design of a resonant snubber inverter for photovoltaic ... · design of a resonant snubber inverter...

92
Design of a Resonant Snubber Inverter for Photovoltaic Inverter Systems William Eric Faraci Thesis submitted to the faculty of the Virginia Polytechnic Institute and State University in partial fulfillment of the requirements for the degree of Master of Science In Electrical Engineering Jih-Sheng Lai, Chair Kathleen Meehan Qiang Li April 16, 2014 Blacksburg, Virginia Keywords: Inverter, dc/ac, Soft Switching, Resonant Snubber Inverter, RSI Copyright © 2014 William Eric Faraci

Upload: others

Post on 11-Mar-2020

14 views

Category:

Documents


3 download

TRANSCRIPT

Design of a Resonant Snubber Inverter for

Photovoltaic Inverter Systems

William Eric Faraci

Thesis submitted to the faculty of the

Virginia Polytechnic Institute and State University

in partial fulfillment of the requirements for the degree of

Master of Science

In

Electrical Engineering

Jih-Sheng Lai, Chair

Kathleen Meehan

Qiang Li

April 16, 2014

Blacksburg, Virginia

Keywords: Inverter, dc/ac, Soft Switching, Resonant Snubber Inverter, RSI

Copyright © 2014 William Eric Faraci

Design of a Resonant Snubber Inverter for Photovoltaic Inverter Systems

William Eric Faraci

ABSTRACT

With the rise in demand for renewable energy sources, photovoltaics have become

increasingly popular as a means of reducing household dependence on the utility grid for power.

But solar panels generate dc electricity, a dc to ac inverter is required to allow the energy to be

used by the existing ac electrical distribution. Traditional full bridge inverters are able to

accomplish this, but they suffer from many problems such as low efficiency, large size, high

cost, and generation of electrical noise, especially common mode noise. Efforts to solve these

issues have resulted in improved solutions, but they do not eliminate all of the problems and

even exaggerate some of them.

Soft switching inverters are able to achieve high efficiency by eliminating the switching

losses of the power stage switches. Since this action requires additional components that are

large and have additional losses associated with them, these topologies have traditionally been

limited to higher power levels. The resonant snubber inverter is a soft switching topology that

eliminates many of these problems by taking advantage of the bipolar switching action of the

power stage switches. This allows for a significant size reduction in the additional parts and

elimination of common mode noise, making it an ideal candidate for lower power levels.

Previous attempts to implement the resonant snubber inverter have been hampered by low

efficiency due to parasitics of the silicon devices used, but, with recent developments in new

semiconductor technologies such as silicon carbide and gallium nitride, these problems can be

minimized and possibly eliminated.

The goal of this thesis is to design and experimentally verify a design of a resonant

snubber inverter that takes advantage of new semiconductor materials to improve efficiency

while maintaining minimal additional, parts, simple control, and elimination of common mode

noise. A 600 W prototype is built. The performance improvements over previous designs are

verified and compared to alternative high efficiency solutions along with a novel control

technique for the auxiliary resonant snubber. A standalone and grid tie controller are developed

iii

to verify that the auxiliary resonant snubber and new auxiliary control technique does not

complicate the closed loop control.

iv

Acknowledgements

I would like to first thank my advisor, Dr. Jih-Sheng Lai. Dr. Lai introduced me to the

field of power electronics when I was an undergraduate student and provided me the opportunity

to continue my education in the Master of Science program. While working under him, I have

learned far more than any classroom could teach, and his guidance and knowledge has allowed

me to succeed throughout my time at Virginia Tech.

I also would like to thank Dr. Kathleen Meehan and Dr. Qiang Li for serving on my

committee. I have taken classes taught by both professors, and what I learned from those classes

has helped set up the foundation of my technical ability.

I would also like to thank my colleagues at the Future Energy Electronics Center (FEEC)

Baifeng Chen, Rui Chen, Bin Gu, Thomas LaBella, Seung-Ryul Moon, Zaka Ullah Zahid,

Lanhua Zhang, Cong Zheng, Jason Dominic, Hidekazu Miwa, Wei-Han Lai, Nathan Kees, and

Gary Kerr. All were helpful in teaching me parts of engineering that are not taught in a

classroom and were indispensable when I was stuck or confused about a problem I was having.

I also would like to thank Michael Seeman, Sandeep Bahl, Gianpaolo Lisi, and Matt

Senesky from Texas Instruments and my fellow intern Lixing Fu. When I started the project that

turned into my thesis as an intern at Texas Instruments, they and everyone else I worked with

were very knowledgeable and helpful to show me how to apply what I learned in school and how

be a successful electrical engineer in industry.

I would like to thank my parents, Tess and Steve Faraci, my sisters Jess and Chrissy, the

rest of my family, and all of my friends for supporting me throughout my education. They have

always been there for me, giving the encouragement and confidence needed to be successful in

my undergraduate, graduate, and professional career.

All photos, screenshots, and figures used have been created by the author for this thesis.

I would also like to thank Texas Instruments, Inc for funding this work.

v

CONTENTS

1 Introduction ............................................................................................................................. 1

1.1 Traditional Central String Inverter ................................................................................... 2

1.2 Microinverter .................................................................................................................... 3

1.3 Microconverter with Centralized Inverter ........................................................................ 4

1.4 Inverter Requirements ...................................................................................................... 5

1.5 High Efficiency Hard Switching Inverters ....................................................................... 6

1.6 Soft Switching Inverters ................................................................................................... 8

1.6.1 Auxiliary Resonant Snubber with Capacitor Reset .................................................. 9

1.6.2 Auxiliary Resonant Snubber with Coupled Magnetic Reset .................................. 10

1.6.3 Auxiliary Resonant Snubber with No External Reset ............................................. 11

1.7 Goal and Scope of Thesis ............................................................................................... 12

2 Resonant Snubber Inverter Basic Operation ......................................................................... 13

2.1 Operating Modes ............................................................................................................ 13

2.1.1 Auxiliary Resonant Snubber Control Method ........................................................ 14

2.1.2 Operating Mode with Positive Load Current .......................................................... 17

2.1.3 Operating Mode with Negative Load Current ........................................................ 19

2.2 Design Limitations ......................................................................................................... 22

3 Parameter Design ................................................................................................................... 23

3.1 Power Stage Switch Selection ........................................................................................ 23

3.2 Auxiliary Resonant Snubber Capacitor .......................................................................... 26

3.3 Auxiliary Resonant Snubber Inductor for Adaptive Case (a) ........................................ 27

3.4 Adaptive Auxiliary Resonant Snubber Control Timing for Adaptive Case (a) ............. 30

3.5 Auxiliary Resonant Snubber Inductor for Adaptive Case (b) ........................................ 32

3.6 Auxiliary Resonant Snubber Switch .............................................................................. 33

3.7 Switching Frequency ...................................................................................................... 35

3.8 DC Bus Voltage ............................................................................................................. 35

3.9 Output Filter ................................................................................................................... 36

3.10 Design Summary ............................................................................................................ 37

3.11 Power Stage Hardware Test Setup ................................................................................. 37

3.12 Auxiliary Voltage Overshoot Issue ................................................................................ 39

3.13 Power Stage Experimental Results ................................................................................ 43

vi

3.14 Efficiency Measurement ................................................................................................ 49

3.15 Thermal Measurement Loss Analysis ............................................................................ 51

4 Control ................................................................................................................................... 56

4.1 Standalone Mode Control............................................................................................... 56

4.1.1 Standalone Mode Plant Model ................................................................................ 56

4.1.2 Design of Standalone Controller ............................................................................. 57

4.1.3 Simulation of Standalone Controller ...................................................................... 60

4.1.4 Experimental Results of Standalone Controller ...................................................... 62

4.2 Grid Tie Control ............................................................................................................. 65

4.2.1 Phase Lock Loop..................................................................................................... 66

4.2.2 Grid Tie Plant Model .............................................................................................. 67

4.2.3 Control Block Diagram ........................................................................................... 69

4.2.4 Current Loop Control Compensator Design ........................................................... 70

4.2.5 Feed Forward Compensator Design ........................................................................ 73

4.2.6 Simulation of Grid Tie Controller........................................................................... 73

4.2.7 Experimental Results of Grid Tie Controller .......................................................... 74

5 Conclusion ............................................................................................................................. 78

5.1 Future Work ................................................................................................................... 79

References ..................................................................................................................................... 80

vii

TABLE OF FIGURES

Figure 1.1: Traditional Central String Inverter ............................................................................... 2

Figure 1.2: Microinverter ................................................................................................................ 3

Figure 1.3: Microconverter with Parallel Connection .................................................................... 4

Figure 1.4: Dual Buck Inverter Schematic ..................................................................................... 6

Figure 1.5: H5 Inverter Schematic .................................................................................................. 7

Figure 1.6: HERIC Inverter Schematic ........................................................................................... 8

Figure 1.7: Auxiliary Resonant Snubber with Capacitor Reset Schematic .................................... 9

Figure 1.8: Auxiliary Resonant Snubber with Coupled Magnetic Reset Schematic .................... 10

Figure 1.9: Auxiliary Resonant Snubber with No External Reset ................................................ 11

Figure 2.1: Resonant Snubber Inverter Schematic ....................................................................... 13

Figure 2.2: Two Auxiliary Resonant Snubber Control Methods .................................................. 14

Figure 2.3: Adaptive Control Method of Auxiliary Resonant Snubber with Case (a) ................. 15

Figure 2.4: Adaptive Control Method of Auxiliary Resonant Snubber with Case (b) ................. 16

Figure 2.5: Schematic and Timing Diagram with Positive Load Current .................................... 17

Figure 2.6: Schematic with Negative Load Current ..................................................................... 19

Figure 2.7: Timing Diagram with Negative Load Current and Case (a) Control ......................... 20

Figure 3.1: Schematic of Body Diode Reverse Recovery Comparison ........................................ 24

Figure 3.2: MOSFET Body Diode Reverse Recovery Comparison with Double Pulse Test....... 25

Figure 3.3: Resonant Snubber Current caused by Lr .................................................................... 27

Figure 3.4: PSIM Simulation of Switching Action when Iout is 0.5 A .......................................... 28

Figure 3.5: PSIM Simulation of Switching Action for Adaptive Case (a) Control when Iout is 3.5

A .................................................................................................................................................... 30

Figure 3.6: PSIM Simulation of Switching Action for Adaptive Case (b) Control when Iout is 3.5

A .................................................................................................................................................... 32

Figure 3.7: Cascade Configuration of TPH3006 .......................................................................... 34

Figure 3.8: Experimental Test Setup ............................................................................................ 38

Figure 3.9: Experimental Test PCB .............................................................................................. 38

Figure 3.10: Waveform of Switching Action with Voltage Overshoot Issue ............................... 40

Figure 3.11: Waveform of Switching Action with Separate Resonant Snubber Legs .................. 41

viii

Figure 3.12: Resonant Snubber Inverter with Clamping Diodes .................................................. 42

Figure 3.13: Waveform of Switching Action during High Line Current ..................................... 43

Figure 3.14: Waveform of Switching Action during Low Line Current ...................................... 44

Figure 3.15: Waveform of Output with Adaptive Case (a) Control and 600 W (100%) Output

Power ............................................................................................................................................ 45

Figure 3.16: Waveform of Output with Adaptive Case (a) Control and60 W (10%) Output Power

....................................................................................................................................................... 46

Figure 3.17: Waveform of Output with Simple Case (a) Control and 600 W (100%) Output

Power ............................................................................................................................................ 47

Figure 3.18: Waveform of Output with Adaptive Case (b) Control and 600 W (100%) Output

Power ............................................................................................................................................ 48

Figure 3.19: Measured Efficiency over CEC Operating Range ................................................... 49

Figure 3.20: Photo of Thermal Measurement Point of Auxiliary Resonant Snubber ................... 52

Figure 3.21: Thermal Measurement of Auxiliary Resonant Snubber at 120 W and 600 W Output

....................................................................................................................................................... 52

Figure 3.22: Photo of Thermal Measurement Point of Output Inductor....................................... 53

Figure 3.23: Thermal Measurement of Output Inductor at 120 W Output and 600 W Output .... 53

Figure 3.24: Photo of Thermal Measurement Point of Power Stage Switches ............................. 54

Figure 3.25: Thermal Measurement of Power Stage Switches at 120 W Output and 600 W

Output ........................................................................................................................................... 54

Figure 4.1: Bode Plot of Control to Output Voltage ..................................................................... 57

Figure 4.2: Block Diagram of Standalone Controller ................................................................... 57

