d818/et minipurge manual · 2020. 4. 27. · the purge system commences the purge cycle: • the...
Embed Size (px)
TRANSCRIPT

ML511 | v12 17-April-2020
D818/ET MiniPurge®
ManualML 511
Important Note:It is essential for safety that the installer and user of the Expo system follow these instructions.Please refer to the standard for principles and definition.These instructions apply only to the pressurizing system. it is the responsibility of the manufacturer of the pressurized enclosure to provide instructions for the enclosure.Expo Technologies reserves the right to replace any component, with one of the equivalent functionality.


ML511 | v12 i
Section 1: System Specification................................................................................................1MiniPurge® Control Unit Data...................................................................................................2Relief Valve Unit and Purge Outlet Valve with integral spark arrestor......................................3
Section 2: Quick User Guide......................................................................................................4Installation ................................................................................................................................4Operation of the System...........................................................................................................4
Section 3: Application Suitability ..............................................................................................5Section 4: Description and Principle of Operation ..................................................................6Section 5: Main Components .....................................................................................................7
Air Supply Filter / Regulator......................................................................................................7Logic Air Supply Regulator .......................................................................................................7Minimum Pressure Sensor .......................................................................................................7Purge Flow Sensor ...................................................................................................................7Intermediate Sensor .................................................................................................................8Electronic Purge Timer .............................................................................................................8Purge Complete Valve..............................................................................................................8OR Gate ...................................................................................................................................8Alarm Only Circuit (/AO) ...........................................................................................................8Visual Indicators .......................................................................................................................9Power Interlock Switch .............................................................................................................9Alarm / Pressurized Switch.......................................................................................................9System Purging Switch (Optional) ............................................................................................9Purge Valve ..............................................................................................................................9Purge Flow Restrictor ...............................................................................................................9CLAPS Sensor .........................................................................................................................9CLAPS Regulator .....................................................................................................................9Relief Valve Unit .....................................................................................................................10/PA Terminal Box....................................................................................................................10
Section 6: Installation of the System.......................................................................................10Relief Valve Unit .....................................................................................................................10Air Supply Quality ...................................................................................................................10Pipe Work ...............................................................................................................................11Multiple Enclosures ................................................................................................................11Provision and Installation of Alarm Devices ...........................................................................11Power Supplies and their Isolation .........................................................................................12Power Interlock Switch ...........................................................................................................12
Section 7: Commissioning .......................................................................................................13Commissioning the System ....................................................................................................13Normal Operation ...................................................................................................................14
Section 8: Maintenance of the System....................................................................................15General maintenance .............................................................................................................15Additional maintenance checks ..............................................................................................15Maintenance of Electronic Timer ............................................................................................15Re-calibration of the Relief Valve Unit ....................................................................................15Re-calibration of the Pressure Sensors..................................................................................16
Section 9: Fault Finding............................................................................................................17General Information................................................................................................................17System purges correctly but trips and auto re-purges at the end of the purge time. ..............17Relief Valve opens (continuously or intermittently).................................................................18System enters purging but purge indication does not occur...................................................18System begins purging but cycles fail to complete.................................................................18
Section 10: Recommended Spares List ..................................................................................19Section 11: Glossary.................................................................................................................19Section 12: Drawings and Diagrams .......................................................................................19Section 13: Certifications .........................................................................................................20

Section 1: System Specification
3 X LC / ss / ET / OV / PC / PA
Size 3 = MiniPurge®
Purge flow rate:1000-1500 NI/min
Approval / Certification
Sira 01ATEX1295X 2813 II 2(2) GD
Ex [pxb] ia IIC T5 GbEx [pxb] ia IIIC T100ºC DbTamb -20ºC to +55ºC
IECEx SIR07.0027XEx [pxb] ia IIC T5 GbEx [pxb] ia IIIC T100ºC DbTamb -20ºC to +55ºC
TÜV 12.1462XEx [pxb] ia IIC T5 GbEx [pxb] ia IIIC T100ºC DbTamb -20ºC to +55ºC
PC = Pressurized Control. Automatic leakage compensation (CLAPS)
OV = Purge Outlet Valve is pneumatically operated
Timing MethodET = Electronic Timer
MiniPurge® Housingss = Stainless Steel 316L
Pressurization MethodLC = Leakage Compensation
ATEX Certificate:
IECEx Certificate:
TÜV INMETRO Certificate:
PA = Power and Alarm Switches. Integral /PA Terminal Box
Page1
ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011
Expo Technologies UST: +1 (440) 247 5314
Expo Technologies ChinaT: +86 532 8906 9858

MiniPurge® Control Unit DataAction on Pressure Failure: Alarm and Trip (isolate power to pressurized enclosure), user
adjustable Alarm Only.Type of Operation: Automatic leakage compensation using the Closed Loop Automatic
Pressurization System (CLAPS System).Leakage Compensation Capacity: 500 NI/min @ 4barg inlet pressureLeakage Compensation over capacity:
+40%(minimum) of the normal enclosure leakage
Enclosure Material: Stainless Steel 316L.Mounting Method Wall mounting straps. Fixing holes as per drawing.Temperature Limits: -20oC to +55oCCompressed Air Supply: Clean, dry, oil free air or inert gas. Refer to Air Supply Quality section
in Installation of the System.Supply Pressure: 4 to 8 barg (60 to 120 psi). Main Regulator: Set at 4 barg, 40 μm automatic drain supply inlet filter.Logic Regulator and Gauge: Fitted and set to 2.5 barg (36 psi).Process Connections: Purge supply and outlet to pressurized enclosure 1/2” NPT female.
Minimum supply line 13 mm (1/2”) ID tube, inlet sized appropriately for flow rate.Reference points & signals 1/8” NPT female, minimum 6 mm pipe to be used.
Visual Indicators: Alarm (Red ) / Pressurized (Green ).System Purging: 4 LEDs that flash sequentially to indicate elapsed time (black when not purging).
/PA Terminal Box: Stainless Steel, Ex e IIC T5 Gb / Ex tb IIIC T100ºC Db IP66 Tamb : -20ºC to +55ºC with terminals, front access cover & lower removable gland plate. Stainless Steel, Ex e IIC T4 Gb Tamb : -20ºC to +60ºC with terminals, front access cover & lower removable gland plate.
Power Interlock Switch: DPNO switch, contact ratings 250 Vac 4 Amps (AC-15) / 24V DC 4A, Ex d IIC T6 Gb / Ex tb IIIC T80ºC Db.
Alarm Switch: SPCO switch, contact ratings 250 Vac 4 Amps (AC-15) / 24V DC 4A, Ex d IIC T6 Gb / Ex tb IIIC T80ºC Db.
Minimum Pressure Sensor: Minimum: 0.5 mbarg.Maximum: 5.0 mbarg.Default Setting: 1.5 mbarg.Tolerance -0, +0.7 mbarg.
Purge Flow Sensor: Set at 6.4 mbarg (Tolerance: -0, +10%).CLAPS Sensor: Minimum: 5.0 mbarg.
Maximum:15 mbarg.Default Setting: 10 mbarg.Tolerance: -0, +10%
Note: there must be a 2.5 mbarg difference between the intermediate and CLAPS sensor calibration point. For example: Minimum pressure = 5 mbarg, intermediate pressure = 6.5 mbarg, CLAPS sensor = 9 mbarg.
Purge Time: User selectable, in 1 minute intervals, up to 99 minutes (tolerance -0, +3 seconds).
ML511 | v12 Page2
Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]
Expo Technologies UST: +1 (440) 247 5314E:[email protected]
Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Relief Valve Unit and Purge Outlet Valve with integral spark arrestor
Note: Special settings are available on request, see Test and Inspection Sheet.
Default Setting 99 minutes.Weight: 16 kg (35lb).
Type: ARV-0528-107Bore: Purge Outlet Valve Ø 52 mm, Relief Valve Ø 52 mm.Relief Valve Lift-Off Pressure: Minimum: 20 mbarg.
Maximum: 50 mbarg.Default: 30 mbarg (+0, -20%).
Flow Rate: Range: 500, 1000 or 1500 NI/min.Default: 1500 NI/min.
Material: Housing: Stainless steel 316L.Gasket: Silicone.Spark arrestor: Stainless steel mesh.
Mounting Method: Rectangular cut-out and fixing holes as per drawing.Weight: 4 kg (8.8 lb).
Page3
ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011
Expo Technologies UST: +1 (440) 247 5314
Expo Technologies ChinaT: +86 532 8906 9858

Section 2: Quick User GuideInstallationThe MiniPurge® System must be installed by a competent engineer, in accordance with relevant standards,such as IEC / EN 60079-14 and any local codes or practice.
• Mount the purge system in accordance with the hook-up drawing.
• Ensure the system is installed according to the full instructions in the “Installation of the System” section of this manual.
• All pipings must be clean and free of dirt, condensation and debris prior to connection to the purge system or pressurized enclosure.
• It is strongly recommended that a local isolation valve is installed on the air supply upstream of the purge system.
Note: Most faults are due to restricted air supply, inadequate supply pipe work or drop in air supply pressure during the purge process.
Operation of the SystemOnce the system is installed correctly, turn on the air supply. Refer to Commissioning section.
The purge system commences the purge cycle:
• The purge air will enter the enclosure.
• The pressurized enclosure will obtain a positive pressure.
• The Purge Outlet Valve will open within the Relief Valve Unit.
• The air will then exit the Relief Valve Unit housing via the spark arrestor.
Open the Purge Flow Restrictor Valve until the air flow reaches the required rate; the system will initiate the timed purge cycle. Start a stopwatch when the purging indicator flashes yellow
On completion of an uninterrupted purge cycle of the required length, the system will indicate purge complete. Stop the stopwatch when the purging indicator stops flashing.
Indicator Colour Status
Alarm / Pressurized Red Low pressure alarm (enclosure pressure too low)
Purging Black Purge flow too low or not in purge mode
Indicator Colour Status
Alarm / Pressurized Green Pressurized (minimum enclosure pressure achieved)
Purging Black Purge flow too low
Indicator Colour Status
Alarm / Pressurized Green Pressurized
Purging Sequential flashing Yellow
Purge flow rate above minimum
Indicator Colour Status
Alarm / Pressurized Green Pressurized and in leakage compensation mode
ML511 | v12 Page4
Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]
Expo Technologies UST: +1 (440) 247 5314E:[email protected]
Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Check stopwatch timing to verify that the actual purge time is equal to or greater than the required purge time.
Note: The recorded purge time must never be less than the required purge time.The system is now operating correctly in leakage compensation mode.
If the system has not performed as expected, check the installation thoroughly and ensure it has been carried out according to the instructions.
If an obvious problem has not been highlighted and corrected, follow the procedures in the Fault Finding section.
If all checks have been carried out and the system still does not perform as expected, contact your local distributor or Expo Technologies.
Section 3: Application SuitabilityMiniPurge® systems are certified for use in hazardous locations, where the hazardous location is non-mining (above ground) and the hazard is caused by flammable gasses, vapours or dust. Depending on the model the systems may be used in IECEx and ATEX Zone 1 and/or Zone 2 - Categories 2 and 3 respectively.
MiniPurge® systems may be used for hazards of any gas group. Apparatus associated with the MiniPurge® system, such as intrinsically safe signalling circuits and flameproof enclosures containing switching devices may be limited in their gas group. The certification documentation supplied with any such devices must be checked to ensure their suitability.
This system is primarily designed for use with compressed air. Where other inert compressed gasses are used (Nitrogen, for example) the user must take suitable precautions so that the build up of the inert gas does not present a hazard to health. Consult the Control of Substances Hazardous to Health (COSHH) data sheet for the gas used. Where a risk of asphyxiation exists, a warning label must be fitted to the pressurized enclosure.
The following materials are used in the construction of MiniPurge® systems. If substances that will adversely affect any of these materials are present in the surrounding environment, please consult Expo Technologies for further guidance.
Purging Black No longer in purge mode
Materials of Construction
Stainless Steel Aluminium Acrylic
Mild (Carbon) Steel Nylon Silicone
Brass Polyurethane Neoprene
ABS Polycarbonate Polyester (glass filled)
Indicator Colour Status
Page5
ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011
Expo Technologies UST: +1 (440) 247 5314
Expo Technologies ChinaT: +86 532 8906 9858

