differential protection function block description - · pdf file1.8 example for the setting...
TRANSCRIPT
Differential protection function block description
Document ID: PRELIMINARY VERSION
Budapest, October 2009
Differential protection
PRELIMINARY VERSION 2/48
User’s manual version information
Version Date Modification Compiled by
Preliminary 30.10.2009. Preliminary version, without technical information Petri
18.06.2010 Technical information added Petri
Differential protection
PRELIMINARY VERSION 3/48
CONTENTS 1 Differential protection function .............................................................................................4
1.1 Structure of the differential protection algorithm ..........................................................4
1.2 The vector shift compensation (Vector group) .............................................................7 1.2.1 Principle of transformation to the D side ...............................................................7 1.2.2 Mathematical modeling of the current transformer’s vector group connection .....7 1.2.3 The matrix equations ............................................................................................8 1.2.4 Operation with the zero sequence current in case of phase-to-ground fault on the delta side .................................................................................................................... 10 1.2.5 The principal scheme of the vector group compensation .................................. 11
1.3 Harmonic analysis of the differential currents (Diff basic harm.), (Diff 2. harm.), (Diff
5. harm.)............................................................................................................................... 13 1.3.1 The principle of calculation ................................................................................ 13 1.3.2 The principal scheme of the harmonic analysis ................................................. 14
1.4 The harmonic restraint decision (2. harmonic restraint) and (5. harmonic restraint)
15 1.4.1 The principle of the restraint decision ................................................................ 15 1.4.2 The principal scheme of the harmonic restraint decision .................................. 16
1.5 The current magnitude calculation (Current magnitude) .......................................... 19 1.5.1 The principle of the current magnitude calculation ............................................ 19 1.5.2 The principal scheme of the current magnitude calculation .............................. 19
1.6 The evaluation of the differential characteristics (Differential characteristics) . 21 1.6.1 The principle of the differential characteristics................................................... 21 1.6.2 The unrestricted differential function .................................................................. 22 1.6.3 The principal scheme of the evaluation of differential characteristics ............... 24
1.7 The decision logic (Decision logic) ........................................................................... 26 1.7.1 The principle of the decision logic ...................................................................... 26 1.7.2 The principal scheme of the decision logic ........................................................ 26
1.8 Example for the setting calculation in the Protecta differential protection ................ 29 1.8.1 Data for the calculation ...................................................................................... 29 1.8.2 The setting parameters: ..................................................................................... 29
1.9 Technical summary ................................................................................................... 30 1.9.1 Technical data .................................................................................................... 30 1.9.2 The measured values ........................................................................................ 30 1.9.3 The parameters of the differential protection function ....................................... 30 1.9.4 The binary output status signals ........................................................................ 32 1.9.5 Binary input signal .............................................................................................. 32 1.9.6 The function block .............................................................................................. 33
2 Appendix: .......................................................................................................................... 34
2.1 Current distribution inside the Y/d transformers ........................................................ 34 2.1.1 Three-phase fault (or normal load state) ........................................................... 34 2.1.2 Phase-to-phase fault on the Y side .................................................................... 36 2.1.3 Phase-to-phase fault at the delta side ............................................................... 37 2.1.4 Single phase external fault at the Y side ........................................................... 38 2.1.5 Single phase fault at the delta side .................................................................... 40
2.2 Checking the setting example ................................................................................... 44 2.2.1 Checking in case of symmetrical rated load currents ........................................ 44 2.2.2 Checking for Y side external phase-to-phase fault ............................................ 45 2.2.3 Checking for D side external phase-to-phase fault ............................................ 46 2.2.4 Checking for Y side external phase-to-ground fault .......................................... 47
Differential protection
PRELIMINARY VERSION 4/48
1 Differential protection function The differential protection function provides main protection for transformers, generators or large motors, but it can also be applied for overhead lines and cables of solidly grounded networks or for the protection of any combination of the aforementioned protected objects. Version DIF87_3w can be applied to protect three-winding transformers. The simpler version DIF87_2w does not process analogue inputs from the tertiary side. This chapter describes the three-winding transformer version but it also refers to necessary changes in application with transformers of two sides only.
1.1 Structure of the differential protection algorithm Fig.1-1 shows the structure of the differential protection (DIF87_3w) algorithm.
Figure 1-1 Structure of the differential protection algorithm
IprimL1
Vector Group Diff
base harm.
DIF87_3w
Binary
outputs
Measured values
Parameters
IprimL2
IprimL3
IsecL1
IsecL2
IsecL3
ItercL1
ItercL2
ItercL3
Diff
2. harm
Diff
5. harm
2. harm. restraint
5. harm.
restraint
Decision
logic
Current magnitude
Differential characteristics
Status signal
Differential protection
PRELIMINARY VERSION 5/48
The inputs are
the sampled values of three primary phase currents,
the sampled values of three secondary phase currents,
the sampled values of three tertiary phase currents (in DIF87_3w version only) ,
parameters
status signal.
The outputs are
the binary output status signals,
the measured values for displaying. The software modules of the differential protection function:
Vector group
This module compensates the phase shift and turns ratio of the transformer. The results of this calculation are the “sampled values” of the phase-shifted phase currents for all three (two) sides of the transformer and those of the three differential currents.
Diff base harm.
This module calculates the basic Fourier components of the three differential currents. These results are needed for the high-speed differential current decision and for the second and fifth harmonic restraint calculation.
Diff 2. harm.
This module calculates the second harmonic Fourier components of the three differential currents. These results are needed for the second harmonic restraint decision.
Diff 5. harm.
This module calculates the fifth harmonic Fourier components of the three differential currents. These results are needed for the fifth harmonic restraint decision.
2. harm. restraint.
The differential current can be high during the transients of transformer energizing, due to the current distortion caused by the transformer iron core asymmetric saturation. In this case, the second harmonic content of the differential current is applied in this module to disable the operation of the differential protection function. The result of this calculation is needed for the decision logic.
5. harm. restraint.
The differential current can be high if the transformer is over-excited by a connected generator, due to the current distortion caused by the transformer iron core symmetric saturation. In this case, the fifth harmonic content of the differential current is applied in this module to disable the operation of the differential protection function. The result of this calculation is needed for the decision logic.
Current magnitude
This module calculates the magnitude of the phase-shifted phase currents and that of the differential currents. The result of this calculation is needed for the evaluation of differential characteristics.
Differential characteristics
This module performs the necessary calculations for the evaluation of the “percentage differential characteristics”. The result of this calculation is needed for the decision logic.
Differential protection
PRELIMINARY VERSION 6/48
Decision logic
The decision logic module decides if the differential current of the individual phases is above the characteristic curve of the differential protection function. This curve is the function of the restraint current, which is calculated based on the magnitude of the phase-shifted phase currents. This module calculates the second and fifth harmonic ratios of the differential current relative to the basic harmonic content. The result can restrain the operation of the differential protection function. The high-speed overcurrent protection function based on the differential currents is also performed in this module. The following description explains the details of the individual components.
Differential protection
PRELIMINARY VERSION 7/48
1.2 The vector shift compensation (Vector group) The three-phase power transformers transform the primary current to the secondary side according to the turns ratio and the vector group of the transformers. The Y (star), D (delta) or Z (zig-zag) connection of the three phase coils on the primary and secondary sides causes the vector shift of the currents. The conventional electromechanical or static electronic devices of the differential protection compensate the vector shift with the appropriate connection of the current transformer coils. The numerical differential protection function applies matrix transformation of the directly measured currents of one side of the transformer to match them with the currents of the other side. In Protecta’s transformer differential protection the „Vector_group” software module calculates the matrix transformation and turns ratio matching. In this case, the target of the matrix transformation is the delta (D) side.
