directional kgf.pdf

Upload: anoopksurendran13

Post on 09-Oct-2015

56 views

Category:

Documents


5 download

TRANSCRIPT

  • Types KCGG 122, 142, KCEG 112, 142, 152,

    242 and KCEU 142, 242

    Overcurrent and Directional Overcurrent Relays

    Service Manual

    R8551E

  • Pxxxx/EN SS/B11

    SAFETY SECTION

  • Pxxxx/EN SS/B11 Safety Section Page 1/10

    CONTENTS

    1. INTRODUCTION 3 2. HEALTH AND SAFETY 3 3. SYMBOLS AND EXTERNAL LABELS ON THE EQUIPMENT 4

    3.1 Symbols 4

    3.2 Labels 4

    4. INSTALLING, COMMISSIONING AND SERVICING 4 5. DECOMMISSIONING AND DISPOSAL 7 6. EQUIPMENT WHICH INCLUDES ELECTROMECHANICAL ELEMENTS 7 7. TECHNICAL SPECIFICATIONS FOR SAFETY 7

    7.1 Protective fuse rating 7

    7.2 Protective Class 7

    7.3 Installation Category 7

    7.4 Environment 8

    8. CE MARKING 8 9. RECOGNIZED AND LISTED MARKS FOR NORTH AMERICA 9

  • Pxxxx/EN SS/B11 Page 2/10 Safety Section

    BLANK PAGE

  • Pxxxx/EN SS/B11 Safety Section Page 3/10

    1. INTRODUCTION This guide and the relevant operating or service manual documentation for the equipment provide full information on safe handling, commissioning and testing of this equipment and also includes descriptions of equipment label markings.

    Documentation for equipment ordered from AREVA T&D is despatched separately from manufactured goods and may not be received at the same time. Therefore this guide is provided to ensure that printed information normally present on equipment is fully understood by the recipient.

    Before carrying out any work on the equipment the user should be familiar with the contents of this Safety Guide.

    Reference should be made to the external connection diagram before the equipment is installed, commissioned or serviced.

    Language specific, self-adhesive User Interface labels are provided in a bag for some equipment.

    2. HEALTH AND SAFETY The information in the Safety Section of the equipment documentation is intended to ensure that equipment is properly installed and handled in order to maintain it in a safe condition.

    It is assumed that everyone who will be associated with the equipment will be familiar with the contents of that Safety Section, or this Safety Guide.

    When electrical equipment is in operation, dangerous voltages will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger personnel and equipment and cause personal injury or physical damage.

    Before working in the terminal strip area, the equipment must be isolated.

    Proper and safe operation of the equipment depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason only qualified personnel may work on or operate the equipment.

    Qualified personnel are individuals who

    are familiar with the installation, commissioning, and operation of the equipment and of the system to which it is being connected;

    are able to safely perform switching operations in accordance with accepted safety engineering practices and are authorised to energize and de-energize equipment and to isolate, ground, and label it;

    are trained in the care and use of safety apparatus in accordance with safety engineering practices;

    are trained in emergency procedures (first aid). The operating manual for the equipment gives instructions for its installation, commissioning, and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate AREVA technical sales office and request the necessary information.

  • Pxxxx/EN SS/B11 Page 4/10 Safety Section

    3. SYMBOLS AND EXTERNAL LABELS ON THE EQUIPMENT For safety reasons the following symbols and external labels, which may be used on the equipment or referred to in the equipment documentation, should be understood before the equipment is installed or commissioned.

    3.1 Symbols

    Caution: refer to equipment documentation Caution: risk of electric shock

    Protective Conductor (*Earth) terminal.

    Functional/Protective Conductor Earth terminal Note This symbol may also be used for a Protective Conductor (Earth) terminal if that terminal is part of a terminal block or sub-assembly e.g. power supply.

    *NOTE: THE TERM EARTH USED THROUGHOUT THIS GUIDE IS THE DIRECT EQUIVALENT OF THE NORTH AMERICAN TERM GROUND.

    3.2 Labels

    See "Safety Guide" (SFTY/4L M) for equipment labelling information.

    4. INSTALLING, COMMISSIONING AND SERVICING

    Equipment connections

    Personnel undertaking installation, commissioning or servicing work for this equipment should be aware of the correct working procedures to ensure safety.

    The equipment documentation should be consulted before installing, commissioning or servicing the equipment.

    Terminals exposed during installation, commissioning and maintenance may present a hazardous voltage unless the equipment is electrically isolated.

    Any disassembly of the equipment may expose parts at hazardous voltage, also electronic parts may be damaged if suitable electrostatic voltage discharge (ESD) precautions are not taken.

    If there is unlocked access to the rear of the equipment, care should be taken by all personnel to avoid electric shock or energy hazards.

    Voltage and current connections should be made using insulated crimp terminations to ensure that terminal block insulation requirements are maintained for safety. To ensure that wires are correctly terminated the correct crimp terminal and tool for the wire size should be used.

    The equipment must be connected in accordance with the appropriate connection diagram.

  • Pxxxx/EN SS/B11 Safety Section Page 5/10

    Protection Class I Equipment - Before energising the equipment it must be earthed using the protective

    conductor terminal, if provided, or the appropriate termination of the supply plug in the case of plug connected equipment.

    - The protective conductor (earth) connection must not be removed since the protection against electric shock provided by the equipment would be lost.

    The recommended minimum protective conductor (earth) wire size is 2.5 mm (3.3 mm for North America) unless otherwise stated in the technical data section of the equipment documentation, or otherwise required by local or country wiring regulations.

    The protective conductor (earth) connection must be low-inductance and as short as possible.

    All connections to the equipment must have a defined potential. Connections that are pre-wired, but not used, should preferably be grounded when binary inputs and output relays are isolated. When binary inputs and output relays are connected to common potential, the pre-wired but unused connections should be connected to the common potential of the grouped connections.

    Before energising the equipment, the following should be checked: - Voltage rating/polarity (rating label/equipment documentation); - CT circuit rating (rating label) and integrity of connections; - Protective fuse rating; - Integrity of the protective conductor (earth) connection (where

    applicable); - Voltage and current rating of external wiring, applicable to the

    application.

    Equipment Use If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

    Removal of the equipment front panel/cover Removal of the equipment front panel/cover may expose hazardous live parts which must not be touched until the electrical power is removed.

    UL and CSA Listed or Recognized Equipment To maintain UL and CSA approvals the equipment should be installed using UL and/or CSA Listed or Recognized parts of the following type: connection cables, protective fuses/fuseholders or circuit breakers, insulation crimp terminals, and replacement internal battery, as specified in the equipment documentation.

    Equipment operating conditions The equipment should be operated within the specified electrical and environmental limits.

    Current transformer circuits Do not open the secondary circuit of a live CT since the high voltage produced may be lethal to personnel and could damage insulation. Generally, for safety, the secondary of the line CT must be shorted before opening any connections to it.

    For most equipment with ring-terminal connections, the threaded terminal block for current transformer termination has automatic CT shorting on removal of the module. Therefore external shorting of the CTs may not be required, the equipment documentation should be checked to see if this applies.

    For equipment with pin-terminal connections, the threaded terminal block for current transformer termination does NOT have automatic CT shorting on removal of the module.

  • Pxxxx/EN SS/B11 Page 6/10 Safety Section

    External resistors, including voltage dependent resistors (VDRs) Where external resistors, including voltage dependent resistors (VDRs), are fitted to the equipment, these may present a risk of electric shock or burns, if touched.

    Battery replacement Where internal batteries are fitted they should be replaced with the recommended type and be installed with the correct polarity to avoid possible damage to the equipment, buildings and persons.

    Insulation and dielectric strength testing Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of each part of the test, the voltage should be gradually reduced to zero, to discharge capacitors, before the test leads are disconnected.

    Insertion of modules and pcb cards Modules and pcb cards must not be inserted into or withdrawn from the equipment whilst it is energised, since this may result in damage.

    Insertion and withdrawal of extender cards

    Extender cards are available for some equipment. If an extender card is used, this should not be inserted or withdrawn from the equipment whilst it is energised. This is to avoid possible shock or damage hazards. Hazardous live voltages may be accessible on the extender card.

    Insertion and withdrawal of integral heavy current test plugs

    It is possible to use an integral heavy current test plug with some equipment. CT shorting links must be in place before insertion or removal of heavy current test plugs, to avoid potentially lethal voltages.

    External test blocks and test plugs

    Great care should be taken when using external test blocks and test plugs such as the MMLG, MMLB and MiCOM P990 types, hazardous voltages may be accessible when using these. *CT shorting links must be in place before the insertion or removal of MMLB test plugs, to avoid potentially lethal voltages.

    *Note when a MiCOM P992 Test Plug is inserted into the MiCOM P991 Test Block, the secondaries of the line CTs are automatically shorted, making them safe.

    Fibre optic communication

    Where fibre optic communication devices are fitted, these should not be viewed directly. Optical power meters should be used to determine the operation or signal level of the device.

    Cleaning

    The equipment may be cleaned using a lint free cloth dampened with clean water, when no connections are energised. Contact fingers of test plugs are normally protected by petroleum jelly which should not be removed.

  • Pxxxx/EN SS/B11 Safety Section Page 7/10

    5. DECOMMISSIONING AND DISPOSAL

    Decommissioning:

    The supply input (auxiliary) for the equipment may include capacitors across the supply or to earth. To avoid electric shock or energy hazards, after completely isolating the supplies to the equipment (both poles of any dc supply), the capacitors should be safely discharged via the external terminals prior to decommissioning.