Section 4: Description and Principle of OperationThe MiniPurge® system is pneumatic in operation, with electrical interfaces.
Purge and pressurization is a method of protection used in Zone 1 (21) and/or Zone 2 (22) hazardous locations to ensure that the interior of an enclosure is free of flammable gas. Addition of a MiniPurge® system allows the electrical equipment within the enclosure to be used safely in a hazardous location.
The principle of purge and pressurization is as follows:
• Clean compressed air or inert gas is drawn from a non-hazardous location.
• The interior of the pressurized enclosure is flushed to remove any hazardous gas or dust.
• This is introduced into the pressurized enclosure to keep the internal pressure at least 0.5 mbarg abovethe external pressure.
• Whilst pressurized, flammable gas cannot enter the enclosure from the environment.
Prior to switching on the power to the electrical equipment, the enclosure must be purged to remove any flammable gas that might have entered the enclosure before pressurization. Purging is the process of removal contaminated air and replacement with air (or inert gas) known to be free from flammable gas. The duration of this purge process is normally ascertained by performing a purge test.
At the end of the purge cycle the system automatically switches to leakage compensation mode. The Purge Outlet Valve is closed and the airflow is reduced but remains high enough to compensate for the leakage of air from the enclosure whilst maintaining the minimum over pressure state.
In the event of pressure failure within the pressurized enclosure the system will raise an alarm in the form of visual indicators and a volt free contact depending on the specification of the system. The default action on loss of pressurization is alarm and automatic disconnect of power (A&T - Alarm and Trip). This can be changed by the customer to Alarm Only (/AO), please refer to section titled Main Components.
The MiniPurge® system incorporates a Closed Loop Automatic Pressurization System (CLAPS). This allows the system to detect a rise or fall of the enclosure’s internal pressure and adjust the leakage compensation rate accordingly. Pressure variations are more likely during sudden start up of large rotating electrical machines but can also be caused by changes in running temperature. This system has been specifically designed to maintain a stable internal pressure within the enclosure.
ML511 | v12 Page6
Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]
Expo Technologies UST: +1 (440) 247 5314E:[email protected]
Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Pressure characteristics during purge and pressurization of a pressurized enclosure using a MiniPurge® system that incorporates a CLAPS system:
Section 5: Main ComponentsAir Supply Filter / RegulatorThe unit is provided with a 40 μm liquid / dust filter element as a precaution. The user of the MiniPurge® system must ensure that air supply is to the quality stated in Air Supply Quality paragraph found in the Installation of the System section. The regulator is factory set to 4 barg (60 psig) and regulates the pressure of an air supply between 4 and 8 barg (60 to 120 psig). A pressure gauge is fitted down stream of the filter; this should indicate no less than 4 barg (60 psig). During the purge cycle a pressure drop will be indicated on the gauge.
Logic Air Supply RegulatorThis device provides the system with a stable air supply pressure to the logic system and allows consistent operation. The pressure level is factory set to 2.5 barg (36 psig) and can be verified by means of the integral pressure gauge.
Minimum Pressure SensorThis monitors the pressure inside the pressurized enclosure. When the pressure is below the minimum required for safe operation, the pressure sensor causes the system to reset and the Alarm / Pressurized indicator turns Red . The sensor is factory calibrated and set to operate in falling pressure at or above the minimum specified pressure.
Purge Flow SensorThe Purge Flow Sensor monitors flow through the Purge Outlet Valve. At correct purge flow rates, above the minimum specified for purging, the sensor sends a signal that activates the purge timer. This sensor is factory calibrated to operate on falling flow rate at or above the minimum specified purge flow rate.
Intermediate PressureSensor Pressure
Power Interlock switchAlarm &Trip
Purge Time Machinery Start Normal Operation
CLAPS RegulatorPressure
Intermediate switch contactsopen. Intermediate sensorsends falling pressure signal
Fault Condition - loss of pressureoutside of CLAPS regulation
Minimum PressureSensor Pressure
Purging Pressure
Minimum pressure switch contactsopen. Minimum pressure sensor sendsa low pressure signal.Alarm indicator shows red (alarm only)Alarm indicator shows red and poweris disconnected (Alarm and Trip)
Minimumpressure switch
Intermediatepressure switch
Power Interlock switchAlarm Only
ContactsActive
Inactive
Page7
ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011
Expo Technologies UST: +1 (440) 247 5314
Expo Technologies ChinaT: +86 532 8906 9858

Intermediate SensorThis sensor monitors the pressure inside the pressurized enclosure. It senses when the pressure is drops and provides early warning before the low pressure sensor trips the system. The setting on this is user selectable.
Electronic Purge TimerWhen both the enclosure pressure and the purge flow rate are correct, the Purge Flow Sensor activates the timer and the electronic timer starts. The timing period is selected using switches mounted on the timer module.
Note: Setting the timer to 00 minutes will cause infinite purging; the cycle will never complete.During timing, the percentage of the purge cycle is indicated by four LEDs which flashes sequentially while the timer is running.
The Electronic Timer contains an intrinsically safe battery pack that needs regular replacement. See Commissioning section.
Purge Complete ValveThis valve receives a signal from the purge timer that indicates the completion of the purge cycle and verifies that the pressurization signal is still present. If both conditions are satisfied a signal is sent to indicate that the purge is complete. This performs two functions: to turn on the electrical supply to the pressurized enclosure and to reduce the high purge flow rate to leakage compensation mode. It also provides a hold-on signal that maintains the leakage compensation mode with the power switch on, even when the purge timer has reset ready for the next purge cycle.
OR GateThis device provides the Purge Complete Valve with the hold-on function referred to previously. When either the timed-out signal or the purge complete signal is present it allows the pilot signal to be sent to the purge complete valve.
Alarm Only Circuit (/AO)If the pressure in the pressurized enclosure is too low the system will normally cut off electrical power to it. In certain circumstances, where local codes of practice allow, the system can be altered to provide a hold-on circuit that will maintain the electrical power supply to the pressurized enclosure while also providing a pressure failure alarm. The user must respond to the alarm and either restore the pressure to the pressurized enclosure or otherwise make the installation safe; for example, cut off the electrical supply. The decision to use the Alarm Only facility, and the allowable length of time for non-pressurized operation, is the responsibility of the user.
Warning: It is potentially dangerous to energise the pressurized enclosure in an non-pressurized condition when it is known that there is potentially explosive gas or dust in the hazardous location.
LED 1
LED 2LED 3
LED 4 LED 1
LED 2LED 3
LED 4 LED 1
LED 2LED 3
LED 4 LED 1
LED 2LED 3
LED 4
0 to 25%of purge time
26 to 50%of purge time
51 to 75%of purge time
76 to 100%of purge time
ML511 | v12 Page8
Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]
Expo Technologies UST: +1 (440) 247 5314E:[email protected]
Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Visual IndicatorsVisual indicators are fitted to provide status information to the operator.
* The Green / Black combination indicates normal operation of the pressurized enclosure after the initial purging cycle has been completed.
Power Interlock SwitchThis flameproof power switch is activated by the signal from the Purge Complete Valve. This activation can be used to turn on the electrical supply to the pressurized enclosure. The cable from the switch is terminated in the /PA terminal box.
Alarm / Pressurized SwitchThis flameproof switch is operated by the pressurized signal. It allows a remote electrical system status indicator to show either pressurized or a pressure failure alarm. The cable from the switch is terminated in the /PA terminal box.
System Purging Switch (Optional)This switch is operated by the purge flow signal that allows a remote electrical system status indicator to signal that the system is purging; sometimes referred to as purge in progress. The cable from the switch is terminated in the /PA terminal box.
Purge ValveThis changeover valve selects between purge air flow or leakage compensation. It is sized to allow sufficient air into the enclosure during purging based on: the specified air supply pressure range, the minimum specified purging outlet flow rate +10% and the expected leakage rate from the pressurized enclosure. At the end of the purge cycle, the purge valve closes in response to the “Purge Complete” signal; it remains in the closed position until the next purge cycle is initiated.
Purge Flow RestrictorThis valve restricts the purge flow to the minimum required flow rate. The Purge Flow Restrictor must be readjusted during commissioning.
CLAPS SensorThis sensor monitors the pressure within the pressurized enclosure and sends a control signal to the CLAPS Regulator. The normal running pressure must be determined prior to system start-up so that the CLAPS Sensor may be set to the level required to control the CLAPS Regulator.
CLAPS Regulator This is the regulator that controls the leakage compensation air flow into the enclosure after the purging is complete. It either increases or decreases the air flow into the enclosure as appropriate to maintain a stable running pressure. The CLAPS Regulator must be set at the time of commissioning.
Alarm / Pressurized Indicator
Green* Pressurized
Red Pressure Alarm (enclosure pressure low)
System Purging Indicator
Black* Purge flow too low (not in purge mode)
Yellow (flashing) Purging (flow above minimum)
Page9
ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011
Expo Technologies UST: +1 (440) 247 5314
Expo Technologies ChinaT: +86 532 8906 9858

Relief Valve UnitThe Relief Valve Unit allows the purge air to exit the enclosure safely via a built-in spark arrestor. This spark arrestor is designed to prevent the emission of arcs, sparks and incandescent particles produced within the pressurized enclosure.
Purge air passes through the Relief Valve Unit; the preset pressure differential across the appropriate orifice ensures that the purge flow sensor is activated once the selected purge flow has been attained.
During the purge cycle a pneumatic cylinder operates the Purge Outlet Valve that lets the air from inside the enclosure exhaust through the Relief Valve Unit. When the system changes to leakage compensation mode, the Purge Outlet Valve is closed and the enclosure sealed.
The Relief Valve Unit has an in-built relief valve. This is sized to ensure that, if the air supply pressure rises up from the specified maximum, the internal enclosure pressure will not exceed the specified maximum working pressure of the pressurized enclosure.
/PA Terminal BoxThe Terminal Box is increased safety (Ex e) certified and incorporates the terminal connection points for the alarm and interlock switches. All contacts provided are volt free (dry).
Cable entry methods (for example conduit or cable glands) must be certified to IECEx, ATEX or INMETRO standards. The main requirement is that IP66 (or better) ingress protection must be provided by use of seals or washers.
Section 6: Installation of the SystemThe MiniPurge® is designed for use under normal industrial conditions of ambient temperature, humidity and vibration. Please consult Expo before installing this equipment in conditions that may cause stresses beyond normal industrial conditions.The MiniPurge® system must be installed by a competent person in accordance with relevant standards, such as IEC / EN 60079-14, and any local codes of practice.
The MiniPurge® control unit should be installed either directly on, or close to the pressurized enclosure. It should be installed such that the system indicators and certification labels are in view.
All parts of the system carry a common serial number. If installing more than one system, ensure that this commonality is maintained within each system installed.
Relief Valve UnitTo achieve effective purging, the points where air enters and exits the pressurized enclosure should normally be at opposite ends of the enclosure. The RLV unit must be mounted vertically and there should be a minimum clearance of 300 mm (12") around the spark arrestor (purge outlet).
It is important that the interior and exterior of the spark arrestor is kept clean and debris is not allowed to accumulate; this might affect the calibration of the device. In particular the exterior of the spark arrestor should not be painted or blocked in any way.
Air Supply QualityThe MiniPurge® system should be connected to a protective gas supply, which is suitable for purging and pressurization.
The supply pipe connection to the MiniPurge® must be appropriate for the maximum input flow rate for the application.
The air supply must be regulated at a pressure less than the maximum stated inlet pressure.
ML511 | v12 Page10
Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]
Expo Technologies UST: +1 (440) 247 5314E:[email protected]
Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

The air supply must be: clean, non-flammable and from a non-hazardous location. The air should be of Instrument Air Quality. Although the purge control system will operate with lower air quality, its operational life will be adversely affected. The equipment that is being protected by the MiniPurge® may also suffer because of poor air quality.
With reference to BS ISO 8573-1: 2010, Instrument Air is typically specified as:
Particle Class 1
In each cubic metre of compressed air, the particulate count should not exceed 20,000 particles in the 0.1 to 0.5 micron size range, 400 particles in the 0.5 to 1 micron size range and 10 particles in the 1 to 5 micron size range.
Humidity or pressure dew point
The dew point, at line pressure, shall be at least 10 °C below the minimum local recorded ambient temperature at the plant site. In no case, should the dew point at line pressure exceed +3 °C.
Oil Class 2
In each cubic metre of compressed air, not more than 0.1mg of oil is allowed. This is a total level for liquid oil, oil aerosol and oil vapour.
When an inert gas is being used to supply the purge system, risk of asphyxiation exists. Refer to Application Suitability section.
Before connection of the air supply to the purge system, the supply pipe work should be flushed through with instrument quality air to remove any debris that may remain in the pipes. This must be carried out for at least 10 seconds for every meter of supply pipe.
Unless a supply shut-off valve has been fitted to the MiniPurge® system, an external shut-off valve with the same, or larger, thread size as the Control Unit inlet fitting should be fitted by the installer to prevent any restriction of purge flow.
The purge air from the MiniPurge® Control Unit should be piped within the pressurized enclosure to ensure purging of potential dead air spots.
The purge system is fitted with an internal regulator factory set to 3 bar feeding the logic.
Pipe WorkIf the MiniPurge® is not connected directly to the pressurized enclosure, pipe work and fittings used to connect the Control Unit to the pressurized enclosure should be either metallic or appropriate to the environment into which the system is installed. No valve may be fitted in any signal pipe connecting the Control Unit to the pressurized enclosure. This pipe work must be fitted in accordance with local codes of practice where relevant.
Multiple EnclosuresThis system is suitable for the purge and pressurization of the primary pressurized enclosure and its associated terminal boxes.
Provision and Installation of Alarm DevicesWhen the pressure inside the pressurized enclosure is above the minimum, the Minimum Pressure Sensor returns a positive (pressurized) signal causing the alarm indicator on the control unit to change from red to green.
Page11
ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011
Expo Technologies UST: +1 (440) 247 5314
Expo Technologies ChinaT: +86 532 8906 9858

