11
PX 1 Sizing, Installation, Dimensions and Weight We reserve the right to alter specifications. GOLD PX Model Size A B F G H I J K L Wgt (lb) Airflow ERV Airflow CWC PX 05 32.4 32.5 12.0 18.0 36.2 6.1 22.8 7.2 91.9 768-851 1300 cfm 920 cfm* GOLD PX, plate heat exchanger, size 05 DELIVERY AND TRANSPORT WITHIN THE SITE The GOLD PX 05 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit. The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. The air handling unit is supplied on a wooden pallet. The set of support legs, for mounting the base beams, is available as an accessory. DUCT CONNECTION OPTIONS A: Specify right-hand or left-hand version when ordering. Power Connection 230/1/60 FLA 11.43 MCA 12.81 RFS 15 Right-Hand Version Left-Hand Version Outside Air Supply Air Return Air Exhaust Air *based on 550 fpm CLEAR SPACE FOR INSPECTION A clear space of 40 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood. PX J 0.5 2* 15 0.7 2 2 3 4 3 4 1.75 1.75 1.75 1.75 J 3 3 K G K G I I 0.5 0.5 Power connection

Upload: others

Post on 03-Aug-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 1

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

Size A B F G H I J K L Wgt (lb) Airflow ERV Airflow CWC

PX 05 32.4 32.5 12.0 18.0 36.2 6.1 22.8 7.2 91.9 768-851 1300 cfm 920 cfm*

GOLD PX, plate heat exchanger, size 05

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 05 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit.

The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.

The air handling unit is supplied on a wooden pallet.

The set of support legs, for mounting the base beams, is available as an accessory.

DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.

Power Connection

230/1/60

FLA 11.43

MCA 12.81

RFS 15

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

*based on 550 fpm

CLEAR SPACE FOR INSPECTIONA clear space of 40 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.

PX

J

0.52*15 0.7

22

3

4

3

4

1.751.75 1.751.75 J 33

K GKG

II

0.50.5

Power connection

Page 2: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 2

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

GOLD PX, plate heat exchanger, size 07

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 07 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit.

The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.

The air handling unit is supplied on a wooden pallet.

The set of support legs, for mounting the base beams, is available as an accessory.

DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.

PX

J

0.52*15 0.7

22

3

4

3

4

1.751.75 1.751.75 J 33

K GKG

II

0.50.5

Power connection

Size A B F G H I J K L Wgt (lb) Airflow ERV Airflow CWC

PX 07 35.9 39.2 14.0 24.0 42.7 7.4 29.5 7.6 98.5 957-1082 1500 cfm 1420 cfm*

*based on 550 fpm

CLEAR SPACE FOR INSPECTIONA clear space of 40 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

Power Connection

230/1/60

FLA 11.43

MCA 12.81

RFS 15

Page 3: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 3

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

GOLD PX, plate heat exchanger, size 08

PX

J

0.52*15 0.7

22

3

4

3

4

1.751.75 1.751.75 J 33

K GKG

II

0.50.5

If a water trap (accessory) is fitted, the air handling unit must be raised at least 2 inches to provide space for the water trap. Support feet (accessories) can be used for this purpose. The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Power connection

Size A B F G H I J K L Wgt (lb) Airflow ERV Airflow CWC

PX 08 35.9 39.2 14.0 24.0 42.7 7.4 29.5 7.6 98.5 988-1113 2000 cfm 1420 cfm*

*based on 550 fpm

CLEAR SPACE FOR INSPECTIONA clear space of 40 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 08 is produced in one single variant, in which all the components are arranged at their given physical locations inside the air handling unit.

The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.

The air handling unit is supplied on a wooden pallet.

The set of support legs, for mounting the base beams, is available as an accessory.

DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.

Power Connection

230/1/60

FLA 11.43

MCA 12.81

RFS 15

Page 4: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 4

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

Size A B D E F G H I J K L Wgt (lb) Airflow ERV Airflow CWC

PX 11 25.5 47.2 64.2 18.5 18.0 32.0 51.0 7.5 37.5 7.6 115.2 1571-1769 2300 cfm 2300 cfm*

GOLD PX, plate heat exchanger, size 11

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 11 is always supplied as one unit. The air handling unit can be split into multiple sections to facilitate transporting it within the building site.

The multiple sections are joined together by bolts and the electrical and control cables between the sections have quick-fit connectors. The air handling unit is delivered on wooden pallets.

The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the

building site.

A: Specify right-hand or left-hand version when ordering.