    Disposal:

    It is recommended that incineration and disposal to water courses is avoided. The equipment should be disposed of in a safe manner. Any equipment containing batteries should have them removed before disposal, taking precautions to avoid short circuits. Particular regulations within the country of operation, may apply to the disposal of batteries.

    6. EQUIPMENT WHICH INCLUDES ELECTROMECHANICAL ELEMENTS

    Electrical adjustments

    It is possible to change current or voltage settings on some equipment by direct physical adjustment e.g. adjustment of a plug-bridge setting. The electrical power should be removed before making any change, to avoid the risk of electric shock.

    Exposure of live parts

    Removal of the cover may expose hazardous live parts such as relay contacts, these should not be touched before removing the electrical power.

    7. TECHNICAL SPECIFICATIONS FOR SAFETY

    7.1 Protective fuse rating The recommended maximum rating of the external protective fuse for equipments is 16A, high rupture capacity (HRC) Red Spot type NIT, or TIA, or equivalent, unless otherwise stated in the technical data section of the equipment documentation. The protective fuse should be located as close to the unit as possible.

    DANGER - CTs must NOT be fused since open circuiting them may

    produce lethal hazardous voltages. 7.2 Protective Class

    IEC 61010-1: 2001 EN 61010-1: 2001

    Class I (unless otherwise specified in the equipment documentation). This equipment requires a protective conductor (earth) connection to ensure user safety.

    7.3 Installation Category

    IEC 61010-1: 2001 EN 61010-1: 2001

    Installation Category III (Overvoltage Category III):

    Distribution level, fixed installation.

    Equipment in this category is qualification tested at 5kV peak, 1.2/50s, 500, 0.5J, between all supply circuits and earth and also between independent circuits

  • Pxxxx/EN SS/B11 Page 8/10 Safety Section

    7.4 Environment

    The equipment is intended for indoor installation and use only. If it is required for use in an outdoor environment then it must be mounted in a specific cabinet or housing which will enable it to meet the requirements of IEC 60529 with the classification of degree of protection IP54 (dust and splashing water protected).

    Pollution Degree Pollution Degree 2 Altitude operation up to 2000 m IEC 61010-1: 2001 EN 61010-1: 2001

    Compliance is demonstrated by reference to safety standards.

    8. CE MARKING

    Marking Compliance with all relevant European Community directives:

    Product safety: Low Voltage Directive - 73/23/EEC amended by 93/68/EEC EN 61010-1: 2001 EN 60950-1: 2001 EN 60255-5: 2001 IEC 60664-1: 2001

    Compliance demonstrated by reference to safety standards.

    Electromagnetic Compatibility Directive (EMC) 89/336/EEC amended by 93/68/EEC.

    The following Product Specific Standard was used to establish conformity:

    EN 50263 : 2000

    Compliance demonstrated via the Technical Construction File route.

    Where applicable :

    II (2) G

    ATEX Potentially Explosive Atmospheres directive 94/9/EC, for equipment.

    The equipment is compliant with Article 1(2) of European directive 94/9/EC. It is approved for operation outside an ATEX hazardous area. It is however approved for connection to Increased Safety, Ex e, motors with rated ATEX protection, Equipment Category 2, to ensure their safe operation in gas Zones 1 and 2 hazardous areas.

    CAUTION Equipment with this marking is not itself suitable for operation within a potentially explosive atmosphere.

    Compliance demonstrated by Notified Body certificates of compliance.

    Radio and Telecommunications Terminal Equipment (R & TTE) directive 95/5/EC.

    Compliance demonstrated by compliance to the Low Voltage Directive, 73/23/EEC amended by 93/68/EEC, down to zero volts, by reference to safety standards.

  • Pxxxx/EN SS/B11 Safety Section Page 9/10

    9. RECOGNIZED AND LISTED MARKS FOR NORTH AMERICA CSA - Canadian Standards Association

    UL - Underwriters Laboratory of America

    UL Recognized to UL (USA) requirements

    UL Recognized to UL (USA) and CSA (Canada) requirements

    UL Listed to UL (USA) requirements

    UL Listed to UL (USA) and CSA (Canada) requirements

    Certified to CSA (Canada) requirements

  • Pxxxx/EN SS/B11 Page 10/10 Safety Section

    BLANK PAGE

  • SERVICE MANUAL R8551DKCGG 122, 142 ContentsKCEG 112, 142, 152, 242KCEU 142, 242

    SAFETY SECTION

    THIS MUST BE READ BEFORE ANY WORK IS CARRIED OUT ON THE RELAY

    CHAPTER 1 INTRODUCTION

    CHAPTER 2 HANDLING AND INSTALLATION

    CHAPTER 3 RELAY DESCRIPTION

    CHAPTER 4 APPLICATION OF PROTECTION FUNCTIONS

    CHAPTER 5 MEASUREMENT AND RECORDS

    CHAPTER 6 SERIAL COMMUNICATIONS

    CHAPTER 7 TECHNICAL DATA

    CHAPTER 8 COMMISSIONING

    APPENDIX 1 RELAY CHARACTERISTIC CURVES

    APPENDIX 2 LOGIC DIAGRAMS

    APPENDIX 3 CONNECTION DIAGRAMS

    APPENDIX 4 COMMISSIONING TEST RECORD

    Page 2

  • SAFETY SECTION

    This Safety Section should be read before commencing any work onthe equipment.

    Health and safety

    The information in the Safety Section of the product documentation is intended toensure that products are properly installed and handled in order to maintain themin a safe condition. It is assumed that everyone who will be associated with theequipment will be familiar with the contents of the Safety Section.

    Explanation of symbols and labels

    The meaning of symbols and labels which may be used on the equipment or in theproduct documentation, is given below.

    Caution: refer to product documentation Caution: risk of electric shock

    Protective/safety *earth terminal

    Functional *earth terminal.Note: this symbol may also be used for a protective/safety earth terminal if that terminal is part of aterminal block or sub-assembly eg. power supply.

    *Note: The term earth used throughout the product documentation is the directequivalent of the North American term ground.

    Installing, Commissioning and ServicingEquipment connections

    Personnel undertaking installation, commissioning or servicing work on thisequipment should be aware of the correct working procedures to ensure safety.The product documentation should be consulted before installing, commissioning orservicing the equipment.

    Terminals exposed during installation, commissioning and maintenance maypresent a hazardous voltage unless the equipment is electrically isolated.

    If there is unlocked access to the rear of the equipment, care should be taken by allpersonnel to avoid electric shock or energy hazards.

    Voltage and current connections should be made using insulated crimpterminations to ensure that terminal block insulation requirements are maintainedfor safety. To ensure that wires are correctly terminated, the correct crimp terminaland tool for the wire size should be used.

    Page 3

  • Before energising the equipment it must be earthed using the protective earthterminal, or the appropriate termination of the supply plug in the case of plugconnected equipment. Omitting or disconnecting the equipment earth may cause asafety hazard.

    The recommended minimum earth wire size is 2.5 mm2, unless otherwise stated inthe technical data section of the product documentation.

    Before energising the equipment, the following should be checked:

    Voltage rating and polarity;

    CT circuit rating and integrity of connections;

    Protective fuse rating;

    Integrity of earth connection (where applicable)

    Equipment operating conditions

    The equipment should be operated within the specified electrical andenvironmental limits.

    Current transformer circuits

    Do not open the secondary circuit of a live CT since the high voltage producedmay be lethal to personnel and could damage insulation.

    External resistors

    Where external resistors are fitted to relays, these may present a risk of electricshock or burns, if touched.

    Battery replacement

    Where internal batteries are fitted they should be replaced with the recommendedtype and be installed with the correct polarity, to avoid possible damage to theequipment.

    Insulation and dielectric strength testing

    Insulation testing may leave capacitors charged up to a hazardous voltage. At theend of each part of the test, the voltage should be gradually reduced to zero, todischarge capacitors, before the test leads are disconnected.

    Insertion of modules and pcb cards

    These must not be inserted into or withdrawn from equipment whilst it is energised,since this may result in damage.

    Fibre optic communication

    Where fibre optic communication devices are fitted, these should not be vieweddirectly. Optical power meters should be used to determine the operation or signallevel of the device.

    Page 4

  • Older ProductsElectrical adjustments

    Equipments which require direct physical adjustments to their operating mechanismto change current or voltage settings, should have the electrical power removedbefore making the change, to avoid any risk of electric shock.

    Mechanical adjustments

    The electrical power to the relay contacts should be removed before checking anymechanical settings, to avoid any risk of electric shock.

    Draw out case relays

    Removal of the cover on equipment incorporating electromechanical operatingelements, may expose hazardous live parts such as relay contacts.

    Insertion and withdrawal of extender cards

    When using an extender card, this should not be inserted or withdrawn from theequipment whilst it is energised. This is to avoid possible shock or damagehazards. Hazardous live voltages may be accessible on the extender card.

    Insertion and withdrawal of heavy current test plugs

    When using a heavy current test plug, CT shorting links must be in place beforeinsertion or removal, to avoid potentially lethal voltages.

    Decommissioning and Disposal

    Decommissioning: The auxiliary supply circuit in the relay may includecapacitors across the supply or to earth. To avoid electricshock or energy hazards, after completely isolating thesupplies to the relay (both poles of any dc supply), thecapacitors should be safely discharged via the externalterminals prior to decommissioning.

    Disposal: It is recommended that incineration and disposal to watercourses is avoided. The product should be disposed of in asafe manner. Any products containing batteries should havethem removed before disposal, taking precautions to avoidshort circuits. Particular regulations within the country ofoperation, may apply to the disposal of lithium batteries.