When the pressure falls below the minimum permissible the positive (pressurized) signal is removed. This absence of signal indicates a low pressure alarm condition and causes the alarm indicator on the control unit to go from green to red.
There are volt free (dry) contacts available within the terminal box for remote usage.
The user must make use of this alarm facility in accordance with the local code of practice for Action on Pres-sure or Flow Failure. Most codes include the following recommendations:
• Zone 1 Installations: Alarm and Automatic Trip of Power.
• Zone 2 Installations: Alarm Only on pressure or flow failure with power being removed manually.
Power Supplies and their IsolationAll power entering the pressurized enclosure should have a means of isolation. This requirement also applies to any external power sources that are connected to the equipment such as volt-free (dry) contacts within the pressurized enclosure. This is commonly achieved using the Power Interlock Switch.
Power Interlock SwitchThis switch is a Double Pole Normally Open, double-break switch: it provides two independent contacts that should be connected in series and used to isolate the power. This can be achieved using switchgear or other suitable switching device. These contacts are terminated and accessible to the user in the Ex e terminal box.
It is the responsibility of the user to ensure that the switch is only operated within appropriate technical limits.
The switch must be replaced after any short circuit that occurs within the main circuit; the switch is a piece of encapsulated equipment and as such it is not possible to check the state of the contacts. Technical modifications to the switch are not permitted.
Prior to commissioning, check that the Ex e terminal box is clean, the connections have been made properly, the cables laid correctly and all screws in the terminals are secure.
In all cases the application and isolation of power must be controlled by the MiniPurge® system using the power interlock signal.
No switches are permitted between the power switch and the MiniPurge® system other than an authorized manual override circuit.
The safe use of this switch is the responsibility of the user, all electrical installations must conform to local codes of practice.
ExceptionPower to apparatus that is already suitable for use in hazardous locations need not be isolated by the MiniPurge® system.
ML511 | v12 Page12
Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]
Expo Technologies UST: +1 (440) 247 5314E:[email protected]
Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Section 7: CommissioningCommissioning the SystemNote: The steps 11 and 15 to 21 represent detailed commissioning testsThe following equipment is needed for this process:• Continuity meter• Gauge manometer (0 to 200 mbarg)• Differential manometerIf, after commissioning, the system does not perform as expected, refer to the Fault Finding Section.Follow the steps as outlined:1. Check all connections and that the Relief Valve Unit is fitted correctly with an unobstructed path to the
purge exhaust.2. Close the Purge Flow Restrictor Valve.3. Fully open external supply shut-off valve where fitted.4. Check that the internal logic pressure gauge reads 2.5 barg / 36 psi / 250 kPag.5. Check that the pressure gauge on main air supply reads 4 barg / 60 psi / 400 kPag.6. Check that the Pressure Relief Valve is correctly set by disconnecting the minimum pressure sensing pipe
at the bulkhead fitting on the input to the MiniPurge®. This will disable all of the pressure sensors.• Using a 4 mm nylon tube, connect a manometer to the bulkhead fitting from which the minimum pressure sensing pipe was removed.• Open the Purge Flow Restrictor Valve very slowly, until the Pressure Relief Valve opens • Check the opening pressure is within calibration limits. • This test can be carried out several times to ensure repeatability and compliance.Refer to the Maintenance of the System section if the Relief Valve needs recalibrating.
7. Close the Purge Flow Restrictor Valve.8. Remove the manometer and reconnect the minimum pressure sensing pipe to the bulkhead fitting.9. Remove red plug from the top of the Minimum Pressure Sensor and connect a gauge manometer.10.Connect a differential manometer to the test points on the flow sensor.11.To check sensor calibration
• The internal pressure in the pressurized enclosure must be below Relief Valve lift off pressure and above the CLAPS pressure• At this time the pressurized indicator should be green.• gradually open Purge Flow Restrictor Valve until purging indicator flashes yellow.Note: For large volumes it may take a long time for the purge flow to start.• very slowly close Purge Flow Restrictor Valve until the purging indicator stops flashing yellow.• Take a reading from pressure gauge.
12.To set the purge flow rate:
• Turn on the compressed air to the MiniPurge®.• Gradually open the Purge Flow Restrictor Valve until the black / yellow indicator changes to yellow (flashing). • The flashing yellow indicator confirms the correct flow rate.• The differential pressure should be greater than 6.4 mbarg.
Page13
ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011
Expo Technologies UST: +1 (440) 247 5314
Expo Technologies ChinaT: +86 532 8906 9858

• The relief valve is supplied with different orifice plates for the specified flow rate. This orifice plate is held in position by two M3 screws and can easily be changed by removing the large cover plate from over the outlet valve assembly and screws.
Warning: When opening the Purge Flow Restrictor Valve, ensure the over pressure within the pres-surized enclosure does not exceed the pressure relief valve setting.13.The purge timer will start as soon as the Purging Indicator flashes yellow. Check that the time delay
between the indicator turning to yellow (flashing) and returning to black is not less than the minimum time required for complete purging of the pressurized enclosure. Times in excess of minimum are permitted.
14.After the purge has been completed, the Purge Valve will close and the air flow into the pressurized enclosure will be controlled by the CLAPS Regulator. The initial setting may be too high or too low.
15.Gradually turn the CLAPS Regulator anti-clockwise to reduce enclosure pressure.16.Reduce regulator until intermediate sensor causes contacts to open.17.Check the manometer on the minimum pressure sensor.18.Continue to reduce the CLAPS Regulator to test the minimum pressure sensor.19.To check operation of Minimum Pressure Sensor, check readings on manometer as system will
automatically re-purge when it reaches minimum pressure.20.While the system re-purges, return the CLAPS Regulator to the initial setting. 21.If minimum pressure is below the set point, refer to the Recalibration section22.If the setting is too high, continual rising and falling of the enclosure pressure will be seen as the CLAPS
Regulator automatically shuts off and reinstates the flow. The CLAPS Regulator should be adjusted to reduce the flow into the pressurized enclosure by turning the adjuster screw anti-clockwise.
23.If the initial setting is too low the CLAPS Regulator may not provide enough air flow causing a gradual decline in enclosure pressure. To increase the flow into the pressurized enclosure, adjust the CLAPS Regulator Relief Valve unit by turning the adjuster screw clockwise.
24.To test the CLAPS settings, create a leak in the system by removing a bolt or losening a gland plate in order to create a 15mm hole. Remember to replace bolt or retighten gland plate after testing.
25.The setting of the CLAPS Sensor is factory calibrated to the normal working pressure expected in the pressurized enclosure, typically 10 mbarg. The pressure in the pressurized enclosure should be stabilized as close as possible to this figure. This can be checked by a manometer attached to the minimum pressure sensor.
26.Remove the air supply to the system, remove all test equipment and replace all plugs.Normal OperationFor normal operation of the system, after commissioning has been carried out it is possible to turn the air supply valve on or off to start or stop the system. After this, the purge and pressurization sequence is automatic.
ML511 | v12 Page14
Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]
Expo Technologies UST: +1 (440) 247 5314E:[email protected]
Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Section 8: Maintenance of the SystemGeneral maintenanceThe maintenance of the system outlined in this manual should be supplemented with any additional requirements set out in appropriate local codes of practice.The following checks should be carried out every 6 – 36 months dependent on environment according to IEC / EN 60079-17 • Tests outlined in the Detailed Commissioning section.• Ensure that the Relief Valve Unit is free from contamination prior to making any adjustment. To do this:
• Remove large cover plate using a 8 mm spanner (wrench).• Check that the interior and all components are clean and free from contamination.• Replace large cover plate.
• Check the condition of the air supply filter element. Clean or replace as necessary.Additional maintenance checksThe following additional checks are recommended at least every 3 years:Check that:• Apparatus is suitable for use in the hazardous location.• There are no unauthorised modifications.• The air supply is uncontaminated.• The interlocks and alarms function correctly.• Approval labels are legible and undamaged.• Adequate spares are carried.• The action on pressure failure is correct.
Maintenance of Electronic Timer
This should be carried out every 3 years.
• The intrinsically safe battery pack associated with the electronic timer should be replaced and the commissioning tests repeated.
• After the timing phase has elapsed, the battery may be hot-swapped in the hazardous location without affecting the operation of the MiniPurge® system
Re-calibration of the Relief Valve Unit
Warning
Incorrect adjustment of the Relief Valve Unit can lead to significant over pressure and result in damage to the enclosure.If maximum pressure setting is reached, stop adjustment and reduce the pressure.To perform the following adjustments, an 8 mm spanner (wrench) and a 2.5 mm hex key will be required.Ensure that the Relief Valve Unit is free from contamination prior to making any adjustment. To do this: • Remove large cover plate using a 8 mm spanner (wrench).• Check that the interior and all components are clean and free from contamination.• Replace large cover plateTo adjust the lift off pressure of the Relief Valve:• Attach test equipment as described in the Commissioning Section.
Page15
ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011
Expo Technologies UST: +1 (440) 247 5314
Expo Technologies ChinaT: +86 532 8906 9858

• Remove small cover plate.• Whilst holding the central adjustment screw in position using the hex key, loosen the retaining nut.• Adjust the hex key clockwise to increase, or anti-clockwise to reduce the lift off pressure.• Before testing, retighten the locking nut whilst holding the adjustment screw in place.• Carry out the commissioning tests to check the correct setting of the relief valve after adjustment.
• The adjustment is sensitive and it is recommended that a 1/4 turn (maximum) adjustments are applied between tests.
Re-calibration of the Pressure SensorsThe brass nozzle on the sensor is sealed into position using Loctite thread sealant. If the thread has seized up, remove to a safe area and heat slightly to soften prior to making any adjustment. This prevents potential damage to the brass of the nozzle.• Disconnect pipe work from the sensor, including pipe located below the sensor.• Remove sensor by unscrewing anti-clockwise.• The nozzle is located under the sensor.
• The adjustment is sensitive, turn the nozzle in 1/8 of a turn steps.• Turn clockwise to reduce the pressure setting and anti-clockwise to increase.• Replace sensor, screwing clockwise.• Reconnect all pipe work.
Orifice PlateAllen Screw and Lock NUT
Removing the small cover plate to set the RLV opening pressure
ML511 | v12 Page16
Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]
Expo Technologies UST: +1 (440) 247 5314E:[email protected]
Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Section 9: Fault FindingGeneral InformationIf you are having problems that cannot be corrected using one of the methods described, please call Expo oryour supplier for further assistance. If the system is less than 12 months old, parts under warranty should bereturned to Expo for investigation. A full report of the fault and the system serial number should accompanythe parts.It is common for problems with the MiniPurge® system to be caused by contamination of the air supply withoil, water or dirt. To prevent these problems, the air supply must contain a dust filter and a water filter. Thiswill ensure that the air is instrument quality and protect both the purge system and the equipment beingpurged. This filtration system is not provided by Expo and must be sourced separately.Contamination can enter the system from a number of sources. To prevent this, it is essential that theprocedures described in the Installation section are carried out prior to first use of the system. Theseprocedures should also be carried out following any disconnection and re-connection of the pipe work. Failureto perform these procedures may cause damage to the system that will not be covered by the warranty.The system has been designed for ease of fault finding and many of the components fitted are plug-in orchassis mounted. Check components by substitution only after establishing that such action is necessary.Before carrying out the fault finding procedures, ensure that:• Both the main air pressure to the system and for Motor Purge Systems, the regulated pressure to the logic
manifold are as specified on the settings sheet.• Air pressure does not drop below the minimum supply pressure during purging; the majority of faults
reported are due to insufficient air supply during the purge cycle.
System purges correctly but trips and auto re-purges at the end of the purge time.This is a result of the pressure within the pressurized enclosure being below the minimum pressure sensor setting. The pressure can be checked using a manometer. The most common causes of this problem are outlined below.Fault Location Cause SolutionPressurized Enclosure There is debris on the face of the
Relief Valve disk held in place by the magnet.
• Remove debris and ensure RLV disk is clean.
Enclosure leaking excessively. • Ensure all doors and covers are closed and that all conduit and cable glands are properly sealed.
• Seal any other leaks.Pressure sensing tube damaged. • Replace tubing.
CLAPS Regulator The CLAPS Regulator setting is too low.
• Increase the setting of the CLAPS regulator to raise the pressure in the pressurized enclosure after purging.
• To do this, turn clockwise.MiniPurge® Control Unit the Minimum Pressure Sensor
setting has drifted above the CLAPS setting
The Minimum Pressure Sensor needs re-calibrating.
• Refer to Re-calibration of PressureSensors in the Maintenancesection
Page17
ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011
Expo Technologies UST: +1 (440) 247 5314
Expo Technologies ChinaT: +86 532 8906 9858

Relief Valve opens (continuously or intermittently)
System enters purging but purge indication does not occur
System begins purging but cycles fail to complete
Fault Location Cause SolutionPressurized Enclosure Enclosure pressure is too high
due to CLAPS Regulator being open to far.
Adjust the CLAPS Regulator.
Relief Valve Unit Debris on the Relief Valve disk allowing air to leak from the valve.
Remove Relief Valve cover and clean the valve disk.
Fault Location Cause SolutionAir Supply Insufficient flow rate due to
inadequate air supply pressure. Often due to pressure drop in the supply pipe.
Static pressure of 5 barg must bemaintained during purge• Check air supply pressure at the
inlet to the control unit. • Ensure that the supply pipe bore is
suitable for the flow ratePressurized Enclosure Excessive leakage from the
pressurized enclosure.• Check around the enclosure while
purging is taking place. • Total leakage at purge outlet valve
should not exceed 10% of purge flow sensor setting.
• Check for leakage down cables and conduit.
Pipe Work Tubing from Relief Valve flow sensing point not air tight.
• Ensure fitting nuts are tightened.• Check for tube damage.• Repair as necessary.
Relief Valve Unit Relief Valve opening during purge • Check enclosure pressure on start up is less than Relief Valve lift off pressure.
MiniPurge Control Unit Flow sensor setting incorrect • Check the pressure is correct on the flow sensor.
Fault Location Cause SolutionElectronic Timer Time set to 00 • Reset timer to correct purge
time.The intrinsically safe battery pack is discharged
• Replace as necessary .
ML511 | v12 Page18
Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]
Expo Technologies UST: +1 (440) 247 5314E:[email protected]
Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Section 10: Recommended Spares List
Section 11: Glossary
Section 12: Drawings and Diagrams
Part Number DescriptionS0015/250 Filter kit for main air supply filter/regulatorS0030/606 Purge flow sensor factory set to 6.4 mbargS0030/016 Minimum Pressure sensor, must be factory set to the value as stated on the
Customer Test and Inspection SheetS0030/588 CLAPS Sensor must be factory set to the value as stated on the Customer Test
and Inspection SheetS0015/018 Pressure gauge (Air Supply Pressure), 0 - 10 bargS0015/135 Miniature gauge (Logic Pressure), 0-4 bargETM-IS31-001 IS battery pack for electronic timer moduleAGE-GE00-168 Electronic Timer Assembly c/w potted Timer Switch
Acronym DefinitionA&T Alarm and TripAO Alarm OnlyCLAPS Closed Loop Automatic Pressurization SystemCU Control UnitET Electronic TimerFCV Flow Control ValveIS Intrinsically SafeLC Leakage CompensationPA Power and Alarm RLV Relief Valve Unit
Title Drawing Number Number of SheetsD818 Control Unit Motorsys-E XBR-7TD0-068 2Motorpurg Hook-Up MOTOR-HU 1P and I Diagram XBR-7TD0-064 1D818 Circuit Diagram XBR-7TD0-071 1D818 Ex e Terminal Box Layout AGE-WC00-224 1Manual Override Switch Hook-up AGE-WC00-117 1Size 3 MotorPurge Relief Valve XBR-RTD0-010 1
Page19
ML511 | v12Expo Technologies UKT: +44 (0) 20 8398 8011
Expo Technologies UST: +1 (440) 247 5314
Expo Technologies ChinaT: +86 532 8906 9858

