Shimaden, Temperature and Humidity Control Specialists Series MR13 SHIMADEN DIGITAL CONTROLLER °C %RH 3-channel controller, 3-channel input, 3-channel setting and simultaneous 3-channel display are possible Accuracy: ± (0.3% FS + 1 digit) Follow-up type PV input function Follow-up type SV setting function Remote/local and DI input function Programmable 1 pattern with 9-step function Included a new processing system, Expert PID, remarkably improved PID control efficiency; overshoot and undershoot are controlled effectively. Interface RS232C/RS485 BASIC FEATURES approved

Upload: william-parra-pinzon

Post on 13-Apr-2015

58 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Control Adores

Shimaden, Temperature and Humidity Control Specialists

Series MR13

SHIMADEN DIGITAL CONTROLLER

°C

%RH

3-channel controller, 3-channel input, 3-channel setting and

simultaneous 3-channel display are possible

Accuracy: ± (0.3% FS + 1 digit)

Follow-up type PV input function

Follow-up type SV setting function

Remote/local and DI input function

Programmable 1 pattern with 9-step function

Included a new processing system, Expert PID, remarkably

improved PID control efficiency; overshoot and undershoot

are controlled effectively.

Interface RS232C/RS485

BASIC FEATURES

approved

mercadeo
logo + direccion
Page 2: Control Adores

Front Panel Information

Application Example

As the controller is capable of 3-channel input and setting,it is most suitable for zone control.Control of three points is possible by a single controllerusing three sensors. PV values of three points aredisplayed simultaneously. The use for zone control such asthe upper, middle and lower stages of a batch furnace andthe inlet, center and outlet of a tunnel furnace, and for heatcontrol of plastic molds, packing, machines and so forthare highly recommendable.

Follow-up Type PV Input Function

PV input of CH2 and CH3 can be linked to CH1 input. This function enables the controller to be used for 1-input 2-setting or 1-input 3-setting control.

• Multistage control of heating/cooling • Control of heating/cooling and humidification/dehumidification

Follow-up Type SV Setting Function

As it is possible to make CH2 and CH3 set values follow that of CH1, SVs of these channels can be changed simplyby changing CH1 setting.This function is conveniently made use of when temperature levels multiple points are changed or multipleprogramming functions are used.

Use of Expert PID Reduces Overshoot

Higher controllability has been attainted by the useof expert PID which can suppress hunting byovershoot or disturbance.

Series MR13MR13 SERIES 3-CHANNEL CONTROLLER

MR13

PV 1

PV 2

PV 3

SVCH

AT

FLW

REM

COM

RUN

OUT1 EV1

OUT2

OUT3

EV2

EV3

PV1 display

PV2 display

PV3 display

Key switches

SV displaySV channel display

Action displayLEDs

7

1

2

3

4

6

5

TC2 TC1 TC3

PACthyristor

PACthyristor

PACthyristor

Electric Furnace

Heater

T

Room

F

Air conditioner

CH1

MR13

CH2

CH3PAC15

PAC15

Heat

Cool

TH

Room

F

Air conditioner

CH1

MR13

CH2

CH3

converter

Heat

Cool

T

H

PID control by new operatingmethod (Expert PID)

Shimaden's previousPID control

DisturbanceDisturbance

SV

PV

SV

PV

t t

Page 3: Control Adores

Programming Function

With the addition of the programming control function, it has become possible to carry out zone control of furnaces forchina, ceramics, etc., which can be made in an ascending pattern of one pattern with nine steps maximum.

* Program control of 1 pattern with 9 steps maximum

* Step execution time: 1-9999 minutes* The number of executions: 1-9999 times* Either PV start or SV start selectable* The temporary stop (HLD) function and

the step forward (ADV) function are include.

* A program ramp is automatically determined by selecting the temperature and time for each step.* In the MR13, only CH1 is equipped with the programming function. In case CH2 and CH3 are used for program

control, follow-up type SV should be set for each of them.

Remote and DI Input Functions

* The remote or DI input function can be added.

a. DI setting allows the controller to operate in response to an external control (non-voltage contact or open collector)signal.

* RUN/RST (during program control)* HLD (during program control)* ADV (during program control)

b. Remote setting of an SV value by means of an external analog signal is possible as per the below drawing nos.1and 2.

c. Simple cascade control by remote setting

* When CH1 control output is made remote SV of CH2, a single MR13 controller can carry out cascade control.* Select control output (OUT) from CH1 transmission

signals (SV, PV and OUT) and input it to the remoteterminal of CH2 instead of inputting the control outputdirectly to the remote SV of CH2.This raises the resolution of CH1 control output sothat control characteristics can be improved.

Event Function

* Three points are available for event outputs.* Event output selected from the list of Events shown on page 6 can be assigned to EV1, EV2 and EV3.

Communication Function

For the MR13 series controllers, there are two types of communication interface, RS232C and RS485. Each allows apersonal computer, etc., to set and read data of the MR13 series using signals based on EIA standards.

Series MR13ADDITIONAL FUNCTIONS (OPTIONAL)

No.1

Drawing No.1

No.2 No.3T T T

CH1

MR13 REM1.

REM2.

REM3.CH2

CH3

CH1

CH2

CH3

T1T3 T2

EMMD CP2

EM

AL

REM

Analog out

OUT

Drawing No.2

1 2

5 6

7

175˚CS5, 6125˚C

S7

75˚CS1, 225˚CS-SV

STEP1t-1

STEP2t-2

STEP6t-6

STEP7t-7

Page 4: Control Adores

Series MR13

Display• LED display: PV display 7-segment LED green 4

digits 3 channels to be displayed individually.SV display 7-segment LED orange 4 digits CH display 7-segment LED orange 1 digit

• Action display LED: Control output display: 3 - OUT1, OUT2, OUT3 Auto tuning: 1 - ATFollow type SV display: 1 - FLW Program RUN: 1 - RUNEvent output display: 3 - EV1, EV2, EV3 Remote input display: 1 - REMCommunication display: 1 - COM

• Display accuracy: ±(0.3%FS + 1 digit) Standard accuracy

• Temperature range in which accuracy is maintained: 23°C±5°C

• Display resolution: Depends on measuring range(0.001, 0.01, 0.1, 1)

• Sampling cycle: 0.5 seconds • Measured value

display range: –10% to 110% of measuring range

Setting• Setting: By 6 front key operation• Setting range: Same as measuring range• Higher/lower limit

setting limiter: Higher and lower limits to be set separately; free within measuring range (Lower limit < higher limit)

• Follow type SV setting: SV of CH2 or CH3 can be set to follow CH1 (deviation setting) (on condition that measuring range of CH2 or CH3 is the same as that of CH1.)

Input• Input type has to be the same for 3 channels (measuring range

can be selected individually).• Thermocouple: B, R, S, K, E, J, T, N, PL II, WRe5-26,

L, U (DIN43710)(Multiple input, multiple range. Refer to measuring range code table.)

External resistance: 100Ω maximumInput impedance: 500kΩ minimumBurnout: Standard feature (up scale)Cold junction temperature compensation accuracy: ±2.0 °C (5~45 °C)

• R.T.D.: JIS Pt100/JPt100 3-wire type (Multiple range. Refer to measuring range code table.)

Amperage: Approx. 0.25 mALead wire tolerable resistance: 5Ω maximum/wire

• Voltage: ±10, 0~10, 0~20, 0~50, 10~50, 0~100mV DC, or ±1, 0~1, 0~2, 0~5, 1~5, 0~10V DC (Multiple input, programmable range.Refer to measuring range code table.)

Input impedance: 500kΩ minimum• Current: 4~20, 0~20mA DC

(Multiple input, programmable range.Refer to measuring range code table.)

Receiving impedance: 250Ω

• Sampling cycle: 0.5 seconds• PV bias ±1999 units• PV filter: OFF, 1~100 seconds• Follow type PV input: PV input of CH2 or CH3 can be set

to follow CH1 (deviation setting) (on condition that measuring range of CH2 or CH3 is the same as that of CH1.)

