description series: adjustable set point range

2
Hazardous Areas Adjustable Pressure Switch 6403DZE* - Diaphragm Sensor DESCRIPTION Highly reliable devices utilizing the CCS Dual-Snap® Belleville disc spring principle pioneered by CCS’ engineers. Engineering based on aerospace technology. Rigid and internally adjustable for convenient field set point adjustment. Repeatable and stable set points. Vibration and shock resistant. High cycle life. INSTALLATION DRAWING Models: 6403DZE*, Page 1 of 2 Form 830G, 5.27.11 DESIGN PRINCIPLES ccsdualsnap.com SERIES: 6403DZE* ADJUSTABLE SET POINT RANGE: DIFFERENTIAL PRESSURE: .39 to 75 PSID 0.027 to 5.17 bar 2.7 to 517 kPa OPERATING TEMPERATURE: Temperature limits change with O-ring selection. -40° to 186°F -40° to 86°C STANDARD FEATURES: Hermetically Sealed Electrical Assembly Integral Junction Box ATEX - Baseefa Certified CE Mark NACE MR0175:2003 NEMA: 4, 7, 9,13 / IP66 & 67 FIELD SETTING: Loosen access cover. Adjust adjustment screw using screwdriver. Clockwise to increase settings. Counterclockwise to decrease setting. High over-pressure capability. (System and Proof) Various options for electrical ratings to meet a wide range of application requirements and media capability. SHIPPING WEIGHT: APPROXIMATELY7.5 LBS (3.4 KGS)

Upload: others

Post on 02-Oct-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DESCRIPTION SERIES: ADJUSTABLE SET POINT RANGE

Hazardous AreasAdjustable Pressure Switch

6403DZE* - Diaphragm Sensor

DESCRIPTION

• HighlyreliabledevicesutilizingtheCCSDual-Snap®BellevillediscspringprinciplepioneeredbyCCS’engineers.

• Engineeringbasedonaerospacetechnology.

• Rigidandinternallyadjustableforconvenientfieldsetpoint

adjustment.• Repeatableandstablesetpoints.• Vibrationandshockresistant.• Highcyclelife.

INSTALLATION DRAWING

Models:6403DZE*,Page1of2Form830G,5.27.11

DESIGN PRINCIPLES

ccsdualsnap.com

SERIES: 6403DZE*ADJUSTABLE SET POINT RANGE: DIFFERENTIAL PRESSURE: .39to75PSID 0.027to5.17bar 2.7to517kPaOPERATING TEMPERATURE:TemperaturelimitschangewithO-ringselection.

-40°to186°F -40°to86°C

STANDARD FEATURES: • HermeticallySealedElectricalAssembly• IntegralJunctionBox• ATEX-BaseefaCertified• CEMark• NACEMR0175:2003• NEMA:4,7,9,13/IP66&67

FIELD SETTING:Loosenaccesscover.Adjustadjustmentscrewusingscrewdriver.Clockwisetoincreasesettings.Counterclockwisetodecreasesetting.

• Highover-pressurecapability.(SystemandProof)• Variousoptionsforelectricalratingstomeetawiderangeofapplicationrequirementsandmediacapability.

SHIPPINGWEIGHT:APPROXIMATELY7.5LBS(3.4KGS)

Page 2: DESCRIPTION SERIES: ADJUSTABLE SET POINT RANGE

OPERATING AND ORDERING DATA

SERIES6403DZE*

WETTEDPARTS:1/4"-18NPTSTAINLESSSTEELPRESSUREPORT,POLYIMIDEDIAPHRAGM,VITONO-RING

ADJUSTABLESETPOINTRANGE APPROX.

DEADBAND

PSI(BAR)

SYSTEMPRESSUREPSIG(BAR)

PROOFPRESSUREPSIG(BAR)

INCREASINGPRESSUREPSID(BAR)

DECREASINGPRESSUREPSID(BAR)

BOTHPORTSSIMULT.

HIGHOVERLOWLOWOVERHIGH

HIGH LOW

6403DZE*1 1.4-18(0.097-1.2)

0.39-16.99(0.027-1.13)

1.01(0.07)

400(27.6)

750(52)

750(52)

400(27.6)

6403DZE*2 6-75(0.41-5.1)

2-71(.13-4.82)

4(0.28)

OPTIONAL STANDARD MODIFIED SUFFIXES7008:GoldContacts7011:StainlessSteelDiaphragm

ELECTRICAL CHARACTERISTICSRATINGOFSWITCHELEMENT

SCHEMATIC AND WIRING CODE

SPDT DPDT"M"Res. Res.

125AC - 50/60Hz 15 11250AC - 50/60Hz 15 11480AC - 50/60Hz 15 -28DC - 5

.5 .5250DC .2 -*125AC - 50/60Hz 1max 1max*30DC 1max 1max

VOLTS

125DC

AMPERES

*GoldContacts-7008Suffix

HOW TO ORDERFollowthesestepstobuildyourpartnumber:1. Specifytheseries

basedonyourrequiredsetpoint,range,deadband,systempressureandproofpressure.

2. Adddesiredoptionsmodelcodeletter.

3. Addtheapplicablestandardsuffixnumber.

(Ex:6403DZEM1-7008)

PRESSURE CONVERSION1BAR=14.5PSI1kPa=0.145PSI

ccsdualsnap.com Models:6403DZE*,Page2of2Form830G,5.27.11

Note:Additionalmodifiedstandardsuffixesareavailable,consultCCSsalesdepartmentorCCSRepresentative.

CERTIFICATIONS ConsultCCSwebsiteforcompletecertificationandapprovallisting.

Hazardous AreasAdjustable Pressure Switch

6403DZE* - Diaphragm Sensor

OPTIONS MODEL CODESM: DPDTElectrical

ELECTRICAL ENCLOSURE CERTIFICATIONS*ATEX-CertificateNo.Baseefa04ATEX0113.Baseefacertifiedforpotentiallyexplosiveatmosphereselectricalassemblyseries.IncompliancewithEN60079-0:2004,EN60079-1:2004andEN50281-1-1:1998+Amendment1.(Standard)