics are optimally tuned to the

motor. Shutoff of rotor locking and overload protection are options

that can be integrated. In individual cases, adaptation to the burner

control is required.

Speed output

The blowers with the designation HRG, NRG and RG have a Hall IC

signal output with two pulses per revolution. The G3G 250 MW has

fi ve pulses per revolution, while the G1G and G3G each have three

pulses per revolution. In the case of motors for mains voltage opera-

tion, the speed signal output is galvanically isolated.

Speed control

The speed is controlled by a pulse-width modulated signal (PWM).

You can obtain more information from your contact person on-site.

ErP 2015

ebm-papst fans with GreenTech EC technology meet the legal

requirements for ErP directive Step 2 (by 2015). This directive applies

to devices with an output greater than 125W. This catalogue provides

information on blowers NRG 137, RG 148, RG 175, G1G and G3G.

1 2 3 4 5 6

Modern gas-fi red or oil-fi red modulating condensing boilers have

to be supplied with the ideal volume and composition of air and fuel,

whatever the operating state and external conditions. Controllable

blowers with a steep pressure-fl ow rate curve and a high pressure

maximum are required for this purpose. ebm-papst played a critical

role in the development of suitable EC blowers for this and now offers

the most extensive product line for this application area. The special

properties of these blowers can, however, be used for many other

applications as well. Some examples of this include gas-powered

cookers in the food service industry and gas-powered deep fryers for

commercial use.

Basic structure

Housing

The housing of NRG, RG and G1G/G3G blower types are made of

die-cast aluminium, the housing of the HRG 134 is made of PA6 GF

plastic. The tight sealing required for gas-premix technology is

achieved by a special seal for the housing halves and the drive shaft

entry point. The special requirements, inspections and approval

criteria are co-ordinated for each individual case. The required safety

inspections for the complete functional unit have to be carried out

by the manufacturer of the terminal device.

Impellers

The impellers of HRG, NRG and RG blower types consist of pentane-

resistant plastic. They are dynamically fi ne-balanced. Models G1G 170,

G3G 200 and G3G 250 have impellers made of aluminium sheet.

Drive

The drive consists of brushless direct current (EC) motors with

integrated electronics. The motor has a vibration-free mounting to

minimise structure-borne noise.

Type of protection

The blowers fulfi ll the IP20 type of protection with cover, depending

on the mounting position.

Protection class

The motors fulfi ll the requirements for protection class I.

Bearings

Maintenance-free ball bearings covered on both sides provide for

durability and running smoothness.

Overview of blowers

Our comprehensive product portfolio offers blowers for heat output

values from 2kW to 1MW. The overview shows the available blower

types and the application area that we recommend. Please note that

the heat output actually attained in the end device depends on vari-

ous factors.

The gas type, burner and heat exchanger are just a few of the com-

ponents responsible for achieving a certain output.

0.5

Heat load in kW

1000750250 500

G3G 250 MW

G3G 250

G3G 200

G1G 170

RG 175

NRG 137

RG 148

RG 128

NRG 118

NRG 77

Radial blowers

Page 11: Condensing boiler technology

20 21

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

NRG 77 230 50/60 78 1650 50 12500 60 80 55667.70030

Subject to alterations.

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

NRG 118 230 50/60 95 2500 75 8500 60 80 55667.31160

Subject to alterations.

12000

10000

8000

6000

4000

2000

10 20 30 40 50 60 70 80

12000

10000

8000

6000

4000

2000

10 20 30 40 50 60 70 80

2400

2000

1600

1200

800

400

10 20 30 40 50 60 70 80

2400

2000

1600

1200

800

400

10 20 30 40 50 60 70 80

Curves Curves

– Material: Housing: Aluminium

Impeller: Plastic

Motor protection cap: Plastic

– For potential mounting positions, page 18

– Multi-venturi available

– Mains connector X, interface connector W and interface see page 31 ff.

Dimensions in mm. Dimensions in mm.

NRG 77 NRG 118

– Material: Housing: Aluminium

Impeller: Plastic

Motor protection cap: Plastic

– For potential mounting positions, page 18

– Multi-venturi available

– Mains connector X, interface connector W and interface see page 31 ff.

Page 12: Condensing boiler technology

22 23

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

RG 128 230 50/60 150 2500 110 8400 60 80 55667.22510

Subject to alterations.

Curves

2400

2000

1600

1200

800

400

12000

10000

8000

6000

4000

2000

20 40 60 80 100 120 140 160 20 40 60 80 100 120 140 160

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

RG 148 230 50/60 230 4300 200 9500 60 80 55667.25230

Subject to alterations.

Curves

3750

3000

2250

1500

750

9000

7500

6000

4500

3000

1500

30 60 90 120 150 180 210 240 30 60 90 120 150 180 210 240

Dimensions in mm. Dimensions in mm.

RG 128 RG 148

– Material: Housing: Aluminium

Impeller: Plastic

Motor protection cap: Plastic

– For potential mounting positions, page 18

– Mains connector X, interface connector W and interface see page 31 ff.

– Material: Housing: Aluminium

Impeller: Plastic

Motor protection cap: Plastic

– For potential mounting positions, page 18

– Mains connector X, interface connector W and interface see page 31 ff.

Page 13: Condensing boiler technology

24 25

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

NRG 137 230 50/60 235 3500 190 9000 60 80 55667.33110

Subject to alterations.

Curves

3000

2500

2000

1500

1000

500

9000

7500

6000

4500

3000

1500

30 60 90 120 150 180 210 240 30 60 90 120 150 180 210 240

3750

3000

2250

1500

750

50 100 150 200 250 300 350

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

RG 175 230 50/60 390 3700 275 7800 60 80 55667.14090

Subject to alterations.

Curves

9000

7500

6000

4500

3000

1500

50 100 150 200 250 300 350

Dimensions in mm. Dimensions in mm.

NRG 137 RG 175

– Material: Housing: Aluminium

Impeller: Plastic

Motor protection cap: Plastic

– For potential mounting positions, page 18

– Multi-venturi available

– Mains connector X, interface connector W and interface see page 31 ff.

– Material: Housing: Aluminium

Impeller: Plastic

Motor protection cap: Plastic

– For potential mounting positions, page 18

– Mains connector X, interface connector W and interface see page 31 ff.

Page 14: Condensing boiler technology

26 27

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

G1G 170 -AB53-01 230 50/60 620 3000 360 5830 55 80 55600.01270

G1G 170 -AB53-801 230 50/60 620 3000 360 5830 55 80 55600.01350

Subject to alterations. 1) With linear input (0-10 VDC).

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

G3G 200 -GN20-01 230 50/60 1150 2900 890 6100 60 60 55600.03030

Subject to alterations.

G1G 170 G3G 200

– Material: Housing: Aluminium

Impeller: Plastic

Motor protection cap: Plastic

– For potential mounting positions, page 18

– Mains connector X, interface connector W and interface see page 31 ff.