• Isolation: Insulated between input and various outputs (not insulated between input and system, remote input and DI input)

Control• Control mode: Expert PID control with auto tuning

functionProportional band (P): OFF, 0.1~999.9%FS

(OFF=ON/OFF action)Integral time (I): OFF, 1~6000s (OFF=P, PD action

with manual reset)Derivative time (D): OFF, 1~3600s (OFF=P, PI action)Manual reset: ±50.0%ON/OFF hysteresis: 1~999 units

• Proportional cycle: 0.5~120.0 seconds(0.5 sec. is unit for setting.)

• Control output characteristics: RA/DA selectable (set to RA when

shipped)• Output limiter: Higher limit, lower limit 0.0~100.0%

(lower limit < Higher limit)• Soft start: OFF, ON (Fixed to 10 sec.; Valid

when power is turned on, RTS RUN, and when returned from scaleover.)

Control output/rating• Output specification has to be the same for 3 channels.• Contact output (Y): 1a 240V AC 2.5A/resistive load• Current output (I): 4~20mA, 0~10mA DC/

load resistance 600Ω maximum.• SSR drive voltage

output (P): 15V±3V DC/Load current 20mA maximum

• Voltage output (V): 0~10V DC/Load current 2mA maximum

• Operation output updating cycle: 0.5 second

• Isolation: Insulated between control output and system and input(not insulated between control output I, P or V and analog output)

Event output (optional)• Number of outputs: 3 -EV1, EV2, EV3 (Selectable from

CH1, CH2 and CH3, individual setting, individual output)

• Output rating: Contact output 1a (common) 240V AC / 1A (resistive load)

• Setting: Individual setting0) NON: Not assigned1) DEV: Higher limit deviation value

alarm2) DEV: Lower limit deviation value

alarm3) DEV: Higher/lower limit value

alarm in case SV is out of measuring range

4) DEV: Higher/lower limit value alarm in case SV is within measuring range

5) PV: Higher limit absolute value alarm

6) PV: Lower limit absolute value alarm

7) SO: ON upon scaleover8) RUN: ON during program RUN9) END: ON for 1 sec. upon

termination of program10) STEP: ON for 1 sec. upon

termination of program step• Hysteresis: 1~999 units

(when DEV or PV has been selected)• Standby action: Selectable

(when DEV or PV has been selected) • Action delay time: OFF, 1~9999 seconds

(when DEV or PV has been selected)• Isolation: Insulated between alarm output and

various inputs/outputs and system

SPECIFICATIONS

Page 5: Control Adores

Remote setting (optional, selectable between this function and DI)• Setting signal: 1~5V, 0~10V, 4~20mA• Setting range: Same as measuring range• Accuracy of setting: ±(0.3%FS + 1) digit• Channel for setting: Selectable from CH1, CH2 and CH3• Remote scaling: Within measuring range (inverted

scaling possible)• Remote bias: –1999~5000 units• Remote filter: OFF, 1~100 seconds• Sampling time: 0.5 second• Isolation: Insulated between remote input and

various outputs (not insulated from system and various inputs)

External control input (DI) (optional, selectable between thisfunction and remote setting)• Number of input point: 1• Input rating: Non-voltage contact, open collector

input (about 5V/0.4mA DC impress)• Action type: NON, FLW (follow type SV), RST/

RUN, HLD and ADV• Isolation: Insulated between DI input and

various outputs (not insulated from system and various inputs)

Program (optional)• Registrable pattern: 1• Number of steps: 9 maximum• Program setting range

Level: Same as measuring rangeTime: 1~9999 minutes/stepRamp: To be set automatically according to

level and time• Number of executions: 9999 maximum• PID output limiter: To be set selectively from 3 types of

PID & output limiter• External control input: DI/non-voltage 1 point (RUN/RST,

HLD, ADV)• Action status output: RUN, END and STEP to be

selectively output to event output• CH2 and CH3 in

SV follow setting: Program to be executed by making CH2 or CH3 deviation-follow to pattern set in CH1 in SV follow setting. Not in SV follow setting, program is executed in FIX mode.

• Additional functions: Temporary suspension (HLD), carry-forward (ADV), PV start

Analog output (optional, selectable between this function andcommunication)• Number of output: 1• Output types: Selectable from CH1_PV, CH2_PV,

CH3_PV, CH1_SV, CH2_SV, CH3_SV, CH1_OUT, CH2_OUT and CH3_OUT

• Output rating: 0~10mV DC/Output impedance 10Ω

0~10V DC/Load current 1mAmaximum4~20mA DC/Load resistance 300Ω

maximum• Output accuracy: ±0.3%FS (to displayed value) • Output resolution: Approx. 1/8000 • Output updating cycle: 0.5 seconds• Output scaling: Within measuring range (inverted

scaling possible)• Isolation: Insulated between analog output and

various inputs and system (not insulated between analog output and control outputs I, P and V)

Communication (optional, selectable between this function andanalog output)• Communication type: RS-232C, RS-485• Communication system: Half duplex start-stop synchronous

system• Communication speed: 1200, 2400, 4800, 9600, 19200bps• Data format: 7 bits, 8 bits, no parity, even parity

selectable

• Communicationaddress: 1~99

• Communication code: ASCII code• Communication

protocol: Shimaden standard protocol• Communication format: Control code selectable, BCC check

arithmetic system selectable• Isolation: Insulated between communication

signal and system/input/output • Others: Meets the EMC standards with an

additional clamp filter (E04SR301334, SEIWA Information Systems Co.,LTD)

Others• Data storage: By non-volatile memory (EEPROM)• Ambient temperate/

humidity ranges: -10~+50°C/below 90% RH(on condition that there is no dew condensation)

• Temperaturefor storage: Between-20 and +65 °C

• Power voltage: 100V~260V AC ±10% (50/60 Hz)• Power consumption: 18VA maximum• Input noise

removal ratio: Normal mode 45 dB minimum(50/60 Hz)Common mode 140 dB minimum(50/60 Hz)

• Applicable standardSafety: IEC1010-1 and EN61010-1EMC: EN61326

• Insulation resistance: Between input/output terminals and power terminal: 500V DC 20MΩ

minimumBetween input/output terminals and protective conductor terminal: 500V DC 20MΩ minimum

• Dielectric strength: 1 minute at 2300V AC between input/output terminals and power terminal (inductive current 5mA) 1 minute at 2300V AC between power terminal and ground terminal(inductive current 5mA)

• Protective structure: Only front panel has simple dust-proof and drip-proof structure

• Material: PPO resin molding (equivalent to UL94V-1)

• External dimensions: 96 x 96 x 110 mm(Panel depth: 100 mm)

• Mounting: Push-in panel (one-touch mount)• Panel cutout size: H92 x W92 mm• Weight: Approx. 420 g

Series MR13SPECIFICATIONS

Page 6: Control Adores

ITEMS CODE SPECIFICATIONS

SERIES MR13- MPU-Based 3 Channel Auto-Tuning PID Controller DIN 96 × 96mm

1Thermocouple B, R, S, K, E, J, T, N, PLII, Multi-input

WRe5-26, U, L Multi-range

2 R.T.D. Pt100 / JPt100 Multi-range

INPUT3

Voltage (mV) -10-10, 0-10, 0-20, 0-50, 10-50, Multi-input

0-100mV DCProgrammable

4 Current (mA) 0-20, 4-20mA DCRange

6 Voltage (V) -1-1, 0-1, 0-2, 0-5, 1-5, 0-10V DC

Y1-Contact: Proportional Cycle 0.5-120.0 sec.

Contact capacity: 240V AC 2.5A / resistive load

I1-Current: 4-20, 0-10mA DC

CONTROL OUTPUTLoad resistance: 600Ω max.

P1-SSR drive voltage: Proportional Cycle 0.5-120.0 sec.

Output rating: 15V±3V DC / 20mA max.

V1-Voltage: 0-10V DC

Load current: 2mA max.

PROGRAM FUNCTION (OPTION)N None

P 1 Pattern, 9 step

0 None

EVENT OUTPUT (OPTION)1

Contact (1a common): 240V AC 1A / resistive load EV1, EV2,

EV3 / 3 Point

00 None

04 4-20mA DC Receiving resistance: 250Ω

REMOTE OR DI INPUT (OPTION) 05 1-5V DC Input resistance: 500kΩ min.

06 0-10V DC Input resistance: 500kΩ min.