    Page 5

  • Technical SpecificationsProtective fuse rating

    The recommended maximum rating of the external protective fuse for thisequipment is 16A, Red Spot type or equivalent, unless otherwise stated in thetechnical data section of the product documentation.

    Insulation class: IEC 61010-1: 1990/A2: 1995 This equipment requires aClass I protective (safety) earthEN 61010-1: 1993/A2: 1995 connection to ensure userClass I safety.

    Installation IEC 61010-1: 1990/A2: 1995 Distribution level, fixedCategory Category III installation. Equipment in(Overvoltage): EN 61010-1: 1993/A2: 1995 this category is qualification

    Category III tested at 5kV peak,1.2/50s, 500, 0.5J,between all supply circuitsand earth and also betweenindependent circuits.

    Environment: IEC 61010-1: 1990/A2: 1995 Compliance is demonstratedPollution degree 2 by reference to genericEN 61010-1: 1993/A2: 1995 safety standards.Pollution degree 2

    Product safety: 73/23/EEC Compliance with theEuropean Commission LowVoltage Directive.

    EN 61010-1: 1993/A2: 1995 Compliance is demonstratedEN 60950: 1992/A11: 1997 by reference to generic

    safety standards.

    Page 6

  • Types KCGG 122, 142,KCEG 112, 142, 152, 242 and

    KCEU 142, 242Overcurrent and Directional Overcurrent

    RelaysService Manual

    Chapter 1Introduction

  • SERVICE MANUAL R8551DKCGG 122, 142, Chapter 1KCEG 112, 142, 152, 242, ContentsKCEU 142, 242

    1. INTRODUCTION 12. USING THE MANUAL 13. AN INTRODUCTION TO K RELAYS 24. MODELS AVAILABLE 35. AVAILABILITY OF MAIN FEATURES 4

  • SERVICE MANUAL R8551DKCGG 122, 142, Chapter 1KCEG 112, 142, 152, 242, Page 1 of 4KCEU 142, 242

    Section 1. INTRODUCTION

    The K Range of overcurrent and directional overcurrent relays has beenrationalised and additional features have been added to the individual relays towiden their application. Some menu cell locations have changed to accommodatethe new features and so setting files that have been generated for the series 1relays to suit particular applications may need some small modification before theycan be used with the new K Range series 2. However, the menu locations formeasured values and other data that is accessed by SCADA equipment retain theiroriginal locations. Hence the changes should be transparent to mostcommunication interfaces that may have been developed.

    Manual R8501 should be used for K Range series 1 relays.

    This manual details the menu, functions and logic for the K Range series 2 relays.

    Section 2. USING THE MANUAL

    This manual provides a description of the K Range series 2 overcurrent anddirectional overcurrent range of protection relays. It is intended to guide the userthrough application, installation, setting and commissioning of the relays.

    The manual has the following format:

    Chapter 1. Introduction

    An introduction on how to use this manual and a generalintroduction to the relays covered by the manual.

    Chapter 2. Handling and installation

    Precautions to be taken when handling electronic equipment

    Chapter 3. Relay description

    A detailed description of features that are common to allK Range series 2 relays.

    Chapter 4. Application of protection functions

    An introduction to the applications of the relays and specialfeatures provided.

    Chapter 5. Measurements and records

    How to customise the measurements and use the recording features.

    Chapter 6. Serial communications

    Hints on using the serial communication feature.

    Chapter 7. Technical data

    Comprehensive details on the ratings, setting ranges andspecifications etc.

    Chapter 8. Commissioning

    A guide to commissioning, problem solving and maintenance.

    Appendix Appendices include relay characteristic curves, logic diagrams,connection diagrams and commissioning test records.

  • SERVICE MANUAL R8551DKCGG 122, 142, Chapter 1KCEG 112, 142, 152, 242, Page 2 of 4KCEU 142, 242

    Section 3. AN INTRODUCTION TO K RELAYS

    The K Range of protection relays brings numerical technology to the successfulMidos range of protection relays. Fully compatible with the existing designs andsharing the same modular housing concept, the relays offer more comprehensiveprotection for demanding applications.

    Each relay includes an extensive range of control and data gathering functions toprovide a completely integrated system of protection, control, instrumentation, datalogging, fault, event and disturbance recording. The relays have a user-friendly 32character liquid crystal display (LCD) with 4 push buttons which allow menunavigation and setting changes. Also, by utilising the simple 2-wire communicationlink, all of the relay functions can be read, reset and changed on demand from alocal or remote personal computer (PC) loaded with the relevant software.

    With enhanced versatility, reduced maintenance requirements and low burdens,K Range relays provide a more advanced solution to power system protection.The K Range series 2 relays have new features that are additional to those foundon series 1 relays. The additional functions include:

    Protection thermal, underfrequency, broken conductor detection, rectifierprotection and improved undervoltage

    Measurement thermal ammeters, single phase W and VAR

    Logic improved logic flexibility

    Recording additional methods of resetting the disturbance recorder, triggeringthe disturbance recorder from the logic inputs, thresholds on circuitbreaker maintenance counter and contact arcing duty plus 5 fullfault records.

    KCGG relays provide overcurrent and earth fault protection for power distributionsystems, industrial power systems and all other applications where overcurrentprotection is required. The relays are used in applications where time gradedovercurrent and earth fault protection is required. The earth fault protectionprovides suitable sensitivity for most systems where the earth fault current is limited.

    KCEG relays provide directional overcurrent and earth fault protection.The overcurrent elements can be selectively directionalised, making the relays acost effective option where both directional and non-directional protection isrequired. The sensitivity of earth fault protection has been increased to cover mostapplications. The earth fault protection provides suitable sensitivity for most systemswhere the earth fault current is limited.

    KCEU relays provide directional overcurrent and sensitive wattmetric earth faultprotection for systems which are earthed through a Petersen coil.

    Integral features in K Range relays include circuit breaker failure protection, backtripping, blocked overcurrent protection for feeders or busbars, cold load pick-upfacilities, load shedding capabilities and two alternative groups of predeterminedsettings. The relays also have integral serial communication facilities via K-Bus.

  • SERVICE MANUAL R8551DKCGG 122, 142, Chapter 1KCEG 112, 142, 152, 242, Page 3 of 4KCEU 142, 242

    Section 4. MODELS AVAILABLE

    The following list of models is covered by this manual

    KCGG 122 One phase overcurrent and earth fault relay

    KCGG 142 01 Three phase overcurrent and earth fault relay

    KCGG 142 02 Three phase overcurrent and earth fault relay with reduced I/O

    KCEG 112 Directional earth fault

    KCEG 142 Directional three phase overcurrent and directional earth fault relay

    KCEG 152 Three phase overcurrent relay and directional earth fault relay

    KCEG 242 Directional three phase overcurrent and directional earth fault relay

    KCEU 142 Directional three phase overcurrent and wattmetric sensitive earthfault relay

    KCEU 242 Directional three phase overcurrent and wattmetric sensitive earthfault relay

    Note: The 100 series of relays are powered by a DC/AC auxiliarysupply. The 200 series of relays are dual powered, ie. poweredby a DC/AC auxiliary supply or from the current transformercircuit in the absence of an auxiliary supply.

    K Range series 2 relay Equivalent K Range series 1 relays

    KCGG 122 KCGG 110, KCGU 110

    KCGG 142 KCGG 120, KCGG 130, KCGG 140, KCGU 140

    KCEG 112 KCEG 110, KCEU 110

    KCEG 142 KCEG 130, KCEG 140, KCEU 140

    KCEG 152 KCEG 150, KCEU 150, KCEG 160, KCEU 160

    KCEG 242 KCGG/KCEG 210, KCGG/KCEG 230,KCGG/KCEG 250, KCGG/KCGU 240,KCEG/KCEU 240

    KCEU 142 KCEU 141

    KCEU 242 KCEU 241

    Table of equivalence between K Range series 1 and series 2 relays

  • SERVICE MANUAL R8551DKCGG 122, 142, Chapter 1KCEG 112, 142, 152, 242, Page 4 of 4KCEU 142, 242

    Section 5. AVAILABILITY OF MAIN FEATURES

    The following table lists the features that vary between models

    Feature KCGG KCGG KCGG KCEG KCEG KCEG KCEG KCEU KCEU122 142 01 142 02* 112 142 152 242 142 242

    Protection

    Overcurrent l l l l l l l lEarth fault l l l l l l l l lDirectional overcurrent l l l lDirectional earth fault l l l l l lUnderfrequency l l l l lUndervoltage l l l lThermal overload l l l l l l l lWattmetric l lMeasurement

    Frequency l l l l l l lCurrent l l l l l l l l lVoltage l l l lSingle phase power l lThree phase power l l l lThermal ammeter(s) l l l l l l l lThermal demand(s) l l l l l l l lThermal state l l l l l l l lCB operations l l l l l l l l lCB contact duty l l l l l l l lProgrammable Inputs/Outputs

    Logic inputs 3 8 3 3 8 8 8 8 8

    Output relays 4 8 4 4 8 8 8 8 8

    * The fully functionality KCGG 142 01 relay is also available as a KCGG 142 02with reduced I/O.

  • Types KCGG 122, 142,KCEG 112, 142, 152, 242 and

    KCEU 142, 242Overcurrent and Directional Overcurrent

    RelaysService Manual

    Chapter 2Handling and Installation

  • SERVICE MANUAL R8551CKCGG 122, 142 Chapter 2KCEG 112, 142, 152, 242 ContentsKCEU 142, 242

    1. GENERAL CONSIDERATIONS 11.1 Receipt of relays 11.2 Electrostatic discharge (ESD) 12. HANDLING OF ELECTRONIC EQUIPMENT 13. RELAY MOUNTING 24. UNPACKING 25. STORAGE 3

  • SERVICE MANUAL R8551CKCGG 122, 142 Chapter 2KCEG 112, 142, 152, 242 Page 1 of 3KCEU 142, 242

    Section 1. GENERAL CONSIDERATIONS

    1.1 Receipt of relays

    Protective relays, although generally of robust construction, require carefultreatment prior to installation on site. Upon receipt, relays should be examinedimmediately to ensure no damage has been sustained in transit. If damage hasbeen sustained during transit a claim should be made to the transport contractorand AREVA T&D should be promptly notified.