Section 13: CertificationsCertificates can be found in the accompanying booklet (ML497) or download the certificates at www.expoworldwide.com/downloads.
*Certificates are attached to the manual.
Component Certificate NumberPurge System ATEX Certificate SIRA 01ATEX1295X
IECEx Certificate IECEx SIR07.0027XINMETRO/TÜV Certificate TÜV 12.1462X
MIU/e Ex e Terminal Box ATEX Certificate Sira 99ATEX3173X*IECEx Certificate IECEx SIR 06.0087X*
Electronic Timer ATEX Certificate FM 10 ATEX0003X IECEx Certificate IECEx FME 10.0001X
Electronic Switches Ex d limit switch IECEx EPS 14.0092XEx d limit switch EPS 14 ATEX 1766 X
ML511 | v12 Page20
Expo Technologies UKT: +44 (0) 20 8398 8011E: [email protected]
Expo Technologies UST: +1 (440) 247 5314E:[email protected]
Expo Technologies ChinaT: +86 532 8906 9858E: [email protected]

Min
iPurg
e
NO
TES
1.
MIN
IPU
RG
EM
UST
BE
MO
UN
TED
INTH
EATTIT
UD
ESH
OW
N.
2.
WEIG
HT:
16
kg
MO
DEL
NO
.3XLC/s
s/E
T/P
A/O
V/P
C/D
818
EXPO
TECH
NO
LO
GIE
SPART
CO
DE:
D818M
OTO
RSYS-E
MATERIA
LS
SYSTEM
HO
USIN
G:
STAIN
LESS
STEEL
316
ALL
BU
LKH
EAD
FIT
TIN
GS:
STAIN
LESS
STEEL
304/3
16
210
72
430
400
250
215
120
400
110
56
A B
42
31
30
18
50
100
50
VIE
WO
N
ARRO
W'A
'
VIE
WO
NARRO
W'B
'
MA
TE
RIA
L
DR
'WN
AP
P'D
CH
K'D
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.N
o:
DA
TE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CT
ION
DIM
EN
SIO
NS
INm
m
DO
NO
TS
CA
LE
Exp
oT
ech
no
log
ies
Lim
ited
JO
BN
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No.
OF
SU
RR
EY
TW
16
5D
B
UN
ITE
DK
ING
DO
M
DR
AW
ING
No.
SC
ALE
The
conte
nts
ofth
isdra
win
g/docum
entare
Copyrightã
Expo
Technolo
gie
sLim
ited.
They
are
tobe
treate
das
confidentialand
are
retu
rnable
upon
request.
They
are
notto
be
copie
dor
com
munic
ate
din
part
or
inw
hole
withoutw
ritten
consentfr
om
Expo
Technolo
gie
sLim
ited,neither
are
they
tobe
used
inany
way
again
stour
inte
rests
.
80
D.P
.LO
FRO
MRELIE
FVALVE
1/8
"N
PT
MO
TO
R
LO
WPRESSU
RE
ALARM
/PRESSU
RIZ
ED
IND
ICATO
R(R
ED
/G
REEN
)
SYSTEM
PU
RG
ING
IND
ICATO
R
(BLACK
/YELLO
W)
4H
OLES
Ø9.5
FO
RW
ALL
MO
UN
TIN
G
PU
RG
EAIR
SU
PPLY
1/2
"N
PT
MAIN
SYSTEM
DATA
LABEL
FIT
TED
INSID
ECO
VER
PU
RG
EAIR
OU
TLET
1/2
"N
PT
FIL
TER
DRAIN
1/8
"N
PT
MO
TO
REN
CLO
SU
RE
PRESSU
RE
CO
NN
ECTIO
N
1/8
"N
PT
D.P
.H
IFRO
MRELIE
FVALVE
1/8
"N
PT
OPEN
PU
RG
EO
UTLET
SIG
NAL
TO
RELIE
FVALVE
1/8
"NPT
MO
TO
REN
CLO
SU
RE
PRESSU
RE
CO
NN
ECTIO
N
1/8
"N
PT
535
M6
x25
LO
NG
EXTERN
AL
EARTH
STU
DS

MA
TE
RIA
L
DR
'WN
AP
P'D
CH
K'D
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.N
o:
DA
TE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CT
ION
DIM
EN
SIO
NS
INm
m
DO
NO
TS
CA
LE
Exp
oT
ech
no
log
ies
Lim
ited
JO
BN
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No.
OF
SU
RR
EY
TW
16
5D
B
UN
ITE
DK
ING
DO
M
DR
AW
ING
No.
SC
ALE
The
conte
nts
ofth
isdra
win
g/docum
entare
Copyrightã
Expo
Technolo
gie
sLim
ited.
They
are
tobe
treate
das
confidentialand
are
retu
rnable
upon
request.
They
are
notto
be
copie
dor
com
munic
ate
din
part
or
inw
hole
withoutw
ritten
consentfr
om
Expo
Technolo
gie
sLim
ited,neither
are
they
tobe
used
inany
way
again
stour
inte
rests
.
VIE
WO
FFRO
NT
OF
UN
ITW
ITH
DO
OR
REM
OVED
TO
SH
OW
INTERN
AL
LAYO
UT
SCRAP
VIE
WW
ITH
DO
OR
FIT
TED
TO
SH
OW
IND
ICATO
RS
NO
TES
CERTIF
ICATIO
NLABEL
FIT
TED
INSID
ED
OO
RO
FSYSTEM
EN
CLO
SU
RE.
MAIN
AIR
SU
PPLY
FIL
TER/R
EG
ULATO
R
FLO
WRESTRIC
TO
R(C
LAPS
SEN
SO
RSU
PPLY)
SYSTEM
PU
RG
ING
SW
ITCH
,250V
4A,
SPN
OEx
dII
(OPTIO
NAL)
27
22
24
25
26
23
21
20
19
17
GAU
GE,
MAIN
AIR
SU
PPLY
GAU
GE,
LO
GIC
AIR
SU
PPLY
LO
GIC
AIR
SU
PPLY
REG
ULATO
R
CLAPS
SEN
SO
R
MO
TO
RIN
TERLO
CK
SW
ITCH
,250V
4A,
DPN
OEx
dII
LEAKAG
ECO
MPEN
SATIO
N,
CLAPS
VALVE
INTERM
ED
IATE
PRESSU
RE
SEN
SO
R
MIN
IPU
RG
ED
OU
BLE
IND
ICATO
RLABEL
IND
ICATO
R,
ALARM
/PRESSU
RIZ
ED
ALARM
/PRESSU
RIZ
ED
SW
ITCH
,250V
4A,
SPN
OEx
dII
PU
RG
EO
UTLET
OPEN
SIG
NAL
VALVE
(1)
PU
RG
ECO
MPLETE
BO
OST
VALVE
12
14
16
15
13
11
10983 5 7641 2
REF
IND
ICATO
R,
SYSTEM
PU
RG
ING
PU
RG
EFLO
WSEN
SO
R
LO
GIC
MAN
IFO
LD
MIN
IMU
MPRESSU
RE
SEN
SO
R
ELECTRO
NIC
PU
RG
ETIM
ER
PU
RG
EFLO
WRESTRIC
TO
R
PU
RG
EVALVE
DESCRIP
TIO
N
-28
15
26
24
23
22
21
20
14
13
12
18
19
11
10
98
7
462
16
25
1
SCRAP
VIE
WO
FD
OO
RFRO
MIN
SID
E
27
35
TIM
ER
SELECTO
RSW
ITCH
ES
18
TERM
INAL
BO
X,
Ex
eII
T100°C
(Tam
b-2
0°C
-55°C)
IP64
I.S
BATTERY
PACK
29
PU
RG
ECO
MPLETE
VALVE
29
TIM
ER
VALVE
30
30
STAIN
LESS
STEEL
VIS
IWIN
KPRO
TECTO
R31
31
PU
RG
EO
UTLET
OPEN
SIG
NAL
VALVE
(2)
INTERM
ED
IATE
PRESSU
RE
SW
ITCH
,250V
4A,
SPN
OEx
dII
17

RE
LIE
FV
ALV
EU
NIT
Air
inle
t
PU
RG
EO
UT
LET
VA
LVE
open
sign
al
Mea
surin
gpo
intf
orflo
wof
purg
eai
r
Air
outle
t
MO
TO
RC
OO
LER
MO
TO
R
Mea
surin
gpo
intf
orm
inim
umpr
essu
re
MIN
IPU
RG
E
PU
RG
EA
IRD
IST
RIB
UT
ION
AS
RE
QU
IRE
D
FLA
TN
ES
ST
OB
ELE
SS
TH
AN
0.4
mm
OV
ER
AN
Y100m
mLE
NG
TH
UN
SP
EC
IFIE
D
TO
LE
RA
NC
ES
MA
TE
RIA
L
DR
'WN
AP
P'D
CH
K'D
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.N
o:
DA
TE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CT
ION
DIM
EN
SIO
NS
INm
m
DO
NO
TS
CA
LE
Exp
oT
ech
no
log
ies
Lim
ited
JO
BN
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No.
OF
SU
RR
EY
TW
16
5D
B
UN
ITE
DK
ING
DO
M
DR
AW
ING
No.
SC
ALE
The
conte
nts
ofth
isdra
win
g/docum
entare
Copyrightã
Expo
Technolo
gie
sLim
ited.
They
are
tobe
treate
das
confidentialand
are
retu
rnable
upon
request.
They
are
notto
be
copie
dor
com
munic
ate
din
part
or
inw
hole
withoutw
ritten
consentfr
om
Expo
Technolo
gie
sLim
ited,neither
are
they
tobe
used
inany
way
again
stour
inte
rests
.
NO
DE
CP
LA
CE
±0.5
1D
EC
PLA
CE
±0.2
2D
EC
PLA
CE
±0.1
PO
WE
RIN
TE
RLO
CK
cont
acts
INT
ER
ME
DIA
TE
PR
ES
SU
RE
cont
acts
ALA
RM
/PR
ES
SU
RIZ
ED
cont
acts
RE
FE
RT
O
CIR
CU
ITD
IAG
RA
M
SY
ST
EM
PU
RG
ING
cont
acts
(OP
TIO
NA
L)
Ens
ure
outle
tis
noto
bstr
ucte
d
BO
OS
TA
IR
CO
NT
RO
L
UN
IT
HIG
HP
RE
SS
UR
Eco
ntac
ts(O
PT
ION
AL)

SU
PPLY
4-8
barg
INSTRU
MEN
T
AIR
/IN
ERT
GAS
1/2
"N
PT
H H
MO
TO
REN
CLO
SU
RE
1/2
"[1
2m
m]
I.D
.M
INIM
UM
PU
RG
EO
UTLET
VALVE
OPEN
CO
NTRO
LSIG
NAL
1/2
"[1
2m
m]
I.D
.RECO
MM
EN
DED
MIN
IMU
MSIZ
EFO
RPU
RG
EAIR
DIS
TRIB
UTIO
NPIP
EW
ORK
AU
TO
MATIC
LEAKAG
ECO
MPEN
SATIO
NVALVE
MAN
UALLY
SET
PU
RG
EFLO
WCO
NTRO
LVALVE
1/8
"N
PT
MIN
IPU
RG
ECO
NTRO
LLO
GIC
XC
1/4
"[6
mm
]I.
D.
1/8
"N
PT
MO
TO
RIN
TERLO
CK
ALARM
/PRESSU
RIZ
ED
RELIE
FVALVE
ASSEM
BLY
XIPAL
PI
PU
RG
ING
/PU
RG
ECO
MPLETE
LO
WPRESSU
RE
ALARM
MIN
IPU
RG
ESYSTEM
EN
CLO
SU
RE
1/8
"N
PT
1/4
"[6
mm
]I.
D.
D.P
.H
IFRO
MRELIE
FVALVE
1/8
"N
PT
1/8
"N
PT
TEST
PO
INT
NO
RM
ALLY
PLU
GG
ED
1/2
"N
PT
ELECTRIC
AL
SIG
NAL
VIA
Ex
eJU
NCTIO
NBO
X
OPTIO
NAL
1/8
"N
PT
D.P
.LO
FRO
MRELIE
FVALVE
1/4
"[6
mm
]I.
D.
1/8
"N
PT
SYSTEM
PU
RG
ING
(OPTIO
NAL)
INTERM
ED
IATE
PRESSU
RE
ALARM
1/8
"N
PT
PRIM
ARY
EN
CLO
SU
RE
PRESSU
RE
1/4
"[6
mm
]I.
D.
FLA
TN
ES
ST
OB
ELE
SS
TH
AN
0.4
mm
OV
ER
AN
Y100m
mLE
NG
TH
UN
SP
EC
IFIE
D
TO
LE
RA
NC
ES
MA
TE
RIA
L
DR
'WN
AP
P'D
CH
K'D
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.N
o:
DA
TE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CT
ION
DIM
EN
SIO
NS
INm
m
DO
NO
TS
CA
LE
Exp
oT
ech
no
log
ies
Lim
ited
JO
BN
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No.
OF
SU
RR
EY
TW
16
5D
B
UN
ITE
DK
ING
DO
M
DR
AW
ING
No.
SC
ALE
The
conte
nts
ofth
isdra
win
g/docum
entare
Copyrightã
Expo
Technolo
gie
sLim
ited.
They
are
tobe
treate
das
confidentialand
are
retu
rnable
upon
request.
They
are
notto
be
copie
dor
com
munic
ate
din
part
or
inw
hole
withoutw
ritten
consentfr
om
Expo
Technolo
gie
sLim
ited,neither
are
they
tobe
used
inany
way
again
stour
inte
rests
.
NO
DE
CP
LA
CE
±0.5
1D
EC
PLA
CE
±0.2
2D
EC
PLA
CE
±0.1