51 DI Non-Voltage Contact, Open Collector Input

00 None

03 Voltage 0-10mV DC, Output resistance: 10Ω

ANALOG OUTPUT OR 04 Current 4-20mA DC, Load resistance: 300Ω max.

COMMUNICATION FUNCTION (OPTION) 06 Voltage 0-10V DC, Load current: 1mA max.

15 RS-485

17 RS-232C

REMARKS0 Without

9 With (Please consult before ordering.)

TYPES OF EVENTS

Event type code table

Code Event type

Not assigned

Higher limit deviation value

Lower limit deviation value

Out of higher/lower limit ranges

Within higher/lower limit ranges

Higher limit absolute value

Lower limit absolute value

Setting range of event set value

Initial value of event set value

0~1999 Unit

0~–1999 Unit

0~1999 Unit

0~1999 Unit

1999 Unit

–1999 Unit

1999 Unit

1999 Unit

Within measuring range

Within measuring range

Higher limit value of measuringrange Lower limit valueof measuringrange

OFF

1

2

3

4

5

6

Code Event type

Scale-over

Program RUN

Setting range of event set value

Initial value of event set value

In the case of scale-over, EV output is continued.

EV output is continued whileprogram is in execution.

Program END EV output is produced for about 1 second upon termination of program.

Program STEP EV output is produced for about 1 second upon switching steps.

7

8

9

10

Note: The above codes from 8 to 10 are selectable only whenprogram option is added.

ORDERING INFORMATION Series MR13

Page 7: Control Adores

Series MR13

EXTERNAL DIMENSIONS

13

0 m

in

130 min

92+0.8 0

92

+0

.8

0

110

10010

91.6

91

.6

222

211 1131

1232

1333

1434

1535

1636

1737

1838

1939

2040

23

244

255

3

26

277

6

9

28

29

8

3010

ENTDISP CH

MR13

OUT 3 EV 3

OUT 2 EV 2

OUT 1 EV 1

RUN

FLW COM

AT REM

CH

PV 3

PV 2

PV 1

SV

96

96

MEASURING RANGE CODES

01 15

16

17

18

19

20

21

22

23

24

25

26

27

28

02

03

04

05

06

07

08

09

10

11

12

14

31

32

33

34

35

36

37

38

47

48

49

50

51

52

53

54

39

40

41

42

43

44

45

46

55

56

57

58

59

60

61

62

Code CodeMeasuring range Measuring range

0

0.0

0

0

0

-199.9

-199.9

-200

0

0

0

0

0

0

-100.0 400.0

800.0

200.0

200.0

-100.0

-100.0 300.0

-50.0 50.0

-200 500

-100.0 100.0

-100.0 300.0

-50.0 50.0

0.0

0.0

0.0

0.0

100.0

100.0

200.0

500.0

50.0

1700

1200

1300

1300

2300

700

600

600

600

1700

1800

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

13 °C

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

°C

0

0

0

0

0

-300

-300

0

0

0

0

0

0

-150 750

1500

400

400

200.0

3100

2200

2300

2300

4200

1300

1100

1100

3100

3300

°F

°F

°F

°F

°F

°F

°F

°F

°F

°F

°F

°F

°F

°F

°F-300 1100

600

°F-150.0

°F-150

120.0 °F-50.0

120.0 °F0.0

200.0 °F0.0

400.0 °F0.0

1000 °F

°F

°F

°F

°F

°F

°F

°F

°F

0

900-300

200.0-150.0

*3

*3 0.0 50.0

0.0 100.0

0.0 200.0

0.0 500.0

600-150

120.0-50.0

120.00.0

200.00.0

400.00.0

9000

B

R

S

K

E

J

T

N

PLII

WRe5-26

U

L

*2

*2

*1

Pt100(New)

JIS/IEC

JPt100(Old)JIS

Input type

Therm

ocouple

R.T

.D.

71

72

73

74

75

76

81

82

83

84

85

86

94

95

Code Measuring range

mV

V

mA

-10 10

10

20

50

50

100

0

0

0

10

0

-1 1

1

2

5

5

10

0

0

0

1

0

200

204

Input type

Depending on scaling function, you may set measuring range at any value within the following range: Scaling range: –1999~9999 count Span: 10~5000 countNote: Lower limit value < Higher limit value

InputStandard/

rating CodeMeasuring

range

1. Thermocouple

2. R.T.D.

3. Voltage

4. Current

5. Voltage

JIS K

JIS Pt100

0 10mV DC

4 20mA DC

0 10V DC

05

37

72

95

86

0.0 800.0°C

0.0 200.0°C

0.0 100.0

0.0 100.0

0.0 100.0

Panel Cutout

(Unit : mm)

*1 Thermocouple B: Temperature above 400°C or below 750 °Fis excluded from accuracy assurance.

*2 Thermocouple T, U: Accuracy of temperature between -199.9and 100.0°C is ±0.5% FS.

*3 R.T.D.: Accuracy is ±0.3°C (±0.8 °F).

The following table shows factory-set measuring range codes:

Page 8: Control Adores

1 1 21 21 31 1111

2 2 22 22 32 1212

3 3 23 23 33 1313

4 4 24 24 34 1414

5 5 25 25 35 1515

6 6 26 26 36 1616

7 7 27 27 37 1717

8 8 28 28 38 1818

9 9 29 29 39 1919

10 10 30 30 40 2020

15

16

15

16

+

21

22

21

22

+

11

13

12

CH1

17

18

17

18

+

CH2

19

20

19

20

+

CH3

I. V. OutputSSR. drive.V Output

100-260V AC~50/60Hz 18VA

GND

Contact Output

A-output RS-232C RS-485

Control Output

Power SupplyDIREM

23

24

SG

SD

25RD

23

24

SG

+

25—

23+

24—

Analog Out • Com

27

28

29

30

COM

EV1

EV2

EV3

Event Output

I.V. Input TC Input RTD Input

2

4

2

3

A

B

4B

+

+

2

4

5

7

5

6

A

B

7B

+

+

5

7

8

10

8

9

A

B

10B

+

+

8

10

INPUT

Series MR13TERMINAL ARRANGEMENT

ISO 9001

(The contents of this brochure are subject to change without notice.)

Temperature and Humidity Control Specialists

Head Office: 2-30-10 Kitamachi, Nerima-Ku, Tokyo 179-0081 JapanPhone: +81-3-3931-7891 Fax: +81-3-3931-3089

E-MAIL: [email protected] URL: http://www.shimaden.co.jp

00IMR13 1030

Warning

• The MR13 series is designed for the control of temperature, humidity and other physical values of general industrial

equipment. (It is not to be used for any purpose which regulates the prevention of serious effects on human life or safety.)

Caution

• If the possibility of loss or damage to your system or property as a result of failure of any part of the process exists, proper

safety measures must be made before the instrument is put into use so as to prevent the occurrence of trouble.

TERMINAL COVER (AVAILABLE SEPARATELY)

Mounting: 2+B tight pan-head screwsM2.3x6mmModel

MR13

Material/ Appearance: PVC/ transparentThickness: 1mm

SR5301-9

Page 9: Control Adores

Series SR1 / SR3

SHIMADEN DIGITAL CONTROLLER

C

%RH

INPUT

ORDERING INFORMATION

BASIC FEATURES

MEASURING RANGE CODES

01

02

03

04

05

06

07

08

09

10

11

12

14

31

32

33

34

35

36

37

38

Code Scaling range

13*3

B

R

S

K

E

J

T

N

PLII

U

L *2

*3

*4

*5

*3

*2,

*1

Pt100

JPt100

Type of input

Th

erm

oco

up

leR

.T.D

.

Vo

lta

ge

71

72

73

74

75

76

81

82

83

84

85

86

Scaling range

(mV)

Vo

lta

ge

(V)

10 10

10

20

50

50

100

0

0

0

10

0

1 1

1

2

5

5

10

0

0

0

1

0

Type of input

Optional setting of Measuring range is possible by the scaling function as shown below.