– Material: Housing: Aluminium

Impeller: Plastic

Motor protection cap: Plastic

– For potential mounting positions, page 18

– Mains connector X, interface connector W and interface see page 31 ff.

3000

2400

1800

1200

600

100 200 300 400 500 600 700

Curves

detail V

enlarged

slot for O-ring fixing

Ø110

9,5

3

6xM

8 3,5

Ø140

±0,

3

Ø 78

176 +3

257±2

273

±2

101 15

8

76,5V

view Z

cover for motorand electronics

3-pole header

5-pole header

pressure tappingconnection possible

60

120

140

97+

1

93,5

+1

Z

9

43,5X/W

5

123

135

2500

2000

1500

1000

500

200 400 600 800 1000

Curves

detail V

323,2

168 6x60°

90 ±0,1

235,5 =1,5

57

109,5

124

±0,

1

Ø9

Ø96

112,

8

117,

5

355,

5

pressure tappingconnection possible

X/W

V

140

180

Dimensions in mm.Dimensions in mm.

Page 15: Condensing boiler technology

28 29

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

G3G 250 -GN17-01 230 50/60 1650 3250 1150 4800 60 60 55600.05021

Subject to alterations.

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

G3G 250 -MW50-01 380 - 480 50/60 2200 5400 2500 6400 50 50 G3G 250 -MW50-01

Subject to alterations.

G3G 250 G3G 250 MW

– Material: Housing: Aluminium

Impeller: Plastic

Motor protection cap: Plastic

– For potential mounting positions, page 18

– Mains connector X, interface connector W and interface see page 31 ff.

– Material: Housing: Die-cast aluminium

Impeller: Sheet aluminium

Rotor: Coated in black

Electronics enclosure: Die-cast aluminium

– For mains connector see operating instructions

3000

2500

2000

1500

1000

500

400 800 1200 1400

Curves

249 ±1,5

120,5

92

180

Ø120

66,3

169,

8

9

171

6x60°

60°

view Z

2,9

10 +1

M8

3,4 Ø1

85

Ø220

detail V enlarged

sideplates of housingsealed with rubber loop(NBR pentane-resistant)

V

Z

434 ±1

459

±1

265

pressure tapping is possible

8

204,5

X/W

220

Ø220

178,

6+0,

3

5

2,9-0,3

10+1

M8

459±

1

265

434±1

204,5

66,3

6x60°

220

180

92

Ø9

Ø120

395±2

120,5

171

169,

8

5000

4000

3000

2000

1000

400 800 1200 1600 2000

Curves

cable gland

view Z

detail V

Ø120

Z

V

sideplates of housingsealed with rubber loop(NBR pentane-resistant)

Dimensions in mm.Dimensions in mm.

Page 16: Condensing boiler technology

30 31

Power supply ACPower supply ACProtective earth

Part number for mating connector:Connector shell 24309.45012; Crimp socket 24307.45002/3

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

1 = Power supply +2 = Hall Sensor OUT3 = PWM Input4 = GND

1 3 5

2 4 6

Part number for mating connector: 24310.45025 Part number for mating connector:Connector shell 24310.45133;Crimp socket 24300.45128

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = Input 0-10V DC Control4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

3-pin pin-connector with coding type 0A according to RAST 5in 90° angled / horizontal designwith locking feature on top or down for locking devicesuitable for mating connector according to RAST 5with coding type 0A as e. g.CoHaMo YY-A5002-H03-K01 or Lumberg 3623 03 K01

Power supply AC

Protective earth

Power supply AC

3-pin pin-connector according RAST 6.35in 90° angled / horizontal designsuitable for mating connector according to RAST 6.35e. g. Tyco Universal MATE-N-LOKorder number: 1586847-1 and 3 x socket 926882-1

4-pin pin-connector according RAST 3.0in 90° angled / horizontal designsuitable for mating connector according to RAST 3.0e. g. Molex Micro-Fit 3.0order number: 43645-0408and 4 x socket 43030-0001

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal design suitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

Power supply ACPower supply ACProtective earth

Part number for mating connector:Connector shell 24309.45012; Crimp socket 24307.45002/3

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

1 = Power supply +2 = Hall Sensor OUT3 = PWM Input4 = GND

1 3 5

2 4 6

Part number for mating connector: 24310.45025 Part number for mating connector:Connector shell 24310.45133;Crimp socket 24300.45128

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = Input 0-10V DC Control4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

3-pin pin-connector with coding type 0A according to RAST 5in 90° angled / horizontal designwith locking feature on top or down for locking devicesuitable for mating connector according to RAST 5with coding type 0A as e. g.CoHaMo YY-A5002-H03-K01 or Lumberg 3623 03 K01

Power supply AC

Protective earth

Power supply AC

3-pin pin-connector according RAST 6.35in 90° angled / horizontal designsuitable for mating connector according to RAST 6.35e. g. Tyco Universal MATE-N-LOKorder number: 1586847-1 and 3 x socket 926882-1

4-pin pin-connector according RAST 3.0in 90° angled / horizontal designsuitable for mating connector according to RAST 3.0e. g. Molex Micro-Fit 3.0order number: 43645-0408and 4 x socket 43030-0001

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal design suitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

Mains connector X

Mains connector X

1 3

4

5

62

Interface connector W

Interface connector W

Interface connector W

Interface connector W

Power supply ACPower supply ACProtective earth

Part number for mating connector:Connector shell 24309.45012; Crimp socket 24307.45002/3

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

1 = Power supply +2 = Hall Sensor OUT3 = PWM Input4 = GND

1 3 5

2 4 6

Part number for mating connector: 24310.45025 Part number for mating connector:Connector shell 24310.45133;Crimp socket 24300.45128

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = Input 0-10V DC Control4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

3-pin pin-connector with coding type 0A according to RAST 5in 90° angled / horizontal designwith locking feature on top or down for locking devicesuitable for mating connector according to RAST 5with coding type 0A as e. g.CoHaMo YY-A5002-H03-K01 or Lumberg 3623 03 K01

Power supply AC

Protective earth

Power supply AC

3-pin pin-connector according RAST 6.35in 90° angled / horizontal designsuitable for mating connector according to RAST 6.35e. g. Tyco Universal MATE-N-LOKorder number: 1586847-1 and 3 x socket 926882-1

4-pin pin-connector according RAST 3.0in 90° angled / horizontal designsuitable for mating connector according to RAST 3.0e. g. Molex Micro-Fit 3.0order number: 43645-0408and 4 x socket 43030-0001

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal design suitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

Power supply ACPower supply ACProtective earth

Part number for mating connector:Connector shell 24309.45012; Crimp socket 24307.45002/3

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

1 = Power supply +2 = Hall Sensor OUT3 = PWM Input4 = GND

1 3 5

2 4 6

Part number for mating connector: 24310.45025 Part number for mating connector:Connector shell 24310.45133;Crimp socket 24300.45128