Figure 4.3: Bode Plot of Loop Gain and Controller ..................................................................... 58

Figure 4.4: Comparison between Continuous and Discrete Time Domain of Standalone

Controller ...................................................................................................................................... 59

Figure 4.5: PSIM Simulation of Output Waveforms .................................................................... 60

Figure 4.6: PSIM Simulation of 100% to 10% Load Step ............................................................ 61

Figure 4.7: Waveform of Output with Standalone Control .......................................................... 62

Figure 4.8: Waveform of Output During 20% to 100% Load Step with Standalone Controller .. 63

Figure 4.9: Close Up Waveform of Output with Standalone Control .......................................... 64

Figure 4.10: Schematic of Grid Tie Resonant Snubber Inverter .................................................. 65

ix

Figure 4.11: Block Diagram of Phase Locked Loop .................................................................... 66

Figure 4.12: Loop Gain of Phase Locked Loop ............................................................................ 66

Figure 4.13: PSIM Simulation of Phase Locked Loop (Red: Input, Blue: Output)...................... 67

Figure 4.14: Bode Plot of Control to Inductor Current ................................................................. 68

Figure 4.15: Grid Tie Control Block Diagram.............................................................................. 69

Figure 4.16: Comparison between Continuous and Discrete Time Domain of Grid Tie Controller

....................................................................................................................................................... 71

Figure 4.17: Current Loop Gain of Grid Tie Control ................................................................... 72

Figure 4.18: PSIM Simulation of Grid Tie Control under Full Load ........................................... 73

Figure 4.19: Waveform of Output with Grid Tie Control under Full Load .................................. 76

x

TABLE OF TABLES

Table 3.1: Specification Parameters ............................................................................................. 23

Table 3.2: Auxiliary Resonant Snubber Adaptive Timing for Adaptive Case (a) ........................ 31

Table 3.3: Auxiliary Resonant Snubber Adaptive Timing for Adaptive Case (b)........................ 33

Table 3.4: Parameter Values from Design .................................................................................... 37

Table 3.5: Ideal and Measured Output Power Levels ................................................................... 50

Table 3.6: Measured Efficiency of Various Control Methods ...................................................... 50

Table 4.1: Standalone Closed Loop Operating Parameters .......................................................... 59

Table 4.2: Standalone Controller Steady State Simulation Results .............................................. 61

Table 4.3: Standalone Controller Dynamic Simulation Results ................................................... 61

Table 4.4: Measured Steady State Operating Parameters ............................................................. 62

Table 4.5: Grid Tie Current Closed Loop Operating Parameters ................................................. 72

Table 4.6: Maximum Harmonic Current Distortion in Percent of Current from IEEE Std. 1547 74

Table 4.7: Harmonic Content of Grid Tie Output Current under Full Load ................................. 77

1

1 INTRODUCTION

As renewable energy sources become cheaper and more prevalent, there is an increasing desire

for inexpensive and efficient means of converting this power to work with the existing electrical

utility grid. One common source is photovoltaics. With recent decreases in cost and government

programs such as Solarize Mass [1] and Go Solar California [2] to help further subsidize the

price, this renewable energy source is becoming affordable and practical for homeowners to

install. These incentives have help solar to be the fastest growing alternative energy source, with

growth expectations from $11B in 2005 to $51B in 2015 [3]. To take full advantage of this

renewable energy, the dc voltage from the solar panel has to be converted to ac voltage in a

highly efficient and low cost manner. In order to draw the most power out of the panel possible,

a maximum power point tracking (MPPT) algorithm needs to be implemented, which is usually

done with a dc/dc converter [3]. To work with the existing utility power grid or household

appliances that run off of ac power, a second inverter stage is needed to convert the dc to ac.

There are multiple ways that this conversion from panel voltage to utility grid can be

implemented, from the traditional central string inverter to the microinverter to the

microconverter with a centralized dc/ac inverter. Previously, the most popular architecture is the

traditional central string inverter, but a large amount of generated energy is wasted due to limited

power optimization. Microinverters have been introduced to overcome this issue, but, due to

high additional part count, the cost is prohibitive for higher power level applications. The

microconverter with centralized inverter has the potential to overcome these issues, but they have

not been commercially yet developed due to the additional complexity and cost.

2

1.1 TRADITIONAL CENTRAL STRING INVERTER

Traditionally, a single dc/dc and dc/ac converter are used to convert the dc energy from the solar

panel to ac power that can be connected to the utility grid [4]. There are many commercial

products currently available from various manufactures, such as Power-One Aurora Uno Series

and SMA Sunny Boy Series[5, 6]. This is schematically shown in Fig. 1.1.

dc/dcMPPT

Controldc/ac AC Grid

Figure 1.1: Traditional Central String Inverter

Due to the minimal additional components, this architecture has the benefits of low cost and

simple installation. By connecting all of the panels in series, the total power of the system is

limited by each individual panel. Thus, one single shaded panel is able to cause large reductions

in total output power. Since partial shading on the solar panels is common, the output power of

the system is often times significantly less than the available power generated.

3

1.2 MICROINVERTER

The most efficient way to optimize the power delivery for a photovoltaic installation is to have a

dedicated maximum power point tracking converter that is attached to each individual solar

panel. Currently this is achieved with microinverters, which are small inverter modules that

perform both the MPPT and dc/ac inversion for a single solar panel. There are two ways that the

microinverter can be implemented, a two-stage solution that is similar to the traditional central

string inverter (Fig. 1.2 a), or a one-stage solution that performs both the MPPT and dc/ac

inversion at once (Fig. 1.2 b).

dc/dcMPPT

Controldc/ac AC Grid

dc/acMPPT

ControlAC Grid

Case (a) Two Stage

Case (b) One Stage

Figure 1.2: Microinverter

By reducing the total components with the elimination of a stage the one stage solution generally

achieves higher efficiency. This requires a large electrolytic capacitor bank since the double line

frequency ripple from the ac grid can decrease the available power from the solar panel that is

4

delivered to the load. The large capacitor reduces lifetime and reliability since these inverters

generally tend to operate outdoors where there are large temperature variations. Many

commercial products are currently available, such as Power-One Aurora Micro and Solarbridge

Pantheon II for the two stage solution and Enphase for the one stage solution [7-9]. While both

implementations allow for high efficiency and power optimization for each panel, the cost is

drastically increased for large solar panel installations due to the dedicated dc/ac inverter for

each panel.

1.3 MICROCONVERTER WITH CENTRALIZED INVERTER

In order to maintain the solar panel power optimization while keeping the part count and cost

low, the microconverter with centralized dc/ac inverter has been proposed, shown in Fig. 1.3.

This architecture has the benefits of individual MPPT control for each panel while minimizing

additional parts count by only using one dc/ac inverter.

dc/dcMPPT

Control

dc/dcMPPT

Control

dc/ac AC Grid

Figure 1.3: Microconverter with Parallel Connection

5

The only commercial product currently available that utilizes this implementation is Texas

Instruments (formally National Semiconductor) SolarMagic. Unlike Figure 3, the dc/dc

converters in the TI SolarMagic are connected in series to the dc/ac inverter as opposed to

parallel [10]. The problem with series connected dc/dc converters is that many are needed in

order to reach voltages high enough for grid connection. This problem is solved with parallel

connections, but this requires less efficient high voltage gain dc/dc converters [11, 12].

1.4 INVERTER REQUIREMENTS

All of these implementations require inverters that operate at high efficiency while minimizing

cost and conform to various standards in order to be attached to the utility grid. Traditional full

bridge inverters, while the most simple to implement, have many issues such as low efficiency,

large size, high cost, and generation of electronic noise. In order to solve these problems and

take full advantage of improved architecture designs like the microinverter and microconverter

with central dc/ac inverter, improvements need to be made on the inverter stage.

6

1.5 HIGH EFFICIENCY HARD SWITCHING INVERTERS

One popular way to limit the losses of the inverter is to minimize the switching losses by

reducing the number of high frequency pulse with modulated (PWM) switches. Since the

switching losses are a major source of loss the efficiency of the converter is improved by

minimizing the number of switches operating at high frequency.

DC AC

Figure 1.4: Dual Buck Inverter Schematic

The dual buck inverter shown in Fig. 1.4 achieves this by having two separate buck converters,

with one generating the positive and the other generating the negative line cycle. This allows

only two high frequency PWM switches to run at any given time, which allows the inverter to

achieve a peak efficiency of 99% [13]. By utilizing two separate converters, this topology

suffers many drawbacks such as poor magnetic utilization, zero crossing distortion, and large

common mode noise from the unipolar style switching. Attempts to fix these problems reduce

the zero crossing and magnetic utilization issues, but these drawbacks still cause major problems

[14].

7

DC AC

Figure 1.5: H5 Inverter Schematic

A topology that was developed by SMA to eliminate the common mode noise while achieving

high efficiency by minimizing high frequency switches is the H5 inverter shown in Fig. 1.5 [15].

By adding an additional switch before a unipolar switching full bridge converter, the common

mode noise issue is eliminated. But, this topology requires higher loss isolated gate bipolar

transistors (IGBTs) with fast body diodes for the low frequency switches, and along with an

extra semiconductor device the number of parts and cost are increased. This causes the

efficiency to drop slightly with a reported peak of 98.7% for a 6 kW system under ideal

operating conditions [6]. Attempts to improve the drawbacks of the H5 with topographies such

as the H6 improve the efficiency by eliminating the IGBTs with more efficient MOSFETs, but

the extra switch needed to eliminate the common mode noise further increases the high costs and

limits the efficiency [16]. In order to maintain the high efficiency of the dual buck inverter while

eliminating the common mode noise, new topologies have been derived from these circuits, but,

like the dual buck, they suffer from poor magnetic utilization and high part count, which increase

the size and cost [17].

8

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

CDC

Figure 1.6: HERIC Inverter Schematic

Another topology that further improves the bipolar switching while eliminating the common

mode noise issue is the highly efficient and reliable converter (HERIC), shown in Fig. 1.6, which

works by having two of the four power stage switches operate at PWM during half of the line

cycle while the auxiliary branch of a switch and diode that serve as the inductor current

freewheeling path [18]. This topology is able to achieve very high efficiency, with measured

peak efficiency of 99% at around 1 kW output in a design that employed SiC JFETs as switches

[19]. This topology, also, has the added benefit of no common mode noise and minimal

additional components. There are some slight downsides though, with the auxiliary diodes

required to be ultrafast, which, along with licensing fees from the patent, increase the cost.

1.6 SOFT SWITCHING INVERTERS

Another way to improve the efficiency of an inverter is to eliminate the switching loss with

auxiliary resonant snubbers. Originally designed to commutate thyristors, resonant snubbers

were found to improve the efficiency of inverter circuits since they eliminated the switching

losses of the power stage switches [20]. Unlike hard switching inverters, the additional

components conduct less current than the power stage devices, which allow them to be smaller,

cheaper, and more efficient.

9

1.6.1 Auxiliary Resonant Snubber with Capacitor Reset

The first auxiliary resonant snubber was developed by General Electric to eliminate switching

losses, limit device stresses, and allow higher frequency switching which gave a smaller output

filter and overall size, shown in Fig. 1.7 [21-24]. By utilizing an inductor to store the energy that

would normally become the switching losses, the resonant snubber is able to eliminate the losses

and reduce stress across the device by limiting the voltage and current slew rates. The inductor

is reset with a capacitor so the added energy in the snubber is delivered to the load instead of

converted into a loss. Unlike the hard switching inverter, the additional components in the

auxiliary resonant branch do not conduct as much average current as the power stage

components, which allows them to be smaller. There are some disadvantages with this topology

though, with the resonant inductor reset capacitors voltage balancing and large size, increasing

the size and cost of these components. The converter also suffers from complicated control for

zero voltage switching and additional circulating currents caused by the auxiliary branch that

increase losses.

DC

Csp

Csp

Q1 C1

Q2 C2

Q3 C3

Q4 C4

Q5 C5

Q6 C6

QA

QB

QC

ACGrid

Figure 1.7: Auxiliary Resonant Snubber with Capacitor Reset Schematic

10

1.6.2 Auxiliary Resonant Snubber with Coupled Magnetic Reset

By replacing the reset capacitor with a coupled inductor, the voltage balancing issue is

eliminated and the size and circulating current losses are reduced, as shown in Fig. 1.8 [25, 26].

This modification allows the control to be simplified, which reduces the additional losses

associated with the resonant snubber [27-29]. By splitting the coupled magnetics into two

separate components, their size can be further reduced, which eliminates the need for saturable

inductor snubbers to prevent unexpected magnetizing current circulating loops [30]. These

modifications allow the auxiliary resonant snubber with coupled magnetic reset to reach peak

efficiency of 99.26% at about 4 kW [31].

