    TECHNICAL SPECIFCATIONS

    FOR 11KV VACUUM CIRCUIT BREAKER HT

    PANEL

    TECHNICAL SPECIFCATIONS

    FOR 11KV VACUUM CIRCUIT BREAKER HT

    PANEL

    Draft Specification

    Page 1 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    2/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    1.0.0 GENERAL

    1.0.1 This specification covers design, fabrication, testing, packing, and supply of

    11KV, H.T. indoor, freestanding, drawout type metal clad switchgear of 11kV

    trolley mounted vacuum circuit breakers. The switchboards shall be new which

    specifically produced against this order.

    1.0.2 Reliability of equipment and ease of maintenance without hazards to operation

    and maintenance personnel are of utmost importance. The workmanship shalbe of highest grade and the entire construction in accordance with the best

    modern practice. The equipment shall be capable of continuous and reliable

    trouble free operation at full load ratings.

    1.0.3 The design and construction of vacuum circuit breakers, bus bars and other

    components shall meet the requirements of severe fault levels. Protective

    devices and control components shall meet the standard design and the

    system requirements.

    1.0.4 The design and construction shall be capable of with standing the severest stress

    likely to occur in actual service and of resisting rough handling during

    shipment. All similar materials and parts of similar equipment shall be inter-

    changeable with each other. The boards shall be fitted with the same family of

    vacuum circuit breakers and other components of various rating with a view to

    ensure uniformity of design and ease in maintenance and replacement of

    spares. The fabrication and arrangement of the switchboard shall be such thatit can be extended on both sides at a future date.

    1.0.5 The manufacturer of the switchgear has to be the manufacturer of Interrupter.

    1.1.0 CODES AND STANDARDS:

    1.1.1 The Switchboard shall conform to latest editions of the following Indian

    Standards:

    a) IS: 13118 Alternating current circuit breakers.

    b) IS : 4710 Switches and switch isolators above 1.0 kV but

    not exceeding 11 kV.

    c) IS : 370 Marking and arrangement of switchgear bus

    barsd) IS : 2705 (P-I TO IV) Current transformers

    Page 2 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    3/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    e) IS : 3156 Voltage transformers

    f) IS : 1248 Electrical indicating instruments

    g) IS : 2208 HRC cartridge Fuse link upto 650 V

    h) IS : 694 PVC insulated power cables (for voltage upto

    1100 V) with copper conductors.

    i) IS : 3427 Degree of protection provided for metal enclosed

    switchgear and control gear.

    j) IS : 3231 Electrical relays for power system protection.

    k) IS : 6875 Control switches and push buttons.

    l) IS : 5578 Guide for marking of insulated conductors.

    m) IS : 772 Integrated meters

    n) IS : 5082 Materials for data for aluminium busbars

    o) IS : 3618 Phosphate treatment of iron and steel forprotection against corrosion.

    p) IS : 6005 Code of practice of phosphating of iron and

    steel.

    q) IEC:62271-100 High voltage alternating current circuit breakers

    r) IEC:62271-200 AC metal enclosed switchgear and control gear

    for rated voltage above 1 kV upto 52 kV.

    1.2.0 SYSTEM:

    The Switchboards shall be suitable for the following system:

    a) Rated voltage 11 kV + 10%

    b) Fault level 25/31.5 KA for 1Sec

    c) Bus bars Adequate capacity Electrolytic grade

    Copper bus bars with uniform cross

    section, Heat shrinkable PVC sleeved.

    d) Operating

    frequency

    50 Hz + 3%

    e) No. of phases 3

    f) Control and 110V DC for Control & Protection and 230V

    Page 3 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    4/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    auxiliary supply single phase for space heater, spring

    charge motor etc. Control supply shall be

    fed from the battery bank to be supplied bythe Owner.

