MTU 12V2000 DS1000Diesel Generator Set
Product highlights
380V-415V/50Hz/prime/fuelconsumptionoptimized12V2000G26F/air charge air cooling
Bene� ts— Lowfuelconsumption— Optimizedsystemintegrationability— Highreliabilityandavailabilityofpower— Longmaintenanceintervals— Optimizedratiobetweensizeandpower— Wideoperatingrangewithoutderating
Support— Globalproductsupportoffered
Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001
— GeneratorsetcompliestoG3accordingtoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards
— NFPA110
Power rating— Systemrating:800kVA— AcceptsratedloadinonestepperNFPA110— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5
Performance assurance certi� cation (PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 75%loadfactorforprimepowerapplications— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested
Complete range of accessories available— Controlpanel— Power panel— Fuelsystem— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaustsystem— Mechanicalradiator— Oversizedvoltagealternators
Emissions— Fuelconsumptionoptimized— TA-Luft,Tier2compliantandNEA(ORDE)optimizationoptionallyavailable
Certi� cations— CEcertificationoption— VDE4110Certification
Optionalequipmentandfinishingshown.Standardmayvary.Optionalequipmentandfinishingshown.Standardmayvary.
Application data 1)
Engine Fuel consump. opt. Emission opt. 2)
Manufacturer MTU MTU Model 12V2000G26F 12V2000G26F Type 4-cycle 4-cycle Arrangement 12V 12V Displacement: l 26.8 26.8 Bore: mm 135 135 Stroke: mm 156 156 Compression ratio 17.5 17.5 Rated speed: rpm 1500 1500 Engine governor ADEC (ECU 9) ADEC (ECU 9) Speed regulation ± 0.25% ± 0.25% Max power: kWm 709 709 Mean effective pressure: bar 21.2 21.2 Air cleaner dry dry
Fuel systemMaximum fuel lift: m 5 5 Total fuel flow: l/min 30 30
Fuel consumption 2)
At 100% of power rating: l/hr g/kWh 162/190 167/196 At 75% of power rating: l/hr g/kWh 124/193 127/199 At 50% of power rating: l/hr g/kWh 87/204 90/211
Lube oil systemTotal oil system capacity: l 80 80 Max. lube oil temp. (alarm): °C 103 103 Max. lube oil temp. (shutdown): °C 105 105 Min. lube oil pressure (alarm): bar 4.5 4.5 Min. lube oil pressure (shutdown): bar 4 4
Combustion air requirementsCombustion air volume: m3/s 0.79 0.91 Max. air intake restriction: mbar 40 40
Cooling/radiator system Fuel consump. opt. Emission opt. 2)
Coolant flow rate (HT circuit): m3/hr 31.6 31.6 Heat rejection to coolant: kW 290 280 Heat radiated to charge air cooling: kW 120 150 Heat radiated to ambient: kW 35 35 Fan power for mech. radiator (40°C): 34 34 Fan power for mech. radiator (50°C): 51.1 51.1 Air flow required for mech. radiator (40°C) cooled unit: m3/min 969 969 Air flow required for mech. radiator (50°C) cooled unit: m3/min 1328 1328 Engine coolant capacity (without cooling equipment): l 63 63 Radiator coolant capacity (40°C): l 59 59 Radiator coolant capacity (50°C): l 140 140 Max. coolant temperature (warning): °C 102 102 Max. coolant temperature (shutdown): °C 105 105
Exhaust systemExhaust gas temp. (after turbocharger): °C 540 505 Exhaust gas volume: m³/s 2.2 2.4 Maximum allowable back pressure: mbar 50 50 Minimum allowable back pressure: mbar 30 30
GeneratorProtection class IP23 IP23 Insulation class H H Voltage regulation (steady state) ± 0.25% ± 0.25% Rado interference class N N
