![Page 1: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/1.jpg)
PX 1
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
Size A B F G H I J K L Wgt (lb) Airflow ERV Airflow CWC
PX 05 32.4 32.5 12.0 18.0 36.2 6.1 22.8 7.2 91.9 768-851 1300 cfm 920 cfm*
GOLD PX, plate heat exchanger, size 05
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 05 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
The air handling unit is supplied on a wooden pallet.
The set of support legs, for mounting the base beams, is available as an accessory.
DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.
Power Connection
230/1/60
FLA 11.43
MCA 12.81
RFS 15
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
*based on 550 fpm
CLEAR SPACE FOR INSPECTIONA clear space of 40 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.
PX
J
0.52*15 0.7
22
3
4
3
4
1.751.75 1.751.75 J 33
K GKG
II
0.50.5
Power connection
![Page 2: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/2.jpg)
PX 2
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
GOLD PX, plate heat exchanger, size 07
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 07 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
The air handling unit is supplied on a wooden pallet.
The set of support legs, for mounting the base beams, is available as an accessory.
DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.
PX
J
0.52*15 0.7
22
3
4
3
4
1.751.75 1.751.75 J 33
K GKG
II
0.50.5
Power connection
Size A B F G H I J K L Wgt (lb) Airflow ERV Airflow CWC
PX 07 35.9 39.2 14.0 24.0 42.7 7.4 29.5 7.6 98.5 957-1082 1500 cfm 1420 cfm*
*based on 550 fpm
CLEAR SPACE FOR INSPECTIONA clear space of 40 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
Power Connection
230/1/60
FLA 11.43
MCA 12.81
RFS 15
![Page 3: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/3.jpg)
PX 3
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
GOLD PX, plate heat exchanger, size 08
PX
J
0.52*15 0.7
22
3
4
3
4
1.751.75 1.751.75 J 33
K GKG
II
0.50.5
If a water trap (accessory) is fitted, the air handling unit must be raised at least 2 inches to provide space for the water trap. Support feet (accessories) can be used for this purpose. The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.
Power connection
Size A B F G H I J K L Wgt (lb) Airflow ERV Airflow CWC
PX 08 35.9 39.2 14.0 24.0 42.7 7.4 29.5 7.6 98.5 988-1113 2000 cfm 1420 cfm*
*based on 550 fpm
CLEAR SPACE FOR INSPECTIONA clear space of 40 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 08 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
The air handling unit is supplied on a wooden pallet.
The set of support legs, for mounting the base beams, is available as an accessory.
DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.
Power Connection
230/1/60
FLA 11.43
MCA 12.81
RFS 15
![Page 4: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/4.jpg)
PX 4
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
Size A B D E F G H I J K L Wgt (lb) Airflow ERV Airflow CWC
PX 11 25.5 47.2 64.2 18.5 18.0 32.0 51.0 7.5 37.5 7.6 115.2 1571-1769 2300 cfm 2300 cfm*
GOLD PX, plate heat exchanger, size 11
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 11 is always supplied as one unit. The air handling unit can be split into multiple sections to facilitate transporting it within the building site.
The multiple sections are joined together by bolts and the electrical and control cables between the sections have quick-fit connectors. The air handling unit is delivered on wooden pallets.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the
building site.
A: Specify right-hand or left-hand version when ordering.
PX
0.6 52*
15 0.7
D
E E 22
3
4
1.75 1.75J 3
K G
I
0.5
J
3
4
1.75 1.753
KG
I
0.5
If a water trap (accessory) is fitted, the air handling unit must be raised at least 2 inches to provide space for the water trap. Support feet (accessories) can be used for this purpose. The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.
Power connection
*based on 550 fpm
DIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.
Dimensions: See A and D in the table above.Weight: A = 297-385 lbs, D = 977-1518 lbs.
CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
A AD
Power Connection
230/1/60
FLA 11.43
MCA 12.81
RFS 15
![Page 5: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/5.jpg)
PX 5
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
Size A B D E F G H I J K L Wgt (lb) Airflow ERV Airflow CWC
PX 12 25.5 47.2 47.2 18.5 18.5 32.0 51.0 7.5 37.5 7.6 115.2 1619-1830 2850 cfm 2480 cfm*
GOLD PX, plate heat exchanger, size 12
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 12 is always supplied as one unit. The air handling unit can be split into multiple sections to facilitate transporting it within the building site.
The multiple sections are joined together by bolts and the electrical and control cables between the sections have quick-fit connectors. The air handling unit is delivered on wooden pallets.
The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the
building site.
A: Specify right-hand or left-hand version when ordering.
Power Connection
460/3/60 575/3/60
FLA 7.4 5.8
MCA 8.3 6.5
RFS 15 15
*based on 550 fpm
DIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.
Dimensions: See A and D in the table above.Weight: A = 322-416 lbs, D = 977-999 lbs.
CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
PX
0.6 52*
15 0.7
D
E E 22
3
4
1.75 1.75J 3
K G
I
0.5
J
3
4
1.75 1.753
KG
I
0.5
Power connection
A AD
![Page 6: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/6.jpg)
PX 6
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
Size A B D E F G H I J K L M N Wgt (lb) Airflow ERV Airflow CWC
PX 14 29.8 55.1 72.3 20.8 16.0 40.0 61.1 17.9 45.4 7.6 131.9 8.1 7.4 2044-2308 3150 cfm 3150 cfm*
GOLD PX, plate heat exchanger, size 14
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 14 is always supplied as one unit. The air handling unit can be split into multiple sections to facilitate transporting it within the building site.
The multiple sections are joined together by bolts and the electrical and control cables have quick connectors.
The air handling unit is delivered on wooden pallets.
The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit
within the building site.
DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering. B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).
Power Connection
460/3/60 575/3/60
FLA 7.4 5.8
MCA 8.3 6.5
RFS 15 15
D
E E 22
PX
M M
L
15 0.7
N
0.5
0.8
0.8
2*
N
31.75
1.75
4
D
E E 22
PX
M M
L
N
0.5
0.8
0.8
2*
N
31.75
1.75
4
Power connection
*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.
Dimensions: See A and D in the table above.Weight: A = 48-537 lbs, D = 1208-1235 lbs.
CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.
A AD
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.
![Page 7: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/7.jpg)
PX 7
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
GOLD PX, plate heat exchanger, size 20
Power Connection
460/3/60 575/3/60
FLA 10.4 8.2
MCA 11.7 9.2
RFS 15 15
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 20 is always supplied as one unit. The air handling unit can be split into multiple sections to facilitate transporting it within the building site.
The multiple sections are joined together by bolts and the electrical and control cables have quick connectors.
The air handling unit is delivered on wooden pallets.
The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit
within the building site.
DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering. B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).
*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.
Dimensions: See A and D in the table above.Weight: A = 440-581 lbs, D = 1208-1235 lbs.
CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.
Size A B D E F G H I J K L M N Wgt (lb) Airflow ERV Airflow CWC
PX 20 29.8 55.1 72.3 20.8 16.0 40.0 61.1 17.9 45.4 7.6 131.9 8.1 7.4 2088-2396 4200 cfm 3700 cfm*
D
E E 22
PX
M M
L
15 0.7
N
0.5
0.8
0.8
2*
N
31.75
1.75
4
D
E E 22
PX
M M
L
N
0.5
0.8
0.8
2*
N
31.75
1.75
4
Power connection
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
A AD
The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.
![Page 8: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/8.jpg)
PX 8
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
GOLD PX, plate heat exchanger, size 25
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 25 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into multiple sections to facilitate transporting it within the building site. The multiple sections are joined together by bolts and the electrical and control cables have quick connectors.
The air handling unit is delivered on wooden pallets. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.
DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.
B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).
