Ducted SplitAir ConditionerSERVICE MANUALMODELS: LN-0880CC

LN-1080CCLN-1380CCLN-1580CCLN-2080CC

Page 2: Dik Tip Servis

L N - 1 0 8 0 C CC: ConvertibleH: Horizontal FlowD: Down Flow

C: Cooling OnlyH: Heat Pump

1 : 115/60/15 : 200-220/50/18 : 380-415/50/3B : 220/60/3

2 : 220/60/16 : 220-240/50/19 : 380-415/60/3C : 440-460/50/3

3 : 208-230/60/17 : 100/50(60)/1A : 220/50/3D : 440-460/60/3

03 : 3 ton 08 : 7.5 ton 15 : 15 ton04 : 4 ton 09 : 8.5 ton 18 : 17.5 ton05 : 5 ton 10 : 10 ton 20 : 20 ton06 : 6.25 ton 13 : 12.5 ton 25 : 25 ton

Development Sequence

Nominal cooling capacity

LGDucted Split Air Conditioner

— 2 —

Contents

Model Number Nomenclature

Model Number Nomenclature...............................................................................................2

General Data ..........................................................................................................................3

Dimensions ............................................................................................................................5

Wiring Diagram......................................................................................................................6

Troubleshooting Guide .........................................................................................................8

Features of Controller .........................................................................................................20

Exploded View and Replacement Parts List .....................................................................25

Page 3: Dik Tip Servis

— 3 —

General Data

Table-1

1) Test Condition of ARI Rated Cooling Capacity :Ambient:95°F , Air entering temprature : 80°F DB and 67°F WB

2) ARI standard210/240 or 360 for EER270 for Sound

Models

(Btu/h)

Cooling (W)

(kcal/h)

Electric Heater (Watt)

Electrical Data Voltage (PH,Hz,V)

Running CurrentCooling

(Amps)

M.C.A (Amps)

Power Input Cooling (Watt)

Performance EER Cooling (Btu/hr.W)

Air Circulation (Indoor/Outdoor) (m3/min)

Moisture Removal ( /hr)

Noise Cooling dB(A)

Outdoor (dB(A),1m)

Wired Remote Controller

Time Delay Safety Function

Vertical Air-flow Direction control

Horizontal Air-flow Directioon control

Cooling Operation Mode

Heating Operation Mode

Features Air Circulation Mode

Soft Dry Operation

Fan Speeds (steps)

Auto-Operation

Sleep Mode

Timer Setting (24-Hour on/off)

Forced Operation

Self-Diagnosis Function

Tube Size (mm)

Outdoor CoilRow/FPI

Length (mm)

Face Area (m2)

Tube Size (mm)

Indoor CoilRow/FPI

Length (mm)

Face Area (m2)

Type

Outdoor FanNo. used/Diameter

Drive Type

RPM

DimensionsIndoor unit (WxHxD) (mm)

Outdoor unit (WxHxD) (mm)

Net WeightIndoor unit kg(Ibs)

Outdoor unit kg(Ibs)

Service ValveLiquid (mm)

Gas (mm)

Stuffing Without S/Parts (20FT/40FT)

LN-0880CC LN-1080CC

78,000 108,000

22,854 31,644

19,656 27,216

Option(9/18kW) Option(9/18kW)

3/380-415/50 3/380-415/50

16.5 20

21 30

8,200 11,200

9.5 9.6

75 / 121 100 / 130

7.5 11

- -

88 90

O O

O O

O O

O O

O O

O(With E/Heater) O(With E/Heater)

O O

O O

Variable Speed Variable Speed

Auto-Restart Auto-Restart

O O

O O

O O

O O

9.52 9.52

2/17FPI 2/17FPI

1809.4 2076

1.65 1.9

9.52 9.52

2/17FPI 2/17FPI

1100 1100

0.84 0.84

Propeller Propeller

2/526 2/526

Direct Direct

900 900

1260*1120*635 1260*1120*635

1245*930*650 1245*930*650

140(307) 150(331)

160(353) 169(373)

15.88 12.7*2

25.4 19.05*2

12/24 12/24

Capacity

Page 4: Dik Tip Servis

— 4 —

General Data

Table-2

1) Test Condition of ARI Rated Cooling Capacity :Ambient:95°F , Air entering temprature : 80°F DB and 67°F WB

2) ARI standard210/240 or 360 for EER270 for Sound

Models

(Btu/h)

Cooling (W)

(kcal/h)

Electric Heater (Watt)

Electrical Data Voltage (PH,Hz,V)

Running CurrentCooling

(Amps)

M.C.A (Amps)

Power Input Cooling (Watt)

Performance EER Cooling (Btu/hr.W)