Scaling range: 1999~9999 countSpan: 10~5000 countLower limit value < Upper limit valuePosition of decimal point : None : Decimal point below digits, 1, 2, 3

Code

0

0.0

0

0

0

200

200

0

0

0

0

0

0

100.0

50.0

0.0

0.0

199.9

199.9

199.9

100.0

50.0

400.0

800.0

200.0

200.0

50.0

200.0

100.0

1700

1200

1300

1300

2300

700

600

600

600

1700

1800

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

50.0

200.0

100.0

500

C

C

C

C

0

0

0

0

0

300

300

0

0

0

0

0

0

150.0

50.0

0.0

0.0

300

300

300

150.0

50.0

750

1500

400

400

120.0

400.0

200.0

3100

2200

2300

2300

4200

1300

1100

1100

1100

3100

3300

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

120.0

400.0

200.0

1000

F

F

F

F

WRe5-26

Note:*1 Thermocouple B: Accuracy guarantee not applicable Temp. below 400 C.*2 Thermocouple U, L: DIN 43710*3 Thermocouple K, T, U: Accuracy guarantee not applicable Temp.

below –100.0 C (1.0%FS+1digit) & –100.0 0.0 C (0.5%FS+1digit)*4 Thermocouple PLII: Platinel*5 Thermocouple WRe5-26: ASTM988

Input Specification/Rating Measuring range

Multi input

Voltage (V)

K thermocouple

0 10V DC

0.0 800.0 C

0.0 100.0

*Unless otherwise specified, following setting will be applied for shipment.

approved UL approved (except SR4)

Series SR1 / SR3 / SR4

Multi-input and multi-range

performance

SHIMADEN DIGITAL CONTROLLER

˚C

%RH

Y ON-OFF

Control ModeControl Output

I, P, V PID Control (P=3.0)

(P=OFF)

ITEM CODE SPECIFICATIONS

SERIES

SR1 MPU-Based Auto-Tuning PID Digital Controller, DIN H48 x W48 x D111mm

MPU-Based Auto-Tuning PID Digital Controller, DIN H96 x W96 x D111mmSR3

8 Multi input

Thermocouple: B, R, S, K, E, J, T, N, PLII, WRe5-26 U, L (DIN 43710)

-10~10, 0~10, 0~20,Scaling possible

Span: 10~5000

Range: -1999~99990~20mA DC:(V) 0~5V DC

(applied via enclosed 250Ω shunt resistor)

0~50, 10~50, 0~100mV DCVoltage(mV):

Contact 1a Contact capacity: 240V AC 2.0A/resistive load Proportional cycle: 1~120 seconds

Current 4~20mA DC Load Resistance: 600Ω max.

Voltage 0~10V DC Load current: 2mA max.

With (Please consult before ordering.)

Without

Event output (1a) x 2 points, Contact capacity: 240V AC 1A/resistive load

SSR drive voltage 12V ±1.5V DC 30mA max. Proportional cycle:1~120 seconds

Current (mA): 4~20mA DC:(V) 1~5V DC

Voltage (V): -1~1, 0~1, 0~2, 0~5, 1~5, 0~10V DC

R.T.D.: Pt100/JPt100

6

Y

CONTROL OUTPUTI

P

V

EVENT OUTPUT 1

REMARKSW

X

Shimaden, Temperature and Humidity Control Specialists

Large 20mm bright display (SR3)

Dust and splash proof front panel

NEMA4X / IP66

MPU-Based Auto-Tuning PID Digital Controller, DIN H96 x W48 x D111mmSR4

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

°

° ± ±°

Page 10: Control Adores

Terminal Arrangement

Unit: mm

1 6

I.

I.

7

8

9

10

2

3

4

5

OUTPUT4-20mA DC0-10V DC30mA12V DC2A 240V AC

100-240V AC50/60Hz10VA

DC

+ +

+

A

B

B

COMEV11A240V AC

EV21A240V AC

L

N

100-240VAC50/60Hz 10VA

OUTPUT4-20mA DC0-10V DC30mA12VDC2A240V AC

1

2

3

4

5

6

7

8

9

10DC

+ + A

B

B

COMEV1

1A240V AC

EV21A240VAC

+

L

N

ISO 9001 ISO 14001

(The contents of this brochure are subject to change without notice.)

Temperature and Humidity Control Specialists

Head Office: 2-30-10 Kitamachi, Nerima-Ku, Tokyo 179-0081 JapanPhone: +81-3-3931-7891 Fax: +81-3-3931-3089

E-MAIL: [email protected] URL: http://www.shimaden.co.jp

Warning • The SR1 / SR3 / SR4 series are designed for the control of temperature, humidity and other physical values for the general industrialequipment. It is not to be used for any purpose which regulates the prevention of serious effects on human life or safety. No warranty, express or implied is valid if used without proper safety measures.

Caution • If the possibility of loss or damage to your system or property as a result of failure of any part of the process exists, proper safety measures must be made before the instrument is put into use as to prevent the occurrence of trouble.

Material:PVC, Appearance:transparent, Thickness: 1 mm

SR1

SR3

SR4

QCR001

QCR006

QCR004 (Individual Mounting)

QCR005 (Tight-lock coupling)

One-touch mount

One-touch mount

Plus screw, B tight, M2.3 x 6 - 2 pcs.

Plus screw, B tight, M2.3 x 6 - 4 pcs.

Model Terminal Cover (P/N) MountingTERMINAL COVER (AVAILABLE SEPARATELY)

SR1 SR3 / SR4

Series SR1 / SR3 / SR4

ENT

Model SR1: SR3:

Display Digital display:SR1, SR4:

SR3:

Display accuracy:

Display accuracy maintaining range:

Display resolution: Display updating cycle: Action display:Setting Setting method:Target value setting range:

Setting limiter:

InputType of input:

Thermocouple: Input impedance: External resistance tolerance:

Burnout function: Cold junction compensation accuracy:

R.T.D.: Amperage: Lead wire tolerance:

Voltage mV: (Burnout)

V: Input impedance:

Input scaling function: Scaling range:

Span: Decimal point:

Sampling cycle: PV bias: PV filter: Isolation:

Control Control mode:Proportional band (P):

Integral time (I): Derivative time (D):

Manual reset: ON-OFF hysteresis: Proportional cycle:

Control output characteristic:

Type of control/rating: Contact: SSR drive voltage:

Voltage: Current:

Control output resolution: Isolation:Event outputNumber of events:Type:

Event setting range:

Event action: Hysteresis: Standby action:

(EV1 and EV2)

Output type/rating: Output updating cycle: Action display:General Specifications Data storage: Operating conditions:

Storage temperature: Supply voltage: Power consumption: Input/noise

removal ratio:

Applicable standards:

Insulation resistance:

Dielectric strength:

Protective structure:

Material / Color of case: External dimensions:

Mounting: Panel thickness: Panel cutout / Weight:

RA (reverse action characteristic)/DA (direct actioncharacteristic) is selectable (Default setting =RA) *P=OFF by default for contact output, others: PID control

1a 240V AC 2A (resistive load)12V ±1.5V DC (Max load current 30mA)0~10V DC (Max load current 2mA)4~20mA DC (Max load resistance 600Ω )Approx.0.5%(1/200)Output isolated from all

Total 2 points of EV1 and EV2 as standardSelectable from the following 8 types for EV1 and EV2:No selection, Higher limit deviation, Lower limit deviation,Outside higher/lower limit deviations, Withinhigher/lower limit deviations, Higher limit absolute value,Lower limit absolute value, ScaleoverAbsolute values: (both higher limit and lower limit): Withinmeasuring range, Deviations: (both higher limit and lower limit): -1999~2000 units, Higher/lower limitdeviations (within/outside): 0~2000 unitsON-OFF action1~999 unitsSelectable from the following 4 types(1) None. (2) Standby when power is applied. (3) Standbywhen power is applied and when SV value in executionis changed. (4) Control mode without standby action(No alarm is output at the time of abnormal input).Contact (1a x 2 points common)/240V AC 1A (resistive load)0.5 seconds2 LED lamp displays (EV1/EV2)