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = Input 0-10V DC Control4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

3-pin pin-connector with coding type 0A according to RAST 5in 90° angled / horizontal designwith locking feature on top or down for locking devicesuitable for mating connector according to RAST 5with coding type 0A as e. g.CoHaMo YY-A5002-H03-K01 or Lumberg 3623 03 K01

Power supply AC

Protective earth

Power supply AC

3-pin pin-connector according RAST 6.35in 90° angled / horizontal designsuitable for mating connector according to RAST 6.35e. g. Tyco Universal MATE-N-LOKorder number: 1586847-1 and 3 x socket 926882-1

4-pin pin-connector according RAST 3.0in 90° angled / horizontal designsuitable for mating connector according to RAST 3.0e. g. Molex Micro-Fit 3.0order number: 43645-0408and 4 x socket 43030-0001

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal design suitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

Power supply ACPower supply ACProtective earth

Part number for mating connector:Connector shell 24309.45012; Crimp socket 24307.45002/3

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

1 = Power supply +2 = Hall Sensor OUT3 = PWM Input4 = GND

1 3 5

2 4 6

Part number for mating connector: 24310.45025 Part number for mating connector:Connector shell 24310.45133;Crimp socket 24300.45128

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = Input 0-10V DC Control4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

3-pin pin-connector with coding type 0A according to RAST 5in 90° angled / horizontal designwith locking feature on top or down for locking devicesuitable for mating connector according to RAST 5with coding type 0A as e. g.CoHaMo YY-A5002-H03-K01 or Lumberg 3623 03 K01

Power supply AC

Protective earth

Power supply AC

3-pin pin-connector according RAST 6.35in 90° angled / horizontal designsuitable for mating connector according to RAST 6.35e. g. Tyco Universal MATE-N-LOKorder number: 1586847-1 and 3 x socket 926882-1

4-pin pin-connector according RAST 3.0in 90° angled / horizontal designsuitable for mating connector according to RAST 3.0e. g. Molex Micro-Fit 3.0order number: 43645-0408and 4 x socket 43030-0001

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal design suitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

Power supply ACPower supply ACProtective earth

Part number for mating connector:Connector shell 24309.45012; Crimp socket 24307.45002/3

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

1 = Power supply +2 = Hall Sensor OUT3 = PWM Input4 = GND

1 3 5

2 4 6

Part number for mating connector: 24310.45025 Part number for mating connector:Connector shell 24310.45133;Crimp socket 24300.45128

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = NC4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

1 = Power supply +2 = Hall Sensor OUT3 = Input 0-10V DC Control4 = PWM Input5 = Power supply - (GND)

Part number for mating connector:Connector shell 24309.45035;Crimp socket 24308.45065

3-pin pin-connector with coding type 0A according to RAST 5in 90° angled / horizontal designwith locking feature on top or down for locking devicesuitable for mating connector according to RAST 5with coding type 0A as e. g.CoHaMo YY-A5002-H03-K01 or Lumberg 3623 03 K01

Power supply AC

Protective earth

Power supply AC

3-pin pin-connector according RAST 6.35in 90° angled / horizontal designsuitable for mating connector according to RAST 6.35e. g. Tyco Universal MATE-N-LOKorder number: 1586847-1 and 3 x socket 926882-1

4-pin pin-connector according RAST 3.0in 90° angled / horizontal designsuitable for mating connector according to RAST 3.0e. g. Molex Micro-Fit 3.0order number: 43645-0408and 4 x socket 43030-0001

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal designsuitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

5-pin pin-connector according RAST 4.2in 90° angled / horizontal design suitable for mating connector according to RAST 4.2e. g. Stocko STO-FIT, CoHaMoorder number: Stocko EH 705-005-004-960and 5 x socket RBB 8230.120order number: CoHaMo YY-5700-H05AS-GW

Nominal data Rate

d vo

ltage

Freq

uenc

y

Max

. air

flow

Max

. pr

essu

re in

crea

se

Max

. inp

ut p

ower

Max

. spe

ed

Perm

. am

b. m

otor

tem

p.

Perm

. te

mp.

of m

ediu

m

Part

num

ber

Type V Hz m³/h Pa W min-1 °C °C

HRG 134 230 50/60 78 3000 70 8500 60 80 55667.40160

Subject to alterations.

9000

7500

6000

4500

3000

1500

10 20 30 40 50 60 70

Curves

3000

2500

2000

1500

1000

500

10 20 30 40 50 60 70

Dimensions in mm.

HRG 134for oil condensing boilers

– Material: Housing: Plastic

Impeller: Plastic

Motor protection cap: Plastic

– For potential mounting positions, page 18

– Mains connector X, interface connector W and interface see page 31 ff.

Connectors

Connectors NRG

77

NRG

118

RG 1

28

RG 1

48

NRG

137

RG 1

75

G1G

170

-AB5

3-01

G1G

170

-AB5

3-80

G3G

200

G3G

250

HRG

134

G3G

250

MW

Inte

rface

04

600.

451…

1 Mains connector X × × × × × × ×

see

oper

atin

g in

stru

ctio

ns2 Mains connector X × × × ×

3 Interface connector W × 31

4 Interface connector W × × × × × × 04

5 Interface connector W × 38

6 Interface connector W × × × 39

Further connector types on request.

Page 17: Condensing boiler technology

32 33

Electrical interfaces Electrical interfaces

Interface 31

Interface 04

115 / 230 VACInterface 38

230 VAC, 50/60 Hz 120 VAC, 50/60 Hz control Interface 39 115 / 230 VAC

04600.45131 04600.45138

04600.45104

Further types on request. Further types on request.

04600.45139

counter

controller

alarm

speed display

maximum ripple ±3,5% UB +24 - 45VDC / 15mA

nominal voltage

tach output 3 pulses / revolution

open PWM andcontrol input-> max. speed

Fuse

Fuse

min.operation->Ucontrol>2V

voltage output+10V max 10mA

tach output3 pulses per revolution

lin. control input

VACground

main voltage

counter

speed setting speed settingspeed

setting with alterable

resistance

controller

alarm

speed display

safe start up at 25% PWMcontrol signal - square pulsePWM-Low -> blower off PWM-High -> blower on

starting -> PWM > 25%min. operation -> PWM 18%control input signal - rectangle impulsPWM-Low - fan offPWM-High - fan on

Customer circuit example Interface ebm-papst circuit

HS out

GND

VCC

PW Min

GND

18-43VDC1

HS2

PW M

GND

3

12K

1K

22K

10nF

4K7

4

12K22

K

7.5V

15K

12V1K

Customer circuit example Customer circuit exampleInterface Interfaceebm-papst circuit ebm-papst circuit