Air Circulation (Indoor/Outdoor) (m3/min)

Moisture Removal ( /hr)

Noise Cooling dB(A)

Outdoor (dB(A),1m)

Wired Remote Controller

Time Delay Safety Function

Vertical Air-flow Direction control

Horizontal Air-flow Directioon control

Cooling Operation Mode

Heating Operation Mode

Features Air Circulation Mode

Soft Dry Operation

Fan Speeds (steps)

Auto-Operation

Sleep Mode

Timer Setting (24-Hour on/off)

Forced Operation

Self-Diagnosis Function

Tube Size (mm)

Outdoor CoilRow/FPI

Length (mm)

Face Area (m2)

Tube Size (mm)

Indoor CoilRow/FPI

Length (mm)

Face Area (m2)

Type

Outdoor FanNo. used/Diameter

Drive Type

RPM

DimensionsIndoor unit (WxHxD) (mm)

Outdoor unit (WxHxD) (mm)

Net WeightIndoor unit kg(Ibs)

Outdoor unit kg(Ibs)

Service ValveLiquid (mm)

Gas (mm)

Stuffing Without S/Parts (20FT/40FT)

LN-1380CC LN-1580CC LN-2080CC

132,000 159,000 215,000

38,676 46,587 62,995

33,264 40,068 54,180

Option(18/36kW) Option(18/36kW) Option(18/36kW)

3/380-415/50 3/380-415/50 3/380-415/50

24 33 42

34 42 54

13,300 16,200 22,000

9.9 9.8 9.8

124 / 140*2 150 / 121*2 199 / 130*2

13.5 16.5 20

- - -

92 92 92

O O O

O O O

O O O

O O O

O O O

O(With E/Heater) O(With E/Heater) O(With E/Heater)

O O O

O O O

Variable Speed Variable Speed Variable Speed

Auto-Restart Auto-Restart Auto-Restart

O O O

O O O

O O O

O O O

9.52 9.52 9.52 9.52 9.52 9.52

2/17FPI 2/17FPI 2/17FPI 2/17FPI 2/17FPI 2/17FPI

1809.4 1809.4 1809.4 1809.4 1809.4 1809.4

1.65 1.65 1.65 1.65 1.65 1.65

9.52 9.52 9.52

3/17FPI 3/17FPI 3/17FPI

1100 1400 1300

0.84 1.07 1.42

Propeller Propeller Propeller

2/526 2/526 2/526 2/526 2/526 2/526

Direct Direct Direct Direct Direct Direct

900 900 900 900 900 900

1260*1120*635 1560*1120*635 1460*1653*818

1245*930*650 1245*930*650 1245*930*650 1245*930*650 1245*930*650 1245*930*650

160(373) 170(375) 210(463)

2*160(2*353) 2*160(2*353) 2*169(2*373)

12.7 12.7 15.88 15.88 15.88 15.88

25.4 25.4 25.4 25.4 25.4 25.4

9/20 7/16 4/9

Capacity

Page 5: Dik Tip Servis

— 5 —

Dimensions

LN-0880CC/LN-1080CC/LN-1380CC/LN-1580CC/LN-2080CC

1. Indoor unitUnit Dimensions

2. Outdoor unitLN-0880CC, LN-1080CCLN-1380CC, LN-1580CCLN-2080CC

• Each model of these three models(LN-1380CC/LN-1580CC/LN-2080CC) is operated with the dou-bled of the right outdoor unit.

A

D

E

C

HI

J

K

M

BL

F

G

930

130

70.5

750

650

750

1245

435

350

A 49.6(1,260) 49.6(1,260) 61.4(1,500) 57.5(1,460)B 25(635) 25(635) 25(635) 25.6(650)C 44.1(1,120) 44.1(1,120) 44.1(1,120) 65.1(1,653)D 14.2(362) 9.8(248) 10.6(269) 12.7(332)E 14(356) 18.5(470) 18.5(470) 24.3(617)F 13.4(340) 13.4(340) 15.7(398) 19.2(487)G 10.8(274) 10.8(274) 8.4(214) 11.8(299)H 23.3(593) 23.3(593) 23.3(593) 29.2(740)I 2(51) 2(51) 2(51) 2(51)J 7.1(180) 7.1(180) 7.1(180) 7.1(180)K 7.9(200) 7.9(200) 7.9(200) 7.9(200)L 2(51) 2(51) 2(51) 2(51)M 22.1(562) 22.1(562) 22.1(562) 22.1(562)

Unit: inch(mm)

Unit: inch(mm)

MODELLN-0880CC LN-1380CC LN-1580CC LN-2080CCLN-1080CC

Page 6: Dik Tip Servis

— 6 —

Wiring Diagram

LN-0880CC

LN-1080CC

Page 7: Dik Tip Servis

— 7 —

Wiring Diagram

LN-1380CC/LN-1580CC/LN-2080CC

Page 8: Dik Tip Servis

Troubleshooting Guide

— 8 —

Ineffective Cooling or Heating

Check of outdoor coil(heat exchanger) & the fanoperation.