Non-volatile memory (EEPROM)(Ambient temperature) -10~50 ˚C(Ambient humidity) 90%RH or less (no dew condensation)(Altitude) 2000m from the sea level or lower(Category) II, (Degree of pollution) 2-20~65˚C100-240V AC±10% 50/60Hz10VA 240V AC, 6VA 100V AC(Normal mode) 40 dB or higher (50/60 Hz)(Common mode)120 dB or higher (50/60 Hz)For Voltage (V) input: 90 dB or higher (50/60 Hz)Safety: IEC61010 and EN61010-1EMC: EN61326 (Class A: Industrial environment)Input/output - power supply: 500V DC 20MΩ or aboveInput/output - contact output: 500V DC 20MΩ or aboveInput/output - power supply: 2300V AC 1 minuteContact output - power supply: 2300V AC 1 minuteOnly front panel has dust-proof and drip-proof structureNEMA4X and IP66 PPO resin molding (equivalent to UL94V-1) / IvorySR1: H48 x W48 x D111 (Panel depth: 100) mmSR3: H96 x W96 x D111 (Panel depth: 100) mm

Push-in panel (one-touch mount)1.0~4.0 mmSR1: H45 x W45 mm / Approx. 150 gSR3: H92 x W92 mm / Approx. 270 g

SPECIFICATIONS

48 x 48 Digital Controller96 x 96 Digital Controller

SR4: 96 x 48 Digital Controller

(PV)/4 digit 7 segments red LED (H: 11mm)(SV)/4 digit 7 segments green LED (H: 9.5mm)(PV)/4 digit 7 segments red LED (H: 20mm)(SV)/4 digit 7 segments green LED (H: 13mm)± (0.3%FS + 1 digit) (see "Note" in Measuring Range Codes) (Excluding cold junction compensation accuracy)

23˚C ± 5˚CDepends on measuring range (0.001, 0.01, 0.1, 1)0.5 seconds5 LED lamp displays (OUT/EV1/EV2/AT/MAN)

By operating 4 keys ( , , , )(front panel)

Same as measuring range (within setting limitter)Individual setting for higher & lower limits are possiblewithin measuring range (Lower limit value < Higher limit value)

Selectable from multiple (TC,Pt,mV) and voltage (V)*Current input 0-20mA DC (Voltage: 0-5V), 4-20mA DC(Voltage: 1-5V) applied via 250Ω shunt resistorB,R,S,K,E,J,T,N,PL II,WRe5-26, U,L(DIN 43710)500kΩ minimum

100 Ω maximumStandard feature (up scale)

± 1˚C (within 23˚C ± 5˚C)± 2˚C (ambient temperature: 5˚C to 45˚C)Pt100/JPt100, 3-wire type0.25 mALead wire tolerance:5 Ω max/wire(3 lead wires should have the same resistance.)-10~10,0~10,0~20,0~50,10~50, 0~100mv DCUp scale at time of abnormal input-1~1, 0~1, 0~2, 0~5,1~5, 0~10V DC500kΩ minimumScaling possible for voltage (mV,V) or current (mA) input-1999~9999 counts10~5000 counts(Position) None, 0.0, 0.00, 0.0000.5 seconds-1999~2000 units0~100 secondsInsulated between input and output (not insulatedbetween input and system)

Expert PID control with auto tuning functionOFF, 0.1~999.9%(ON-OFF action by OFF)OFF, 1~6000 seconds (P or PD action by OFF)OFF, 1~3600 seconds (P or PI action by OFF)-50.0~50.0% (Effective when I=OFF)1~999 units (Effective when P=OFF)1~120 seconds (for contact and SSR drive voltage output)

SR4: H92 x W45 mm / Approx. 190 g

SR4: H96 x W48 x D111 (Panel depth: 100) mm

External Dimensions & Panel Cutout

92 +0.80

92+

0.8

0

11

100

111

P V

S V

SR 3

ENT

OUT EV1 EV2 AT MAN

96

96 91.6

1 1

100

111

91.6

PV

S V

ENT

SR 1

OUT EV1 EV2 AT MUN

48

48 44.6

11

100

11145

+0.60

45+

0.6

0

SR1

SR3

96

48

SR 4

EV2EV1

SV

OUT

PV

ENT

MANAT

45+0.6 0

92

+0

.8 0

SR4

Page 11: Control Adores

Series SR90

SHIMADEN DIGITAL CONTROLLER

°C

%RH

Shimaden, Temperature and Humidity Control Specialists

Multi-input and multi-range performance

Large 20mm bright display (SR93)

Readable from a distance and in a low light area

2-output heating and cooling control available

RS232C or RS485 Interface available

Dust and splash proof front panel equivalent to IP66

A wide selection of additional functions (optional) is

available to suit various needs.

BASIC FEATURES

mercadeo
logo + direccion
Page 12: Control Adores

SPECIFICATIONS Series SR90

Display Digital display: Measured value (PV)/7 segments red LED

4 digits

Target set value (SV)/7 segments green

LED 4 digits

Display accuracy: ±(0.3%FS + 1 digit)

Excluding reference contact temperature

compensation accuracy of thermocouple

input.

Accuracy of readings lower than −100˚C of

thermocouples K, T, U inputs is ±0.7%FS.

Accuracy guarantee not applicable to

400˚C (752˚F) and below of B

thermocouple.

Display accuracy maintaining range:

23˚C ± 5˚C (18~28˚C)

Display resolution: Depends on measuring range (0.001, 0.01,

0.1 and 1)

Measured value display range: −10%~110% of measuring range

Display updating cycle: 0.25 seconds

Action display/color: 7 type, LED lamp display

Control output (OUT1, OUT2)/Green

Event (EV1, EV2)/Orange

Auto tuning/Green

Manual control output (MAN)/Green

Set value bias, communication

(SB/COM)/Green

Setting

Setting method: By operating 4 keys ( , ,

and ) on the front panel

Target value setting range: Same as measuring range (within setting

limiter)

Setting limiter: Individual setting for higher and lower

limits, any value is selectable within

measuring range (Lower limit

value<Higher limit value)

Input Type of input: Selectable from multiple (TC, Pt, mV),

voltage (V) and current (mA)

Thermocouple: B, R, S, K, E, J, T, N, PL II, Wre5-26 U, L

(DIN 43710)

Input impedance: 500kΩ minimum

External resistance tolerance: 100Ω maximum

Burnout function: Standard feature (up scale)

Reference junction compensation accuracy:

± 1˚C (within the accuracy maintaining

range (23 ± 5˚C))

± 2˚C (between 5 and 45˚C of ambient

temperature)

R.T.D.: Pt100/JPt100, 3-wire type

Normal current: 0.25 mA

Lead wire tolerance: 5Ω maximum/wire (3 lead wires should

have the same resistance.)

Voltage mV: −10~10, 0~10, 0~20, 0~50, 10~50,

0~100mv DC

V: −1~1, 0~1, 0~2, 0~5, 1~5, 0~10V

Input impedance: 500kΩ minimum

Current mA: 0~20, 4~20mA DC

Receiving impedance: 250Ω

Input scaling function: Scaling possible for voltage (mV, V) or

current (mA) input

Scaling range: −1999~9999 counts

Span: 10~5000 counts

Position of decimal point: None, 1, 2 and 3 digits on the right of

decimal point

Sampling cycle: 0.25 seconds

PV bias: −1999~2000 units

PV filter: 0~100 seconds

Isolation: Control input not insulated from system, set

value bias, and CT input but insulated from

others

Control Control mode

With 1 output: Expert PID control with auto tuning function

RA (reverse action characteristic): Heating action

DA (direct action characteristic): Cooling action

With 2 outputs: Expert PID control with auto tuning function +

PID control

PID (output 1) + PID (output 2)

ENT

RA (reverse action characteristic): Heating action

(OUT1) and cooling action (OUT2)

DA (direct characteristic): 2-stage heating action

Type of control/rating: Contact/1a 240V AC 2A (resistive load)

1.2A (inductive load)

(Common to Output 1 and 2): SSR drive voltage/12V±1.5V DC

(Maximum load current 30mA)

Current/4~20mA DC (Maximum load

resistance 600Ω)

Voltage/0~10V DC (Maximum load

current 2mA)

Control output resolution: Control output 1: approx. 0.0125% (1/8000)

Control output 2: approx. 0.5% (1/200)

Control output 1

Proportional band (P): OFF, 0.1~999.9% (ON-OFF action by OFF)

Integral time (I): OFF, 1~6000 seconds

(P or PD action by OFF)