DC

C1Q1

C2Q2

1

n

QA

QA

AC

C3Q3

C4Q4

1

n

QC

QD

DD

DCDA

DB

Lo1 Lo2

Figure 1.8: Auxiliary Resonant Snubber with Coupled Magnetic Reset Schematic

11

1.6.3 Auxiliary Resonant Snubber with No External Reset

While an ideal topology for higher power levels, the coupled magnetic reset loses its advantages

for lower power levels that residential solar panel installations typically operate at due to the

high part count, bulky size, and loss from the auxiliary resonant snubber parasitics. To overcome

these issues, the auxiliary resonant snubber without external reset (auxiliary resonant snubber)

was developed, shown in Fig. 1.9, where the auxiliary resonant snubber magnetics is reset by the

bipolar switching of the power stage switches [32, 33].

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

CDC

C1

Lr

C3

C4C2

Figure 1.9: Auxiliary Resonant Snubber with No External Reset

This topology has the benefits of maintaining the simple auxiliary control from the coupled

magnetic reset while drastically reducing the number of components and size. By removing the

coupled inductors the voltage clamping across the auxiliary branch is removed. The reverse

recovery of the diode and parasitic capacitances in the auxiliary branch cause a high voltage

overshoot that requires a voltage clamping circuit [34, 35]. This problem has limited the

attempts to improve the efficiency and performance of this converter [36-38]. With the recent

advancement in high voltage SiC Schottky diodes and GaN FETs, these issues with the resonant

snubber can be minimized and possibly eliminated [39], allowing the auxiliary resonant snubber

to achieve high efficiency like the cutting edge hard switching topologies for lower power levels

while minimizing additional parts and cost.

12

1.7 GOAL AND SCOPE OF THESIS

The goal of this thesis is to take advantage of new semiconductor materials and novel control

techniques of the auxiliary resonant snubber to allow the inverter to achieve high efficiency

while minimizing additional parts and maintaining simple control. The basic operation of the

resonant snubber is presented in Section 2 along with a demonstration on how the inverter

achieves zero voltage switching (ZVS) while proposing techniques to minimize additional

circulating currents without any additional sensors or parts. In Section 3, a detailed design of all

of the components and parameters of a 600 W prototype and experimental results to verify the

inverter performance are described. A design and experimental test of standalone and grid tie

control to demonstrate that the auxiliary resonant snubber does not add any additional

complexity to closed loop control is discussed in Section 4. Section 5 is a summary of the results

of the design and experimental results and a discussion on potential future work to further

improve the resonant snubber inverter and overcome limitations of current inverters.

13

2 RESONANT SNUBBER INVERTER BASIC OPERATION

By utilizing the bipolar switching action of the power stage switches, the auxiliary resonant

snubber inverter is able to have a significant size reduction of the additional components when

compared to other auxiliary resonant snubber topologies. This allows it to be an attractive

alternative to unipolar style hard switching inverters for the 100 W to few kilowatts range. By

having the additional components handle less current than the power stage, the resonant snubber

inverter has the potential to improve over existing cutting edge inverters since the additional

parts can allow the converter to be cheaper, smaller, and more efficient.

2.1 OPERATING MODES

There are two conditions that the auxiliary resonant snubber inverter can be in when switching

occurs. The first is when the load current is negative and hurts ZVS by not reducing the voltage

during dead time when no switch is on, requiring the auxiliary resonant snubber to achieve ZVS.

The second is when the load current is positive and helps ZVS without the aid of the auxiliary

resonant snubber. Since the resonant snubber is made of non-ideal parts that have losses, an

optimal design will have the resonant snubber conduct the minimum amount of current necessary

to achieve ZVS.

Figure 2.1: Resonant Snubber Inverter Schematic

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

CDC

C1

Lr

C3

C4C2

14

2.1.1 Auxiliary Resonant Snubber Control Method

The auxiliary resonant snubber works by discharging the respective capacitors C1, C2, C3, or C4

across the power stage switches before they are turned on, enabling the switch to achieve ZVS.

The control method of the auxiliary resonant snubber affects the operating modes so it needs to

be selected first.

Q1,Q4 Q2,Q3

QB

tdly

tdt

Q,Q4 Q2,Q3

QB

tdt

tdly

Case (a) Case (b)

Figure 2.2: Two Auxiliary Resonant Snubber Control Methods

There are two control methods that can be used, case (a) where the auxiliary switch turns on

before the power stage switch turns off, and case (b) where the auxiliary switch turns on after the

power stage switch turns off as shown in Fig. 2.2. Case (a) allows the dc source to charge the

resonant snubber inductor for a bit when both switches are on, which helps discharge the

capacitor and achieve ZVS easier but increases the current through the auxiliary resonant branch

and loss associated with the snubber. Case (b) eliminates the time overlap and charging current,

minimizing the current and loss that the resonant snubber components of Lr, QA and QB have, but

the ZVS window for the power stage switch is very small and greatly varies depending on the

load.

15

Q1,Q4 Q2,Q3

QB

tsn

Figure 2.3: Adaptive Control Method of Auxiliary Resonant Snubber with Case (a)

In order to maximize the benefits of both cases, an adaptive control method for the auxiliary

resonant snubber based off of case (a) is proposed, as shown in Fig. 2.3. Instead of running a

fixed time control, the time between the auxiliary switch turn on and power stage turn off (tsn) is

varied as a function of the load current. By adjusting this time, the inductance of the resonant

snubber can be selected to be ideal at low output current levels, which will limit the frequency

and peak current of the resonant snubber and in turn decrease additional losses. As the load

increases and the ZVS window changes, tsn and the charging current can be increased to allow a

fixed dead time to still achieve ZVS. Since the auxiliary resonant snubber operates like case (a)

during negative high current line conditions, ZVS is able to be easily achieved. As the load

current becomes large enough in the positive direction where it helps ZVS, the auxiliary resonant

snubber is disabled, allowing the circuit to naturally achieve ZVS without any additional losses.

This control is able to be implemented with only one sensor for the output inductor current.

Since this sensor is already required for control and protection purposes, the adaptive control

method can be thought of as sensorless.

16

Q1,Q4 Q2,Q3

QB

tsn

Figure 2.4: Adaptive Control Method of Auxiliary Resonant Snubber with Case (b)

One limitation of the case (b) control method is the small and varying ZVS window, which

requires an additional voltage sensor across each switch for any significant amount of output

current. By implementing the proposed control technique in a similar fashion as the adaptive

case (a) by varying tsn, the ZVS window can be set to occur during a constant dead time, as

shown in Fig. 2.4. This control technique keeps all of the benefits and problems associated with

case (b). While this control technique will guarantee the minimum amount of auxiliary resonant

snubber current, there will be a slight loss of ZVS during some switching states. Since no sensor

is required across the switch, this control method can also be thought of as sensorless.

17

2.1.2 Operating Mode with Positive Load Current

When load current is large enough and the dead time between the power stage switches is long

enough, the auxiliary resonant snubber is not needed since the load current can allow the

switches to achieve ZVS.

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

C1

Lr

C3

C4C2

Iload

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

C1

Lr

C3

C4C2

Iload

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

C1

Lr

C3

C4C2

Iload

t0 – t1

t1 – t2

t2 – t3

Q1,Q4

tdt

Q2,Q3

VDS Q2,Q3 VDS Q1,Q4

t0 t1 t2 t3

I

I

I

I

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

C1

Lr

C3

C4C2

Iload

t3 – t4

t4

Figure 2.5: Schematic and Timing Diagram with Positive Load Current

18

This transition occurs when the switches transition to have the dc bus voltage vary from positive

to negative across the load. As Figure 12 shows:

a) Between to – t1: The load current flows through Q1 and Q4.

b) Between t1 – t2: At t1, Q1 and Q4 turn off. As time increases, the load current causes the

capacitors C1 and C4 to charge, causing the voltage across Q1 and Q4to increase to VDC

and the capacitors C2 and C3 to discharge, which then cause the voltage across Q2 and Q3

to drop to zero.

c) Between t2 – t3: At t2, the voltage across Q2 and Q3 reach zero, causing their anti-parallel

diodes to conduct. This begins the ZVS window for Q2 and Q3.

d) Between t3 – t4: At t3, the switches Q2 and Q3 are turned on if they are MOSFETs to

reduce the conduction losses of the switches, completing the switching action. If IGBTs

are used then the antiparallel diode will conduct since it is not a bidirectional device like

a MOSFET.

By not using the auxiliary snubber to achieve ZVS between t1 and t2, the discharge time of the

output capacitors is extended slightly, but the additional losses that occur from the resonant

snubber conducting are eliminated. When the magnitude of the load current is large enough, this

is not a problem. However, as the current becomes very small, this time increases, requiring the

auxiliary resonant snubber to be enabled to achieve ZVS even though the line current is positive.

19

2.1.3 Operating Mode with Negative Load Current

When the load current is in the opposite direction, the auxiliary resonant snubber is needed to

achieve ZVS. The basic operating principle is that the net current at the switching nodes needs

to change direction for ZVS to be achieved, which the resonant snubber achieves.

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

C1

Lr

C3

C4C2

Iload

t0 – t1

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

C1

Lr

C3

C4C2

Iload

t1 – t2

Isnubber

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

C1

Lr

C3

C4C2

Iload

t2 – t3

I

I

I

I

Isnubber

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

C1

Lr

C3

C4C2

Iload

t3 – t4

Isnubber

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

C1

Lr

C3

C4C2

Iload

t4 – t5

Isnubber

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

C1

Lr

C3

C4C2

Iload

t5 – t6

Figure 2.6: Schematic with Negative Load Current

20

Q2,Q3 Q1,Q4

VDS Q1,Q4 VDS Q2,Q3

t0 t1

QB

t2 t3 t4 t5 t6

Iload

Isnubber

Figure 2.7: Timing Diagram with Negative Load Current and Case (a) Control

21

This transition occurs when the switches transition to have the dc bus voltage vary from negative

to positive across the load. As Figure 13 and Figure 14 show:

a) Between to – t1: The load current flows through Q2 and Q3.

b) Between t1 – t2: The switch QB is turned on at t1, which allows Lr to begin conducting

current as the anti-parallel diode of QA turn on. Before Q2 and Q3 are turned off, Lr is

charged by the dc bus, which allows ZVS to be achieved more easily. Q2 and Q3 are

turned off during this time, but the anti-parallel diodes of Q2 and Q3 conduct since the

load current is still larger than the snubber current.

c) Between t2 – t3: At t2, the snubber current becomes larger than the load current. This

causes the net direction of the current at switches to change, which causes the voltage

across Q2 and Q3 to rise to VDC and the voltage across Q1 and Q4 to drop to zero.

e) Between t3 – t4: At t3, the voltage across Q1 and Q4 reach zero and their anti-parallel

diodes start to conduct. This begins the ZVS window.

d) Between t4 – t5: At t4, Q1 and Q4 turn on with ZVS and the dc voltage across the load and

auxiliary resonant snubber changes direction. The current through Lr decreases to zero

and the anti-parallel diode of QA prevents any more current to go through the auxiliary

branch.

e) Between t5 – t6: At t5, QB is turned off under zero current condition, completing the

switching action.

By placing external capacitors across each power stage switch, the resonant time can be more

predictable and consistent between switches due to the highly nonlinear and variation of the

internal output capacitance of each switch. If the capacitance is large enough, it will absorb the

turn off energy, which means that all of the switching losses can be minimized along with the

turn on loss eliminated from the auxiliary resonant snubber to the point where they are

negligible. This increase in capacitance also requires larger snubber current to achieve ZVS,

which increases the additional losses of the auxiliary resonant snubber, making it important to

prevent excessive external capacitances. By utilizing the diode to turn off the auxiliary resonant

snubber, QA and QB are naturally turned off, achieving zero current switching. This allows QA

and QB to be turned off without any additional losses without precise timing, simplifying the

control and minimizing additional loss. The case (b) auxiliary resonant snubber control method

22

works in a similar fashion with the exception that the primary switches are turned off before the

auxiliary switch turns on, eliminating the time where Lr is charged by the dc bus.

2.2 DESIGN LIMITATIONS

As ZVS is achieved by utilizing the auxiliary resonant snubber, there are some additional

limitations that impact the design of the inverter. In order to prevent the auxiliary resonant

snubber action from interfering with other switching actions, the effective dead time is increased

which requires higher dc bus voltages to achieve a desired output voltage. The resonant snubber

also has losses associated with the switch, diode, and inductor so excessive auxiliary resonant

currents are undesired since they decrease the efficiency of the converter. These losses increase

with higher switching frequencies. Even though the switching losses are eliminated, the

frequency cannot be drastically increased.