    Relays that are supplied unmounted and not intended for immediate installationshould be returned to their protective polythene bags.

    1.2 Electrostatic discharge (ESD)

    The relays use components that are sensitive to electrostatic discharges.The electronic circuits are well protected by the metal case and the internal moduleshould not be withdrawn unnecessarily. When handling the module outside itscase, care should be taken to avoid contact with components and electricalconnections. If removed from the case for storage, the module should be placed inan electrically conducting antistatic bag.

    There are no setting adjustments within the module and it is advised that it is notunnecessarily disassembled. Although the printed circuit boards are pluggedtogether, the connectors are a manufacturing aid and not intended for frequentdismantling; in fact considerable effort may be required to separate them. Touchingthe printed circuit board should be avoided, since complementary metal oxidesemiconductors (CMOS) are used, which can be damaged by static electricitydischarged from the body.

    Section 2. HANDLING OF ELECTRONIC EQUIPMENT

    A persons normal movements can easily generate electrostatic potentials of severalthousand volts. Discharge of these voltages into semiconductor devices whenhandling electronic circuits can cause serious damage, which often may not beimmediately apparent but the reliability of the circuit will have been reduced.

    The electronic circuits are completely safe from electrostatic discharge whenhoused in the case. Do not expose them to risk of damage by withdrawingmodules unnecessarily.

    Each module incorporates the highest practicable protection for its semiconductordevices. However, if it becomes necessary to withdraw a module, the folowingprecautions should be taken to preserve the high reliability and long life for whichthe equipment has been designed and manufactured.

    1. Before removing a module, ensure that you are at the same electrostaticpotential as the equipment by touching the case.

    2. Handle the module by its frontplate, frame or edges of the printed circuit board.Avoid touching the electronic componenets, printed circuit track or connectors.

    3. Do not pass the module to another person without first ensuring you are both atthe same electrostatic potential. Shaking hands achieves equipotential.

  • SERVICE MANUAL R8551CKCGG 122, 142 Chapter 2KCEG 112, 142, 152, 242 Page 2 of 3KCEU 142, 242

    4. Place the module on an antistatic surface, or on a conducting surface which isat the same potential as yourself.

    5. Store or transport the module in a conductive bag.

    If you are making measurements on the internal electronic circuitry of anequipment in service, it is preferable that you are earthed to the case with aconductive wrist strap. Wrist straps should have a resistance to ground between500k 10M.If a wrist strap is not available you should maintain regular contact with the case toprevent a build-up of static. Instrumentation which may be used for makingmeasurements should be earthed to the case whenever possible.

    More information on safe working procedures for all electronic equipment can befound in BS5783 and IEC 60147-OF. It is strongly recommended that detailedinvestigations on electronic circuitry or modification work should be carried out ina special handling area such as described in the above-mentioned BS and IECdocuments.

    Section 3. RELAY MOUNTING

    Relays are dispatched either individually or as part of a panel/rack assembly.If loose relays are to be assembled into a scheme, then construction details can befound in Publication R7012. If an MMLG test block is to be included it should bepositioned at the right-hand side of the assembly (viewed from the front). Modulesshould remain protected by their metal case during assembly into a panel or rack.The design of the relay is such that the fixing holes are accessible without removalof the cover. For individually mounted relays an outline diagram is normallysupplied showing the panel cut-outs and hole centres. These dimensions will alsobe found in Publication R6551.

    Section 4. UNPACKING

    Care must be taken when unpacking and installing the relays so that none of theparts is damaged or the settings altered. Relays must only be handled by skilledpersons. The installation should be clean, dry and reasonably free from dust andexcessive vibration. The site should be well lit to facilitate inspection. Relays thathave been removed from their cases should not be left in situations where they areexposed to dust or damp. This particularly applies to installations which are beingcarried out at the same time as construction work.

  • SERVICE MANUAL R8551CKCGG 122, 142 Chapter 2KCEG 112, 142, 152, 242 Page 3 of 3KCEU 142, 242

    Section 5. STORAGE

    If relays are not to be installed immediately upon receipt they should be stored in aplace free from dust and moisture in their original cartons. Where de-humidifierbags have been included in the packing they should be retained. The action of thede-humidifier crystals will be impaired if the bag has been exposed to ambientconditions and may be restored by gently heating the bag for about an hour, priorto replacing it in the carton.

    Dust which collects on a carton may, on subsequent unpacking, find its way intothe relay; in damp conditions the carton and packing may become impregnatedwith moisture and the de-humifier will lose its efficiency.

    Storage temperature 25C to +70C.

  • Types KCGG 122, 142,KCEG 112, 142, 152, 242 and

    KCEU 142, 242Overcurrent and Directional Overcurrent

    RelaysService Manual

    Chapter 3Relay Description

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 ContentsKCEU 142, 242

    1. RELAY DESCRIPTION 12. USER INTERFACE 22.1 Frontplate layout 22.2 LED indications 32.3 Keypad 32.4 Liquid crystal display 32.5 Flag display format 33. MENU SYSTEM 53.1 Default display 53.2 Accessing the menu 53.3 Menu contents 63.4 Menu columns 63.5 System data 73.6 Fault records 83.7 Measurements 1 83.8 Measurements 2 83.9 Measurements 3 93.10 Earth fault 1 93.11 Phase fault 1 103.12 Earth fault 2 113.13 Phase fault 2 123.14 Logic 133.15 Input masks 143.16 Relay masks 143.17 Recorder 154. CHANGING TEXT AND SETTINGS 174.1 Quick guide to menu controls 174.2 To enter setting mode 184.3 To escape from the setting mode 184.4 To accept the new setting 184.5 Password protection 194.6 Entering passwords 194.7 Changing passwords 194.8 Restoration of password protection 204.9 Entering text 204.10 Changing function links 204.11 Changing setting values 204.12 Setting communication address 214.13 Setting input masks 214.14 Setting output masks 214.15 Resetting values and records 214.16 Resetting trip LED indication 22

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 ContentsKCEU 142, 242

    5. EXTERNAL CONNECTIONS 225.1 Auxiliary supply 235.2 Dual powered relays 235.3 Logic control inputs 235.4 Analogue inputs 245.5 Output relays 255.6 Ouput relay minimum dwell time 255.7 Setting the relay with a PC or laptop 256. ALARM FLAGS 25

    Figure 1. Frontplate layout 2Figure 2. Flag display format 4

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 1 of 26KCEU 142, 242

    Section 1. RELAY DESCRIPTION

    The KCGG, KCEG and KCEU relays use numerical techniques to derive protectionand control functions. They can have up to eight multiplexed analogue inputs,sampled eight times per power frequency cycle. The Fourier derived powerfrequency component returns the rms value of the measured quantity. To ensureoptimum performance, frequency tracking is used. The channel that is tracked ischosen on a priority basis, Va, Vb, Vc, Ia, Ib, Ic. Frequency tracking is notemployed on the residual voltage, or current to ensure the maximum harmonicrejection. In the absence of a signal to frequency track, the sampling frequencydefaults to the rated frequency of the power system.

    Up to eight output relays can be programmed to respond to any of the protectionor control functions and up to eight logic inputs can be allocated to controlfunctions. The logic inputs are filtered to ensure that induced AC current in theexternal wiring to these inputs does not cause an incorrect response. Software linksfurther enable the user to customise the product for their own particularapplications. They select/interconnect the various protection and control elementsand replace the interconnections that were previously used between the cases ofrelays that provided discrete protection or control functions.

    The relays are powered from either a DC or an AC auxiliary supply which istransformed by a wide ranging DC/DC converter within the relay. This providesthe electronic circuits with regulated and galvanically isolated supply rails.The power supply also provides a regulated and isolated field voltage to energisethe logic inputs.

    The dual powered version of the relay draws its energising supply from the currenttransformers in the absence of an auxiliary voltage supply. This makes it suitablefor application where the auxiliary supply is not reliable or not available. They canbe used in shunt trip, capacitor discharge and AC series trip arrangements.

    An interface on the front of the relay allows the user to navigate through the menuto access data, change settings and reset flags, etc. As an alternative the relayscan be connected to a computer via their serial communication ports and the menuaccessed on-line. This provides a more friendly and intuitive method of setting therelay, as it allows a whole column of data to be displayed at one time instead ofjust a single menu cell. Computer programs are also available that enable settingfiles to be generated off-line and these files can then be downloaded to the relayvia the serial port.

    In addition to protection and control functions the relays can display all the valuesthat it measures and many additional ones that it calculates. They also store usefultime stamped data for post fault analysis in fault records, event records anddisturbance records. This data is available via a serial communication port foraccess locally and/or remotely with a computer. The fault records, event recordsand disturbance records can be extracted automatically via the serial port andvalues can be polled periodically to determine trends. Remote control actions canalso be made and to this end many K Range relays have been integrated intoSCADA systems.

    K Range relays provide the user with the flexibility to customise the relay for theirparticular applications. They provide many additional features that would beexpensive to produce on an individual basis and, when the low installation costsare taken into account, it will be seen to provide an economic solution forprotection and control.