Customer circuit example Interface ebm-papst circuit

Standardschnittstelle 1 24 VDC Steuerung

Standardschnittstelle 2 230 VAC, 50/60 Hz 120 VAC, 50/60 Hz Steuerung

Schnittstellen für Gebläse mit EC-Innenläufermotor BG3612/3633

Drehzahl-auswertung

PWM:Start: >20% PWMRechtecksignalPWM-low = Gebläse ausPWM-high = Gebläse ein

12K

1K8)*

1K2)*

10K10K

10K

10K

10K

15K

+12 VDC

+12 VDC+12 VDC

+12 VDC

12KPC817

BC546B

12K

12K

EMV-Filter

Vcc

Hall Signal

PWM-SignalGND

1K

15K

1K

PC817

BC846B

1K

6K8

ZMM

5,1

ZMM

12

1K

L (187 V ... 253 V 50/60 Hz)(91V ... 126 V 50/60 Hz)

+18..43 VDC

Hallsignal2 Pulse pro Umdrehung

3 N.C.

5 GND

PWM 1-6 kHz

Imax = 3,3mA

Imax, „High“: 1,6mAImax, „Low“: -2,0mA

PE

1

2

4

PWM:Start: >20% PWMRechtecksignalPWM-low = Gebläse ausPWM-high = Gebläse ein

+18..43 VDC

Hallsignal2 Pulse pro Umdrehung

3 N.C.

5 GND

PWM 1-6 kHz

Imax, „High“: 5mAImax, „Low“: -2,0mA

1

2

4

I

N

Kundenseite Schnittstelle ebm-papst Seite

Kundenseite Schnittstelle

8 mm Isolation (Kriechstecke)

Hallsensor mitOpen KollektorAusgang

ebm-papst Seite

85

Allg

emei

nes

Quer

stro

mve

ntila

tore

nRa

dial

gebl

äse

ACRa

dial

gebl

äse

ECUm

wäl

zgeb

läse

für H

eißl

uft

Axia

lven

tilat

oren

Pum

pen

Adre

ssen

tach output2 pulses per revolution

Digital PWMPWM-low = Blower offPWM-high = Blower on

Page 18: Condensing boiler technology

34 35

Gas valves

Page 19: Condensing boiler technology

36 37

Our zero-pressure gas valves for gas-condensing systems are primarily

used for domestic applications in the lower and medium power range.

These gas valves compensate for pressure fl uctuations occurring in

the public gas grid as well as regulate the offset pressure to zero re-

gardless of the suction pressure being generated by a premix blower.

The offset (zero point shift) can be confi gured at the servo regulator.

At the same time the desired gas quantity can be adjusted by using

an integrated throttle element. Both together ensure an accurate air-

gas ratio setting.

Depending on the design a reference pressure can be connected to

the servo regulator if required.

Technical information

Length 105mm

Permitted gas families II + III (in accordance with EN 437)

Maximum inlet pressure 65mbar (CE), 0,5psi (CSA)

Permitted ambient temperature 0°C to 60°C

(-15°C to 70°C on request)

Permitted storage temperature -25°C to 70°C

Type of protection IP40 in combination with

a suitable plug

Offset correction +/- 20Pa

Minimum signal pressure -30Pa

Permitted mounting position Solenoid at any position between

vertical and horizontal –

but not upside down.

Type�examination certifi cate in accordance with EC Gas

Appliances Directive: CE�0085CM0036 (product ID number)

Applicable standards

– EN126:2012�06: Multifunctional controls for gas burning appliances

– EN13611:2007 + A2:2011: Safety and control devices for gas

burners and gas burning appliances – General requirements

– EN161:2012�08: Automatic shut-off valves for gas burners and gas

appliances

– EN88-1:2011: Pressure regulators and associated safety devices

for gas appliances – Part 1: Pressure regulators for inlet pressures

up to and including 50kPa

Type�examination certifi cate for North America (USA and Canada):

Master Contract No. 172723

Applicable standards

– ANSI Z21.78�2010 / CSA 6.20�2010:

Combination Gas Controls for Gas Appliances

Approvals exist for the chief gas�consuming countries.

Additional notes

– Work on the gas valve may be performed by authorised

specialists only.

– Please be sure to observe the corresponding installation instructions.

– Corresponding documents with safety instructions are available

upon request or on the Internet.

Approvals and applicable standardsGas valves

Page 20: Condensing boiler technology

38 39

– Housing: Aluminium

– Electrical connection: Connector shell with 4.20mm grid

– Inlet (gas connection): External thread G3/4 or G1/2 (DIN EN ISO 228)

or 4 x M4 mounting holes (optional)

– Outlet: ebm-papst specific quick-connector

– Safety valves: Coaxial design: valve class B/C in accordance with EN161

Vn [m3/h] Erdgas / Natural gas (dv = 0,65) °

∆p [m

bar]

2

3

4

5

6

1

8

10

20

30

40

60

80

100

50

2 3 4 5 6 71 8 9 10 20

Bedingungen: + 15° C / 59 °F, p = 1013 mbar

0,1 0,2 0,3 0,4 0,5 0,6 0,8

2 3 4 5 6 71 8 9 10 20 300,2 0,3 0,4 0,5 0,6 0,8

Vn [m3/h] Luft / Air (dv = 1,00) °

Capacity curve – GB055

electrical connectionsolenoid coil

main flow throttlepressure test nipple P1

pressure test nipple P2

servo regulator

– Housing: Aluminium

– Electrical connection: Connector shell with 5.08mm grid

– Inlet (gas connection): 4 x M5 mounting holes (36mm hole spacing)

– Outlet: 4 x M5 mounting holes (36mm hole spacing)

– Safety valves: Valve class B/B in accordance with EN161

Nominal data Rate

d vo

ltage

Max

. inp

ut p

ower

Nom

inal

dia

met

er

Max

imum

inle

t pr

essu

re

Flow

rate

(a

t Δp

= 5

mba

r)

Auto

mat

ic

shut

off v

alve

s (E

N161

)

Min

imum

si

gnal

pre

ssur

e

Open

ing

and

cl

osin

g tim

e

Type V VA mbar m³/h Pa s

GB-ND 057 D01 230 RAC 2 x 12.5 DN20 65 5.3 Class B/B -30 < 1

120 RAC 2 x 12.5 DN20 65 5.3 Class B/B -30 < 1

24 RAC 2 x 12.5 DN20 65 5.3 Class B/B -30 < 1

24 DC 2 x 12.5 DN20 65 5.3 Class B/B -30 < 1

Bedingungen + 15°C, 1013 mbar, trocken

V°n [m3/h] Erdgas / Natural gas (dv = 0,65)

V°n [m3/h] Luft / Air (dv = 1,00)

empfohlener Arbeitsbereich

∆p [m

bar]