23

3 PARAMETER DESIGN

To verify the improvements that newer generations of semiconductor devices and proposed

auxiliary resonant snubber control improve performance, a prototype inverter was designed,

built, and tested using the adaptive case (a) and adaptive case (b) control for the auxiliary

resonant snubber. The following specifications were set to represent a typical lower power US

residential photovoltaic installation:

Table 3.1: Specification Parameters

Parameter Value

Output Voltage 240 Vrms

Output Frequency 60 Hz

Power Level 600 W

A 300 W inverter for a single photovoltalic (PV) panel was originally designed to measure the

performance with a microinverter architecture. However, it was found that the power level could

easily be increased to 600 W from the parameter selection so further tests were run at this higher

power level to verify performance for a microconverter with central inverter architecture.

Typical residential electric voltages supplied by the utility in the United States are 240 Vrms at 60

Hz with a center tap in the transformer to create the commonly used 120 Vrms, so to evenly

deliver the power form the PV panel the output is set to the full 240 Vrms a household receives.

3.1 POWER STAGE SWITCH SELECTION

Before any switches could be compared, the device parameters needed to be specified. For a 240

Vrms output, the minimum dc bus is 330 V if ideal components were used and there was no duty

cycle loss. Since both of these problems occur, as well as an additional duty cycle loss from the

auxiliary resonant snubber, a 400 V bus is selected as the maximum input voltage, which limits

24

the switch selection to the 600 V blocking range. MOSFETs were selected since they have the

lowest conduction losses and can take advantage of the higher switching frequencies. Since the

anti-parallel diode conduct during the switching process, the minority carriers need to be

removed before the resonance between the output capacitors and snubber inductor can begin. If

a slow diode was used, the additional current from the reverse recovery will drastically increase

the required dead time and peak current, causing major performance issues. These issues can be

mitigated by using faster diodes that have small reverse recovery charges. The Infineon

CoolMOS CFD2 series MOSFETs were selected due to their low channel resistance and

integrated fast body diode. By selecting a MOSFET, the conduction losses can be minimized by

turning them on during the freewheeling period. In order to select which CFD2 MOSFET would

be the best, a SPICE simulation of their body diodes were compared using a double pulse test at

3.53 A using models provided by Infineon since the datasheets lacked enough information to

make a fair comparison.

Figure 3.1: Schematic of Body Diode Reverse Recovery Comparison

25

Figure 3.2: MOSFET Body Diode Reverse Recovery Comparison with Double Pulse Test

The 110 mΩ IPB65R110CFD, 190 mΩ IPB65R190CFD, 310 mΩ IPB65R310CFD, and 420 mΩ

IPB65R420CFD CFD2 MOSFET body diode reverse recovery are compared using the results

from the simulation as shown in Fig. 3.2. For contrast, the 225 mΩ IPB65R225C7 and 95mΩ

IPB65R095C7 from the Infineon C7 series MOSFETs are simulated as well since their channel

resistances are much lower than the CFD2 but lack the fast body diode. Based upon data from

the datasheets, it appears that the 110 mΩ IPB65R110CFD is the best. However, its higher

reverse recovery charge causes problems by severely extending the time that the resonant

26

snubber conducts, causing the dead time to become too large and eliminating the benefit of using

a device with a smaller channel resistance. With the best combination of low reverse recovery

charge and channel resistance the 310 mΩ IPB65R310CFD is selected as the power stage

MOSFET.

3.2 AUXILIARY RESONANT SNUBBER CAPACITOR

Once the power stage switch is selected, the output capacitance can be selected to have a value

that is large enough to eliminate the majority of the turn off loss of the MOSFET. From the

datasheet of the IPB65R310CFD, the output capacitance at 75 V is about 100 pF so a

capacitance of about ten times larger is selected. Since this capacitance is significantly larger

than the output capacitance the turn off loss is absorbed then delivered to the load, eliminating

most of this loss. Due to the limited values of capacitors available from manufactures, a 1.12 nF

capacitor is constructed by placing two 560 pF capacitors in parallel. Since they handle high

currents in the power stage and large variations in capacitance based on operating temperature is

undesired, ceramic NP0/C0G capacitors are used.

27

3.3 AUXILIARY RESONANT SNUBBER INDUCTOR FOR ADAPTIVE CASE (A)

In order to minimize the peak current and frequency of the snubber current, the resonant inductor

needs to have a large inductance, which will help to reduce the additional losses incurred by the

circulating current. If the inductance is too high, the resonant snubber action would cause

excessive dead time requirements, which would force the switching frequency to be low and

limit the performance of the inverter. Figure 3.3 shows the relationship between the peak current

of the auxiliary resonant snubber current with respect to different Lr inductances.

Figure 3.3: Resonant Snubber Current caused by Lr

𝐼𝐿𝑟(𝐶 𝑎𝑛𝑑 𝐿𝑟 𝑑𝑒𝑝𝑒𝑛𝑑𝑒𝑛𝑐𝑒) =𝑉𝐷𝐶

√𝐿𝑟

𝐶𝑜𝑠𝑠

With a fixed dc bus voltage VDC and a capacitance Coss that is equal to the external capacitor C1,

C2, C and C4, the resonant inductance Lr causes an exponential increase in the resonant snubber

28

current ILr as the inductance is decreased. For lower inductances, there is a large change in peak

current for small changes in inductance, but the change in peak current decreases as the

inductance increases. Due to the adaptive control method for the auxiliary resonant snubber, the

inductance selected only needs to achieve ZVS for when the load current is below 0.5 A. When

the load current increases above 0.5 A, the turn on time tsn of the auxiliary resonant snubber will

be increased to turn on earlier, which will charge the resonant inductor enough to allow the

switches to still achieve ZVS.

Figure 3.4: PSIM Simulation of Switching Action when Iout is 0.5 A

From these requirements, an inductance of 40 μH is selected using a PSIM simulation shown in

Fig. 3.4 and verified with experimental tests, which allows only a modest increase in current and

a reasonable dead time of 535 ns.

29

𝑓𝑠𝑛𝑢𝑏𝑏𝑒𝑟 =1

2𝜋√𝐿𝑟𝐶𝑜𝑠𝑠

The frequency of the current through the inductor fsnubber is inversely proportional to the values of

the resonant inductor and capacitor. With a capacitance of 1.12 nF and inductance of 40 μH, the

snubber resonant current frequency is about 750 kHz. From simulation, the peak resonant

current is 5 A and the RMS current is 0.63 A. To keep the losses of the inductor down while

maintaining a reasonable size, a RM8/I sized 3F35 core from Ferroxcube was chosen. In order

to give an inductance of 40 μH, 42 turns of 175/46 litz wire was used, which was achieved using

only half of the core.

30

3.4 ADAPTIVE AUXILIARY RESONANT SNUBBER CONTROL TIMING FOR

ADAPTIVE CASE (A)

With the large auxiliary inductor, the firing angle of the auxiliary resonant snubber has to be

modified if the load current is above 0.5 A in order to achieve ZVS. From the simulation results

shown in Fig. 3.5, it is shown that tsn has to be modified every 0.5 A.

Figure 3.5: PSIM Simulation of Switching Action for Adaptive Case (a) Control when Iout is 3.5

A

31

Table 3.2: Auxiliary Resonant Snubber Adaptive Timing for Adaptive Case (a)

Load Condition Simulation Turn

On Delay (tsn)

Experimental

Turn On Delay

(tsn)

0 A – 0.5 A 0 ns 60 ns

0.5 A – 1.0 A 60 ns 120 ns

1.0 A – 1.5 A 120 ns 180 ns

1.5 A – 2.0 A 190 ns 250 ns

2.0 A – 2.5 A 260 ns 310 ns

2.5 A – 3.0 A 340 ns 370 ns

3.0 A – 3.5 A 420 ns 420 ns

Since the PSIM simulation is ideal and does not include the reverse recovery of the body diode,

propagation delays, component tolerances, and timing mismatches between switches, a 60 ns

margin is added. When the load current is high the experimental turn on delay margin is reduced

since the additional margin caused the turn on time to enter the previous pulse with modulation

period of the digital controller. The delay margin required to achieve ZVS is also reduced as the

load current increases since the resonant current is able to remove the minority charges of the

body diode faster. This loss of tsn causes a slight loss of ZVS, but the voltage across the switch is

measured to only be around 40 V so the additional losses are minimal. This control is

implemented by using a lookup table from the output inductor current during the switching

action and the turn on delay time is adjusted accordingly.

32

3.5 AUXILIARY RESONANT SNUBBER INDUCTOR FOR ADAPTIVE CASE (B)

To allow a fair comparison between adaptive case (a) and adaptive case (b), the same dead time

of 535 ns is used. From simulation, it is found that when the resonant inductance is 15 μH case

(b) works when tsn is equal to zero.

Figure 3.6: PSIM Simulation of Switching Action for Adaptive Case (b) Control when Iout is 3.5

A

33

Table 3.3: Auxiliary Resonant Snubber Adaptive Timing for Adaptive Case (b)

Load Condition Simulation Turn

On Delay (tsn)

Experimental

Turn On Delay

(tsn)

0 A- 0.5 A 130 ns 70 ns

0.5 A – 1 A 130 ns 70 ns

1.0 A -1.5 A 130 ns 70 ns

1.5 A – 2.0 A 100 ns 40 ns

2.0 A – 2.5 A 90 ns 30 ns

2.5 A – 3.0 A 70 ns 10 ns

3.0 A – 3.5 A 0 ns 0 ns

For currents below 3 A, tsn is adjusted to allow the ZVS window to occur without modifying the

dead time. To compensate for the reverse recovery of the body diode, a 60 ns margin is added.

As the load current reached its peak values the 60 ns margin was found to be excessive, so it was

reduced to allow the converter to achieve ZVS. Unlike the adaptive case (a) control, the

propagation delays, component tolerances, and timing mismatches cannot be compensated so

these variations can lead to a slight loss of ZVS.

3.6 AUXILIARY RESONANT SNUBBER SWITCH

In order to minimize the losses associated with the auxiliary branch and to operate with the high

frequency resonant currents, Gallium Nitride MOSFETs (GaN FETs) are selected as the

auxiliary resonant snubber. The switch needs to block the dc bus voltage, which creates a

specification for the maximum blocking voltage of 400 V. Due to the limited availability of high

voltage GaN FETs, Transphorm’s TPH3006 is selected.

34

D

G

S(K) S

GaN

Si

Figure 3.7: Cascade Configuration of TPH3006

GaN FETs, like the TPH3006, are depletion mode devices, which mean that they are normally on

and have to be driven off. To modify them to behave like a traditional power MOSFET and

operate in enhancement mode, a low voltage and highly efficient silicon FET is connected in

series as shown with Fig. 3.7. Called a cascade configuration, this allows the GaN FET to

operate as an enhancement mode device while minimizing additional parasitic elements. This

silicon FET also has a built in body diode with a minimal reverse recovery charge, which can be

used as the diode in the auxiliary resonant snubber to reduce additional parts and cost [40]. This

configuration has some downsides since the controllable gate is not connected to the GaN gate.

This means that the turn-on speed of the device cannot be controlled, and, with the parasitic

inductances that are added with the TO-220 package, severe voltage ringing is a major problem.

These problems are eliminated by the zero switching from the auxiliary resonant snubber since

the current slew rate is set by the resonant inductor current source, removing the voltage

overshoot issues and making this application ideal for the TPH3006.

35

3.7 SWITCHING FREQUENCY

After selecting a dead time the switching frequency can be chosen. Since the switching losses are

eliminated, the switching frequency can be increased without significant additional losses, but

the conduction losses of the resonant snubber prevent the frequency from being increased too

high. The switching frequency was selected to be 40 kHz, which made the dead time equivalent

to 2.1% of the switching period. Once the design was finalized and experimental results were

run, the efficiency was found to decrease by 0.07% as the switching frequency was increased to

50 kHz, verifying the original design switching frequency as an optimal value.

3.8 DC BUS VOLTAGE

Once the switching frequency was set, the dc bus voltage could be specified. It is ideal to keep

the dc bus as low as possible, which will allow the modulation index and efficiency to be as high

as possible. From the PSIM simulation, it is found that the entire switching action requires a

worst case 915 ns for adaptive case (a) control.