    1.3.0 SITE CONDITIONS:

    a) Altitude Less than 1000 M above MSL

    b) Temperature range +4 C to + 42C

    c) Humidity 90% (max)

    d) Average ambient temperature 35C

    e) Environment Highly corrosive

    f) Design Ambient Temperature 40C

    g) Temperature Rise Allowed As per IEC:60694, Table - 3

    1.4.0 GENERAL REQUIREMENTS:

    1.4.1 Switchgear shall be suitable for indoor installation, metal clad, drawout type and

    shall comprise standard prefabricated, cold rolled sheet steel units, assembled

    to form a rigid free standing dead front structure. All front doors shall be

    hinged type. Rear doors shall be with bolted construction and consists of 3sections with inspection window, interlocked in such a way that the lower

    section can be opened only when the upper one is opened and thus

    inadvertent access to live parts is avoided. Vertical units Panels shall be

    assembled to form a continuous line up of uniform height

    1.4.2 The cubicles shall be totally enclosed and vermin proof design. If necessary,

    opening for natural ventilation shall be provided in the busbars chamber with

    uniformly distributed louvers backed up by G.I. wire mesh for protectionagainst entry of insects etc. Thickness of the sheet steel shall be minimum 2.0

    mm for front and rear doors & for pressure discharge flaps 1.6 mm. The

    enclosure protection shall be IP 4X as per IEC: 62271-200.

    1.4.3 Doors and openings shall be provided with high life cross-linked polyuretherene

    gaskets. All doors shall be key operated & hinged type.

    Page 4 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    5/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    1.4.4 Switchboards shall be suitable for operating in tropical climate and under the

    ambient conditions as specified.

    1.4.5 Compartments for cable connections shall be separate and allow cable pulling,

    termination and connection work with switchgear energized.

    1.4.6 Adequate barrier shall permit personnel to work safely within an empty

    compartment with the bus bars energized.

    1.4.7 The design shall be such as to allow extension on both sides, i.e. to provide

    additional two outgoing switchgear panels complete with all accessories and

    fittings, if required in future. Ends of bus bars shall be suitably drilled for this

    purpose. Panels at extreme ends shall have openings, which shall be covered

    with plate screwed at panel.

    1.4.8 The drawout carriage in the switchboard for all breakers shall have threepositions viz., Service, Test and Drawout. Automatic Metallic safety shutter

    shall be provided to ensure the inaccessibility of all live parts after the breakeris drawn out. It shall not be possible to drawout the carriage with circuit

    breaker closed.

    The breaker, shall remain outside the cubicle in the drawnout position.

    1.4.9 Suitable interlocks shall be provided to prevent faulty operation such as:

    - Plugging in or drawing out of a closed breaker.

    - Pulling out of auxiliary circuit plug with breaker in service position.

    - Pushing in breaker to service position with auxiliary circuit plug not in

    position.

    1.4.10 ACCESSIBILITY

    All the components in the Switch board panels shall be mounted in such a way

    that checking and removal of components shall be possible without disturbing

    that checking and removal of components shall be possible without disturbing

    adjacent components. All auxiliary equipments shall be easily accessible and

    visible from front side with their name plate details. It shall be possible to set

    all measuring relays in situ without de-energizing the switchboard. Al

    mounted equipments and associated components shall have identification tags

    of permanent nature at front and at the rear also.

    1.4.11 Unused C.T. secondary terminals shall be short circuited. All terminals shall beshrouded with plastic covers to prevent accidental contact.

    Page 5 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    6/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    1.4.12 BUSBARS

    1.4.12.1 The swichboard shall comprise of 3 phase busbars, which shall extend through

    all panels of the switchboard. All phase busbars shall be of uniform cross

    section throughout the switchgear board and shall be suitably sized to carry

    continuously the required current. Busbars shall be housed in a separate

    chamber and shall be accessible for inspection only with specified tools.

    Busbars shall be of HDHC electrolytic grade Copper and shall be insulated

    with black coloured heatshrinkable PVC sleeves throughout their length

    Phase identification shall be marked with HT coloured tape at regular interval.

    All joints shall be covered with good quality HT tape and monoplast

    compound.