FLA
TN
ES
ST
OB
ELE
SS
TH
AN
0.4
mm
OV
ER
AN
Y100m
mLE
NG
TH
UN
SP
EC
IFIE
D
TO
LE
RA
NC
ES
MA
TE
RIA
L
DR
'WN
AP
P'D
CH
K'D
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.N
o:
DA
TE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CT
ION
DIM
EN
SIO
NS
INm
m
DO
NO
TS
CA
LE
Exp
oT
ech
no
log
ies
Lim
ited
JO
BN
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No.
OF
SU
RR
EY
TW
16
5D
B
UN
ITE
DK
ING
DO
M
DR
AW
ING
No.
SC
ALE
The
conte
nts
ofth
isdra
win
g/docum
entare
Copyrightã
Expo
Technolo
gie
sLim
ited.
They
are
tobe
treate
das
confidentialand
are
retu
rnable
upon
request.
They
are
notto
be
copie
dor
com
munic
ate
din
part
or
inw
hole
withoutw
ritten
consentfr
om
Expo
Technolo
gie
sLim
ited,neither
are
they
tobe
used
inany
way
again
stour
inte
rests
.
NO
DE
CP
LA
CE
±0.5
1D
EC
PLA
CE
±0.2
2D
EC
PLA
CE
±0.1

NO
TES
REFER
TO
CERTIF
ICATES
IECEx
10.0
003X
AN
DIT
S10ATEX37092X
FO
RRESTRIC
TIO
NS
AN
DPERM
ITTED
CO
NTEN
TS
FLA
TN
ES
ST
OB
ELE
SS
TH
AN
0.4
mm
OV
ER
AN
Y100m
mLE
NG
TH
UN
SP
EC
IFIE
D
TO
LE
RA
NC
ES
MA
TE
RIA
L
DR
'WN
AP
P'D
CH
K'D
DR
AW
ING
ST
AT
US
:
AP
PR
OV
ED
:
MO
D.N
o:
DA
TE
:
ISS
UE
:
3rd
AN
GLE
PR
OJE
CT
ION
DIM
EN
SIO
NS
INm
m
DO
NO
TS
CA
LE
Exp
oT
ech
no
log
ies
Lim
ited
JO
BN
o:
FIN
ISH
TIT
LE
CU
ST
OM
ER
:S
HE
ET
No.
OF
SU
RR
EY
TW
16
5D
B
UN
ITE
DK
ING
DO
M
DR
AW
ING
No.
SC
ALE
The
conte
nts
ofth
isdra
win
g/docum
entare
Copyrightã
Expo
Technolo
gie
sLim
ited.
They
are
tobe
treate
das
confidentialand
are
retu
rnable
upon
request.
They
are
notto
be
copie
dor
com
munic
ate
din
part
or
inw
hole
withoutw
ritten
consentfr
om
Expo
Technolo
gie
sLim
ited,neither
are
they
tobe
used
inany
way
again
stour
inte
rests
.
NO
DE
CP
LA
CE
±0.5
1D
EC
PLA
CE
±0.2
2D
EC
PLA
CE
±0.1
ALARM
/PRESSU
RIS
ED
CO
NTACTS
BLACK
101
MO
TO
RIN
TERLO
CK
CO
NTACTS
BROWN
103
GREY
102
108
107
BLACK
BLUE
110
GREY
109
BROWN
INTERM
ED
IATE
PRESSU
RE
SW
ITCH
BLACK
BROWN
GREY
BLACK
BROWN
GREY
104
105
106
111
112
113
PN
EU
MATIC
TIM
ER
XBR-7
TD
0-0
60
CIR
CU
ITD
IAG
RAM
VERSIO
N
(OPTIO
NAL)
SYSTEM
PU
RG
ING
CO
NTACTS
ELECTRO
NIC
TIM
ER
XBR-7
TD
0-0
71

FLA
TNE
SS T
O B
E LE
SS
THAN
0.4
mm
OVE
R A
NY
100m
m L
ENG
TH
UN
SPE
CIF
IED
TOLE
RAN
CES
MA
TER
IAL
DR'W
N
APP'
D
CHK'
D
DR
AWIN
G S
TATU
S:A
PPR
OVE
D:
MO
D. N
o:D
ATE
:
ISSU
E:
3rd
ANG
LEP
RO
JEC
TIO
ND
IMEN
SIO
NS
IN m
m
DO
NO
T SC
ALE
Expo
Tec
hnol
ogie
s Li
mite
d
JOB
No:
FIN
ISH
TITL
E
CU
STO
MER
:S
HEE
T N
o.O
F
SU
RR
EY
KT7
0R
HU
NIT
ED
KIN
GD
OM
DR
AWIN
G N
o.
SC
ALE
The
cont
ents
of t
his
draw
ing
/ doc
umen
t are
Cop
yrig
ht �
Exp
o Te
chno
logi
es L
imite
d. T
hey
are
to b
e tre
ated
as
conf
iden
tial a
nd a
re re
turn
able
upon
requ
est.
The
y ar
e no
t to
be c
opie
d or
com
mun
icat
ed in
par
t or i
n w
hole
with
out w
ritte
n co
nsen
t fro
m E
xpo
Tech
nolo
gies
Lim
ited,
nei
ther
are
they
to b
e us
ed in
any
way
aga
inst
our
inte
rest
s.
NO
DEC
PLA
CE
±0.
51
DE
C P
LAC
E ±0
.22
DE
C P
LAC
E ±0
.1
MA
NU
AL O
VE
RR
IDE
SW
ITC
H S
UPP
LIED
LO
OS
E.
GLA
ND
PLA
TE IN
PU
RG
E S
YSTE
M IS
UN
DR
ILLE
D.
CA
BLE
GLA
ND
S A
RE
NO
T S
UPP
LIE
D.
* TE
RM
INA
L N
UM
BE
R A
CC
OR
DIN
G T
O M
OTO
R S
YS
TEM


Sira
Cer
tific
atio
n Se
rvic
e R
ake
Lan
e,
Eccle
sto
n, C
he
ste
r, C
H4
9JN
, E
ngla
nd
Te
l:+
44 (
0)
12
44
670
90
0
Fax:
+4
4 (
0)
12
44
681
33
0
Em
ail:
info
@sira
cert
ific
ation
.co
mW
eb:
ww
w.s
ira
cert
ific
ation
.co
m
CE
RT
IF
IC
AT
IO
N
Proj
ect
Num
ber
7000
4712
C El
laby
D
eput
y Ce
rtifi
catio
n M
anag
er
This
cer
tific
ate
and
its s
ched
ules
may
onl
y be
re
prod
uced
in it
s en
tiret
y an
d w
ithou
t ch
ange
.
Page
1 o
f 6
Form
9400
Iss
ue 1
1EC
TY
PE-
EXA
MIN
ATI
ON
CER
TIFI
CA
TE2
Equi
pmen
t in
tend
edfo
rus
e in
Pot
entia
lly E
xplo
sive
Atm
osph
eres
Dire
ctiv
e94
/9/E
C
3Ce
rtifi
cate
Num
ber:
Sir
a 99
ATE
X31
73X
Issu
e:11
4Eq
uipm
ent:
BP
G R
ang
e o
f Ju
ncti
on
Box
es
5Ap
plic
ant:
AB
TEC
HLi
mit
ed
6Ad
dres
s:Sa
nder
son
Stre
etLo
wer
Don
Val
ley
Shef
field
S92U
AU
K
7Th
iseq
uipm
ent
and
any
acce
ptab
leva
riatio
nth
eret
ois
spec
ified
inth
esc
hedu
leto
this
cert
ifica
tean
dth
e do
cum
ents
the
rein
ref
erre
d to
.
8Si
raCe
rtifi
catio
nSe
rvic
e,no
tifie
dbo
dynu
mbe
r05
18in
acco
rdan
cew
ithAr
ticle
9of
Dire
ctiv
e94
/9/E
Cof
23M
arch
1994
,cer
tifie
sth
atth
is e
quip
men
t ha
s be
enfo
und
to c
ompl
y w
ith t
he E
ssen
tial H
ealth
and
Safe
tyRe
quire
men
tsre
latin
gto
the
desi
gnan
dco
nstr
uctio
nof
equi
pmen
tin
tend
edfo
rus
ein
pote
ntia
lly e
xplo
sive
atm
osph
eres
giv
en in
Ann
ex I
I to
the
Dire
ctiv
e.
The
exam
inat
ion
and
test
res
ults
are
rec
orde
d in
the
con
fiden
tial r
epor
ts li
sted
inSe
ctio
n14
.2.
9Co
mpl
ianc
ew
ithth
eEs
sent
ial
Hea
lthan
dSa
fety
Requ
irem
ents
,w
ithth
eex
cept
ion
ofth
ose
liste
din
the
sche
dule
to
this
cer
tific
ate,
has
bee
n as
sure
d by
com
plia
nce
with
the
fol
low
ing
docu
men
ts:
EN 6
0079
-0:2
012
EN 6
0079
-7:2
007
EN 6
0079
-11:
2012
EN
600
79-2
6:20
07
EN 6
0079
-31:
2009
The
abov
elis
tof
docu
men
tsm
ayde
tail
stan
dard
sth
atdo
not
appe
aron
the
UKA
SSc
ope
ofAc
cred
itatio
n,bu
tha
vebe
enad
ded
thro
ugh
Sira
’s fl
exib
le s
cope
of a
ccre
dita
tion,
whi
ch is
ava
ilabl
e on
req
uest
.
10If
the
sign
‘X’i
spl
aced
afte
rth
ece
rtifi
cate
num
ber,
itin
dica
tes
that
the
equi
pmen
tis
subj
ect
tosp
ecia
lco
nditi
ons
for
safe
use
spec
ified
in t
he s
ched
ule
to t
his
cert
ifica
te.
11Th
isEC
type
-exa
min
atio
nce
rtifi
cate
rela
tes
only
toth
ede
sign
and
cons
truc
tion
ofth
esp
ecifi
edeq
uipm
ent.
Ifap
plic
able
, fu
rthe
rre
quire
men
tsof
this
Dire
ctiv
eap
ply
toth
em
anuf
actu
rean
dsu
pply
ofth
is e
quip
men
t.
12Th
e m
arki
ngof
the
equ
ipm
ent
shal
l inc
lude
the
follo
win
g:
II2
GD
orII
1G
DEx
e I
ICT6
Gb
(Ta
=-6
5°C
to+
#°C
)Ex
ia I
ICT6
Ga
(Ta
= -
65°C
to+
#°C
)Ex
e I
ICT5
Gb
(Ta
=-6
5°C
to+
#°C
)Ex
ia I
ICT5
Ga
(Ta
= -
65°C
to+
#°C
)Ex
e I
ICT4
Gb
(Ta
=-6
5°C
to+
#°C
)Ex
ia I
ICT4
Ga
(Ta
= -
65°C
to+
#°C
)Ex
ib I
IC T
6G
b(T
a=
-65°
C to
+#
°C)
Ex t
a II
ICT8
5°C
Da
(Ta
=-6
5°C
to+
#°C
Ex ib
IIC
T5
Gb
(Ta
=-6
5°C
to+
#°C
)Ex
ta
IIIC
T100
°C D
a (T
a=
-65°
C to
+#
°CEx
ib I
IC T
4G
b(T
a=
-65°
C to
+#
°C)
Ex t
b II
IC T
85°C
Db
(Ta
= -
65°C
to+
#°C
Ex t
b II
IC T
100°
CD
b(T
a =
-65
°C to
+#
°C
Sira
Cer
tific
atio
n Se
rvic
e R
ake
Lan
e,
Eccle
sto
n, C
he
ste
r, C
H4
9JN
, E
ngla
nd
Te
l:+
44 (
0)
12
44
670
90
0
Fax:
+4
4 (
0)
12
44
681
33
0
Em
ail:
info
@sira
cert
ific
ation
.co
mW
eb:
ww
w.s
ira
cert
ific
ation
.co
m
CE
RT
IF
IC
AT
IO
N
SCH
EDU
LE
EC T
YP
E-EX
AM
INA
TIO
N C
ERTI
FIC
ATE
Sir
a 99
ATE
X31
73X
Issu
e 11
This
cer
tific
ate
and
its s
ched
ules
may
onl
y be
re
prod
uced
in it
s en
tiret
y an
d w
ithou
t ch
ange
.
Page
2 o
f 6
Form
9400
Iss
ue1
13D
ESC
RIP
TIO
NO
FEQ
UIP
MEN
T
The
BPG
rang
eof
junc
tion
boxe
sut
ilise
sa
BPG
encl
osur
eco
vere
dby
cert
ifica
tenu
mbe
rSi
ra 9
9ATE
X317
2U a
nd a
refit
ted
with
an
arra
ngem
ent
of s
uita
bly
cert
ified
ter
min
als.
BPG
ref.
12
34
56
78
910
1112
1313
.5
1415
Leng
th80
110
160
190
230
122
220
160
260
360
560
255
400
400
600
400
Wid
th75
7575
7575
120
120
160
160
160
160
250
250
250
250
405
Hei
ght
5555
5555
5590
9090
9090
9012
012
016
012
012
0(A
ll di
men
sion
s ar
e in
mm
)
Befo
reth
eJu
nctio
nBo
xis
inst
alle
d,its
tota
ldis
sipa
ted
pow
erfo
rth
epa
rtic
ular
appl
icat
ion
will
beca
lcul
ated
inac
cord
ance
with
EN 6
0079
-7:2
003,
Anne
xE,
E.2
and
will
note
xcee
dth
eva
lues
give
nin
the
tabl
esbe
low
(Jun
ctio
nbo
xes
ofsi
zeno
tsp
ecifi
edin
the
tabl
esm
aybe
man
ufac
ture
dsu
bjec
tto
the
max
imum
diss
ipat
edpo
wer
bein
g ba
sed
ona
smal
ler
encl
osur
e):
EPL
Ga
Gb
Db
BPG
ref
.M
axim
um P
ower
Dis
sipa
tion
(W)
T6/T
85°C
Ta+
40°C
(max
)
T6/T
85°C
Ta+
55°C
(max
)
T6/T
85°C
Ta+
60°C
(max
)
T6/T
85°C
Ta+
65°C
(max
)
T5/T
100°
CTa
+55
°C(m
ax)
T4/T
100°
CTa
+90
°C(m
ax)
18.
390
2.23
1.73
1.45
8.39
08.
390
28.
551
2.00
1.70
1.45
8.55
18.
551
38.
833
2.00
1.70
1.45
8.83
38.
833
49.
012
2.07
1.80
1.29
9.01
29.
012
59.
260
2.00
1.70
1.10
9.26
09.
260
69.
378
2.00
1.70
1.45
9.37
89.
378
710
.500
2.30
1.70
1.10
10.5
0010
.500
810
.348
2.00
1.70
1.10
10.3
4810
.348
911
.933
2.30
1.70
1.10
11.9
3311
.933
1013
.793
4.50
3.29
2.10
13.7
9313
.793
1118
.338
6.68
5.20
4.00
18.3
3818
.338
1215
.474
2.30
1.70
1.10
15.4
7415
.474
1320
.867
5.20
4.00
3.00
20.8
6720
.867
13.5
20.8
675.
204.
003.
0020
.867
20.8
6714
30.3
847.
976.
594.
7930
.384
30.3
8415
31.3
508.
266.
004.
4031
.350
31.3
50

