MODEL 1011 TYPE Z PURGE/PRESSURIZATION SYSTEM
PROCESS AUTOMATION
INSTALLATION AND OPERATION MANUAL
Model 1011 Installation and Operation Manual
2
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Table of Contents
Page 2 System Purpose and Description Purpose,Systemdescription,Importantnotes
Page 3 Identifying Your System Definesspecificfeaturesofthesystem
Page 3 General Information System&materialspecifications,System
accessories,Spareparts,Tools&testequipment
Page 4 Enclosure and Device Design Designrequirements,Adjacentenclosures,Device
ventilation,Temperaturelimitations
Page 5 Installation Overview Installationdiagram
Page 6 Getting Started Establishingconnectionsizes,Determiningenclosure
inlet&outletconnectionlocations
Page 7 System Mounting LH,RH,TM,BM&WMconfigurations,
FM&PMconfigurations
Page 8 Mounting Plate Dimensions Mountingplatedimensiondiagrams
Page 9 Hardware Mounting Optionalenclosureprotectionvent,Warning
nameplates
Page 10 Pneumatic Tubing Requirements Protectivegassupplyrequirements,Pneumatic
connectionrequirements
Page 11 Tubing Installation LH,RH,TM,BM,WM,FM&PMtubing
configurations
Page 12 Tubing Connection Diagrams LH,RH,TM,BM,WM,FM,&PMconfiguration
connectionpoints,Pneumaticdiagram
Page 13 Electrical Supply Requirements Wiringrequirements,Enclosurepower&alarmsignal,
Enclosurewiringmethods&connections
Page 14 Set-Up Procedure ClassI&ClassIIset-up
Page 15 Operating Sequence ClassI&ClassIIoperation
Page 16 Troubleshooting Procedures Troubleshootingchart
Page 17 Warranty and Liability Statement Warrantynotes,Generalterms,Limitations
Page 18 System Maintenance Regularmaintenance,Long-termmaintenance,
Maintenanceschedule
Page 19 Systems Identification & Application Information
Purpose and Description
PurposePepperl+FuchsEnclosureProtectionSystem’spurposeistoallowtheuseofgeneralpurposeornon-ratedelectricalorelectronicdevices,withexceptiontodeviceswhichproduceexcessiveheat,utilizecombustiblegas,orexposearcingcontactstothehazardousatmosphere,inType4or12enclosuresintheplaceofexplosionproofType7enclosures.Otherpurposesincludeheat,moistureanddustcontaminationprevention.
DescriptionModel1011isanenclosurepressurizationorpurgingsystemthatoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressurewithinsealed(protected)enclosures,topreventcombustibledustaccumulationorremoveandpreventflammablegasorvaporaccumulations.InClassIIareas,thesystemmaintainsa“safe”(1.0")pressure.InClassIareas,thesystemaccomplishesfourairexchangesandmaintainsa“safe”(0.25")pressure.Theseprocessesreducethehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4
Important NotesOne(1)permanentfilecopyandone(1)operationscopyofthisManualmustbestudiedandretainedbytheoperatorofthisSystem.User’sAgentsareresponsiblefortransferringthisManualtotheuser,priortostart-up.
Thecontentsofthismanualhavebeenarrangedtoallowtheuseofthisproductasastand-alonedeviceonequipmentandenclosuressuppliedbytheuseroritsagents.Themanual’sparametersencompassacombinationofbothNationalFireProtectionAssociation(NFPA)requirementsandPepperl+Fuchsrequirements.Pepperl+FuchsthereforeacknowledgestheuseofNFPA496asaguideline,thatwehaveenhancedcertainNFPArequirementsandthatadditionalinformationhasbeencompiledtocompletethisdocument.Themanualisintendedasacompleteguideandmustbeconsidered,unlessspecificallystatedotherwise,thatalldirectivescontainedhereinarePepperl+Fuchsrequirementsforsafe,practicalandefficientuseofthisproduct.
Thissystemisnotintendedforusetoprotectenclosuresordeviceswhichcontainignitableconcentrationsofgasesorvapors.Thisexclusiongenerallyappliestoprocessorproductanalyzingsystemsequipment.
All specifications are subject to change without notice.
Model 1011 Installation and Operation Manual
3
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Identifying Your System
Thisenclosureprotectionsystemisofferedinvariousstyles.Forproperinstallationandoperation,examinethesystemmodelnumbernameplatetoidentifythesystemstyle,areaclassification,andtype,asnotedbelow.
General Information
System SpecificationsSystemdimensions: SeePage8Shippingweight(lbs.): 7Operatingtemperaturerange: -20°F-120°FSupplypressurerange: *5-120psimax.Supplyrequirements: CleanairorinertgasSafepressure(CI/CII): 0.25"/1.0"Safepressureflowrate: **0.1-3.5SCFHSystemsupplyfitting: 1/4"tubefittingEnclosuresupplyfitting: 1/4"tubefittingEnclosurereferencefitting: 1/4"tubefitting* Withenclosureprotectionvent-120psimaximum Withoutenclosureprotectionven-5psimaximum
InordertocomplywiththeNFPA496standardrequiringprotectionagainstoverpressurizationoftheprotectedenclosure,theinstallermustinstalloneofthefollowingitemsinadditiontotheenclosureprotectionsystem.
a)Installanenclosureprotectionvenontheprotectedenclosure.
b)Installatamperproofregulatorupstreamoftheenclosureprotectionsystem'ssystemsupplyinlettopre-regulateprotectivegassupplyto5psimax.
Inaddition,forsmall,tightlysealedenclosures,ortocompensateforafluctuatingprotectivegassupply,itmaybenecessarytopre-regulatetheprotectivegassupplytoaconstant5psiregardlessofwhetheranenclosureprotectionvenisinstalled.Thiswillreducetheamountof"drifting"thatcannormallyoccurwhenmaintaininga"Safe"pressureinsideaprotectedenclosure.Thepre-regulationcanbeaccomplishedbyinstallingaTR-10Gtamperproofregulatoraccessoriesorequivalent.
**Enclosureintegritydeterminesactualflowrate
Material SpecificationsRegulatorbody: Zincw/enamelfinish,brassRegulatorhandle: PolycarbonateEnclosurepressuregauge: Alum.w/enamelfinishTubefittings: 316SSForgedbodyTubing: 316SS1/4".035weldedSystemnameplates: Silkscreen&Lexan®
Fastenerhardware: Aluminum&stainlesssteelMountingplate&bracket: AnodizedaluminumEnclosurewarningnameplate: SilkscreenedSSLexan®isaregisteredtrademarkoftheGeneralElectricCorporation
Recommended Spare PartsQty Description Part#(supercedes)1 Enclosurepressureindicator-CI 510023(001000)1 Enclosurepressureindicator-CII 513235(001027)1 Enclosurepressurecontrolregulator 513315(002000)1 Installation&operationmanual 129-02051 Enclosurewarningnameplate-CI 513008(EWN-1)1 Enclosurewarningnameplate-CII 513009(EWN-2)
Pleasecallandreferencepartnumberaboveforcurrentsparepartspricing.Immediatepricingisavailabletoallconfirmedcustomers.