2 3 4 5 6 71

2 3 4 5 6 71

8 9 10

71 8 9 10

20

20 30

0,1 0,2 0,3 0,4 0,5 0,6

0,2 0,3 0,4 0,5 0,6

0,8

0,8

2

3

4

5

6

1

8

10

20

30

40

60

80

100

50

Capacity curve – GB057

electrical connection

solenoid coilmain flow throttle

pressure test nipple P1

pressure test nipple P2

servo regulator

pressure regulatoroffset adjustment

recommended work range

recommended work range

E01Size GB055

D01Size GB057

Nominal data Rate

d vo

ltage

Max

. inp

ut p

ower

Nom

inal

dia

met

er

Max

imum

in

let p

ress

ure

Flow

rate

(a

t Δp

= 5

mba

r)

Auto

mat

ic

shut

off v

alve

s (E

N161

)

Min

imum

si

gnal

pre

ssur

e

Open

ing

and

cl

osin

g tim

e

Type V VA mbar m³/h Pa s

GB-ND 055 E01 230 RAC 9.8 DN15/20 65 3.4 Class B/C -30 < 1

120 RAC 9.8 DN15/20 65 3.4 Class B/C -30 < 1

24 RAC 9.8 DN15/20 65 3.4 Class B/C -30 < 1

24 DC 9.8 DN15/20 65 3.4 Class B/C -30 < 1

22 DC 9.8 DN15/20 65 3.4 Class B/C -30 < 1

Page 21: Condensing boiler technology

40 41

F01

– Housing: Aluminium

– Electrical connection: Connector shell with 4.20mm grid

– Inlet (gas connection): External thread G3/4 or G1/2 (DIN EN ISO 228)

– Outlet: ebm-papst specific quick-connector

– Safety valves: Coaxial design: valve class B/C in accordance with EN161

Nominal data Rate

d vo

ltage

Max

. inp

ut p

ower

Nom

inal

dia

met

er

Max

imum

in

let p

ress

ure

Flow

rate

(a

t Δp

= 5

mba

r)St

eppe

r mot

or m

odul

e w

ith n

omin

al

diam

eter

8m

m

Flow

rate

(a

t Δp

= 5

mba

r)St

eppe

r mot

or m

odul

e w

ith n

omin

al

diam

eter

12m

m

Auto

mat

ic

shut

off v

alve

s (E

N161

)

Open

ing

and

cl

osin

g tim

e

Type V VA mbar m³/h m³/h s

GB-SXX 06X F01 230 RAC 9.8 DN15/20 60 2.1 2.9 Class B/C < 1

120 RAC 9.8 DN15/20 60 2.1 2.9 Class B/C < 1

24 RAC 9.8 DN15/20 60 2.1 2.9 Class B/C < 1

24 DC 9.8 DN15/20 60 2.1 2.9 Class B/C < 1

22 DC 9.8 DN15/20 60 2.1 2.9 Class B/C < 1

Capacity curve – F01

electrical connection stepper motor module

electrical connection safety valve

solenoid coilG 3/4" or G1/2" ISO 228-1

pressure test nipple

∆p

[mba

r]∆

1

10

100

V°n [m3/h] Erdgas / Natural gas

V°n [m3/h] Luft / Air

0,01 0,1 1 10

°

0,0135 0,135 1,35 13,5

F01 - 12 mm

F01 - 8 mm

Bedingungen: 15° C, p=1013 mbar

empfohlener Arbeitsbereichrecommended work range

Page 22: Condensing boiler technology

42 43

Burner Controls

Page 23: Condensing boiler technology

44 45

In co-operation with the Dutch electronic control unit specialist ebm-

papst Heating Systems B.V. (formerly Argus Vision B.V.), we also offer

our customers a control element for their gas heaters from a single

source. ebm-papst Heating Systems already has 20 years of experi-

ence in developing burner controls to look back on and also has the

required expertise for mastering the current challenges in condensing

boiler technology. In modulating condensing boilers, the link between

mechanical components and the electronic drive has to be co-ordi-

nated with a high-degree of precision in order to achieve optimum

combustion beha viour. ebm-papst Heating Systems earned a reputa-

tion for the highest innovative strength and quality in electronic moni-

toring for gas-fi res heating systems.

ebm-papst Heating Systems supplies the electronics for controlling

ignition, performance regulation and monitoring the function of

the condensing boiler as well as a user input interface with various

displays for conveniently controlling central heating and DHW. The

burner control can also be used in combination with other modules

and provide control with a system regulation, for example a cascade

operation.

The standard platform, consisting of tried-and-tested hardware and

software, enables reliable operating performance and short develop-

ment cycles. The versatile software architecture enables customer-

specifi c interfaces to be integrated with ease. In addition, as with our

blowers, we value having the lowest possible energy consumption.

Markets and application areas

Gas fi red combi-boilers, commercial gas boilers, air heaters, direct

fi red water heaters, indirect fi red water heaters, gas stoves, catering

equipment such as fryers and mCHP.

Service tools

LabVision computer software for communication between computer

and burner control.

System in operation

Trio / Multiple Trio Application

– Function: To control central heating, DHW, cascade operation, multiple burners

(trio and multiple trio). No additional controller needed.

– Application: Domestic (combi) boilers, commercial boilers, water heaters

– Connections: Supports a wide range of in- and outputs for sensors, valves,

ignition, pumps, etc.

– Support: LabVision PC Software, to confi gure hard- and software functions,

remote diagnostics, logging and graphs

Nominal data Pow

er s

uppl

y

Freq

uenc

y

Dim

ensi

ons

hous

ing

l x w

x h

Safe

ty ti

me

Igni

tion

atte

mpt

s

Wei

ght

On B

oard

Us

er In

terfa

ce

Even

t his

tory

(e

rror

& lo

ckou

t)

Argu

s Li

nk

LabV

isio

n Di

agno

stic

s So

ftwar

e

Type VAC Hz mm Sec. gram

850MN 230 40-70 212 x 152 x 46 6 3 530 No 15 + 15 x x

850MN 120 40-70 212 x 152 x 46 6 3 530 No 15 + 15 x x

900MN 230 40-70 212 x 152 x 49 6 3 512 Yes 15 + 15 x x

Features

– Low standby power consumption and class A modulating

pump control

– Insensitivity of mains supply for a reliable operation

– Thermostat options: Switched Live, OT-interface or 24V

– Connect controls with each other via Argus Link

(2-wire communication interface)

– Wide choice of control modules for hybrid heating applications

and systems within a building or house

– Easy interfacing with Building Management Systems,

for example via ModBUS

900MN Burner Control

230V

GASAC or DC

230VNTC 7X ARGUS LINK

or 24VACIGNITIONINT or EXT

230VON 2X / 1X PWMOFF

230V PWM or DIGIT AL

IN SWITCH2X

5V SENSOR 2X

3X

850MN Burner Control

230V

GASAC or DC

230VNTC 6X SWITCH ARGUS LINK

or 24VACIGNITIONINT or EXT

230V230V PWM or DIGIT AL

5V SENSOR

900MN Burner Control

230V

GASAC or DC

230VNTC 7X ARGUS LINK

or 24VACIGNITIONINT or EXT

230VON 2X / 1X PWMOFF

230V PWM or DIGIT AL

IN SWITCH2X

5V SENSOR 2X

3X

850MN Burner Control

230V

GASAC or DC

230VNTC 6X SWITCH ARGUS LINK

or 24VACIGNITIONINT or EXT

230V230V PWM or DIGIT AL

5V SENSOR

Burner Control UnitsBurner Controls

Page 24: Condensing boiler technology

46 47

– Function: External display modules to be used as an user interface for burner

controls or optional modules

– Integrated features: User and installer menu, multiple languages and graphics

– Optional features: Specifi c application menus, for example solar control and

catering equipment

– 2�Wire Argus Link: One connection for power and communication

Nominal data Di

men

sion

s (l

x w

x h

)