Sira
Cer
tific
atio
n Se
rvic
eR
ake
Lan
e,
Eccle
sto
n, C
he
ste
r, C
H4
9JN
, E
ngla
Te
l:+
44 (
0)
12
44
670
90
0
Fax:
+4
4 (
0)
12
44
681
33
0
Em
ail:
info
@sira
cert
ific
ation
.co
mW
eb:
ww
w.s
ira
cert
ific
ation
.co
m
CE
RT
IF
IC
AT
IO
N
SCH
EDU
LE
EC T
YP
E-EX
AM
INA
TIO
N C
ERTI
FIC
ATE
Sir
a 99
ATE
X31
73X
Issu
e 11
This
cer
tific
ate
and
its s
ched
ules
may
onl
y be
re
prod
uced
in it
s en
tiret
y an
d w
ithou
t ch
ange
.
Page
3 o
f 6
Form
9400
Iss
ue1
EPL
Da
BPG
ref
.M
axim
um P
ower
Dis
sipa
tion
(W)
T6/T
85°C
Ta+
40°C
(max
)
T6/T
85°C
Ta+
55°C
(max
)
T6/T
85°C
Ta+
60°C
(max
)
T6/T
85°C
Ta+
65°C
(max
)
T5/T
100°
CTa
+55
°C(m
ax)
T4/T
100°
CTa
+90
°C(m
ax)
14.
195
1.11
50.
865
0.72
54.
195
4.19
52
4.27
551
0.85
0.72
54.
2755
4.27
553
4.41
651
0.85
0.72
54.
4165
4.41
654
4.50
61.
035
0.9
0.64
54.
506
4.50
65
4.63
10.
850.
554.
634.
636
4.68
91
0.85
0.72
54.
689
4.68
97
5.25
1.15
0.85
0.55
5.25
5.25
85.
174
10.
850.
555.
174
5.17
49
5.96
651.
150.
850.
555.
9665
5.96
6510
6.89
652.
251.
645
1.05
6.89
656.
8965
119.
169
3.34
2.6
29.
169
9.16
912
7.73
71.
150.
850.
557.
737
7.73
713
10.4
335
2.6
21.
510
.433
510
.433
513
.510
.433
52.
62
1.5
10.4
335
10.4
335
1415
.192
3.98
53.
295
2.39
515
.192
15.1
9215
15.6
754.
133
2.2
15.6
7515
.675
Var
iati
on 1
-Th
isva
riatio
n in
trod
uced
the
follo
win
gch
ange
s:
i.Th
eBP
Gra
nge
of ju
nctio
nbo
xes
wer
epe
rmitt
edto
have
alte
rnat
ive
pow
erdi
ssip
atio
nra
tings
that
enab
leth
emto
beus
edin
anup
per
ambi
ent
tem
pera
ture
ofei
ther
+40
°Cor
+55
°Cor
+60
°Cor
+65
°C,t
he a
ssoc
iate
d ra
tings
and
mar
king
s w
ere
reco
gnis
ed.
Var
iati
on 2
-Th
isva
riatio
n in
trod
uced
the
follo
win
gch
ange
s:
i.Th
e re
cogn
ition
of a
min
orre
visi
onof
the
info
rmat
ion
mar
ked
on t
he la
bel.
Var
iati
on3
-Th
is v
aria
tion
intr
oduc
edth
e fo
llow
ing
chan
ges:
i.W
hen
cert
ified
,int
rinsi
cally
safe
term
inal
s ar
eus
ed,a
ltern
ativ
e m
arki
ng, ‘
ia’ a
nd ‘i
b’, w
as r
ecog
nise
d.
Var
iati
on 4
-Th
isva
riatio
n in
trod
uced
the
follo
win
gch
ange
s:
i.Th
eBP
G13
.5ju
nctio
nbo
xco
vere
dby
cert
ifica
tenu
mbe
rSi
ra99
ATEX
3172
Uw
asad
ded
toth
era
nge.
Var
iati
on 5
-Th
isva
riatio
n in
trod
uced
the
follo
win
gch
ange
s:
i.Th
e op
tion
tofit
slo
tted
tru
nkin
g in
side
the
Jun
ctio
n Bo
xes,
thi
s tr
unki
ng m
ay b
esi
ted
as r
equi
red.
Th
ein
stru
ctio
ns w
ere
mod
ified
to
reco
gnis
e ad
ditio
nal r
estr
ictio
ns a
ssoc
iate
d w
ithth
isch
ange
and
a
new
Con
ditio
n of
Man
ufac
ture
was
intr
oduc
ed.
ii.Th
e re
cogn
ition
of m
inor
dra
win
g m
odifi
catio
nsin
clud
ing
the
intr
oduc
tion
of a
new
com
pany
logo
;th
ese
amen
dmen
ts a
re a
dmin
istr
ativ
e or
invo
lve
chan
ges
to t
he d
esig
n th
at d
o no
t af
fect
the
aspe
cts
of t
he p
rodu
ct t
hat
are
rele
vant
to
expl
osio
n sa
fety
.
Sira
Cer
tific
atio
n Se
rvic
e R
ake
Lan
e,
Eccle
sto
n, C
he
ste
r, C
H4
9JN
, E
ngla
nd
Te
l:+
44 (
0)
12
44
670
90
0
Fax:
+4
4 (
0)
12
44
681
33
0
Em
ail:
info
@sira
cert
ific
ation
.co
mW
eb:
ww
w.s
ira
cert
ific
ation
.co
m
CE
RT
IF
IC
AT
IO
N
SCH
EDU
LE
EC T
YP
E-EX
AM
INA
TIO
N C
ERTI
FIC
ATE
Sir
a 99
ATE
X31
73X
Issu
e 11
This
cer
tific
ate
and
its s
ched
ules
may
onl
y be
re
prod
uced
in it
s en
tiret
y an
d w
ithou
t ch
ange
.
Page
4 o
f 6
Form
9400
Iss
ue1
Var
iati
on 6
-Th
isva
riatio
n in
trod
uced
the
follo
win
gch
ange
s:
i.Fo
llow
ing
appr
opria
tere
-ass
essm
ent
tode
mon
stra
teco
mpl
ianc
ew
ithth
ere
quire
men
tsof
the
EN60
079
serie
sof
stan
dard
s,th
edo
cum
ents
prev
ious
lylis
ted
inse
ctio
n9,
EN50
014:
1997
(am
endm
ents
A1to
A2),
EN50
019:
1994
,EN
5002
0:20
02an
dEN
5028
1-1-
1:19
98,w
ere
repl
aced
byth
ose
curr
ently
liste
d.As
part
ofth
isch
ange
,th
em
arki
ngs
inse
ctio
n12
wer
eup
date
dac
cord
ingl
yan
dth
e‘ia
’m
arki
ngpr
evio
usly
incl
uded
asVa
riatio
n1
(dat
ed30
Mar
ch20
05)
was
rem
oved
.ii.
The
Cond
ition
ofCe
rtifi
catio
nth
atde
fined
the
ambi
ent
tem
pera
ture
rang
eof
spec
ific
type
sof
gask
ets
was
rem
oved
beca
use
only
silic
one
rubb
erga
sket
sar
eno
wus
edin
the
cons
truc
tion
ofth
ese
Junc
tion
Boxe
s.iii
.It
was
reco
gnis
edth
ata
new
proc
edur
efo
rse
lect
ing
term
inal
sha
sbe
enad
opte
dby
the
man
ufac
ture
r;th
isal
low
sth
ete
rmin
als
tobe
chos
enfr
oman
Appr
oved
Com
pone
ntD
ocum
ent,
Sira
12AC
087,
that
isis
sued
and
cont
rolle
dby
Sira
.Th
ere
leva
ntCo
nditi
onof
Cert
ifica
tion
was
amen
ded
to r
ecog
nise
thi
sch
ange
.iv
.Th
ere
cogn
ition
ofdr
awin
gm
odifi
catio
nsre
quire
dfo
rus
ew
ithot
her
cert
ifica
tion
asso
ciat
edw
ithth
ese
prod
ucts
.v.
The
Cond
ition
of
Cert
ifica
tion
deal
ing
with
pow
er d
issi
patio
n w
as m
odifi
ed.
vi.
ACo
nditi
onof
Cert
ifica
tion
that
requ
ires
the
man
ufac
ture
rto
mon
itor
the
stat
usof
prev
ious
lyce
rtifi
ed d
evic
es w
as a
dded
.
Var
iati
on 7
-Th
isva
riatio
n in
trod
uced
the
follo
win
gch
ange
s:
R30
711A
/00
i.U
sing
EN60
079-
26,
the
junc
tion
boxe
sw
ere
allo
wed
tobe
mar
ked
with
‘Ex
ia’
and
‘Ex
ta’
conc
epts
for
EPL
leve
lsG
aan
dD
a,as
are
sult
ofth
isch
ange
,th
em
axim
umpo
wer
diss
ipat
ion
tabl
ew
asm
odifi
edan
da
Spec
ialC
ondi
tion
for
Safe
Use
was
intr
oduc
edne
cess
itatin
gth
ead
ditio
nof
an
‘X’ s
uffix
to
the
cert
ifica
te n
umbe
r.ii.
IEC
6007
9-0:
2011
was
rep
lace
d by
EN
6007
9-0:
2012
in t
he li
st o
f st
anda
rds.
R32
242A
/00
i.Th
eBP
Gra
nge
ofju
nctio
nbo
xes
wer
eal
low
edto
beus
edin
anup
per
ambi
ent
+55
°Cw
itha
tem
pera
ture
clas
s/su
rfac
ete
mpe
ratu
reof
T5/T
100°
C,th
eas
soci
ated
max
imum
pow
erdi
ssip
atio
nra
tings
(W
) an
d m
arki
ngs
wer
e re
cogn
ised
.
Var
iati
on 8
-Th
isva
riatio
n in
trod
uced
the
follo
win
gch
ange
s:
i.To
perm
itth
ere
plac
emen
tof
the
term
‘cer
amic
’w
ith‘th
ete
rmin
als
shal
lha
vean
insu
latio
nlim
iting
tem
pera
ture
of
130°
Cm
inim
um’i
nth
eCo
nditi
on o
fM
anuf
actu
re,
whe
n th
e ju
nctio
n bo
xes
are
mar
ked
for
T4/1
00°C
.
14D
ESC
RIP
TIV
E D
OC
UM
EN
TS
14.1
Dra
win
gs
Refe
r to
Cer
tific
ate
Anne
xe.