Check gas leakage.

Repair gas leak.

Replacement of unit if theunit is beyond repair.

Satisfactory operation withtemperature difference ofinlet & outlet air ;COOLING : 7~10°CHEATING : 15~17°C

Check heat load increase incooling operation.

Unexpected residue

Added electrical utencil

Check of inside gaspressure.

Adjust refrigerantcharge.

Malfunction of compressor.

Replacement ofcompressor

Check of cold (warm) air cir-culation for smooth flow.

Dirty indoor coil(heat exchanger.)

Malfunction of fan.

Clogging of air filter.

Obstruction at air outlet.

Countermeasure againstabove trouble.

Check clogging in refrigera-tion circuit.

Repair clogging in refrigera-tion circuit.

In general, possible trouble is classified in two causes.The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective AirConditioning caused by a defect in the refrigeration circuit and improper application.

Unit runs but ineffective cooling

Page 9: Dik Tip Servis

— 9 —

Troubleshooting Guide

Fails to Start

Check of circuit breakerand fuse.

Check control switch.

Fan only fails to start.

Improper wiring.

Defect of fan motorcapacitor.Defect of compressor

capacitor.

Irregular motor resistance( Ω )Irregular motor insulation( Ω )

Replacement of fan motor.

Improper electric heater

Replacement of electric heater.

Regular but fails to start.

Replacement of compressor.

Electric heater is not energized

Loose terminal connection.

Improper wiring

Irregular motor resistance ( Ω )

Irregular motor insulation ( Ω )

Replacement of compressor

Drop of power voltage.

Capacitor check.

Replacement of capacitor.

Compressor only fails to start.

Check power source.

Check control switchsetting.

Page 10: Dik Tip Servis

— 10 —

Troubleshooting Guide

VOLTAGE LIMITS

1. No cooling and heating operation performed1) Both the blower and the compressor do not work

NAME PLATE RATING MINIMUM MAXIMUM

380 - 415 V 342 V 456 V

2) Only Indoor blowers do not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Other parts except theunit

Magnetic switch for com-pressor & fan motor

Operating switch

• Electric supply interrupted• Defective power wiring• Cut off power fuse

Too low voltage

Control point is on condi-tion of "OFF" due to trou-ble.

Troubled or defectivecontactor

Measure power sypplywith a tester in case thatthe same power source issupplied to other equip-ment except the unit,what and where troubledcan be discovered bychecking the operation ofother equipment.

Measure it with a tester.

Make short-circuit, thenmeasure it with tester.

Check it with the eyes ortester.

• Repair a switch box andrelative instrument.

• Replacement of fuse

• Request a powersupplier to repair.

Check the power source.Use a thick cable if nec-essary.

Replace it if necessary.

Repair or replace it.

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Motor

Capacitor

Electric wiring

• Over heated• Wiring short

Defected

• Cut- OFF of wiring• Short circuited on

operation

Check it with tester

Check it with a tester.

Check it with a tester.

Repair or replace it.

Replace it.

Rewiring or Repair.

Page 11: Dik Tip Servis

— 11 —

Troubleshooting Guide

3) Only outdoor fan does not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Motor

Electric Wiring

• Over-heated• Wire short

Cut off of wiring

Short circuited onoperation

Check how it is insulated.

Check it with a tester.

Repair or replace it.

Rewiring or repair.

4) Only compressor does not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Magnetic switch forcompressor motor

Compressor motor

High pressure switch(Option part)

Electric circuit

Defective contact,magnetic coil troubled.

Troubled over-heated(layer short)

Troubled or defectivecontact or operating

Defective connection ordisconnection of the circuitfor compressor.

Check it with the eyes onwith a tester.

Check how it is insulated.

Check it with a tester.

Check it with a tester.

Repair or replace it.

Replace or repair thecompressor.

Replace it if neces-sary.

Rewiring or push resetbutton.

Page 12: Dik Tip Servis

— 12 —

Troubleshooting Guide

Note: Use an appropriate measuring instrument for readjustment.

*1: High-pressure switch moves.

*2: Low- pressure switch moves.

2. The Units discontinue after the operation started

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Outdoor coil

In-condensable gasblended.

