Type Series Booklet5125.53-10 Controlmatic E
Automatic Control Units
Fields of ApplicationControlmatic E can be used to start up, switch off and controlsmall pumps in water supply systems.
Medium HandledDrinking water, service water, rain water, fire-fighting water,cooling water, provided the fluid pumped is not chemically ormechanically aggressive to the control unit’s materials.
Operating DataCapacity Q up to 10 m3/h, 2.77 l/sOperating pressure p 10 bar 1)Minimum start-up pressure 1.5 barMinimum flow rate 0.1 m3/hWater temperature 0 up to 60 °CMaximum ambient temperature 60 °CIntegrated pressure setting from 1.5 to 2.6 barOnly single-phase a. c. motor1) Controlmatic E must be protected against any pressure higher than the
operating pressure.
DesignationControlmatic E
DesignMonitoring unit governed by pressure gauge and flow meter.Controlmatic E controls start-up and stopping of the pumpwhen the consumer installation is opened or closed.
Function1. The consumer installation is closed, the pump is switched off.Controlmatic E’s green ’availability’ LED is lit.
2. When the consumer installation is opened, the hydraulicpressure in the system decreases. The pump is started up.
3. The pump is working, the yellow ’operation’ LED is lit.
4. When the consumer installation is closed and the flow rateis zero, the pump is switched off after 10 seconds.
Dry-running protectionThe pump is protected against dry-running thanks tosimultaneous monitoring of the pump’s pressure and flow rate.If there is a lack of water, Controlmatic E automatically stops thepump, the red ’fault’ LED lights up.
MaterialsCasing PolyamideMembrane Elastomer
Minimum flow rate 0.10 m3/h
The pump isstarted up
The pump is stopped
Curve to be selected
This type of curve mustbe avoided.
Max. duty point
When selecting pumps, please note:The start-up pressure set on Controlmatic E must be lower than the max. shutoff head.
Minimum start-up pressure 1.5 bar
Rp 1
G 1 1/4G 1 1/4
Rp 1
G 1 1/4
Controlmatic E
2
Designation Controlmatic EMax. operating pressure 1) bar 10Capacity m3/h
l/s102.77
Type of enclosure IP 44
Temperature of medium handled / ambient temperature 0 up to 60 °CMains voltage 1~220/240 VFrequency Hz 50 / 60Max. current intensity A 10Dry-running protection yesRe-start after lack of water manualWeight kg 1.3Ident-No. 39 019 124
1) The automatic control unit Controlmatic E must be protected against any pressure higher than the operating pressure. Minimum start-uppressure 1.5 bar.
The following must be strictly complied with:Pressuresuction side + pressuremax. pump (at zero flow) < 10 barIn case of doubt regarding the suction side pressure:-- either a safety margin of 3 bar has to be taken into account, i.e.:
(pressuresuction side + 3 bar) + [pressuremax. pump (at zero flow)] < 10 bar-- or a pressure reducer (pressure stabiliser) must be installed between the pump and Controlmatic E or on the pump suction side in order to avoidexcessive pressure.If the plant is expected to be subject to surge pressures by quick-closing valves (e.g. solenoid valves), please contact one of KSB’s sales branches.
Controlmatic E can be used with the following pumps (single-phase motor only)
Pumpe Multi Eco Multichrom S Movichrom NB Ixo S 100B
33 E, 34 E, 35 E,36 E, 65 E
33 E, 34 E, 35 E,36 E, 53 E, 54 E,55 E
3 E, 5 E 45 E, 55 E, 65 E,48 E, 58 EIxo RWS 45 E,55 E, 65 E
1/7, 1/9, 1/12, 1/14, 1/162/7, 2/11, 2/15, 2/184/4, 4/6, 4/9, 4/127/5, 7/7, 7/9
Controlmatic E • • • • •Connectionparts Accessory Accessory Accessory Accessory Accessory
An additional correction part might be required depending on the pump nozzle diameter.
The start-up pressure has been set to1.5 bar at the factory and may beincreased to 2.6 bar, if required.
226
18079
,5
G1”
G1”
After modification the pressure gauge can be fitted at 2 different positions.
Mul
tichr
omS
Ixo
/Ixo
RW
S
S10
0B
Mov
ichr
omN
B
Mul
tiE
co
Controlmatic E
3
DimensionsControlmatic E
Installation Positions
Accessories
ca. kg
Connection part made of brassExternal / internal thread G 1
X X 39 019 415 0.6
Connection part made of brassExternal thread G 1 1/4 / internal thread G 1
X X X 39 019 530 0.5
KSB Aktiengesellschaft67225 Frankenthal • Johann-Klein-Str. 9 • 67227 Frankenthal (Germany)Tel. +49 6233 86--0 • Fax +49 6233 86--3401 • www.ksb.com
5125
.53-
101.
5.20
03S
ubje
ctto
tech
nica
lmod
ifica
tion
with
outp
rior
notic
e.
Compared with pump sets fitted with pressure vessels, pumps controlled by Controlmatic Eautomatic control units will supply a constant pressure at any particular flow rate.
Dischargehead
Time
Controlmatic ECustomer Benefits: The start-up pressure can
be set externallyto a value between1.5 and 2.6 bar
Pressure readingvia integratedpressure gaugewhich can be fitted at2 different positions
Integrated socketfor pump connection
Cable with shockproof plugfor mains connection
LEDs:Green -- AvailableYellow -- Pump runningRed -- Fault or lack of water
Controlmatic E
Pressure Characteristics in Comparision