Size A B D E F G H I J K L M N Wgt (lb) Airflow ERV Airflow CWC
PX 25 33.4 63.0 83.9 26.6 20.0 48.0 71.3 20.2 53.3 7.5 150.6 7.9 8.0 2717-3139 4750 cfm 4750 cfm*
Power Connection
460/3/60 575/3/60
FLA 10.4 8.2
MCA 11.7 9.2
RFS 15 15
*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.
Dimensions: See A and D in the table above.Weight: A = 548-733 lbs, D = 1622-1675 lbs.
CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit.
D
E E 22
PX
M M
L
15 0.7
N
0.5
0.8
0.8
2*
N
31.75
1.75
4
D
E E 22
PX
M M
L
N
0.5
0.8
0.8
2*
N
31.75
1.75
4
The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.
Power connection
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
A AD
![Page 9: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/9.jpg)
PX 9
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
GOLD PX, plate heat exchanger, size 30
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 30 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into multiple sections to facilitate transporting it within the building site. The multiple sections are joined together by bolts and the electrical and control cables have quick connectors.
The air handling unit is delivered on wooden pallets.The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).
Size A B D E F G H I J K L M N Wgt (lb) Airflow ERV Airflow CWC
PX 30 33.4 63.0 83.9 26.6 20.0 48.0 71.3 20.2 53.3 7.5 150.6 7.9 8.0 2831-3192 5800 cfm 5260 cfm*
Power Connection
460/3/60 575/3/60
FLA 15.1 11.9
MCA 17 13.3
RFS 20 15
PX
M M
L
D
E E 22
N
N
3
4
1.75
1.75
0.5
0.6
0.6
*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.
Dimensions: See A and D in the table above.Weight: A = 605-759 lbs, D = 1622-1675 lbs.
CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.
A AD
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.
![Page 10: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/10.jpg)
PX 10
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
GOLD PX, plate heat exchanger, size 35
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 35 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors.
The air handling unit is delivered on wooden pallets.The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).
Size A B D E F G H I J K L N Wgt (lb) Airflow ERV Airflow CWC
PX 35 40.9 78.3 94.5 31.7 24.0 56.0 85.0 22.3 68.7 11.2 176.3 9.4 3942-4484 7000 cfm 7000 cfm*
Power Connection
460/3/60 575/3/60
FLA 15.1 11.9
MCA 17 13.3
RFS 20 15
PX
L
D
E E 22
N
N
3
0.5
4
1.75
1.75
0.8
*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.
Dimensions: See A and D in the table above.Weight: A = 830-1060 lbs, D = 2284-2363 lbs.
CLEAR SPACE FOR INSPECTIONA clear space of 44 inches should be provided in front of the unit.
A AD
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.
![Page 11: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right](https://reader034.vdocuments.net/reader034/viewer/2022042622/5f8b361616f97e130f3c0867/html5/thumbnails/11.jpg)
PX 11
Sizing, Installation, Dimensions and Weight
We reserve the right to alter specifications.
GOLD PX Model
GOLD PX, plate heat exchanger, size 40
DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 40 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors.
The air handling unit is delivered on wooden pallets.The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).
Power Connection
460/3/60 575/3/60
FLA 15.1 11.9
MCA 17 13.3
RFS 20 15
PX
L
D
E E 22
N
N
3
0.5
4
1.75
1.75
0.8
*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.
Dimensions: See A and D in the table above.Weight: A = 858-1089 lbs, D = 2284-2363 lbs.
CLEAR SPACE FOR INSPECTIONA clear space of 44 inches should be provided in front of the unit.
A AD
Right-Hand Version
Left-Hand Version
Outside Air Supply Air Return Air Exhaust Air
Size A B D E F G H I J K L N Wgt (lb) Airflow ERV Airflow CWC
PX 40 40.9 78.3 94.5 31.7 24.0 56.0 85.0 22.3 68.7 11.2 176.3 9.4 4000-4541 8400 cfm 8400 cfm*
The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.