High pressure switch(Option part)

Refrigerant

Outdoor Fan

Coil is dirty *1

Air intruded into therefrigerant pipe line *1

Improper adjustment

A shortage of refrigerantamount. * 2

Check pressure

Reverse rotation of fanObstacle

Air short circuit *1

Checking

In the event thatdifference between thesaturating temperaturecorresponding to highpressure and thetemperature of airdischarged from theoutdoor coil is more than15°C, incondensable gasmay be blended.

Check it with a pressuregauge.

Confirm the wind blowingout upward.

Check it with eyes.

Wash it by means ofsomething like chemicalwashing.

Extract air by vacuumpump, then replenish(charge) the refrigerant.

Read just it to normaloperating pressure.(Note)Don't alternate thespecified adjustingpressure. If the adjustedpressure exceed thespecified range, it willcause a great accident.

Replenish therefrigerant. Repair thespot where it is leaked.

If reversed, connectinterchanged wires toeach terminal.Power wirings.

Page 13: Dik Tip Servis

— 13 —

Troubleshooting Guide

3. The unit is working, but not cooling and heating sufficiently(Both blower and compressor are working)

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Load

Air flow

Short air volume

Refrigerant

Air passage

Air filter

Much Cooling or Heatingload

Obstacle disturbs Intakeof uniform airflow.

Reverse rotation ofblower.

Shortage in the chargedrefrigerant.

Improper or foreign bodies

Clogged with dust

Heat load increased.Window or door has manycracks or gaps.

Checking

Checking

Coil inlet pipe is frosted

Checking

Checking

Do necessary disposalrespectively.

Correct it.

Correct it.

Recharge it.(Repair the leakage spot).

Correct or clear theforeign bodies.

Cleaning

4. All the functions are performed as specified, but very noisy and vibrantWHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Compressor

Blower

Screws

Electric troubles(Magnetic contactor)

Others

• Checking

Checking

Checking

Checking

Improper installation Checking

• Replace thecompressor

Repair or replace it.Clear the foreign bodies.

Correct

Repair and clean orreplace it.

Correct it.

Liquid refrigerant floodingback from the evaporator.

Faulty Discharge valveand suction valve.

Fan broken.

Foreign matters intruded.

Looseness or fail-off ofscrews

Defective contact.Defective contact point.Rusting and foreign mat-ters in the iron core con-tact face. Defective con-tact of theoperating switch.

• Check for refrigerant over-charge.• Check to see if the intake air temperature is

extremely cold.• Check for insufficient air flow quantity.

Page 14: Dik Tip Servis

— 14 —

Electronic parts Troubleshooting Guide

YES

YES

YES

NO

YES

Is the input voltage oftransformer AC220V?

Is the output voltageof IC02D(7805) on the

main PCB DC5V?

1. Check the Fuse.2. Check the wiring of AC220V.

Is the output voltageof IC01D(7812 ) on the

main PCB DC12V?

OSC vibration?

1. Exchange main PCB ASS'Y

1. Exchange remote-controller2. Check or exchange the Main PCB ASS'Y.

YES

NO 1. Exchange the transformer.2. Check the connector of transformer.

NO

NO

1. Exchange IC02D(7805) on the main PCB.2. Check the D01D~D05D, R05C on the main PCB.

NO

YES

Is the output voltageof IC01A(7036) on the

main PCB DC5V?

NO

1. Exchange IC01D(7812) on the main PCB.2. Check the D01D~D05D, R05C on the main PCB.

1. Exchange IC01A(7036) on the main PCB.

Is the output voltage oftransformer AC24V & AC13V?

1. Exchange OSC.2. Check the pattern around OSC on the main PCB.

Is the input voltageof remote-controller

DC12V?

YES

NO

YES

Is the power ON?NO

1. Exchange or exchange FUSE.2. Check the input voltage of Main PCB ASS'Y.

1. Check or exchange the IC01D on the Main PCB.2. Check or exchange the Connector (RED, BROWN) of the remote controller.

Possible trouble 1 : The unit does not operate.

Possible trouble 2 : The remote-controller does not operate.

Page 15: Dik Tip Servis

— 15 —

Electronic parts Troubleshooting Guide

YES

NO

YES

NO

NO

Is the connection betweenMAIN PCB and remote-controller

correct?

Is there Check(F**) onthe remote controller LCD?

1. Check or repair Connector wiring.2. Exchange the Connector.

Is the input power voltage ofremote-controller DC12V?

Do Keys have troubles?

Exchange remote-controller.

Exchange remote-controller.

NO

YES 1. Replace the pressed key.2. Exchange the Knob or Key.

YES

NO

1. Remove cause of Check.2. Reenergize the power supply.

YES

YES

Is there OSC vibration onthe remote-controller PCB?