    Busbars shall be supported at regular intervals and both, busbars and the

    supports shall be adequately size and braced to withstand the specified shortcircuit level without permanent deformation. Dynamic stress shall be

    calculated on the basis of the specified peak short circuit. All busbar supports

    shall be of non-carbonizing material resistant to acids and alkalis and shall

    have non-hygroscopic characteristics such as SMC, DMC epoxy bonded

    fibreglass.

    1.4.13 DRAWOUT COMPARTMENTS:

    All circuit breakers shall be fully drawout type and Truck mounted. Cassettemounted breaker is not acceptable. The connections on the bus side, outgoing

    and control circuits shall be through drawout contacts so that the breaker can

    be drawn out without disturbing any wiring. The current transformers for themetering and protection circuits shall preferably be mounted on the fixed

    portion of the circuit breakers.

    The circuit breaker mobile portion shall get earthed automatically as soon as

    the same is inserted into the fixed compartment, irrespective of its position in

    the compartment.

    It shall not be possible to rack in or drawout a breaker in service position whenthe same is in closed position.

    Page 6 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    7/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    1.4.14 POWER CONNECTION

    The incoming and outgoing power connections shall be through XLPE insulated

    aluminium conductor cables of suitable size. Ample space for connection of

    cables Cupal washers shall be used for all copper to aluminium joints.

    The switchboard shall be supplied complete with supports for clamping

    outgoing and incoming cables. Terminal blocks shall not be used to support

    cables.

    1.4.15 AUXILIARY WIRING AND TERMINALS:

    Inside the panels, the wiring for control, signaling, protection and instruments

    circuits shall be done with PVC insulated copper conductors. The insulation

    grade shall be 1100 V. The wiring shall be enclosed in plastic channels or

    neatly bunched together.

    10% spare terminals shall be provided on each terminal block. Conductors

    shall be terminated with adequately sized compression type lugs forconnection to terminal strips of Elmex / Tosha/ Essen / Connectwell makes

    only. All auxiliary equipment termination shall be made with pressure type

    terminals. Sufficient terminals shall be provided on each terminal block to

    ensure that not more than one outgoing wire is connected per terminals.

    Terminal strips shall preferably be separated from Power circuits by meta

    barriers or enclosures.

    Each auxiliary circuit wire shall be identified at both ends by PVC ferrules.

    Shorting links shall be provided for all C.T. terminals.

    For CT circuits PVC insulated 2.5 mm2

    copper conductor cables shall be usedOther wiring shall be carried out with PVC insulated 1.5 mm2 copper

    conductor cables.

    Supporting facilities shall be provided for clamping the control cables.

    All auxiliary circuits shall be protected by HRC fuses / MCB bearing

    identification labels. All control fuses shall be of link type in fuse carries and

    shall have operation indicators.

    1.4.16 CONTROL AND INDICATION:

    All controls, critical indications, annunciations of Switchboard shall be on 110 VD.C., Breaker position (ON/OFF/spring charged/ test position/ service position)

    Page 7 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    8/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    shall be indicated. Electrical indications with colours as given below shall be

    provided:

    Breaker ON - Red lamp

    Breaker OF - Green lamp

    Breaker Auto trip - Amber lamp

    Trip ckt healthy - White lamp

    DC fails - Blue lamp

    1.4.17 EARTHING ARRANGEMENTS:

    All cubicles shall be connected to an earth busbar running throughout the

    length of the switchboard. The earth bus size shall be 50x6 m copper. Al

    doors and moveable parts shall be connected to the earth bus with flexible

    copper connections. Provision shall be made to connect the earthing busbar to

    the plant earthing grid at two ends. All non-current carrying metallic parts ofthe switchboard shall be earthed. Earth bus shall be brought back to cable

    compartments and earthing bolts shall be provided to ground cable armours.Mating surfaces of all bolted parts shall be specially zinc passivated to ensure

    continuity between them.

    1.4.18 NAME PLATE

    a) Nameplates of approved design shall be provided at the top of the panel to

    represent switchgear designation. A separate nameplate giving details shal

    be provided at front and rear end of each panel also.

    b) Identification / Name plate shall be provided for each equipment (lamps,

    Push buttons, switches, relays, auxiliary contactor, indicating instrumentetc.,) mounted on the panels. Special warning plates shall be provided on

    all removal covers or doors giving access to high voltage cable

    terminations/ bus bars. Special warning label shall be provided inside thepanels also wherever considered necessary.

