    MAGNETIC MOTOR STARTERSAND MAGNETIC CONTACTORS

    seriesseries

  • Incorporation of CAN terminal for simple wiring

    Unified design for N seriesThe design has been unified for the MS-N series.The front face of the product is a bright white color, making the inside of the panel brighter and providing a clean image.

    Arc space reduced to approx. one-third!By adopting the new extinguishing mechanism, the arc space has been reduced to approx. 1/3 (Mitsubishi comparison).

    Compatible with International StandardsMost of Mitsubishi's standard products comply with International Standards.Applicable standards: JIS, JEM, IEC, EN, VDE, BSApproved standards: UL, CSA, LR, BV, NK, KR, TV, GB

    By adopting a CAN terminal, there is no need to remove the screws, and losing of the terminal screw is prevented by the integrated screw holder and terminal screw. The terminal screw is set in a plastic screw holder. When each pole is moved and the screw loosened, the screw is naturally set in the screw holder. This is Mitsubishi's original CAN terminal. (Patented)(S-N10CX~N35CX, SD-N11CX~N35CX, SR/SRD-N4CX)

    Substantial safety and

    functionality realized

    with a full lineup

  • Simple inspectionsThe contactor can be inspected easily by removing the arc cover.

    Built-in surge absorberThe model with built-in surge absorber for coils is obtainable as an option.

    Pull up the screw holder. Insert the closed eyelet connector, and push up the screw holder.

    Tighten the screw.

    Stronger barrier strength is improved with the thermoplastic mold.

    Improved magnetBy using a spiral kick-out spring, the dynamic balance of the moving parts is improved, bouncing is reduced, and the core life is extended. Furthermore, the core movement is generally stabilized. The efficient magnet has been achieved through modern technology of the magnet section using a computer. Thecontactor has a performance to withstand a voltage drop to 35% with the closed contact.

    Spiral kick-outspring

    Coil

    Moving core

    Stationarycore

    Small-Sized ModelsS-N10~N35

    15mm 15mm 15mm 15mm 15mm

    38.5

    mm

    Indication of absorber Surge absorber

    Simple installation and wiringThe MS-N series contactors, starters and relays can be installed on a mounting rail (35mm width). The terminals of these coils are arranged on the contactor with simple wiring. Furthermore, the distance between the center of the rail and the coil terminals is unified at 38.5mm. (S-N10 to N21, MSO-N10 to N21 and SR-N4)

    CAN terminal realizes safety and speedy The models with finger protection are safer and speedier even if the lug of a closed type eyelet (ring) terminal plate is used.(S-N10CX~N35CX, SD-N11CX~N35CX, SR/SRD-N4CX)

  • Medium-and Large-Sized Models:S-N50~S-N800

    DC Electromagnet with ACOperation (Patented)

    Even Greater Contact Reliability

    MATCH WITH ELECTRONIC CONTROL FOR FACTORY AUTOMATION

    If the magnetic relay coil is opened and closed near an electronic circuit, malfunctioning of the electronic circuit could be induced by a surge voltage. The UN-SA type surge absorber suppresses the surge voltage when this coil is opened and closed. In

    addition to the general varistor type and the CR type that lays importance on suppressing the induction voltage when starting, the type with operating indicator(varistor type), and the varistor type with CR are available.

    One-touch surge absorberAn easy-to-install terminal cover, which lays importance on further safety and is compatible with finger protection, has been prepared.

    Finger Protection Compatible

    A new extinguishing structure, which eliminates the blow off of hot gas (arc) to the front (direction to door of control panel) when the current is cutoff has been incorporated.

    In addition to improved safety, the freedom of panel design has been increased allowing space to be saved.

    The arc blowoff direction has been changed to further improve safety and space conservation

    This is an auxiliary contact unit with low level contact, capable of opening and closing the low voltage and minute current of the electronic control circuit. It can be installed with one touch onto the magnetic contactor or magnetic relay that opens and closes the power of the motor, etc. The junction relay for opening and closing the low voltage and minute current is not needed, so this unit is suitable for opening and closing electronic input circuits in programmable logic controllers, etc. A compact microswitch is used for the low level contact, so the unit will not

    malfunction due to fields and surge voltages from the main circuit current and coil of the magnetic contactor.A 1NO+1NC low level contacts and 1NO+1NC standard contacts are built-in, so the opening and closing of 200VAC and 24VDC can be handled with one unit.

    Auxiliary contact unit with low level contact

    S2 types of inputsThe long life no-contact output type (UN-SY21, SY31) and contact output type (UN-SY22, SY32) are available.SOne touch installationThe UN-SY21, SY22, SY31 and SY32 types can be mounted with one touch onto the coil terminal. Post-installation work is easy.

    SSingle standalone unitA single unit installation type (UN-SY11, SY12) is available for the S-KR11 and S-N80 to N400 magnetic contactor.

    Interface unit

    Coil power consumption is greatly low so MS-N Series contactors can be controlled by almost any type of relay, even small output relays of programmable controllers.

    Lower Power Consumption

    When switching a coil, the energy will be desipated within internal circuit of electromagnet

    Contact reliability has been greatly improved by the bifurcated auxiliary moving contact

    Less Noise nor Surge from Coil

    The voltage rating ranges is widened and the coil type are reduced to one-third.

    Contactor Coils Have Ultra-Wide Range of Ratings

    DC excitation does not cause humming so operation is quiet.

    Internal circuit of the electromagnet

    Humming Completely Eliminated

    S-N510101010

    FrameN50/N65N80/N95N125~N220N300/N400N600/N800

    S-K1010305010

    Arc space(mm)

    Direct installation is possible on the following units:S-N series (Magnetic contactor) 65A frame or lessSR-N series (Magnetic relay) 4-pole, 5-pole and 8-poles types

    C

    Coil

    R

    Contactspring

    Bifurcated movingcontact

    Bifurcatedmovingcontact

    Stationarycontact

    Arc space

  • TYPE REFERENCE LIST ........................................................................................................................................ 1

    1. GENERAL PURPOSE CONTACTORS & STARTERS ........................................ Series MS-N1.1 Conformity to International Standards ....................................................................................................... 2

    1.1.1 List of Marked Type ............................................................................................................................. 31.1.2 TV Certified Type ................................................................................................................................... 31.1.3 UL Approval for U.S.A. and Canada ......................................................................................................... 51.1.4 CCC Certified Products ............................................................................................................................ 71.1.5 Approved Marine Standards ................................................................................................................... 11

    1.2 Selection Guide ........................................................................................................................................... 121.3 The Overview (Type designation breakdown).......................................................................................... 14

    1.3.1 Non-Reversing Types ............................................................................................................................. 141.3.2 Reversing Type ....................................................................................................................................... 15

    1.4 Technical Data of Series S-N Contactors ................................................................................................. 161.4.1 Ratings and Characteristics .................................................................................................................... 161.4.2 Performance of Series S-N Contactors .................................................................................................. 181.4.3 Mounting Attitude of Starters and Contactors ......................................................................................... 18

    1.5 When Ordering ............................................................................................................................................ 191.6 Selection Table of Contactors ................................................................................................................... 20

    1.6.1 Non-Reversing Contactors ............................................. Type S-N , SD-N ......................................... 201.6.2 Reversing Contactors ..................................................... Type S-2xN , SD-2xNN .............................. 211.6.3 Non-Reversing Mechanically Latched Contactors .......... Type SL-N , SLD-NN .................................. 221.6.4 Reversing Mechanically Latched Contactors .................. Type SL-2xN , SLD-2xN , SLxS-NN ............. 23

    1.7 Selection Table of Direct-On-Line Motor Starters.................................................................................... 241.7.1 Non-Reversing Motor Starters without Enclosure(IP 00) Type MSO-N ................................................. 241.7.2 Reversing Motor Starters without Enclosure(IP 00) ........ Type MSO-2xN ............................................. 251.7.3 Enclosed Non-Reversing Motor Starters(IP 20) ............. Type MS-N .................................................... 261.7.4 Enclosed Non-Reversing Motor Starters with Pushbutton Switch(IP 20) ............. Type MS-N PM ................. 27

    1.8 Optional Parts and Accessories for Contactors ...................................................................................... 281.8.1 Replacement Coils .................................................................................................................................. 281.8.2 Replacement Contact Kits ...................................................................................................................... 281.8.3 Auxiliary Contact Blocks ......................................................................................................................... 291.8.4 Mechanical Interlocks ............................................................................................................................. 291.8.5 Connecting Bar Kits ................................................................................................................................ 291.8.6 Surge Absorbers ..................................................................................................................................... 301.8.7 Terminal Covers ..................................................................................................................................... 301.8.8 Pneumatic Time Delay Modules ............................................................................................................. 301.8.9 DC Interface Modules ............................................................................................................................. 30

    1.9 Connections and Contact Arrangement ................................................................................................... 311.9.1 S, SD-N................................................................................................................................................... 311.9.2 S, SD-2xN ............................................................................................................................................... 321.9.3 SL, SLD-(2x)N ........................................................................................................................................ 331.9.4 MSO-(2x)N.............................................................................................................................................. 341.9.5 MS-N....................................................................................................................................................... 351.9.6 MS-N PM .............................................................................................................................................. 35

    1.10 Outline Dimensions .................................................................................................................................. 361.10.1 Outline Dimensions of Non-Reversing Contactors ............................................................................... 361.10.2 Outline Dimensions of Reversing Contactors ....................................................................................... 371.10.3 Outline Dimensions of Open Type Starters .......................................................................................... 381.10.4 Outline Dimensions of Enclosed Motor Starters ................................................................................... 39

    CONTENTS

  • 2. MOTOR PROTECTION RELAYS2.1 Thermal Overload Relays ............................................................................. Series TH-N ........................ 40

    2.1.1 Selection Guide of Thermal Overload Relays ......................................................................................... 412.1.2 Selection Guide of the Current Transformers for TH-N600KP ............................................................... 422.1.3 Technical Data ........................................................................................................................................ 422.1.4 Selection Guide of Quick Trip Thermal Overload Relay ......................................................................... 422.1.5 Operating Characteristics of Thermal Overload Relays ......................................................................... 43

    (Connecting wire size : Refer to standard wire size of Table 2.1.3)2.1.6 Optional Parts and Accessories .............................................................................................................. 442.1.7 Outline Dimensions ................................................................................................................................. 45

    2.2 Electronic Motor Protection Relays ............................................................ Series ET-N ........................ 463. DEFINITE PURPOSE CONTACTORS & STARTERS

    3.1 DC Contactors ............................................................................................... Series DU-K/A .................... 493.2 Medium Voltage Vacuum Contactors ......................................................... Series SH-V ........................ 523.3 Compact 3-Pole Contactors ......................................................................... Series S-N 8 .................... 553.4 NC Main Contact Contactors ....................................................................... Series B-N .......................... 563.5 Delay Open Type Magnetic Starters & Contactors .................................... Series S/MSO-N DL ........ 583.6 DC Interface Contactors ............................................................................... Series SD-Q ....................... 603.7 DC Interface Modules ................................................................................... Series UN-SY ..................... 63

    4. RELAYS4.1 Contactor Relays .......................................................................................... Series SR-N ........................ 65

    4.1.1 Specifications .......................................................................................................................................... 664.1.2 Auxiliary Contact Blocks ......................................................................................................................... 674.1.3 Contact Arrangements of Contactor Relay ............................................................................................. 684.1.4 Spare Coils & Accessories ..................................................................................................................... 684.1.5 Outline Dimensions ................................................................................................................................. 68