NO

1. Check or exchange IC01D (7812) on the MAIN PCB.

1. Exchange OSC2. Check the pattern around OSC on the remote-controller PCB.

Is any key on the remote-controllerkeeping pressed?

1. Check Keys.2. Repair or exchange Key.

Is there trouble in theremote-controller PCB

ASS'Y?

NO

YES

NO

Are there trouble inLCD parts?

YES1. Check crack, damage of LCD.2. Check LCD pattern.

1. Check or repair all IC with dust or moisture on the PCB.2. Exchange remote-controller PCB.

Possible trouble 3 : Key input of remote-controller does not respond.

Possible trouble 4 : LCD display on the remote-controller shows some trouble.

Page 16: Dik Tip Servis

— 16 —

Electronic parts Troubleshooting Guide

YES

YES

NO

YES

Is the cooling mode?1. Press cooling operation key.2. After reenergizing power supply, press power "ON/OFF" button.

YES

NOIs the unit operating? 1. Press power ON/OFF button.

Is the outputvoltage of Micom's 4PIN on the

MAIN PCB DC0V?

Is the magnetic contactorfor compressor OK?

1. Check Compressor and Capacitor for Compressor.

NOTE: 3ø model has not capacitor for compressor.

YES

NO 1. Set flowing. 'Set Temp. < Room Temp.'

NO

NO

YES

Is the voltagebetween 1PIN of CN-COMP and

NEUTRAL 220V?

NO

1. Check or exchange IC02D.2. Check 3-minutes time delay.

1. Check or exchange RY4.

Set Temp. < Room Temp.?

1. Check the wiring of Magnetic contactor.2. Exchange Magnetic contactor.

Possible trouble 5 : No cooling operation performed.

Page 17: Dik Tip Servis

— 17 —

Electronic parts Troubleshooting Guide

Is the heater LCD "ON"?1. Reconnetting power supply. press Heater Key.

Is the heater operation? 1. Select heater operation mode.

Is the outputvoltage of Micom's 13PIN on the

MAIN PCB 5V?

Is the magnetic contactor forheater OK?

Check or exchange E/Heater.

1. Set following. 'Set temp. > Room temp.'

1. Check or exchange IC01D, IC02D on the MAIN PCB.

Is the voltagebetween 1PIN of CN6 and

NEUTRAL 220V?1. Check or exchange RY13.

Set temp. > Room temp.?

1. Check the wiring of Magnetic contactor.2. Exchange Magnetic contactor.

YES

YES

NO

YES

YES

NO

YES

NO

NO

NO

YES

NO

Possible trouble 6 : No heater operation performed.

Page 18: Dik Tip Servis

— 18 —

Electronic parts Troubleshooting Guide

Is the indoor fan operation?1. Press cooling or fan operation or heater operation key.

Is the outputvoltage of Micom's 3PIN on

the MAIN PCB 5V?

Is the magneticcontactor for humidifier OK?

Check the humidifier.

1. Press humidifier Key.

1. Check or exchange IC02D on the MAIN PCB.

Is the voltagebetween 1PIN of CN5 and

NEUTRAL 220V?1. Check or exchange RY3.

Is the HUMID LCD "ON"?

1. Check the wiring or Magnetic contactor.2. Exchange Magnetic contactor.

YES

YES

NO

YES

YES

NO

NO

NO

YES

NO

Possible trouble 7 : No humidifier operation performed.

Page 19: Dik Tip Servis

— 19 —

Electronic parts Troubleshooting Guide

Is the unit operating?

Is the outputvoltage of Micom's 10PIN on

the MAIN PCB 5V?

Is the "Power relay" forindoor motor OK?

Check the indoor motor.

1. Press power ON/OFF button.2. Reconnect the power supply.

Is the voltagebetween 1PIN of CN8 and

NEUTRAL 220V?

1. Check or exchange IC01D, IC02D on the main PCB.

1. Check or exchange RY10.

1. Check the wiring of "Power relay".2. Exchange "Power relay".

YES

YES

YES

NO

NO

NO

YES

NO

Is the compressor operating?

1. Check wiring for outdoor motor and magnetic contactor.2. Check outdoor motor & capacitor.

Is it cooling operation? 1. Press power "ON/OFF" button.2. Select cooling operation.

1. Set following. Set temp. < Room temp.2. Wait, if the unit has operating with 3-minute time delay.

YES

NO

YES

NO

Possible trouble 8 : Indoor motor does not operate.

Possible trouble 9 : Outdoor motor does not operate.