    Engraved Panel name plates shall preferably be of 3 ply (Black-White-Black)

    laminated sheets or anodised aluminium. Name plates shall be fastened by

    counter sunk screws and not by adhesive.

    1.4.19 SURFACE TREATMENT AND PAINTING:

    Switchboard shall be powder coated (epoxy based) with a paint shade LightGrey RAL 7032 as per DIN.

    Page 8 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    9/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    The switchboard shall be free from imperfections like pinholes, orange peels,

    run off paint etc. All unpainted steel parts shall be cadmium plated or suitably

    treated to prevent any rust.

    1.4.20 SPACE HEATERS:

    Each cubicle shall be provided with a space heater to prevent moisturecondensation and maintain cubicle temperature at 5C above the ambient. The

    space heater shall be located at the bottom of each panel of switchboard and

    shall be controlled through a thermostat with an adjustable setting and a

    manually operated switch and with miniature circuit breaker of suitable rating

    for circuit protection. Switchboard space heater supply of 230 V A.C. for each

    switchgear panel shall be given at one point for each section. 230 V A.C.

    control wire bus with loop-in loop-out method shall also run along the

    switchboard for feeding space heaters.

    1.5.0 POWER CIRCUIT BREAKER (VACUUM CIRCUIT BREAKER):

    1.5.1 Power circuit breaker shall be triple pole, vacuum type, spring closed, horizonta

    draw out & horizontal isolation type breaker with transport truck rated 11KV

    having symmetrical breaking capacity of minimum as per cl. 1.3.0 andequipped with auto spring charging motor working on 230 V, 50 Hz. Single

    phase, AC and a closing coil suitable for 110 V D.C. it shall be possible to

    charge the spring manually, if, required. The breaker drawout carriage shall be

    so designed and constructed as to permit the smooth withdrawal and insertion

    of the breaker into it. The movement shall be free of jerks and easy tooperate.

    1.5.2 ON and OFF switches/ push buttons shall be mounted on the front door of eachpanel so as to operate the breaker manually (by removing one fiber glass

    sheet on panel front door) or electrically. The closing time and tripping time of

    breaker shall be independent of the speed of the operating handle.

    1.5.3 The breaker shall be provided with an auxiliary relay to achieve the antipumping

    function. This is to ensure that when closing on a fault, it does not reclose

    after tripping even if the closing input is maintained.

    1.5.4 If the breaker is in closed position, a closing operation of an initiating contro

    device shall not result in further operation of the breaker closing mechanism.

    Page 9 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    10/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    1.5.5 The breaker shall have following interlocking mechanism.

    i) Breaker can be operated electrically only when it is either in service

    or in test position.

    ii) Withdrawal of breaker from operating position is possible only when

    the breaker is in OFF position. Also the breaker cannot be inserted in

    ON position.

    iii) In the operating position the breaker shall be securely housed and

    locked. It can be withdrawn or inserted only with appropriateoperation of the interlocking levers.

    1.5.6 Vacuum circuit breaker shall be provided with at least 4 N.O. and 4 N.C. auxiliary

    contacts. For requirements of extra space contacts an auxiliary contactor shal

    be used to multiply the auxiliary contacts of the breakers. All the contacts shall

    be wired to the terminal blocks and shall be so located as to allow free access.The control circuit shall be suitable for local as well as remote control. Auxiliary

    contacts and limit switches shall be in dust tight enclosures.

    1.5.7 Mechanical trip push buttons shall be provided for all breakers for emergency

    tripping.

    1.5.8 For all motor feeders only ZnO type surge suppressors shall be provided.

    1.5.9 Circuit Breaker / Panel have to be tested for IEC: 62271-100 and for Capacitor

    duty switching. Bidder to submit test report not older than 5-years.