    4.2 Voltage Detection Relays ............................................................................. Series SRE ......................... 694.3 Re-Starting Relays ........................................................................................ Series UA-DL ..................... 714.4 Solid State Time Delay Relays ..................................................................... Series SRS-H ..................... 734.5 Pneumatic Time Delay Relays ..................................................................... Series SRT-N ..................... 74

    5. STAR-DELTA STARTERS ................................................................................... Series EYD-N5.1 Selection Table............................................................................................................................................ 765.2 Specifications.............................................................................................................................................. 775.3 Outline Dimensions .................................................................................................................................... 78

    5.3.1 Open Type (EYDO-N) ............................................................................................................................. 785.3.2 Enclosed Type (EYD-N) ......................................................................................................................... 78

    6. SOLID STATE CONTACTORS ............................................................................ Series US-N/K, H6.1 Features ....................................................................................................................................................... 796.2 Product Scope............................................................................................................................................. 80

  • 1TYPE REFERENCE LISTDescriptionType

    NC main contact contactors ............................................................................................56DC contactors ..................................................................................................................49Electronic motor protection relays ...................................................................................46Star-delta starters ............................................................................................................76General purpose enclosed type motor starters ...............................................................26Enclosed non-reversing motor starters with pushbutton switch ......................................27General purpose open type motor starters ......................................................................14,24,38Delay open type magnetic contactors .............................................................................58General purpose open and reversing type motor starters ...............................................15,25,38Plug-in sockets for,UA-DL2 .............................................................................................72Compact 3-pole contactors .............................................................................................55General purpose contactors ............................................................................................2~DC interface contactors ...................................................................................................60Delay open type magnetic contactors .............................................................................58General purpose reversing contactors ............................................................................32Medium voltage vacuum contactors ................................................................................52Medium voltage reversing vacuum contactors ................................................................52Mechanically latched contactors .....................................................................................22Mechanically latched reversing contactors ......................................................................23Mechanically latched and normal reversing contactors ...................................................23Contactor relays ..............................................................................................................65Voltage detection relays ..................................................................................................69Solid state time delay relays ............................................................................................73Pneumatic time delay relays ...........................................................................................74Thermal overload relays ..................................................................................................40Saturable reactors for TH-N ............................................................................................44Auxiliary contact blocks for SH-V ....................................................................................54Re-starting relay ..............................................................................................................71Surge absorbers for SH-V ...............................................................................................53Auxiliary contact blocks ...................................................................................................29,50,67Mechanical interlocks for S-N ..........................................................................................29Reset release for TH-N ...................................................................................................44Surge absorbers for S-N and SR-N4 ...............................................................................30DC interface modules for S-N .........................................................................................30,63Trip indicator for TH-N .....................................................................................................44Pneumatic time delay modules .......................................................................................30,78Solid State Contactors .....................................................................................................79Solid State Contactors .....................................................................................................79

    Ref.PageB(D)-N DU(D)-ET-NEYD(O)-NMS-NMS-N PMMSO(D)-NMSO-N DLMSO(D)-2XNPF-S-N 8S(D)-NSD-QS-N DLS(D)-2XNSH(L)(D)-VSH(L)(D)-2XVSL(D)-NSL(D)-2XNSLXS-NSR(D)-NSRE-SRS-HSRT(D)-NTH-NTHR-UA-AXVVUA-DL2UA-SUUN-AXUN-MLUN-RRUN-SAUN-SYUN-TLUN-TRUS-N /KUS-H

  • 21. GENERAL PURPOSE CONTACTORS & STARTERS1.1 Conformity to International Standards Series MS-NMitsubishi magnetic motor starters and contactors are designed to conform to therelevant IEC recommendations and to the standards of as many countries aspossible. Specifically, they conform to the following:

    VDE0660NEMA-ICS

    IEC60947-4-1EN60947-4-1

    InternationalEurope

    GermanyU.S.A

    Table 1.1

    DCOperatedContactor

    OverloadRelay

    ACOperatedContactor

    Type

    (2)

    Canada

    U.K. France Korea Japan

    LloydsRegister ofShipping

    KoreanRegister ofShipping

    BureauVeritas

    NipponKaiji

    Kyokai

    ACOperatedContactorRelayDCOperatedContactorRelay

    AuxiliaryContactBlock

    U.S.ACanadaU.S.A

    Listing RecognitionEurope North America / UL

    TVCE Mark

    (2)

    (2)

    (2)

    Marine

    ( Mark)

    ( Mark)

    ( Mark)

    ( Mark)

    ( Mark)

    ( Mark)

    (2)

    ( Mark)

    ( Mark)

    ( Mark)

    (2)

    Model Name

    SR-N4(CX)

    SRD-N4(CX)

    UN-AX2(CX)UN-AX4(CX)UN-AX11(CX)UN-AX80UN-AX150

    S-N10(CX)S-N11(CX)/N12(CX)S-N18(CX)S-N20(CX)/N21(CX)S-N25(CX)S-N35(CX)S-N28(CX)S-N38(CX)S-N48(CX)S-N50S-N65S-N80S-N95S-N125S-N150S-N180S-N220S-N300S-N400S-N600S-N800TH-N12(CX)KPTH-N18(CX)KPTH-N20(TA)(CX)KPTH-N60(TA)KPTH-N120(TA)KPTH-N220RHKP/HZKPTH-N400RHKP/HZKPSD-N11(CX)/N12(CX)SD-N21(CX)SD-N35(CX)SD-N50SD-N65SD-N80SD-N95SD-N125SD-N150SD-N220SD-N300SD-N400SD-N600SD-N800

    China

    CCCcertification

    Notes:1. : CE Mark (Manufacturers Declaration) == Standard model applicable, marking on the product.UL, TV, CCC == Standard model applicable, marking on the product.NK == Standard model applicable, Certificate No. on the product.

    : Standard model applicable, no marking on the product. If marking required, order model name followed by suffix DZ. : Standard model applicable, no marking on the product. : Special model applicable, marking on the product. Order model name followed by suffix UL. : China export applicable, no marking on the product. Ensure to add CN after the model name when placing an order. : Not applicable to the Standard or not approved.2. Finger protection type is certified according to DIN VDE 0106 part 100. For finger protection type, order model name followed by suffix CX.3. For each certificate conditions, see next three pages.

  • 3Notes:1. Listed types are representatives and containes standard models.2. Applicable product standards

    Contactors : EN60947-1, EN60947-4-1, EN60947-5-1Thermal overload relays : EN60947-1, EN60947-4-1, EN60947-5-1Aux. contact blocks : EN60947-1, EN60947-5-1Mechanical interlocks : EN60947-1, EN60947-4-1, EN60947-5-1

    3. For mechanical interlocks, no marking on the product. Mechanical interlocks are applicable when used in reversing contactors.4. Necessary to connect a varistor etc., in order to provide compliance for CE marking for the US-N5/N8SS(TE)and US-N(H) 70/N(H)

    80NS(TE) type.

    1.1.1 List of Marked TypeStandard ContactorsNon-reversing

    A.C. operated

    D.C. operated

    A.C. operated

    D.C. operated

    Additional Auxiliary Contact Blocks

    Standard ContactorsReversing

    Mechanical Interlocks3

    S-N10, S-N11, S-N12, S-N18, S-N20, S-N21, S-N25, S-N28, S-N35, S-N38, S-N48, S-N50, S-N65, S-N80,S-N95, S-N125, S-N150, S-N180, S-N220, S-N300, S-N400, S-N600, S-N800SD-N11, SD-N12, SD-N21, SD-N35, SD-N50, SD-N65, SD-N80, SD-N95, SD-N125, SD-N150, SD-N220,SD-N300, SD-N400, SD-N600, SD-N800S-2XN10, S-2XN11, S-2XN20, S-2XN21, S-2XN25, S-2XN35, S-2XN50, S-2XN65, S-2XN80, S-2XN95,S-2XN125, S-2XN150, S-2XN180, S-2XN220, S-2XN300, S-2XN400, S-2XN600, S-2XN800SD-2XN11, SD-2XN21, SD-2XN35, SD-2XN50, SD-2XN65, SD-2XN80, SD-2XN95, SD-2XN125, SD-2XN150,SD-2XN220, SD-2XN300, SD-2XN400, SD-2XN600, SD-2XN800UN-AX2, UN-AX4, UN-AX11, UN-AX80, UN-AX150, UQ-AX2(KR)UN-ML11, UN-ML21, UN-ML80, UN-ML150, UN-ML220

    Thermal Overload Relays TH-N12KP, TH-N18KP, TH-N20KP, TH-N20TAKP, TH-N60KP, TH-N60TAKP, TH-N120KP, TH-N120TAKP,TH-N220RHKP, TH-N220HZKP, TH-N400RHKP, TH-N400HZKP, TH-N600KP

    Contactor Relays A.C. operatedD.C. operated

    D.C. Interface Contactors Non-reversingReversing

    SR-N4SRD-N4SD-Q11, SD-Q12, SD-Q19SD-QR11, SD-QR12, SD-QR19

    Table 1.1.1

    Solid state Contactors (for motor/heater load)

    Solid state Contactors (for heater load)

    US-N5SS(TE), US-N8SS(TE), US-N20(TE), US-N30(TE), US-N40(TE), US-N50(TE), US-N70NS(TE), US-N80NS(TE),US-NH70NS(TE), US-NH80NS(TE), US-N20(TE)CX, US-N30(TE)CX, US-N40(TE)CX, US-N20(TE)RMUS-H20(DD), US-H30(DD), US-H40(DD), US-H50(DD), US-H20(DD)RM, US-H30(DD)RM

    Notes:1. Standard models are applicable under following conditions.Main circuits : AC-3 rated current at 440V AC max.(Main contacts) and rated continuous current.Auxiliary contacts : AC-15 rated current at 550V AC max.

    and rated continuous current.Operation coil : AC coil designation

    N10~N12, N18~N48 and SR-N4 ; AC12V~AC440VN20~N35 ; AC12V~AC380VN50~N150 ; AC24V~AC500VN180~N400 ; AC48V~AC500VDC coil designation DC12V~DC220V

    2. For contactors, standard models are with TV mark on the product.For other products, standard models are with no TV mark on the product.

    3. Finger protection type is certified according to DIN VDE 0106 part 100. For finger protection type, order model name followed by suffix CX.4. Models with built-in surge absorber (model name followed by SA) are also certified.5. Mirror contact function compliance certification has been obtained from TV. This product is suitable for use in a machine tool's interlock circuit. The mirror

    contact function refers to a function in which the auxiliary NC contact can withstand a 2500V impulse voltage without contacting even if the main contact melts.

    1.1.2 TV Certified Type Contactor Table 1.1.2 (1)

    S-N10(CX)(SA)S-N11(CX)(SA)S-N12(CX)(SA)S-N20(CX)(SA)S-N21(CX)(SA)S-N25(CX)(SA)S-N35(CX)(SA)S-N18(CX)(SA)S-N28(CX)(SA)S-N38(CX)(SA)S-N48(CX)(SA)S-N50/S-N65S-N80/S-N95S-N125S-N150S-N180/S-N220S-N300/S-N400SD-N11(CX)(SA)SD-N12(CX)(SA)SD-N21(CX)(SA)SD-N35(CX)(SA)SD-N50/SD-N65SD-N80/SD-N95SD-N125SD-N150SD-N220SD-N300/SD-N400

    Model Name Certificate No.