Page 20: Dik Tip Servis

Features of Controller

— 20 —

1. Main Controller Circuit Diagram

Page 21: Dik Tip Servis

— 21 —

2. Feature of Main Controller

Page 22: Dik Tip Servis

— 22 —

3. Feature of Remote-Controller PCB ASS'Y

4. Feature of Remote-Controller LCD

Page 23: Dik Tip Servis

— 23 —

5. Error Mode & Corrective Method

6. Principal part list of controller

7. Principal part list of Main PCB ASM 8. Principal part list of Remote Controller

Error mode

F01

F04

F05

F02

F03

Cause of error

OPEN/SHORT ofroom temp.sensor

OPEN/SHORT ofoutdoor pipesensor

OPEN/SHORT ofindoor pipe temp.sensor

OPEN/SHORT ofoutdoor roomtemp. sensor

CommunicationError

RemarkSensing condition of error

Voltage of sensing: Over 4.8VVoltage of sensing: Less than

0.5V

Voltage of sensing: Over 4.8VVoltage of sensing: Less than

0.5V

1. Check the voltage of "CO1H"on the remote controller.

2. Check the temp. sensor ofremtote controller.

1. Check the voltage between PIN1 and 2 of CN-A cycle/CN-Bcycle ON the main PCB.

2. Check the temp. sensor of rem-tote controller.

1. Check the voltage between PIN 3and 4 of CN-A cycle/CN-B cycle.

2. Check the temp. sensor ofindoor pipe.

1. Check the voltage betweenPIN 1 and 3 of CN-TEMPOUT on the main PCB.

2. Check the temp. sensor ofoutdoor room.

1. Check the connecting wirebetween main PCB remotecontroller.

2. Check the input voltage ofremote-controller.

3. Check the wiring ofremote-controller.

Roomtemp.(25°C)= DC 2.5V

Pipetemp.(25°C)= DC 2.5V

Pipe temp.(25°C)= DC 2.2V

Roomtemp.(25°C)= DC 2.2V

Input voltage ofremote-controller

= DC 12V

Voltage of sensing: Over 4.8VVoltage of sensing: Less than

0.5V

Voltage of sensing: Over 4.8VVoltage of sensing: Less than

0.5V

Communication interruptionbetween remote controller andMain PCB for 2 minutes.

Method of SVC

LN-0880CC 6871A20085G 6711A20043A 6323A20002N -6323AQ3214M

6171AQ2138D Cooling Only(Option)

LN-1080CCLN-1380CC 6871A20085H 6711A20043A 6711A20002N 6323A20002P 6323AQ3214M 6171AQ2138D Cooling OnlyLN-1580CC (Option)LN-2080CC

Model Main PCBASM

Remote con-troller

PipeSensor A

PipeSensor B

Return AirSensor Power Trans Remark

No Part No Part Name Remarks1 0ITO874000E MICOM(Main) MICOM2 6920AQ9033F Relay3 6212AQ9002J Oscillator4 6900AQ9028D Fuse5 6102A90001A Varistor

No Part No Part Name Remark1 OITO641010B MICOM(Remote Controller) MICOM2 6304A30001C LCD3 6871A10022M Remote C PCB ASM Cooling Only

Page 24: Dik Tip Servis

— 24 —

9. Explanation of principal function Flow Chart

Power ON?

Cooling Mode?

Time delay mode

Cooling operating

Set Temp. < Indoor Temp.

YES

YES

YES

NO

YES

YES

Stop condition?

YES

1. Initialize "micom".2. A/D convert.3. Main PCB: Waiting cooling operation.4. Remote controller: Waiting input.

YES

START(Power supply)

Go to A

Fan only operating

Stop condition?

YES

Go to A

Dehumidification Mode?

Dehumidification operating

YES

Stop condition?

YES

Go to A

Set Temp. > Indoor Temp.

Heater operating

YES

Heater operation mode?

YES

Stop condition?

