copy of dgt 321 l cw ws 001

Upload: aadelaadel-fd

Post on 03-Jun-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    1/18

    1

    A) Introduction:-

    Two numbers of circular thickeners have been provided as per

    the process requirement. The wall of the thickener is designed as

    circular wall as per the coefficents in IS 3370-part IV.

    The wall is designed as hinged at base for hoop forces and span

    B.M in the wall . On inner face of the wall steel is provided for

    100% fixity condition.

    B) Geo-technical Investigation & Soil Data Adopted in Design:-

    One number of Bore hole BH10 has been done at thickener

    location. Average EGL at this location is 595.5 . Refusal strata

    is met at depth of 1.5 M , N value =112 ( 594 M level).

    Proposed FGL in this area is 593.0 M . The founadtion is provided

    500 mm below FGL on the refulsal strata.

    The bearing capacity as per the soil report is as follows :-

    1.5 M below EGL 25 T/Sqm

    2.5 M below EGL 30T/Sqm

    For hard Rock Bearing pressure of 60 T/sqm is adopted.

    Note:- The bearing capacities in the table are Net safe bearing

    Capacities of the soil and gross bearing capacity at founding levelare adopted as follows:-

    Gross Bearing Capacity = Net Bearing Capacity + 1.6 x Depth of Foundation.

    ( Soil load from Existing Ground level to Finished ground level

    or above due to plinth filling will be treated as load , with soil

    weight of 2.0 T/Cum)

    For the Back fill soil following soil properties are adopted:-

    Soil Properties adopted in the design:- ( Back Fill material)

    Soil weight T/Cum

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    2/18

    2

    j Angle of Internal Friction 30 Degree

    ( For cantilever walls) Coefficient Active pressure 0.33 Ka

    ( For propped / circular Walls) Pressure at Rest 0.5 Kr

    ( For Computation of Loads) Weight of Soil 20 Kn/M3

    Submerged Soil Weight 10 Kn/M3

    (For stability against Uplift) Weight of Soil 16 Kn/M3

    (For stability against Uplift) Submerged Soil Weight 8 Kn/M3

    Subsoil Water level Not Present

    Force resistance from soil due to friction is computed as per the

    following equation.

    F= 2 / 3 ( tan ( )) x W

    W= Vertical Load on the Slab / Footing

    2/3xtan ( ) =0.384

    C) Liquid Retaining Structures:-

    All water retaining structure are designed as per the provisions

    in IS 3370-Part II - 2009 with controlled crack width of 0.1mm

    as per the specifications. The water level for the design shall be

    adopted as follows :-

    For strength calculations water shall be taken up to top of the wall

    assuming all outlets are blocked . For serviceability limit statecondition water level is adopted at working top liquid level or the

    overflow level as appropriate ( refer cl.4.2 of IS 3370-II -2009)

    Strength Calculations will be carried out using limit state design

    as per IS456-2000 with load factor of 1.5 .

    For empty condition soil level will be adopted as applicable.

    Non Liquid Retaining Structures and Buildings :-

    All non liquid retaining structures like foundations and columns of

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    3/18

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    4/18

    4

    Buildings / non Liquid retaining Structures M25

    All structural concrete will be with aggregates 40mm down for

    Footings and base slab and with 20mm down aggregates for all

    water retaining and other structures. For screed concrete 12.5mm

    down size aggregates will be used.

    III) Steel as Reinforcement for the Concrete:-

    For Water retaining structures : CRS Fe 500Grade.

    ( Steel with corrosion resistant Characteristics)