    EN60947-4-1 R9551340

    Applicable standardMirror contact5

    Internal auxiliary NC contact Auxiliary contact blockAuxiliary NC contact

    EN60947-4-1

    EN60947-4-1

    EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1

    EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1

    EN60947-4-1

    R9651190

    R9651189

    R9851170R9851138R9851169R9851167R9851164R9851171

    R9551336R9651190R9851170R9851138R9851169R9851167R9851164R9851171

    R9551340

    (UN-AX2(CX), UN-AX4(CX))

    (UN-AX2(CX), UN-AX4(CX))

    (UN-AX150)

    (UN-AX2(CX), UN-AX4(CX))

    (UN-AX150)

    EN60947-4-1 R9551336

    Solid state Contactors : EN60947-4-2, EN60947-4-3(for motor/heater load)Solid state Contactors : EN60947-4-3(for heater load)

  • 4Notes:1. Standard models are applicable under following conditions.Main circuits : AC-3 rated current at 440V AC max.(Main contacts) and rated continuous current.Auxiliary contacts : AC-15 rated current at 550V AC max. (SD-Q(R)11~Q(R)19 : 440V AC max.)

    and rated continuous current.Operation coil : AC coil designation

    SR-N4 ; AC12V~AC440VDC coil designation DC12V~DC220V (SD-Q(R)11~Q(R)19 : DC12V~DC24V)

    2. For contactors, standard models are with TV mark on the product.For other products, standard models are with no TV mark on the product.For contactor relays, order model name followed by suffix DZ if TV mark on the product is required.

    3. Finger protection type is certified according to DIN VDE 0106 part 100. For finger protection type, order model name followed bysuffix CX.

    4. Models with built-in surge absorber (model name followed by SA) are also certified.5. Miller contact function compliance certification has been obtained from TV. This product is suitable for use in a machine tool's

    interlock circuit. The miller contact function refers to a function in which the auxiliary NC contact can withstand a 2500V impulsevoltage without contacting even if the main contact melts.

    6. If the SD-Q11 with 1NC is required, it must be so indicated when placing an order.

    Thermal Overload RelayTH-N12(CX)KPTH-N18(CX)KPTH-N20(TA)(CX)KPTH-N60(TA)KPTH-N120(TA)KPTH-N220RHKP/HZKPTH-N400RHKP/HZKP

    Model Name Applicable standard Registration No.EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1EN60947-4-1

    J9551338J9551338J9551341J9851140J9851168J9851166J9851172

    Table 1.1.2 (3) DC Interface Contactor

    SD-Q11SD-Q12SD-Q19SD-QR11SD-QR12SD-QR19

    Model Name Certificate No.Miller contact5

    R2-50004919R2-50004919R2-50004918R2-50004919R2-50004919R2-50004918

    Table 1.1.2 (2)

    Internal auxiliary NC contact Auxiliary contact blockAuxiliary NC contact

    6 (UQ-AX2)

    Contactor RelaySR-N4(CX)(SA)SRD-N4(CX)(SA)

    Model Name Applicable standard Certificate No.EN60947-5-1EN60947-5-1

    R9551339R9551339

    Table 1.1.2 (4) Auxiliary Contact BlockUN-AX2(CX)UN-AX4(CX)UN-AX11(CX)UN-AX80UN-AX150

    Model Name Applicable standard Registration No.

    EN60947-5-1 J9551337

    EN60947-5-1 R9851225

    Table 1.1.2 (5)

    Solid state contactor (for motor/heater lord) Table 1.1.2 (6)

    Standard Finger protected Mounting on 35mm rail

    Certificate No.

    US- US-CX US-RM

    R50037627

    R50037628

    R50037629

    R50037630

    R50037628

    R50037628

    Model Name

    US-N5SS(TE)US-N8SS(TE)US-N20(TE)US-N30(TE)US-N40(TE)US-N50(TE)US-N70NS(TE)US-N80NS(TE)US-NH70NS(TE)US-NH80NS(TE)

    Approval rating (A)Heater (AC-51) Motor (AC-53)

    AC100-240V AC200-440V AC200-240V AC400-440V

    58203040

    50(45)7080

    34.8121824

    30(27)4248

    203040

    50(45)

    6575

    121824

    30(27)

    3945

    3.23.211.117.4262648484848

    11.117.42626

    4848

    40C 60C 40C 60C 40C 40C

    Applicablestandard

    Motor:EN60947-4-2

    Heater:EN60947-4-3

    Solid state contactor (for heater lord) Table 1.1.2 (7)

    Standard No cooling fin Mounting on 35mm rail

    Certificate No.

    US- US-HZ US-RM

    R50018958 R50018958R50018958

    Model Name

    US-H20(DD)US-H30(DD)US-H40(DD)US-H50(DD)

    Approval rating (A)Heater (AC-51)

    AC24-480V

    20304050

    12182430

    40C 60C

    Applicable standard

    Heater : EN60947-4-3

    Notes: 1. The number in the type field indicates the certificate number, and hyphen - indicates that there are no compatible models.2. The value in the certified rating field in the bracket ( ) indicates the rating for US-N50TE.3. The frame field (TE) indicates 3-pole, 3-element type main circuit.4. Standard models are with TV mark on the product.

    Notes: 1. The number in the type field indicates the certificate number, and hyphen - indicates that there are no compatible models.2. The frame field (DD) indicates 3-pole individual control.3. Standard models are with TV mark on the product.

  • 5S-N800UR2

    910

    250300600600

    12004

    S(D)-N11(CX)S(D)-N12(CX)

    20

    1/21-1/2

    33

    7-1/27-1/2

    MSO-N11KP(CX)N12KP(CX)

    33

    7-1/27-1/2

    30

    S-N10(CX)

    13

    1/21-1/2

    3355

    MSO-N10KP(CX)

    3355

    30

    A

    120V HP240V HP

    208V HP240V HP480V HP600V HP

    208V HP240V HP480V HP600V HP

    AA

    Conta-ctor

    (open)

    Starter(open)

    Max. rating of shortcircuit protection deviceFuse class K5Circuit breaker

    S-N18(CX)

    30

    1355

    1010

    MSO-N18KP(CX)

    55

    1010

    70

    S-N20(CX)S(D)-N21(CX)

    30

    1355

    1010

    MSO-N20KP(CX)N21KP(CX)

    55

    1010

    70

    S-N25(CX)

    35

    23

    7-1/27-1/2

    1515

    MSO-N25KP(CX)

    7-1/27-1/2

    1515

    100100

    S(D)-N35(CX)

    40

    25

    10102020

    MSO-N35KP(CX)

    10102020

    125125

    S(D)-N50

    80

    37-1/2

    15153030

    MSO-N50KP

    15153030

    250

    S(D)-N65

    95

    31015204040

    MSO-N65KP

    15204040

    250

    S(D)-N80

    100

    515

    20255050

    MSO-N80KP

    20255050

    300300

    S(D)-N1252

    125

    102040407575

    MSO-N125KP 2

    40407575

    350350

    S(D)-N952

    100

    7-1/215

    25306060

    MSO-N95KP 2

    25306060

    225225

    S(D)-N1502

    150

    1525

    4050100100

    MSO-N150KP 2

    4050100100

    350350

    S-N1802

    220

    15306060125125

    MSO-N180KP 2

    6060125125

    500500

    S(D)-N2202

    220

    15406075150150

    MSO-N220KP 2

    6075150150

    500500

    S(D)-N3002

    300

    100100200200

    MSO-N300KP 2

    100100200200

    6003600

    S(D)-N4002

    400

    125150300300

    MSO-N400KP 2

    125150300300

    50031000

    S-N6002

    680

    150200400400

    8004

    Notes: 1. UL listed types for S-N600 and S-N800 require suffix letters UL (eg. S-N800UL).2. Types S-N95 to S-N800 and MSO-N95KP to N400KP with Ilsco lugs are also listed as type name with suffix letters UL (eg. S-N95UL)3. Time delay fuse4. Class L fuse

    1.1.3 UL Approval for U.S.A. and Canada Contactor and Motor Starter

    Model Name

    Continuous current ratingopen

    Horsepower ratingSingle phase

    Three phase

    Model Name

    Horsepower ratingThree phase

    Mark

    Mark

    Table 1.1.3 (1)

    Type Model Name MarkRatings

    UN-AX2(CX)UN-AX4(CX)UN-AX11(CX)

    UN-AX80UN-AX150

    SR-N4SRD-N4

    Contactor Relay

    Auxiliary Contact Block

    Contactor Relay and Auxiliary Contact Block Table 1.1.3 (3)

    Rated Code;A600AC600V maxMake 7200VABreak 720VA

    Rated Code;R300DC250V maxMake 28VABreak 28VA

    Thermal Overload Relay Table 1.1.3 (2)

    0.12A(0.1~0.16),0.17(0.14~0.22),0.24A(0.2~0.32),0.35A(0.28~0.42),0.5A(0.4~0.6),0.7A(0.55~0.85),0.9A(0.7~1.1),1.3A(1~1.6),1.7A(1.4~2),2.1A(1.7~2.5),2.5A(2~3),3.6A(2.8~4.4),5A(4~6),6.6A(5.2~8),9A(7~11),11A(9~13)

    Model Name

    TH-N12(CX)KPTH-N12(CX)1TH-N12(CX)HZKP2TH-N12(CX)HZ1TH-N18(CX)KPTH-N18(CX)1

    1.3A(1~1.6),1.7(1.4~2),2.1A(1.7~2.5),2.5A(2~3),3.6A(2.8~4.4),5A(4~6),6.6A(5.2~8),9A(7~11),11A(9~13),15A(12~18)0.24A(0.2~0.32),0.35A(0.28~0.42),0.5A(0.4~0.6),0.7A(0.55~0.85),0.9A(0.7~1.1),1.3A(1~1.6),1.7A(1.4~2),2.1A(1.7~2.5),2.5A(2~3),3.6A(2.8~4.4),5A(4~6),6.6A(5.2~8),9A(7~11),11A(9~13),15A(12~18)

    TH-N20(CX)KPTH-N20(CX)1TH-N20CXHZKPTH-N20CXHZ1TH-N20TAKPTH-N20TA1

    22A(18~26)29A(24~34)

    TH-N60KP 15A(12~18),22A(18~26),29A(24~34),35A(30~40),42A(34~50)54A(43~65)TH-N60TAKP 67A(54~80)82A(65~100)TH-N120KP 42A(34~50),54A(43~65),67A(54~80),82A(65~100)

    105A(85~125)125A(100~150)82A(65~100),105A(85~125),125A(100~150),150A(120~180)180A(140~220)

    TH-N220RHKPTH-N220HZKP

    105A(85~125),125A(100~150),150A(120~180),180A(140~220),250A(200~300)330A(260~400)

    TH-N400RHKPTH-N400HZKP

    Heater designation (Rated current [A]) Contactor tobe coupled

    S-N10S-N11S-N12

    S-N18

    S-N20S-N21S-N25S-N35

    S-N25,N35S-N35

    S-N50,N65,N80,N95S-N65,N80,N95

    S-N80,N95S-N95

    S-N125,N150S-N125,N150

    S-N150S-N180,N220

    S-N220S-N300,N400

    S-N400

    Auxiliary Contact

    RatedCode

    Make

    C600AC600Vmax

    1800VA(15A max)Break 180VA(1.5A max)

    RatedCode

    Make

    B600AC600Vmax

    3600VA(30A max)Break 360VA(3A max)

    /

    /

    TH-N120TAKP

    Notes: 1. is to be coupled with contactor and can not be mounted separately from contactor. is only for separate mounting.2. Suffix KP ; Overload and phase failure protection type with three heater elements.3. 1 ; TH-N12(CX), N12(CX)HZ, N18(CX), N20(CX), N20CXHZ and N20TA are recognized ( ) for single phase motors.4. 2 is to be coupled with TH-N12(CX)KP ( ) and UN-HZ12( ).

