DOE Transmission Reliability ProgramPeer Review

 

                                        

WAMS Outreach Project: Sharing of Knowledge &

Technology

John F. Hauer

Pacific Northwest National Laboratory

Richland, WA 99352

Prepared for the Transmission Reliability Program – 2004 Program Peer Review, January 27-29, 2004, Washington, D.C.

Page 2: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 2

Project: WAMS Outreach for Sharing of Knowledge & Technology

Objectives:

1. Expand the geographic reach of advanced wide area measurement systems (WAMS) to all regions of the North American interconnected grid.

2. Facilitate extraction & use of WAMS information for management of power system reliability & performance.

3. Facilitate development of technology, operational practices, and overall information infrastructure required by the objectives above.

Page 3: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 3

Deliverables: (established prior to August 14 Blackout)

1. Assistance in WAMS startup operations(technical advice, DOE/WAMS software, workshops)

2. Application of WAMS technologies (system tests, disturbance analysis, methods development for grid reliability management)

3. Validation of system dynamic performance(assessment of system behavior, comparisons against model results)

4. PMU evaluation & standards(Applications, functional requirements, laboratory tests, field evaluation, dialog with developers of technology & standards)

Project: WAMS Outreach for Sharing of Knowledge & Technology

Page 4: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 4

Progress in FY03:

1. Extensive support to WECC technical groups in WAMS deployment, system tests, disturbance analysis, and model validation.

2. Several training workshops within the WECC and the eastern interconnection.

3. Extensive advice to developers and vendors of WAMS technology (see activity report for PMU testing).

4. Assistance in data management & analysis for the U.S.-Canada Blackout of August 14, 2003.

5. These contributions are reflected in about 40 working documents, including confidential reports and two IEEE publications on the August 14 Blackout.

Project: WAMS Outreach for Sharing of Knowledge & Technology

Page 5: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 5

WSCC Monitor Facilities - 2003

Phasor measurement facilities: 8 PDCs (2 linked together) 40 integrated PMUs 7 stand-alone PMUs

~500 primary signals ~3.4 Mbytes per minute PPSM units: ~20 units ~560 primary signals ~2.8 Mbytes per minute

Other monitors: ~10 units ~80 primary signals

Page 6: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 6

view(0,20)

view(-20,20)

Keeler-Alston tripKeeler-Alston trip

oscillation activityoscillation activity

breakup breakup oscillationsoscillations

ambient activityambient activity

Waterfall Display of Dynamic Activity Just Before WSCC Breakup on August 10, 1996

Page 7: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 7

AEP & Ameren PMUs on August 14, 2003

Rush Island

Callaway

Jackson's Ferry

Kanawha River

Primary disturbance area

Page 8: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 8

AEP Kanawha River bus frequency for Aug14 Blackout12:00-16:10 EDT

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0

5000

10000

15000

0

0.01

0.02

Time in Seconds since 14-Aug-2003 12:00 EDT

Frequency in Hertz

KNRV Kanawha River Bus KV1 FreqLLcaseID=AEPpmu030814_krNBP1 casetime=09/22/03_14:36:45

Sca

lar

Aut

ospe

ctru

m:

WF

mod

e 3

view(10,70)

Page 9: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 9

Measurements Backbone for WAMS East on August 14, 2003 [1]

American Electric Power (AEP)2 PMUs (Macrodyne 1690G), at 12 spsContinuous recording to corporate serversoftware PDC based upon BPA/PNNL DSI tool box

Ameren2 PMUs (ABB RES521), at 60 spsContinuous recording to central PDCBPA PDC [2]

Entergy3 PPSMs (BPA/PNNL), at 20 spsContinuous local recordingperiodically downloaded to central locations

[1] Performance of 'WAMS East' in Providing Dynamic Information for the North East Blackout of August 14, 2003 , J. F. Hauer, Navin Bhatt, Kirit Shah, and Sharma Kolluri. IEEE/PES Panel on Major Grid Blackouts of 2003 in North America and Europe, IEEE PES General Meeting, Denver, CO, June 6-12, 2004.

[2] Summary Description of the BPA Phasor Data Concentrator (PDC), K. E. Martin,. Internal Report of the Bonneville Power Administration, December 2003. Available: ftp.bpa.gov/outgoing/WAMS%20Information/

Page 10: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 10

Measured vs. state estimator value of Kanawha River bus angle for U.S.-Canada Blackout on August 14, 2003

0 0.5 1 1.5 2 2.5 3 3.5 46

8

10

12

14

16

18

20

P 3: KNRV Kanawha River Bus KV1 VAngRLcaseID=Blackout030814_AEP5hrAdj casetime=01/06/04_09:23:55

Time in Hours since 14-Aug-2003 13:00 EDT

Measured value

AEP state estimator

angle relative to Jackson's Ferry bus

Data provided by Azra Hasanovic, AEP

Page 11: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 11

Evaluation of Phasor

Technology

Page 12: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 12

Inconsistent Signals for NW Generation Trip Event on April 18, 2002 (initial offsets removed)