𝐷𝑚𝑎𝑥 = 1 − 𝑡𝑑 𝑒𝑞𝑢𝑓𝑠𝑤

𝑉𝑜

𝑉𝑑𝑐= 𝑀 = 2𝐷𝑚𝑎𝑥 − 1

With a maximum equivalent dead time (td equ) equal to 915 ns, the minimum dc bus voltage that

can give a 240 Vrms output voltage is 366.2 V. In order to give an additional margin for voltage

drop from losses and approximations in the design model, the dc bus is selected to be 370 V.

This voltage is much higher than typical PV panel voltage, so the MPPT dc/dc stage will need to

boost the voltage.

36

3.9 OUTPUT FILTER

The output inductor has to filter out the switching noise on the output and keep the load current

relatively constant throughout the switching interval. By having a large inductance, the ripple

current will be minimized, which will decrease the core losses associated with the output

inductor. But in order to have a large inductance, a bulky core with many turns will be required,

causing the wire length, copper losses, size, and cost to all increase.

𝐿 =𝑉𝑑𝑐 − 𝑉𝑜

𝐼𝑜∆𝑖𝑇𝑠𝐷𝑚𝑎𝑥

To compare the tradeoff and improve the efficiency of the converter, two inductors were tested, a

1.76 mH which gave a 12% current ripple on the output inductor, and 0.88 mH, which gave a

24% current ripple. From an open loop experimental test, the circuit containing the 1.76 mH

inductor had 0.33% higher efficiency, so it was selected as the output inductor. In order to

minimize the losses, two RM14/I sized 3C95 cores from Ferroxcube were used. Each inductor

had 62 turns of 60/36 litz wire, which gave an inductance of 0.88 mH each to yield a 1.76 mH in

total when placed in series.

𝑓𝑐 =1

2𝜋√𝐿𝑜𝐶𝑜

In order to finalize the output filter design, the cut-off frequency of the second order low pass

output filter was set to be about 10 times lower than the switching frequency of 40 kHz. Based

on availability of high voltage film capacitors, 0.68 μF was selected, which gave a cutoff

frequency of 4.6 kHz.

37

3.10 DESIGN SUMMARY

The final list of parameters used in the resonant snubber inverter design is listed in Table 4. To

help filter out any potential input noise, a 2.2 μF film capacitor was placed on the input.

Table 3.4: Parameter Values from Design

Parameter

Value

Adaptive

Case (a)

Adaptive

Case (b)

Power Stage Switch IPB65R310CFD

External Capacitance 1.12 nF

Resonant Inductance 40 μH 15 μH

Auxiliary Switch TPH3006

Switching Frequency 40 kHz

Input DC Voltage 370 V

Output Inductance 1.76 mH

Output Capacitance 0.68 μF

Input Capacitance 2.2 μF

3.11 POWER STAGE HARDWARE TEST SETUP

In order to verify the design, a prototype 600 W resonant snubber inverter was built. To insure

that there would be no computation issues that would impact the performance of the inverter,

Texas Instrument’s TMS320F28335 32 bit floating point DSP was used as the controller.

38

Figure 3.8: Experimental Test Setup

Figure 3.9: Experimental Test PCB

39

The dc bus voltage is supplied by two Sorensen power supplies, a 150 V XG 150-11.2 and a 330

V SGA330/15C-0AAA, that were connected in series to generate the required 370 V. The

control is powered by a 12 V auxiliary supply, a BK Precision 1672 power supply. The loads are

supplied by various FVT20020E250R0JE 250 Ω and 500 Ω 225 W power resistors from Vishay.

Since the input current has a significant double line frequency ripple that prevents simple

measurements, a Yokogawa WT1600 digital power meter is used to measure efficiency. The

oscilloscope waveforms are taken with a Teledyne LeCroy 104MXs-B Oscilloscope.

3.12 AUXILIARY VOLTAGE OVERSHOOT ISSUE

When the experimental test was first run, there was a significant voltage overshoot seen across

the drain to source of the auxiliary resonant snubber GaN FETs that prevented the input voltage

from reaching the designed value of 370 V. As the waveform shows in Fig. 3.10, when the

auxiliary resonant snubber switch turns off, a large ringing voltage occurs across the drain to

source of the GaN FET, which prevents the input voltage from reaching the design voltage of

370 V.

40

Figure 3.10: Waveform of Switching Action with Voltage Overshoot Issue

This issue is caused by the snubber inductor resonating with the parasitic output capacitance of

the auxiliary switch. This problem still occurred when the anti-parallel diodes of the resonant

snubber branch were replaced with Cree CSD01060E and Infineon IDD03SG60C SiC Schottky

diodes, which have negligible reverse recovery charge unlike traditional PN diodes.

Vg Q4

(5 V/div) Vds Q4

(200 V/div)

Isn

(5 A/div)

Vds QA

(200 V/div)

Time

(2 μs/div)

41

Figure 3.11: Waveform of Switching Action with Separate Resonant Snubber Legs

An attempt to remove the voltage overshoot issue by splitting the auxiliary resonant branch into

two independent legs was implemented, but this caused the parasitic capacitance to be equal to

the series connection of a GaN FET and SiC Schottky diode and significantly lower than the

original shared leg as shown in Fig. 3.11. While eliminating the voltage overshoot issue, the

diode allowed conduction in one direction but not the other. This caused the voltage across the

GaN FET to have a steady state voltage significantly higher than the dc bus, with the peak

voltage across the auxiliary branch equal to 459 V when the dc bus was only at 200 V. This

voltage increase prevented the inverter from operating at the designed dc bus value. With the

additional components required to implement this solution, it was found to not be an ideal

solution. To eliminate this problem, the original shared auxiliary leg with a clamping circuit to

eliminate the voltage overshoot is used instead.

Vg Q4

(5 V/div)

Vds Q4

(200 V/div)

Isn

(1 A/div) Vds QA

(200 V/div)

Time

(500 ns/div)

42

DC

Lo Ro

QBQA

Q1

Q2

Q3

Q4

CDC

C1 C3

C4C2

Lr

Co

Figure 3.12: Resonant Snubber Inverter with Clamping Diodes

The best way to eliminate the voltage overshoot problem was to place clamping diodes that

prevented the voltage across the switch from reaching voltages higher than the dc bus as shown

in Fig. 3.12. By circulating the energy until the power stage FETs switch again as opposed to

dissipating it, the clamping diodes are able to reduce the additional losses associated with

eliminating the voltage overshoot. Other attempts to limit the voltage such as RC (resistor and

capacitor), RCD (resistor, capacitor, and diode), and a saturable inductor placed across QA, QB,

and from the source of QA to ground and VDC had excessive losses that further hurt the efficiency

and caused hot spots that would limit the operating temperature range. Multiple diodes were

compared to find which one would be the best clamping diode with the goal to minimize

additional losses. After experimentally comparing Cree 2A CSD02060 and 20 A C4D20120A

SiC Schottky diodes against a traditional PN type NXP BYV29B ultrafast diode, the CSD02060

was found to give the inverter the highest measured efficiency so it was selected as the clamping

diode.

43

3.13 POWER STAGE EXPERIMENTAL RESULTS

After solving the voltage overshoot issue, the resonant snubber inverter was run to measure its

performance. As the waveforms show in Fig. 3.13 during high line current, the converter

achieves ZVS. The large negative spike across the drain to source of the GaN FET is generated

by the high voltage isolated probe and is not real. The switch is also able to achieve ZVS when

the load current is in the helping direction without the firing of the auxiliary branch, as illustrated

by the drain to source of Q4 rising smoothly from 0 V to 370 V. The effect of the clamping

diode can be seen as the auxiliary current does not return to zero after turn off. However, the

next switching action prevents the current from reaching zero since the duty cycle of the power

stage switches are so small.

Figure 3.13: Waveform of Switching Action during High Line Current

Vg Q4

(5 V/div) Vds Q4

(200 V/div)

Isn

(2 A/div)

Vds QA

(200 V/div)

Time

(500 ns/div)

44

As the waveforms show during low line current in Fig. 3.14, the converter fully achieves ZVS.

The noise generated by the switching action is significantly reduced since there is no ringing

across any of the devices observed when they change states. The effect of the clamping diode

over a longer period of time can be seen during this waveform, although the resonant snubber

current does not return to zero and the circulating energy slowly dissipating over time. This

additional current causes additional losses, which are further increased at smaller duty cycles

since there is more time for the current to circulate and energy dissipate through the loss

elements of the snubber and clamping circuitry.

Figure 3.14: Waveform of Switching Action during Low Line Current

Vg Q4

(5 V/div)

Vds Q4

(200 V/div)

Isn

(2 A/div)

Vds QA

(200 V/div)

Time

(2 μs/div)

45

The full load power condition is measured with a resistive load of 96.7 Ω, but the output power

is measured at 579 W instead of the designed 600 W since the system operates close to but not

exactly at 240 V. As the waveform shows in Fig. 3.15 of the auxiliary resonant snubber behaves

as expected with the step changes in the snubber current the adaptive control method as the

resonant current following the load current, eliminating most of the excessive currents associated

with case (a) control. Since the PSIM simulation used in the design did not include the reverse

recovery of the body diodes of the power stage MOSFETs, the experimental value for the peak

current of the auxiliary resonant snubber is higher than that found during the simulation. This

current is further increased by the clamping diode circulating currents, which also cause the

current to not be equal to zero when the auxiliary resonant snubber is not used.

Figure 3.15: Waveform of Output with Adaptive Case (a) Control and 600 W (100%) Output

Power

Iout

(2 A/div)

Isn

(2 A/div)

Vout

(100 V/div)

Time

(5 ms/div)

46

The minimum power load of 10% is measured to compare the performance when the line current

is small. As the waveform in Fig. 3.16 shows, the adaptive control of the auxiliary resonant

snubber does not adjust to achieve ZVS since the load current never becomes too high. Since the

auxiliary resonant snubber inductor was sized to operate around this power level, the additional

losses are minimized, but this extra current will reduce the light load efficiency.

Figure 3.16: Waveform of Output with Adaptive Case (a) Control and60 W (10%) Output Power

Iout

(2 A/div)

Isn

(2 A/div)

Vout

(100 V/div)

Time

(5 ms/div)

47

In order to measure the improvement that the adaptive case (a) control gives, the original non-

adaptive case (a) control was run during a full power test. As the waveform shows in Fig. 3.17,

the auxiliary resonant snubber current is significantly larger, which will cause additional losses

and hurt the converter efficiency as shown with the efficiency measurement section.

Figure 3.17: Waveform of Output with Simple Case (a) Control and 600 W (100%) Output

Power

Iout

(2 A/div)

Isn

(2 A/div)

Vout

(100 V/div)

Time

(5 ms/div)

48

The adaptive case (b) control was run as well. As the results show in Fig. 3.18, the peak and

RMS current of the adaptive case (b) is higher than the adaptive case (a). This is due to the

smaller inductance and characteristic impedance of the resonant snubber.

Figure 3.18: Waveform of Output with Adaptive Case (b) Control and 600 W (100%) Output

Power

Iout

(5 A/div)

Isn

(5 A/div)

Vout

(100 V/div)

Time

(5 ms/div)

49

3.14 EFFICIENCY MEASUREMENT

The efficiency was measured using the Yokogawa WT1600 digital power meter, with the results

shown in Fig. 3.19. Adaptive case (a) and case (b) control efficiency are compared to one

another, as well as a non-adaptive case (a) control to allow the efficiency boost of the adaptive

control to be measured.

Figure 3.19: Measured Efficiency over CEC Operating Range

0.98160.98160.9799

0.9665

0.9561

0.9183

0.97970.97920.9754

0.9594

0.9479

0.9058

0.98110.98160.9796

0.9646

0.9553

0.9198

0.9

0.91

0.92

0.93

0.94

0.95

0.96

0.97

0.98

0.99

0 100 200 300 400 500 600

Eff

icie

ncy

Output Power (W)

Measured Efficiency

Adaptive Case (a)

Case (a)

Adaptive Case (b)

50

In order to easily compare the performance of the inverter over the entire operating region, the

California Energy Commission (CEC) efficiency is calculated, which is a weighted average of

the typical power level based on the power received by a solar installation in the Southwest

United States [41].

𝑛𝐶𝐸𝐶 = 0.04𝑛10% + 0.05𝑛20% + 0.12𝑛30% + 0.21𝑛50% + 0.53𝑛75% + 0.05𝑛100%

Since the exact power level for each weighted point could not be derived from the resistor bank,

there are some slight discrepancies between the ideal and measured output power. Using the test

protocol specifications for CEC efficiency measurements, all of the measured power levels are

within the allowed tolerance band so the average efficiency can be calculated.

