Retrofit Doors to Open Vertical Cases
Provisional UES Proposal Presentation to the Regional Technical Forum
August 30, 2011
1
![Page 2: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/2.jpg)
Measure Summary
• Retrofitting insulated glass doors to existing medium temperature open multi-deck cases
• Provisional savings estimates ~440-kWh/lin ft and 52-therms/lin ft
• Based on a calibrated DOE2.2r simulation
• Requesting Provisional UES Status
2
![Page 3: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/3.jpg)
3
UES Analysis Summary
![Page 4: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/4.jpg)
Appendix A: Provisional UES Checklist
4
![Page 5: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/5.jpg)
5
Appendix B: UES Measure Summary
![Page 6: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/6.jpg)
6
![Page 7: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/7.jpg)
7
![Page 8: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/8.jpg)
8
![Page 9: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/9.jpg)
9
![Page 10: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/10.jpg)
Implementation and Product Standards
10
• No anti-sweat heat in door glass, frames or mounting equipment
• Total lighting power may not be increased as a part of the retrofit
![Page 11: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/11.jpg)
Estimation Procedure
11
• Modeled using DOE 2.2R to capture interactive effects
• “Typical” store was built using GrocerSmart Audit Data
• Multiplex Baseline assumes Floating Head Pressure, T8 lamps, and EC motors are in place.
• Stand-alone system baseline assumes T8 lamps and EC motors.
• Infiltration, conduction, and radiation load based on manufacturer data, the ASHRAE Refrigeration Handbook, and SCE lab test reports
![Page 12: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/12.jpg)
Model Calibration: Whole Building
12
![Page 13: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/13.jpg)
Model Calibration:Compressor Energy Use
13
![Page 14: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/14.jpg)
Model Calibration- Baseline:Case Refrigeration Load
14
Total case load based on ANSI/ASHRAE 72 testing = 1600 btu/hr-ft
ASHRAE data used to disaggregate load components
![Page 15: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/15.jpg)
Model Calibration – Efficient-Case: Fixture Refrigeration Load
15
![Page 16: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/16.jpg)
16
Costs Estimated
• All measure variants: $566/ft
• Average of 4 bids from 2 vendors
• Includes additional costs from minor system upgrades required to compensate for reduced load (replace expansion valves, etc.)
![Page 17: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/17.jpg)
17
Measure Effective Useful Life
• EUL: 12 years
• Source: CALMAC
• Assumes display cases have a 16 year EUL and have expended 25% of EUL
![Page 18: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/18.jpg)
18
Reliable Efficient Case Data
![Page 19: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/19.jpg)
Calibration Plan• Collect Metered Data
– Rack: Volts, Amps, PF– Condenser: Volts, Amps, PF– Defrost: 1-time Voltage reading, Amps– HVAC Unit: 1-time Voltage reading, Amps– Hourly Natural Gas via Utility Interval Meter– Hourly Outside Air Temperature
• Minimum 3 weeks baseline • Minimum 3-weeks post
– This is a direct load measure. We expect less seasonal interaction than system measures like floating head pressure.
19
![Page 20: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/20.jpg)
Calibration Plan• Develop regressions for daily or hourly
refrigeration use correlated to ambient temperature
• Annualize using TMY data– Pre, Post and Savings (Pre minus Post)
20
![Page 21: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/21.jpg)
Calibration Plan
• Collect DOE2.2r inputs per data collection specifications• Use inputs to run DOE2.2r for Baseline & Post estimates
of total refrigeration energy• Compare estimates of Baseline, Post & Savings
estimates of refrigeration energy to best-practice estimates
• Modify DOE2.2r models and iterate tests until both baseline energy use, post energy use and energy savings at all sites are reasonable and there is no significant bias.
21
![Page 22: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/22.jpg)
Proposed Provisional UES Values
Measure
Site Savings (kWh/ft)
Site Savings
(therms/ft)Measure
LifeCapital
Cost ($/ft)TRC B/C
Ratio
Door Retrofit- No night covers in Baseline/Multiplex Compressor- Seattle, WA 457.2 57.4 12 $566 2.2
Door Retrofit- Night covers in Baseline/Multiplex Compressor- Seattle, WA 415.2 51.9 12 $566 2.0
Door Retrofit- No night covers in Baseline/Stand-alone Compressor- Seattle, WA 477.4 57.4 12 $566 2.2
Door Retrofit- Night covers in Baseline/Stand-alone Compressor- Seattle, WA 432.7 51.9 12 $566 2.0
Door Retrofit- No night covers in Baseline/Multiplex Compressor- Spokane, WA 419.1 51.7 12 $566 2.0
Door Retrofit- Night covers in Baseline/Multiplex Compressor- Spokane, WA 377.5 46.5 12 $566 1.8
Door Retrofit- No night covers in Baseline/Stand-alone Compressor- Spokane, WA 436.7 51.7 12 $566 2.0
Door Retrofit- Night covers in Baseline/Stand-alone Compressor- Spokane, WA 392.7 46.5 12 $566 1.8
Door Retrofit- No night covers in Baseline/Multiplex Compressor- Billings, MT 417.3 48.0 12 $566 1.9
Door Retrofit- Night covers in Baseline/Multiplex Compressor- Billings, MT 371.6 43.1 12 $566 1.7
Door Retrofit- No night covers in Baseline/Stand-alone Compressor- Billings, MT 433.9 48.0 12 $566 2.0
Door Retrofit- Night covers in Baseline/Stand-alone Compressor- Billings, MT 386.1 43.1 12 $566 1.8
![Page 23: Retrofit Doors to Open Vertical Cases Provisional UES Proposal Presentation to the Regional Technical Forum August 30, 2011 1](https://reader036.vdocuments.net/reader036/viewer/2022062806/56649e215503460f94b0de00/html5/thumbnails/23.jpg)
RTF Proposed Motion:
“I _________ move that the RTF approve the UES for Adding Doors to Medium Temperature Open Vertical Refrigerated Display Cases under provisional status with a sunset date of August 31st, 2013.