LCD

type

Disp

lay

Colo

r

Back

light

LCD

disp

lay

Area

(l

x h)

No. o

f Pus

h Bu

ttons

Avai

labl

e w

ith

hous

ing

Conn

ectio

n

Mul

tiple

lang

uage

s

Tem

p. S

enso

r

Real

Tim

e Cl

ock

Type mm mm

900PB 178 x 85 x 13 Pixel 255 x 80 blue/white x 106.4 x 39 8 2-wire x x

900DI 142 x 63.5 x 29 Icons & segment green/black x 37 x 22 5 2-, 3- or 4-wire

900LB 119 x 115 x 20 Icons & segment blue/white x 93 x 31 5 2- or 4-wire optional

850HC 129 x 129 x 24 Pixel 255 x 80 blue/white x 106.4 x 39 11 x 2-wire x x x

– Function optional modules: Add-on modules to extend your system

– Argus Link Interface: To connect easily to other controls

– Support: RemoteVision PC Software, for monitoring, controlling and

data-logging of fi eld appliances via a permanent TCP/IP internet connection

(also available as SiteVision for installers)

Nominal data Pow

er S

uppl

y

Dim

ensi

ons

(l x

w x

h)

Wei

ght

Argu

s Li

nk

Type VAC mm gram

850DS 87 x 50 x 27 45 x

850IF 110V/230 155 x 110 x 51 439 x

850SC 110V/230 150 x 105 x 14 525 x

850GP 110V/230 150 x 105 x 14 254 x

850USB 78 x 54 x 28 116 x

850GP GPRS Communication Module Wireless communication module using GPRS technology

850USB PC Communication Interface For communication between the PC/LabVision and the control

850SC Solar ControlControl for thermal solar heat systems with or without drainback tank

850DS Digital SensorRobust outdoor or room temperature sensor

850SC Solar ControlControl for thermal solar heat systems with or without drain-back tank

850IF Interface ModuleInterface Module to extend several heat generation control modules

T RETURN NTC 3X

850SC Solar Control

230V

ARGUS LINK

5V FLOW24V STEPPER 230V MODQ-SOLAR + T SYSTEM

T COLLECT OR T STORE

850IF Interface Module

ARGUS LINK

EXT RESET INALARM OUT

STATUS OUT

T RETURN NTC 3X

850SC Solar Control

230V

ARGUS LINK

5V FLOW24V STEPPER 230V MODQ-SOLAR + T SYSTEM

T COLLECT OR T STORE

850IF Interface Module

ARGUS LINK

EXT RESET INALARM OUT

STATUS OUT

Displays Optional Modules

900DI LCD Display

900LB LCD Display900PB Pixel Display

Page 25: Condensing boiler technology

48 49

ebm-papst in Germany ebm-papst in Europe

ebm-papst Mulfi ngen GmbH & Co. KGBachmühle 274673 Mulfi ngenGERMANYPhone +49 7938 81-0Fax +49 7938 [email protected]

ebm-papst St. Georgen GmbH & Co. KGHermann-Papst-Straße 178112 St. GeorgenGERMANYPhone +49 7724 81-0Fax +49 7724 [email protected]

ebm-papst Landshut GmbHHofmark-Aich-Straße 2584030 LandshutGERMANYPhone +49 871 707-0Fax +49 871 [email protected]

BerlinDipl.-Ing. (TH) Jens DuchowHändelstraße 716341 PanketalGERMANYPhone +49 30 944149-62Fax +49 30 [email protected]

BielefeldDipl.-Ing. (FH) Wolf-Jürgen WeberNiehausweg 1333739 BielefeldGERMANYPhone +49 5206 91732-31Fax +49 5206 [email protected]

DortmundDipl.-Ing. (FH) Hans-Joachim PundtAuf den Steinern 359519 Möhnesee-VöllinghausenGERMANYPhone +49 2925 800-407Fax +49 2925 [email protected]

FrankfurtDipl.-Ing. Christian KleffmannDr.-Hermann-Krause-Straße 2363452 HanauGERMANYPhone +49 6181 1898-12Fax +49 6181 [email protected]

HalleDipl.-Ing. (TU) Michael HanningLercheneck 406198 Salzatal / OT LieskauGERMANYPhone +49 345 55124-56Fax +49 345 [email protected]

HamburgIngenieurbüro Breuell GmbHIng. Dirk KahlElektroingenieurGrützmühlenweg 4822339 HamburgGERMANYPhone +49 40 538092-19Fax +49 40 [email protected]

Heilbronn / HeidelbergDipl.-Ing. Mark GartnerGehrweg 1274199 UnterheinrietGERMANYPhone +49 7130 404569-1Fax +49 7130 [email protected]

KasselDipl.-Ing. (FH) Ralph BrückHoherainstraße 3 b35075 GladenbachGERMANYPhone +49 6462 4071-10Fax +49 6462 [email protected]

KoblenzWinfried SchaeferHinter der Kirch 1056767 UersfeldGERMANYPhone +49 2657 16-96Fax +49 2657 [email protected]

MunichDipl.-Wirt.-Ing. (FH) Jens PeterLandsbergerstraße 1486932 PürgenGERMANYPhone +49 8196 99877-54Fax +49 8196 [email protected]

NurembergDipl.-Wirt.-Ing. (FH) Axel ReschDr.-August-Koch-Str. 191639 Wolframs-EschenbachGERMANYPhone +49 9875 9783-170Fax +49 9875 [email protected]

OffenburgDipl.-Ing. (FH) Ralf BraunHubeneck 2177704 OberkirchGERMANYPhone +49 7802 9822-52Fax +49 7802 [email protected]

StuttgartDipl.-Ing. (FH) Rudi WeinmannHindenburgstraße 100/173207 PlochingenGERMANYPhone +49 7153 9289-80Fax +49 7153 [email protected]

UlmM.Sc. Reinhard SommerreißerAm Germanenring 1386674 Baar / SchwabenGERMANYPhone +49 8276 5899-775Fax +49 8276 [email protected]

Distributors

FrankfurtR.E.D. Handelsgesellschaft mbHGutenbergstraße 363110 Rodgau - JügesheimGERMANYPhone +49 6106 841-0Fax +49 6106 [email protected]