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 2 of 26KCEU 142, 242

    Section 2. USER INTERFACE

    The front plate of the relay provides a man machine interface providing the userwith a means of entering settings to the relay displaying measured values, faultrecords and alarms. The series 2 relays have additional graphics to assist the user.The area in which the fault flags are displayed is divided up to denote the areaassociated with each phase and there is a marked position for the appropriatephase colours to be marked and for labels to be affixed to denote the use of thethree overcurrent stages and the three auxiliary timers.

    2.1 Frontplate layout

    F + 0

    Relay types

    Liquidcrystaldisplay

    LED indicators

    Ratings

    Model number

    Serial number

    Digit identifiers

    Entry keys

    Hz110/125 V

    Vn

    KCGG142 KCGG14200102125No P967701

    -

    In 1 A V110 50/60V

    STAGE 2STAGE 1

    STAGE 3

    ALARMALARM

    AUX 2AUX 3

    AUX 1

    TRIP

    * * *

    GROUP

    CAUX TIMER

    EF D

    FAULT NoSETTING

    3C

    AB 89 67 5 4

    A B

    12 0

    HEALTHY

    F n _ 2G2 A __ * B __ *B TAU X 2 C * NV , t>>, t>>>)associated with that phase (phase C in this example) and an asterisk (*) will bedisplayed for the stage or stages that have operated.

    Thus:

    C would indicate that a current above the I> setting had been detected bythe phase C element during the fault (START condition).

    C* would indicate the first overcurrent stage (t>) had operated

    C_* would indicate the second stage (t>>) had timed out

    C__* would indicate t>>> had timed out third overcurrent stage

    C*_* would indicate that both t> and t>>> had timed out

    Flag information is similarly provided for the other two phases and for earth faults.

    The six digits at the left-hand side of the display on the bottom line identify theauxiliary functions AUX1, AUX2, AUX3 as AUX123. Two printed panels below thedisplay may be used to indicate the function of each of the three auxiliary functionsand those of the three main overcurrent functions respectively. The appropriate pre-printed labels can be affixed in these two areas.

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 5 of 26KCEU 142, 242

    The two characters at the extreme right-hand end of the top line of the display willindicate V< when the undervoltage element has operated. Operation of thebreaker failure protection is indicated by the letter B and operation of the thermalelement by the letter T immediately below the V

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 6 of 26KCEU 142, 242

    should be depressed for one second. Section 4 gives instructions for changing thevarious types of settings.

    Password protection is provided for the configuration settings of the relay becausean accidental change could seriously affect the ability of the relay to perform itsintended functions. Configuration settings include the selection of time curves,function links, CT and VT ratios, opto-input and relay output allocation. Individualprotection settings are protected from change when the relay cover is in place.

    3.3 Menu contents

    Related data and settings are grouped in separate columns of the menu.Each column has a text heading (in capital letters) that identifies the data containedin that column. Each cell may contain text, values, limits and/or a function.The cells are referenced by the column number/row number. For example 0201 iscolumn 02, row 01. When a cell is displayed the four characters at the top lefthand corner of the LCD indicate the column number and row number in the menutable.

    The full menu is given in the following tables, but not all the items listed will beavailable in a particular relay. For example, a single pole earth fault relay wouldnot display any phase fault settings and a non-directional relay would not displayany settings associated with the directional feature. Those cells that do not provideany useful purpose are not made available in the factory configuration.Certain settings will disappear from the menu when the user de-selects them; thealternative setting group is a typical example. If group 2 settings have not beenenabled then the menu columns EARTH FLT 2 and PHASE FLT 2 will be hidden andmake them visible, the system data link SD4 must be set to 1. This note is includedat this time to explain why some of the items listed below may not appear in themenu for a relay that is being compared with the full list.

    3.4 Menu columns

    The menu tables shown below are for KCEG directional overcurrent and earth faultprotection relays, unless otherwise stated. The directional elements shown in themenu tables are not available in KCGG relays.Column Heading DescriptionNumber

    00 SYSTEM DATA Settings and data for the system - relay andserial communications

    01 FLT RECORDS Fault records for the last five faults

    02 MEASURE 1 Directly measured quantities (V & I etc.)

    03 MEASURE 2 Calculated quantities (W & VAR etc.)

    04 MEASURE 3 Calculated (additional)

    05 EARTH FLT 1 Earth fault protection settings group 1

    06 PHASE FLT 1 Phase fault protection settings group 1

    07 EARTH FLT 2 Earth fault protection settings group 2

    08 PHASE FLT 2 Phase fault protection settings group 2

    09 LOGIC Settings for miscellaneous functions usedin the logic

    0A INPUT MASKS User assigned allocation of logic input

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 7 of 26KCEU 142, 242

    0B RELAY MASKS User assigned allocation of output relays

    0C RECORDER Settings for the disturbance recorder

    The menu cells that are read only are marked [READ].Cells that can be set are marked [SET].Cells that can be reset are marked [RESET].Cells that are password protected are marked [PWP].

    3.5 System dataDisplay Status Description0000 SYSTEM DATA READ Column heading0002 Password PWP Password that must be entered before certain settings

    may be changed0003 SD Links PWP Function links that enable the user to enable (activate)

    the options required0 Rem ChgStg 1 = enable remote setting changes2 Rem CB Ctrl 1 = enable remote control of circuit breaker3 Rem ChgGrp 1 = enable remote change of setting group4 En Grp2 1 = enable group 2 settings to be used and

    displayed5 Auto Flag 1 = enable flags to be reset automatically on load

    restoration6 Auto Rec 1 = enable disturbance recorder to reset on load

    restoration7 Log Evts 8 1 = enable logic inputs and output relay status to be

    stored in event records8 Alt Rec Rst 1 = enable alternative reset method for disturbance

    recorder0004 Description PWP Product description user programmable text0005 Plant PWP Plant reference user programmable text0006 Model READ Model number that defines the product0008 Serial No. READ Serial number unique number identifying the

    particular product0009 Freq SET Default sampling frequency must be set to power

    system frequency (not available on KCEU relays)000A Comms Level READ Indicates the Courier communication level supported

    by the product000B Rly Address SET Communication address (1 to 255)000C Plnt Status READ Binary word used to indicate the status of circuit

    breakers and isolators000D Ctrl Status READ Binary word used to indicate the status of control data000E Grp now READ Indicates the active setting group000F LS Stage READ Indicates the last received load shedding command0010 CB Control SET Indicates the status of the circuit breaker control0011 Software READ Software reference for the product0020 Log Status READ Indicates the current status of all the logic inputs0021 Rly Status READ Indicates the current status of the output relay drives0022 Alarms READ Indicates the current state of internal alarms0 Uncfg READ Error in factory configuration settings1 Uncalib READ Operating in uncalibrated state2 Setting READ Error detected in stored settings3 No Service READ Protection out-of-service and not functioning

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 8 of 26KCEU 142, 242

    4 No Samples READ No A/D samples but still in service5 No Fourier READ Fourier is not being performed6 Test Wdog SET Test watchdog by setting this bit to 10023 FnowG1 READ Indicates the current status of the fault flags

    (These flags are not latched)

    3.6 Fault recordsDisplay Status Description0100 FLT RECORDS READ Column heading0101 Fault No 1 SET Number of fault record displayed may be selected

    (Fn; Fn -1; Fn -2; . . . Fn -5)0102 Fn G1 READ Flags (latched) indicating the functions that operated

    during the fault0103 Ia READ Highest value of current measured in phase A during

    the fault0104 Ib READ Highest value of current measured in phase B during

    the fault0105 Ic READ Highest value of current measured in phase C during

    the fault0106 Io READ Highest value of residual current measured during the

    fault0107 Vab READ Value of Vab during the fault0108 Vbc READ Value of Vbc during the fault0109 Vca READ Value of Vca during the fault010A Vo READ Highest value of residual voltage measured during

    the fault010B CB Trip Time READ Circuit breaker trip time0110 Clear = O RESET Press [0] key to clear all fault records when this cell is

    displayed

    3.7 Measurements 1Display Status Description0200 MEASURE 1 READ Column heading0201 Ia READ Measured current in phase A0202 Ib READ Measured current in phase B0203 Ic READ Measured current in phase C0204 Io READ Measured residual current0205 Vab READ Measured line voltage Vab0206 Vbc READ Measured line voltage Vbc0207 Vca READ Measured line voltage Vca0208 Va READ Measured phase voltage Va

    (not available on KCEU relays)0209 Vb READ Measured phase voltage Vb

    (not available on KCEU relays)020A Vc READ Measured phase voltage Vc

    (not available on KCEU relays)020B Vo READ Measured residual voltage Vo020C F READ Measured power system frequency F

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 9 of 26KCEU 142, 242

    3.8 Measurements 2Display Status Description0300 MEASURE 2 READ Column heading0301 3W READ Three phase active power0302 3VA READ Three phase apparent power0303 3VAr READ Three phase reactive power0304 Imax READ Highest of the three phase currents measured not a

    peak demand value0309 Wa READ Active power in phase A

    (not available on KCEU relays)030A Wb READ Active power in phase B

    (not available on KCEU relays)030B Wc READ Active power in phase C

    (not available on KCEU relays)030C PowerFactor READ Power factor three phase030D VARa READ Reactive power in phase A