NWgentrips020418_BPAS&DIT2_Malin MW Swings NWgentrips020418_BPAS&DIT2_Malin 08/26/02_10:40:24

Malin-Round Mountain #1 MW (enhanced analog transducer)

PG&E Captain Jack MW (standard analog transducer) PG&E Malin Interchange/2 MW (standard analog transducer)

237 238 239 240 241 242 - 600

- 400

- 200

0

200

Time in Seconds

standard analog transducers

enhanced analog transducers and PMU

Malin-Round Mountain #1 MW (PMU)

Malin-Round Mountain #2 MW (enhanced analog transducer)

Page 13: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 13

0

100

200

300

400

500

600 58.5

59

59.5

60

60.5

61

61.5 Pinnacle Pk Bus FreqL

caseID=Aug10PMUs_APS_PPKrecs casetime=12/07/01_08:13:54

Time in Seconds

Recording time span = 15:47:33.670 - 15:57:47.503

PMU data from Doug Selin, Arizona Public Service Co.

Challenge: Good measurements during protracted off-nominal frequencyWestern System Breakup on August 10, 1996

Page 14: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 14

Bus Frequencies Observed in New York Area for Aug14 Blackout

30 40 50 60 70 80 90 58

59

60

61

62

63

64

Data provided by BruceFardanesh, NYPA

Time in Seconds since 14-Aug-2003 16:10 EDT

Challenge: Good measurements during protracted off-nominal frequencyU.S.-Canada Blackout on August 14, 2003

Page 15: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 15

3 voltage

3 current

Three Phase

Signal Generator

Stored Test Signals

For Playback

Manual Controls

Matlab Signal

Generation

Tools

Phasor Data

Concentrator

(PDC)

Data Handler

#1

Data Handler

#2

PMU 1* Communication Link #1

Communication Link #2

PMU 2

PMU Network

Response Data

Real TimeStreamReader

Matlab Analysis

Tools

PhasorFile

Utility

Timing reference

*Preferably a reference unit with well known characteristics

Geometry and Nomenclature for Laboratory Testing of Synchronized Phasor Networks

Page 16: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Laboratory Tests of

PMU Performance

(RESERVE SLIDES FOR TECHNICAL QUESTIONS)

Page 17: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 17

Desired Characteristics for Next Generation Transducers

• High resolution & bandwidth, in control applications

• Rigorous protection against out-of-band input signals

• Absence of processing artifacts, such as spurious outputs

• Assured high accuracy, in metering applications

• Programmable outputs, for versatility of application

• Good networking options, both local and dial-in

• Option for synchronizing measurements against a precise external reference

• Overall affordability, considering all cost elements

Page 18: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 18

Fscan000480A0309042035Fscan000480A0309042035 10/21/03_16:39:57

PMU1 Voltage1 FreqL

PMU2 Voltage1 FreqL

PMU3 Voltage1 FreqL

PMU4 Voltage1 FreqL

Input Freq timed to PMU4

43.5 44 44.5 4559.5

60

60.5

61

61.5

62

62.5

Time in Seconds

1 sample time4

Measured Step Response of Four PMUs(Playback test file Fscan000480A)

Page 19: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 19

Measured Filter Performance of Four PMUs(Playback test file Fscan000480A)

Fscan000480A0309042035Dec30Fscan000480A0309042035Dec30 10/21/03_16:39:57

PMU1 Voltage1 VMag

PMU2 Voltage1 VMag

PMU3 Voltage1 VMag

PMU4 Voltage1 VMag

0 50 100 150 200 250 300 350 400 450 5000

20

40

60

80

100

Input Freq timed to PMU4

Page 20: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 20

TEST FILE: PMU_Mod6006MseriesB

Modulation frequencies are

[0 0.28 1.4 6.64 12.0 15.0 21.72 28.7 30.0 30.85 36.89 45.0] Hz

Dwell is adjusted to yield sufficient response data for each modulation frequency.

Note conspicuous aliasing near 30 Hz for PMU_Box4X30 (classical 4-cycle average). Exact frequencies and distortion components (if any) can be closely determined with Prony analysis.

TEST ISSUES:

a. Aliasing effects

b. Modulation harmonics

c. Noise levels

TEST: Modulation of Balanced 60.06 Hz carrier

Page 21: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 21

Frequency Aliasing in Four PMUs (Playback file Mod6006MseriesB)

Mod6006MseriesB0309042210Mod6006MseriesB0309042210 09/04/03_15:45:29

60

80

100

60

80

100

60

80

100

26 28 30 32 34 36 38 4060

80

100

Time in Seconds

0 0.28 1.4 6.64 12 15 21.72 28.72 30.85 36.89 4530

input modulation frequency (Hz)

0 0.28 1.4 6.64 12 15 8.28 1.28 0.85 6.89 150

PMU output frequency (Hz)

PMU1 Voltage1 VMag

PMU2 Voltage1 VMag

PMU3 Voltage1 VMag

PMU4 Voltage1 VMag

42

Nyquist Frequency=15 Hz

Page 22: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 22

Relative Timing among Four PMUs (Playback file Mod6006MseriesB)