YES

NO

NO

NO NO

NO

NO

NO

NO

A

YES

Go to A

Page 25: Dik Tip Servis

— 25 —

Exploded View and Replacement Parts List

359012

354210 713269

346810

249951

261704

268714

552111

W6920

330870

W4400

145610

1. Indoor Unit• Exploded View (LN-08/10/13/15/2080CC)

Page 26: Dik Tip Servis

— 26 —

Exploded View and Replacement Parts List

5540

31

5660

01

6499

50

5522

03

4353

11

5541

60

W0C

ZZ

W69

20

3468

11

5590

10

2. Outdoor Unit• Exploded View (LN-08/10/13/15/2080CC)

Page 27: Dik Tip Servis

— 27 —

Exploded View and Replacement Parts List

W4400 BELT, V 4400A30001V 1

W0CZZ CAPACITOR, DRAWING 2H00841J 2

554160 COMPRESSOR ASSY, FINAL 5417A20007F 1

554031 CONDENSER ASSY, BENT 5403AP2618H 4

249951 CONTROL BOX ASSEMBLY, INDOOR 4995A10043D 1

649950 CONTROL BOX ASSY, OUTDOOR 4995AP2608K 1

330870 DRAIN PAN ASSEMBLY 3087A20009B 2

354210 EVAPORATOR ASSY, FIRST 5421A20029C 1

559010 FAN ASSEMBLY, PROPELLER 0A00026B 4

359012 FAN, SIDE 5835A20001A 1

435311 GRILLE ASSY, DISCHARGE(OUTDOOR) 2A00144P 2

346811 MOTOR ASSEMBLY, OUTDOOR 4680AP2610B 2

346810 MOTOR ASSY, INDOOR 4681A20018B 1

145610 PULLEY ASSEMBLY 3A00217R 1

145610 PULLEY ASSY 4561A30001L 1

268714 PWB(PCB) ASSY, MAIN 6871A20085G 1

W6920 RELAY 6920AP3400A 2

694790 REMOTE CONTROLLER ASSY 6711A20043A 1

566001 SWITCH, MAGNET 2A01031A 1

713269 THERMISTOR ASSY 6323A20002N 1

261704 TRANSFORMER, POWER 6171AQ2138D 1

552111 TUBE ASSY, CAPILLARY 5211A20297K 1

552203VALVE, SERVICE 2A00468C 1

VALVE, SERVICE 2A00469H 1

LOCATION No. DESCRIPTION LN-0880CC QUANTITY

• Replacement Parts ListLN-0880CC

Page 28: Dik Tip Servis

— 28 —

Specification of components

W4400 BELT,V 4400A30002M 1

W0CZZ CAPACITOR,DRAWING 2H00841J 2

554160 COMPRESSOR 5417A20008G 2

554031 CONDENSER ASSY,BENT 5403AP2618B 4

249951 CONTROL BOX ASSEMBLY,INDOOR 4995A10043C 1

649950 CONTROL BOX ASSY,OUTDOOR 4995A20080D 1

330870 DRAIN PAN ASSEMBLY 3087A20009B 1

354210 EVAPORATOR ASSY,FIRST 5421A20029D 2

559010 FAN ASSEMBLY,PROPELLER 0A00026B 2

359012 FAN,SIDE 5835A20003A 1

435311 GRILLE ASSY,DISCHARGE(OUTDOOR) 2A00144P 2

346811 MOTOR ASSEMBLY,INDOOR 4681A20025C 2

346810 MOTOR ASSEMBLY,OUTDOOR 4680AP2610B 2

145610 PULLEY ASSEMBLY 3A00217R 1

145610 PULLEY ASSY 4561A30002B 1

268714 PWB(PCB) ASSY,MAIN 6871A20085H 1

W6920 RELAY 6920AP3400A 2

694790 REMOTE CONTROLLER ASSY 6711A20043A 1

566001 SWITCH,MAGNET 2A01031A 2

713269THERMISTOR ASSY 6323A20002N 1

THERMISTOR ASSY 6323A20002P 1

261704 TRANSFORMER,POWER 6171AQ2138D 1

552111 TUBE ASSY,CAPILLARY 5211A20297E 2

552203VALVE,SERVICE 2A00499E 2

VALVE,SERVICE 2H01890M 2

LOCATION No. DESCRIPTION LN-1080CC QUANTITY

• Replacement Parts ListLN-1080CC

Page 29: Dik Tip Servis

— 29 —

Exploded View and Replacement Parts List

W4400 BELT, V 4400A30002M 1

W0CZZ CAPACITOR, DRAWING 2H00841J 4

554160 COMPRESSOR 5417A20007H 2

554031 CONDENSER ASSY, BENT 5403AP2618H 8

249951 CONTROL BOX ASSEMBLY, INDOOR 4995A10043C 1

649950 CONTROL BOX ASSY, OUTDOOR 4995AP2608M 2

330870 DRAIN PAN ASSEMBLY 3087A20009D 2

354210 EVAPORATOR ASSY, FIRST 5421A20029B 1