PX

0.6 52*

15 0.7

D

E E 22

3

4

1.75 1.75J 3

K G

I

0.5

J

3

4

1.75 1.753

KG

I

0.5

If a water trap (accessory) is fitted, the air handling unit must be raised at least 2 inches to provide space for the water trap. Support feet (accessories) can be used for this purpose. The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Power connection

*based on 550 fpm

DIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.

Dimensions: See A and D in the table above.Weight: A = 297-385 lbs, D = 977-1518 lbs.

CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

A AD

Power Connection

230/1/60

FLA 11.43

MCA 12.81

RFS 15

Page 5: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 5

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

Size A B D E F G H I J K L Wgt (lb) Airflow ERV Airflow CWC

PX 12 25.5 47.2 47.2 18.5 18.5 32.0 51.0 7.5 37.5 7.6 115.2 1619-1830 2850 cfm 2480 cfm*

GOLD PX, plate heat exchanger, size 12

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 12 is always supplied as one unit. The air handling unit can be split into multiple sections to facilitate transporting it within the building site.

The multiple sections are joined together by bolts and the electrical and control cables between the sections have quick-fit connectors. The air handling unit is delivered on wooden pallets.

The electrical cabinet and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the

building site.

A: Specify right-hand or left-hand version when ordering.

Power Connection

460/3/60 575/3/60

FLA 7.4 5.8

MCA 8.3 6.5

RFS 15 15

*based on 550 fpm

DIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.

Dimensions: See A and D in the table above.Weight: A = 322-416 lbs, D = 977-999 lbs.

CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

PX

0.6 52*

15 0.7

D

E E 22

3

4

1.75 1.75J 3

K G

I

0.5

J

3

4

1.75 1.753

KG

I

0.5

Power connection

A AD

Page 6: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 6

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

Size A B D E F G H I J K L M N Wgt (lb) Airflow ERV Airflow CWC

PX 14 29.8 55.1 72.3 20.8 16.0 40.0 61.1 17.9 45.4 7.6 131.9 8.1 7.4 2044-2308 3150 cfm 3150 cfm*

GOLD PX, plate heat exchanger, size 14

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 14 is always supplied as one unit. The air handling unit can be split into multiple sections to facilitate transporting it within the building site.

The multiple sections are joined together by bolts and the electrical and control cables have quick connectors.

The air handling unit is delivered on wooden pallets.

The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit

within the building site.

DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering. B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).

Power Connection

460/3/60 575/3/60

FLA 7.4 5.8

MCA 8.3 6.5

RFS 15 15

D

E E 22

PX

M M

L

15 0.7

N

0.5

0.8

0.8

2*

N

31.75

1.75

4

D

E E 22

PX

M M

L

N

0.5

0.8

0.8

2*

N

31.75

1.75

4

Power connection

*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.

Dimensions: See A and D in the table above.Weight: A = 48-537 lbs, D = 1208-1235 lbs.

CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.

A AD

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Page 7: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 7

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

GOLD PX, plate heat exchanger, size 20

Power Connection

460/3/60 575/3/60

FLA 10.4 8.2

MCA 11.7 9.2

RFS 15 15

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 20 is always supplied as one unit. The air handling unit can be split into multiple sections to facilitate transporting it within the building site.

The multiple sections are joined together by bolts and the electrical and control cables have quick connectors.

The air handling unit is delivered on wooden pallets.

The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit

within the building site.

DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering. B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).

*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.

Dimensions: See A and D in the table above.Weight: A = 440-581 lbs, D = 1208-1235 lbs.

CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.

Size A B D E F G H I J K L M N Wgt (lb) Airflow ERV Airflow CWC

PX 20 29.8 55.1 72.3 20.8 16.0 40.0 61.1 17.9 45.4 7.6 131.9 8.1 7.4 2088-2396 4200 cfm 3700 cfm*

D

E E 22

PX

M M

L

15 0.7

N

0.5

0.8

0.8

2*

N

31.75

1.75

4

D

E E 22

PX

M M

L

N

0.5

0.8

0.8

2*

N

31.75

1.75

4

Power connection

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

A AD

The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Page 8: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 8

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

GOLD PX, plate heat exchanger, size 25

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 25 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into multiple sections to facilitate transporting it within the building site. The multiple sections are joined together by bolts and the electrical and control cables have quick connectors.

The air handling unit is delivered on wooden pallets. The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site.

DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.

B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).

Size A B D E F G H I J K L M N Wgt (lb) Airflow ERV Airflow CWC

PX 25 33.4 63.0 83.9 26.6 20.0 48.0 71.3 20.2 53.3 7.5 150.6 7.9 8.0 2717-3139 4750 cfm 4750 cfm*

Power Connection

460/3/60 575/3/60

FLA 10.4 8.2

MCA 11.7 9.2

RFS 15 15

*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.