Derivative time (D): OFF, 1~3600 seconds

(P or PI action by OFF)

Set value function: OFF, 0.01~1.00

ON-OFF hysteresis: 1~999 units (Effective when P=OFF)

Manual reset: −50.0~50.0% (Effective when I=OFF)

Higher/lower limit output limiter: Lower limit 0.0~99.9%, higher limit

0.1~100.0% (Lower limit value < Higher

limit value)

Proportional cycle: 1~120 seconds (for contact and SSR drive

voltage output)

Control output 2 (option)

Proportional band (P): OFF, 0.1~999.9%

(ON-OFF action by OFF)

Integral time (I): OFF, 1~6000 seconds

(P or PD action by OFF)

Derivative time (D): OFF, 1~3600 seconds

(P or PI action by OFF)

Set value function: OFF, 0.01~1.00

ON-OFF hysteresis: 1~999 units (Effective when P=OFF)

Dead band: −1999~5000 units (Overlap with a negative

value)

Higher/lower limit output limiter: Lower limit 0.0~99.9%, higher limit

0.1~100.0% (Lower limit value < Higher

limit value)

Proportional cycle: 1~120 seconds (for contact and SSR drive

voltage output)

Manual control

Output setting range: 0.0~100.0%

Setting resolution: 0.1%

Manual ↔ auto switching: Balanceless bumpless (within proportional

range)

Soft start: OFF, 1~100 seconds

AT point: SV value in execution

Control output characteristic: RA (reverse action characteristic)/DA

(direct action characteristic) switching by

front key or communication

With 2 outputs: RA (heating/cooling)/DA (2 stage heating)

Isolation: Contact output isolated from all.

Analog output not insulated from SSR drive

voltage, current and voltage but insulated

from others. (In case another output is also

SSR drive voltage, current or voltage,

two outputs are not insulated from

each other.)

Event output (option) Number of event points: 2 points of EV1 and EV2

Types: Selectable from the following 9 types for

EV1 and EV2:

Event setting range: Absolute values (both higher limit and

lower limit): Within measuring range

Deviations (both higher limit and lower

limit): −1999~2000 units

Higher/lower limit deviations

(within/outside): 0~2000 units

: No selection

: H igher limit deviation

: Lower limit deviation

: Outside higher/lower limit deviations

: W ithin higher/lower limit deviations

: H igher limit absolute value

: Lower limit absolute value

: Scaleover

: Heater break/loop alarm

Page 13: Control Adores

Series SR90

Event action: ON-OFF action

Hysteresis: 1~999 units

Standby action: Selectable from the following 4 types

EV1 and EV2: 1 Without standby action.

2 Standby when power is applied.

3 Standby when power is applied and

when SV value in execution is changed.

4 Control mode without standby action (No

alarm is output at the time of abnormal

input).

Output type/rating: Contact (1a × 2 points common)/240V AC

1A (resistive load)

Output updating cycle: 0.25 seconds

Heater break/heater loop alarm (option)Break/loop detection only for OUT1 (Selectable when output type is

contact or SSR drive voltage)

Current capacity: 30A, 50A to be designated when CT is

ordered.

Alarm action: Heater current is detected by external CT

provided as an accessory.

When heater break is detected while control

output is ON=Alarm output ON

When heater loop alarm is detected while

control output is OFF=Alarm output ON

Current setting range: OFF, 0.1~50.0A (Alarm action is stopped

by setting OFF)

Setting resolution: 0.1A

Current display range: 0.0~55.0A

Display accuracy: ±2.0A (Sine wave at 50Hz)

Minimum time to identify action: 0.25 seconds (every 0.5 seconds) common

to ON and OFF

Alarm retention mode: Selectable from lock (to retain) and real

(not to retain).

Standby action: Selectable from without (OFF) and with

(ON).

Sampling cycle: 0.5 seconds

Isolation: CT input not insulated from system and

other inputs but insulated from the others.

Set value bias (option) Setting range: −1999~5000 units

Action input: Non-voltage contact or open collector (level

action) about 5V DC, 1mA maximum

Minimum level retention time: 0.15 seconds

Isolation: Action input not insulated from system and

other inputs but insulated from others

Communication function (option) Type of communication: RS-232C, RS-485

Communication system: RS-232C 3-line type half duplex system

RS-485 2-line type half duplex system

RS-485 is of half-duplex multi-drop (bus)

system

Synchronization system: Start-stop synchronization system

Communication distance: RS-232C The longest: 15 m

RS-485 The longest 500 m (depending on

conditions)

Communication speed: 1200, 2400, 4800, 9600, 19200 bps

Data format: 7 bits, even parity, 1 stop bit or

8 bits, non-parity, 1 stop bit

Communication address: 1~255

Communication memory mode: EEP/RAM/r_E

Communication BCC: Add/Add two's cmp/XOR/None

Communication delay time: 1~100 (× 0.512 msec)

Communication code: ASCII code

Communication protocol: Shimaden's standard protocol

Number of connectable instruments:

RS-232 1

RS-485 up to 31

Isolation: Communication signals insulated from

system, each input and each output.

Analog output (option) Number of output points: 1 point

Type of analog output: Selectable from measured value, target

value (SV in execution), control output 1

and control output 2.

Output signal/rating: 4~20mA DC/Maximum load resistance 300Ω

0~10V DC/Maximum load current 2mA

0~10mV DC/Output resistance 10Ω

Output scaling: Measured value, target value: Within

measuring range (inversed scaling possible)

Control output 1 and 2 0.0~100.0%

(inversed scaling possible)

Output accuracy: ±0.3% FS (with respect to displayed value)

Output resolution: Approx. 0.01% (1/10000)

Output updating cycle: 0.25 seconds

Isolation: Analog output insulated from system and

inputs but not insulated from control output

except contact output.

General specifications Data storage: Non-volatile memory (EEPROM)

Environmental conditions for instrument operation:

Temperature: −10~50˚C

Humidity: 90% RH or less (no dew condensation)

Height: 2000m from the sea level or lower

Category: II

Degree of pollution: 2

Storage temperature: −20~65˚C

Supply voltage: Either 100-240V AC±10% 50/60Hz or

24V AC/DC±10% to be designated.

Power consumption: SR91: 100-240VAC 11VA maximum for

AC; 6W for DC 24V; 7VA for AC 24V

SR92, SR93 and SR94: 100-240VAC

15VA maximum for AC; 8W for DC

24V; 9VA for AC 24V

Input/noise removal ratio: 50 dB or higher in normal mode (50/60 Hz)

130 dB or higher in common mode

(50/60 Hz)

Applicable standards: Safety: IEC1010 and EN61010-1

EMC: EN61326

Insulation resistance: Between input/output terminals and power

terminal 500V DC 20MΩ or above;

Between input/output terminals and

protective conductor terminal 500V DC

20MΩ or above

Dielectric strength: Between input/output terminals and power

terminal 2300V AC/minute; Between

power terminal and protective conductor

terminal 1500V AC/minute

Protective structure: Only front panel has dust-proof and drip-

proof structure equivalent to IP66.

Material of case: PPO resin molding

(equivalent to UL94V-1)

External dimensions:

SR91: H48 × W48 × D111 (Panel depth: 100) mm

SR92: H72 × W72 × D111 (Panel depth: 100) mm

SR93: H96 × W96 × D111 (Panel depth: 100) mm

SR94: H96 × W48 × D111 (Panel depth: 100) mm

Mounting: Push-in panel (one-touch mount)

Panel thickness: 1.0~4.0 mm

Panel cutout: SR91: H45 × W45 mm

SR92: H68 × W68 mm

SR93: H92 × W92 mm

SR94: H92 × W45 mm

Weight: SR91: Approximately 170 g

SR92: Approximately 280 g

SR93: Approximately 330 g

SR94: Approximately 240 g

Page 14: Control Adores

ITEM CODE SPECIFICATIONS

SERIES SR91-

INPUT

Multi input

CONTROL OUTPUT (1)

POWER SUPPLY

REMARKS

OPTION

Control output (2)

Heater break alarm

Analog output

Communication

Set value bias

EVENT OUTPUT (OPTION)

4

8

6

Y-

I-

P-

V-

90-

08-

0

1

N

Y

I

P

V

1

2

8

3

4

6

5

0

9

MPU-Based Auto-Tuning PID Digital Controller, DIN H48 W48 D110mm

Thermocouple: B, R, S, K, E, J, T, N, PLII, Wre5-26 U, L (DIN 43710)

R.T.D.: Pt100 Ω /JPt100 Ω

Voltage: -10~10, 0~10, 0~20, 0~50,

10~50, 0~100mV DC

Current (mA): 0~20, 4~20mA DC

Receiving impedance: 250 Ω

Voltage (V): -1~1, 0~1, 0~2, 0~5,

1~5, 0~10V DC

For voltage and current input:

Scaling Possible

Range: -1999~9999

Span: 10~5000

Note: Inverse scaling

is not possible

Contact: 1a, Contact capacity: 240V AC 2.5A/resistive load

Proportional cycle: 1~120 sec.