559010 FAN ASSEMBLY, PROPELLER 0A00026B 4

359012 FAN, SIDE 5835A20003B 1

435311 GRILLE ASSY, DISCHARGE(OUTDOOR) 2A00144P 4

346811 MOTOR ASSEMBLY, INDOOR 4681A20025C 1

346810 MOTOR ASSEMBLY, OUTDOOR 4680AP2610B 4

145610PULLEY ASSEMBLY 3A00217R 1

PULLEY ASSY 4561A30002A 1

268714 PWB(PCB) ASSY, MAIN 6871A20085H 1

W6920 RELAY 6920AP3400A 1

694790 REMOTE CONTROLLER ASSY 6711A20043A 1

566001 SWITCH, MAGNET 2A01031A 2

713269THERMISTOR ASSY 6323A20002N 1

THERMISTOR ASSY 6323A20002P 1

261704 TRANSFORMER, POWER 6171AQ2138D 1

552111 TUBE ASSY, CAPILLARY 5211A20297T 2

552203VALVE, SERVICE 2A00468C 2

VALVE, SERVICE 2A00469H 2

LOCATION No. DESCRIPTION LN-1380CC QUANTITY

• Replacement Parts ListLN-1380CC

Page 30: Dik Tip Servis

— 30 —

Exploded View and Replacement Parts List

W4400 BELT, V 4400A30002G 1

W0CZZ CAPACITOR, DRAWING 2H00841J 4

554160 COMPRESSOR 5417A20007F 2

554031 CONDENSER ASSY, BENT 5403AP2618H 8

249951 CONTROL BOX ASSEMBLY, INDOOR 4995A10043C 1

649950 CONTROL BOX ASSY, OUTDOOR 4995AP2608M 2

330870 DRAIN PAN ASSEMBLY 3087A20009F 2

354210 EVAPORATOR ASSY, FIRST 5421A20029E 1

559010 FAN ASSEMBLY, PROPELLER 0A00026B 4

359012 FAN, SIDE 5835A20003B 1

435311 GRILLE ASSY, DISCHARGE(OUTDOOR) 2A00144P 4

346811 MOTOR ASSEMBLY, INDOOR 4681A20025D 1

346810 MOTOR ASSEMBLY, OUTDOOR 4680AP2610B 4

145610PULLEY ASSEMBLY 3A00217R 1

PULLEY ASSY 4561A30002A 1

268714 PWB(PCB) ASSY, MAIN 6871A20085H 1

W6920 RELAY 6920AP3400A 1

694790 REMOTE CONTROLLER ASSY 6711A20043A 1

566001 SWITCH, MAGNET 2A01031A 2

713269THERMISTOR ASSY 6323A20002N 1

THERMISTOR ASSY 6323A20002P 1

261704 TRANSFORMER, POWER 6171AQ2138D 1

552111 TUBE ASSY, CAPILLARY 5211A20297T 2

552203VALVE, SERVICE 2A00469H 2

VALVE, SERVICE 2A00468E 2

LOCATION No. DESCRIPTION LN-1580CC QUANTITY

• Replacement Parts ListLN-1580CC

Page 31: Dik Tip Servis

— 31 —

Exploded View and Replacement Parts List

W4400 BELT, V 4400A30002J 1

W0CZZ CAPACITOR, DRAWING 2H00841J 4

554160 COMPRESSOR 5417A20007G 2

554031 CONDENSER ASSY, BENT 5403AP2618H 8

249951 CONTROL BOX ASSEMBLY, INDOOR 4995A10043C 1

649950 CONTROL BOX ASSY, OUTDOOR 4995AP2608M 2

330870 DRAIN PAN ASSEMBLY 3087A20009F 2

354210 EVAPORATOR ASSY, FIRST 5421A20029H 2

559010 FAN ASSEMBLY, PROPELLER 0A00026B 4

359012 FAN, SIDE 5835A20003D 1

435311 GRILLE ASSY, DISCHARGE(OUTDOOR) 2A00144P 4

346811 MOTOR ASSEMBLY, INDOOR 4681A20031D 1

346810 MOTOR ASSEMBLY, OUTDOOR 4680AP2610B 4

145610PULLEY ASSEMBLY 3A00217S 1

PULLEY ASSY 4561A30003C 1

268714 PWB(PCB) ASSY, MAIN 6871A20085H 1

W6920 RELAY 6920AP3400A 1

694790 REMOTE CONTROLLER ASSY 6711A20043A 1

566001 SWITCH, MAGNET 2A01031A 2

713269THERMISTOR ASSY 6323A20002N 1

THERMISTOR ASSY 6323A20002P 1

261704 TRANSFORMER, POWER 6171AQ2138D 1

552111 TUBE ASSY, CAPILLARY 5211A20297U 2

552203VALVE, SERVICE 2A00469H 2

VALVE, SERVICE 2A00468E 2

LOCATION No. DESCRIPTION LN-2080CC QUANTITY

• Replacement Parts ListLN-2080CC

Page 32: Dik Tip Servis

— 32 —

Memo

Page 33: Dik Tip Servis

— 33 —

Memo

Page 34: Dik Tip Servis

P/No.: 3828A30027Z

Novermber, 2001

Printed in Korea