Installation Tools & Testing Equipment1/2"chuckdrill
Completesetofdrillbits
1/2"conduitknockoutpunchor0.875"holesaw
Completesetoftubing,conduitbending,instrumentfittingandelectricalcraftsmanhandtools
0-250scfhflowmeter(connectedupstreamoftheprotectionsystemtodetermineairconsumptionandflowduringset-upprocedure)
1011 - CI - Z - UH - ##
Series Model NumberArea Classificatio CI - Class I Area CII - Class II AreaSystem Type Z - Div. 2 to NonhazardousMounting Configuratio UM - universal mount external surface FM - frame mount external frame or rack PM - panel mount enclosure surface cutout## - Additional factory installed accessories FM & PM confi uration mounting plates include four (4) 1/4" mounting holes at each corner, on 5/16" centers.
Confidential according to ISO 16016
sheet
respons.
approved
norm 3 of 5
scale: 1:1
Labels and Mounting Platefor MODEL 1011-CII Type Z
date: 2004-MAR-11Only valid as long as released in EDM or with a valid production documentation!
Twinsburg
125-0916change notice.
Dieses Dokument enthält sicherheitsrelevante Angaben. Es darf nicht ohne Absprache mit dem Normenfachmann geändert werden!
This document contains safety-relevant information. It must not be altered without the authorization of the norm expert!
TECHNICAL INFORMATION:
PLATE MATERIAL:
LABEL MATERIAL:
LABEL COLOR:
NOTE:
0.12” ALUMINUMN/A
WHITE BACKGROUND WITH BLACK COPY AND BORDERFULL INFORMATION PERTAINING TO PRINT FONTS,DIMENSIONS AND COLOR SCHEMES ARE CONTAINED INTHIS COREL DRAW (.CDR) FILENAME UNDER DRAWINGNUMBER 125-0916
US.JMB
US.SSJ
US.WDB
SCALE = 1X
All dimensions are in inches.All outside corners R=0.1
Tolerances: 2-place dec. +/- .01
1.00
2.50
10 CUBIC FEET MAXIMUM ENCLOSURE VOLUME
CLASS II, DIVISION 2, GROUPS F & G TO NONHAZARDOUS
10 CUBIC FEET MAXIMUM ENCLOSURE VOLUME
CLASS II, DIVISION 2, GROUPS F & G TO NONHAZARDOUS
Model 1011 CII Type Z
Model 1011 CII Type Z
PURGE CONTROL FOR USE
IN HAZARDOUS LOCATIONS
PURGE CONTROL FOR USE
IN HAZARDOUS LOCATIONS
CLASSIFIED BY UNDERWRITERS LABORATORIES INC.® IN ACCORDANCEWITH THE NATIONAL FIRE PROTECTION ASSOCIATION STANDARD FOR
PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL EQUIPMENTNFPA 496-1996
4S11
CLASSIFIED BY UNDERWRITERS LABORATORIES INC.® IN ACCORDANCEWITH THE NATIONAL FIRE PROTECTION ASSOCIATION STANDARD FOR
PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL EQUIPMENTNFPA 496-1996
4S11
C
LASSIFIE
D
®
C
LASSIFIE
D
®
SCALE = 2X
Released EDM checkout 2008-AUG-21
Model 1011 Installation and Operation Manual
4
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Model 1011 System AccessoriesOptional Enclosure Protection VentsEPV-1-SA-00 Straightw/sparkarrestorEPV-1-SA-90 Rtanglew/sparkarrestor
Additional ItemsSMK-1,or-4 SystemmountingkitEPSK-1 ClassI,GroupC-DpressureswitchkitEPSK-1A ClassI,GroupA-DpressureswitchkitEPSK-2 ClassII,GroupE-GpressureswitchkitGPSK-1 ClassI,general-purposeswitchkitGPSK-2 ClassII,general-purposeswitchkitRAH Div.1remotealarmhornRAB-1 Div.1remotealarmbeaconRAB-2 Div.2remotealarmbeaconLCK LfittingconduitkitTCK TfittingconduitkitTR-10G Tamperproofregulatorw/gaugeEFC-4 1/4"flushconnectorEBC-4 1/4"bulkheadconnectorEPC-10 1/2"pipeconnectorILF-4 1/4"filterETW Enclosuretemperaturewarning
Enclosure & Device Design
Enclosure Design Requirements1. Allwindowsmustbeshatterproofandsizedassmallas
possible.
2. AllNFPA496requiredmarkingsmustbeplacedonornearallenclosuredoorsandcovers.
3. Theenclosuremustwithstandaninternalpressureoften(10)inchesofwaterwithoutsustainingpermanentdeformationandresistallcorrosiveelementsinthesurroundingatmosphere.
4. Alllightweightobjectsintheenclosure,suchaspaperorinsulation,mustbefirmlysecured.
5. TheenclosureshouldbeconstructedfrommaterialssuchasmetalornonstaticpolycarbonatetomeetorexceedNEMA4or12performancerequirements,butdoesnotrequirethirdpartyapproval.
6. Theinstallationofobstructionsorotherbarriersthatblockorimpedetheflowofprotectivegasmustbeavoided.
7. Thecreationofairpocketsorotherareasthattrapflammablegaseswithintheenclosureordevicesmustbeavoided.
8. Theenclosureshouldbelocatedinanareawhereimpacthazardsareminimal.
9. Iftheenclosureisnonmetallicandcontainsequipmentthatutilizesorswitchespowerloadsgreaterthan2500VA,itmustbeconstructedfromsubstantiallynoncombustiblematerials,suchasmaterialsdesignedtomeetorexceedANSI/UL94ratingsof94V-0or945V.
Adjacent Enclosures1. Adjacentenclosuresmustbeprotectedbyoneofthe
followingmeans:
a) purgedorpressurizedinserieswiththeprotectedenclosure
b) purgedorpressurizedseparatelyor
c) protectedbyothermeans;e.g.,explosionproofenclosures,hermeticallysealeddevicesorintrinsicsafecircuits
2. Adjacentpurgedorpressurizedenclosuresmustbedesignedtomeetallconstructionrequirementsabove.
Total Volume Calculation1. Thetotalvolumeofallpressurizedenclosures,devicesand
wirewaysmustbeconsidered.
2. Allenclosure,device,andwirewayvolumesmustbecalculatedwithoutconsiderationofinternallyconsumedspace.
Device Ventilation1. Encloseddeviceswithintheprotectedenclosurethatdonot
exceed1.22in3offreevolumedonotrequireventilationtotheprotectedenclosure.
2. Ifthefreevolumeofaninternaldeviceexceeds1.22in3itmustbeprotectedbyoneofthefollowingmeans:
a) ventilatedonthetopandbottomsideswith1in2ofopeningforeach400in3ofvolumewithintheinternalprotectedenclosure,ataminimumdiameterof1/4"
b) purgedinserieswiththeprotectedenclosureorbepurgedseparatelyor
c) protectedbyothermeans;e.g.,explosionproofenclosures,hermeticallysealeddevices,orintrinsicsafecircuits.
Temperature Limitations1. Theenclosuremusthavenosurfaceareathatexceeds80
percentoftheflammableorignitablesubstance’sauto-ignitiontemperature.