1.2.1 Principle of transformation to the D side The conventional electromechanical or static electronic devices of the differential protection compensate the vector shift with the appropriate connection of the current transformer coils. The principle is that the Y-connected current transformers on the delta side of the transformer do not shift the currents flowing out of the transformer. The delta-connected current transformers on the Y side of the transformer, however, result in a phase shift. This means that the Y-side currents are shifted according to the vector group of the transformer to match the delta-side currents. Additionally, the delta connection of the current transformers eliminates the zero sequence current component flowing on the grounded Y side of the transformer. As no zero sequence current can be detected on the delta side, this compensation is essential for the correct operation of the differential protection. If a phase-to-ground fault occurs on the Y side of the transformer, then zero sequence current flows on the grounded Y side while no out-flowing zero sequence current can be detected on the delta side. Without the elimination of the zero sequence current component, the differential protection generates a trip command in case of an external ground fault. If, however, the connection group of the current transformers on the Y side is delta, no zero sequence current flows out of the group. Thus the problem of zero sequence current elimination in case of an external ground fault is solved.
1.2.2 Mathematical modeling of the current transformer’s vector group connection
The numerical differential protection function applies numerical matrix transformation for modeling the delta connection of the current transformers. In practice, it means cyclical subtraction of the phase currents. In the vector shift compensation the sampled rst currents of the primary side (I1r, I1s, I1t) and those of the secondary side ((I2r, I2s, I2t)) are transformed to (RSTshift) values of both sides respectively, using matrix transformation. The method of transformation is defined by the „Code” parameter identifying the transformer vector group connection.
Differential protection
PRELIMINARY VERSION 8/48
1.2.3 The matrix equations
The table below summarizes the method of transformation, broken down by the connection group of the transformers with two voltage levels. The tertiary side, if any – related to the primary – is processed similarly:
Tr. Conn. Group.
Code Transformation of the primary side currents
Transformation of the secondary side currents
Dy1 00
tI
sI
rI
TshitftI
SshitftI
RshitftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshitftI
SshitftI
RshitftI
2
2
2
101
110
011
3
1
2
2
2
Dy5 01
tI
sI
rI
TshitftI
SshitftI
RshitftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshitftI
SshitftI
RshitftI
2
2
2
110
011
101
3
1
2
2
2
Dy7 02
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshiftI
SshiftI
RshiftI
2
2
2
101
110
011
3
1
2
2
2
Dy11 03
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshiftI
SshiftI
RshiftI
2
2
2
110
011
101
3
1
2
2
2
Dd0 04
tI
sI
rI
TshitftI
SshitftI
RshitftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshitftI
SshitftI
RshitftI
2
2
2
100
010
001
2
2
2
Dd6 05
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshiftI
SshiftI
RshiftI
2
2
2
100
010
001
2
2
2
Dz0 06
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshifI
SshifI
RshiftI
2
2
2
211
121
112
3
1
2
2
2
Dz2 07
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshifI
SshifI
RshiftI
2
2
2
112
211
121
3
1
2
2
2
Dz4 08
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshifI
SshifI
RshiftI
2
2
2
121
112
211
3
1
2
2
2
Dz6 09
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshifI
SshifI
RshiftI
2
2
2
211
121
112
3
1
2
2
2
Differential protection
PRELIMINARY VERSION 9/48
Dz8 10
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshifI
SshifI
RshiftI
2
2
2
112
211
121
3
1
2
2
2
Dz10 11
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
100
010
001
1
1
1
tI
sI
rI
TshifI
SshifI
RshiftI
2
2
2
121
112
211
3
1
2
2
2
Yy0 12
tI
sI
rI
TshitftI
SshitftI
RshitftI
1
1
1
110
011
101
3
1
1
1
1
tI
sI
rI
TshitftI
SshitftI
RshitftI
2
2
2
110
011
101
3
1
2
2
2
Yy6 13
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
110
011
101
3
1
1
1
1
tI
sI
rI
TshiftI
SshiftI
RshiftI
2
2
2
110
011
101
3
1
2
2
2
Yd1 14
tI
sI
rI
TshitftI
SshitftI
RshitftI
1
1
1
110
011
101
3
1
1
1
1
tI
sI
rI
TshitftI
SshitftI
RshitftI
2
2
2
100
010
001
2
2
2
Yd5 15
tI
sI
rI
TshitftI
SshitftI
RshitftI
1
1
1
101
110
011
3
1
1
1
1
tI
sI
rI
TshitftI
SshitftI
RshitftI
2
2
2
100
010
001
2
2
2
Yd7 16
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
110
011
101
3
1
1
1
1
tI
sI
rI
TshiftI
SshiftI
RshiftI
2
2
2
100
010
001
2
2
2
Yd11 17
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
101
110
011
3
1
1
1
1
tI
sI
rI
TshiftI
SshiftI
RshiftI
2
2
2
100
010
001
2
2
2
Yz1 18
tI
sI
rI
TshitftI
SshitftI
RshitftI
1
1
1
110
011
101
3
1
1
1
1
tI
sI
rI
TshifI
SshifI
RshiftI
2
2
2
211
121
112
3
1
2
2
2
Yz5 19
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
101
110
011
3
1
1
1
1
tI
sI
rI
TshifI
SshifI
RshiftI
2
2
2
211
121
112
3
1
2
2
2
Yz7 20
tI
sI
rI
TshitftI
SshitftI
RshitftI
1
1
1
110
011
101
3
1
1
1
1
tI
sI
rI
TshifI
SshifI
RshiftI
2
2
2
211
121
112
3
1
2
2
2
Yz11 21
tI
sI
rI
TshiftI
SshiftI
RshiftI
1
1
1
101
110
011
3
1
1
1
1
tI
sI
rI
TshifI
SshifI
RshiftI
2
2
2
211
121
112
3
1
2
2
2
Table 1-1 Vector shift compensation with transformation to the delta side
Differential protection
PRELIMINARY VERSION 10/48
The differential currents are calculated using the (RSTshift) values and the DIF87_TRPr_IPar (TR primary) and DIF87_TRSec_IPar (TR secondary) parameters, defined by the turns ratio of the transformer and that of the current transformers, resulting in the currents marked with an apostrophe (’). The tertiary side is processed similarly. (The positive direction of the currents is flowing IN on both sides.)
TshiftI
SshiftI
RshiftI
ondaryTRTshiftI
SshiftI
RshiftI
primaryTRTshiftI
SshiftI
RshiftI
TshiftI
SshiftI
RshiftI
IdT
IdS
IdR
2
2
2
sec_
100
1
1
1
_
100
'2
'2
'2
'1
'1
'1
The current measuring software modules process these momentary values of the differential currents and calculate values that are proportional to the RMS values.
1.2.4 Operation with the zero sequence current in case of a phase-to-ground fault on the delta side
On the secondary side of a high voltage /medium voltage transformer which is connected in delta on the medium voltage side, an additional neutral grounding transformer is applied. Between the neutral point of this grounding transformer and the ground either a grounding resistor is connected to limit the single phase-to-ground fault currents below 100 A (in some cases 200 A only), or a Petersen coil is applied here, which limits the single-phase fault currents to a small value of a few Amps. In these cases, there are two locations for the current transformers on the delta side to supply the differential protection. In one case, the neutral grounding transformer is located inside the protected zone of the differential protection (In Fig. 2-7 and 2-8 of the Appendix it is location ”Z”), in the other case the neutral grounding transformer is outside the protected zone (In Fig. 2-7 and 2-8 of the Appendix, this is the application of the current transformers at location „Y”). If the neutral grounding transformer is in the protected zone, then the current distribution depends on the location of the supplying generator, as it is shown in Figures 2-7 and 2-8 of the Appendix. In these cases, for the correct operation of the differential protection (if the operating characteristic lines are set to be sensitive) the subtraction of the zero sequence current is needed. This additional transformation „moves” the measuring location to the point („Y”) where no zero sequence current can flow, so these transformed currents do not include the zero sequence current of the neutral grounding transformer.
Differential protection
PRELIMINARY VERSION 11/48
1.2.5 The schema of the vector group compensation Figure 1-2 shows the principal scheme of the vector shift compensation.