1 All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
2 Emission optimized data refer to TA-Luft optimized and NEA (ORDE) optimized/Tier 2 compliant engines.
Representsstandardfeatures
Representsoptionalfeatures
Standardandoptionalfeatures
System ratings (kW/kVA)
Generator model Voltage with mechanical radiator
kWel kVA* AMPS
LeroySomerLSA49.3L9 (Lowvoltage LeroySomerstandard)
380 V 640 800 1215
400 V 640 800 1155
415 V 640 800 1113
LeroySomerLSA50.2M6 (Lowvoltage LeroySomeroversized)
380 V 640 800 1215
400 V 640 800 1155
415 V 640 800 1113
Marathon575RSL7181 (Lowvoltage Marathonstandard)
380 V 640 800 1215
400 V 640 800 1155
415 V 640 800 1113
Marathon740RSL7183 (Lowvoltage Marathonoversized)
380 V 640 800 1215
400 V 640 800 1155
415 V 640 800 1113 *cosphi=0.8
Engine
4-Cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve Fullflowoilfilters Closedcrankcaseventilation
ADECelectronicisochronousenginegovernor Commonrailfuelinjection Dryexhaustmanifold Electricstartingmotor(24V)
Fuelconsumptionoptimizedengine TA-Luftoptimizedengine Tier2optimizedengine NEA(ORDE)optimizedengine
Generator
LeroySomerlowvoltagegenerator MeetsNEMAMG1,BS5000, IEC60034-1,VDE0530, DINEN12601,AS1359 andISO8528requirements Superiorvoltagewaveform Solidstate,volts-per-Hertzregulator 4polethree-phasesynchronous generator Brushless,self-excited,self-regulating,self-ventilated Digitalvoltageregulator Anticondensationheater StatorwindingY-connected, accessibleneutral(broughtout)
ProtectionIP23 lessthan5%harmonicdistorsion 2/3 pitch stator windings Noloadtofullloadregulation ±0.25%voltageregulationnoloadto fullload InsulationclassH,utilizationacc.toH RadiosuppressionEN55011, group1,cl.B Shortcircuitcapability3xInfor10sec Sustainedshortcircuitcurrentofupto300%oftheratedcurrentforupto10seconds(LeroySomergenerator) WindingandbearingRTDs (withoutmonitoring)
ExcitationbyAREP+PMI MountingofCT´s:3x2coreCT´s Voltagesetpointadjustment±10V Sustainedshortcircuitcurrentofupto250%oftheratedcurrentforupto10seconds(Marathongenerator) Marathonlowvoltagegenerator Oversizedgenerator
Standard and optional features
Representsstandardfeatures
Representsoptionalfeatures
Cooling system
Jacketwaterpump Thermostat(s)
Airchargeaircooling Mechanicalradiator
Jacketwaterheater
Power Panel
Availablein600x600 Phasemonitoringrelay230V/400V
Supplyforbatterycharger Supplyforjacketwaterheater
Plugsocketcabinetfor230V compatibleEuro
Fuel system
Flexiblefuelconnectorsmountedto baseframe
Fuelfilterwithwaterseparator Switchablefuelfilterwithwaterseparator
Fuel cooler
Starting/charging system
24Vstarter Starterbatteries,cables,rack, disconnect switch
Batterycharger Redundantstarter2x7.5KW
Mounting system
Weldedbaseframe Resilientengineandgeneratormounting Modularbaseframedesign
Exhaust system
Exhaustbellowswithconnectionflange Exhaustsilencerwith10dB(A)soundattenuation
Exhaustsilencerwith30dB(A)soundattenuation Exhaustsilencerwith40dB(A)soundattenuation
Y-connection-pipe
Control Panel
Pre-wiredcontrolcabinetforeasy applicationofcustomizedcontroller(V1+) Islandoperation(V2) AutomaticmainsfailureoperationwithATS(V3a) Automaticmainsfailureoperation incl.controlofgeneratorandmainsbreaker(V3b) Islandparalleloperationofmultiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparallel overlapsynchronization(V5) Mainsparalleloperationofasinglegenset(V6)
Mainsparalleloperationofmultiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engineparameters Generatorprotectionfunctions Engineprotection SAEJ1939engineECU communications Parametrizationsoftware Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs
Eventrecording IP54frontpanelratingwith integratedgasket Differentexpansionmodules Remoteannunciator Daytankcontrol Generatorwindingtemperature monitoring Generatorbearingtemperature monitoring Differentialprotectionwith multi-functionprotectionrelay ModbusRTU-TCPgateway
Rolls-Royce Groupwww.mtu-solutions.com/powergen
Weights and dimensions
Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings.
Weightsanddimensionsarebasedonopenpowerunitsandareestimatesonly.Consultthefactoryforaccurateweightsanddimensionsforyourspecificengine-generatorset.
System Dimensions (L x W x H) Weight (dry/less tank)
Openpowerunit(OPU) 4120x1910x2190mm 5800kg
Sound data
— ConsultyourlocalMTUdistributorforsounddata.
Emissionsdata
— ConsultyourlocalMTUdistributorforemissionsdata.
Ratingdefinitionsandconditions
— Primepowerratingsapplytoinstallationswhereutilitypowerisunavailableorunreliable.Atvaryingload,thenumberofgeneratorsetoperatinghoursisunlimited.A10%overloadcapacityisavailableforonehourintwelve.RatingsareinaccordancewithISO8528-1,ISO3046-1,BS5514andAS2789. Averageloadfactor:≤75%.Operatinghours/year:unlimited
— ConsultyourlocalMTUdistributorforderatinginformation.
Subjecttochange.|3239531|Edition01/19|ESM2019-12.