Dimensions: See A and D in the table above.Weight: A = 548-733 lbs, D = 1622-1675 lbs.

CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit.

D

E E 22

PX

M M

L

15 0.7

N

0.5

0.8

0.8

2*

N

31.75

1.75

4

D

E E 22

PX

M M

L

N

0.5

0.8

0.8

2*

N

31.75

1.75

4

The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Power connection

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

A AD

Page 9: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 9

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

GOLD PX, plate heat exchanger, size 30

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 30 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into multiple sections to facilitate transporting it within the building site. The multiple sections are joined together by bolts and the electrical and control cables have quick connectors.

The air handling unit is delivered on wooden pallets.The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).

Size A B D E F G H I J K L M N Wgt (lb) Airflow ERV Airflow CWC

PX 30 33.4 63.0 83.9 26.6 20.0 48.0 71.3 20.2 53.3 7.5 150.6 7.9 8.0 2831-3192 5800 cfm 5260 cfm*

Power Connection

460/3/60 575/3/60

FLA 15.1 11.9

MCA 17 13.3

RFS 20 15

PX

M M

L

D

E E 22

N

N

3

4

1.75

1.75

0.5

0.6

0.6

*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.

Dimensions: See A and D in the table above.Weight: A = 605-759 lbs, D = 1622-1675 lbs.

CLEAR SPACE FOR INSPECTIONA clear space of 36 inches should be provided in front of the unit and at least 8 inches should be provided above the junction hood.

A AD

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Page 10: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 10

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

GOLD PX, plate heat exchanger, size 35

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 35 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors.

The air handling unit is delivered on wooden pallets.The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).

Size A B D E F G H I J K L N Wgt (lb) Airflow ERV Airflow CWC

PX 35 40.9 78.3 94.5 31.7 24.0 56.0 85.0 22.3 68.7 11.2 176.3 9.4 3942-4484 7000 cfm 7000 cfm*

Power Connection

460/3/60 575/3/60

FLA 15.1 11.9

MCA 17 13.3

RFS 20 15

PX

L

D

E E 22

N

N

3

0.5

4

1.75

1.75

0.8

*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.

Dimensions: See A and D in the table above.Weight: A = 830-1060 lbs, D = 2284-2363 lbs.

CLEAR SPACE FOR INSPECTIONA clear space of 44 inches should be provided in front of the unit.

A AD

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.

Page 11: GOLD PX, plate heat exchanger, size 05swegonnorthamerica.com/wp-content/uploads/2017/09/GOLD... · 2017-09-25 · PX 2 Siing, Installation, Dimensions and Weight We reserve the right

PX 11

Sizing, Installation, Dimensions and Weight

We reserve the right to alter specifications.

GOLD PX Model

GOLD PX, plate heat exchanger, size 40

DELIVERY AND TRANSPORT WITHIN THE SITEThe GOLD PX 40 is supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section to the right of the centre section (viewed from the inspection side). The other unit consists of a fan/filter section to the left of the centre section (viewed from the inspection side). The air handling unit can be split into three sections to facilitate transporting it within the building site. The three sections are joined together by bolts and the electrical and control cables have quick connectors.

The air handling unit is delivered on wooden pallets.The electrical equipment cubicle and the drain pipe on the front of the air handling unit can be removed, if required, for transporting the unit within the building site. DUCT CONNECTION OPTIONSA: Specify right-hand or left-hand version when ordering.B: Specify whether the unit shall have an air intake from above for outdoor air and/or return air when placing orders (not for outdoor units).

Power Connection

460/3/60 575/3/60

FLA 15.1 11.9

MCA 17 13.3

RFS 20 15

PX

L

D

E E 22

N

N

3

0.5

4

1.75

1.75

0.8

*based on 550 fpmDIVISION INTO SECTIONS FOR TRANSPORTThe unit can be divided into three sections at the building site.

Dimensions: See A and D in the table above.Weight: A = 858-1089 lbs, D = 2284-2363 lbs.

CLEAR SPACE FOR INSPECTIONA clear space of 44 inches should be provided in front of the unit.

A AD

Right-Hand Version

Left-Hand Version

Outside Air Supply Air Return Air Exhaust Air

Size A B D E F G H I J K L N Wgt (lb) Airflow ERV Airflow CWC

PX 40 40.9 78.3 94.5 31.7 24.0 56.0 85.0 22.3 68.7 11.2 176.3 9.4 4000-4541 8400 cfm 8400 cfm*

The air handling unit is supplied without end connection panel if a duct accessory housed in an insulated casing will be connected.