Figure 1-2 Schema of the vector shift compensation.
The inputs are the sampled values of:
the three phase currents of the primary side (IprimL1, IprimL2, IprimL3)
the three phase currents of the secondary side (IsecL1, IsecL2, IsecL3)
the three phase currents of the tertiary side (ItercL1, ItercL2, ItercL3 in version DIF87_3w only)
parameters for vector shift and turns ratio compensation.
IprimL1
Vector Group
Parameters
IprimL2
IprimL3
IsecL1
IsecL2
IsecL3
ItercL1
ItercL2
ItercL3
IdR
IdS
IdT
I1Rshift’1
I1Sshift’
I1Tshift’
I2Rshift’
I2Sshift’
I2Tshift’
I3Rshift’
I3Sshift’ I3Tshift’
Differential protection
PRELIMINARY VERSION 12/48
Enumerated parameters for the vector shift compensation:
Parameter name Title Selection range Default
Parameter to select connection group of the transformer coils in primary-secondary relation:
DIF87_VGrSec_EPar_ Pri-Sec VGroup*
Dy1,Dy5,Dy7,Dy11,Dd0,Dd6,Dz0,Dz2,Dz4,Dz6,Dz8,Dz10,Yy0,Yy6,Yd1,Yd5,Yd7,Yd11,Yz1,Yz5,Yz7,Yz11
Dd0
Parameter to select connection group of the transformer coils in primary-secondary relation:
DIF87_VGrTer_EPar_ Pri-Ter VGroup*
Dy1,Dy5,Dy7,Dy11,Dd0,Dd6,Dz0,Dz2,Dz4,Dz6,Dz8,Dz10,Yy0,Yy6,Yd1,Yd5,Yd7,Yd11,Yz1,Yz5,Yz7,Yz11
Dd0
Table 1-2 Enumerated parameters for the vector shift compensation
* If the connection of the primary winding in the primary-secondary and primary-tertiary relations is selected in contradiction, the protection function is automatically disabled and the function generates a warning signal. Boolean parameter for the vector shift compensation:
Parameter name Title Default Explanation
DIF87_0Seq_BPar_ ZeroSequ.Elimination True See Chapter 1.2.4
Table 1-3 The Boolean parameter for the vector shift compensation
Integer parameters for the turns ratio compensation:
Parameter name Title Unit Min Max Step Default
Parameters for the current magnitude compensation:
DIF87_TRPr_IPar_ TR Primary comp. % 20 500 1 100
DIF87_TRSec_IPar_ TR Secondary comp. % 20 500 1 100
DIF87_TRTer_IPar_ TR Tertiary comp. % 20 500 1 100
Table 1-4 Integer parameters for the vector shift compensation
The outputs are the “sampled values” of the phase-shifted currents:
The differential currents after phase-shift,
IdT
IdS
IdR
The primary currents after phase-shift,
'1
'1
'1
TshiftI
SshiftI
RshiftI
The secondary currents after phase-shift,
'2
'2
'2
TshiftI
SshiftI
RshiftI
The tertiary currents after phase-shift (in version DIF87_3w only).
Differential protection
PRELIMINARY VERSION 13/48
1.3 Harmonic analysis of the differential currents (Diff
basic harm.), (Diff 2. harm.), (Diff 5. harm.)
1.3.1 The principle of calculation The differential current can be high during the transients of transformer energizing due to the current distortion caused by the transformer iron core asymmetrical saturation. In this case, the second harmonic content of the differential current is applied to disable the operation of the differential protection function. The differential current can be high in case of the over-excitation of the transformer due to the current distortion caused by the transformer iron core symmetrical saturation. In this case, the fifth harmonic content of the differential current is applied to disable the operation of the differential protection function. The harmonic analysis block of modules consists of three individual software modules.
Diff base harm.
This module calculates the basic Fourier components of the three differential currents. These results are needed for the high-speed differential current decision and for the second and fifth harmonic restraint calculation.
Diff 2. harm.
This module calculates the second harmonic Fourier components of the three differential currents. These results are needed for the second harmonic restraint decision.
Diff 5. harm.
This module calculates the fifth harmonic Fourier components of the three differential currents. These results are needed for the fifth harmonic restraint decision.
Differential protection
PRELIMINARY VERSION 14/48
1.3.2 The schema of the harmonic analysis
Figure 1-3 shows the structure of the harmonic analysis.
Figure 1-3 Principal scheme of the harmonic analysis.
The inputs are the “sampled values” of the differential currents, based on the phase-
shifted currents:
The differential currents after phase-shift
IdT
IdS
IdR
The outputs are the basic, the second and the fifth harmonic Fourier components of
the differential currents:
The basic harmonic Fourier components of the differential currents
IdTF
IdSF
IdRF
1
1
1
The second harmonic Fourier components of the differential currents
IdTF
IdSF
IdRF
2
2
2
The fifth harmonic Fourier components of the differential currents
IdTF
IdSF
IdRF
5
5
5
These values are processed by the software modules 2. harmonic restraint and
5. harmonic restraint
Diff base harm.
Diff 2. harm
Diff 5. harm
IdR
IdS
IdT
F1IdR
F1IdS
F1IdT
F2IdR2
FI2dS
FI2dT
FI5dR
FI5dS
FI5dT
Differential protection
PRELIMINARY VERSION 15/48
1.4 The harmonic restraint decision (2. harmonic
restraint) and (5. harmonic restraint)
1.4.1 The principle of the restraint decision The differential current can be high during transformer energizing due to the current distortion caused by the transformer iron core asymmetrical saturation. In this case, the second harmonic content of the differential current is applied to disable the operation of the differential protection function. The differential current can be high in case of the over-excitation of the transformer due to the current distortion caused by the transformer iron core symmetrical saturation. In this case, the fifth harmonic content of the differential current is applied to disable the operation of the differential protection function. The harmonic analysis block of modules consists of two sub-blocks, one for the second harmonic decision and one for the fifth harmonic decision. Each sub-block includes three individual software modules for the phases. The software modules evaluate the harmonic content relative to the basic harmonic component of the differential currents and compare the result with the parameter values set for the second and fifth harmonic. If the content is high, then the assigned status signal is set to “true” value. If the duration of the active status is at least 25 ms, then the resetting of the status signal is delayed by an additional 15 ms.
Differential protection
PRELIMINARY VERSION 16/48
1.4.2 The principal scheme of the harmonic restraint decision
Figure 1-4 Principal scheme of the harmonic restraint decision
The inputs are the basic, the second and the fifth harmonic Fourier components of the
differential currents:
The basic harmonic Fourier components of the differential currents
IdTF
IdSF
IdRF
1
1
1
The second harmonic Fourier components of the differential currents
IdTF
IdSF
IdRF
2
2
2
The fifth harmonic Fourier components of the differential currents
IdTF
IdSF
IdRF
5
5
5
The outputs of the modules are the status signals for each phase and for the second and fifth harmonics separately, indicating the restraint status caused by high harmonic contents.
F1IdR
F1IdS
F1IdT
F2IdR2
FI2dS
FI2dT
F5IdR
F5IdS
F5IdT
2.harm restr. L1
2.harm restr. L2
2.harm restr. L3
5.harm restr. L1
5.harm restr. L2
5.harm restr. L3
Para meters
2. harmonic restraint decision
5. harmonic restraint decision
Differential protection
PRELIMINARY VERSION 17/48
Figure 1-5 Logic schema of the harmonic restraint decision.
The logic schema is repeated for the second (n=2) and fifth (n=5) harmonic restraint decision for all three phases separately (x=L1, L2, L3). First the ratio of the harmonic and the base harmonic is calculated, and this ratio is compared to the parameter setting (second and fifth separately). If the ratio is high, the restraint signal is generated immediately and a timer is started at the same time. If the 25 ms delay is over and during the running time the ratio was continuously high, then a drop-off timer is started, which extends the duration of the restraint signal. The decisions of the phases are connected in an OR gate to result in general second or fifth harmonic restraint status signals. The binary output status signals of the harmonic restraint decision function are listed in Table 1-5.