  • 6 DC Interface Contactor Table 1.1.3 (4)

    SD-Q11SD-Q12MSOD-Q11(KP)MSOD-Q12(KP)SD-Q19MSOD-Q19(KP)

    Model Name Continuouscurrent rating [A]

    Horsepower rating [HP]Single-phase (only non-reversing type) three-phase

    Note: 1. MSOD-Q11, Q12 and Q19 are approved for single-phase circuits.

    Non-reversing type Reversing typeSD-QR11SD-QR12MSOD-QR11KPMSOD-QR12KPSD-QR19MSOD-QR19KP

    110 ~ 120V 220 ~ 240V 200 ~ 208V 220 ~ 240V 440 ~ 480V

    20

    13

    3018

    13

    12

    1 3 3 5

    1 12 5 5 712

    Model Name

    US-N5SSUS-N8SSUS-N20(CX)(RM)US-N30(CX)US-N40(CX)US-N50(CX)US-N70NSUS-N80NSUS-NH70NSUS-NH80NS

    US-N5SSTEUS-N8SSTEUS-N20TE(CX)(RM)US-N30TE(CX)US-N40TE(CX)US-N50TE(CX)US-N70NSTEUS-N80NSTEUS-NH70NSTEUS-NH80NSTE

    1223333

    15151515

    353

    33

    5102020

    3030

    582030405070807080

    100~120V 220~240V 220~240V 440~480V3-pole,2-element type 3-pole,3-element type

    Solid state contactor (for motor/heater load) Table 1.1.3 (5)Continuous

    current rating [A]

    110

    110

    12

    1414

    127

    127

    127

    127

    121

    127

    127

    3434

    Single-phase three-phase Horsepower rating [HP]

    US-H20(RM)(HZ)US-H30(RM)

    US-H40US-H50

    US-H20DD(RM)(HZ)US-H30DD(RM)

    US-H40DDUS-H50DD

    20304050

    Solid state contactor (for heater load) Table 1.1.3 (6)Continuous current rating

    [A]Model Name

    Batch control Individual control

    Notes: 1. (HZ) has no cooling fin. (RM) is available rail mounting.2. The US-H (DD) HZ type is certified at the continuous current rating when combined with the fin used on the US-H (DD) type.

    3. The US-H (DD) HZ type is UR certified.

  • 71.1.4 CCC Certified ProductsMagnetic motor starters, etc., are designated as products targeted for China Compulsory Certification. CCC certification must be acquired before theproduct is exported to main land China from Domestic or marketed in China.The certified models are shown in Tables 1.1.4 (1-1) to 1.1.4 (8-2). The option units (UN-CV, ML, RR, SA, etc.) which are mounted on the magneticmotor starter and which do not have a load switching function are excluded from the CCC certification target.

    Model Name

    MSO-(2)N10MSO(D)-(2)N11MSO(D)-N12MSO-(2)N18MSO-(2)N20MSO(D)-(2)N21MSO-(2)N25MSO(D)-(2)N35MSO(D)-(2)N50KPMSO(D)-(2)N65KPMSO(D)-(2)N80KPMSO(D)-(2)N95KPMSO(D)-(2)N125KPMSO(D)-(2)N150KPMSO-(2)N180KPMSO(D)-(2)N220KPMSO(D)-(2)N300KPMSO(D)-(2)N400KP

    2.5/43.5/5.53.5/5.54.5/7.55.5/115.5/117.5/1511/18.515/22

    18.5/3022/4530/5537/6045/7555/9075/13290/160125/220

    Approval rating AC-3 Class(200~240V/380~440V) Heater

    designation

    Coil designationAC operated (MSO type)DC operated (MSOD type)Rated capacity (kW)

    11/913/1213/1218/1622/2222/2230/3040/4055/5065/6585/85

    105/105125/120150/150180/180250/250300/300400/400

    0.12-9A0.12-11A0.12-11A0.12-15A0.24-19A0.24-19A0.24-22A0.24-35A15-42A15-54A15-67A15-95A

    42-105A42-125A82-150A82-210A

    105-250A105-330A

    AC12V~AC500VDC12V~DC220V

    AC24V~AC500VDC12V~DC220V

    AC48V~AC500VDC12V~DC220V

    CX, KP, SA, SR

    CX, SA

    CX, KP, SA, SR

    CX, SR

    SR

    Certificate No.Type application range (combination possible)

    Number of aux. contacts

    Non-reversingStandard (special)

    20020103 04093078

    20020103 04093077

    20020103 04093076

    20020103 04093073

    20020103 04093064

    20020103 0409306720020103 04093079

    20020103 04093070

    20020103 04093066

    1NO(1NC)1NO(1NC)

    1NO1NC(2NO)

    1NO1NC(2NO)2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC

    Rated operational current (A)MSO : AC operatedMSOD : DC operated2 : Reversing type

    Table 1.1.4 (1-2)

    Notes: 1. The MSO-(2) N10KP, MSO(D)-(2)N11KP or MSO(D)-N12KP type with heater designation 0.12A and 0.17A are not certified.2. MSO-(2)N18KP type is not certified.

    Model Name

    MS-N10CNMS-N11CNMS-N12CNMS-N20CNMS-N21CNMS-N25CNMS-N35CNMS-N50CNKPMS-N65CNKPMS-N80CNKPMS-N95CNKPMS-N125CNKPMS-N150CNKPMS-N180CNKPMS-N220CNKPMS-N300CNKPMS-N400CNKP

    2.5/43.5/5.53.5/5.55.5/115.5/117.5/15

    11/18.515/22

    18.5/3022/4530/5537/6045/7555/90

    75/13290/160

    125/220

    Approval rating AC-3 Class(200~240V/380~440V) Heaterdesignation

    Coil designation

    AC operatedRated capacity (kW)11/9

    13/1213/1222/2222/2230/3040/4055/5065/6585/85

    105/105125/120150/150180/180250/250300/300400/400

    0.12~9A0.12~11A0.12~11A0.24~19A0.24~19A0.24~22A0.24~35A15~54A15~54A15~67A15~95A42~105A42~125A82~150A82~210A105~250A105~330A

    AC12V~AC500V

    AC24V~AC500V

    AC48V~AC500V

    KP, SA, PM

    KP, SA, PM

    PM

    Certificate No.Type application range (combination possible)

    Number of aux. contacts

    Non-reversingStandard (special)

    20030103 04093078

    20030103 04093077

    20030103 04093076

    20030103 04093073

    20030103 04093064

    20030103 0409306720030103 04093079

    20030103 04093070

    20030103 04093066

    1NO1NO

    1NO1NC(2NO)1NO1NC(2NO)

    2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC

    Rated operational current (A)

    Magnetic motor starter

    MS : AC operated

    Table 1.1.4 (1-1) With Enclosure

    Without Enclosure

  • 8Model Name

    S-(2)N10S(D)-(2)N11S(D)-N12S-(2)N18S-(2)N20S(D)-(2)N21S-(2)N25S(D)-(2)N35S(D)-(2)N50S(D)-(2)N65S(D)-(2)N80S(D)-(2)N95S(D)-(2)N125S(D)-(2)N150 S-(2)N180S(D)-(2)N220S(D)-(2)N300S(D)-(2)N400S(D)-(2)N600CNS(D)-(2)N800CN

    2.5/43.5/5.53.5/5.54.5/7.55.5/115.5/117.5/1511/18.515/22

    18.5/3022/4530/5537/6045/7555/9075/13290/160125/220190/330220/440

    Approval rating AC-3 Class(200~240V/380~440V)

    Conventional free air thermal

    currentIth (A)

    Coil designationAC operated (S type)DC operated (SD type)Rated capacity (kW)

    11/913/1213/1218/1622/2222/2230/3040/4055/5065/6585/85

    105/105125/120150/150180/180250/250300/300400/400630/630800/800

    202020253232506080100135150150200260260350450660800

    AC12V~AC500VDC12V~DC220V

    AC24V~AC500VDC12V~DC220V

    AC48V~AC500VDC12V~DC220V

    AC100V~AC500VDC24V~DC220V

    CX, SA

    CX

    Certificate No.Type application range (combination possible)Number of aux.

    contactsNon-reversing

    Standard (special)

    20020103 04023375

    20020103 04023377

    20020103 04024684

    20020103 04024704

    20020103 04024705

    20020103 0402470620020103 04024707

    20020103 04024708

    20020103 04024709

    20030103 04095569

    1NO (1NC)1NO (1NC)

    1NO1NC(2NO)

    1NO1NC (2NO)2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC

    Rated operational current (A)

    Magnetic Contactors

    S : AC operatedSD : DC operated2 : Reversing type

    Table 1.1.4 (2-1)

    Table 1.1.4 (2-2)Model Name

    SL(D)-(2)N21SL(D)-(2)N35SL(D)-(2)N50SL(D)-(2)N65SL(D)-(2)N80SL(D)-(2)N95SL(D)-(2)N125SL(D)-(2)N150SL(D)-(2)N220SL(D)-(2)N300SL(D)-(2)N400SL(D)-(2)N600CNSL(D)-(2)N800CN

    5.5/1111/18.515/22

    18.5/3022/4530/5537/6045/7575/13290/160125/220190/330220/440

    Approval rating AC-3 Class(200~240V/380~440V)

    Conventional free air thermal

    currentIth (A)

    Coil designationAC operated (SL type)DC operated (SLD type)Rated capacity (kW)

    22/2240/4055/5065/6585/85

    105/105125/120150/150250/250300/300400/400630/630800/800

    326080100135150150200260350450660800

    AC100V~AC500VDC12V~DC200V

    AC100V~AC500VDC24V~DC200V

    CX, SA

    CX

    Certificate No.Type application range (combination possible)Number of aux.

    contactsNon-reversing

    Standard20020103 0402337720020103 04024684

    20020103 04024704

    20020103 04024705

    20020103 0402470620020103 0402470720020103 04024708

    20020103 04024709

    20030103 04095569

    2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC2NO2NC

    1NO2NC

    Rated operational current (A)SL : AC operatedSLD : DC operated2 : Reversing type

    Table 1.1.4 (2-3)

    Model Name

    S-(2)N18S-(2)N28S-(2)N38S-(2)N48

    4.5/7.57.5/7.511/15

    15/18.5

    Approval rating AC-3 Class(200~240V/380~440V)

    Conventional free air thermal

    currentIth (A)

    Coil designation

    AC operated (S type)Rated capacity (kW)18/1626/1739/3250/40

    25306080

    AC12V~AC500V CX, SA

    Certificate No.Type application range (combination possible)Number of aux.

    contactsNon-reversing

    Standard

    20020103 04023377

    20020103 04024684

    Rated operational current (A)S : AC operated2 : Reversing type

    Model Name

    B(D)-N20CN

    B(D)-N65CN

    B(D)-N100CN

    DC110V 2P3P

    DC220V 2P3P

    DC110V 2P3P

    DC220V 2P3P

    DC110V 2PDC220V 2P

    B:1NO2NC,

    3NCBD:1NO2NC

    B:1NO2NCBD:1NO2NC

    Certification ratings (A)Maincontact

    Arrangement

    Conventional free air thermal

    currentIth (A)

    Coil designationAC operated (B type)DC operated (BD type)

    Number ofseries

    815152050320303

    25

    80

    120

    AC24V~AC500VDC12V~DC220V

    SA

    Number of aux. contacts

    Non-reversing

    20020103 04023377

    20020103 04024705

    20020103 04024706

    2NO

    2NO2NC

    2NO2NC

    NCDC-3,5

    1520510306510304020

    NCDC-1B : AC operated

    BD : DC operated

    Table 1.1.4 (2-4)

    Certificate No.Type application range (combination possible)

    General Type Contactors

    Mechanically Latched Contactors

    3-Pole Contactors

    NC Main Contact Type Contactors

  • 920020103 03024700

    20020103 03024720

    20020103 03024722

    20020103 03024720

    Model Name Certificate No.