Table 3.5: Ideal and Measured Output Power Levels

Power

Level

Ideal Output

Power

Measured

Output Power

Measured

Output Power

Level

Tolerance

100% 600 W 578.6 W 96.4% 95%-105%

75% 450 W 464.2 W 77.4% 70%-80%

50% 300 W 318.2 W 53.0% 45%-55%

30% 180 W 169.0 W 28.2% 27.5%-

32.5%

20% 120 W 118.2 W 19.7% 18%-22%

10% 60 W 59.6 W 9.9% 8%-10%

Table 3.6: Measured Efficiency of Various Control Methods

Control Method Peak Efficiency CEC Efficiency

Adaptive Case

(a) 98.16% 97.56%

Case (a) 97.97% 97.16%

Adaptive Case

(b) 98.16% 97.53%

51

As listed in Table 3.6, the efficiency of the microinverter operated in adaptive case (a). There is

a significant improvement in peak efficiency when adaptive case (a) is compared to the simple

case (a) control and there is a slight improvement in CEC efficiency for adaptive case (a) over

the adaptive case (b) control. Adaptive case (b) control has a large variation of auxiliary

resonant snubber timing to guarantee ZVS from small resonant inductor changes, which along

with the already small ZVS window that will make production of multiple units that perform

without a significant efficiency drop due to slight loss of ZVS difficult. Adaptive case (a) has a

much smaller variation on timing from component tolerance. With this simplification in

manufacturing and slightly higher CEC efficiency, adaptive case (a) is the best control method.

The CEC efficiency of 98.16% for case (a), which when compared to the peak efficiency of

95.6% for previous work with the resonant snubber inverter [38] is a significant improvement

but is still lower when compared to high efficiency hard switching topologies that are above 99%

[19]. Since the additional losses that the resonant snubber has are mostly dependent on the input

voltage, this causes a fixed loss that drastically hurts the light load power level. In order have a

system level CEC efficiency that is equivalent to the highest industry level of 96.5% for

microinverter applications [9], the dc/dc MPPT stage would have to have a CEC efficiency of

98.9%, which is currently unavailable for the high voltage gain required.

3.15 THERMAL MEASUREMENT LOSS ANALYSIS

The temperatures of the components that have large losses are measured with a Fluke Ti40FT

thermal imager to verify their performance at different power levels. The inverter is operating

with the adaptive case (a) control method and a fan used to prevent severe temperature rises.

52

Figure 3.20: Photo of Thermal Measurement Point of Auxiliary Resonant Snubber

Figure 3.21: Thermal Measurement of Auxiliary Resonant Snubber at 120 W and 600 W Output

As the thermal measurement in Fig. 3.21 show, the temperature of the auxiliary resonant snubber

components does not vary much based on the power level, implying that the temperature rise is

primarily due to a fixed loss associated with these components. The inverter can run without a

fan, but the additional temperature rise of the devices cause the efficiency to drop off around

0.1%, so a fan was implemented to maximize the system efficiency. This fixed loss causes the

light load efficiency to drop off quickly, since the output power decreases while the loss remains

constant. This issue prevents the resonant snubber inverter from having higher efficiency at light

loads when compared to high efficient hard switching topologies since the hard switching losses

decrease with light power levels since the current is reduced while the resonant snubber loss

remains constant.

53

Figure 3.22: Photo of Thermal Measurement Point of Output Inductor

Figure 3.23: Thermal Measurement of Output Inductor at 120 W Output and 600 W Output

As the measurements in Fig. 3.23 show, the output inductor has a slight rise in temperature as the

output power and current through the device increases, but there are no significant hot spots that

cause excessive losses. Eddy currents from the magnetic flux in the metal clips of the inductor

cause the hot spot shown on the test.

54

Figure 3.24: Photo of Thermal Measurement Point of Power Stage Switches

Figure 3.25: Thermal Measurement of Power Stage Switches at 120 W Output and 600 W Output

As the thermal measurements in Fig. 3.25 show, the power stage switches have a large

temperature rise when the output power is increased. Due to the reverse recovery requirement of

the body diode, higher channel resistance MOSFETs had to be used, which limit the efficiency at

higher power levels.

55

From the thermal analysis, it can be seen that the resonant snubber causes the primary losses at

light power levels, but the power stage switches limit the efficiency as the power level is

increased to 600 W. With the devices and parameters selected, this gives a sweet spot of highest

efficiency around 500 W (Fig. 3.19), and, while performing better than previous resonant

snubber inverters, it has a lower efficiency than highly efficient hard switching topologies.

56

4 CONTROL

A large benefit of the resonant snubber inverter is that the zero voltage switching action does not

affect the plant duty cycle to output voltage and current plant transfer functions so the design of a

closed loop controlled system for standalone and grid tie applications is simple and easy to

implement.

4.1 STANDALONE MODE CONTROL

A standalone controller is needed if the solar panel installation is used in an application that

directly connects it to a specific load as opposed to a utility grid. This allows the inverter to

work in remote areas where a utility grid is not accessible, as well as serve as a backup generator

if there is a grid outage.

4.1.1 Standalone Mode Plant Model

Since the inverter is generating an ac voltage source, the control to output voltage (Gvd) transfer

function is required to allow the converter to regulate the output voltage.

𝐺𝑣𝑑 =𝑣𝑜

𝑑=

𝑉𝑑𝑐

1 + 𝑠𝐿𝑜

𝑅𝑜+ 𝑠2𝐿𝑜𝐶𝑜

57

Figure 4.1: Bode Plot of Control to Output Voltage

4.1.2 Design of Standalone Controller

A type 2 controller, which consists of a zero, a pole, and an integrator, was selected as the

standalone voltage controller. In order to give a sufficient gain at the 60 Hz line frequency to

minimize the output voltage error, a proportional resonant controller was additionally

implemented in series.

Hv(s)

Vref Gc(s) Fm Gvd(s) Vac

Figure 4.2: Block Diagram of Standalone Controller

58

𝐺𝑐(𝑠) = 𝐺𝑡𝑦𝑝𝑒2 + 𝐺𝑝𝑟 = 7501 +

𝑠

2𝜋∙1.94𝑘𝐻𝑧

𝑠 (1 +𝑠

2𝜋∙7.81𝑘𝐻𝑧)

+ 3

𝑠

2𝜋∙60𝐻𝑧

1 +𝑠

5∙2𝜋∙60𝐻𝑧+ (

𝑠

2𝜋∙60𝐻𝑧)

2

Figure 4.3: Bode Plot of Loop Gain and Controller

The loop gain Tv is calculated with the gain of the PWM generator Fm equal to 1 and the voltage

sensor gain Hv equal to 0.00501 and the two single-order low pass filters designed at 967 Hz and

1.3 kHz. As shown the Bode plots in Fig. 4.3, the crossover frequency is 480 Hz, which is well

below the switching frequency of 40 kHz. Since the controller is implemented with a digital

signal processor, the continuous s domain controller has to be converted to the discrete z domain

before the final closed loop parameters can be calculated. Using zero order hold on the inputs,

which have an exact match on staircase inputs from sampling, the controller is converted from

continuous to discrete time with a sampling frequency of 40 kHz.

59

Figure 4.4: Comparison between Continuous and Discrete Time Domain of Standalone

Controller

𝐺𝑐(𝑧) = 𝐺𝑡𝑦𝑝𝑒2(𝑧) + 𝐺𝑝𝑟(𝑧) =0.05143 𝑧−1 − 0.03818 𝑧−2

1 − 1.293 𝑧−1 + 0.2932 𝑧−2+

0.02825 𝑧−1 − 0.02825 𝑧−2

1 − 1.998 𝑧−1 + 0.9981 𝑧−2

As the conversion shows in Fig. 4.4, the continuous and discrete controller around and below the

crossover frequency of 480 Hz is equal. The system is still guaranteed to be stable as the

sampling delay at 40 kHz is sufficiently far away from the crossover frequency.

Table 4.1: Standalone Closed Loop Operating Parameters

Parameter Tv with 10% Load Tv with 100% Load

fc 481 Hz 480 Hz

Φm 48.4° 45.5°

Gm 14.4 dB 12 dB

60 Hz Gain 28.6 dB 28.8 dB

60

As the final parameters in Table 4.1 show, the system is stable with large safety margins. With a

60 Hz gain of 28.6 dB and 28.8 dB for a 10% load and 100% load, respectively, the steady state

line frequency error will be about 3.6%, which is a reasonable error for a utility scale voltage

source application.

4.1.3 Simulation of Standalone Controller

The controller design was verified in PSIM with the steady state and dynamic from 10% to 100%

load step performance measured. The worst case response occurs when the load steps from full

load to minimum load as the simulation results show in Fig. 4.5 and Fig. 4.6, and as the

simulation shows the converter is stable.

Figure 4.5: PSIM Simulation of Output Waveforms

0

-200

-400

200

400

Vout

0.1 0.12 0.14 0.16 0.18 0.2

Time (s)

0

-2

-4

2

4

Iout

Iout

Vout

61

Figure 4.6: PSIM Simulation of 100% to 10% Load Step

Table 4.2: Standalone Controller Steady State Simulation Results

Parameter Steady State 10%

Load Response

Steady State 100%

Load Response

Vout 232 Vrms 232 Vrms

Output Voltage THD 2.2% 2.2%

Output Current THD 2.2% 2.2%

Table 4.3: Standalone Controller Dynamic Simulation Results

Parameter Step Up 10% to

100% Load Response

Step Down 10% to

100% Load Response

Vpeak 363 V 478 V

Overshoot 10% 44%

Settling Time 0.2 ms 0.7 ms

The controller allows the inverter to operate within the design parameters without any problems.

While the voltage overshoot for the step down response is slightly large this overshoot behaves

like a voltage spike that are caused by surges in the utility grid due to the inverter’s quick

response. Since loads connected to the output of the inverter are designed to run off the grid, this

voltage overshoot will not cause any problems.

200

250

300

350

400

450

Vout

0.154 0.1545 0.155 0.1555 0.156

Time (s)

0

0.5

1

1.5

2

2.5

3

3.5

Iout

Iout

Vout

62

4.1.4 Experimental Results of Standalone Controller

To verify the design, the standalone controller was implemented with the 600 W prototype. The

control was implemented with a Texas Instruments TMS320F28335 DSP. Due to offsets in the

output voltage sensing the output voltage was regulated at 222 Vrms when the reference voltage

in the controller was set to 240 Vrms. To compensate for this error, the reference voltage was

increased to 255 Vrms. The total harmonic distortion was measured with a Fluke 43B Power

Quality Analyzer.

Figure 4.7: Waveform of Output with Standalone Control

Table 4.4: Measured Steady State Operating Parameters

Parameter Steady State 20%

Load Response

Steady State 100%

Load Response

Vout 236.5 Vrms 237.4 Vrms

Output Voltage THD 3.0% 2.8%

Output Current THD 2.9% 2.8%

Vout

(100 V/div)

Iout

(2 A/div) Time

(5 ms/div)

63

As the measurements show in Fig. 4.7, the controller allows the inverter to operate within the

operating specifications. Since non-ideal components are used, there is a slight increase in the

THD, but the operating parameters are well within the design criteria. In order to measure the

dynamic response, the load step was measured by connecting a circuit breaker between two

resistor banks to give a change from 486.7 Ω to 97.25 Ω, which is equivalent to a 20% to 100%

load step.

Figure 4.8: Waveform of Output During 20% to 100% Load Step with Standalone Controller

Vout

(100 V/div)

Iout

(2 A/div) Time

(2 ms/div)

64

Figure 4.9: Close Up Waveform of Output with Standalone Control

As the measurements in Fig. 4.8 and Fig 4.9 show, the controller is able to stabilize the output

voltage and reach steady state from a 20% to 100% load step in about 150 μs. There is a slight

voltage sag during the transition, but the magnitude of the output voltage never drops off too

much and recovers within 150 μs so that this behavior would not cause any problems with the

load since this time is extremely small when compared to the line frequency.

Vout

(100 V/div) Iout

(2 A/div) Time

(200 μs/div)

65

4.2 GRID TIE CONTROL

The most popular use for solar panel inverters is to convert the generated energy from the PV to

tie into the existing utility grid and to power various electrical devices that connected to the grid

or directly to the PV inverter. For residential applications, the solar-generated energy can be

used to reduce or even eliminate power bought from the utility. To deliver power to the grid,

certain standards need to be met to keep the power quality high and safe, which require a more

stringent controller as well as a need to protect the inverter from being damaged by the transients

from the grid. In order to allow the output current to satisfy the THD requirements of IEEE Std.