2. Internaldevicesthatexceedthistemperaturemustbeprotectedbyoneofthefollowingmanners:
a) ThedeviceisenclosedinachamberthatisCULUSlistedasahermeticallysealeddevicethatprohibitstheentranceofaflammableorignitablesubstance,andmaintainsasurfacetemperaturebelowtemperaturelimits.
b) Itcanbeprovenbytestingthatthedeviceswillnotignitethesubstanceinvolved.
c) ThedeviceispurgedinaseparateenclosurethatbearsanETW(enclosuretemperaturewarningnameplate).Devicesmaybeaccessedonlyafterpowerhasbeenremovedandthedevicehasbeenallowedtocooltosafetemperature,ortheareaispositivelyknowntobenonhazardous.
Model 1011 Installation and Operation Manual
5
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Model 1002-WPS-LH Shown
Installation Overview
PROTECTIVE GAS SUPPLY
SYSTEM SUPPLY TUBING
ELECTRICAL ALARM WIRING CONDUIT & SEAL
SERVICE VALVE
SYSTEM SUPPLY FITTING
ENCLOSURE PROTECTION
SYSTEM
SYSTEM MOUNTING
BOLT
ENCLOSURE SUPPLY TUBING
ENCLOSURE PROTECTION
VENT
PROTECTED ENCLOSURE
ENCLOSURE CONNECTION
FITTINGS
ENCLOSURE REFERENCE
TUBING
ENCLOSURE WARNING
NAMEPLATE
Model 1011 Installation and Operation Manual
6
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Getting Started
Typical Single Protected Enclosure Connections
HELPFUL HINTSIfflammablegasesarelighterthanair,theinletconnectiontoeachenclosuremustenternearabottomcorner.Theoutletconnection,foranoptionalenclosureprotectionventorpipingtoanadjacentprotectedenclosure,mustexitnearanextremeoppositetopcorner.
Ifflammablegasesareheavierthanair,inletandoutletconnectionsmustbereversed.
Inallcases,themostprevalentgasmustdeterminethelocationofinletandoutletconnections.
Determining Enclosure Inlet & Outlet Connection Locations
HELPFUL HINTSToensureadequateprotectivegasflowtotheprotectedenclosure(s),allpipingandtubingmustbefullyreamed.
Precautionsmustbetakentopreventcrimpingandotherdamagetoprotectivegaspipingandtubing.
Whenprotectingmultipleenclosureswithasingleenclosureprotectionsystem,theenclosuresmustbeconnectedinseriesfromthesmallesttothelargesttoensureadequateprotectivegasflow.
PROTECTED ENCLOSURE
C
B
ENCLOSURE PROTECTION VENT(Optional)
E
SUPPLY
REFERENCE
1/2" PROTECTIVE GAS SUPPLY
HEADER
ENCLOSURE PROTECTION
SYSTEM
Maximum tubing / pipe pength and maximum number of bends / elbows
1/4"O.D.tubingfullyreamed
20feet10bends
1/4"O.D.tubingfullyreamed
Description
*Tubing or pipe diameter
Enclosure supply
System supply tubing
Enclosure reference
1/4"O.D.tubingfullyreamed
5feet5bends
20feet10bends
Multi - enclosure connections
1/2"I.D.pipefullyreamed
10feet5elbows
Optional remote venting
1/2"I.D.pipefullyreamed
30feet5elbows
A B EDC
ENCLOSURE PROTECTION
SYSTEM
PROTECTED ENCLOSURE
PROTECTED ENCLOSURE
D
SUPPLY
REFERENCE
B
TYPICAL MULTIPLE PROTECTED ENCLOSURE CONNECTIONS
1/2" PROTECTIVE GAS SUPPLY
HEADER
A
A
D
C
PROTECTED ENCLOSURE
*NOTE: Tube and pipe sizes are not equal in inside diameters. DO NOT substitute tube for pipe with same trade size.
INLET
INLET
Connectionsforheavierthanairgasesandvapors
OUTLET
OUTLET
Connectionsforlighterthanairgasesandvapors
Model 1011 Installation and Operation Manual
7
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
System Mounting
IMPORTANT NOTESThe system should be mounted at EYE LEVEL.
Care must be taken to ensure the system and all protruding components are clear of all enclosure accesses (doors and covers) and conduit, pipe, tubing or cable entries.
LH, RH, TM and BM configurations are intended for mounting adjacent to the protected enclosure.
Determine the mounting configuration for your application using the diagrams on page 8.
Remove and save the manila envelope (containing the enclosure warning nameplate) which may be taped to the System mounting bracket.
Although all systems are factory tested and calibrated, we strongly suggest a bench test of basic functions prior to installation.
Mounting LH, RH, TM, & BM Configurations1. Determinethemountingconfigurationforyourapplication
usingthediagramsonpage8.
2. Securethesystemmountingbrackettotheappropriateedgeofthesystemmountingplateusingthehexheadsetscrewsprovidedwiththesystem.
3.Transferholepatternofsystemmountingbrackettointendedsurface.
4. Checkforobstructionshinderingboltfastening,drillandreamthemountingholesbeforemountingthesystem.
5. Securethesystemtotheenclosure,orothermountingsurface,usingthefasteninghardwareprovided.
Mounting FM & PM Configurations1. CarefullyreadtheHELPFULHINTSlocatedbelow.
2. Transferpanelcutoutpatterntotheintendedsurface.
3. Checkforobstructionswhichcouldprohibitboltfasteningorsystempneumaticconnections.
4. Cutpanelcutoutpatternontheintendedsurface.
5. Deburrallcutoutsurfaces.
6. SecuresystemtoenclosureusingSMK-4,orequivalent1/4"x3/4"stainlesssteelnuts,bolts,mountingclipsandlockwashers.
HELPFUL HINTSFMandPMconfigurationsaredesignedtomountthroughapanelcutoutone(1)inchsmallerthantheoverallheightandwidthofthesystemmountingplate,usingclipsandfastenersprovidedwiththeSMK-4mountingkit.Thisdesignfeatureeliminatestheneedtodrillthesystemmountingboltholesintheprotectedenclosure.
FMconfigurationsareintendedformountingadjacenttotheprotectedenclosure.
PMconfigurationsareintendedformountingthroughacutoutintheprotectedenclosuresurface.
Typical Surface Mounted System(Model 1002-LPS-CI-Z-LH shown)
Typical Panel/Frame Mounted System(Model 1002-LPS-CI-Z-LH shown)
Model 1011 Installation and Operation Manual
8
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Mounting Plate Dimensions (continued)
8.25"
8"
8"
8.25"
8"
8.25"
8"
8"Panel Cutout7"
Panel Cutout7"
3.25" 1.25"
.6875"
7.3125"
8"
.875"2.4375"
.25" O.D.TYP 2
SystemMounting
Plate
8.25"
8"
1011-LH(Left hand configuration)
1011-RH(Right hand configuration)
1011-TM(Top mount configuration)
1011-BM(Bottom mount configuration)
1011-FM & 1011-PM(Frame & panel mount configuration)
Universal mounting bracket
Model 1011 Installation and Operation Manual
9
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Hardware Mounting
Optional Enclosure Protection VentAllconfigurationsmustbemountedinatrueverticalposition.