Binary output signals Signal title Explanation
Second harmonic restraint signals
DIF87_2HBlkL1_GrI 2.Harm Restr. L1 Restraint in phase L1 caused by high second harmonic content in the differential current
DIF87_2HBlkL2_GrI 2.Harm Restr. L2 Restraint in phase L2 caused by high second harmonic content in the differential current
DIF87_2HBlkL3_GrI 2.Harm Restr. L3 Restraint in phase L3 caused by high second harmonic content in the differential current
DIF87_2HBlk_GrI 2.Harm Restr. Restraint caused by high second harmonic content in any of the differential currents
Fifth harmonic restraint signals
DIF87_5HBlkL1_GrI 5.harm Restr. L1 Restraint in phase L1 caused by high fifth harmonic content in the differential current
DIF87_5HBlkL2_GrI 5.harm Restr. L2 Restraint in phase L2 caused by high fifth harmonic content in the differential current
DIF87_5HBlkL3_GrI 5.harm Restr. L3 Restraint in phase L3 caused by high fifth harmonic content in the differential current
DIF87_5HBlk_GrI 5.Harm Restr. Restraint caused by high fifth harmonic content in any of the differential currents
Table 1-5 Binary output status signals of the harmonic restraint decision function
F1Idx
FnIdx2
DIFF87_2HBlkL1GrI_ DIFF87_2HBlkL2GrI_ DIFF87_2HBlkL3GrI_ DIFF87_5HBlkL1GrI_ DIFF87_5HBlkL2GrI_ DIFF87_5HBlkL3GrI_
Parameters
Ratio
25ms
t t
15ms
OR
0.2
&
Differential protection
PRELIMINARY VERSION 18/48
Integer parameters of the harmonic restraint decision function are listed in Table 1-6.
Parameter name Title Unit Min Max Step Default
Parameter of the second harmonic restraint:
DIF87_2HRat_IPar_ 2. Harm. Ratio % 5 50 1 15
Parameter of the fifth harmonic restraint:
DIF87_5HRat_IPar_ 5. Harm. Ratio % 5 50 1 25
Table 1-6 Integer parameters of the harmonic restraint decision function
Differential protection
PRELIMINARY VERSION 19/48
1.5 The current magnitude calculation (Current
magnitude)
1.5.1 The principle of the current magnitude calculation The module, which evaluates the differential characteristics, compares the magnitudes of the differential currents and those of the restraint currents. The current magnitudes are needed for this calculation. These magnitudes are calculated in this module.
1.5.2 The principal scheme of the current magnitude calculation
Figure 1-6 Principal scheme of the current magnitude calculation.
IdR
IdS
IdT
I1Rshift’1
I1Sshift’
I1Tshift’
I2Rshift’
I2Sshift’
I2Tshift’
I3Rshift’
I3Sshift’ I3Tshift’
Id
I1 shift
I2 shift
I3 shift
M_IdR
M_IdS
M_IdT
M_I1Rshift’
M_I1Sshift’
M_I1Tshift’
M_I2Rshift’
M_I2Sshift’
M_I2Tshift’
M_I3Rshift’
M_I3Sshift’ M_I3Tshift’
Differential protection
PRELIMINARY VERSION 20/48
The inputs are the “sampled values” of the phase-shifted currents:
The differential currents after phase-shift,
IdT
IdS
IdR
The primary currents after phase-shift,
'1
'1
'1
TshiftI
SshiftI
RshiftI
The secondary currents after phase-shift,
'2
'2
'2
TshiftI
SshiftI
RshiftI
The tertiary currents after phase-shift (in version DIF87_3w only).
'3
'3
'3
TshiftI
SshiftI
RshiftI
The outputs are the magnitudes of the calculated currents
The magnitudes of the differential currents after phase-shift,
IdTM
IdSM
IdRM
_
_
_
The magnitudes of the primary currents after phase-shift,
'1_
'1_
'1_
TshiftIM
SshiftIM
RshiftIM
The magnitudes of the secondary currents after phase-shift,
'2_
'2_
'2_
TshiftIM
SshiftIM
RshiftIM
The magnitudes of the tertiary currents after phase-shift
(in version DIF87_3w only)
'3_
'3_
'3_
TshiftIM
SshiftIM
RshiftIM
Differential protection
PRELIMINARY VERSION 21/48
1.6 The evaluation of the differential characteristics
(Differential characteristics)
1.6.1 The principle of the differential characteristics This module evaluates the differential characteristics. It compares the magnitudes of the differential currents and those of the restraint currents. The restraint currents are calculated using the following formulas:
2
''3_'2_'1__
RshiftIMRshiftIMRshiftIMIresRM
2
''3_'2_'1__
SshiftIMSshiftIMSshiftIMIresSM
2
''3_'2_'1__
TshiftIMTshiftIMTshiftIMIresTM
Based on these values (generally denoted as “Ires”) and the values of the differential current magnitudes (generally denoted as “Id”), the differential protection characteristics are shown in Figure 1-7.
Figure 1-7 The differential protection characteristics
Additionally, separate status signals are set to “true” value if the differential currents in the individual phases are above the limit set by the dedicated parameter (see “Unrestricted differential function”).
Ires
Slope=DIF87_f2_IPar_
DIF87_f3_IPar_
DIF87_f1_IPar_
Slope=const=2
Id
Differential protection
PRELIMINARY VERSION 22/48
Integer parameters
Parameter name Title Unit Min Max Step Default
Base sensitivity:
DIF87_f1_IPar_ Base sensitivity % 10 50 1 20
Slope of the second section of the characteristics:
DIF87_f2_IPar_ 2nd part of TripChar - 10 50 1 20
Slope of the third section of the characteristics:
DIF87_f3_IPar_ 3rd part of TripChar - 200 2000 1 200
Table 1-7 Integer parameters of the differential protection characteristics
Binary output signals Signal title Explanation
Differential characteristics
DIF87_L1St_GrI_i Start L1
This internal status is true if the differential current in phase R at the restraint current is above the characteristic lines
DIF87_L2St_GrI_i Start L2
This internal status is true if the differential current in phase S at the restraint current is above the characteristic lines
DIF87_L3St_GrI_i Start L3
This internal status is true if the differential current in phase T at the restraint current is above the characteristic lines
Table 1-8 Binary output status signals of the differential protection characteristics
1.6.2 The unrestricted differential function If the calculated differential current is very high, then the differential characteristic is not considered anymore because the separate status signals for the phases are set to “true” value if the differential currents in the individual phases are above the limit defined by parameter setting. The decisions of the phases are connected in an OR gate to result in the general start status signal. Integer parameter of the unrestricted differential function is shown in Table 1-9.