    (not available on KCEU relays)030E VARb READ Reactive power in phase B

    (not available on KCEU relays)030F VARc READ Reactive power in phase C

    (not available on KCEU relays)0310 Sum (ops) PWP Number of circuit breaker operations0311 CBdutyA PWP Sum of I, or I2 broken by phase A of circuit breaker0312 CBdutyB PWP Sum of I, or I2 broken by phase B of circuit breaker0313 CBdutyC PWP Sum of I, or I2 broken by phase C of circuit breaker031E Power mode PWP Sets the convention used for signing the direction of

    measured power flow

    3.9 Measurements 3Display Status Description0400 MEASURE 3 READ Column heading0404 IthA READ Thermal ammeter reading in phase A0405 IthB READ Thermal ammeter reading in phase B0406 IthC READ Thermal ammeter reading in phase C0407 Thermal PWP Thermal state (%)040A Pk IthA PWP Peak thermal ammeter reading in phase A demand

    value040B Pk IthB PWP Peak thermal ammeter reading in phase B demand

    value040C Pk IthC PWP Peak thermal ammeter reading in phase C demand

    value

    3.10 Earth fault 1Display Status Description0500 EARTH FLT1 READ Column heading0501 EF Links PWP Software links that are used to select the available

    optional earth fault functions1 En Io>> 1 = enable earth fault stage 22 EN Io>>> 1 = enable earth fault stage 33 Drn to> 1 = directionalise earth fault stage 14 Drn to>> 1 = directionalise earth fault stage 25 Drn to>>> 1 = directionalise earth fault stage 3

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 10 of 26KCEU 142, 242

    6 Io>>NoPeak 1 = no peak measurement for stage 2 earth faults (KCGG only)

    E Rev Io>>> 1 = reverse direction of third earth fault stage (Io>>>)0502 CT Ratio PWP Overall ratio of the line or neutral CT feeding the

    earth fault protection elements0503 VT Ratio PWP Overall ratio of the voltage transformer feeding the

    relay0504 Curve PWP Selected characteristic from the definite time or 10

    inverse time options0505 Io> SET Current setting for start output and first earth fault

    stage0506 to>/TMS SET Time multiplier setting that will be used with a

    selected inverse time curve0507 to>/DT SET Time delay that will be effective when the definite time

    characteristic is selected0508 toRESET SET Hold time for which the current must remain below

    Io> before the timer resets to zero0509 Io>> SET Current setting for second earth fault stage050A to>> SET Time delay for second earth fault stage050B Io>>> SET Current setting for third earth fault stage050C to>>> SET Time delay for third earth fault stage050D Char Angle SET Characteristic angle setting for earth fault directional

    element050E Io< SET Setting for earth fault undercurrent element050F Vop> SET Setting for minimum polarising voltage below which

    the directional element is blocked0510 Po> SET Wattmetric power threshold

    (only available on KCEU relays)

    3.11 Phase fault 1Display Status Description0600 PHASE FLT 1 READ Column heading0601 PF Links PWP Software links that are used to select the available

    optional phase fault functions0 En Therm 1 = enable thermal element1 En I>> 1 = enable stage 2 overcurrent2 En I>>> 1 = enable stage 3 overcurrent3 Drn t> 1 = directionalise stage 1 overcurrent4 Drn t>> 1 = directionalise stage 2 overcurrent5 Drn t>>> 1 = directionalise stage 3 overcurrent6 I>> NoPeak 1 = No peak measurement for stage 2 overcurrent

    (KCGG only)7 I>>> = 2/3 1 = 2 out of 3 phase elements to operate for t>>>

    to give an output8 CB blk V< 1 = undervoltage blocked when circuit breaker is

    open9 V< any = 1 1 = output for any phase undervoltage;

    0 = output for all phases undervoltageA V< P-N = 1 1 = undervoltage responds to phase voltage;

    0 = undervoltage responds to line voltage (not available on KCEU relays)

    B SynPol = 3.2 1 = synchronous polarising extended to 3.2s;0 = 0.32s

    C Brkn Cond 1 = enables broken conductor logic

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 11 of 26KCEU 142, 242

    D En F< 1 = enable under frequency element to initiate tAUX1 (not available on KCEU relays)

    E Rev I>>> 1 = reverse direction of third overcurrent stageF All 2/3 1 = 2/3 logic applied to all phase outputs0602 CT Ratio PWP Overall ratio of the line CT feeding the phase fault

    protection elements0603 VT Ratio PWP Overall ratio of the voltage transformer feeding the

    relay0604 Curve PWP Selected characteristic from the definite time or 10

    inverse time options0605 I> SET Current setting for start output and first overcurrent

    stage0606 t>/TMS SET Time multiplier setting that will be used with a

    selected inverse time curve0607 t>/DT SET Time delay that will be effective when the definite time

    characteristic is selected0608 tRESET SET Hold time for which the current must remain below I>

    before the timer resets to zero0609 I>> SET Current setting for second overcurrent stage060A t>> SET Time delay for second overcurrent stage060B I>>> SET Current setting for third overcurrent stage060C t>>> SET Time delay for third overcurrent stage060D Char Angle SET Characteristic angle setting for overcurrent directional

    element060E I< SET Setting for phase fault undercurrent element060F V< SET Setting for undervoltage element0610 tV< SET Definite time delay for undervoltage feature0611 F< SET Setting for underfrequency

    (not available on KCEU relays)0612 th> Alarm SET Thermal alarm level (%)0613 Ith> Trip SET Thermal current rating (trip level = 100%)0614 TC SET Setting for thermal time constant

    3.12 Earth fault 2Display Status Description0700 EARTH FLT 2 READ Column heading0701 EF Links PWP Software links that are used to select the available

    optional earth fault functions1 En Io>> 1 = enable earth fault stage 22 En Io>>> 1 = enable earth fault stage 33 Drn to> 1 = directionalise earth fault stage 14 Drn to>> 1 = directionalsise earth fault stage 25 Drn to>>> 1 = directionalise earth fault stage 36 Io>> NoPeak 1 = no peak measurement for stage 2 earth faults

    (KCGG only)E Rev Io>>> 1 = reverse direction of third earth fault stage (Io>>>)0702 CT Ratio PWP Overall ratio of the line or neutral CT feeding the

    earth fault protection elements0703 VT Ratio PWP Overall ratio of the voltage transformer feeding the

    relay0704 Curve PWP Selected characteristic from the definite time or 10

    inverse time options0705 Io> SET Current setting for start output and first earth fault

    stage

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 12 of 26KCEU 142, 242

    0706 to>/TMS SET Time multiplier setting that will be used with aselected inverse time curve

    0707 to>/DT SET Time delay that will be effective when the definite timecharacteristic is selected

    0708 toRESET SET Hold time for which the current must remain belowIo> before the timer resets to zero

    0709 Io>> SET Current setting for second earth fault stage070A to>> SET Time delay for second earth fault stage070B Io>>> SET Current setting for third earth fault stage070C to>>> SET Time delay for third earth fault stage070D Char Angle SET Characteristic angle setting for earth fault directional

    element070E Io< SET Setting for earth fault undercurrent element070F Vop> SET Setting for minimum polarising voltage below which

    the directional element is blocked0710 Po> SET Wattmetric power threshold

    (only available on KCEU relays)

    3.13 Phase fault 2Display Status Description0800 PHASE FLT 2 READ Column heading0801 PF Links PWP Software links that are used to select the available

    optional phase fault functions0 En Therm 1 = enable thermal element1 En I>> 1 = enable stage 2 overcurrent2 En I>>> 1 = enable stage 3 overcurrent3 Drn t> 1 = directionalise stage 1 overcurrent4 Drn t>> 1 = directionalise stage 2 overcurrent5 Drn t>>> 1 = directionalise stage 3 overcurrent6 I>> NoPeak 1 = No peak measurement for stage 2 overcurrent

    (KCGG only)7 I>>> = 2/3 1 = 2 out of 3 phase elements to operate for t>>>

    to give an output8 CB blk V< 1 = undervoltage blocked when circuit breaker is

    open9 V< any = 1 1 = output for any phase undervoltage;

    0 = output for all phases undervoltageA V< P-N = 1 1 = undervoltage responds to phase voltage;

    0 = undervoltage responds to line voltageB SynPol = 3.2 1 = synchronous polarising extended to 3.2s;

    0 = 0.32sC Brkn Cond 1 = enables broken conductor logicD EN F< 1 = enable under frequency element to initiate tAUX1

    (not available on KCEU relays)E Rev I>>> 1 = reverse direction of third overcurrent stageF All 2/3 1 = 2/3 logic applied to all phase outputs0802 CT Ratio PWP Overall ratio of the line CT feeding the phase fault

    protection elements0803 VT Ratio PWP Overall ratio of the voltage transformer feeding the

    relay0804 Curve PWP Selected characteristic from the definite time or 10

    inverse time options0805 I> SET Current setting for start output and first overcurrent

    stage

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 13 of 26KCEU 142, 242

    0806 t>/TMS SET Time multiplier setting that will be used with aselected inverse time curve

    0807 t>/DT SET Time delay that will be effective when the definite timecharacteristic is selected

    0808 tRESET SET Hold time for which the current must remain below I>before the timer resets to zero

    0809 I>> SET Current setting for second overcurrent stage080A t>> SET Time delay for second overcurrent stage080B I>>> SET Current setting for third overcurrent stage080C t>>> SET Time delay for third overcurrent stage080D Char Angle SET Characteristic angle seting for overcurrent directional

    element080E I< SET Setting for phase fault undercurrent element080F V< SET Setting for undervoltage element0810 tV< SET Definite time delay for undervoltage feature0811 F< SET Setting for underfrequency

    (not available on KCEU relays)0812 th>Alarm SET Thermal alarm level (%)0813 Ith>Trip SET Thermal current rating (trip level = 100%)0814 TC SET Setting for thermal time constant