Theventmustbelocatedtoprovideaccessforroutinetestingofthevent’sflapperassembly.Aminimum8"clearanceisrequiredbelowtheventopening.
1. Determinethevent’smountingconfiguration,i.e.;-00verticalmountor-90sidemount.Seephotosbelow.
2.Determineventlocationandlayoutventmountingholeontheprotectedenclosure.(asdeterminedonpage6,“GettingStarted”)
3. Usinga0.875"holesawor1/2"conduitpunch,drillanddeburrtheenclosureprotectionventmountinghole.
4. Removethehubmountingnutfromtheventhubandplacethehub,withO-ringintact,throughthemountinghole.TheO-ringmustbeontheoutsideoftheprotectedenclosure.
5. Reinstallthehubmountingnuttothemountinghubfrominsidetheprotectedenclosureandtighten.
EPV - 1 - SA - 00Vertical Mount
EPV - 1 - SA - 90Side Mount
Warning Nameplate(s)AnEWN(enclosurewarningnameplate)mustbelocatedinaprominentpositiononornearallenclosureaccesses(doorsandcovers).
One(1)EWNisprovidedwitheachsystem,locatedinthemanilaenvelopetapedtothemountingflangeofthesystem.AdditionalEWNsareavailablefromPepperl+Fuchs.
AllEWNsprovidelabeledspacesallowingthecustomertomarktheprotectedenclosurewith:1)aTCode(temperatureidentificationnumber),2)Class,GroupandDivisionofsurroundingarea,and3)NFPApressurizationTypeX,YorZ,asmayberequiredbyplantandlocalcodesandisrequiredbyNFPA496.
AnETW(enclosuretemperaturewarningnameplate)mustbelocatedinaprominentpositiononornearallenclosureaccesses(doorsandcovers)whenthetemperatureofaninternalcomponentexceeds80percentoftheignitiontemperatureoftheflammablevapor,gasordustinvolved.
TheETWwarnstheoperatortodeenergizeallequipmentforaspecifiedlengthoftime,allowingtheprotectedequipmenttocoolbeforeopeningtheprotectedenclosure.Thelengthoftimerequiredisdeterminedbythecustomerandcanbefactoryorfieldengraved.
AllEWNsandETWsarefurnishedwithanadhesiveback,butshouldalsoberivetedorscrewedtotheprotectedenclosure.
Enclosure temperature warning nameplate
Enclosure warning nameplate - Class II
Enclosure warning nameplate - Class I
Model 1011 Installation and Operation Manual
10
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Pneumatic Tubing Requirements
Protective Gas Supply RequirementsTheprotectivegassupplytotheprotectionsystemmustbeaclean,instrumentqualitycompressedairornitrogenandmustcontainnomorethantraceamountsofflammablegas,vaporordust.
Theprotectivegassupplycompressorintakemustoriginateinanonhazardouslocation.Suctionductpassingthroughahazardouslocationandtheprotectionsystemtubingandpipingmustbefabricatedfromnoncombustiblematerialssuitableforprevailinghazardsandenvironmentalconditions.
Theprotectivegassupplymustoriginatefromadedicatedinstrumentqualitycompressedairheader(1/2"pipeorlarger),nofartherthantwenty(20)feetfromtheprotectionsystem.LocalcompressorsandgascylindersshouldnotbeusedbeforeconsultingwithPepperl+Fuchs.
Theprotectivegassupplytotheprotectionsystemmustbeequippedwithatamper-proofregulatorsetat5psimaximum.
Exception:Iftheprotectedenclosure(s)isequippedwithanEnclosureProtectionVent,theprotectivegassupplytotheprotectionsystemmustnotexceed120psimaximum,5psiminimum.(Seepage3,"SystemSpecifications"foradditionalinformationconcerningprotectivegassupplyrequirements.)
SC-4 NC-4
EBC-4EFC-4
EPC-10
SYSTEM SUPPLY FITTINGS
ENCLOSURE SUPPLY & REFERENCE FITTINGS
MULTIPLE ENCLOSURE CONNECTION FITTING
Pneumatic Connection RequirementsALLFITTINGSMAYBECUSTOMERORFACTORYFURNISHED
1. Forsystemsupply,one(1)SC-41/4"malestraightconnectororone(1)NC-41/4"maleelbowconnectororequivalentfittingpersystem.
NOTE: Above fitting is required only if protection system is furnished with an optional in-line filter kit (model ILFK) accessory.
One(1)similarfittingwhichwillconnecttheinertgassupplytubingtotheinertgassupplyheaderconnectionpointandone(1)lotof1/4"O.D.,.035"wallthickness,weldedorseamlessstainlesssteeltubing.
2. Forenclosuresupply,one(1)EFC-41/4"flushconnector,orone(1)EBC-41/4"feed-throughconnectororequivalentfittingpersystem.
3.Forenclosurereference,one(1)EFC-41/4"flushconnector,orone(1)EBC-41/4"feed-throughconnectororequivalentfittingpersystem.
4. One(1)lotof1/4"O.D.,.035"wallthickness,weldedorseamlessstainlesssteeltubing.
5. Formultipleenclosureconnections,two(2)EPC-101/2"pipemountinghubsorequivalentand1/2"150#ratedpipecouplings&unionsperinterconnection.
One(1)lot150#rating1/2"galvanizedoraluminumpipeandfittings,fullyreamedandunrestricted.
PM Pneumatic Connection RequirementsInadditiontoitemnumbers1,4,and5above,thefollowingfittingsarerequiredforallPMconfigurations.
1. ForsystemsupplyonPMconfigurations,one(1)additionalEBC-4orequivalent1/4"throughbulkheadfittingpersystemisrequired.
2. Foratmosphericreference,one(1)PRB-4orequivalent1/4"femalebulkheadfittingandstainlesssteelsinteredelementisrequired.
PRB-4SYSTEM ATMOSPHERIC REFERENCE FITTING
Model 1011 Installation and Operation Manual
11
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Tubing Installation
Tubing LH, RH, TM, BM & FM ConfigurationsSystem supply connections
1. Selectorinstallaprotectivegassupplyheadertap,fittedwiththepropertubesizefittingandlocatedwithintwenty(20)feetoftheenclosureprotectionsystem.
2. Ifaservicevalveisplacedbetweentheprotectivegassupplyheaderandtheenclosureprotectionsystem,itmustbeinstalledincloseproximityoftheprotectedenclosureandbelabeledinaccordancewithNFPA496.
3. Selecttheappropriatefittingsrequiredtoconnecttheprotectivegassupplytotheprotectionsystemregulatorasdeterminedonpage10,“PneumaticConnectionRequirements.”
4. Determineappropriatetubingroutefromtheprotectivegassupplyheadertotheprotectionsystemregulator.
5. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.
6. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingtoappropriatestructuralsupportsasrequired.
Enclosure supply & reference connections
1.Chooselocationfortheenclosuresupplyconnection(s)basedontherequirementsonpage6,“GettingStarted”.