Parameter name Title Unit Min Max Step Default
High-speed differential protection current level:
DIF87_HCurr_IPar_ Unrestrained I-Diff % 800 2500 1 800
Table 1-9 The integer parameters of the unrestricted differential protection
characteristics
Differential protection
PRELIMINARY VERSION 23/48
Binary output signals Signal title Explanation
Unrestricted decision
DIF87_UnRL1St_GrI_i Start L1 unrestr. This internal status is true if the differential current in phase R is above the high current setting
DIF87_UnRL2St_GrI_i Start L1 unrestr. This internal status is true if the differential current in phase R is above the high current setting
DIF87_UnRL3St_GrI_i Start L1 unrestr. This internal status is true if the differential current in phase R is above the high current setting
DIF87_UnRGenSt_GrI General start unrestr. This status is true if in any of the phases the differential current is above the high current setting
Table 1-10 The binary output status signals of the unrestricted differential protection
characteristics
Differential protection
PRELIMINARY VERSION 24/48
1.6.3 The principal scheme of the evaluation of differential characteristics
Figure 1-8 Schema of evaluation of differential protection characteristics
The inputs are the magnitudes of the calculated currents:
The magnitudes of the differential currents after phase-shift,
IdTM
IdSM
IdRM
_
_
_
The magnitudes of the primary currents after phase-shift,
'1_
'1_
'1_
TshiftIM
SshiftIM
RshiftIM
The magnitudes of the secondary currents after phase-shift,
'2_
'2_
'2_
TshiftIM
SshiftIM
RshiftIM
The magnitudes of the tertiary currents after phase-shift
(in version DIF87_3w only)
'3_
'3_
'3_
TshiftIM
SshiftIM
RshiftIM
M_IdR
M_IdS
M_IdT
M_I1Rshift’
M_I1Sshift’
M_I1Tshift’
M_I2Rshift’
M_I2Sshift’
M_I2Tshift’
M_I3Rshift’
M_I3Sshift’ M_I3Tshift’
Start L1
Start L2
Start L3
UnRestr.Start L1
UnRestr.Start L2
UnRestr.Start L3
Differential characteristics
Unrestricted decision
Parameters
Differential protection
PRELIMINARY VERSION 25/48
Binary output signals Signal title Explanation
Differential characteristics
DIF87_L1St_GrI_ Start L1 This status is true if the differential current in phase R at the restraint current is above the characteristic lines
DIF87_L2St_GrI_ Start L2 This status is true if the differential current in phase S at the restraint current is above the characteristic lines
DIF87_L3St_GrI_ Start L3 This status is true if the differential current in phase T at the restraint current is above the characteristic lines
Unrestricted decision
DIF87_UnRL1St_GrI Start L1 unrestr. This status is true if the differential current in phase R is above the high current setting
DIF87_UnRL2St_GrI Start L1 unrestr. This status is true if the differential current in phase R is above the high current setting
DIF87_UnRL3St_GrI Start L1 unrestr. This status is true if the differential current in phase R is above the high current setting
Table 1-11 The binary output status signals of the unrestricted differential protection
characteristics
Differential protection
PRELIMINARY VERSION 26/48
1.7 The decision logic (Decision logic)
1.7.1 The principle of the decision logic
The decision logic combines the following binary signals:
Start signals of the differential characteristic module
Unrestricted start signals of the differential characteristic module
Harmonic restraint signals of the 2nd harmonic restraint decision
Harmonic restraint signals of the 5th harmonic restraint decision
Disabling status signals defined by the user applying the graphic equation editor DIF87_Blk_GrO
1.7.2 The schema of the decision logic
The inputs are the calculated status signals of the Differential characteristics and Unrestricted
differential modules, those of the 2.harmonic restraint and 5.harmonic restraint modules and
binary input parameters.
Binary input signals Signal title Explanation
Differential characteristics
DIF87_L1St_GrI_i Start L1 This internal status is true if the differential current in phase R at the restraint current is above the characteristic lines
DIF87_L2St_GrI_i Start L2 This internal status is true if the differential current in phase S at the restraint current is above the characteristic lines
DIF87_L3St_GrI_i Start L3 This internal status is true if the differential current in phase T at the restraint current is above the characteristic lines
Unrestricted decision
DIF87_UnRL1St_GrI_i Start L1 unrestr. This internal status is true if the differential current in phase R is above the high current setting
DIF87_UnRL2St_GrI_i Start L1 unrestr. This internal status is true if the differential current in phase R is above the high current setting
DIF87_UnRL3St_GrI_i Start L1 unrestr. This internal status is true if the differential current in phase R is above the high current setting
Second harmonic restraint signals
DIF87_2HBlkL1_GrI 2.Harm Restr. L1 Restraint in phase L1 caused by high second harmonic content in the differential current
DIF87_2HBlk L2_GrI 2.Harm Restr. L2 Restraint in phase L2 caused by high second harmonic content in the differential current
DIF87_2HBlkL3_GrI 2.Harm Restr. L3 Restraint in phase L3 caused by high second harmonic content in the differential current
Fifth harmonic restraint signals
DIF87_5HBlkL1_GrI 5.Harm Restr. L1 Restraint in phase L1 caused by high fifth harmonic content in the differential current
DIF87_5HBlkL2_GrI 5.Harm Restr. L2 Restraint in phase L2 caused by high fifth harmonic content in the differential current
DIF87_5HBlkL3_GrI 5.Harm Restr. L3 Restraint in phase L3 caused by high fifth harmonic content in the differential current
Table 1-12 The binary input status signals of the decision logic
Differential protection
PRELIMINARY VERSION 27/48
Blocking input signal The differential protection function has a binary input signal, which serves the purpose of disabling the function. The conditions of disabling are defined by the user applying the graphic equation editor for the signal DIF87_Blk_GrO.
Binary input signal Explanation
DIF87_Blk_GrO Output status of a graphic equation defined by the user to disable the differential protection function.
Table 1-13 The blocking input status signals of the decision logic
These input status signals are processed by the decision logic to generate additional status signals, but at the same time they are output signals as well. The binary output signals are listed in Table 1-14 below.
Binary output signals Signal title Explanation
Differential characteristics
DIF87_L1St_GrI_ Start L1
This status is true if the differential current in phase R at the restraint current is above the characteristic lines and the function is not blocked
DIF87_L2St_GrI_ Start L2
This status is true if the differential current in phase S at the restraint current is above the characteristic lines and the function is not blocked
DIF87_L3St_GrI_ Start L3
This status is true if the differential current in phase T at the restraint current is above the characteristic lines and the function is not blocked
Unrestricted decision
DIF87_UnRL1St_GrI_ Start L1 unrestr. This status is true if the differential current in phase R is above the high current setting and the function is not blocked
DIF87_UnRL2St_GrI_ Start L1 unrestr. This status is true if the differential current in phase R is above the high current setting and the function is not blocked
DIF87_UnRL3St_GrI_ Start L1 unrestr. This status is true if the differential current in phase R is above the high current setting and the function is not blocked
Harmonic blocking
DIF87_2HBlk_GrI 2.Harm Restr. Restraint caused by high second harmonic content in any of the differential currents
DIF87_5HBlk_GrI 5.Harm Restr. Restraint caused by high fifth harmonic content in any of the differential currents
DIF87_HarmBlk_GrI_ HarmBlk This status is true if either the second or the fifth harmonic in any of the phases blocks the output
Table 1-14 The binary output status signals of the differential protection
characteristics
These signals are processed by the trip logic of the device.
Differential protection
PRELIMINARY VERSION 28/48
Figure 1-9 The logic schema of the differential protection function
DIF87_L1St_GrI_i
DIF87_L2St_GrI_i
DIF87_L3St_GrI_i
DIF87_UnRL1St_GrI_i
DIF87_UnRL1St_GrI_i
DIF87_UnRL1St_GrI_i
DIF87_2HBlkL1_GrI_
DIF87_2HBlkL2_GrI_
DIF87_2HBlkL3_GrI_
DIF87_5HBlkL1_GrI_
DIF87_5HBlkL2_GrI_
DIF87_5HBlkL3_GrI_
DIF87_5HBlkL3_GrI_
OR
OR
DIF87_L1St_GrI_
OR
AND
AND
AND
AND
AND
AND
OR
OR
DIF87_L2St_GrI_
DIF87_L3St_GrI_
DIF87_GenSt_GrI_
DIF87_UnRL1St_GrI_
DIF87_UnRL2St_GrI_
DIF87_UnRL3St_GrI_
DIF87_UnRGenSt_GrI_
DIF87_HarmBlk_GrI_
NOT
NOT
Differential protection
PRELIMINARY VERSION 29/48
1.8 Example for the setting calculation in the Protecta differential protection
1.8.1 Data for the calculation
As an example, the transformer data:
Sn = 125 MVA U1/U2 = 132/11.5 kV/kV Yd11
Current transformer:
CT1 600/1 A/A CT2 6000/1 A/A
Rated currents of the transformer:
I1np = 546 A On the secondary side of the CT I1n = 0.91 A I2np = 6275 A On the secondary side of the CTI2n = 1.05 A
1.8.2 The setting parameters:
TR primary = 91 %
(This is a free choice, giving the primary side current transformer’s current, as a percentage of the rated current of the CT.)