HamburgBreuell + Hilgenfeldt GmbHGrützmühlenweg 4822339 HamburgGERMANYPhone +49 40 538092-20Fax +49 40 [email protected]

MunichA. Schweiger GmbHOhmstraße 182054 SauerlachGERMANYPhone +49 8104 897-0Fax +49 8104 [email protected]

(1 to 5 pieces)

NorthBreuell + Hilgenfeldt GmbHGrützmühlenweg 4822339 HamburgGERMANYPhone +49 40 538092-20Fax +49 40 [email protected]

SouthHDS Ventilatoren Vertriebs GmbHGlaswiesenstraße 174677 DörzbachGERMANYPhone +49 7937 80355-20Fax +49 7937 [email protected]

Europe

Austriaebm-papst Motoren & Ventilatoren GmbHStraubingstraße 174030 LinzAUSTRIAPhone +43 732 321150-0Fax +43 732 [email protected]

Belarusebm-papst Bel AgmbHLipkovskaya Gasse 34Offi ce No.6, Room 106,107223010 MinskBELARUSPhone +375 17 3851556Fax +375 17 [email protected]

Belgiumebm-papst Benelux B.V.Sales offi ce Belgium-LuxemburgRomeinsestraat 6/0101Research Park Haasrode3001 Heverlee-LeuvenBELGIUMPhone +32 16 396-200Fax +32 16 [email protected]

Bulgariaebm-papst Romania S.R.L.Str. Tarnavei No. 20500327 BrasovROMANIAPhone +40 268 331859Fax +40 268 [email protected]

Croatiaebm-papst Industries Kft.Ezred u. 2.1044 BudapestHUNGARYPhone +36 1 8722-190Fax +36 1 8722-194offi [email protected]

Czech Republic / Slovakiaebm-papst CZ s.r.o.Kaštanová 34a620 00 BrnoCZECH REPUBLICPhone +420 544 502-411Fax +420 547 [email protected]

Denmarkebm-papst Denmark ApSVallensbækvej 212605 BrøndbyDENMARKPhone +45 43 631111Fax +45 43 [email protected]

Estoniaebm-papst Oy, Eesti FiliaalKesk tee 13Aaviku küla, Jüri Tehnopark75301 Rae Vald, HarjumaaESTONIAPhone +372 65569-78Fax +372 65569-79www.ebmpapst.ee

Finlandebm-papst OyPuistotie 102760 EspooFINLANDPhone +358 9 887022-0Fax +358 9 [email protected] www.ebmpapst.fi

Franceebm-papst sarlZI Nord - rue A. MohlerBP 6267212 Obernai CedexFRANCEPhone +33 820 326266Fax +33 3 [email protected]

GreeceHelcomaTh. Rotas & Co OEDavaki 6517672 Kallithea-AttikiGREECEPhone +30 210 9513-705Fax +30 210 [email protected]

Hungaryebm-papst Industries Kft.Ezred u. 2.1044 BudapestHUNGARYPhone +36 1 8722-190Fax +36 1 8722-194offi [email protected]

IcelandRJ EngineersStangarhyl 1a110 ReykjavikICELANDPhone +354 567 8030Fax +354 567 [email protected]

Irelandebm-papst UK Ltd.Chelmsford Business ParkChelmsford Essex CM2 5EZUNITED KINGDOMPhone +44 1245 468555Fax +44 1245 [email protected]

AuBren LimitedPortlaoise Business & Technology ParkMountrath RoadPortlaoise, Co. LaoisIRELANDPhone +353 57 8664343Fax +353 57 [email protected]

Italyebm-papst SrlVia Cornaggia 10822076 Mozzate (Co)ITALYPhone +39 0331 836201Fax +39 0331 [email protected]

Macedoniaebm-papst Industries Kft.Ezred u. 2.1044 BudapestHUNGARYPhone +36 1 8722-190Fax +36 1 8722-194offi [email protected]

fan agent compact fan agent motor specialist motor agent

Page 26: Condensing boiler technology

50 51

ebm-papst in America and Africaebm-papst in Europe

Netherlandsebm-papst Benelux B.V.Polbeemd 75741 TP Beek en DonkTHE NETHERLANDSPhone: +31 49250 2900Fax: +31 49250 [email protected]

ebm-papst Heating Systems B.V.Van Veldekekade 3605216 KT’s-HertogenboschTHE NETHERLANDSPhone +31 73 64889-00Fax +31 73 [email protected]

Norwayebm-papst ASP.B. 173 Holmlia1203 OsloNORWAYPhone +47 22 763340Fax +47 22 [email protected]

Polandebm-papst Polska Sp. z o.o.ul. Annopol 4A03236 WarszawaPOLANDPhone +48 22 6757819Fax +48 22 6769587offi [email protected]

Portugalebm-papst (Portugal), Lda.Centro Empresarial de AlvercaRua de Adarse, Vale D’ErvasCorpo D / Fracção 32615-178 Alverca do RibatejoPORTUGALPhone +351 218 394 880Fax +351 218 394 [email protected]

Romaniaebm-papst Romania S.R.L.Str. Tarnavei Nr. 20500327 BrasovROMANIAPhone +40 268 331859Fax +40 268 [email protected]

Russiaebm-papst Ural GmbHPosadskaja-Strasse, 23(E), 3620102 EkaterinburgRUSSIAPhone +7 343 2338000Fax +7 343 [email protected]

ebm-papst Rus GmbHproezd 4529, vladenie 5, stroenie 1141000 Mytistschi, Oblast MoskauRUSSIAPhone +7 495 9807524Fax +7 495 [email protected]

Serbia & Montenegroebm-papst Industries Kft.Ezred u. 2.1044 BudapestHUNGARYPhone +36 1 8722-190Fax +36 1 8722-194offi [email protected]

Spainebm-papst Ibérica S.L.Avda. del Sistema Solar, 2928830 San Fernando de Henares (Madrid)SPAINPhone +34 91 6780894Fax +34 91 [email protected]

Swedenebm-papst ABÄggelundavägen 217562 JärfällaSWEDENPhone +46 10 4544400Fax +46 8 [email protected]

Switzerlandebm-papst AGRütisbergstrasse 18156 OberhasliSWITZERLANDPhone +41 44 73220-70Fax +41 44 [email protected]

TurkeyAkantel Elektronik San. Tic. LTD. Sti.Atatürk Organize SanayiBölgesi 10007 SK. No.:635620 Cigli-IzmirTURKEYPhone +90 232 3282090Fax +90 232 [email protected]

Ukraineebm-papst Ukraine LLCLepse Boulevard, 4, Building 2103067 KievUKRAINEPhone +38 044 2063091Fax +38 044 2063091 [email protected]