    UN-AX2CNUN-AX4CNUN-AX11CNUN-AX80CNUN-AX150CNUN-AX600CNUN-LL22CN

    2NO, 1NO1NC4NO, 3NO1NC, 2NO2NC

    1NO1NC1NO1NC1NO1NC2NO2NC

    1NO1NC(low level), 1NO1NC(standard)

    Available contact arrangements

    CX

    CX

    S-N10~N65

    S-N10, N11, N20~N65S-N80~N125S-N150~N400S-N600, N800S-N10~N65, SR-N4

    Type application range(combination possible) Applicable magnetic contactor

    Auxiliary contact block Table 1.1.4 (4)

    Note: 1. The TH-N12KP type with heater designation 0.12A and 0.17A, and the TH-N18KP type are not certified.Note: 2. Heater designation 210A are certified for S-N220 type.

    20020103 09024710

    20020103 09024712

    20020103 09024714

    20020103 09024724

    20020103 09024719

    20030103 04095454

    Model Name Certificate No.

    TH-N12KP

    TH-N20KP

    TH-N20TAKPTH-N60KPTH-N60TAKPTH-N120KPTH-N120TAKPTH-N220RHKPTH-N220HZKPTH-N400RHKPTH-N400HZKPTH-N600KP

    0.24A, 0.35A, 0.5A, 0.7A, 0.9A, 1.3A, 1.7A, 2.1A, 2.5A, 3.6A, 5A, 6.6A, 9A, 11A0.24A, 0.35A, 0.5A, 0.7A, 0.9A, 1.3A, 1.7A, 2.1A, 2.5A, 3.6A, 5A, 6.6A, 9A, 11A, 15A22A, 29A15A, 22A, 29A, 35A, 42A, 54A67A, 82A42A, 54A, 67A, 82A105A, 125A

    82A, 105A, 125A, 150A, 180A, 210A2

    105A, 125A, 150A, 180A, 250A, 330A

    250A, 330A, 500A, 660A

    Heater designation

    CX, HZ

    CX, HZ, SR

    CX, SRCX, SR

    SRHZ, SR

    SR

    SR

    S-N10~N12

    S-N20~N35

    S-N25, N35S-N50~N95S-N80, N95

    S-N125, N150

    S-N180, N220

    S-N300, N400

    Type application range (combination possible)

    Combination magnetic contactor

    Thermal overload relay

    Dedicated for independent mounting

    Dedicated for independent mountingDedicated for independent mounting

    Table 1.1.4 (3-1) Three heater type with phase failure protection

    Model Name

    SD-Q11SD-Q12SD-Q19SD-QR11SD-QR12SD-QR19

    3/4

    4.5/5.5

    3/4

    4.5/5.5

    Approval rating AC-3 Class(200~240V/380~440V)

    Conventional free air thermal

    currentIth (A)

    Coil designation

    DC operationRated capacity (kW)

    12/9

    18/13

    12/9

    18/13

    20

    30

    20

    30

    DC24V

    DC24V

    Certificate No.Number of aux. contacts

    Standard (special)

    20030103 04095567

    20030103 04086213

    20030103 04095567

    20030103 04086213

    1NO(1NC)1NO1NC(2NO)1NO1NC(2NO)

    2NC2NO2NC2NO2NC

    Rated operational current (A)Q : Non-reversing typeQR : Reversing type

    Table 1.1.4 (5-2) Magnetic contactor

    Magnetic motor starter

    Note: 1. Heater designation 0.12A and 0.17A are not certified for MSOD-Q11KP and Q12KP types.

    Model Name

    MSOD-Q11MSOD-Q12MSOD-Q19MSOD-QR11MSOD-QR12MSOD-QR19

    3/4

    4.5/5.5

    3/4

    4.5/5.5

    Approval rating AC-3 Class(200~240V/380~440V) Heaterdesignation

    Coil designation

    DC operationRated capacity (kW)

    12/9

    18/13

    12/9

    18/13

    0.12~11A

    1.3~15A

    0.12~11A

    1.3~15A

    DC24V

    DC24V

    CX, KP

    CX

    CX, KP

    CX

    Certificate No.Type application range (combination possible)Number of aux.

    contactsStandard (special)

    20030103 04093069

    20030103 04093080

    20030103 04093069

    20030103 04093080

    1NO(1NC)1NO1NC(2NO)1NO1NC(2NO)

    2NC2NO2NC2NO2NC

    Rated operational current (A)

    DC interface contactor

    Q : Non-reversing typeQR : Reversing type

    Table 1.1.4 (5-1)

    20020103 0902470120020103 09024702

    20020103 09024703

    Model Name Certificate No.

    TH-N12TH-N18TH-N20TH-N20TA

    0.12A, 0.17A, 0.24A, 0.35A, 0.5A, 0.7A, 0.9A, 1.3A, 1.7A, 2.1A, 2.5A, 3.6A, 5A, 6.6A, 9A, 11A1.3A, 1.7A, 2.1A, 2.5A, 3.6A, 5A, 6.6A, 9A, 11A, 15A0.24A, 0.35A, 0.5A, 0.7A, 0.9A, 1.3A, 1.7A, 2.1A, 2.5A, 3.6A, 5A, 6.6A, 9A, 11A, 15A22A, 29A, 35A1

    Heater designation

    CX, HZ, SRCX, DM

    CX, HZ, SRCX, SR

    S-N10~N12S-N18S-N20~N35S-N25, N35

    Type application range (combination possible)

    Combination magnetic contactor

    Table 1.1.4 (3-2) Two heater type

    Note: 1. Heater designation 35A are certified for S-N35 type.

  • 10

    Model Name

    SR-N4SRD-N4SRL-N4SRLD-N4

    Coil designationAC operated (SR, SRL type)

    DC operated (SRD, SRLD type)AC12V~AC440VDC12V~DC220VAC100V~AC440VDC12V~DC200V

    4NO, 3NO1NC, 2NO2NC

    4NO, 3NO1NC, 2NO2NCCX, SA

    Certificate No.Available contact arrangementType application range (combination possible)

    20020103 03024696

    Contactor RelaysSR : AC operatedSRD : DC operatedSRL : AC operatedSRLD : DC operated

    Table 1.1.4 (6)

    SRT(D)-NNCNSRT(D)-NFCN

    Coil designationAC operated (SRT type)

    DC operated (SRTD type)AC12V~AC440VDC12V~DC220V

    Instantaneous : 2NO2NCDelayed : 1NO1NCCX, SA

    Certificate No.Available contact arrangementType application range (combination possible)

    20050103 03152666

    Pneumatic Time Delay Relays Table 1.1.4 (7)Model Name

    SRT : AC operatedSRTD : DC operated

    Solid State ContactorsTable 1.1.4 (8-1)

    US-N5SSUS-N8SSUS-N20US-N30US-N40US-N50US-N70NSUS-N80NSUS-NH70NSUS-NH80NS

    582030405070806575

    DC12~24V

    0.4 (3.2) /0.4 (3.2) /

    2.2 (11.1) /3.7 (8.7)3.7 (17.4) /7.5 (17.4)

    5.5 (26) /11 (26)5.5 (26) /11 (26)

    11 (48) /11 (48) /

    11 (48) /22 (48)11 (48) /22 (48)

    CX, RM

    CX

    Certificate No.Approval rating

    AC-51 class(A)

    1.9/3.0/

    7.6/13.111.4/19.715.2/26.319.0/32.9

    26.6/30.4/

    24.7/42.728.5/49.3

    3-ph Heater capacity220/380V

    AC-51 (kW)

    3-ph Motor capacity220-240/380-440V

    AC-53a (kW(A))Rated operating

    voltage

    Type application range (combination

    possible)

    20060103 04174448

    20050103 04162980

    20060103 04174451

    Model Name

    2-elements type

    Table 1.1.4 (8-2)

    US-N5SSTEUS-N8SSTEUS-N20TEUS-N30TEUS-N40TEUS-N50TEUS-N70NSTEUS-N80NSTEUS-NH70NSTEUS-NH80NSTE

    582030405070806575

    DC12~24V

    0.4 (3.2) /0.4 (3.2) /

    2.2 (11.1) /3.7 (8.7)3.7 (17.4) /7.5 (17.4)

    5.5 (26) /11 (26)5.5 (26) /11 (26)

    11 (48) /11 (48) /

    11 (48) /22 (48)11 (48) /22 (48)

    CX, RM

    CX

    Certificate No.Approval rating

    AC-51 class(A)

    1.9/3.0/

    7.6/13.111.4/19.715.2/26.317.1/29.6

    26.6/30.4/

    24.7/42.728.5/49.3

    3-ph Heater capacity220/380V

    AC-51 (kW)

    3-ph Motor capacity220-240/380-440V

    AC-53a (kW(A))Rated operating

    voltage

    Type application range (combination

    possible)

    20060103 04174448

    20050103 04162980

    20060103 04174451

    Model Name

    3-elements type

    Model Name

    SH(D)-V160CNSH(D)-V320CNSH(D)-V400CNSHL(D)-V160CNSHL(D)-V320CNSHL(D)-V400CN

    SH : AC operatedSHD : DC operatedSL : Mechanical Latched(AC operated)SLD : Mechanical Latched(DC operated)

    Conventional free air thermal

    currentIth (A)200350450200350450

    Coil designation

    AC100V~AC500VDC100V, DC200V

    AC100V~AC500VDC100V, DC200V

    Certificate No.Number of aux. contacts

    Standard

    20060103 04201618

    20060103 04201618

    2a2b

    SHL : 2a2bSHLD : 2a4b

    45/90/22075/150/40095/200/50045/90/22075/150/40095/200/500

    Approval rating AC-3 Class(200~240V/380~440V/1000V)

    Rated capacity (kW)180/180/160320/320/320400/400/400180/180/160320/320/320400/400/400

    Rated operational current (A)

    Medium Voltage Vacuum Contactors

    20070103 03224330

    Model Name Certificate No.

    SRE-AACNSRE-AAUCNSRE-KCNSRE-KTCN

    AC3V~AC250VDC0.1V~DC250V

    AC75V~AC250V, DC9V~DC105VAC80V~AC260V, DC10V~DC115V

    Detectable voltage rangeMin~Max

    1c

    Output contact arrangement

    Voltage Detection Relays

    20070103 03224347Model Name Certificate No.

    SRS-HNPSCN AC100V, AC200V, AC400VControl voltage designation

    Instantaneous : 1c, Delayed : 1cOutput contact arrangement

    Solid State Time Delay Relays

    Table 1.1.4 (9)

    Table 1.1.4 (10)

    Table 1.1.4 (11)

  • 11

    Lloyds Register of Shipping (LR) Bureau Veritas (BV)

    S-N10, N11, N12, N20, N21(CX)SD-N11, N12, N21(CX)(SA)S-N18, N25, N28, N35(CX)(SA)/SD-N35(CX)(SA)S/SD-N50, N65, N80, N95S/SD-N125, N150, N220, N300, N400, S-N180S/SD-N600, N800TH-N12 (CX)(KP), N20(CX)(KP)TH-N18(CX)(KP), N20TA(CX)(KP)TH-N60(KP), N60TA(KP), N120(KP), N120TA(KP), N220(KP), N400(KP)TH-N600(KP)SR-N4(CX)SRD-N4(CX)UN-AX2, AX4, AX11(CX)UN-AX80, AX150, AX600

    Type BV Certificate No.061392634/69872634/69882634I/079052634I/079052634I/07905061392634/69882634I/079052634I/07905061392634/6987061392634I/07905

    Model Name

    Contactor

    Thermal Overload Relay

    Contactor Relay

    Auxiliary Contact Block

    LR Certificate No.95/1000896/1003596/1003498/1001698/1001698/1001695/1000996/1003398/1001798/1001795/1001096/1003595/1001098/10016

    Note

    AC-3Maximum 550VStandard modelcan be applied.