    3.14 LogicDisplay Status Description0900 LOGIC READ Column heading0901 LOG Links PWP Software links that are used to select the available

    optional logic functions0 CB Rec 1 = enable CB operations and contact duty registers

    to be incremented1 CB1*I = 0 1 = CB contact proportional to I;

    0 = CB contact duty proportional to I2

    2 BF blk strt 1 = enables the start outputs to be reset when breaker failure protection operates

    3 tAUX2 = I< 1 = tAUX2 initiated by undercurrent in all three phases

    4 tAUX2=/Io< 1 = tAUX2 initiated when the earth fault current exceeds the Io< setting

    5 tAUX3 Grp2 1 = tAUX3 selects setting grp26 tAUX2-tAUX3 1 = enables the pick up of tAUX3 to be delayed by

    tAUX27 Latch Strt 1 = start latches fault flags and generate fault record8 Hold Grp2 1 = selects and holds the grp2 settings operational9 Rst CBclose 1 = enables a circuit breaker trip to reset the close

    pulse timerA Log Rly7 1 = enable relay 7 to initiate fault recordsB tAUX3=DDO 1 = tAUX3 is delayed on drop-off

    0 = tAUX3 is delayed on pick-up0902 tBF SET Breaker failure protection time delay setting0903 tAUX1 SET Auxiliary timer 1 setting0904 tAUX2 SET Auxiliary timer 2 setting0905 tAUX3 SET Auxiliary timer 3 setting0906 tTRIP SET Trip pulse time setting0907 tCLOSE SET Close pulse time setting0908 CB ops> SET Alarm 1 setting for excessive circuit breaker operations

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 14 of 26KCEU 142, 242

    0909 CB duty> SET Alarm 1 setting for excessive circuit breaker contactduty

    090F Display SET Default display that is selected on power-up0 Manufact Manufacturers name1 Descript Description of product2 Plant Plant reference3 Thermal Thermal State (%)4 IthA B C Thermal ammeter readings for each of the three

    phases5 Ia Ib Ic Instantaneous reading of phase currents (prospective

    value of thermal ammeter)6 Ia Io Vab Vo Line current and voltage plus residual current and

    voltage7 kW kVAr Active and reactive three phase power

    3.15 Input masksDisplay Status Description0A00 INPUT MASKS READ Column heading0A01 Blk to> PWP Logic input to block first stage earth fault timer to>0A02 Blk to>> PWP Logic input to block second stage earth fault timer

    to>>0A03 Blk to>>> PWP Logic input to block third stage earth fault timer

    to>>>0A04 Blk t> PWP Logic input to block first stage overcurrent timer t>0A05 Blk t>> PWP Logic input to block second stage overcurrent timer

    t>>0A06 Blk t>>> PWP Logic input to block third stage overcurrent timer

    t>>>0A07 L Trip PWP Logic input to initiate trip pulse timer from external

    input0A08 L Close PWP Logic input to initiate close pulse timer from external

    input0A09 Ext Trip PWP Logic input to initiate breaker fail and records from

    an external trip signal0A0A Aux 1 PWP Logic input to initiate timer tAUX1 from external input0A0B Aux 2 PWP Logic input to initiate timer tAUX2 from external input0A0C Aux 3 PWP Logic input to initiate timer tAUX3 from external input0A0D Set Grp 2 PWP Logic input to select group 2 protection settings from

    external input0A0E CB Closed PWP Logic input to indicate circuit breaker in closed

    position0A0F CB Open PWP Logic input to indicate circuit breaker in open position0A10 Bus2 PWP Logic input to indicate circuit breaker in bus 2

    position0A11 Reset Ith PWP Logic input to block/reset thermal protection,

    also resets thermal ammeters

    3.16 Relay masksDisplay Status Description0B00 RELAY MASKS READ Column heading0B01 Io> Fwd PWP Earth fault forward start (non directional start for non

    directional relays)0B02 Io> Rev PWP Earth fault reverse start (only available when

    directionalised)

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 15 of 26KCEU 142, 242

    0B03 to> PWP First stage time delayed earth fault output0B04 to>> PWP Second stage time delayed earth fault output0B05 to>>> PWP Third stage time delayed earth fault output0B06 I> Fwd PWP Overcurrent forward start (non directional start for non

    directional relays)0B07 I> Rev PWP Overcurrent reverse start (only available when

    directionalised)0B08 tA> PWP First stage time delayed overcurrent output for

    phase A0B09 tB> PWP First stage time delayed overcurrent output for

    phase B0B0A tC> PWP First stage time delayed overcurrent output for

    phase C0B0B t>> PWP Second stage time delayed overcurrent output0B0C t>>> PWP Third stage time delayed overcurrent output0B0D CB Trip PWP Trip pulse output0B0E CB Close PWP Close pulse output0B0F CB Fail PWP Breaker fail output for initiation of back tripping0B10 Aux 1 PWP Output from the auxiliary 1 time delayed function0B11 Aux2 PWP Output from the auxiliary 2 time delayed function0B12 Aux3 PWP Output from the auxiliary 3 time delayed function0B13 tV< PWP Undervoltage time delayed output0B14 Level 1 PWP Output in response to command to load shed to

    level 1 (not available on KCEU relays)0B15 Level 2 PWP Output in response to command to load shed to

    level 2 (not available on KCEU relays)0B16 Level 3 PWP Output in response to command to load shed to

    level 3 (not available on KCEU relays)0B17 thAlarm PWP Thermal overload alarm0B18 thTrip PWP Thermal overload trip0B19 CB Alarm PWP Alarm for circuit breaker maintenance

    3.17 RecorderDisplay Status Description0C00 RECORDER READ Column heading0C01 Control SET Manual stop/start control (running = started;

    triggered = stopped)0C02 Capture SET Select the functions to be captured: magnitudes/

    phase angles/samples0C03 Post trigger SET Select the number of samples recorded after the

    trigger (1 to 511)0C04 Logic trig SET Select the logic input to trigger the recorder

    (0 to 7 pick-up or drop-off)0 +Opto0 Trigger in response to energisation of logic input L01 +Opto1 Trigger in response to energisation of logic input L12 +Opto2 Trigger in response to energisation of logic input L23 +Opto3 Trigger in response to energisation of logic input L34 +Opto4 Trigger in response to energisation of logic input L45 +Opto5 Trigger in response to energisation of logic input L56 +Opto6 Trigger in response to energisation of logic input L67 +Opto7 Trigger in response to energisation of logic input L78 Opto0 Trigger in response to de-energisation of logic

    input L0

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 16 of 26KCEU 142, 242

    9 Opto1 Trigger in response to de-energisation of logicinput L1

    A Opto2 Trigger in response to de-energisation of logicinput L2

    B Opto3 Trigger in response to de-energisation of logicinput L3

    C Opto4 Trigger in response to de-energisation of logicinput L4

    D Opto5 Trigger in response to de-energisation of logicinput L5

    E Opto6 Trigger in response to de-energisation of logicinput L6

    F Opto7 Trigger in response to de-energisation of logicinput L7

    0C05 Relay Trig SET Select the output relay tio trigger the recorder(0 to 7 pick-up or drop-off)

    0 +Rly 0 Trigger in response to energisation of output relayRLY 0

    1 +Rly 1 Trigger in response to energisation of output relayRLY 1

    2 +Rly 2 Trigger in response to energisation of output relayRLY 2

    3 +Rly 3 Trigger in response to energisation of output relayRLY 3

    4 +Rly 4 Trigger in response to energisation of output relayRLY 4

    5 +Rly 5 Trigger in response to energisation of output relayRLY 5

    6 +Rly 6 Trigger in response to energisation of output relayRLY 6

    7 +Rly 7 Trigger in response to energisation of output relayRLY 7

    8 Rly 0 Trigger in response to de-energisation of output relayRLY 0

    9 Rly 1 Trigger in response to de-energisation of output relayRLY 1

    A Rly 2 Trigger in response to de-energisation of output relayRLY 2

    B Rly 3 Trigger in response to de-energisation of output relayRLY 3

    C Rly 4 Trigger in response to de-energisation of output relayRLY 4

    D Rly 5 Trigger in response to de-energisation of output relayRLY 5

    E Rly 6 Trigger in response to de-energisation of output relayRLY 6

    F Rly 7 Trigger in response to de-energisation of output relayRLY 7

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 17 of 26KCEU 142, 242

    Section 4. CHANGING TEXT AND SETTINGS

    Settings and text in certain cells of the menu can be changed via the userinterface. To do this the cover must be removed from the front of the relay so thatthe [+] and [] keys can be accessed.

    4.1 Quick guide to menu controls

    Quick guide to menu control with the four keys

    Current display Key press Effect of action

    Default display [0] long Back-light turns ON no other effect

    [0] short Steps through the available default displays

    [F] steps down to column heading SYSTEMDATA

    [+] Back-light turns ON no other effect

    [] Back-light turns ON no other effect

    Fault flags after a trip [0] short Back-light turns ON no other effect

    [F] steps down to column heading SYSTEMDATA without resetting the fault flags

    [0] long resets trip LED and returns default display

    [+] Back-light turns ON no other effect

    [] Back-light turns ON no other effect

    Column heading [0] short Back-light turns ON no other effect

    [0] long Re-establishes password protectionimmediately and returns the default display

    [F] long move to next column heading

    [F] short steps down the menu to the next item inthe column

    [] move to next column heading

    [+] move to previous column heading

    Any menu cell [F] short steps down the menu to the next item inthe column

    [F] long displays the heading for the next column

    [F] + [0] steps back up the menu to the previousitem

    [0] short Back-light turns ON no other effect

    [0] long Resets the value if the cell is resettable

    Any settable cell [+] or [] Puts the relay in setting mode. The passwordmust first be entered for protected cells

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 18 of 26KCEU 142, 242

    Current display Key press Effect of action

    Setting mode [0] Escapes from the setting mode without asetting change

    [+] Increments value with increasing rapidity ifheld

    [] Decrements value with increasing rapidityif held

    [F] Changes to the confirmation display

    [F] If function links, relay or input masks aredisplayed the [F] key will step through themfrom left to right and finally changing to theconfirmation display

    Confirmation mode [+] Confirms setting and enters new setting ortext

    [] Returns prospective change to check/modify

    [0] Escapes from the setting mode without asetting change

    The actions shown in the shaded area can only be performed when the cover isremoved.