TR secondary = 105 % (This is a direct consequence of selecting TR primary; this is the current of the secondary side current transformer related to the rated current of the CT.) The code value of the transformer’s connection group (see Table 1-1) (Yd11):
Code = 17
Differential protection
PRELIMINARY VERSION 30/48
1.9 Technical summary
1.9.1 Technical data
Function
Accuracy
Operating characteristic Dual slope + unrestrained section
Unrestrained differential < 3%
Base sensitivity <2%
Reset ratio 0.95
Operate time, restrained <35 ms
Reset time, restrained <40 ms
Operate time, unrestrained <20 ms
Reset time, unrestrained <40 ms
1.9.2 The measured values
The measured values of the differential protection function.
Measured value Dim. Explanation
Idiff. L1 In % The calculated differential current in phase L1 (after vector group compensation)
Idiff. L2 In % The calculated differential current in phase L2 (after vector group compensation)
Idiff. L3 In % The calculated differential current in phase L3 (after vector group compensation)
Ibias L1 In % The calculated restraint current in phase L1 (after vector group compensation)
Ibias L2 In % The calculated restraint current in phase L2 (after vector group compensation)
Ibias L3 In % The calculated restraint current in phase L3 (after vector group compensation)
Table 1-15 The measured analogue values of the differential protection function
Remark: The evaluated basic harmonic values of the measured input phase currents (without vector group compensation) help the commissioning of the differential protection function. These evaluations, however, are performed by an independent software measuring module; therefore, this chapter does not cover the description of these measurements.
1.9.3 The parameters of the differential protection function The parameters of the differential protection function are explained in the following tables. Enumerated parameters for the differential protection function:
Parameter name Title Selection range Default
Parameter to enable the differential protection function:
DIF87_Op_EPar_ Operation Off,On On
Parameter to select connection group of the transformer coils in primary-secondary relation:
DIF87_VGrSec_EPar_ Pri-Sec VGroup*
Dy1,Dy5,Dy7,Dy11,Dd0,Dd6,Dz0,Dz2,Dz4,Dz6,Dz8,Dz10,Yy0,Yy6,Yd1,Yd5,Yd7,Yd11,Yz1,Yz5,Yz7,Yz11
Dd0
Parameter to select connection group of the transformer coils in primary-secondary relation:
DIF87_VGrTer_EPar_ Pri-Ter VGroup*
Dy1,Dy5,Dy7,Dy11,Dd0,Dd6,Dz0,Dz2,Dz4,Dz6,Dz8,Dz10,Yy0,Yy6,Yd1,Yd5,Yd7,Yd11,Yz1,Yz5,Yz7,Yz11
Dd0
Table 1-16 The enumerated parameters of the differential protection function
Differential protection
PRELIMINARY VERSION 31/48
* If the connection of the primary winding in the primary-secondary and primary-tertiary relations is selected in contradiction, then the protection function is automatically disabled and the function generates a warning signal. Boolean parameter for the differential protection function:
Parameter name Title Default Explanation
DIF87_0Seq_BPar_ ZeroSequ.Elimination True See Chapter 1.2.4
Table 1-17 The Boolean parameters of the differential protection function
Integer parameters
Parameter name Title Unit Min Max Step Default
Parameters for the current magnitude compensation:
DIF87_TRPr_IPar_ TR Primary comp. % 20 500 1 100
DIF87_TRSec_IPar_ TR Secondary comp. % 20 500 1 100
DIF87_TRTer_IPar_ TR Tertiary comp. % 20 200 1 100
Parameter of the second harmonic restraint:
DIF87_2HRat_IPar_ 2nd Harm. Ratio % 5 50 1 15
Parameter of the fifth harmonic restraint:
DIF87_5HRat_IPar_ 5th Harm. Ratio % 5 50 1 25
Parameters of the percentage characteristic curve:
Base sensitivity:
DIF87_f1_IPar_ Base sensitivity % 10 50 1 20
Slope of the second section of the characteristics:
DIF87_f2_IPar_ 2. part of TripChar - 10 50 1 20
Slope of the third section of the characteristics:
DIF87_f3_IPar_ 3. part of TripChar - 200 2000 1 200
High-speed differential protection current level:
DIF87_HCurr_IPar_ Unrestrained I-Diff % 800 2500 1 800
Table 1-18 The integer parameters of the differential protection function
Floating point parameters The differential protection function does not have floating point parameters. Timer parameters The differential protection function does not have timers.
Differential protection
PRELIMINARY VERSION 32/48
1.9.4 Binary output status signals
The binary output status signals of the differential protection function.
Binary output signals Signal title Explanation
Restrained differential protection function
DIF87_L1St_GrI_ Start L1 Start of the restrained differential protection function in phase L1 (after vector group compensation)
DIF87_L2St_GrI_ Start L2 Start of the restrained differential protection function in phase L2 (after vector group compensation)
DIF87_L3St_GrI_ Start L3 Start of the restrained differential protection function in phase L3 (after vector group compensation)
DIF87_GenSt_GrI General Start General start of the restrained differential protection function
Unrestrained differential protection function
DIF87_UnRL1St_GrI_ Start L1 unrestr. Start of the unrestrained differential protection function in phase L1 (after vector group compensation)
DIF87_UnRL2St_GrI_ Start L2 unrestr. Start of the unrestrained differential protection function in phase L2 (after vector group compensation)
DIF87_UnRL3St_GrI_ Start L3 unrestr. Start of the unrestrained differential protection function in phase L3 (after vector group compensation)
DIF87_UnRGenSt_GrI_ General Start unrestr General start of the unrestrained differential protection function
Harmonic blocking
DIF87_2HBlk_GrI 2.Harm Restr. Restraint caused by high second harmonic content in any of the differential currents
DIF87_5HBlk_GrI 5.Harm Restr. Restraint caused by high fifth harmonic content in any of the differential currents
Table 1-19 The binary output status signals of the differential protection function
1.9.5 Binary input signal
The differential protection function has a binary input signal, which serves the purpose of disabling the function. The conditions of disabling are defined by the user applying the graphic equation editor.
Binary input signal Explanation
DIF87_Blk_GrO Output status of a graphic equation defined by the user to disable the differential protection function.
Table 1-20 The binary input signal of the differential protection function
Differential protection
PRELIMINARY VERSION 33/48
1.9.6 The function block
The function blocks of the differential protection function for transformers with two or three voltage levels are shown in Figure 1-10. This block shows all binary input and output status signals that are applicable in the graphic equation editor.
Figure 1-10 The function block of the differential protection function
Differential protection
PRELIMINARY VERSION 34/48
2 Appendix:
2.1 Current distribution inside the Y/d transformers For the explanation, the following positive directions are applied:
Fig. A2-1
Positive directions
2.1.1 Three-phase fault (or normal load state)
The figure below shows the current distribution inside the transformers in case of three-phase fault or at normal, symmetrical load state:
Currents in case of normal load (or three-phase fault)
Fig. A2-2
In this figure, k is the current ratio. The positive directions are supposed to be directed out of the transformer on both sides, as it is assumed by the differential protection. (If the directions suppose currents flowing through the transformer, then
I2R input = kI/√3(1-a2)
This indicates that the connection group of this transformer is Yd11.)