    Maximum 550VStandard modelcan be applied.

    AC-15Maximum 550VStandard modelcan be applied.

    Korean Register of Shipping (KR)

    KOB02571-EL020KOB02571-EL018KOB02571-EL020KOB02571-EL020KOB02571-EL020KOB02571-EL020

    Contactor Model Name Certificate No.

    Note: 1. Standard models are applicable. (AC3 Max. 440V according to JEM standard.)

    S-N10(CX)S-KR11S-N11(CX)S-N12(CX)S-N18(CX)(SA)S-N20(CX)

    KOB02571-EL020KOB02571-EL020KOB02571-EL020KOB02571-EL020KOB02571-EL020KOB02571-EL020

    Contactor Model Name Certificate No.S-N21(CX)S-N25(CX)(SA)S-N35(CX)(SA)S-N50S-N65S-N80

    KOB02571-EL020KOB02571-EL020KOB02571-EL020KOB02571-EL020KOB02571-EL020KOB02571-EL020

    Contactor Model Name Certificate No.S-N95S-N125S-N150S-N220S-N300S-N400

    Nippon Kaiji Kyokai (NK)Contactor Model Name Certificate No.

    Note: 1. Standard models are applicable. (AC3 Max. 440V according to JEM standard.)

    S-N10(CX)S-KR11S-N11(CX)S-N12(CX)S-N18(CX)(SA)S-N20(CX)S-N21(CX)S-N25(CX)(SA)S-N35(CX)(SA)S-N50S-N65S-N80S-N95

    SD-N11(CX)SD-N12(CX)

    SD-N21(CX)

    SD-N35(CX)(SA)SD-N50SD-N65SD-N80SD-N95

    94T41585T40594T41694T41795T40494T41894T41995T402

    98T40398T40498T40598T406

    95T403 96T401

    Contactor Model Name Certificate No.S-N125S-N150S-N180S-N220S-N300S-N400S-N600S-N800

    S-N38(CX)(SA)S-N48(CX)(SA)

    B-N20B-N65

    B-N100

    SD-N125SD-N150

    SD-N220SD-N300SD-N400SD-N600SD-N800

    BD-N20BD-N65

    BD-N100

    98T40798T40898T40998T41098T41198T41285T40685T40796T40296T40396T40401T40101T402

    Contactor Model Name Certificate No.SL(D)-N21NKSL(D)-N35NKSL(D)-N50NKSL(D)-N65NKSL(D)-N80NKSL(D)-N95NK

    SL(D)-N125NKSL(D)-N150NKSL(D)-N220NKSL(D)-N300NKSL(D)-N400NKSL(D)-N600NKSL(D)-N800NK

    95T40196T40198T41398T41498T41598T41698T41798T41898T41998T42098T42185T40885T409

    1.1.5 Approved Marine Standards

    Table 1.1.5 (1)

    Table 1.1.5 (2)

    Table 1.1.5 (3)

  • 12

    Three-phase motorratings IEC categoryAC-3 kW(hp)

    11(15)18.5(25)18.5(25)15(20)

    602NO+2NC

    121

    1

    2.5(3-1/4)4(5-1/2)4(5-1/2)4(5-1/2)

    201NO1NC

    121

    1

    1.2 Selection Guide

    220-240V380-440V500V690V

    1NO + 1NC (front)1NO + 1NC (side)2NO + 2NC (front)Low level signal (front)[1NO+1NC(+Standard 1NO + 1NC)]

    Conventional free air thermal current Ith AAuxiliary contacts1 (standard)

    (special)

    3.5(4-1/2)5.5(7-1/2)5.5(7-1/2)5.5(7-1/2)

    201NO1NC

    121

    1

    3.5(4-1/2)5.5(7-1/2)5.5(7-1/2)5.5(7-1/2)

    201NO+1NC

    2NO1

    1

    1

    4.5(6)7.5(10)7.5(10)7.5(10)

    25

    2

    1

    1

    1

    5.5(7-1/2)11(15)11(15)7.5(10)

    321NO+1NC

    2NO121

    1

    5.5(7-1/2)11(15)11(15)7.5(10)

    322NO+2NC

    121

    1

    7.5(10)15(20)15(20)11(15)

    502NO+2NC

    121

    1

    Notes: 1. Number of auxiliary contact shows that for non-reversing type. Twice of the auxiliary contacts are provided on reversing type.2. (2NO + 2NC) 2 auxiliary contacts are provided on reversing type and no additional contact can be mounted.3. Front clip-on and side clip-on block should not be mounted both.

    MS-N35(KP)

    MSO-N35(KP)(CX)

    S-N18(CX)S-2xN18(CX)

    DC operated models

    MS-N25(KP)

    MSO-N25(KP)(CX)

    S-N10(CX)S-2xN10(CX)

    Non-reversingReversing

    S-N11(CX)S-2xN11(CX)SD-N11(CX)

    S-N12(CX)

    SD-N12(CX)

    S-N20(CX)S-2xN20(CX)

    S-N21(CX)S-2xN21(CX)SD-N21(CX)

    S-N25(CX)S-2xN25(CX)

    S-N35(CX)S-2XxN35(CX)SD-N35(CX)

    AC operated models

    MS-N10(KP)

    MSO-N10(KP)(CX)

    Enclosed type (IP20) MS-N11(KP)

    MSO-N11(KP)(CX)

    MS-N20(KP)

    MSO-N20(KP)(CX)

    MS-N21(KP)

    MSO-N21(KP)(CX)

    Open type (IP00) MSO-N18(KP)(CX)

    Contactors

    MS-N12(KP)

    MSO-N12(KP)(CX)

    Staters (AC operated)

    Thermal Overload Relays1

    0.2~0.32(0.24A)0.28~0.42(0.35A)0.4~0.6(0.5A)0.55~0.85(0.7A)0.7~1.1(0.9A)1~1.6(1.3A)1.4~2(1.7A)1.7~2.5(2.1A)

    1~1.6(1.3A)1.4~2(1.7A)1.7~2.5(2.1A)2~3(2.5A)2.8~4.4(3.6A)4~6(5A)5.2~8(6.6A)7~11(9A)9~13(11A)12~18(15A)

    Three heater type withphase failure protectionTwo heater type

    Heater setting range A(Ordering designation)

    TH-N12(CX)TH-N12KP(CX)

    TH-N18(CX)TH-N18KP(CX)

    0.1~0.16(0.12A)0.14~0.22(0.17A)0.2~0.32(0.24A)0.28~0.42(0.35A)0.4~0.6(0.5A)0.55~0.85(0.7A)0.7~1.1(0.9A)1~1.6(1.3A)1.4~2(1.7A)

    1.7~2.5(2.1A)2~3(2.5A)2.8~4.4(3.6A)4~6(5A)5.2~8(6.6A)7~11(9A)9~13(11A)2

    2~3(2.5A)2.8~4.4(3.6A)4~6(5A)5.2~8(6.6A)7~11(9A)9~13(11A)12~18(15A)16~22(19A)3

    TH-N20(CX)TH-N20KP(CX)

    TH-N20TA(CX)TH-N20TAKP(CX)

    18~26(22A)24~34(29A)30~40(35A)4

    Notes: 1. Saturable reactors for thermal overload relays are available as a kit or equipped with the relay. The suffix SR following the modelname of the relay indicates with saturable reactor. (ex. TH-N20KPSR*5A) (Except for type TH-N12KP, TH-N18 and TH-N18KP)

    2. Except for size N10. 3. For size N20 & N21 only. 4. For size N35 only.

    S-2xN11 MSO-N12 S-N21CX MSO-N35

    Number of additionalauxiliary contactblock for 3

    Note: 1.Products which model names are provided with suffix CX are provided with finger protection. (N10~N65)Especially N10~N35 with suffix CX are provided with CAN terminals.

    S-N11CX

  • 13

    S-N800S-N400S-N65 S-N125Table 1.2.137(50)

    60(80)60(80)60(80)

    1502NO+2NC

    2

    22(30)45(60)45(60)45(60)

    1352NO+2NC

    2

    30(40)55(75)55(75)55(75)

    1502NO+2NC

    2

    15(20)22(30)25(34)22(30)

    802NO+2NC

    1

    18.5(25)30(40)37(50)30(40)

    1002NO+2NC

    1

    45(60)75(100)90(125)90(125)

    2002NO+2NC

    2

    55(75)90(125)

    110(150)110(150)

    2602NO+2NC

    2

    75(100)132(180)132(180)132(180)

    2602NO+2NC

    2

    90(125)160(210)160(210)200(270)

    3502NO+2NC

    2

    125(170)220(300)225(330)250(330)

    4502NO+2NC

    2

    190(250)330(450)330(450)330(450)

    8002NO+2NC

    1

    220(300)440(600)500(670)500(670)

    10002NO+2NC

    1

    S-N50(CX)S-2N50(CX)

    SD-N50

    S-N125S-2N125SD-N125

    S-N80S-2N80SD-N80

    S-N95S-2N95SD-N95

    S-N65(CX)S-2N65(CX)

    SD-N65

    S-N150S-2N150SD-N150

    S-N180S-2N180

    S-N220S-2N220SD-N220

    S-N300S-2N300SD-N300

    S-N400S-2N400SD-N400

    S-N600S-2N600SD-N600

    S-N800S-2N800SD-N800

    MS-N50(KP)

    MSO-N50(KP)(CX)

    MS-N125(KP)

    MSO-N125(KP)

    MS-N80(KP)

    MSO-N80(KP)

    MS-N95(KP)

    MSO-N95(KP)

    MS-N65(KP)

    MSO-N65(KP)(CX)

    MS-N150(KP)

    MSO-N150(KP)

    MS-N180(KP)

    MSO-N180(KP)

    MS-N220(KP)

    MSO-N220(KP)

    MS-N300(KP)

    MSO-N300(KP)

    MS-N400(KP)

    MSO-N400(KP)

    12~18(15A)18~26(22A)24~34(29A)30~40(35A)34~50(42A)43~65(54A)

    54~80 (67A)65~100(82A)85~105(95A)5

    TH-N60TAKP

    TH-N60(CX) TH-N60TA

    34~50 (42A)43~65 (54A)54~80 (67A)65~100(82A)

    TH-N120KP

    TH-N120

    85~125 (105A)100~150(125A)6

    TH-N120TAKP

    TH-N120TA

    65~100 (82A)85~125 (105A)100~150(125A)120~180(150A)140~220(180A)7170~250(210A)7

    TH-N220RHKP

    TH-N220RH

    85~125 (105A)100~150(125A)120~180(150A)140~220(180A)200~300(250A)260~400(330A)8

    TH-N400RHKP

    TH-N400RH

    200~300(250A)260~400(330A)400~600(500A)520~800(660A)10

    TH-N600KP9

    TH-N6009

    TH-N60KP(CX)

    5. For size N95 only. 6. For size N150 only. 7. For size N220 only. 8. For size N400 only. 9. TH-N600(KP) must be used with the current transformers (to be supplied by the customer.) See Table 2.1.2.10. For size N800 only.