Current: 4~20mA DC

Load resistance: 600 Ω max.

SSR drive voltage: 12V 1.5V DC/30mA max.

Proportional cycle: 1~120 sec.

Voltage: 0~10V DC

Load current: 2mA max.

100~240V AC 10%, 50/60Hz

24V AC/DC 10%, 50/60Hz

None

Contact output (2a) Ev1, Ev2: 240V AC 1A/resistive load

None

Contact: 1a, Contact capacity: 240V AC 2.5A/resistive load

Proportional cycle: 1~120 sec.

Current: 4~20mA DC

Load resistance: 600 Ω max.

Proportional cycle: 1~120 sec.

SSR drive voltage: 12 1.5V DC/30mA max.

Load current: 2mA max.

Voltage: 0~10V DC

Current setting range: 0.1~30.0A (with CT 30A)

Current setting range: 0.1~50.0A (with CT 50A)

when control output (1)

Note: Avaialble only

output is selected.

is Y or P and when event

Current: 4~20mA DC, Load resistance: 300 Ω max.

Voltage: 0~10mV DC, Output resistance: 10 Ω

RS-485

Voltage: 0~10V DC, Load current: 2mA max.

Open collector input rating: approx. 5V/1mA max.

1 point (setting range: -1999~5000), Non-voltage contact or Open collector input

With (Please consult before ordering.)

Without

Note:

When you purchase a two-output type controller and use it in a one output capacity, larger overshooting or undershooting may happen as

a result of integral operation. Therefore, we recommend you to choose a one-output type.

The cause of the above-mentioned problem is that the positional relationship between the proportional band (PB) and the set value (SV)

of a one-output type controller differs from that of a two-output type.

Series SR90

× ×

±

Page 15: Control Adores

Series SR90

ITEM CODE SPECIFICATIONS

SERIES SR92-

INPUT

Multi input

CONTROL OUTPUT (1)

CONTROL OUTPUT (2)(OPTION)

POWER SUPPLY

REMARKS

ANALOG OUTPUT (OPTION)

COMMUNICATION OR SV BIAS (OPTION)

EVENT OUTPUT/HEATER BREAK ALARM (OPTION)

4

8

6

Y-

I-

P-

V-

Y-

N-

I-

P-

V-

90-

08-

0

1

2

3

0

9

MPU-Based Auto-Tuning PID Digital Controller, DIN H72 × W72 × D110mm

Thermocouple: B, R, S, K, E, J, T, N, PLII, Wre5-26 U, L (DIN 43710)

R.T.D.: Pt100Ω /JPt100Ω

Voltage (mV): -10~10, 0~10, 0~20,

0~50, 10~50, 0~100mV DC

Current (mA): 0~20, 4~20mA DC

Receiving impedance: 250Ω

Voltage (V): -1~1, 0~1, 0~2, 0~5, 1~5,

0~10V DC Input resistance: 500kΩ min.

Scaling Possible

For voltage and current input:

Range: -1999~9999

Span: 10~5000

Note: Inverse scaling

is not possible.

Contact: 1a, Contact capacity: 240V AC 2A/resistive load

Proportional cycle: 1~120 sec.

Current: 4~20mA DC

Load resistance: 600Ω max.

SSR drive voltage: 12V±1.5V DC/30mA max.

Proportional cycle: 1~120 sec.

Voltage: 0~10V DC

Load current: 2mA max.

Contact: 1a, Contact capacity: 240V AC 2A/resistive load

None

Proportional cycle: 1~120 sec.

Current: 4~20mA DC

Load resistance: 600Ω max. (RA when shipped)

SSR drive voltage: 12V±1.5V DC/30mA max.

Proportional cycle: 1~120 sec.

Voltage: 0~10V DC

Load current: 2mA max.

100V~240V AC±10%, 50/60Hz

24V AC/DC±10%, 50/60Hz

None

Event output (2a) Ev1, Ev2

Contact capacity: 240V AC 1A/resistive load

Event output (Ev1) + Heater break alarm (with CT30A)

Event output (Ev1) + Heater break alarm (with CT50A)

Voltage: 0~10mV DC, Output resistance: 10Ω

None

Voltage: 0~10V DC, Load current: 2mA max.

Current: 4~20mA DC, Load resistance: 300Ω max.

RS-485

None

1 point (setting range: -1999~5000), Non-voltage contact or Open collector input

RS-232C

when control output (1)

Note: Available only

is Y or P is selected.

With (Please consult before ordering.)

Open collector input rating: approx. 5V/1mA max.

Without

0

3

4

0

5

7

8

6

Note:

When you purchase a two-output type controller and use it in a one output capacity, larger overshooting or undershooting may happen as

a result of integral operation. Therefore, we recommend you to choose a one-output type.

The cause of the above-mentioned problem is that the positional relationship between the proportional band (PB) and the set value (SV)

of a one-output type controller differs from that of a two-output type.

Page 16: Control Adores

Series SR90

ITEM CODE SPECIFICATIONS

SERIESSR94-

SR93-

INPUT

Multi input

CONTROL OUTPUT (1)

POWER SUPPLY

REMARKS

OPTION

Analog output

Communication

Set value bias (S V bias)

EVENT OUTPUT/HEATER BREAK ALARM (OPTION)

4

8

6

Y-

I-

P-

V-

Y-

I-

P-

V-

N-

08-

90-

0

1

2

3

00

08

38

68

Analog output +Set value bias (S V bias)

48

30

40

60

05

0

9

MPU-Based Auto-Tuning PID Digital Controller, DIN H96 × W48 × D110mm

MPU-Based Auto-Tuning PID Digital Controller, DIN H96 × W96 × D110mm

Thermocouple: B, R, S, K, E, J, T, N, PLII, Wre5-26 U, L (DIN 43710)

R.T.D.: Pt100Ω /JPt100Ω

Voltage: -10~10, 0~10, 0~20,

0~50, 10~50, 0~100mV DC

Current (mA): 0~20, 4~20mA DC

Receiving impedance: 250Ω

Voltage (V): -1~1, 0~1, 0~2, 0~5, 0~10V DC

Load resistance: 600Ω max.

Scaling Possible

Range: -1999~9999

Span: 10~5000

Note: Inverse scaling

is not possible

Contact: 1a, Contact capacity: 240V AC 2A/resistive load

Proportional cycle: 1~120 sec.

Current: 4~20mA DC

Load resistance: 600Ω max.

SSR drive voltage: 12V±1.5V DC/30mA max.

Proportional cycle: 1~120 sec.

Voltage: 0~10V DC

Load current: 2mA max.

None

None

None

Current: 4~20mA DC, Load resistance: 300Ω max.

Voltage: 0~10mV DC, Output resistance: 10Ω

Voltage: 0~10mV DC, Output resistance: 10Ω

SV bias 1 point

Current: 4~20mA DC, Load resistance: 300Ω max.

SV bias 1 point

Voltage: 0~10V DC, Load current: 2mA max.

SV bias 1 point

RS-485

07 RS-232C

Voltage: 0~10V DC, Load current: 2mA max.

Open collector input rating: approx. 5V/1mA max.

1 point (setting range: -1999~5000), Non-voltage contact or Open collector input

With (Please consult before ordering.)

Without

Contact: 1a, Contact capacity: 240V AC 2A/resistive load

Proportional cycle: 1~120 sec.