K L l k
I
+ +
I
r
TR
t
S
s
a2*I1Rinput*k/√3
I1Rinput I2Rinput
I1Rinput*k/√3
a*I1Rinput
I2Tinput
a2*I1Rinput
I2Sinput
a*I1Rinput*k/√3
R
Differential protection
PRELIMINARY VERSION 35/48
Here the primary currents form a symmetrical system:
a
aI
TinputI
SinputI
RinputI2
1
1
1
1
The secondary currents can be seen in the figure (please note the division factor √3 in the effective turns ratio):
)1(
)(
)1(
3
1*
2
2
22
2
a
aa
a
Ik
TinputI
SinputI
RinputI
Differential protection
PRELIMINARY VERSION 36/48
2.1.2 Phase-to-phase fault on the Y side Assume I current on the primary Y side between phases S and T.
Currents inside the transformer at ST fault on the Y side
Fig. A2-3
In this figure, k is the current ratio. The Y-side currents are:
1
1
0
1
1
1
I
TinputI
SinputI
RinputI
The delta-side currents can be seen in this figure:
1
2
1
*3
1*
2
2
2
Ik
TinputI
SinputI
RinputI
r
TR
t
S
s
I*k/√3
0 I*k/√3
0
-I
I*k/√3
-2* I*k/√3
-I*k/√3
R
I
Differential protection
PRELIMINARY VERSION 37/48
2.1.3 Phase-to-phase fault on the delta side
Assume I current on the secondary delta side between phases “s” and “t”. .
Currents inside the transformer at “st” fault on the delta side
Fig. A2-4
In this figure, k is the current ratio. The secondary currents are:
1
1
0
2
2
2
I
TinputI
SinputI
RinputI
These are distributed in the delta assuming a 2/3 : 1/3 distribution factor. Thus, the primary Y-side currents can be seen in this figure:
2
1
1
*3
1*
1
1
1
Ik
TinputI
SinputI
RinputI
r
TR
t
S
s
-1/3*I
-1/3*I*√3/k 0
-1/3*I
2/3*I*√3/k
-I
-1/3*I*√3/k
I
2/3*I
R
Differential protection
PRELIMINARY VERSION 38/48
2.1.4 Single-phase external fault on the Y side A) Assume I fault current in phase R in case of a solidly grounded neutral. No power supply is assumed on the delta side:
Currents inside the transformer at a single-phase fault on the Y side (Bauch effect)
Fig. A2-5
In this figure, k is the current ratio. The primary Y-side currents are:
1
1
1
1
1
1
I
TinputI
SinputI
RinputI
On the delta side, there are no currents flowing out of the transformer:
0
0
0
2
2
2
I
TinputI
SinputI
RinputI
r
TR
t
S
s
I*k/√3
I 0
I*k/√3
I
0
I
0
I*k/√3
R
Differential protection
PRELIMINARY VERSION 39/48
B) Assume I fault current on the Y side in phase R in case of a solidly grounded neutral. Assume the power supply on the delta side:
Currents inside the transformer at a single-phase fault on the Y side, supply on the delta side
Fig. A2-6
In this figure, k is the current ratio. The primary Y-side currents are:
0
0
1
1
1
1
I
TinputI
SinputI
RinputI
The delta-side currents can be seen in this figure:
1
0
1
*3
1*
2
2
2
Ik
TinputI
SinputI
RinputI
r
TR
t
S
s
0
I - I*k/√3
I*k/√3
0
I*k/√3
0
0
0
R
Differential protection
PRELIMINARY VERSION 40/48
2.1.5 Single-phase fault on the delta side
The delta side is usually applied at medium voltage levels. If a high/medium voltage transformer with delta secondary is used, then a separate neutral grounding transformer is applied for neutral grounding (Petersen or grounding resistance). The impedance between the neutral point and the ground suppresses the fault current below 100 A (perhaps 200 A), the Petersen coil allows only a few Amperes. On the delta side there are two locations for the current transformers supplying the differential protection. In one case the neutral grounding transformer is within the protected zone (see figure below, current transformers at location „Z”). The other possibility is for the neutral grounding transformer to be excluded from the protected zone (see figure below, current transformers at location „Y”).
2.1.5.1 Power supply on the Y side
As the zero sequence current component of the delta side can influence the behavior of the differential protection (sensitive setting), this chapter analyses the current distribution in case of a single-phase-to-ground fault on the delta side.
Current distribution at external single-phase-to-ground fault, Y-side power supply
Fig. A2-7
I√3/k
X
r
TR t
S
s
1
R
I√3/k
I√3/k -I√3/k
I√3/k
1
I√3/k
2I
-I
-I I
I
3I
3I
Y Z
2I 3I
CT positve direction Real current direction
Differential protection
PRELIMINARY VERSION 41/48
For the current distribution an external „r” phase fault is assumed, and at the fault location the current is Ir = 3Io. The arrows indicating the real currents can be constructed at this starting point. Based on the figure above, with positive directions out of the transformer the currents in the CT-s are: On the Y side (location X in Fig. 2-7):
0
1
1
/3
1
1
1
kI
TinputI
SinputI
RinputI
The delta-side currents at location „Y”:
1
1
2
2
2
2
I
TinputI
SinputI
RinputI
If the current is measured at location „Z”, then the node - which has to satisfy Kirchhoff’s node law – is extended by the neutral grounding transformer but the current flowing between the neutral point and the ground in not measured and not added to the current summation. This current is the 3Io zero sequence component, which can be calculated as the sum of the phase currents. At location „Z” the zero sequence component has no other path to flow but the neutral grounding transformer. The delta-side currents at location „Z”:
0
0
3
'2
'2
'2
I
TinputI
SinputI
RinputI
In this case, the zero sequence current is I. If the vector group compensation is for the delta side, then the transformation does not change this current; on the high-voltage side, however, there is no zero sequence component. In any event, the transformation would filter this component out. In practice, this zero sequence current component is always below the rated current of the transformer but if the differential protection is set to sensitive or a relay test set is applied mechanically without any logic control this can result in the faulty operation of the differential protection in case of an external fault. To avoid such faulty operation, there is a binary parameter in the differential protection the effect of which is to subtract the zero sequence current component from the phase currents if required:
1
1
2
1
1
1
0
0
3
20'2
20'2
20'2
2
2
2
III
ITinputI
ISinputI
IRinputI
TinputI
SinputI
RinputI
This means that based on the currents of the CT-s located at „Z”, the current that could be measured at location „Y” is calculated. NOTE: This zero sequence current subtraction could also be applied without any consequences to current transformers at location „Y” because in case of external faults, no
Differential protection
PRELIMINARY VERSION 42/48
zero sequence current can be detected at this location. In case of an internal fault, however, this decreases the faulty phase current by 2/3. This could worsen the sensitivity of the differential protection in the event of high-impedance internal faults. The subtraction of the zero sequence current in the case of measurement at location „Y” can be disabled using the aforementioned binary parameter.
2.1.5.2 Power supply on the delta side
If a transformer connects distributed generators on a medium voltage network with neutral grounding, a possible state of operation can be that the transformer is disconnected on the high-voltage Y side. No current can flow on the Y side and if the differential protection measures the currents on the medium voltage side at location „Z” (Fig. 2-8), then in case of a sensitive setting of the characteristic lines or at testing, the differential protection can generate a faulty trip command. The current distribution is shown in Fig. 2-8 below:
Current distribution in case of a delta-side single-phase fault, supply on the delta side
Fig. A2-8
X
r
TR t
S
s
R
3I
Y
CT „+” direction Real current
G
G
G
Z
I
I I I
I I
I
I
I 2I
I
I
3I
Differential protection
PRELIMINARY VERSION 43/48
In this case no current is detected at the point „X” (CB open):
0
0
0
1
1
1
TinputI
SinputI
RinputI
The measured currents at „Z” can be seen in the figure:
1
1
1
'2
'2
'2
I
TinputI
SinputI
RinputI
To avoid mal-operation (trip) in the event of an external fault, a binary parameter is applied the effect of which is to subtract the zero sequence current on the delta side:
0
0
0
1
1
1
1
1
1
20'2
20'2
20'2
2
2
2
II
ITinputI
ISinputI
IRinputI
TinputI
SinputI
RinputI
It means that based on the currents of the CT-s located at „Z”, the current, that could be measured at location „Y” is calculated. The faulty trip is avoided by this transformation.