    Table 1.2.1

  • 14

    N50

    15

    22

    N65

    18.5

    30

    N20

    5.5

    11

    1NO1NC

    2NO

    N11

    3.5

    5.5

    1NO

    1NC

    N18

    4.5

    7.5

    N12

    3.5

    5.5

    1NO1NC

    2NO

    N21

    5.5

    11

    Mounting on 35mm rail

    Notes: 1. Additional head-on type aux. contact blocks cannot be attached to the enclosed type, mechanically latched type of size N50 & N65.2. Surge absorber is provided as a standard on ac operated contactors and starters of sizes N50 to N800.

    N300

    90

    160

    1.3 The Overview (Type designation breakdown)

    N10

    2.5

    4

    1NO

    1NC

    N180

    55

    90

    Provided as a standard

    N125

    37

    60

    N800

    220

    440

    N600

    190

    330

    N80

    22

    45

    N150

    45

    75

    2NO2NC

    AttachableAttachable

    Available

    N95

    30

    55

    N220

    75

    132

    N400

    125

    220

    Frame Size

    Rated capacity

    Category AC-3(kW)

    Number ofaux. contacts

    Additional aux.contact blocks

    Surge absorber3

    Mechanical interlock unitAC operatedDC operated

    Finger protected

    Mechanically latchedAC operatedDC operatedWith phase failure protectionSlow trip typewith saturable reactorQuick-trip typewith 2 heater elementswith phase failure protection

    Standard typeWith push buttonWith phase failure protection

    Spec

    ACCE

    SSO

    RIES

    Ope

    nCO

    NTAC

    TORS

    220-240V

    380-440V

    Standard

    Special

    Front-on1

    Side-on

    S-SD-S- CXSD- CXSL(D)-MSO-MSOD-MSO- KP

    MSO- SR

    MSO- FSMSO- KFMS-MS- PMMS- KP

    STAR

    TERS O

    pen

    Encl

    osed

    Clas

    s IP2

    0

    1NO1NC2(max.)

    1.3.1 Non-Reversing Types

    1NO1NC2(max.) 2NO2NC1(max.)

    N25

    7.5

    15

    Attachable

    N35

    11

    18.5

    2P or 4P

    Table 1.3.1

  • 15

    Notes: 1. Additional head-on type aux. contact blocks cannot be attached to the enclosed type, mechanically latched type of size N50 & N65.2. Surge absorber is provided as a standard on ac operated contactors and starters of sizes 2xN50 to 2xN800.3. Remove a mounting plate for mounting on 35mm rail of sizes 2xN25 to 2xN65.

    Mounting on 35mm rail

    STAR

    TERS

    2xN20

    5.5

    11

    1NO1NC2

    2xN21

    5.5

    11

    2xN25

    7.5

    15

    2xN11

    3.5

    5.5

    1.3.2 Reversing Type2x

    N180

    55

    90

    Provided as a standard

    2xN400

    125

    220

    2xN18

    4.5

    7.5

    2NO2NC2

    Attachable

    Available3

    2xN10

    2.5

    4

    220-240V

    380-440V

    Standard

    Special

    Front-on1

    Side-on

    S-SD-S- CXSL(D)-MSO-MSOD-MSO- KP

    MSO- SR

    MSO- FSMSO- KFMS-MS- KP

    2xN125

    37

    60

    2xN95

    30

    55

    2xN600

    190

    330

    2xN150

    45

    75

    2xN220

    75

    132

    2xN300

    90

    160

    2xN800

    220

    440

    2xN80

    22

    45

    2xN65

    18.5

    30

    2xN50

    15

    22

    2xN35

    11

    18.5

    Rated capacity

    Category AC-3(kW)

    Number ofaux. contacts

    Additional aux.contact blocksSurge absorber2

    AC operatedDC operatedFinger protectedMechanically latchedAC operatedDC operatedWith phase failure protectionSlow trip typewith saturable reactorQuick-trip typewith 2 heater elementswith phase failure protectionStandard typeWith phase failure protection

    2NO2NC2

    Spec

    ACCE

    SS-

    ORIE

    SO

    pen

    CONT

    ACTO

    RSEn

    clos

    ed(IP

    20)

    1NO1NC2

    3NO3NC2

    Frame Size

    4NO4NC2

    1NO1NC2

    1NO1NC2

    4P2 2P2

    4P2 2P2

    Ope

    n

    Table 1.3.2

  • 16

    69032

    12(32)20(32)25(32)30(32)

    2222179

    2.23.73.73.713

    202020

    20158

    5.5101010

    220/220220/220

    1,8001,800600

    15103312

    9015499

    10

    1-61-6

    1-2.5

    69020

    7.5(20)7(11)7(8)7(6)

    11975

    0.751.11.11.16

    1088

    642

    2.23.34

    3.3

    110/110100/721,8001,800600

    1510

    457

    2.4

    10

    1-2.51-2.51-2.5

    690100

    35(100)65(100)85(100)

    100(100)

    65656038

    7.511111147

    656550

    403515

    20403540

    650/620650/620

    1,2001,200600

    25535715

    115202.21818

    5

    2-252-251-2.5

    Rated insulation voltageConventional free air thermal currentRated capacity for resistive loads3-ph, Category AC-1

    Rated operational current3-ph, Category AC-3

    Rated capacity for jogging of AC motors3-ph, category AC-4Electrical life is ca.200,000 operations

    Max. current for AC-4 duty at 440VRated current for DC non-inductive loadsCategory DC-1100 operations/hour max.500,000 operations

    Rated Current for DC motorsCategory DC-2 & DC-4100 operations/hour max.500,000operations

    Applicable standard: JEM-1038 (JAPAN)Rated capacity for 3-ph, capacitors4120 operations/hour max.Electrical durability at maximum load:100,000 operations(ambient temperature 40C)Making & breaking3-ph, cos=0.35240V/440VSwitching frequency

    Operating time (at rated coil voltage)AC operated

    DC operated

    Coil consumption (at rated coil voltage)AC operated

    DC operated

    Coil voltage toleranceMechanical endurance (make/break operations)Permissible ambient temperatureVibration (10-55 Hertz)Shock (10 ms half sine wave)

    Main terminal (contactor)Main terminal (overload relay)

    Control terminalBusbar width

    1.4 Technical Data of Series S-N Contactors1.4.1 Ratings and Characteristics

    TypeContactor

    Notes: 1. 660A at ambient temperature 40-55C. 2. 800A at ambient temperature 40-55C.3. Conductor size in parentheses indicate compression terminal style not for bare clamping.4. The peak value of inrush current should be less than 2000% of the effective value for rated current of capacitors.

    The selection is invalid for the circuit of parallel capacitors which are controlled individually.

    VA

    kW(A)kW(A)kW(A)kW(A)

    AAAA

    kWkWkWkWA

    AAA

    AAA

    kvarkvarkvarkvar

    AAoperations/houroperations/houroperations/hour

    msmsmsms

    VAVAWVAVA

    millionCm/s2m/s2mm2

    mm2

    mm2

    mm

    S-N1069020

    7.5(20)8.5(13)9.5(11)

    8(8)

    131297

    1.11.51.51.59

    121212

    1084

    345

    4.5

    130/120120/100

    1,8001,800600

    15104510

    457

    2.477

    10

    1-2.51-2.51-2.5

    S/SD-N11, N12

    69025

    9.5(25)13(20)13(16)11(10)

    1816139

    1.52.22.22.29

    121212

    1084

    466

    5.5

    180/180180/130

    1,8001,800600

    1510

    60103

    10

    1-61-6

    1-2.5

    S-N18

    0.85 to 1.1 times rated coil voltage

    69032

    12(32)20(32)25(32)30(32)

    2222179

    2.23.73.73.713

    202020

    20158

    5.5101010

    220/220220/220

    1,8001,800600

    1510

    90154

    10

    1-61-6

    1-2.5

    S-N20

    25 to +5519.649

    S/SD-N21

    69050

    18(50)30(50)40(50)50(50)

    30302412

    35.55.55.517

    252522

    252010

    8.5141414

    300/300300/240

    1,8001,800600

    1510

    110134.3

    10

    2-162-161-2.5

    S-N2569060

    20(60)35(60)50(60)60(60)

    40403217

    3.75.55.55.524

    353530

    302010

    12202020

    400/400400/320

    1,8001,800600

    15105013

    110134.399

    10

    2-162-161-2.5

    S/SD-N35

    69080

    30(80)50(80)65(80)80(80)

    55503826

    5.57.57.57.532

    505040

    353012

    20403030

    550/460550/460

    1,2001,200600

    25535715

    115202.21818

    5

    2-252-251-2.5

    S/SD-N50

    S/SD-N65

    Ith

    220-240V380-440V

    500V690V

    220-240V380-440V

    500V690V

    220-240V380-440V

    500V690V

    48V110V220V

    48V110V220V

    220-240V380-440V

    550V690V

    Making currentBreaking currentCategory AC-1Category AC-3Category AC-4

    ClosingOpeningClosingOpening

    InrushSealedWattsInrushSealed

    Conductor size

  • 17

    690260

    95(260)170(260)220(260)260(260)

    180180180120

    22374550150

    180180180

    180150100

    60120150150

    1800/18001450/1450

    1,2001,200300

    30100

    440404.2

    5

    (10-120)3(10-120)3

    1-2.525

    690260

    95(260)170(260)220(260)260(260)

    250250200150

    22455555180

    220220220

    220150100

    60120150150

    2500/25002000/2000

    1,2001,200300

    3010014540

    440404.24141

    5

    (10-150)3(10-150)3

    1-2.525

    A

    A

    A

    A

    A

    A

    A

    A

    A

    A

    Conventional free airthermal current

    Rated operating current

    Category 120VAC

    AC-15 240VAC

    500VAC

    660VAC

    Category 24VDC

    48VDC

    DC-13 110VDC

    220VDC

    69010002

    300(800)530(800)700(800)900(800)

    800800720630

    75130150150630

    800800800

    630630630

    190350350400

    8000/80006400/6400

    1,2001,200300

    657510580

    790901760072

    5

    (70-325)3

    1-435

    S/SD-N600

    S/SD-N400

    6908001

    250(660)430(660)570(660)660(660)

    630630500420

    65110130130400

    630630630

    630630630

    190350350400

    6500/65005040/5040

    1,2001,200300

    657510580

    790901760072

    5

    (70-325)3

    1-435

    690135

    50(135)85(135)

    110(135)135(135)

    85857552

    7.515151562

    808060

    605020

    35604850

    850/850800/750

    1,2001,200600

    27757518

    210232.82424

    5

    2-602-501-2.5

    15

    S/SD-N80

    690150

    55(150)90(150)

    120(150)150(150)

    1051058565

    1118.518.518.575

    939370

    908050

    35606060

    1050/1050930/9301,2001,200300

    27757518

    210 232.82424

    5

    (2-60)32-501-2.5

    15

    S/SD-N95

    690150

    55(150)90(150)

    120(150)150(150)

    1251209070

    1522222290

    12010080

    908050

    38656565

    1250/12501000/1000

    1,2001,200300

    258512522

    270242.93131

    5

    (6-70)3(6-70)31-2.5

    15

    S/SD-N125

    0.85 to 1.1 times rated coil voltage

    690200

    75(200)130(200)170(200)200(200)

    150150140100

    18.5303730110

    150150150

    13012080

    50808080

    1500/15001200/1200

    1,2001,200300

    278513537

    270242.93131

    5

    (6-95)3(6-95)31-2.5

    20

    S/SD-N150

    25 to +5519.649

    S-N180

    S/SD-N220

    690350

    130(350)230(350)300(350)350(350)

    300300250220

    37606075220

    300300300

    280200150

    95150200200

    3000/30002400/2400

    1,2001,200300

    3512017555

    440506.15555

    5

    (25-240)3(25-240)3

    1-2.530

    S/SD-N300

    690450

    170(450)290(450)380(450)450(450)

    400400350300

    45759090300

    400400300

    280200150

    115200250200

    4000/40003200/3200

    1,2001,200300

    3512017555

    440506.15555

    5

    (25-240)3(25-240)3

    1-2.530

    S/SD-N800

    Table 1.4.1 (1)

    Rated operating current ofauxiliary contacts

    Table 1.4.1 (2)

    16

    6

    5

    3

    1.5

    5

    3

    0.6

    0.81

    0.2

    Note: 1 UN-AX2(CX), UN-AX4(CX),UN-AX11(CX).