1547, a smaller second inductor Lg is added after the output capacitor to further filter the output

current. If the required inductance of Lg is small enough it can be implemented with the leakage

inductance of the utility transformer and inductance of the utility wire instead of an additional

component, preventing any additional cost. An external resistor is connected in series with the

capacitor to dampen the peaking effect it has on the control transfer functions, which left

undamped prevent the converter from stabilizing. These changes to the inverter are shown in

Fig. 4.10.

Figure 4.10: Schematic of Grid Tie Resonant Snubber Inverter

DC

Lo

QBQA

Q1

Q2

Q3

Q4

CDC

C1

Lr

C3

C4C2

Co

Lg

AC

+

vac

-

iac ig

ESR

66

4.2.1 Phase Lock Loop

Before the grid tie controller can be designed, a phase lock loop needs to be designed to allow

the controller to synchronize with the grid line frequency. This is achieved with a simple phase

locked loop, with the sinusoidal output used to generate the reference current for the current loop

controller.

Vgrid LPF Kp

ω=2πf

1/s cos(θ)

sin(θ) Vsync

Figure 4.11: Block Diagram of Phase Locked Loop

Figure 4.12: Loop Gain of Phase Locked Loop

67

By using a second order low pass filter (LPF) with a cutoff frequency of 20 Hz and a damping

ratio of 0.7 along with a gain Kp of 60, the crossover frequency is found to be at 9.37 Hz with a

phase margin is 50° and a gain margin of 9.34 dB. To verify the design, the phase locked loop is

simulated in PSIM.

Figure 4.13: PSIM Simulation of Phase Locked Loop (Red: Input, Blue: Output)

As the simulation results in Fig. 4.13 show, the output synchronizes to the input frequency within

0.2 sunder a worst case of a 180° input phase shift. In order to prevent problems with startup,

the controller will have a delay longer than the synchronization time before gating occurs to

allow the phase lock loop to properly lock to the grid frequency.

4.2.2 Grid Tie Plant Model

Since the output voltage is set by the utility grid, the output current is controlled by the inverter,

which requires the control to output current (Gid) transfer function to design a proper controller.

Before Gid can be derived, the output current sensor location needs to be selected since the plant

can dramatically change based on its location. To allow the inverter to work interchangeably

between standalone and grid tie mode, the output voltage and current sensors are left in the same

place of across the output capacitor and through Lo. With this current sense location, the plant

68

transfer function simplifies to a dependence only on the input voltage, output inductor Lo, and

output inductor resistance rLo.With an inductance of 1.76 mH and a measured series resistance of

255.5 mΩ, the plant control to output current transfer function of the resonant snubber inverter

can be derived, as shown with Fig. 4.14. As the inductor current equation shows, the output

current also has an undesirable voltage feed-forward term Giv, which needs to be compensated in

the control design.

𝑖𝑎𝑐 = 𝐺𝑖𝑑𝑑 + 𝐺𝑖𝑣𝑣𝑎𝑐

𝐺𝑖𝑑 =𝑉𝑑𝑐

𝑟𝐿𝑜 + 𝑠𝐿𝑜

𝐺𝑖𝑣 =1

𝑟𝐿𝑜 + 𝑠𝐿𝑜

Figure 4.14: Bode Plot of Control to Inductor Current

69

4.2.3 Control Block Diagram

To design the compensators for the current loop and undesirable feed-forward term, the control

structure needs to be defined. By carefully placing their location as shown in Figure 4.15 the

plant model Gid can be simplified for simple compensator design and Giv can be reduced to a

constant scalar value independent of any dynamic term.

vac Hv/PLL

kxIref

Gi

Hi

Fm Gid

iac

Giv

ig

sCo

Gc

Figure 4.15: Grid Tie Control Block Diagram

The current loop is dependent on Fm, Gid, Hi, and is compensated with Gi. To compensate for the

feed-forward term, Gc is used to eliminate its effect on the output. To eliminate instability issues

that arise from the zero in the capacitor feed-forward term, an external resistor of 3.3 Ω is placed

in series of the output capacitor to increase the equivalent series resistance. Since the ripple

current through the capacitor is small, the additional losses associated by adding a resistive

element are minimal.

70

4.2.4 Current Loop Control Compensator Design

Due to the very low frequency pole that can easily lead to instability with traditional controllers,

a proportional resonant controller is selected as the current loop compensator since it does not

have an integrator and has high gain at the fundamental line frequency. Additional gain was

implemented at the third harmonic of 180 Hz and fifth harmonic of 300 Hz to help reduce the

total harmonic distortion of the output.

𝐺𝑖(𝑠) = 0.07 + 0.15

𝑠

2𝜋∙60𝐻𝑧

1 +𝑠

12∙2𝜋∙60𝐻𝑧+ (

𝑠

2𝜋∙60𝐻𝑧)

2 + 0.044

𝑠

2𝜋∙180𝐻𝑧

1 +𝑠

10∙2𝜋∙180𝐻𝑧+ (

𝑠

2𝜋∙180𝐻𝑧)

2

+ 0.01

𝑠

2𝜋∙300𝐻𝑧

1 +𝑠

10∙2𝜋∙300𝐻𝑧+ (

𝑠

2𝜋∙300𝐻𝑧)

2

Since the control is going to be implemented with a digital signal processor with a sampling rate

of 40 kHz, the continuous transfer function Gi(s) is converted to the discrete transfer function

Gi(z) using zero order hold on the inputs.

𝐺𝑖(𝑧) = 0.07 +0.001413 𝑧−1 − 0.001413 𝑧−2

1 − 1.999 𝑧−1 + −0.9992 𝑧−2+

0.001242 𝑧−1 − 0.001242 𝑧−2

1 − 1.996 𝑧−1 + −0.9972 𝑧−2

+0.00047 𝑧−1 − 0.00047 𝑧−2

1 − 1.993 𝑧−1 + −0.9953 𝑧−2

71

Figure 4.16: Comparison between Continuous and Discrete Time Domain of Grid Tie Controller

As the plots show, the controller is equal between the continuous and discrete time domains.

With the gain of the PWM generator Fm equal to 1, the current sensor gain Hi equal to 610 mV/A

with two single order low pass filter at 4 kHz and 28 kHz, and a 40 kHz sampling delay the loop

gain Ti is calculated.

72

Figure 4.17: Current Loop Gain of Grid Tie Control

Table 4.5: Grid Tie Current Closed Loop Operating Parameters

Parameter TvValue

fc 1.38kHz

Φm 45°

Gm 11.5 dB

60 Hz Gain 55.5dB

As the Bode plot shows, the current loop is stable with sufficient safety and design margins.

73

4.2.5 Feed Forward Compensator Design

In order to eliminate the undesired feed-forward term Giv, a compensator Gc is implemented. By

sensing vac and adding the compensation after the current loop compensator as shown in the grid

tie control block diagram in Figure 55, this term can be reduced to constants and easily be

implemented [42]. Since the crossover frequency of the current loop controller is much lower

than the low pass filter of the ac voltage sensor Hv, the gain can be approximated as the passband

value.

𝐺𝑐 =1

𝐻𝑣𝑉𝑑𝑐𝐹𝑚

4.2.6 Simulation of Grid Tie Controller

The complete grid tie control was verified with a PSIM simulation as shown in Figure 4.18. The

voltage across the output capacitor vac, sensed current iac, and load current ig are measured.

Figure 4.18: PSIM Simulation of Grid Tie Control under Full Load

Ig

Vac

Iac

74

As the output waveforms show, the controller is stable and current is able to track the output

voltage and deliver power to the grid. In order for grid connected inverters to be allowed to

connect to the utility grid, they need to meet the IEEE Standard 1547 for interconnecting

distributed resources with electric power systems. One parameter that is specified and has a

large impact on the control design is the maximum total demand distortion (TDD), which is a

measurement of the total harmonic distortion of the output based in percent of the full load

fundamental current [43].

Table 4.6: Maximum Harmonic Current Distortion in Percent of Current from IEEE Std. 1547

Individual

Harmonic

Order

h < 11 11 ≤ h 17 17 ≤ h 23 23 ≤ h 35 35 ≤ h

Total

Demand

Distortion

Percent (%) 4.0 2.0 1.5 0.6 0.3 5.0

To meet these harmonic requirements with the existing controller, the additional inductor Lg is

set to 0.25 mH. With this additional inductance, the simulated current THD for full load is

measured to be 3.4%, which satisfies the standards requirement.

𝑇𝐷𝐷 =√𝐼ℎ𝑎𝑟𝑚𝑜𝑛𝑖𝑐 2

2 + 𝐼ℎ𝑎𝑟𝑚𝑜𝑛𝑖𝑐 32 + 𝐼ℎ𝑎𝑟𝑚𝑜𝑛𝑖𝑐 4

2 + 𝐼ℎ𝑎𝑟𝑚𝑜𝑛𝑖𝑐 52 + ⋯

𝐼𝐿

Even though the THD of the output current increases as the power level decreases with 15.4%

current THD for 20% power level, the TDD is only 3.5% and remains under the limits since the

harmonic content is measured with respect to the full load IL as opposed to the fundamental of

the individual power levels.

4.2.7 Experimental Results of Grid Tie Controller

To experimentally verify the grid tie control, the inverter was connected to the utility grid using a

2 kVA Square D transformer to step up the 120 V voltage to 240 V. The leakage inductance of

75

the transformer on the inverter side is measured to be 2.65 mH, which increases Lg and allows

the inductance to be much larger than the simulation value without adding any additional

components. Since the grid voltage has low frequency harmonics that do not appear in the

simulation, the controller gains were modified to allow the output current to meet the IEEE Std.

1547 TDD limits. Since these larger gains reduce the phase and gain margin, they were

incrementally adjusted to insure that the system would not become unstable. The controller was

able to be experimentally verified, with the output waveforms show in Fig. 4.19.

𝐺𝑖(𝑠) = 0.23 + 0.1

𝑠

2𝜋∙60𝐻𝑧

1 +𝑠

10∙2𝜋∙60𝐻𝑧+ (

𝑠

2𝜋∙60𝐻𝑧)

2 + 0.09

𝑠

2𝜋∙180𝐻𝑧

1 +𝑠

8∙2𝜋∙180𝐻𝑧+ (

𝑠

2𝜋∙180𝐻𝑧)

2

+ 0.03

𝑠

2𝜋∙300𝐻𝑧

1 +𝑠

8∙2𝜋∙300𝐻𝑧+ (

𝑠

2𝜋∙300𝐻𝑧)

2

𝐺𝑖(𝑧) = 0.23 +0.000942 𝑧−1 − 0.000942 𝑧−2

1 − 1.999 𝑧−1 + −0.9991 𝑧−2+

0.00254 𝑧−1 − 0.00254 𝑧−2

1 − 1.996 𝑧−1 + −0.9965 𝑧−2

+0.001409 𝑧−1 − 0.001409 𝑧−2

1 − 1.992 𝑧−1 + −0.9941 𝑧−2

76

Figure 4.19: Waveform of Output with Grid Tie Control under Full Load

The total harmonic distortion is measured using the Fluke 43B Power Quality Analyzer, where

the THD and individual harmonic contents measured at full load to verify that they meet the

TDD limits. With a measured voltage THD of 2.4%, the output current and voltage waveforms

meet the TDD and individual harmonic standards. These results show that the auxiliary resonant

snubber does not affect the grid tie controller, with the major obstacles in the controller design

caused by the grid voltage as opposed to noise generated by the inverter. Since this noise is not

present in the simulation, the controller gains will likely have to be significantly modified to

conform to the TDD standards.

Vac

(100 V/div)

Ig

(2 A/div) Time

(5 ms/div)

77

Table 4.7: Harmonic Content of Grid Tie Output Current under Full Load

Harmonic Percent Harmonic Percent

Ig THD 4.6% 9 0.1%

2 1.0% 10 0.4%

3 2.6% 11 0.4%

4 0.8% 12 0.5%

5 1.4% 13 1.8%

6 0.3% 14 0.5%

7 1.6% 15 0.0%

8 0.2% 16 0.5%

78

5 CONCLUSION

As highlighted in the design and demonstrated with the experimental test PCB, the resonant

snubber inverter (RSI) is able to achieve a much higher efficiency than previous resonant

snubber inverter designs while minimizing additional parts, maintaining simple control, and

eliminating electrical noise. With only four additional capacitors, one resonant inductor, and two

auxiliary switches, the additional parts and size increase compared to the traditional hard

switching inverter are minimal. These components are not in the power stage path so they can be

small and cheap, especially when compared to the size and cost of the additional components

that are required in high efficiency hard switching inverters. Currently, GaN devices are more

expensive than their Si counterparts since GaN is a new semiconductor material for high voltage

field effect transistors, but, as their cost decreases over time as fabrication processes improve, the

cost of the components for the resonant snubber inverter will reduce further. The efficiency of

the inverter is improved without any additional parts by utilizing the output current sensor, which

is required for closed loop control since the converter is able to achieve soft switching over the

entire line cycle despite the moving ZVS window without any additional circuitry or elements.