Differential protection
PRELIMINARY VERSION 44/48
2.2 Checking the setting example
2.2.1 Checking in case of symmetrical rated load currents
For checking, the positive directions defined in the Appendix are applied:
Based on Fig. A2-2 of the Appendix, the primary currents are:
a
anpI
TinputI
SinputI
RinputI2
1
600
1*1
1
1
1
The transformed values of the primary side (See Table 1-1):
)1(
)(
)1(
00183.0*13
1
1
1
1
)1(
)(
)1(
_
100*
600
1*1
3
1
1
1
1
101
110
011
3
1
_
100
1
1
1
2
2
2
2
a
aa
a
npI
TshiftI
SshiftI
RshiftI
a
aa
a
primaryTRnpI
TinputI
SinputI
RinputI
primaryTRTshiftI
SshiftI
RshiftI
The secondary currents are illustrated in Fig. A2-2 of the Appendix (please note the division by √3 as defined by the turns ratio):
)1(
)(
)1(
6000
1*
3
1*
5.11
132*1
2
2
22
2
a
aa
a
npI
RinputI
RinputI
RinputI
The secondary currents are transformed by the unit matrix (see Table 1-1). It means that only the turns ratio is considered:
)1(
)(
)1(
00182.0*13
1
2
2
2
)1(
)(
)1(
*6000
1*
3
1*
5.11
132*1*
sec_
100
2
2
2
2
2
2
2
a
aa
a
npI
TshiftI
SshiftI
RshiftI
a
aa
a
npIondaryTR
TshiftI
SshiftI
RshiftI
These currents are the same (with the round-off error of 0.5%) as the primary transformed currents but multiplied by „-1”. As the differential currents are the sum of the shifted phase currents, these all result zero; the differential protection is balanced.
Differential protection
PRELIMINARY VERSION 45/48
2.2.2 Checking for Y-side external phase-to-phase fault Assume I fault current on the Y side of the transformer in phases S and T. According to Fig. A2-3 of the Appendix, the input currents from the primary side of the transformer:
1
1
0
**600
1
1
1
1
I
TinputI
SinputI
RinputI
Transforming these currents:
1
2
1
00183.0**3
1
1
1
1
1
2
1
_
100*
600
1**
3
1
1
1
1
101
110
011
*3
1
1
1
1
I
TshiftI
SshiftI
RshiftI
primaryTRI
TinputI
SinputI
RinputI
TshiftI
SshiftI
RshiftI
The input currents from the secondary side of the transformer can be seen in Fig. A2-3 of the Appendix:
1
2
1
**3
1*
5.11
132*
6000
1
2
2
2
I
TinputI
SinputI
RinputI
According to Table 1, these secondary-side currents are transformed with the unit matrix; therefore, only the turns ratio has to be considered:
1
2
1
00182.0*3
1
2
2
2
1
2
1
*6000
1*
3
1*
5.11
132**
sec_
100
2
2
2
I
TshiftI
SshiftI
RshiftI
IondaryTR
TshiftI
SshiftI
RshiftI
These currents are the same (with the round-off error of 0.5%) as the primary transformed currents but multiplied by „-1”. As the differential currents are the sum of the shifted phase currents, these all result zero; the differential protection is balanced. Please note the multiplication factor „2” in phase S. Its consequences will be analyzed in a separate chapter.
Differential protection
PRELIMINARY VERSION 46/48
2.2.3 Checking for D-side external phase-to-phase fault Assume I fault current on the D side of the transformer in phases S and T. According to Fig. A2-4 of the Appendix, the input currents to the differential protection are:
1
1
0
**6000
1
2
2
2
I
TinputI
SinputI
RinputI
According to Table 1-1, these secondary side currents are transformed with the unit matrix, therefore, only the turns ratio has to be considered:
1
1
0
*10*1587.0
2
2
2
1
1
0
*6000
1*
sec_
100
2
2
2
3 I
TshiftI
SshiftI
RshiftI
IondaryTR
TshiftI
SshiftI
RshiftI
The input currents from the primary Y side can be seen on Fig. A2-4 of the Appendix:
2
1
1
3
1**3*
132
5.11*
600
1
1
1
1
I
TinputI
SinputI
RinputI
The transformation of these Y-side currents according to Table 1:
1
1
0
**10*1596.0
1
1
0
**132
5.11*3*
3
1*
1
100*
600
1
1
1
1
101
110
011
*3
1
1
1
1
3 I
IIbe
TinputI
SinputI
RinputI
TshiftI
SshiftI
RshiftI
1
1
0
*10*1596.0*
1
1
1
1
1
0
132
5.11*
_
100*
600
1**
3
1
1
1
1
101
110
011
*3
1
1
1
1
3I
TshiftI
SshiftI
RshiftI
primaryTRI
TinputI
SinputI
RinputI
TshiftI
SshiftI
RshiftI
These currents are the same (with a round-off error of. 0.5%) as the secondary transformed currents but multiplied by „-1”. As the differential currents are the sum of the shifted phase currents, these all result zero; the differential protection is balanced. Please note the multiplication factor „-1” and „1” in phases S and T, respectively. Its consequences will be analyzed in a separate chapter.
Differential protection
PRELIMINARY VERSION 47/48
2.2.4 Checking for Y-side external phase-to-ground fault A) If the neutral point of the transformer is grounded, an R phase-to-ground primary I fault current can be supposed. Suppose additionally that no supply from the delta side can be expected. Based on Fig. A2-5 of the Appendix, the input currents from the Y side are:
1
1
1
**600
1
1
1
1
I
TinputI
SinputI
RinputI
The transformation of the primary currents according to Table 1:
0
0
0
0
0
0
_
100*
600
1**
3
1
1
1
1
101
110
011
*3
1
1
1
1
primaryTRI
TinputI
SinputI
RinputI
TshiftI
SshiftI
RshiftI
The secondary currents can be seen on Fig. A2-5 of the Appendix:
0
0
0
**3
1*
5.11
132*
6000
1
2
2
2
I
TinputI
SinputI
RinputI
Based on Table 1-1, these secondary currents are transformed with the unit matrix, so only the turns ratio is considered:
0
0
0
0
0
0
**3
1*
5.11
132*
6000
1*
2
100
2
2
2
IIbe
TshiftI
SshiftI
RshiftI
0
0
0
0
0
0
5.11
132*
_
100*
6000
1**
3
1
2
2
2
primaryTRI
TshiftI
SshiftI
RshiftI
Because of zero currents, the differential protection is stable. B) Now suppose I fault current in phase R on the external primary side of the transformer if the neutral is grounded. The fault is supplied in this case from the delta side: Based on Fig. A2-6 of the Appendix, the input currents from the primary side are:
0
0
1
**600
1
1
1
1
I
TinputI
SinputI
RinputI
Differential protection
PRELIMINARY VERSION 48/48
The transformation of these primary currents:
1
0
1
00183.0**3
1
1
1
1
1
0
1
_
100*
600
1**
3
1
1
1
1
101
110
011
*3
1
1
1
1
I
TshiftI
SshiftI
RshiftI
primaryTRI
TinputI
SinputI
RinputI
TshiftI
SshiftI
RshiftI
The input currents from the delta side, based on Fig. A2-6 of the Appendix are:
1
0
1
**3
1*
5.11
132*
6000
1
2
2
2
I
TinputI
SinputI
RinputI
Based on Table 1-1, these secondary currents are transformed with the unit matrix, so only the turns ratio is considered:
1
0
1
**3
1*00182.0
1
0
1
**3
1*
5.11
132*
6000
1*
2
100
2
2
2
I
IIbe
TshiftI
SshiftI
RshiftI
1
0
1
00182.0*3
1
2
2
2
1
0
1
*6000
1*
3
1*
5.11
132**
sec_
100
2
2
2
I
TshiftI
SshiftI
RshiftI
IondaryTR
TshiftI
SshiftI
RshiftI
The currents are balanced; the differential protection does not generate a trip command.