2. Placetheenclosurereferenceconnectionfittingdirectlybehindtheenclosureprotectionsystemwheneverpossible.Forsystemsprotectingmultipleenclosuresinseries,theenclosurereferenceconnectionfittingmustbeplacedonthelastenclosureintheseries.Seepage6,“GettingStarted.”
3. Drillanddeburrenclosuresupplyandreferencefittingholesontheprotectedenclosure.Mountthefittings.
4. Determineappropriateroutefortheenclosuresupplyandreferencetubing.
5. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.
6. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingtoappropriatestructuralsupportsasrequired.
Tubing PM ConfigurationsEnclosure bulkhead fittings
1. Selectthefittingsrequiredtoinstallthesystemsupply,systemsupplybulkheadfittingandatmosphericreferencebulkheadfitting.Seepage11,“PneumaticTubingRequirements.”
2.Chooselocationforthesystemsupplybulkheadfitting.Thisfittingallowstheprotectivegassupplytopassthroughthewallofaprotectedenclosuretotheprotectionsystem’sregulatorsupplyinletconnection.
3. Chooselocationfortheatmosphericreferencebulkheadfitting.Thisfittingallowstheenclosurepressuregaugetoreferenceatmosphericpressure.
4. Drillanddeburrsystemsupplyandreferencebulkheadfittingholesintheprotectedenclosure.Mountthefittings.
System supply & reference connections
1. Selectorinstallaprotectivegassupplyheadertap,fittedwiththepropertubesizefittingandlocatedwithintwenty(20)feetoftheenclosureprotectionsystem.
2. Ifaservicevalveisplacedbetweentheprotectivegassupplyheaderandtheprotectionsystem,itmustbeincloseproximityoftheprotectedenclosureandlabeledinaccordancewithNFPA496.
3. Determineappropriatetubingroutefromtheprotectivegassupplyheadertothesystemsupplybulkheadfitting.
4. Determineappropriatetubingroutefromthesystemsupplybulkheadfittingtotheprotectionsystemregulator.
5. Determineappropriatetubingroutefromtheatmosphericreferencebulkheadfittingtotheenclosurepressuregauge’sreferenceinletconnection.
6. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.
7. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingasrequired.
HELPFUL HINTSAllworkmustbeperformedbytechniciansqualifiedinpneumatictubingandelectricalconduitinstallation.
Pepperl+Fuchsrecommendstheuseof.035"wallthickness,weldedorseamlessstainlesssteeltubing.
Ifflexibletubingisused,itmustbeinstalledinamannerthatprotectsitfromdamageandcorrosion.
Model 1011 Installation and Operation Manual
12
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Tubing Connection Diagrams
LH, RH, TM, BM & FM Configuration Connection Points & Pneumatic Diagram
PM Configuration Connection Points & Pneumatic Diagram
HELPFUL HINTPneumaticconnectionsarebolded.
Protectedenclosure
Optionalenclosureprotectionvent
Systemsupply
Venturiorifice
Inlet
Enclosurepressuregauge
Regulator
Sinteredvent Reference
Supply
Enclosurereferencebulkheadfitting
Enclosuresupplybulkheadfitting
Enclosurepressuregauge
Enclosurereference
inlet
Venturiorifice
Mountingbracket
System supply inlet
Enclosurepressurecontrol
regulator
Enclosure supply outlet
Mountingplate
Top Mount Configuration
Enclosurepressuregauge
Atmospheric reference
inlet
Mountingplate
Optionalenclosureprotectionvent
Protectedenclosure
System supply inlet
Enclosurepressurecontrol
regulator
Enclosure supply outlet
Systemsupply
InletSystemsupply
bulkhead
Atmosphericreferencebulkhead
Supply
Reference
Regulator
Enclosurepressuregauge
Sinteredvent
Model 1011 Installation and Operation Manual
13
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Electrical Supply Requirements
General Wiring RequirementsWARNING: THIS DEVICE CONTAINS ELECTRICAL PARTS THAT CAN CAUSE SHOCK OR INJURY
Allelectricalconnections,conduitandfittingsontheprotectedenclosuremustbesuitableforthehazardouslocationinwhichtheyareinstalled.Inaddition,allconduitandwiremustbeinstalledinaccordancewithNECasrequiredandallrelevantplantandlocalcodes.
Note:Donotusesealsonconduitusedasaprotected“wireway”tosupplyprotectivegastoadjacentprotectedenclosures.Thesameconduitcanbeutilizedforbothelectricalandpneumaticservicetoanadjacentprotectedenclosure(s),providedtheconduitisoversizedtoallowaminimumfreeclearanceequaltoorlargerthanthepipesizerequiredbetweenmultipleenclosuresasstatedonpage6,“GettingStarted.”
Enclosure Power RequirementsTheprotectedenclosure(s)electricalpowersourcemustoriginatefromacircuitbreakerorfuseddisconnectsuitableforthehazardouslocationinwhichitisinstalled.Theswitchmustbelocatedwithinfifty(50)feetoftheprotectedenclosure(s)andtheprotectionsystemandbeproperlymarked.
Alarm Signal RequirementsForTypeYandZpurgesystems,audiblealarmsorvisualindicatorsmustbeusedtonotifyoperatorsthatpressureinsidetheenclosureisbelowtheNFPAminimum.
Alarmsareconnecteddirectlytotheenclosureandmonitorthedifferentialairpressurebetweentheenclosureandtheenvironmentoutsideit.Thesealarmsareactivatedbythereductioninfloworpressurewithintheprotectiveenclosureandhaveadirectconnectiontotheenclosure,eliminatingtheneedforanalarmontheprotectivegassupply.
• Thealarmmustbelocatedwheretheoperatorcanseeiteasily.
• Thealarmmusttakeitsmeasurementfromtheenclosureonly.
• Alarmslocatedinthehazardousareamustberatedforthearea.
• Valvescannotbeconnectedbetweenthealarmandtheenclosure.
IMPORTANT NOTE: NFPA 496 requires the use of an alarm or an indicator to detect the loss of safe enclosure pressure. In addition, the NFPA 496 requires that if an indicator alone is utilized, a protective gas supply alarm must also be installed between the last valve in the protective gas supply and the protected enclosure. Therefore, the protective gas supply to all Model 1011 systems must be equipped with the above mentioned protective gas supply alarm. Exception: Systems utilizing an EPSK or GPSK enclosure pressure loss alarm switch accessory will satisfy the above mentioned NFPA requirement.
Typical Enclosure Wiring MethodsProtectedenclosuresshouldbewiredsimilartoexplosionproofenclosures,inaccordancewithArticle500oftheNationalElectricCode-NFPA70.
Singleconductorwiringshouldbeplacedinrigidmetalconduit,seal-flexconduitorothermediumsapprovedforuseinthehazardouslocationsurroundingtheprotectedenclosure.Additionally,NFPA496requirestheuseofapprovedsealsonallpressurizedenclosureconduitwiringentries,inaccordancewithNFPA70.Furthermore,theuseofanapprovedsealissimplythemostpracticalwaytopreventexcessiveleakagethroughconduitconnections.