Sorted PRS Table for pole1: TRange=[7.2667 8.0]+24.8 seconds

Signal Freq in Hz Damp Ratio (pu) Res Mag Res Angle Rel delay (msec)

PMU1 Voltage1 VMag 6.64008767 0.00000005 10.10802100 -61.71652844 8.8

PMU2 Voltage1 VMag 6.64008767 0.00000005 10.11855742 9.44705084 -21.0

PMU3 Voltage1 VMag 6.64008767 0.00000005 7.20636136 -122.54655281 34.2

PMU4 Voltage1 VMag 6.64008767 0.00000005 8.29063475 -40.72127727 0.0

Scaled Compass Plot for mode 6.64008767 Hz

-5 0 5-5

-4

-3

-2

-1

0

1

2

3

4

5

PMU1 Voltage1 VMagPMU2 Voltage1 VMagPMU3 Voltage1 VMagPMU4 Voltage1 VMag

Page 23: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 23

DSItools Simulation, model PMU_Box1X60 Test file PMU_HarmTest5892B

0 2 4 6 8 10 12 14

1.48

1.49

1.50

1.51

1.52Magnitude of Voltage Phasor

Time in Seconds

H1=58.92 Hz, wt=1.0

H2=2*H1 Hz, wt=0.02

H3=3*H2 Hz, wt=0.05

H1 H1+H2H2 H3

H1+H2+H3

H1+H3

Page 24: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Evaluating Phasor

Network Performance

Under Field Conditions

(RESERVE SLIDES FOR TECHNICAL QUESTIONS)

Page 25: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 25

Bus Angles from BPA State Estimator Compared Against PMU Measurements in BPA SCADA System

Table provided by J. J. Graffy, BPA

Page 26: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 26

OBSERVATIONS

• Coverage of state estimator & SCADA extend across more than 1000 miles, but bus angles are consistent within a few degrees.

• State estimators provide a useful means for checking a new PMU installation for local wiring errors, or for wiring changes that may be needed due to remote transpositions of transmission line conductors.

• Even a mature state estimator can gain value by the use of PMU data as an independent means to detect incorrect status information or processing errors.

• Direct incorporation of phase angle data into state estimator calculations seems especially promising for state estimators that draw upon sparse measurements, or that operate in very demanding information environments.

Bus Angles from BPA State Estimator Compared Against PMU Measurements in BPA SCADA System

Page 27: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 27

Modeshape Analysis to Determine Key Generators for Modeling & Control

-6 -4 -2 0 2 4 6

-6

-4

-2

0

2

4

6x 10

-3

Colstrip

Ingledow

Williston

BCH timestamp advanced 0.9 second

-6 -4 -2 0 2 4 6

-6

-4

-2

0

2

4

6x 10

-3

Scaled Compass Plot for mode 0.58377922 Hz

Colstrip

Ingledow

Williston

BCH timestamp advanced 0.9 second

Page 28: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 28

031203BCHfaultTests_BPA&BCH Swings Normalized031203BCHfaultTests_BPA&BCH 12/12/03_10:25:33

ING1 5L52 ING Voltage (pref ) VMag

ING2 5L52 ING Voltage (ABB) VMag

SEL1 5L91 SEL Voltage (pref ) VMag

MPLV Maple Valley Bus Voltage VMag

89 89.5 90 90.5 91 91.5 92

-1

-0.8

-0.6

-0.4

-0.2

0

0.2

Old software

(signals offset for clarity)

031203BCHfaultTests_BPA&BCH Swings Normalized031203BCHfaultTests_BPA&BCH 12/12/03_10:25:33

ING1 5L52 Voltage (PMU typeA, new software)

ING2 5L52 Voltage (PMU typeB)

SEL1 5L91 Voltage (PMU typeA, old software)

MPLV Maple Voltage (PMU typeC)

89 89.5 90 90.5 91 91.5 92

-1

-0.8

-0.6

-0.4

-0.2

0

0.2

Time in Seconds since 03-Dec- 2003 21:50:00.000Time in Seconds since 03-Dec- 2003 21:50:00.000

Old software

(signals offset for clarity)

Relative timing of VMag signals: BCH vs. BPABCH fault test on December 3, 2003

Page 29: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 29

Relative timing of PMU Frequency SignalsWECC system event on October 9, 2003

031009NWosc_TimingA

ING1 5L52 (PMU typeA) Instrument Freq

362 364 366 36859.99

60.00

60.01

Time in Seconds since 09-Oct-2003 19:20:00.000

ING1 5L52 (PMU typeA) Estimated Freq

Page 30: DOE Transmission Reliability Program Peer Review WAMS Outreach Project: Sharing of Knowledge & Technology John F. Hauer Pacific Northwest National Laboratory

Page 30

031009NWosc_BCH

526

528

530

532

534

0 50 100 150 200 250 300524

526

528

530

532

Time in Seconds since 09-Oct-2003 19:50:00.000

Parasitic Voltage Oscillations in ING1 PMUAWECC system event on October 9, 2003

ING1 5L52 Voltage (PMUA) VMag

ING2 5L52 Voltage (PMUB) VMag

Data from Harry Lee, BCH