Sira
Cer
tific
atio
n Se
rvic
eR
ake
Lan
e,
Eccle
sto
n, C
he
ste
r, C
H4
9JN
, E
ngla
Te
l:+
44 (
0)
12
44
670
90
0
Fax:
+4
4 (
0)
12
44
681
33
0
Em
ail:
info
@sira
cert
ific
ation
.co
mW
eb:
ww
w.s
ira
cert
ific
ation
.co
m
CE
RT
IF
IC
AT
IO
N
SCH
EDU
LE
EC T
YP
E-EX
AM
INA
TIO
N C
ERTI
FIC
ATE
Sir
a 99
ATE
X31
73X
Issu
e 11
This
cer
tific
ate
and
its s
ched
ules
may
onl
y be
re
prod
uced
in it
s en
tiret
y an
d w
ithou
t ch
ange
.
Page
5 o
f 6
Form
9400
Iss
ue1
14.2
Ass
ocia
ted
Sir
aR
epo
rts
and
Cer
tifi
cate
His
tory
Issu
eD
ate
Repo
rt/F
ile n
o.Co
mm
ent
019
Jan
uary
2000
R51X
6055
ETh
e re
leas
e of
the
prim
e ce
rtifi
cate
.1
25 M
ay20
01R5
1A67
46A
The
intr
oduc
tion
of V
aria
tion
1.2
28 S
epte
mbe
r20
0153
V793
6Th
ein
trod
uctio
nof
Var
iatio
n 2.
323
Jul
y20
02R5
3A90
09A
The
prim
ece
rtifi
cate
was
re-is
sued
tope
rmit
the
follo
win
g:•
The
inco
rpor
atio
nof
pre
viou
s va
riatio
ns 1
and
2.
•Th
e lo
wer
am
bien
t te
mpe
ratu
re r
ange
was
con
firm
edas
–65
°C.
•Th
ein
trod
uctio
nof
the
chan
ges
incl
uded
in S
ira r
epor
tnu
mbe
r R5
3A90
09A.
430
Mar
ch20
05R5
3V10
438A
The
intr
oduc
tion
of V
aria
tion
3.5
10 M
arch
2008
R51A
1788
1ATh
isIs
sue
cove
rs t
he f
ollo
win
gch
ange
s:•
All p
revi
ousl
y is
sued
cer
tific
atio
n w
as r
atio
nalis
ed in
to
a si
ngle
cer
tific
ate,
Iss
ue 5
, Iss
ues
0 to
4 r
efer
ence
dab
ove
are
only
inte
nded
to
refle
ct t
he h
isto
ryof
the
prev
ious
cert
ifica
tion
and
have
not
bee
n is
sued
as
docu
men
ts in
thi
sfo
rmat
.•
The
chan
geof
the
App
lican
t’s n
ame,
firs
t re
cogn
ised
31 J
anua
ry20
07, w
as r
e-co
nfirm
ed.
•Th
ein
trod
uctio
nof
Var
iatio
n 4.
603
Apr
il20
12R2
6585
A/00
The
intr
oduc
tion
of V
aria
tion
5.7
11 J
une
2012
R265
85A/
01Re
port
R26
585A
/01
repl
aced
rep
ort
R26
585A
/00.
824
Oct
ober
2012
R251
64A/
00Th
isIs
sue
cove
rs t
he f
ollo
win
gch
ange
s:•
The
intr
oduc
tion
of V
aria
tion
6.•
Beca
use
this
cert
ifica
te w
as r
e-is
sued
,som
eVa
riatio
ns 1
and
2 w
ere
dupl
icat
ed, t
his
has
been
cl
arifi
ed a
nd r
efle
cted
in t
he c
ertif
icat
e hi
stor
y; n
o te
chni
cal c
hang
es w
ere
invo
lved
.9
07 A
pril
2014
R307
11A/
00R3
2242
A/00
The
intr
oduc
tion
of V
aria
tion
7.
1008
Jul
y20
14R7
0004
712A
The
intr
oduc
tion
of V
aria
tion
8.11
30 J
uly
2014
N/A
Issu
ed t
oco
rrec
t a
typo
grap
hica
l err
or.
15S
PEC
IAL
CO
ND
ITIO
NS
FO
R S
AFE
US
E (d
enot
ed b
y X
afte
r th
e ce
rtifi
cate
num
ber)
15.1
Whe
nus
edin
anEP
Lta
(Da)
appl
icat
ion
the
pow
ersu
pply
toth
eeq
uipm
ent
isto
bera
ted
for
apr
ospe
ctiv
esh
ort
circ
uit
curr
ent
ofno
t m
ore
than
10kA
.
16ES
SEN
TIA
LH
EALT
H A
ND
SA
FETY
REQ
UIR
EMEN
TS O
F A
NN
EXII
(EH
SRs)
The
rele
vant
EHSR
sth
atar
eno
tad
dres
sed
byth
est
anda
rds
liste
din
this
cert
ifica
teha
vebe
enid
entif
ied
and
indi
vidu
ally
asse
ssed
in t
he r
epor
ts li
sted
in S
ectio
n14
.2.
Sira
Cer
tific
atio
n Se
rvic
e R
ake
Lan
e,
Eccle
sto
n, C
he
ste
r, C
H4
9JN
, E
ngla
nd
Te
l:+
44 (
0)
12
44
670
90
0
Fax:
+4
4 (
0)
12
44
681
33
0
Em
ail:
info
@sira
cert
ific
ation
.co
mW
eb:
ww
w.s
ira
cert
ific
ation
.co
m
CE
RT
IF
IC
AT
IO
N
SCH
EDU
LE
EC T
YP
E-EX
AM
INA
TIO
N C
ERTI
FIC
ATE
Sir
a 99
ATE
X31
73X
Issu
e 11
This
cer
tific
ate
and
its s
ched
ules
may
onl
y be
re
prod
uced
in it
s en
tiret
y an
d w
ithou
t ch
ange
.
Page
6 o
f 6
Form
9400
Iss
ue1
17C
ON
DIT
ION
SO
FC
ERTI
FIC
AT
ION
17.1
The
use
of t
his
cert
ifica
te is
sub
ject
to
the
Reg
ulat
ions
Appl
icab
le t
o H
olde
rsof
Sira
Cer
tific
ates
.
17.2
Hol
ders
ofEC
type
-exa
min
atio
nce
rtifi
cate
sar
ere
quire
dto
com
ply
with
the
prod
uctio
nco
ntro
lre
quire
men
ts d
efin
ed in
Art
icle
8 o
f di
rect
ive
94/9
/EC.
17.3
Whe
nth
em
anuf
actu
rer
has
equi
pped
the
junc
tion
boxe
sw
ithte
rmin
als,
aro
utin
eel
ectr
icst
reng
thte
stsh
allb
eca
rrie
dou
ton
lyif
the
com
pone
nts
are
wire
d.Th
iste
stsh
allb
eca
rrie
dou
tac
cord
ing
toth
efo
llow
ing
stan
dard
s:
- in
dust
rial c
ontr
ol e
quip
men
t: E
N60
947
- m
easu
rem
ent,
con
trol
and
labo
rato
ry u
se:
EN61
010
17.4
The
term
inal
sus
edin
thes
eJu
nctio
nBo
xes
will
beAT
EXap
prov
edde
vice
sch
osen
from
the
Appr
oved
Com
pone
ntD
ocum
ent
num
ber
Sira
12AC
087
that
isis
sued
bySi
ra.
All
term
inal
sw
illbe
inst
alle
din
acco
rdan
cew
ithth
eir
cert
ifica
teco
nditi
ons
and
the
rele
vant
code
sof
pra
ctic
e/w
iring
regu
latio
nspa
ying
part
icul
ar a
tten
tion
to t
hefo
llow
ing:
•Th
e m
axim
um s
ervi
ce t
empe
ratu
re r
ange
. •
The
min
imum
cree
page
and
cle
aran
ce d
ista
nces
sha
llbe
mai
ntai
ned.
•Th
e ra
ted
volta
ges
and
curr
ents
may
var
y if
cros
s-co
nnec
tion
faci
litie
s ar
e us
ed.
•Th
e re
duct
ion
in r
atin
gof
adja
cent
ter
min
als
shal
l be
obse
rved
, whe
re a
pplic
able
.
The
term
inal
sfit
ted
into
the
junc
tion
boxe
ssh
all a
lso
conf
orm
to
the
follo
win
g re
quire
men
ts:
Tem
pera
ture
cla
ss/
Dus
t m
arki
ngRe
quire
men
t
T6/T
85°C
The
term
inal
ssh
all h
ave
an in
sula
tion
limiti
ng t
empe
ratu
re o
f10
0°C
min
imum
T4/T
100°
CTh
e te
rmin
als
shal
l hav
e an
insu
latio
n lim
iting
tem
pera
ture
of
130°
C m
inim
um
17.5
Suita
bly
cert
ified
Exe
equi
pmen
tsu
chas
brea
thin
gde
vice
san
dbl
anks
may
befit
ted
toth
een
clos
ure
prov
idin
g th
e en
clos
ure
mai
ntai
ns c
ompl
ianc
e w
ith B
SEN
605
29co
de I
P64
or b
ette
r.
17.6
The
man
ufac
ture
rw
illta
keal
lrea
sona
ble
step
sto
ensu
reth
atth
epo
wer
diss
ipat
edby
the
Junc
tion
Box
does
not
exce
edth
em
axim
umva
lue
stip
ulat
edin
the
tabl
ede
taile
din
the
Des
crip
tion
ofEq
uipm
ent,
inad
ditio
n,th
em
anuf
actu
rer
will
supp
lyal
lth
ere
leva
ntin
form
atio
nth
atw
illen
able
the
user
/inst
alle
rto
calc
ulat
eth
e di
ssip
ated
pow
erin
Wat
ts fo
r eac
hJu
nctio
n Bo
x in
acco
rdan
cew
ithEN
600
79-7
Anne
xE,
E2.
17.7
Whe
nth
eju
nctio
nbo
xes
are
used
for
intr
insi
cally
safe
appl
icat
ions
,a
3m
mse
para
tion
dist
ance
betw
een
the
encl
osur
eis
requ
ired,
ther
esh
all
also
bea
min
imum
of6
mm
betw
een
diff
eren
tin
trin
sica
lly s
afe
circ
uits
.
17.8
Whe
n tr
unki
ngis
fitt
ed, i
tm
ay b
e si
ted
as r
equi
red
and
the
min
imum
cree
page
and
clea
ranc
e di
stan
ces
shal
l stil
l be
met
.
17.9
The
prod
ucts
cove
red
byth
isce
rtifi
cate
inco
rpor
ate
prev
ious
lyce
rtifi
edde
vice
s,it
isth
eref
ore
the
resp
onsi
bilit
yof
the
man
ufac
ture
rto
cont
inua
llym
onito
rth
est
atus
ofth
ece
rtifi
catio
nas
soci
ated
with
thes
ede
vice
s,an
dth
em
anuf
actu
rer
will
info
rmSi
raof
any
mod
ifica
tions
ofth
ede
vice
sth
atm
ayim
ping
e up
on t
he e
xplo
sion
saf
ety
desi
gn o
f th
eir
prod
ucts
.

Sira
Cer
tific
atio
n Se
rvic
e R
ake
Lan
e,
Eccle
sto
n, C
he
ste
r, C
H4
9JN
, E
ngla
nd
Te
l:+
44 (
0)
12
44
670
90
0
Fax:
+4
4 (
0)
12
44
681
33
0
Em
ail:
info
@sira
cert
ific
ation
.co
mW
eb:
ww
w.s
ira
cert
ific
ation
.co
m
CE
RT
IF
IC
AT
IO
N
Cer
tifi
cate
An
nexe
Cer
tifi
cate
Num
ber
:S
ira
99A
TEX
3173
X
Equi
pmen
t:B
PG
Ran
ge
of
Junc
tio
nB
oxes
App
lican
t:A
BTE
CH
Lim
ited
This
cer
tific
ate
and
its s
ched
ules
may
onl
y be
re
prod
uced
in it
s en
tiret
y an
d w
ithou
t ch
ange
.
Page
1 o
f 1
Form
9400
Iss
ue 1
Issu
e0
to2:
The
draw
ings
ass
ocia
ted
with
the
se I
ssue
s w
ere
ratio
nalis
ed b
y th
ose
liste
d in
Iss
ue3.
Issu
e3
Num
ber
Shee
tRe
v.D
ate
Des
crip
tion
ABT
1026
01
of 1
C25
Jun
02Ex
tern
al L
abel
(BP
G)
ABT
1030
41
of 1
A16
Nov
99BP
G M
anuf
actu
ring
Spec
ifica
tion
Issu
e4
Num
ber
Shee
tRe
v.D
ate
Des
crip
tion
ABT
1484
21
of 1
-
01 F
eb05
BPG
Ran
ge E
Ex ia
Lab
el
ABT
1484
51
of 1
-
01 F
eb05
BPG
Ran
ge E
Ex ib
Lab
el
Issu
e5
:N
o ne
w d
raw
ings
wer
e in
trod
uced
.
Issu
e6
Dra
win
gSh
eets
Rev.
Dat
e(S
ira S
tam
p)Ti
tleAB
T10
260
1 of
1
D30
Mar
12BP
G E
xter
nal l
abel
–Ju
nctio
n Bo
xes
ABT
1030
41
of 1
B
30 M
ar12
BPG
Man
ufac
turin
gsp
ecifi
catio
nAB
T14
842
1 of
1
B30
Mar
12BP
G R
ange
EEx
ia L
abel
ABT
1484
51
of 1
B30
Mar
12BP
G R
ange
EEx
ib L
abel
Issu
e 7
(No
new
dra
win
gs w
ere
intr
oduc
ed.)
Issu
e8
Dra
win
gSh
eets
Rev.
Dat
e(S
ira S
tam
p)Ti
tleAB
T10
260
1 of
1
E30
Sep
12BP
GN
amep
late
–Ju
nctio
nBo
xAB
T10
304
1 of
1
C30
Sep
12BP
G M
anuf
actu
ring
spec
ifica
tion
ABT
1030
51
of 1
C
30 S
ep12
BPG
Ran
ge o
f Enc
losu
res
Issu
e9
R30
711A
/00
Dra
win
gSh
eets
Rev.
Dat
e(S
ira s
tam
p)Ti
tleAB
T102
601
of 1
F
30 O
ct13
BPG
Ran
ge E
x e
Labe
lAB
T148
421
of 1
C
10 O
ct13
BPG
Ran
ge E
x ia
Lab
el
R32
242A
/00
Dra
win
gSh
eets
Rev.
Dat
e(S
ira s
tam
p)Ti
tleAB
T265
281
of 1
A
19D
ec13
Exte
rnal
ATE
X La
bel (
BPG
)AB
T166
891
of 1
C
19D
ec13
BPG
Man
ufac
turin
gSp
ec
Issu
es 1
0 a
nd
11
(No
new
dra
win
gs w
ere
intr
oduc
ed.)