However,whileexplosionproofenclosuresrequireconduitsealsonallcableentries,inaccordancewithNFPA70.Othermethodsofsealedcableentriesthataresuitableforhazardouslocationscanbeused,suchascompressionglands.
Inconclusion,therearetwoprimarygoals.First,theinstallershouldensurethatallassociatedwiringandcableisprotectedbypressurizationorothermeans,suchasexplosionproofconduitorintrinsicsafetybarriers.Secondly,theinstallershouldensurethatallassociatedconduitandwirewaysaresealedtoconserveprotectivegas,unlesstheyareusedtosupplyprotectivegastootherenclosuresordevices.
Typical Enclosure Wiring Connections
AdjacentPpressurized
device
Explosionproofdevice
Seal
Intrinsicallysafeorfiberopticdevice
Independentlypressurized
device
Intrinsicallysafeorfiberopticdevice
Seal
Conduit
Conduit
Conduit
Glandfitting
Cable
Seal
Pressurizedraceway
Protectedenclosureordevice
Model 1011 Installation and Operation Manual
14
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Set-up Procedure
Class I Purging Set-up1.Closetheenclosurepressurecontrolregulatorfullyby
turningcounterclockwise(CCW).
2.Temporarilyconnecttheinertgassupplytoa0to250SCFHflowmeter.Connecttheoutletoftheflowmetertotheenclosurepressurecontrolregulator.
3.Checkoperationofenclosurepressurevent(ifutilized).
4.Sealenclosure(s)andadjustenclosurepressurecontrolregulatorbyopeningslowlyclockwise(CW)toseta“safe”pressureontheenclosurepressureindicator.
NOTE:Ifpressuresettingisdifficulttostabilizeorset,seepage16,“TroubleshootingProcedures.”
5.Whensafeenclosurepressureisstabilized,measureflowofinertgassupplythroughprotectionsystem,tocalculaterequiredexchangetime,basedontheClassIexchangetimechart.
6. Installandtightenallboltsonthepressurelossalarmswitch(ifutilized).Ensuretheconduitissealedwithapprovedcompounds.Energizepowertoswitchandalarmsystem(ifutilized)andtestthefunctionofthealarmsystem.
7.Ceasetestingandremovetestequipment(flowmeter).
8. Connecttheinertgassupplydirectlytotheenclosurepressurecontrolregulator.
IMPORTANT NOTE: Operators must secure wrist or stop watch to manually time exchange cycle for Class I applications.
CLASSIVOLUMEEXCHANGETIMECHART
MEASUREDFLOW REQUIREDEXCHANGETIME
0.10SCFM/6SCFH 40minutespercubicfoot
0.25SCFM/15SCFH 16minutespercubicfoot
0.50SCFM/30SCFH 8minutespercubicfoot
0.75SCFM/45SCFH 5.5minutespercubicfoot
1SCFM/60SCFH 4minutespercubicfoot
2SCFM/120SCFH 2minutespercubicfoot
3SCFM/180SCFH 1.5minutespercubicfoot
4SCFM/240SCFHorgreater 1minutepercubicfoot
NOTE:Thevolumeexchangetimechartisbasedonafour(4)enclosurevolumeexchange.Multiplytherequiredexchangetimeaboveby2.5forapplicationsrequiringaten(10)volumeexchange(motors).
Regardlessofenclosurevolumeorsystemflowrate,itisrequiredthatoperatorswithholdpowertotheenclosurewhileinducingClassIexchange,foratleastfive(5)minutes.Normalexchangetimecalculationsshouldbedoublediflargeobstructionsblockinertgasflow.
Thestart-upinstructionnameplateexchangetimeslotwillbeblank,buttheunitmayfeatureasetofdirectfactornameplateswithself-adhesivebackingsuchas“TENMINUTES,”forapplicationtothestart-upinstructions,dependentonhowthesystemwasspecifiedandpurchased.Fieldmodificationofthisnameplate,toshowadirectfactor,isacceptableasnotedaboveifthemethodusedtomarkthenameplatedoesnotdefacetheinstructionslisted.Materialsusedforthemarkingmustbeindelibleandwithstandprevailingenvironmentalconditions.
Class II Pressurization Set-up1.Closetheenclosurepressurecontrolregulatorfully,by
turningitcounterclockwise(CCW).
2. Removealltracesofcombustibledustfromtheprotectedenclosure.
3.Checkoperationofenclosureprotectionvent(ifutilized).
4.Sealenclosure(s)andadjustenclosurepressurecontrolregulatorbyopeningslowlyclockwise(CW)toseta“safe”pressureontheenclosurepressureindicator.
NOTE:Ifpressuresettingisdifficulttostabilizeorset,seepage16,“TroubleshootingProcedures.”
5. Installandtightenallboltsonthepressurelossalarmswitch(ifutilized).Ensuretheconduitissealedwithapprovedcompounds.Energizepowertoswitchandalarmsystem(ifutilized)andtestthefunctionofthealarmsystem.
HELPFUL HINTSTheterm“Safe”pressureforpurposesofthismanualisdefinedasfollows:
ClassI=aminimum.25inchofwatercolumnpressure
ClassII=aminimum1.0inchofwatercolumnpressure
Regulatormaybeinthelockedpositionuponarrival.Toadjustregulator,pullhandletooutwardposition.
Totestthevent’soperation,gentlyprodtheventflapperopenwithasoft-pointedobject,(example:eraserendofapencil)ensuringthattheventvalveworksfreely.Onverticallyconfiguredvents,thiscanbeaccomplishedfromwithintheprotectedenclosure.Sidemounted-90configuredventscanbetestedbyremovingtheconduitplugatthebottomofthemountingtee.Multipleoperationsrequireonlyonetestperdayifenclosureisnotopenedorleftunattended.
Model 1011 Installation and Operation Manual
15
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Operating Sequence
WARNING! Do not exceed a “safe” pressure with the enclosure pressure control regulator. Operators must
follow step-by-step sequence of the start-up instructions nameplate on the protection system.
Class I Purging OperationStart-Up Conditions
Protectionmethod: Type“Z”purge/pressurizationsystemPoweringmethod: LocaldisconnectswitchSystemstatus: Protectedequipmentde-energized alarmsystemandairsupplyonOperating Procedures
1. Checkoperationofenclosurepressurereliefdevice(ifutilized)andsealtheprotectedenclosure.
2. Pressurizetheprotectedenclosuretosetandmaintainaminimumpositivepressureof0.10inches(2.5mm)ofwater.
3. Exchangetherecommendedvolumesofpurginggas.Exception:Powermaybeenergizedimmediatelyiftheprotectedenclosureatmosphereisknowntobenonflammable.
4. Energizetheprotectedequipmentpowermanuallywithadisconnectswitchorbreakerratedforthehazardouslocation.
5. Lossofpressurizationrequiresimmediateattentionorthemanualde-energizingofprotectedequipmentpower.
6. Excessivelyhotequipmentmustbeisolatedinaseparateprotectedenclosure,unlesstheenclosureismarkedwithawarningwhichindicatesarequiredcool-downtimeperiodbeforeaccess.