    E2) Minimum Thickness of Reinforced Concrete:-

    Following minimum thicknesses of the members will be provided

    Walls Liquid retaining Structures 250.00 mm

    Bottom Slab liquid retaining structures 250.00 mm

    Walls Foundations ( at base slab & wall junction) 250.00 mm

    Roof slab of Liquid retaining structures 200.00 mm

    Launder base slab & wall 150 mm

    Shell roof 100 mm

    Floors , roof slab , walkways , canopy slabs 125 mm

    Walls of cable & Pipe trenches 200 mmUnder ground Pits etc. 200 mm

    Footings at edge 200 mm

    Footing at column face 300 mm

    Columns:- Width 300 mm

    Depth 300 mm

    Beams:- Width 230 mm

    Depth 300 mm

    Parapets , Chajjas etc. 100 mm

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    5/18

    5

    Preacst Trench covers 75 mm

    E3) Minimum Cover to any Reinforcement:-

    Slabs:- Free face 30 mm

    Face in contact with Soil 40 mm

    Beams:- Top & Bottom 40 mm

    Side / face in Contact with Soil 40 mm

    Columns & Pedestals Super Structure 50 mm

    Sub. Structure 50 mm

    Foundations :- Bottom , Top 50 mm

    Sides 50 mm

    Retaining Walls , Basement & Pit Walls:-

    Face in Contact with Soil 40 mm

    Free face 30 mm

    Liquid retaining Structures

    Face in contact with liquid 50 mm

    Face in contact with Soil 50 mm

    Free face 50 mm

    E4) Minimum Bar Diameter of Reinforcement bars :-

    Major Foundations 10 mm

    Block Foundations :- Main bar 10 mm

    Dist. Steel 8 mm

    Columns & Pedestals Main bar 12 mm

    Links 8 mm

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    6/18

    6

    Beams:- Main bar 12 mm

    Stirrups 8 mm

    Slabs & Base Slabs :- Main bar 10 mm

    Dist. Steel 10 mm

    Walls & Wall Foundations :- Main bar 10 mm

    Dist. Steel 8 mm

    Other Minor elements 8 mm

    shell roof :- Main bar 10 mm

    Dist. Steel 8 mm

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    7/18

    7

    F) Design of The wall of the Thickener :-

    Typical Wall Section

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    8/18

    8

    F1) Design of main wall:-

    Wall top Level= 597.5 M

    Base slab level= 593 M

    Wall Height = H= 4.5 M

    Wall Th. provided at base t= 0.25 M

    Wall Th. provided at span t= 0.25 M

    Tank Diameter D= 19.5 M

    HxH/Dxt is adopted = 4.15

    Design of wall For Bending Moment :-

    Base B.M Tank Full case :- Coefficient as per IS 3370= 0.026

    =9.81x4.5 Water pressure at base Triang. 44.145 Kn/Sqm

    Refer table 10 of IS 3370-Part IV for Coefficient

    B.M= 0.026x44.145x4.5x4.5 23.24234 Kn-M

    Ultimate B.M = Mu=1.5 M 34.86 Kn-M

    D ( Cms )= 25 d= 19.5 Cms

    Mu/(bx d x d) 0.916858

    Refer Sp16 , Table 4 Pt ( required ) 0.23 %

    Ast= 4.485 Sqcm

    Provided on Inner Face Y10-175 C/C

    Base B.M for Tank Empty Case:- Not criticalRefer table 13 of IS 3370-Part IV for Coefficient

    Maximum Span B.M in wall for Hinged Case=0.0118xwxHxHxH 10.54845 Kn-M

    D ( Cms )= 25 d= 19.5 Cms

    Mu/(bx d x d) 0.416112

    Refer Sp16 , Table 4 Pt ( required ) 0.105 %

    Ast= 2.0475 Sqcm

    Provided on outer face Y10-175 C/C

    Check for shear force in the wall at base :- Adopted as for fixed base

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    9/18

    9

    Refer table 11 of IS 3370-Part IV

    Coefficient for shear 0.23

    Shear force = V 45.69008 Kn

    (Note : Shear will be lesser at critical section " d " from base slab face.)

    Ultimate shear=1.5 x V 68.53511 Kn

    D ( Cms )= 25 d= 19.5 Cms

    Vu/(b x d) 0.351462

    Refer Sp16 , Table 61 Pt ( required ) 0.23 %

    Ast= 4.485 Sqcm

    Provided on Inner Face Y10-175 C/C

    Mimimum Steel Required :-

    Mimimum Pt 0.35 %

    Surface zone =25/2= 12.5 Cms

    Ast= 4.375 Sqcm

    Provided Y10-175 C/C B.F

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    10/18

    10

    Check for Crack width:-

    As crack width is

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    11/18

    11

    Design of Wall For Hoop Forces :-

    Tank Full Condition is Critical :- Refer table 12 of IS 3370-Part IV

    Hoop force in Top 0.0 H to 0.3 H=0.367x4.5x9.75x9.81 = T 157.9618 Kn

    Tu=T x1.5 236.9428 Kn

    =0.87x500 Permissble stress in steel=fst 435 Mpa

    =Tu/fst Steel required 5.44696 Sqcm

    Steel on each face 2.72348 Sqcn

    Provided minimum steel Y10-175 C/C B.Faces

    Hoop force in 0.3 H to 0.8 H=0.58x4.5x9.75x9.81 = T 249.64 Kn

    Tu=T x1.5 374.46 Kn

    =0.87x500 Permissble stress in steel=fst 435 Mpa

    =Tu/fst Steel required 8.608275 Sqcm

    Steel on each face 4.304138 Sqcn

    Provided minimum steel Y10-175C/C B.Faces

    Below 0.8H steel is provided nominal Y10-175 C/c B.Faces.

    No craking of the section.

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    12/18

    12

    F2) Design of the launder:-

    Vertical wall of the launder :- Wall Top level 597 M

    Base Slab level 596.4 M

    Wall height 0.6 M

    B.M as cantilever 0.35316 Kn-M

    =((0.35x100000x6/(1000x150^2) Bending stress developed 0.093 MPA

    Nominal

    Ast=( fst=130,d=7.5) 0.426136 Sqcm

    Min steel =0.35x15 5.25 Sqcm

    Provided Y10-145 C/C

    Provided above minimum steel Horizontally also.

    Design of Base Slab of the launder:-

    Base slab is designed as cantilever from the main wall.