    1.6.0 INSTRUMENT TRANSFORMERS:

    Current Transformer (CTs) and Potential Transformers (PTs) shall be cast resininsulated. Primary and secondary terminals shall be marked with good quality

    PVC stickers.

    1.6.1 CURRENT TRANSFORMERS

    Current Transformers shall generally conform to IS 2705. They shall be

    mounted on the switchgear stationary part. The CT shall be of suitable rating

    & burden required for individual feeders. The neutral side of the current

    transformers shall normally be earthed through a link. Unused CT secondaryterminals shall be short-circuited with the shorting link.

    Page 10 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    11/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    All CTs shall be capable of withstanding the minimum primary fault current as

    per the respective breaker capacities.

    1.6.2 POTENTIAL TRANSFORMERS

    The Potential transformers shall be drawout type and provided with secondary

    fuses. The primary connection shall be disconnected before PT become

    accessible. The potential transformer shall be mounted on a drawout carriagecomplete with fuses, on top of the Panel or in a separate cubicle. Breaker

    mounted PT is not acceptable.

    All the Incomers shall be provided with Line Connected PT.

    1.7.0 MEASURING INSTRUMENTS:

    All measuring instruments shall be of square pattern 96 mm x 96 mm (min.)

    flush mounted on front hinged door of instrument compartment of a panel. Allauxiliary equipment such as shunt, CTs, PTs etc. that are required shall be

    included in the supply of the switchboard.

    1.7.1 AMMETERS AND VOLTMETERS

    These shall be of Digital Three (3) Phase type with In-built selector switch. The

    accuracy class shall be 1.0 as per IS: 1248.

    1.7.2 MULTI-FUNCTION METERS:

    The Digital non-communicable Multi-function meters shall be flush mounted,

    preferably in a non-draw out case. It shall be suitable for operation on 3 phase3 wire unbalanced load. It shall have atleast A, V, PF, F, KW, KWh, Run Hours,

    ON hours measurement functions. The accuracy class shall be 1.0 as per IEC:

    62052-11.

    1.8.0 AUXILIARY EQUIPMENT:

    Auxiliary relays / contractors shall generally be used for interlocking &

    multiplying contacts. Auxiliary contacts shall be capable of carrying the

    maximum estimated current. In any case their rating must not be less than 5Watt for 230 V AC.

    Page 11 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    12/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    1.8.1 TRIPPING RELAYS:

    All tripping relays shall be lockout type with hand reset contacts and shall be

    suitable to operate on the specific D.C Voltage. These relays shall have coi

    cut-off contacts and shall be provided with hand reset operation indicators.

    The tripping relays shall be non-drawout type.

    1.8.2 PROTECTIVE RELAYS

    All relays shall be back-connected draw out / semi-draw out type suitable for

    flush mounting. All relays shall be mounted in front of the panel and shall be

    as specified in details of the equipment.

    1.8.2.1 NUMERICAL RELAYS

    The numerical relays shall be fitted with RS485 rear port for seria

    communication to substation automation system. The relay shall contain allthe components needed for acquisition and evaluation of measured values,

    data transmission, display and input & evaluation of binary signals. Al

    Numerical relays including Motor Protection relays shall be provided with

    RS485 interface with Modbus / IEC-103 communication protocol.

    Cable Differential protection relay can be work on either Low Impedance or HighImpedance principle.

    Cable Differential protection relay for the cable run more than 500m should be

    capable of flush mounting and provided with the test switch for the necessary

    testing facility. The relay should be provided with the direct fiber opticcommunication. It should have 4-User configurable LEDs with minimum 4:DI and

    8:DO. The relay should also have front RS 232 communication and Disturbance

    recording facility with the recording facility upto 5records, with the maximumrecording time of 15s.

    1.8.3 FUSES / MCBS

    All control fuses shall be of HRC link type conforming to IS 2208. Rewireable

    fuses shall not be accepted. All fuses shall be readily accessible for

    replacement. Fuses shall have operation indicator, which will be visible without

    removal of fuses from the service from its carrier. Fuses shall generally be

    Page 12 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    13/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    mounted on the upper half of the panels. All fuses and links shall be provided

    with suitable labels.