  • 18

    1.4.2 Performance of Series S-N Contactors

    Electrical LifeThe electrical life of the main contacts of a contactor isdetermined mainly by the circuit-opening duty it will perform.The relationship between electrical life and rated current ofMitsubishi contactors under normal and jogging duties ofsquirrel-cage motors is shown in Fig. 1.4.2(1) and 1.4.2(2).In the case of a mixture of normal and jogging duties, theexpected contactor life can be determined as follows:

    N = Nr/1 + (Nr/NI -1) ...................................... Eq.1.1

    where N : Life in the case of % jogging dutyNr : Life in the case of normal dutyNl : Life in the case of 100% jogging duty : Percentage of jogging duty

    Electrical life versus rated operating current

    Normal duty, 6le on, le off, on-load factor 40%,1200 operations/hour (AC3)Jogging duty, 6le on, 6le off, on-load factor 7%,600 operations/hour (AC4)-S-N10~S-N300300 operations/hour (AC4)-S-N400~S-N600150 operations/hour (AC4)-S-N800

    1.4.3 Mounting Attitude of Starters and ContactorsTo assure proper performance, Mitsubishi magnetic motorstarters and contactors should be mounted on a verticalsupporting surface with the line terminals upwards and theload terminals downwards. The supporting surface may havea maximum inclination of 30 from the vertical in any direction.

    100

    30 30 30 30

    Inclined installationRegular installation

    Bottom

    Top

    220~240VAC Fig.1.4.2 (1)5

    3

    21.5

    10.70.5

    0.3

    0.20.15

    0.10.070.05

    0.03

    0.02

    0.012 3 5 7 10 15 20 30 50

    Rated operating current (A)

    Elec

    trica

    l life

    (millio

    n of o

    perat

    ions,

    avera

    ge)

    70 100 150 200 300 500 800

    S-N800S-N600

    S-N400S-N300

    S-N150S-N50 S-N80

    S-N95

    S-N125S-N25S-N20,21

    S-N11,12S-N10

    S-N18

    S-N35S-N65

    S-N180

    S-N220

    380~440VAC Fig.1.4.2 (2)5

    3

    21.5

    10.70.5

    0.3

    0.20.15

    0.10.070.05

    0.03

    0.02

    0.012 3 5 7 10 15 20 30 50

    Rated operating current (A)

    Elec

    trica

    l life

    (millio

    n of o

    perat

    ions,

    avera

    ge)

    70 100 150 200 300 500 800

    S-N800S-N600

    S-N400S-N300

    S-N220S-N150

    S-N80

    S-N95

    S-N180S-N125

    S-N20,21S-N11,N12S-N18S-N10

    S-N25S-N50S-N35

    S-N65

  • 19

    AC24VAC48V

    AC100VAC120VAC127VAC200VAC220VAC230VAC260VAC380VAC400VAC440VAC500V

    1.5 When OrderingContactors, indicate the model name and the ordering designation of the coil.

    Example: S-N20 AC230V ( 2A) Code of arrangement, if special aux. contacts, ref. Table 1.5.4

    Ordering designation of the coilModel name

    Overload relays, indicate the model name and the ordering designation of the heater setting range.

    Example: TH-N400RHKP250AOrdering designation of the heater setting rangeModel name

    Motor starters, indicate the model name, heater setting range, main circuit voltage, coil designation.

    Example: MSO-N11KP6.6A380VAC230VOrdering designation of the coil

    Main circuit voltageOrdering designation of the heater setting range

    Model name

    Note: Mark indicates a blank space.

    Coil Ratings and Ordering Designationsfor S-N10(CX), -N11(CX), -N12(CX), -N18(CX), -N20(CX),

    -N21(CX), -N25(CX), -N35(CX) and SR-N(CX)Table 1.5.1

    50Hz24

    48~50100

    110~120125~127

    200208~220220~240240~260346~380380~415415~440

    500

    60Hz24

    48~50100~110115~120

    127200~220

    220230~240260~280

    380400~440460~480500~550

    Rated voltage (VAC)Ordering designation

    Ordering designationDC24VDC48V

    DC100VDC110VDC125VDC200VDC220V

    Rated voltage (VDC)2448

    100110

    120~125200220

    Table 1.5.3

    for SD-N, SRD-N

    Ordering designationAC100VAC200VAC300VAC400VAC500V

    Rated voltage (50/60Hz)100~127V200~240V260~350V380~440V460~550V

    Table 1.5.2

    for S-N50(CX)~-N800

    AC24V,AC48V are available for S-N50(CX)~-N150

    Code1B2A

    Arrangement1NC2NO

    Table 1.5.4

    Code of arrangement for sepcial aux. Contacts

    A : Normally OpenB : Normally Closed

  • 20

    1

    11

    1

    222222222222222

    SD-N50SD-N65SD-N80SD-N95SD-N125SD-N150

    SD-N220SD-N300SD-N400SD-N600SD-N800

    S-N80S-N95S-N125S-N150S-N180S-N220S-N300S-N400S-N600S-N800

    1

    1

    12

    12222222222222222

    7.5

    7.5

    7.5111522 3045556090

    110132200250330500

    16

    22

    223040506585105120150180250300400630800

    18

    22

    223040556585

    105125150180250300400630800

    4.5

    5.5

    5.57.51115

    18.522303745557590

    125190220

    SD-N11SD-N11CX1SD-N11(1B)SD-N11CX1(1B)SD-N12SD-N12CX1SD-N12(2A)SD-N12CX1(2A)

    1.6.1 Non-Reversing ContactorsOrdering Designation

    Model name ................................................................................................. S-N10Coil designation (See page 13) ............................................................................... AC400VIf required special aux. contact (never specify for standard). ................................................. 1B

    Complete type designation S-N10AC400V1B

    Note: Markindicatesa blank space.

    Ratedoperationalcurrent AC-3

    220240V

    (A)

    380440V

    (A)500V(kW)

    690V(kW)

    Rated motor capacity3-phase AC-2 & AC-3

    Model name

    AC operated220

    240V(kW)

    380440V(kW)

    DC operated

    Standardaux.

    contacts

    Fingerprotectionterminal cover

    Additional auxiliary contact block

    NO NCUN-

    AX2(CX)UN-

    AX4(CX)

    Provided

    Provided

    Provided

    Provided

    Provided

    Provided

    Provided

    Provided

    Provided

    Provided

    Provided

    Provided

    Provided

    Provided

    S-N10S-N10CX1S-N10(1B)S-N10CX1(1B)S-N11S-N11CX1S-N11(1B)S-N11CX1(1B)S-N12S-N12CX1S-N12(2A)S-N12CX1(2A)S-N18S-N18CX1S-N20S-N20CX1S-N20(2A)S-N20CX1(2A)S-N21S-N21CX1S-N25S-N25CX1S-N35S-N35CX1S-N50S-N50CX1S-N65S-N65CX1

    7.5

    11

    1115

    18.522304555607590

    132160220330440

    7.5

    11

    1115

    18.5253745556090110132160 225330500

    SD-N21SD-N21CX1

    SD-N35SD-N35CX1

    UN-AX80

    UN-AX150

    UN-AX600

    Max.2

    Max.2

    1

    1.6 Selection Table of Contactors

    Table 1.6.1

    Type S-N , SD-N

    2

    1

    11 4 4 42.59

    13

    13

    3.5

    3.5

    12

    12

    5.5

    5.5

    5.5

    5.5

    5.5

    5.5

    S-N10CX S-N21 SD-N65 S-N220 SD-N400 S-N800

    2

    UN-AX11(CX)

    Note:1 CX denotes with finger protection terminal covers.

  • 21

    SD-2xN50SD-2xN65SD-2xN80SD-2xN95SD-2xN125SD-2xN150

    SD-2xN220SD-2xN300SD-2xN400SD-2xN600SD-2xN800

    S-2xN150S-2xN21

    2242444444446666688

    DC operated380

    440V(kW)

    1.6.2 Reversing ContactorsOrdering Designation

    Model name ................................................................................................... S-2xN95Coil designation (See page 13) ..................................................................................... AC400V

    Complete type designation S-2xN95AC400V

    Note: Markindicatesa blank space.

    Rated operationalcurrent AC-3

    220240V

    (A)

    380440V

    (A)11131822223040556585

    105125150180250300400630800

    9121622223040506585

    105120150180250300400630800

    S-2xN11

    Type S-2xN ,SD-2xN

    500V(kW)

    690V(kW)

    Rated motor capacity3-phase AC-2 & AC-3

    220240V(kW)

    45.57.5111115

    18.522304555607590

    132160220330440

    45.57.5111115

    18.5253745556090

    110132160 225330500

    45.57.57.57.5111522 3045556090

    110132200250330500

    2.53.54.55.55.57.51115

    18.522303745557590

    125190220

    Model name

    AC operated

    Standardaux.

    contacts

    NO2242444444446666688

    Additional auxiliary contact block(max).

    S-2xN80S-2xN95S-2xN125S-2xN150S-2xN180S-2xN220S-2xN300S-2xN400S-2xN600S-2xN800

    S-2xN10S-2xN10CX1S-2xN11S-2xN11CX1S-2xN18S-2xN18CX1S-2xN20S-2xN20CX1S-2xN21S-2xN21CX1S-2xN25S-2xN25CX1S-2xN35S-2xN35CX1S-2xN50S-2xN50CX1S-2xN65S-2xN65CX1

    NCUN-

    AX2(CX)UN-

    AX4(CX)UN-

    AX11(CX)UN-

    AX80UN-

    AX150

    Table 1.6.2

    2

    2

    2

    2

    2

    2

    2

    2

    SD-2xN11SD-2xN11CX1

    SD-2xN21SD-2xN21CX1

    SD-2xN35SD-2xN35CX1

    Note:1 CX denotes with finger protection terminal covers.

  • 22

    Max.2

    Max.2

    2222222222222

    1.6.3 Non-Reversing Mechanically Latched ContactorsOrdering DesignationModel name ......................................................................... SL-N35Closing coil designation1 ......................................................................... AC200VTripping coil designation1 .............................................................................................. DC100V

    Complete type designation SL-N35MCAC200VMTDC100V

    Type SL-N , SLD-N

    Note: Markindicatesa blank space.1. See Table1.6.3 (2).

    DC operated(closing coil)

    380440V(kW)

    Rated operationalcurrent AC-3

    220240V

    (A)

    380440V

    (A)2240556585

    105125150250300400630800

    2240506585

    105120150250300400630800

    500V(kW)

    690V(kW)

    Rated motor capacity3-phase AC-2 & AC-3

    220240V(kW)

    1118.5223045556075

    132160220330440

    1118.5253745556090

    132160 225330500

    7.51522 3045556090

    132200250330500

    5.51115

    18.5223037457590

    125190220

    Model name

    AC operated(closing coil)

    Standardfree aux.contacts

    Addition