    [F] long means press F key and hold for longer than 1s

    [F] short means press F key and hold for less than 1s

    [F] means press the F key length of time does not change the response

    4.2 To enter setting mode

    Give the [F] key a momentary press to change from the selected default displayand switch on the back-light; the heading SYSTEM DATA will be displayed.Use the [+] and [] keys, or a long press of the [F] key, to select the columncontaining the setting, or text that is to be changed. Then with the [F] key stepdown the column until the contents of that cell are displayed. Press the [+] key toput the relay into the setting mode. Setting mode will be indicated by a flashingcursor on the bottom line of the display. If the cell is read-only, or passwordprotected, then the cursor will not appear and the relay will not be in the settingmode.

    4.3 To escape from the setting mode

    IMPORTANT! If at any time you wish to escape from the setting mode withoutmaking a change to the contents of the selected cell: Hold the [0] key depressedfor 1s, the original setting will be returned and the relay will exit the setting mode.

    4.4 To accept the new setting

    Press the [F] key until the confirmation display appears:

    Are you sure?

    + = YES = NO

    Press the [0] key if you decide not to make any change.

    Press the [] key if you want to further modify the data before entry.

    Press the [+] key to accept the change. This will terminate the setting mode.

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 19 of 26KCEU 142, 242

    4.5 Password protection

    Password protection is provided for the configuration settings of the relay.This includes time curve selection, CT and VT ratios, function links, input masks andrelay masks. Any accidental change to configuration could seriously affect theability of the relay to perform its intended functions, whereas, a setting error mayonly cause a grading problem. Individual settings are protected from change whenthe relay cover is in place by preventing direct access to the [+] and [] keys.

    The password consists of four characters that may contain any upper case letterfrom the alphabet. The password is initially set in the factory to AAAA, but it canbe changed by the user to another combination if necessary. If the password is lostor forgotten, access to the relay will be denied. However, if the manufacturer ortheir agent is supplied with the serial number of the relay, a back-up password canbe supplied that is unique to that particular product.

    4.6 Entering passwords

    Using the [F] key, select the password cell [0002] in the SYSTEM DATA column ofthe menu. The word Password is displayed and four stars. Press the [+] key andthe cursor will appear under the left hand star. Now use the [+] key to step throughthe alphabet until the required letter is displayed. The display will increment fasterif the key is held down and the [] key can be used in a similar way to movebackwards through the alphabet. When the desired character has been set the [F]key can be given a momentary press to move the cursor to the position for the nextcharacter. The process is then repeated to enter the remaining characters thatmake up the password. When the fourth character is acknowledged by amomentary press of the [F] key the display will read:

    Are you sure?

    + = YES = NO

    Press the [0] key if you decide not to enter the password.

    Press the [] key if you want to modify the entry.

    Press the [+] to enter the password. The display will then show four stars and if thepassword was accepted the alarm LED will flash. If the alarm LED is not flashingthe password was not accepted a further attempt can be made to enter it, or the[F] key pressed to move to the next cell.

    Note: When the password cell is displayed, do not press the [+] or [] key whilstthe alarm LED is flashing unless you want to change the password!

    4.7 Changing passwords

    When the password has been entered and the alarm LED is flashing the [+] key ispressed to put the relay in setting mode. A new password can now be entered asdescribed in Section 4.6. After entering the fourth character make a note of thenew password shown on the display before pressing the [F] key to obtain theconfirmation display.

    Are you sure?

    + = YES = NO

    Press the [0] key if you decide not to enter the new password.

    Press the [] key if you want to modify your entry.

    Press the [+] to enter the new password which will then replace the old one.

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 20 of 26KCEU 142, 242

    Note: Make sure the new password has been written down before it is enteredand that the password being entered agrees with the written copy beforeaccepting it. If the new password is not entered correctly you may bedenied access in the future. If the password is lost a back-up passwordunique to that relay can be provided from the factory, or certain agents, ifthe serial number of the product is quoted.

    4.8 Restoration of password protection

    Password protection is reinstated when the alarm LED stops flashing. This will occurfifteen minutes after the last key press. To restore the password protection withoutwaiting for the fifteen minute time-out, select the password cell or any columnheading and hold the reset key [0] depressed for 1s. The alarm LED will cease toflash to indicate the password protection is restored.

    4.9 Entering text

    Enter the setting mode as described in Section 4.2 and move the cursor with the [F]key to where the text is to be entered or changed. Then using the [+] and [] keys,select the character to be displayed. The [F] key may then be used to move thecursor to the position of the next character and so on. Follow the instructions inSection 4.4 to exit from the setting change.

    4.10 Changing function links

    Select the column heading required and step down to the function links SD Links,EF Links, PF Links, or LOG Links and press either the [+] or [] to put therelay in a setting change mode. A cursor will flash on the bottom line at theextreme left position. This is link F; as indicated by the character printed on thefrontplate under the display.

    Press the [F] key to step along the row of links, one link at a time, until some textappears on the top line that describes the function of a link. The [+] key willchange the link to a 1 to select the function and the [] key will change it to a0 to deselect it. Follow the instructions in Section 4.4 to accept the settingchange.

    Not all links can be set, some being factory selected and locked. The links that arelocked in this way are usually those for functions that are not supported by aparticular relay, when they will be set to 0. Merely moving the cursor past a linkposition does not change it in any way.

    4.11 Changing setting values

    Move through the menu until the cell that is to be edited is displayed. Press the [+]or [] key to put the relay into the setting change mode. A cursor will flash in theextreme left hand position on the bottom line of the display to indicate that therelay is ready to have the setting changed. The value will be incremented in singlesteps by each momentary press of the [+] key, or if the [+] key is held down thevalue will be incremented with increasing rapidity until the key is released.Similarly the [] key can be used to decrement the value. Follow the instructions inSection 4.4 to exit from the setting change.

    Note: When entering CT RATIO or VT RATIO the overall ratio should be entered,ie. 2000/5A CT has an overall ratio of 400:1. With rated current appliedthe relay will display 5A when CT RATIO has the default value of 1:1 andwhen the ratio is set to 400:1 the displayed value will be 400 x 5 =2000A.

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 21 of 26KCEU 142, 242

    4.12 Setting communication address

    The communication address will be set to 255, the global address to all relays onthe network, when the relay is first supplied. Reply messages are not issued fromany relay for a global command, because they would all respond at the same timeand result in contention on the bus. Setting the address to 255 will ensure thatwhen first connected to the network they will not interfere with communications onexisting installations. The communication address can be manually set by selectingthe appropriate cell for the SYSTEM DATA column, entering the setting mode asdescribed in Section 4.2 and then decrementing or incrementing the address.Then exit setting mode as described in Section 4.4.

    To automatically allocate an address to the relay, see Chapter 6.

    4.13 Setting input masks

    An eight bit mask is allocated to each protection and control function that can beinfluenced by an external input applied to one or more of the logic inputs.When the menu cell for an input mask is selected the top line of the display showstext describing the function to be controlled by the inputs selected in the mask.A series of 1s and 0s on the bottom line of the display indicates which logicinputs are selected to exert control. The numbers printed on the frontplate under thedisplay indicate each of the logic inputs (L7 to L0) being displayed.A 1 indicates that a particular input is assigned to the displayed control functionand a 0 indicates that it is not. The same input may be used to control more thanone function.

    4.14 Setting output masks

    An eight bit mask is allocated to each protection and control function. When amask is selected the text on the top line of the display indicates the associatedfunction and the bottom line of the display shows a series of 1s and 0s for theselected mask. The numbers printed on the frontplate under the display indicate theoutput relay (RLY7 to RLY0) to which each bit is associated. A 1 indicates that therelay will respond to the displayed function and a 0 indicates that it will not.

    A logical OR function is performed on the relay masks so that more than onerelay may be allocated to more than one function. An output mask may be set tooperate the same relay as another mask so that, for example, one output relaymay be arranged to operate for all the functions required to trip the circuit breakerand another for only those functions that are to initiate autoreclose.

    4.15 Resetting values and records

    Some values and records can be reset to zero, or some predefined value.To achieve this the menu cell must be displayed and then the [0] key helddepressed for at least one second to effect the reset. The fault records are slightlydifferent because they are a group of settings and to reset these the last cell underFLT RECORDS must be selected. This will display:

    Clear = [0]

    To reset ALL FIVE fault records hold the [0] key depressed for more than 1s. If therecords are not cleared the oldest record will be overwritten by the next fault.

  • SERVICE MANUAL R8551DKCGG 122, 142 Chapter 3KCEG 112, 142, 152, 242 Page 22 of 26KCEU 142, 242

    4.16 Resetting trip LED indication

    The trip LED can be reset when the flags for the last fault are displayed. They aredisplayed automatically after a trip occurs, or can be selected in the fault recordcolumn. The reset is effected by depressing the [0] key for 1s. Resetting the faultrecords as described in 4.15 will also reset the trip LED indication.

    Set function link SD5 to 1 for the trip LED to automatically reset. This will thenoccur when the circ