By taking advantage of the bipolar switching, the lower frequency harmonics and common mode

noise generated by the converter are naturally eliminated, which, along with the higher switching

frequency that is allowed by the soft switching, allows the output filter to easily meet the output

waveform distortion requirements.

Despite all of these benefits, there were still some drawbacks with the improved resonant

snubber inverter. When compared to high efficiency hard switching inverters, the resonant

snubber inverter is still less efficient. From the loss analysis, it is shown that the losses of the

auxiliary resonant snubber are largely independent of the power level, which causes the

efficiency to drop off at light load. As the power level increases, the losses associated with the

higher channel resistance of the fast body diode MOSFETs cause the efficiency to peak at levels

below the maximum of other topologies that are able to use lower on-state resistance switches.

The circulating currents caused by the diode clamp further reduce the efficiency of the resonant

snubber inverter.

79

From the experimental results of a 600 W prototype a peak efficiency of 98.16% and CEC

efficiency of 97.56% was measured, with a worst case THD of 3.0% for the output voltage

during a standalone test and 4.6% TDD for the output current during a grid tie test.

5.1 FUTURE WORK

While many improvements have been made on the resonant snubber inverter, there are still some

drawbacks that limit its performance. There are several directions for future research on the

resonant snubber inverter to improve over these issues.

Replace the power stage switches with newer generations of fast body diode switches that

have smaller channel resistances

Replace the auxiliary resonant snubber switches with newer generations of GaN FETs

that have smaller channel resistances and smaller output capacitances, reducing and

possibly eliminating the voltage overshoot and clamping diode losses.

Detailed analysis of external capacitance effect on tradeoff between turn-off loss and

resonant snubber loss to determine an optimal value.

80

REFERENCES

[1] Massachusetts Clean Energy Center. (2014, January 7). Solarize Mass. Available:

http://www.masscec.com/solarizemass

[2] California Energy Commision, State of California, & California Public Utilities

Commission. (2014, January 7). Go Solar California. Available:

http://www.gosolarcalifornia.ca.gov/

[3] N. Sridhar. (2011, January 7 2014). Understanding Photovoltaics and the Market Forces

Behind Them. Available: http://www.ti.com/lit/an/slva448/slva448.pdf

[4] Texas Instruments. (2011, January 7 2014). Energy Harvesting: Solar. Available:

http://www.ti.com/lit/sl/slyy027/slyy027.pdf

[5] Power-One, "UNO-2.0-I UNO-2.5-I," Datasheet, Ed., 2013-04.1 ed, 2014.

[6] SMA, "Sunny Boy 6000TL-US/7000TL-US/8000TL-US/9000TL-US/10000TL-US,"

Datasheet, Ed., 1.3 ed. Online, 2013.

[7] Power-One, "Micro-0.25-I Micro-0.3-I," Datasheet, Ed., 2013-03.8 ed, 2014.

[8] SolarBridge Technologies, "Pantheon II Integrated Microinverter," Datasheet, Ed., 1 ed,

2014.

[9] Enphase, "Enphase M250," Datasheet, Ed., 1 ed. Online, 2014.

[10] Texas Instruments. (2010, January 7 2014). AN-2122 SM3320-RF-EV Reference Design.

Available: http://www.ti.com/lit/an/snosb82e/snosb82e.pdf

[11] Z. Huiying, L. Shuhui, and J. Proano, "PV energy extraction characteristic study under

shading conditions for different converter configurations," in Power and Energy Society

General Meeting, 2012 IEEE, 2012, pp. 1-8.

[12] S. V. Dhople, J. L. Ehlmann, A. Davoudi, and P. L. Chapman, "Multiple-input boost

converter to minimize power losses due to partial shading in photovoltaic modules," in

Energy Conversion Congress and Exposition (ECCE), 2010 IEEE, 2010, pp. 2633-2636.

[13] S. V. Araujo, P. Zacharias, and R. Mallwitz, "Highly Efficient Single-Phase

Transformerless Inverters for Grid-Connected Photovoltaic Systems," Industrial

Electronics, IEEE Transactions on, vol. 57, pp. 3118-3128, 2010.

[14] P. Sun, C. Liu, J.-S. Lai, and C.-L. Chen, "Cascade Dual Buck Inverter With Phase-Shift

Control," Power Electronics, IEEE Transactions on, vol. 27, pp. 2067-2077, 2012.

[15] M. Victor, F. Greizer, S. Bremicker, and U. Hübler, "Method of converting a direct

current voltage from a source of direct current voltage, more specifically from a

photovoltaic source of direct current voltage, into a alternating current voltage," US

Patent 7411802, 2008.

[16] W. Yu, J.-S. Lai, H. Qian, and C. Hutchens, "High-Efficiency MOSFET Inverter with

H6-Type Configuration for Photovoltaic Nonisolated AC-Module Applications," Power

Electronics, IEEE Transactions on, vol. 26, pp. 1253-1260, 2011.

[17] G. Bin, J. Dominic, J.-S. Lai, C.-L. Chen, T. LaBella, and B. Chen, "High Reliability and

Efficiency Single-Phase Transformerless Inverter for Grid-Connected Photovoltaic

Systems," Power Electronics, IEEE Transactions on, vol. 28, pp. 2235-2245, 2013.

[18] H. Schmidt, C. Siedle, and J. Ketterer, "DC/AC converter to convert direct electric

voltage into alternating voltage or into alternating current," US Patent 7,046,534, 2006.

[19] B. Burger and D. Kranzer, "Extreme high efficiency PV-power converters," in Power

Electronics and Applications, 2009. EPE '09. 13th European Conference on, 2009, pp. 1-

13.

81

[20] W. McMurray, "Resonant snubbers with auxiliary switches," in Industry Applications

Society Annual Meeting, 1989., Conference Record of the 1989 IEEE, 1989, pp. 289-834

vol.1.

[21] R. W. De Doncker and J. P. Lyons, "The auxiliary resonant commutated pole converter,"

in Industry Applications Society Annual Meeting, 1990., Conference Record of the 1990

IEEE, 1990, pp. 1228-1235 vol.2.

[22] R. W. DcDoneker, O. Demirci, S. Arthur, and V. A. Temple, "Characteristics of GTO's

and High-Voltage MCT's in High-Power Soft-Switching Converters," Industry

Applications, IEEE Transactions on, vol. 30, p. 1548, 1994.

[23] R. W. A. A. De Doncker, T. M. Jahns, A. V. Radun, D. L. Watrous, and V. A. K.

Temple, "Characteristics of MOS-controlled thyristors under zero voltage soft-switching

conditions," Industry Applications, IEEE Transactions on, vol. 28, pp. 387-394, 1992.

[24] R. W. A. A. De Doncker and J. P. F. Lyons, "Method for controlling a power converter

using an auxiliary resonant commutation circuit," US Patent 5,047,913, 1991.

[25] I. Barbi and D. C. Martins, "A true PWM zero-voltage switching pole, with very low

additional RMS current stress," in Power Electronics Specialists Conference, 1991.

PESC '91 Record., 22nd Annual IEEE, 1991, pp. 261-267.

[26] Y. Xiaoming and I. Barbi, "Analysis, designing, and experimentation of a transformer-

assisted PWM zero-voltage switching pole inverter," Power Electronics, IEEE

Transactions on, vol. 15, pp. 72-82, 2000.

[27] D. Wei, D. Peng, H. Yu, F. C. Lee, and J. Lai, "A simplified control scheme for zero

voltage transition (ZVT) inverter using coupled inductors," in Power Electronics

Specialists Conference, 2000. PESC 00. 2000 IEEE 31st Annual, 2000, pp. 1221-1226

vol.3.

[28] J.-S. Lai, J. Zhang, H. Yu, and H. Kouns, "Source and Load Adaptive Design for a High-

Power Soft-Switching Inverter," Power Electronics, IEEE Transactions on, vol. 21, pp.

1667-1675, 2006.

[29] C. Jae-Young, D. Boroyevich, and F. C. Lee, "A novel inductor-coupled ZVT inverter

with reduced harmonics and losses," in Power Electronics Specialists Conference, 2001.

PESC. 2001 IEEE 32nd Annual, 2001, pp. 1147-1152 vol.2.

[30] W. Yu, J.-S. Lai, and S.-Y. Park, "An Improved Zero-Voltage Switching Inverter Using

Two Coupled Magnetics in One Resonant Pole," Power Electronics, IEEE Transactions

on, vol. 25, pp. 952-961, 2010.

[31] B. Chen, J.-S. Lai, C.-L. Chen, W. Yu, N. Kees, Z. Cong, et al., "Design and

optimization of 99% CEC efficiency soft-switching photovoltaic inverter," in Applied

Power Electronics Conference and Exposition (APEC), 2013 Twenty-Eighth Annual

IEEE, 2013, pp. 946-951.

[32] J. S. Lai, R. W. Young, G. W. Ott, Jr., C. P. White, J. W. McKeever, and D. Chen, "A

novel resonant snubber based soft-switching inverter," in Applied Power Electronics

Conference and Exposition, 1995. APEC '95. Conference Proceedings 1995., Tenth

Annual, 1995, pp. 797-803 vol.2.

[33] D. Chen, J. S. Lai, J. W. McKeever, G. W. Ott, M. B. Scudiere, C. P. White, et al.,

"Resonant snubber inverter," US Patent 5642273, 1997.

[34] J. S. Lai, R. W. Young, G. W. Ott, Jr., and J. W. McKeever, "Efficiency modeling and

evaluation of a resonant snubber based soft-switching inverter for motor drive

82

applications," in Power Electronics Specialists Conference, 1995. PESC '95 Record.,

26th Annual IEEE, 1995, pp. 943-949 vol.2.

[35] J.-S. Lai, "Practical design methodology of auxiliary resonant snubber inverters," in

Power Electronics Specialists Conference, 1996. PESC '96 Record., 27th Annual IEEE,

1996, pp. 432-437 vol.1.

[36] C. C. Chan, K. T. Chau, D. T. W. Chan, Y. Jianming, J.-S. Lai, and L. Yong, "Switching

characteristics and efficiency improvement with auxiliary resonant snubber based soft-

switching inverters," in Power Electronics Specialists Conference, 1998. PESC 98

Record. 29th Annual IEEE, 1998, pp. 429-435 vol.1.

[37] Y. Qinghong and R. M. Nelms, "A single-phase resonant snubber inverter with fixed

timing control for a UPS," in Power Electronics Specialist Conference, 2003. PESC '03.

2003 IEEE 34th Annual, 2003, pp. 1633-1638 vol.4.

[38] N. Hoshi and S. Nagata, "Dead-time compensation scheme for adjustable dead-time

controlled resonant snubber inverter," in Power Electronics and Motion Control

Conference, 2009. IPEMC '09. IEEE 6th International, 2009, pp. 1508-1513.

[39] J. S. Lai, X. Huang, H. Yu, A. R. Hefner, D. W. Berning, and R. Singh, "High current

SiC JBS diode characterization for hard- and soft-switching applications," in Industry

Applications Conference, 2001. Thirty-Sixth IAS Annual Meeting. Conference Record of

the 2001 IEEE, 2001, pp. 384-390 vol.1.

[40] Transphorm, "TPH3006PS," Datasheet, Ed., 1 ed, 2013.

[41] C. W. Ward Bower, William Erdman, Michale Behnke, Mark Fitzgerald. (2004,

Performance Test Protocol for Evaluating Inverters Used in Grid-Connected Photovoltaic

Systems. Available: http://www.gosolarcalifornia.ca.gov/equipment/documents/2004-11-

22_Test_Protocol.pdf

[42] S.-Y. Park, Park, C.-L. Chen, J.-S. Lai, and S.-R. Moon, "Admittance Compensation in

Current Loop Control for a Grid-Tie LCL Fuel Cell Inverter," Power Electronics, IEEE

Transactions on, vol. 23, pp. 1716-1723, 2008.

[43] "IEEE Standard for Interconnecting Distributed Resources With Electric Power

Systems," IEEE Std 1547-2003, pp. 0_1-16, 2003.