    Instead of Fuses, suitable rating of MCBs can be provided.

    1.8.4 PUSH BUTTONS:

    Push buttons colours shall be as follows:

    Stop, Open, Emergency Red

    Start close Green

    Trip circuit Healthy check - Black

    1.8.5 INDICATING LAMPS:

    All indicating lamps on A.C. / D.C. supply shall be low power consumption

    indicating lamps and non-breakable translucent colored (as specified) coversThe lamp rating shall be 6.0 V and 0.75 Watt.

    1.8.6 CONTROL SWITCHES:

    All control switches shall be rotary back-connected types, having a cam

    operated contact mechanism. Preferably, phosphor bronze contacts shall be

    used on the control switches. Unless otherwise stated circuit breaker controlswitches shall be 3 positions spring return to neutral from both ON and OFF

    positions. They shall have pistol grip handle. Number of ways, locking system

    etc. shall be as per requirement and OWNERs approved relevant drawings.

    Two spare ways shall be provided on these switches.

    1.8.7 CABLE COMPARTMENT

    Provision shall be made for terminating 11 kV XLPE cables of suitable size.

    gland plate with cable support clamps shall be supplied along with the

    switchboards. Various cable sizes shall be firmed up during the drawing

    approval stage.

    1.9.0 INSPECTION & TESTING

    Fully assembled switchboard shall be subjected to inspection by owner and by

    an agency authorized by the owner at the manufacturers works. The

    Page 13 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    14/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    inspection call notice shall be given at least 3 (three) weeks before the date of

    inspection.

    1.9.1 Routine test shall be carried out at manufacturers works under his care and

    expense. All routine tests as per IS 13118 (1991) shall be carried out at the

    manufacturers works.

    1.9.2 Acceptance test shall be carried out as follows:

    i) A general visual check shall be carried out. This shall cover measurement

    of overall dimensions, locations, number and type of devices, termina

    boxes, location and connection of terminals etc.

    ii) Manual & electrical operation of circuit breaker shall be checked under

    the worst conditions of auxiliary supply voltage.

    iii) Dry insulation test with power frequency voltage shall be conducted for

    the main and auxiliary circuits shall be checked.

    iv) Insulation resistance of the main and auxiliary circuits shall be checked.

    v) Operation check shall be carried out for every control function as per the

    approved schematic diagrams by manually simulating fault conditions

    and operation of control switches/ relays etc.

    1.9.3 For equipment bought from other sub-suppliers certified test reports of test

    carried out at the manufacturers works shall be submitted. All routine test as

    specified in the relevant standards shall be conducted by the sub-suppliers at

    his works.

    1.9.4 For equipment bought from other sub-suppliers certified test reports of testcarried out at the manufacturers works shall be submitted. All routine tests as

    specified in the relevant standards shall be conducted by the sub-supplier at

    his works.

    1.9.5 Six sets of the inspection report shall be submitted to the owner for obtaining

    despatch clearance.

    1.10.0 AUDIO ANNUNCIATION

    a. Vendor shall include audio alarm by means of Hooter as required for

    maintenance of the system but not be limited to the following.

    Page 14 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    15/23

  • 7/28/2019 Draft 11KV Spec OIL

    16/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    1.12.0 PACKING & FORWARDING

    The switchboard supplied shall be transported to site with proper packing.

    They shall be wrapped with polythene sheets before placing in the crates

    card-board to prevent damage to the finish. Wooden platform at bottom

    should be suitable for handling. Proper care should be taken while packing to

    avoid ingress of moisture. Packing list shall be supplied along with the

    material.

    1.13.0 GUARANTEE

    The switchboard and other equipment supplied shall be guaranteed for trouble

    free operation for a period of 12 months from the date of commissioning or 18

    months from the date of supply whichever is earlier. Any defects discovered

    during this period shall be rectified by the supplier free of charge.