    B.M due to base slab from vertical wall

    Self Load of the wall=V 2.25 KN

    B.M at wall face=0.375*V 0.84375 Kn-M

    B.M due to load on the base slab :-

    Self Load Base slab ( av 0.2th) 0.50625 Kn-M

    PCC fill ( max =0.2 th) 0.216 Kn-M

    ( ht above PCC) Water Load max.(0.4 m ) 0.28122 Kn-MTotal B.M = 1.84722 Kn-M

    Axial force 0.7848 KN

    D provided 25 Cms

    =Mx1e6/(0.85x130xdx100) Ast ( B.M , fst=130,d=19.5) 0.857278 sqcm

    = Tx1e3/(130/100/2) Ast axial force each face 0.030185 Sqcm

    Total steel 0.887463 Sqcm

    Minimum steel =0.35x12.5 4.375 Sqcm

    Provided Y10-175 C/C

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    13/18

    13

    Distribution steel Y8-110 C/C T & B

    F3) Design of Foundation for the Wall :-

    Net safe bearing Capacity at founding level 25 T/Sqm

    say 250 Kn/sqm

    Loading :-

    Dead load of the wall:-

    Wall height provided 4.50 M

    Thickness provided 0.25 M

    Load / Meter 28.13 Kn/m

    Dead load from the launder:-

    Wall Load 2.81 Kn/M

    Base slab + Water+ Screed 4.12 Kn/M

    Total Launder Load 6.93 Kn/M

    Self load Footing :-

    Average thickness 0.25 M

    Base slab width provided 1.45 M

    Load / Meter 9.06 Kn/M

    Total Dead load effect = V d.l. 44.12 Kn/M

    say 45.00 Kn/M

    Footing width provided 1.45 MBase pressure developed 31.03 Kn/Sqm

    Soil Load effect :-

    Soil load on external projection:-

    Soil height 0.1 M

    Projection width 0.6 M

    Load / M @ 20Kn/Cum 1.2 Kn/M

    Soil + Slab Load on Internal Projection:- not present in this case

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    14/18

    14

    Soil height 0 M

    Projection width 0 M

    Load / M @ 20Kn/Cum 0 T/M

    Slab Load 0 T/M

    Total load on inner Projection 0.00

    Total soil Load V s.l 1.20 Kn/M

    say 1.20 Kn/M

    B.M at footing center line 0.51 kn-M

    Additional Base pressure out side 2.28 Kn/sqm

    Additional Base pressure inside -0.63 Kn/sqm

    ( Out side) Maximum base pressure in combination Dead Load 33.32 Kn/sqm

    (Inside) Maximum base pressure in combination Dead Load 30.41 Kn/sqm

    Water Load effect :-

    Water height 4.50 M

    Slab projection 0.60 M

    Load /M = 26.49 Kn/m

    B.M due to water load 11.26 T-M

    Refer page 8 B.M due to water pressure 23.24 Kn-M

    50 % fixity B.M =23.24/2 11.62 Kn-M

    Design B.M -0.36

    Kn-M

    Base pressure developed

    Inside in combination D.L 48.27 Kn/sqm

    Outside in combination D.L 50.34 Kn/sqm

    =48.27-0.63 Inside in combination D.L+S.L 47.64 Kn/sqm

    =50.34+2.28 Outside in combination D.L+SL 52.62 Kn/sqm

    Effect of the Bridge Load :-

    Reaction from Bridge 150 Kn

    Load after dispersion through

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    15/18

    15

    wall at 45 degree=150/(2x4.8) 15.63 Kn/M

    Load/ sqm= 10.78 K/sqm

    Maximum Base pressure 63.40 Kn/sqm

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    16/18

    16

    F5) Seismic Load Effect :- Seismic load is adopted as per IS 1893-2002

    Refer IS-1893 -2000 Part 1

    Sa/g= 2.5

    Damping 5 %

    Z= 0.16

    R= 3

    I= 1.5

    Ah= 0.1000

    Horizontal coefficients are computed as per IS 1893-1984

    ( Referred as Part 2 of code is not published , refer page 2 of

    IS 1893-part 1)

    R= 9.75 M

    H= 4 M Service Condition

    For maximum force Cos ( Phi) = 1 , y= h

    Pw=0.35x9.81 3.4335 Kn/sqm

    As above increase is lesser than the free board , Seismic case not critical

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    17/18

    17

    G) Design of Staircase:- Staircase is provided with stringer Beam

    =1.2x(3.739+2.188

    +1.2+5)+0.3x0.45x25/0.8

    Steel provided 3 nos-Y16 T & B

    Stps Y8-150 C/C 2 legged.

  • 8/11/2019 Copy of Dgt 321 l Cw Ws 001

    18/18

    18

    Design of column below staircase :-

    Provided 300 mm diameter column .

    Maximum load on the column 84.6 Kn

    As load on column is nominal provided nominal 0.8 % steel

    Ast= 5.652 Sqcm

    Provided 6 Nos Y12

    Links Y8-150C/C

    ( As the bearing Capacity of the soil 25 T/sqm , area rquired for

    above load is only 0.34 Sqm , Provided nominal footing )