Class II Pressurization OperationStart-Up Conditions
Protectionmethod: Type“Z”pressurizationsystemPoweringmethod: LocaldisconnectswitchSystemstatus: Protectedequipmentde-energized alarmsystemandairsupplyonOperating Procedures
1. Removehazardoussubstancefromtheprotectedenclosure.Avacuumdeviceisthepreferredtoolfordustremoval.
2. Checkoperationofenclosurepressurereliefdevice(ifutilized)andsealtheprotectedenclosure.
3. Pressurizetheprotectedenclosuretosetandmaintainapositivepressureof0.50inches(12.7mm)ofwater.
4. Energizetheprotectedequipmentpowermanuallywithadisconnectswitchorbreakerratedforthehazardouslocation.
5. Lossofpressurizationrequiresimmediateattentionorthemanualde-energizingofprotectedequipmentpower.
6. Excessivelyhotequipmentmustbeisolatedinaseparateprotectedenclosure,unlesstheenclosureismarkedwithawarningthatindicatesarequiredcool-downtimeperiodbeforeaccess.
Enclosurepressurecontrol
regulator
Model identification
nameplate
Enclosure pressure
gauge
Start-up instruction nameplate
Model 1011 Installation and Operation Manual
16
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Troubleshooting Procedures
Problem or Fault Possible Causes Corrective Action
Enclosurepressurecontrolregulatorwillnotholdasafepressure.
Leakagearoundgasketing,covers,seams,pipingandtubingconnections,conduitconnectionsandelectricalconduitsealsoftheenclosure.
Tightenenclosurelatches:Wheretighteningisnotfeasible,andgasketingmaterialsarenotpractical,holesorgapscanbeclosedwithsiliconesealantappliedfrominsidetheprotectedenclosure.
Enclosurepressureindicatorreadingisdifficulttostabilize.
Insufficientenclosureleakageoropeningoftheventuriorificeiscrimpedtoosmall.
Removetheorifice,cutoffthecrimpedendandreamthetube,thenrecrimpandreinstallthetubetonoteeffect.Astubeisshortened,reamed,andrecrimped,sensitivitydecreases,allowingeasieradjustmentofsetpointontheenclosure.
Enclosurepressureindicator"drifts"upordownfromthe"safe"pressuresetting.
Applicationinvolvesasmall,tightlysealedenclosureand/orafluctuatingprotectivegassupply.
Pre-regulatetheprotectivegassupplyupstreamoftheenclosureprotectionsystemto5psimaximum.
Fordramaticfluctuationsintheprotectivegassupply,itmaybeneccessarytoutilizeaself-relievinglowflowprecisionregulatortopre-regulatetheprotectivegassupply.
Enclosurepressurelossalarmswitchdoesnotappeartobeoperating.
Pressureswitchisoutofcalibration. Calibratebyslowlyadjustingcounterclockwisetodecreasethesetpoint,andclockwisetoraisethesetpoint.(Donotattempttocalibratetheswitchuntilalleffortstomaketheswitchrespondproperlyhavefailed)
Problemspersists,orifthesystemdoesnotappeartobeoperatingproperly.
Problemspersist ContactPepperl+FuchsApplications/CustomerServiceDepartmentat(330)486-0002formoreinformation.
Thissectioncoversthemostcommonproblemsdocumentedwiththissystem.Anyproblemsnotcoveredinthissectionshouldbeaddresseddirectlytoourfactory.Pleaseaddressallserviceneedsto:
Pepperl+Fuchs, Inc. Customer Service Department
Model 1011 Installation and Operation Manual
17
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
PEPPERL+FUCHS STANDARD 24-MONTH WARRANTY1. LimitedWarranty.Pepperl+Fuchs,Inc.(“P+F")warrantsPurgeUnitsandcomponentsforPurgeUnitsmanufacturedbyP+F
(“Product"or“Products")tobefreefromdefectsinmaterialandworkmanshipunderNormalUseforaperiodoftwenty-four(24)monthsfromthedateofshipmentofsuchProductsfromP+F’swarehouseorplaceofmanufacture(orfromP+F’sauthorizedrepresentativeordistributor).OnlytheoriginalpurchaserofsuchProducts(the“Customer")shallbeentitledtothebenefitoftheforegoingLimitedWarranty.Norepresentative,agentorsalesmanofP+FisauthorizedtogiveorprovideanywarrantyormakeanyrepresentationcontrarytoorinadditiontotheforegoingLimitedWarranty.
2. InspectionandClaims.CustomermustinspectandtestallProductsuponreceipt.AllclaimsundertheLimitedWarrantyprovidedhereinmustbemadewithinthirty(30)daysofthediscoveryofthedefect.CustomermustobtainshippinginstructionsfromP+FpriortoreturninganyProduct,whichProductmustbereturnedatCustomer’sexpenseinaccordancewithP+F’sinstructions.
3. LimitationsandExclusions.“NormalUse"shallmeanuseandoperationwithinratedcapacities,atthecorrectvoltage,andwithanyrequiredmaintenanceasprovidedintheapplicableP+FOperatingManuals.TheLimitedWarrantyprovidedhereindoesnotapplyto(i)anyProductswhichhavebeenalteredormodifiedinanywayordisassembledbytheCustomeroranyoneelse,(ii)anyProductswhichhavebeensubjecttomisuse,negligenceoraccident,orimproperlyinstalled,changed,substitutedorreplaced,(iii)anypartorcomponentnotmanufacturedbyP+F,or(iv)anypartorcomponentthatissubjecttowearorconsumption.ForpartsorcomponentsnotmanufacturedbyP+F,theCustomeroranyotheruserorownershallhaveonlythewarrantyprovidedbythemanufacturerofsuchpartorcomponent.TheLimitedWarrantysetforthhereinisalsosubjecttothefollowing:
(1) TheLimitedWarrantyislimitedtoelectronicandmechanicalperformanceonly,asexpresslydetailedintheproductspecifications,anddoesnotapplytocosmeticappearance;
(2) TheLimitedWarrantyshallnotapplytoanycablesattachedto,orintegratedwith,anyProducts.
(3) TheLimitedWarrantyshallnotapplytoanyProductswhicharestored,orutilized,inharshenvironmentalorelectricalconditionsoutsideP+F’swrittenspecifications.
THELIMITEDWARRANTYSETFORTHHEREINISTHEONLYWARRANTYMADEBYP+FWITHRESPECTTOTHEPRODUCTS.ITISEXPRESSLYAGREEDANDUNDERSTOODTHATP+FMAKESNOWARRANTYOFMERCHANTABILITYORFITNESSFORAPARTICULARPURPOSE.EXCEPTFORTHELIMITEDWARRANTYSETFORTHHEREIN,THEREISNOOTHERWARRANTY,EXPRESS,IMPLIEDORSTATUTORY;ANDTHEREISNOAFFIRMATIONOFFACTORPROMISEBYP+FWITHREFERENCETOTHEPRODUCTS.INNOEVENTSHALLP+FBELIABLEFORACTUALORANTICIPATEDLOSTPROFITSORFORINCIDENTALORCONSEQUENTIALORPUNITIVEDAMAGESORFORDAMAGESRESULTINGFROMBUSINESSINTERRUPTION,ORINJURYORDEATHOFPERSONS,ORINJURYTOPROPERTY.P+F’SLIABILITYONANYCLAIMOFANYKINDARISINGOUTOF,CONNECTEDWITHORRESULTINGFROMTHEDESIGN,MANUFACTURE,SALE,REPAIROROPERATIONOFAPRODUCT,SHALLNOTEXCEEDTHEPRICEALLOCABLETOTHATPRODUCTORTHEPARTTHEREOFWHICHGIVESRISETOTHECLAIM.THEREMEDYSETFORTHINTHISLIMITEDWARRANTYCONSTITUTESTHESOLEANDEXCLUSIVEREMEDYOFTHECUSTOMER.P+FSHALLNOTBELIABLEFORPENALTIESOFANYDESCRIPTION.
