DIVAC Vacuum Circuit Breaker
DIVAC® is a three-pole circuit breaker that uses vacuum interrupting technology. The Divac vacuum circuit breakers are suitable as Withdrawable units for air-insulated Metalclad switchgear, as well as “open air” or “doghouse” confi gurations.
Due to their vacuum switching capability and simple, robust construction, Divac circuit breakers are highly reliable and have a long life expectancy.
The Divac series uses a stored energy spring operating mechanism. The basic version is fi tted with a manual spring charging device or with an optional charging motor, making the breaker suitable for auto-reclosing and multi-shot auto-reclosing fast cycles.
Trip-free feature
The Divac operating mechanism will always initiate an opening command prior to a closing one (trip-free feature). If an open command is initiated during the closing process, latch #2 will be opened (using the contact pressure stored, energy free), which will, in turn, open the breaker.
General Characteristics
Safe and reliable
Compact design
Excellent dielectric and arc extinguishing properties
Complete and self-extinguishing properties
Easy installation
User-friendly operation
Extended electrical and mechanical life
Maintenance-free
Optional equipment is available
Construction Philosophy
Sheet steel base frame that supports the poles and houses the operating mechanism
Circuit breaker made up of three cylindrical poles
All circuit breaker live parts are housed inside an epoxy resin en-velope, which eliminates ground arc fault possibility
Applications
The Divac circuit breaker product line can be used for:
Open space substations
Assembly in compartment cubicles
Assembly in Metalclad cubicles
Retrofi tting breakers
Product Sheet
Technical Specifi cations
© 0
1/20
12 E
face
c AC
S, In
c. D
ue t
o ou
r po
licy
of c
onti
nuou
s de
velo
pmen
t, s
peci
fi cai
tons
may
cha
nge
wit
hout
not
ice.
Not
val
id a
s a
cont
ract
ual i
tem
.
Available Ratings
15kV
25kA 1200A / 2000A / 3000A
40kA 1200A / 2000A / 3000A
Technical Data
Making current (kA peak) 2.5 times breaking current for all the range
Short withstand current Equal to the breaking current held for 1 or 3 seconds
Operating cycles O - 3min - CO - 3min - CO/O - 0.3s - CO - 15s - CO - (15s - CO)
Spring charging time <15s
Applicable standards IEEE C .37, .04, .06, .09
Composition
1 - Upper connector 4 - Spring charging level
2 - Vacuum interrupter pole 5 - Operating mechanism
3 - Lower connector