IEC
Ex
Cer
tific
ate
of C
on
form
ity
INT
ER
NA
TIO
NA
L E
LE
CTR
OT
EC
HN
ICA
L C
OM
MIS
SIO
NIE
C C
ertif
icat
ion
Sch
eme
for
Exp
losi
ve A
tmos
phe
res
for
rule
s a
nd
deta
ils o
f th
e I
EC
Ex S
ch
em
e v
isit w
ww
.iecex.c
om
Ce
rtific
ate
No.:
IEC
Ex S
IR 0
6.0
087
Xis
sue
No
.:5
Sta
tus:
Cur
rent
Da
te o
f Is
sue
:20
14-0
7-30
Pa
ge
1 o
f 4
Ap
plican
t:
Ele
ctr
ical A
ppa
ratu
s:
BP
G R
ange
of
Junc
tion
Bo
xes
Op
tiona
l acc
esso
ry:
Typ
e o
f P
rote
ction
:In
crea
sed
Saf
ety
and
Du
st
Mark
ing
:E
x e
IIC
T6
Gb (
Ta
-6
5°C
to +
#°C
)o
rE
x ia
IIC
T6
Ga
(T
a -
65°C
to +
#°C
)E
x e
IIC
T5
Gb (
Ta
-6
5°C
to +
#°C
)E
x ia
IIC
T5
Ga
(T
a -
65°C
to +
#°C
)E
x e
IIC
T4
Gb (
Ta
-6
5°C
to +
#°C
)E
x ia
IIC
T4
Ga
(T
a -
65°C
to +
#°C
)E
x ib
IIC
T6 G
b (
Ta -
65
°C to
+#°C
)E
x ta
III
C T
85°C
Da (
Ta
-65°C
to
+#
°CE
x ib
IIC
T5 G
b (
Ta -
65
°C to
+#°C
)E
x ta
III
C T
100°C
Da
(T
a -
65
°C t
o +
#°C
Ex ib
IIC
T4 G
b (
Ta -
65
°C to
+#°C
)E
x tb
III
C T
85
°C D
b (
Ta
-6
5°C
to +
#°C
)E
x tb
III
C T
10
0°C
Db (
Ta -
65
°C to
+#°C
)(T
em
pe
ratu
re c
lass,
mark
ing f
or
du
st a
nd
Ta
ma
xim
um
dep
en
ds u
po
n t
he
ma
xim
um
pow
er
dis
sip
atio
n,
refe
r to
An
ne
xe
)
Ap
prov
ed fo
r is
sue
on
beha
lf of
the
IEC
Ex
Ce
rtifi
catio
n B
ody:
C E
llaby
Po
sitio
n:
Dep
uty
Cert
ific
ation
Man
ag
er
Sig
nat
ure
:(f
or p
rinte
d ve
rsio
n)
Da
te:
1. T
his
ce
rtific
ate
an
d s
che
du
le m
ay o
nly
be
re
pro
duced
in f
ull.
2. T
his
ce
rtific
ate
is n
ot tr
an
sfe
rab
le a
nd r
em
ain
s t
he p
rope
rty o
f th
e issu
ing b
ody.
3. T
he
Sta
tus a
nd a
uth
en
ticity o
f th
is c
ert
ific
ate
may b
e v
erified b
y v
isitin
g th
e O
ffic
ial IE
CE
x W
ebsite.
Cert
ific
ate
issu
ed
by:
SIR
A C
erti
ficat
ion
Ser
vice
Rak
e L
ane
Ecc
lest
on
Ch
este
rC
H4
9JN
Un
ited
Kin
gd
om
Ce
rtific
ate
his
tory
:
Issu
e N
o. 5 (
20
14
-7-3
0)
Issu
e N
o. 4 (
20
14
-5-2
0)
Issu
e N
o.
3 (
20
14
-5-8
)Is
sue
No
. 2
(2
01
2-1
0-
25)
Issu
e N
o. 1 (
20
10
-7-2
7)
Issue
No
. 0
(2
00
6-1
0-
25)
AB
TEC
H L
imit
edA
B C
ontr
ols
& T
echn
olo
gy
San
de
rso
n S
tre
et
Low
er
Don
Va
lle
yS
he
ffie
ld S
9 2
UA
Un
ited
Kin
gdo
m
IEC
Ex
Cer
tifi
cate
of
Co
nfo
rmit
yC
ert
ific
ate
No.:
IEC
Ex S
IR 0
6.0
087
X
Da
te o
f Is
su
e:
2014
-07-
30Is
su
e N
o.:
5
Pag
e 2
of
4
Man
ufa
ctu
rer:
Ad
ditio
nal M
an
ufa
ctu
rin
g loca
tio
n(s
):
Th
is c
ert
ific
ate
is issue
d a
s v
eri
fica
tio
n t
ha
t a s
am
ple
(s),
rep
resen
tative
of p
rod
uction
, w
as a
ssessed
and
te
ste
d a
nd
fo
un
d to
com
ply
with t
he
IE
C S
tanda
rd lis
t be
low
and
th
at
the m
anu
factu
rer's
quality
syste
m,
rela
tin
g t
o t
he
Ex p
rod
ucts
covere
d b
y t
his
ce
rtific
ate
, w
as a
sse
sse
d a
nd f
ou
nd
to c
om
ply
with
th
e I
EC
Ex Qu
ality
syste
m r
equir
em
ents
. T
his
cert
ific
ate
is g
rante
d s
ub
ject
to th
e c
ond
itio
ns a
s s
et o
ut
in IE
CE
x S
che
me R
ule
s, IE
CE
x 0
2 a
nd
Op
era
tion
al D
ocu
men
ts
as a
men
ded
.
ST
AN
DA
RD
S:
Th
e e
lectr
ical ap
pa
ratu
s a
nd
any a
cce
pta
ble
va
ria
tion
s t
o it
sp
ecifie
d in
th
e s
che
du
le o
f th
is c
ert
ific
ate
and t
he
id
en
tifie
d
docum
ents
, w
as f
ou
nd
to
com
ply
with t
he
follow
ing s
tand
ard
s:
IEC
6007
9-0
: 201
1E
ditio
n:
6.0
Explo
siv
e a
tmo
sph
ere
s -
Part
0:
Gen
era
l require
me
nts
IEC
6007
9-1
1 : 2
011
Editio
n:
6.0
Explo
siv
e a
tmo
sph
ere
s -
Part
11
: Equ
ipm
ent p
rote
ctio
n b
y intr
insic
sa
fety
"i"
IEC
6007
9-3
1 : 2
008
Editio
n:
1
Explo
siv
e a
tmo
sph
ere
s –
Part
31:
Equip
men
t d
ust
ignitio
n p
rote
ctio
n b
y e
nclo
su
re 't'
IEC
6007
9-7
: 200
6-0
7E
ditio
n:
4
Explo
siv
e a
tmo
sph
ere
s -
Part
7:
Equip
men
t pro
tection
by in
cre
ase
d s
afe
ty "
e"
Thi
s C
ertif
icat
e d
oes
not
indi
cate
com
plia
nce
with
ele
ctric
al s
afet
y an
d p
erfo
rma
nce
req
uire
me
nts
othe
r th
an th
ose
ex
pres
sly
incl
uded
in t
he S
tan
dard
s lis
ted
abov
e.
TE
ST
& AS
SE
SS
ME
NT
RE
PO
RTS
:A
sa
mpl
e(s)
of t
he e
quip
me
nt li
sted
has
suc
cess
fully
met
the
exam
ina
tion
and
test
req
uire
me
nts
as r
eco
rded
in
Te
st R
epo
rt:
uality
Assessm
en
t R
epo
rt:
GB/S
IR/E
xT
R06
.010
1/01
GB/S
IR/E
xT
R12
.024
5/0
0G
B/S
IR/E
xT
R14
.01
07/0
0
GB/S
IR/QA
R06
.004
6/00
GB/S
IR/QA
R06
.00
46/0
1G
B/S
IR/QA
R0
6.0
046/0
2G
B/S
IR/QA
R06
.004
6/03
GB/S
IR/QA
R06
.00
46/0
4
AB
TE
CH
Lim
ited
A B
Co
ntr
ols
& T
echn
olo
gy
Sa
nd
ers
on S
tre
et
Lo
we
r D
on V
alle
yS
heff
ield
S9
2U
A
Un
ited
Kin
gd
om

IEC
Ex
Cer
tifi
cate
of
Co
nfo
rmit
yC
ert
ific
ate
No.:
IEC
Ex S
IR 0
6.0
087
X
Da
te o
f Is
su
e:
2014
-07-
30Is
su
e N
o.:
5
Pag
e 3
of
4
Sch
edul
e
EQU
IPM
EN
T:
Equ
ipm
ent
and
sys
tem
s co
vere
d b
y th
is c
ertif
ica
te a
re a
s fo
llow
s:
Th
e B
PG
Junction
Bo
xe
s c
om
pri
se a
poly
este
r, B
PG
En
clo
sure
, co
mpo
ne
nt
cert
ifie
d a
s I
EC
Ex S
IR 0
6.0
086
U, th
afitte
d w
ith
te
rmin
als
. R
efe
r to
cert
ific
ate
Ann
exe f
o a
full p
rodu
ct
de
scri
ptio
n.
CO
ND
ITIO
NS
OF C
ER
TIFIC
ATI
ON
:YE
S a
s sh
own
belo
w:
1.
Wh
en
use
d in a
n E
PL t
a (
Da)
ap
plication t
he
po
we
r sup
ply
to th
e equ
ipm
en
t is
to b
e r
ate
d f
or
a
pro
sp
ective s
hort
circuit c
urr
en
t o
f n
ot
more
tha
n 1
0 k
A.
IEC
Ex
Cer
tifi
cate
of
Co
nfo
rmit
yC
ert
ific
ate
No.:
IEC
Ex S
IR 0
6.0
087
X
Da
te o
f Is
su
e:
2014
-07-
30Is
su
e N
o.:
5
Pag
e 4
of
4
DE
TAIL
S O
F CE
RT
IFICA
TE
CH
AN
GE
S (fo
r is
sues
1 a
nd
above
):
Issu
e 1
–th
is Issue
in
tro
du
ced
th
e f
ollo
win
g c
han
ge
s:
1T
o a
llow
GB/S
IR/E
xT
R0
6.0
101/0
1 t
o r
ep
lace
GB/S
IR/E
xT
R06.0
10
1/00
Issu
e 2
–th
is Issue
in
tro
du
ced
th
e f
ollo
win
g c
han
ge
s:
1T
he
Descrip
tion
wa
s a
lign
ed w
ith
cert
ific
ate
no.
Sira
99A
TE
X3
17
3 a
ssocia
ted w
ith
th
is Ju
nctio
n B
ox,
this
in
clu
de
d r
ecog
nis
ing t
he
fo
llow
ing
cha
ng
es a
sse
sse
d a
s p
art
of
that
ce
rtific
ate
.*
Th
e B
PG
13
.5 e
nclo
sure
was a
dd
ed
to
th
e r
an
ge
.*
Th
e o
ption
to
fit s
lotte
d t
runkin
g in
sid
e th
e e
nclo
sure
s, th
is t
runkin
g m
ay b
e s
ited
as r
equir
ed
.T
he in
str
uction
s w
ere
mo
difie
d t
o r
eco
gn
ise a
dditio
na
l re
str
ictio
ns a
sso
cia
ted w
ith t
his
ch
an
ge
a
nd
a n
ew
Co
nd
itio
n o
f M
anu
factu
re w
as in
trodu
ce
d.
2Follow
ing
app
ropri
ate
re
-assessm
en
t to
dem
onstr
ate
com
plia
nce
with t
he
requ
ire
men
ts o
f th
e la
test
sta
nd
ard
s, th
e d
ocu
men
ts p
revio
usly
used
fo
r a
sse
ssm
en
t w
ere
re
pla
ced
by th
ose c
urr
ently lis
ted
, th
e
mark
ing
s w
ere
upd
ate
d a
ccord
ing
ly.
In a
dditio
n,
the e
nclo
sure
was a
llo
we
d t
o b
e u
sed f
or
intr
insic
ally
safe
app
lication
s a
nd I
EC
60
07
9-1
1:2
012
Ed
itio
n 6
wa
s in
clu
ded
in t
he
lis
t o
f sup
po
rtin
g s
tand
ard
s.
3T
he
Cond
itio
n o
f C
ert
ific
atio
n r
ela
ted t
o s
tatic w
as r
em
ove
d; in
add
itio
n th
e C
on
ditio
ns o
f M
anufa
ctu
re
we
re r
atio
na
lise
d t
o b
ring
th
em
into
lin
e w
ith
Sira
99
AT
EX
317
3.
4It
wa
s r
ecog
nis
ed
th
at
a n
ew
pro
cedu
re f
or
se
lectin
g t
erm
ina
ls h
as b
ee
n a
dop
ted b
y th
e m
anu
factu
rer;
this
allow
s the
te
rmin
als
to b
e c
ho
se
n f
rom
an
Ap
pro
ved
Co
mpo
ne
nt
Docu
me
nt,
Sira
12
AC
087
, th
at is
is
sue
d a
nd c
ontr
olle
d b
y S
ira.
Issu
e 3
–th
is Issue
in
tro
du
ced
th
e f
ollo
win
g c
han
ge
:
1Is
sue
d t
o c
orr
ect
the n
um
berin
g o
f th
e c
ha
ng
es in I
ssu
e 2
and
to e
dit c
han
ge
3.
GB/S
IR/E
xT
R14
.011
3/00
wa
s r
em
ove
d.
Issu
e 4
–th
is Issue
in
tro
du
ced
th
e f
ollo
win
g c
han
ge
:
1U
sin
g I
EC
60
07
9-2
6,
the ju
nctio
n b
oxes w
ere
allow
ed
to
be m
ark
ed
with ‘E
x ia’an
d ‘E
x ta
’co
nce
pts
for
EP
L leve
ls G
a a
nd D
a,
as a
re
su
lt o
f th
is c
ha
ng
e, th
e m
axim
um
po
wer
dis
sip
atio
n t
ab
le w
as m
od
ifie
d
and
a S
pecia
l C
on
ditio
n f
or
Sa
fe U
se
wa
s in
tro
du
ce
d n
ecessita
tin
g t
he a
dd
itio
n o
f a
n ‘X
’suff
ix to t
he
cert
ific
ate
num
ber.
2T
he
BP
G r
an
ge
of jun
ctio
n b
oxe
s w
ere
allow
ed t
o b
e u
se
d in a
n u
pp
er
am
bie
nt +
55°C
with
a
tem
pe
ratu
re c
lass/su
rfa
ce
te
mpe
ratu
re o
f T
5/T
10
0°C
, th
e a
sso
cia
ted
ma
xim
um
pow
er
dis
sip
ation
ra
tin
gs
(W)
and
mark
ing
s w
ere
re
cog
nis
ed.
Issu
e 5
–th
is Issue
in
tro
du
ced
th
e f
ollo
win
g c
han
ge
:
1Is
sue
d t
o c
orr
ect
a typo
gra
phic
al e
rro
r


[This Page Intentionally Left Blank]

Expo Technologies USAExpo Technologies Inc.
9140 Ravenna Road Unit #3Twinsburg,
OH 440878, USAT: +1 440 247 5314F: +1 330 487 0611
Expo Technologies UKExpo Technologies Ltd.
Unit 2 The Summit, Hanworth RoadSunbury-On-Thames,
TW16 5DB, UKT: +44 20 8398 8011F: +44 20 8398 8014
Expo Technologies ChinaQingdao Expo M&E Technologies Co. Ltd
329 Huashan Er LuJimo City, Qingdao,
266200 ChinaT: +86 532 8906 9858F: +86 532 8906 9858
www.expoworldwide.com