    1.14.0 SWITCH BOARD DETAILS:

    The HT Switchboard shall comprise of:

    SNo. HT SWBD Number of

    Panel

    1. 11 KV, 10 Panel Switchboard (31.5 kA for 3

    secs.) consisting of:-

    1) 2 Nos. INCOMERS 1200 Amps VCB with

    Directional relay & cable differentialProtection (AREVA MAKE MICOM P521) (CT suitablefor 10 MW Load)

    (2) 2 Nos. 1200 Amps VCB out going feeders with

    non directional relay ( MICOM P122) for ring

    system (CT suitable for 10 MW Load)

    (3) 630 amps for 500KVA transformer with non

    directional relay (AREVA MAKE MICOM P122)

    (4) 630 Amps - 2nos for Medical & D+107

    substation with non directional relay (AREVA MAKE

    MICOM P122)

    Ten (10)

    Page 16 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    17/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    (5) 1200Amps for Bus coupler with synchronizing

    relay (AREVA MAKE relay type SKD 11)

    (6) 1200Amps VCB -1No spare with with non

    directional relay (AREVA MAKE MICOM P122)

    (7) 630 Amps VCB -1no spare with non directional

    relay( AREVA MAKE MICOM 122)

    (8). 2 Nos. Bus Connected PT To be mounted at

    the top of outgoing panel.

    2. 11 KV, 5 Panel Switchboard (25 kA for 3 secs.)consisting of:-

    (1) 1 No. INCOMER 800 Amps VCB with Non-

    Directional relay (AREVA MAKE MICOM P127)

    (2) 630 amps for 1000 KVA transformer with nondirectional relay( AREVA MAKE MICOM P122)

    (3) 630 Amps - for overhead line with non

    directional relay (AREVA MAKE MICOM P122)

    (4) 630 Amps - spare with non directional relay

    ( AREVA MAKE MICOM P122)

    Five(05)

    Page 17 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    18/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    EQUIPMENT DETAILS Annexure-1

    Sl.

    No.

    Description of feeders Incomer Outgoing

    1. a. Vacuum circuit breaker complete with allaccessories as mentioned in thespecifications.

    1 1

    b. Single busbar arrangement Yes Yes

    c. Bolted Sheet Steel Enclosure Yes Yes

    4. RELAYS:

    i) Cable Differential protection relay

    type MICOM 521 of Areva Make of

    equivalent make of ABB/Siemens.

    ii) Over current , SC Earth fault, Voltageprotection relay type MICOM P127 of

    Areva make or equivalent model of

    ABB/Siemens (50, 51, 50N, 51N, 67,

    37, 46, 81, 27, 2, 59, 95)

    iii) Over current , SC Earth fault, Voltage

    protection relay type MICOM P122 ofAreva make or equivalent model of

    ABB/Siemens (50, 51, 50N, 51N, 37,

    46,49, 95, 50 BF)

    1 ( For Ten

    panel SWBD)

    1

    0

    0

    0

    1

    iv) Lock out relay type - VAJH13 Or

    equivalent ABB/Siemens make

    Operating volt : 110 V DC

    Note: The Buscoupler panel shall be

    provided with Areva make relay type

    SKD 11 for check synchronising.

    1 1

    5. CURRENT TRANSFORMER

    EPOXY RESIN CAST CTS WITH>STR 31.5 KA for 1 sec. For 10 panelSWBD

    3 3

    Page 18 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    19/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    Sl.

    No.

    Description of feeders Incomer Outgoing

    >STR- 25 KA for 1 sec for 5 panel SWBD.

    BURDEN 10 VA

    CLASS 1.0 (Metering ) &

    5 P10 (Protection)

    6. POTENTIAL TRANSFORMER

    EPOXY RESIN CAST 3 PHASE PT (DRAWOUT

    TYPE) WITH:

    BURDEN 50 VA / Phase

    CLASS 1 / 3P

    RATIO 11000/3 / 110/3 V

    1 0

    7. MEASURING INSTRUMENTSi) Digital Ammeter

    1 1

    ii) Digital Voltmeter 1 0

    iii) Multi Function meter 1 1

    6. Power pack with battery backup 30

    minutes

    1 0

    7. ACCESSORIES

    i) TNC switch 1 1

    ii) Emergency trip push button 1 1iii) Space heater with thermostat 230

    V, 80W1 1

    iv) Indicating lamps:

    a) RED

    b) GREEN

    c) AMBER

    d) WHITE

    e) BLUE

    1

    1

    1

    1

    1

    1

    1

    1

    1

    1

    v) Cable Termination : Suitable for the

    following size of 11kV, XLPE, Al.