Current: 4~20mA DC

Load resistance: 600Ω max.

SSR drive voltage: 12V±1.5V DC/30mA max.

Proportional cycle: 1~120 sec.

Voltage: 0~10V DC

Load current: 2mA max.

100~240V AC±10%, 50/60Hz

24V AC/DC±10%, 50/60Hz

Event output (2a) Ev1, Ev2

Contact capacity: 240V AC 1A/resistive load

Event output (Ev1) + Heater break alarm (with CT30A)

Event output (Ev1) + Heater break alarm (with CT50A)

when control output (1)

Note: Available only

is Y or P is selected.

CONTROL OUTPUT (2)(OPTION)

For voltage and current input:

Note:

When you purchase a two-output type controller and use it in a one output capacity, larger overshooting or undershooting may happen as

a result of integral operation. Therefore, we recommend you to choose a one-output type.

The cause of the above-mentioned problem is that the positional relationship between the proportional band (PB) and the set value (SV)

of a one-output type controller differs from that of a two-output type.

Page 17: Control Adores

External Dimensions Panel Cutout

Series SR90SR91

SR92

OUT1 OUT2 EV1 EV2 AT MAN SB/COM

48

48

ENT

SR91

PV

SV C

45+0.60 (48 × N−3)+1

0

45

+0.6

0

45

+0.6

0

60 o

r m

ore

In the case of installation without leaving spacebetween instruments

N=The number of instruments

Unit: mm

11 100

111

44.6

11

12

11

12

11 1 11

1212

+

+

+

4-20mA0-10V30mA 12V

2A 240V

DCDCDC

AC

OUTPUT2

CT/SBSG

RS-485

A-output

1 11 6

7

8

9

10

12

13

14

15

2

3

4

5

+

L

N

+

−+ +

− −

A

B

B

DCCOM

EV11A240VAC

EV21A240VAC

4-20mA0-10V30mA 12V

2A 240V

DCDCDC

AC

100-240VAC~50/60Hz 11VA

24VDC 6W/24VAC~50/60Hz 7VA

OUTPUT1

Terminal Arrangement

SR93 AND SR94

11 100

111

67.6

OUT1

OUT2

EV1

EV2

AT

MAN

SB/COM

72

72

ENT

SR92

PV

SV ˚C

68 +0.70

68

+0

.70

10

0 o

r m

ore

100 or more

Unit: mm

1 15 8

9

10

11

12

13

14

16

17

18

19

20

21

2

3

4

5

6

7

+ +

− −

A

B

B

DC

+

+

COM

EV11A240VAC

EV21A240VAC

L

N

100-240VAC~50/60Hz 15VA

24VDC 8W/24AVC~50/60Hz 9VA

4-20mA0-10V30mA 12V

2A 240V

DCDCDC

AC

OUTPUT1

4-20mA0-10V30mA 12V

2A 240V

DCDCDC

AC

OUTPUT2

SB A-output

CT+

+

∗1

∗1

1

SG

SG SD RD

2 3

+ −

SPECIFICATION

TERMINAL

RS-232C

RS-485

1

2

3

Panel Cutout

• SR93

External Dimensions Panel Cutout

48 11 100

96

111

91

.6 ×

44

.6

OUT1 OUT2 EV2EV1 AT MAN SB/COM

SR94

96

96

ENT

SR93

11 100

111

91

.6

PV

SV ˚C

OUT1 OUT2

EV1 EV2 AT MAN SB/COM

ENT

PV

SV C

45+0.60 (48 × N−3)+1

0

92

+0

.80

92

+0

.80

130 o

r m

ore

In the case of installation without leaving spacebetween instruments

N=The number of instruments

Unit: mm

92 +0.80

92

+0

.80

130 o

r m

ore

130 or more

Unit: mm

13

14

15

16

17

18

19

20

11

12

1

2

3

4

5

6

7

9

10

8

+ +

− −

A

B

B

DCCOM

EV11A240VAC

EV21A240VAC

DCDCDC

AC

DCDCDC

AC

+

A-output

SB

CT

+

+

L

N

100-240VAC~50/60Hz 15VA

4-20mA0-10V30mA 12V

2A 240V

OUTPUT1

4-20mA0-10V30mA 12V

2A 240V

OUTPUT2

+

24VDC 8W/24AVC~50/60Hz 9VA

∗11

SG

SG SD RD

2 3

+ −

SPECIFICATION

TERMINAL

RS-232C

RS-485

∗1

1

2

3

4

External Dimensions

Terminal Arrangement (Common)

Terminal Arrangement

• SR94

Page 18: Control Adores

MEASURING RANGE CODES

TERMINAL COVER (AVAILABLE SEPARATELY)

Warning

• The SR90 series is designed for the control of temperature, humidity and other physical values of general industrial

equipment. (It is not to be used for any purpose which regulates the prevention of serious effects on human life or safety.)

Caution

• If the possibility of loss or damage to your system or property as a result of failure of any part of the process exists,

proper safety measures must be made before the instrument is put into use so as to prevent the occurrence of trouble.

ISO 9001

(The contents of this brochure are subject to change without notice.)

02DSR90500ILC

Material/Appearance: PVC/transparent

Thickness: 1 mm

Mounting: 2+B tight pan-head screws

M2.3 × 6mm

Temperature and Humidity Control Specialists

Head Office: 2-30-10 Kitamachi, Nerima-Ku, Tokyo 179-0081 JapanPhone: +81-3-3931-7891 Fax: +81-3-3931-3089

E-MAIL: [email protected] URL: http://www.shimaden.co.jp

Measuring range (°C) Measuring range (°F)

0

0.0

0

0

0

-199.9

-199.9

-200

-200

0

0

0

0

0

0

-199.9 400.0

800.0

200.0

200.0

-100.0

-50.0 50.00.0 200.0

-100.0

-50.0

0.0

100.0

100.0

50.0

200.0

1700

1200

1300

1300

2300

700

600

600

600

500

1700

1800

Code

0

0

0

0

0

-300

-300

0

0

0

0

0

0

-300 750

1500

400

400

200.0

3100

2200

2300

2300

4200

1300

1100

1100

31003300

-300 1100

-300 1000

-150.0 200.0-150.0

200.0-150.0

400.00.0

400.00.0

120.0-50.0

J

T

N

PLII

WRe5-26

U

L

Pt100

Jpt100

BR

S

K

K

KE

*1

*2

*2

*2

*3

-10 10

10

20

50

50

100

0

0

0

10

0

92

01

02

03

04

05

06

07

08

09

10

11

12

13

14

31

32

33

34

35

36

37

38

71

72

73

74

76

75

81

82

83

84

86

85

91

1-1

10

20

50

51

100

200

204

Input Type

Thermo-couple

Multi-in

put

Voltage(mV)

Voltage (V)

Current (mA)

R.T.D.

Owing to scaling function, any measuring range can be set within the following range.

Scaling range: Span:

*1 Thermocouple: B: Accuracy guarantee not applicable to

400˚C (752˚F) and below.

*2 Thermocouple K, T, U: Accuracy of those whose

readings are below -100˚C is ±0.7% FS

*3 Thermocouple PLII: Platinel

*4 Thermocouple Wre5-26: A product of Hoskins

*5 Thermocouple U, L: DIN 43710

-1999 to 9999 counts10 to 5000 counts on condition of lower side < higher side

-50.0 120.0

Measuring rangeInput Specification/Rating

0.0 ~ 800.0˚CMulti-input K thermocouple

0.0 ~ 100.0Voltage (V) 0 ~ 10V DC

0.0 ~ 100.0Current (mA) 4 ~ 20mA DC

NOTE:Unless otherwise specified, the measuring range will be set as listed below

during the shipment from the factory.

*4

*5

*5

Scaling possible

Refer to the informationon the right.

Series SR90

SR91

SR92

SR93

QCR001

QCR002

QCR003

One-touchmountOne-touchmount

One-touchmount

Model Mounting

SR94

QCR004

QCR005

Plus screw, B tight,M2.3 × 6 - 2 pcs.

Plus screw, B tight,M2.3 × 6 - 4 pcs.

Model

(Individual mounting)

(Tight-lock coupling)

Mounting

Material/Appearance: PVC/transparent Thickness: 1 mm