United Kingdomebm-papst UK Ltd.Chelmsford Business ParkChelmsford Essex CM2 5EZUNITED KINGDOMPhone +44 1245 468555Fax +44 1245 [email protected]

ebm-papst Automotive & Drives (UK) Ltd.The SmithyFidlers LaneEast Ilsley, Berkshire RG20 7LGUNITED KINGDOMPhone +44 1635 2811-11Fax +44 1635 2811-61A&[email protected]

America

Argentinaebm-papst de Argentina S.A.Hernandarias 148 Lomas del MiradorPcia. de Buenos Aires (1752)ARGENTINAPhone +54 11 46576135Fax +54 11 [email protected]

Brasilebm-papst Motores Ventiladores Ltda.Av. José Giorgi, 301 Galpões B6+B7Condominio Logical Center06707-100 Cotia - São PauloBRAZILPhone +55 11 4613-8700Fax +55 11 [email protected]

Canadaebm-papst Canada Inc.1800 Ironstone Manor, Unit 2Pickering, Ontario, L1W3J9CANADAPhone +1 905 420-3533Fax +1 905 [email protected]

Mexicoebm Industrial S. de R.L. de C.V.Paseo de Tamarindos 400-A-5to PisoCol. Bosques de las LomasMexico 05120, D.F.MEXICOPhone +52 55 3300-5144Fax +52 55 [email protected]

USAebm-papst Inc.P.O. Box 4009100 Hyde RoadFarmington, CT 06034UNITED STATESPhone +1 860 674-1515Fax +1 860 [email protected]

ebm-papst Automotive & Drives, Inc.3200 Greenfi eld, Suite 255Dearborn, MI 48120UNITED STATESPhone +1 313 406-8080Fax +1 313 [email protected]

Africa

South Africaebm-papst South Africa (Pty) Ltd.P.O. Box 31241119 Yacht Avenue2040 HoneydewSOUTH AFRICAPhone +27 11 794-3434Fax +27 11 [email protected]

fan agent compact fan agent motor specialist motor agent

Page 27: Condensing boiler technology

52 53

ebm-papst in Asia and Australia

fan agent compact fan agent motor specialist motor agent

Asia

Chinaebm-papst Ventilator (Shanghai) Co., Ltd.No. 418, Huajing RoadWaiGaoQiao Free Trade ZoneNo. 2001, Yang Gao (N) Road200131 ShanghaiP.R. of CHINAPhone +86 21 5046-0183Fax +86 21 [email protected]

Hong Kongebm-papst Hong Kong Ltd.Room 17E, MG Tower133 Hoi Bun Road, Kwun TongHong KongP.R. of CHINAPhone +852 2145-8678Fax +852 [email protected]

Indiaebm-papst India Pvt. Ltd.26/3, G.N.T. Road, ErukkencherryChennai-600118INDIAPhone +91 44 25372556Fax +91 44 [email protected]

Indonesiaebm-papst IndonesiaRepresentative Offi ceGerman Centre, 4th Floor, Suite 4470Jl. Kapt. Subijono Dj. Bumi Serpong Damai15321 TangerangINDONESIAPhone +62 21 5376250Fax +62 21 [email protected]

IsraelPolak Bros. Import Agencies Ltd.9 Hamefalsim StreetKiryat Arie, Petach-Tikva 49514ISRAELPhone +972 3 9100300Fax +972 3 [email protected]

Japanebm-papst Japan K.K.Attend on Tower 13FShinyokohama 2-8-12, Kohoku-ku222-0033 Yokohama-City, KanagawaJAPANPhone +81 45 47057-51Fax +81 45 [email protected]

Koreaebm-papst Korea Co. Ltd.6F, Trutec Bldg.12, WorldCupbuk-ro 56-gilMapo-Gu Seoul 121-835KOREAPhone +82 2 366213-24Fax +82 2 [email protected] www.ebmpapst.co.kr

Malaysiaebm-papst MalaysiaRepresentative Offi ceUnit 12-2, Jalan USJ Sentral 3Persiaran Subang, Selangor Darul Ehsan47600 Subang JayaMALAYSIAPhone +60 3 8024-1680Fax +60 3 [email protected]

Singaporeebm-papst SEA Pte. Ltd.No. 23 Ubi Road 4#06-00 Olympia Industrial BuildingSingapore 408620SINGAPOREPhone +65 65513789Fax +65 [email protected]

TaiwanETECO Engineering & Trading Corp.10F-I, No. 92, Teh-Wei Str.Tsow-Inn District, KaohsiungTAIWANPhone +886 7 557-4268Fax +886 7 [email protected]

Thailandebm-papst Thailand Co., Ltd.99/9 Moo 2, Central Chaengwattana Tower14th Floor, Room 1402Chaengwattana Road Bangtarad, Pakkret11120 NonthaburiTHAILANDPhone +66 2 8353785-7Fax +66 2 [email protected]

United Arab Emiratesebm-papst Middle East FZEPO Box 17755Jebel Ali Free Zone / FZS1 / AP05DubaiUNITED ARAB EMIRATESPhone +971 4 88608-26Fax +971 4 [email protected]

Vietnamebm-papst VietnamRepresentative Offi ceRoom #102, 25 Nguyen Van Thu StreetDistrict 1Ho Chi Minh CityVIETNAMPhone +84 8 39104099Fax +84 8 [email protected]

Oceania

Australiaebm-papst A&NZ Pty Ltd.10 Oxford RoadLaverton North, Victoria, 3026AUSTRALIAPhone +61 3 9360-6400Fax +61 3 [email protected]

New Zealandebm-papst A&NZ Pty Ltd.61 Hugo Johnston Drive, Unit HPenrose 1061, AucklandNEW ZEALANDPO Box 112278,Penrose 1642, AucklandPhone +64 9 525-0245Fax +64 9 [email protected]

Page 28: Condensing boiler technology

54 55

Notes

Page 29: Condensing boiler technology

ebm-papst

Heating Systems B.V.

Van Veldekekade 360

5216 KT’s-Hertogenbosch

The Netherlands

Phone +31 73 64889-00

Fax +31 73 64889-11

[email protected]

www.ebmpapst.comwww.ebmpapst-hs.nl

ebm-papst

Landshut GmbH

Hofmark-Aich-Straße 25

84030 Landshut

Germany

Phone +49 871 707-0

Fax +49 871 707-465

[email protected]

Raw materials are becoming increasingly more valuable. Therefore

heaters have to become increasingly more efficient. Condensing boil-

er technology has long since replaced outdated conventional heating

systems. System solutions from ebm-papst incorporate the next im-

portant step towards greater efficiency: Instead of expending signifi-

cant effort co-ordinating individual components from various suppli-

ers, our customers receive complete condensing heating systems

from a single source, including blower, venturi, valve and burner con-

trol. This ensures optimal combustion under all conditions while re-

ducing installation effort to a minimum.

Simply contact us for more information or a specific quote. We are al-

ways there for you.

The engineer’s choice

37895-7-8811 · 2015-01 · OD-1,0'

Printed in Germany