    Page 19 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    20/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    Sl.

    No.

    Description of feeders Incomer Outgoing

    Conductor cables

    a) 2# 3 C X 240 mm2 1 1

    DATA SHEET ANNEXURE-2

    Page 20 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    21/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    1. System parameters

    i) Design Ambient temperature

    ii) Rated voltage

    iii) Rated frequency

    iv) Neutral system

    v) Fault level

    40C

    11KV + 10%

    50 Hz + 3 Hz

    Solidly grounded

    25/31.5 KA

    2. Control Supply

    i) Closing, tripping, indication,

    auxiliary relays.

    ii) Panel space heater

    iii) Meters

    iv) Spring charging motor

    110 V DC

    230 V AC

    110 V DC

    230 V AC

    3. Vacuum circuit Breakeri) Make

    ii) Type

    iii) Whether drawable

    iv) VCB mechanism

    v) Closing

    vi) Tripping

    vii) Breaking capacity

    viii) Short time ratingix) Basic insulation level

    x) Rated current

    xi) Operating duty

    xii) Rating of the spring charging motor

    SIEMENS/ AREVA /ABB

    HWX

    DRAWOUT TYPE

    Motor charged spring closing

    110 V DC

    110 V DC

    25 KA

    25 KA for 1 sec75 KVp

    1200A/630 A

    O - 3 min -CO-3 min-CO

    250 W, 230 V AC

    4. CURRENT TRANSFORMER EPOXY RESIN CAST CTS WITH

    >STR 31.5 KA for 1 sec. For

    10 panel SWBD

    >STR- 25 KA for 1 sec for 5panel SWBD.

    BURDEN 10 VA

    Page 21 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    22/23

    Document/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    reproduced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    CLASS 1.0 (Metering ) &

    5 P10 (Protection)

    5. POTENTIAL TRANSFORMER EPOXY RESIN CAST 3 PHASE PT

    (DRAWOUT TYPE) WITH:

    BURDEN 50 VA / Phase

    CLASS 1 / 3P

    RATIO 11000/3 / 110/3 V

    6. Main Horizontal Bus Bars

    i) Current rating

    ii) Temperature rise limit

    iii) Material of bus bar

    As per IEC:60694

    HDHC Electrolytic grade copper

    7. EARTH BUS

    i) Size

    ii) Material

    50mmx 6mm

    Copper

    8. Miscellaneuos

    i) Maximum panel dimensions

    Width

    Depth

    Height

    Sheet steel thickness

    Weight

    660 mm

    1950 mm w/o rear extension

    chamber

    2430 mm

    2.0 mm - Load bearing

    2.0 mm Non - load bearing

    650 Kg (approx)

    ii) Whether switch board dust & vermin

    proof.

    Shall be dust & vermin proof.

    iii) Switch board protection class IP 4X

    iv) Switch board auxiliary wiring details Wiring shall be done with multi

    stranded copper conductor size2.5 sq. mm., PVC insulated, 650

    Page 22 of 23

  • 7/28/2019 Draft 11KV Spec OIL

    23/23

    ment/Drawingandthedesign

    itcoversarepropertyofOILINDIALIMITED.

    Theyaremerelyloane

    dandontheborrowersexpressagr

    eementthattheywillnotbe

    duced,copied,

    loaned,exhibited

    ,notusedexceptinthelimitedwayandprivateusepermittedbyanywrittenconsentgivenbythelendertotheborrower.

    Draft Specification

    V grade cable.

    v) Method of cable earthing Not Required

    vi) Location of relay Flush mounted at the front.

    Page 23 of 23