Page 2: cPMS and GIS Smart Switchgear help Pre-installed type substation

The traditional way of load sheddingPower balance and frequency

§ when the power of the output power is greater than theload power consumption, frequency will increased

§ when the output power of the consumption of power isless than the load power, frequency will drop

© ABB GroupDecember 9, 2014 | Slide 2

Page 3: cPMS and GIS Smart Switchgear help Pre-installed type substation

The traditional way of load sheddingIssue

§ Depend on frequency load shedding, due to thefrequency from the voltage loop, in order toprevent the oscillation in the system or thesystem voltage dip device misoperation, requirelow frequency load shedding device must pass atime delay. Result in system frequencydeteriorating even further.

§ Due to system load constantly changes, can'tadvance the time to determine the lightening linenumber. More cutting load or less cutting load,which leads to the system, cause the secondaryfault.

§ effective lightening range 49.5 ~ 48 hz.Couldn'thave done fine load shedding.

© ABB GroupDecember 9, 2014 | Slide 3

Page 4: cPMS and GIS Smart Switchgear help Pre-installed type substation

cPMSCharacteristics

§ Quickness (within 10 ms) and accuracy,and finish the load shedding beforefrequency change

§ Based on accuracy, power balancecalculation,

§ 19 level effectively reducing load level,to do fine load shedding

© ABB GroupDecember 9, 2014 | Slide 4

Page 5: cPMS and GIS Smart Switchgear help Pre-installed type substation

cPMSSystem

© ABB GroupDecember 9, 2014 | Slide 5

Page 6: cPMS and GIS Smart Switchgear help Pre-installed type substation

cPMSAnalysis

G1 T1 G2 T2

3 4 5 6 2 6 7 8 9 1

LBB1SL1

LBB1SL2

LBB1SL3

LBB1SL4

LBB2SL1

LBB2SL2

LBB2SL3

LBB2SL4

LBB2SL5

LBB1SL5

BusTie

REG630

REF615

LBB1 LBB2

§Step 1: Trip event registration by Generator IED, REG630 ~ 10ms§Step 2: Event sent on GOOSE by Relion® REG630; reaches Relion® PML630 ~ 10ms (max)

PML630

§Step 0: Periodic power values from power sources and load IEDs ~ 1000ms

§Step 3: Processing and initiating load-shedding action (10 ms cycle) ~ 20ms (assuming 2 cycles)§Step 4: Relion® PML630 sends shed commands on GOOSE to the load feeder IED, Relion® REF615 ~ 10ms (max)§Step 5: Load feeder IEDs process GOOSE message and release trip command (including contact operation) ~ 10ms§Step 6: ABB switchgear MV circuit breaker opening time ~ 60ms§Total performance time including load-feeder CB operation -> 60+50 ~ 110ms

© ABB GroupDecember 9, 2014 | Slide 6

Page 7: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 7

Gas Insulated Switchgear ZX2The First Generation of MV C-GIS

§ Separated three phases arrangement

§ ZF/8DA10

Page 8: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 8

Gas Insulated Switchgear ZX2The 1.5 Generation of MV C-GIS

§ Tube type with three phases in onegas chamber

§ WI

Page 9: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 9

Gas Insulated Switchgear ZX2The 2nd Generation of MV C-GIS

§ Cubical type with welded gas tank

§ ZV series

Page 10: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 10

Gas Insulated Switchgear ZX2The 3nd Generation of MV C-GIS

§ Gas work free on site

§ ABB ZX series

Page 11: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 11

Gas Insulated Switchgear ZX2

Page 12: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 12

Gas Insulated Switchgear ZX2Double busbar panel

Rated voltage kV 12 24 36 40.5Rated current of busbars A ... 2500 ... 2500 ... 2500 ... 2500Rated current of tee-offs A ... 25003) ... 25003) ... 2500 3) ... 2500 3)

Rated short-circuit breakingcurrent kA ... 40 ... 401) 4) 401) 4) ... 40

Rated voltage kV 12 24 36 40.5Rated currentof busbars A ... 2500 ... 2500 ... 2500 ... 2500

Width a mm 600 / 8005)

Height b mm 2300

Depth c mm 1760

Page 13: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 13

Gas Insulated Switchgear ZX2Typical feeder unit

CB com-partmentABusbar compartmentB

Cable compartmentC

Pressure relief duct of CB chamberD

Pressure relief duct of BB compartmentE

LV compartmentF

Page 14: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 14

Gas Insulated Switchgear ZX2Pressure-relief duct

1

2

34

Pressure relief duct of BB compartment1

Busbar compartment2

Pressure relief duct of CB chamber3

CB com-partment4

Page 15: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 15

Gas Insulated Switchgear ZX2Busbar compartment with 3-position switch

Page 16: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 16

Gas Insulated Switchgear ZX2

Page 17: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 17

Gas Insulated Switchgear ZX2Plug-in busbar

Page 18: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 18

Gas Insulated Switchgear ZX2Plug-in busbar

Page 19: cPMS and GIS Smart Switchgear help Pre-installed type substation

© ABB GroupDecember 9, 2014 | Slide 19

E-house SolutionAssembly

Page 20: cPMS and GIS Smart Switchgear help Pre-installed type substation

E-house SolutionValue properties

Shorten the project cycle: In the factory to complete the installation of electrical equipment,wiring and testing, the overall transportation and hoisting

To reduce the input: the scene only need a small amount of civil engineering and cabling work

Single electrical interface: from design to delivery, with a single interface contact all electricalequipment suppliers

satisfy different working conditions: structural strength, heat insulation, ventilation andair conditioning system design

Avoid redundant construction: can the whole mobile, applicable to a migration requirementsof power supply and distribution system