4. LimitationofRemedies.IntheeventofP+F’sliability,whetheronthisLimitedWarrantyorbasedoncontract,tort(including,butnotlimitedto,negligenceandstrictliability)orotherwise,Customer’ssoleandexclusiveremedywillbelimitedto,atP+F’soption,therepairorreplacement(f/o/bP+F’splaceofmanufacture)byP+Fofanynon-conformingitemsforwhichclaimismadebyCustomerinaccordancewithparagraph2,ortherepaymentoftheportionofthepurchasepricepaidbyCustomerattributabletothenon-conformingitem.
5. ResponsibilityofCustomer:SafetyandProtectionPrecautions.P+FtakesgreatcaretodesignandbuildreliableanddependableProducts;however,someProductscanfaileventually.Customermusttakeprecautionstodesignitsequipmenttopreventpropertydamageandpersonalinjuryintheunlikelyeventofafailure.ASAMATTEROFPOLICY,P+FDOESNOTRECOMMENDTHEINSTALLATIONOFPRODUCTSASTHESOLEDEVICEFORTHEPROTECTIONOFPERSONNELORPROPERTYAND,THEREFORE,THECUSTOMERSHOULDBUILDINREDUNDANCYORDUALCONTROLUSINGAPPROVEDSAFETYDEVICESFORTHESEAPPLICATIONS.
6. Conflicts.IntheeventthereisanyconflictbetweentheprovisionsofthisLimitedWarrantyandanyprovisionscontainedinanyorders,offers,acceptancesorotherwritingsorstatementsprovidedormadebyCustomertoP+F,theprovisionsofthisLimitedWarrantyshallprevail,andthecontractbetweenP+FandtheCustomershallbedeemedformedonlyupontheprovisionssetforthinthisLimitedWarranty,andanyadditionalorconflictingprovisioninsertedbyCustomershallbeofnoforceoreffect.
Warranty Terms and Conditions
Model 1011 Installation and Operation Manual
18
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
System Maintenance
Regular MaintenanceDraintheprotectionsystemregulatorfrequentlyandcleansystemwithnonsolventcleaningagentsonly.
Long-Term MaintenanceCalibratetheenclosurepressureindicatorto0inchesbyventingthepurgepressurereferenceportandtheprotectedenclosuretoatmosphereandadjustingthecalibrationscrewinthelowercenterportionoftheindicator’sface.
Fullyopentheenclosurepressurecontrolregulator,toblowoutanydepositsaroundthetipofthevalveandtoensurethattheenclosureprotectionventisoperatingproperly,thencarefullyreadjustsystemaccordingtotheset-upprocedureandoperatingsequenceonpages14and15.Replaceortightenstempackingnutasrequiredtoprohibitstempackingleakage.
Carefullydisassembletheenclosureprotectionventbylooseningthetwobottomhexnutsthatholdtheunittogether.
(DO NOT REMOVE CAP NUTS ON TOP OF VENT BODY)
Carefullycleantheflappervalveandventbodyseatswithwarmsoapandwater,beingcarefulnottoextendtheventvalvebeyonditsnormalopeningpoint,andbeingcarefulnottoexertanystressonthevalvehinge.
Examinetheentireprotectionsystemandtheprotectedenclosure(s),andreplaceanydefectivepartsduringroutineshutdownoftheprotectedenclosure(s).PartsareavailablefromPepperl+Fuchsonimmediatenoticeasrequired.
MAINTENANCE SCHEDULEDate Work performed Performed by
Model 1011 Installation and Operation Manual
19
Par
t No.
512
083
Dra
win
g N
o. 1
29-0
205a
03/
09
Subject to modifications without notice
Pepperl+Fuchs Groupwww.pepperl-fuchs.com
USA: +1 330 486 [email protected] [email protected]
Singapore: +65 6779 [email protected]
Copyright Pepperl+Fuchs
Germany: +49 621 776 2222
Systems Identification & Application Information
Date of installation _____________________________________________________
Unit serial #____________________________________________________________
Item ___________________________________________________________________
Customer P.O.# ________________________________________________________
Customer project# _____________________________________________________
Service ________________________________________________________________
Type __________________________________________________________________
Features ______________________________________________________________
Application ____________________________________________________________
Notes: _______________________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
5 1
8
4
2
6
7
3
www.pepperl-fuchs.com
PROCESS AUTOMATION – PROTECTING YOUR PROCESS
Worldwide/German Headquarters Pepperl+Fuchs GmbH Mannheim · GermanyTel. +49 621 776 2222E-Mail: [email protected]
1
Asia Pacific HeadquartersPepperl+Fuchs PTE Ltd. SingaporeCompany Registration No. 199003130ETel. +65 6779 9091E-Mail: [email protected]
2
Central/Western Europe & Africa HeadquartersPepperl+Fuchs N.V. Schoten/Antwerp · BelgiumTel. +32 3 6442500E-Mail: [email protected]
3
Middle East HeadquartersPepperl+Fuchs M.E (FZE) Dubai · UAETel. +971 4 883 8378E-Mail: [email protected]
4
North/Central America Headquarters Pepperl+Fuchs Inc. Twinsburg · Ohio · USATel. +1 330 486 0002E-Mail: [email protected]
5
Northern Europe HeadquartersPepperl+Fuchs GB Ltd. Oldham · EnglandTel. +44 161 6336431E-Mail: [email protected]
6
Southern/Eastern Europe HeadquartersPepperl+Fuchs Elcon srl Sulbiate · ItalyTel. +39 039 62921E-Mail: [email protected]
7
South America HeadquartersPepperl+Fuchs Ltda. São Bernado do Campo · SP · BrazilTel. +55 11 4339 9935E-Mail: [email protected]
8
For over a half century, Pepperl+Fuchs has provided new concepts for the world of process automation. Our company sets standards in quality and innovative technology. We develop, produce, and distribute electronic interface modules, Human-Machine Interfaces and hazardous location protection equipment on a global scale, meeting the most demanding needs of industry. Resulting from our world-wide presence and our high flexibility in production and customer service, we are able to offer complete individual solutions – wherever and whenever you need us. We are the recognized experts in our technologies – Pepperl+Fuchs has earned a strong reputation by supplying the world’s largest process industry companies with the broadest line of proven components for a diverse range of applications.
Subject to modifications • © 2009 PEPPERL+FUCHS, INC. • Printed in USA • Part No. 512083 Drawing No. 129-0205a (TDOCT-1360_ENG) 03/09