무정전전원공급장치

(Uninterruptible Power System)

사 양 서

iUPS-33T 50kVA

Ver.090407

Page 2: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

2/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

목 차

가. 적 용 범 위 .............................................................................................................................. 3

나. 적 용 규 격 .............................................................................................................................. 3

다. 환 경 조 건 .............................................................................................................................. 3

라. 시스템 주요 구성 .................................................................................................................... 3

마. 동작 개요 .................................................................................................................................. 31. 정상 시 운전 .................................................................................................................................................... 3

2. 정전 시 운전 .................................................................................................................................................... 3

3. 정전 회복 시 운전 .......................................................................................................................................... 4

4. 동기절체(바이패스 운전) ................................................................................................................................ 4

5. 유지보수용 수동 바이패스 운전 ................................................................................................................... 4

6. 병렬운전(옵션) ................................................................................................................................................. 4

바. 장비의 구성 및 사양에 대한 상세설명 .............................................................................. 41. 개요 .................................................................................................................................................................... 4

2. 주요 특징 .......................................................................................................................................................... 5

3. 구성 .................................................................................................................................................................... 6

4. 디스플레이 ........................................................................................................................................................ 8

5. 순변환부 및 충전장치(Rectifier/Charger) ............................................................................................... 10

6. 순변환부 제어 (Super Charger) ................................................................................................................ 10

7. 역변환부(INVERTER) ..................................................................................................................................... 10

8. 동기 절체부 .................................................................................................................................................... 10

9. 제어회로부 ...................................................................................................................................................... 10

10. 보호장치 ...................................................................................................................................................... 11

11. 원격운용 및 상태 감시 ............................................................................................................................ 11

사. 전기적 특성 ............................................................................................................................ 11

아. 검 사 항 목 ...................................................................................................................... 13

자. 기 타 .................................................................................................................................... 13

Page 3: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

3/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

가. 적 용 범 위

본 장비는 상용 전원 또는 예비 전원의 전압, 주파수 변동 및 정전 시 계속 안정된 교류 전

원을 정해진 정전 보상 시간 동안 지속적으로 공급하는 정지형 무 정전, 정 전압 정 주파수

(C.V.C.F) 전원 장치에 대하여 적용합니다.

나. 적 용 규 격

• K.S (Korean industrial Standards)

• ANSI (American National Standards Ins)

• IEEE (Institute of Electrical and Electronic Engineers)

• Manufacturer’s Standard

• ISO 9001 KS A 9001

다. 환 경 조 건

1. 주위 온도 : 0 - 40˚C

2. 상대 습도 : 95% 이하

3. 설치 장소 : 옥 내

4. 표 고 : 1000m 이하

라. 시스템 주요 구성

본 장치는 다음과 같은 주요 부분으로 구성되어 있습니다.

• 정류부 및 충전부

• 인버터 부

• 동기 절체 스위치부

• 제어부

• 디지탈 디스플레이 운영반

마. 동작 개요

1. 정상 시 운전

UPS 는 정상 작동 중에 과도전류가 없는 정밀 제어된 전력을 전산 부하 장비에 공급합

니다. 이때 메인 전원이 입력 컨버터에 공급되며 입력컨버터는 제어된 직류전력을 공급

하여 인버터를 동작시키고 동시에 배터리의 완전 충전상태를 유지시킵니다.

인버터는 이 직류전력을 교류전력으로 제어, 변환하여 부하에 공급합니다.

2. 정전 시 운전

Page 4: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

4/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

메인 전원공급의 장애시 인버터 입력 전력은 자동적으로 직접 연결된 배터리에 의하여

공급됩니다. 메인 전원이 회복되거나 대기상태에 있던 발전기 (GENERATOR SET)의 공급

이 준비되면 자동적으로 정류기에서 배터리 재충전을 위한 인버터 입력전력을 공급하게

되며. 만약 입력이 회복되지 않을 경우, 배터리의 방전한계에 다다르면 자동적으로 UPS

는 정지(셧다운) 절차를 수행합니다.

3. 정전 회복 시 운전

발전기전원 또는 상용전원이 다시 공급되면 충전부는 자동으로 기동 되어 역 변환부에

전력을 공급하는 동시에 자동으로 충전시킵니다.

4. 동기절체(바이패스 운전)

스태틱 인버터의 장애시, 무순단 스태틱 절체 스위치가 자동으로 활성화되어 장애가 생

긴 인버터를 차단시킴과 동시에 시스템 부하에 연속적으로 급전합니다. 시스템 과부하

나 부하에 대한 불규칙(혹은 불량의) 출력이 나타나는 경우에도 역시 자동절체 모드로

작동하게 되며, 이 경우 장애가 해결되면 시스템은 자동적으로 원래의 정상운전(온라인

모드)으로 복귀합니다.

5. 유지보수용 수동 바이패스 운전

UPS 시스템 시험시 부하로부터 격리하거나 유지보수로 인하여 부하에서 제거하여야 할

때에, 유지보수 바이패스는 부하를 인버터에서 메인으로 (혹은 반대방향으로) 자유로이

전환합니다.

6. 병렬운전(옵션)

본 시스템은 2 대 이상 동일 용량의 출력을 COMMON 하여 부하측에 전원을 공급합니

다. 병렬 연결되는 UPS는 고속 통신 버스로 연결되어 부하를 균등하게 분담합니다.

어느 한 장비의 고장시 잔여 UPS 가 제어를 인계받아 출력의 끊어짐 없이 전원을 공급

합니다.

바. 장비의 구성 및 사양에 대한 상세설명

1. 개요

최근에 들어 첨단산업의 핵심인 전자산업의 급속한 발달로 인하여 각종 반도체소자들

이 더욱 소형화, 정밀화 됨으로써 이에 따른 전원의 불안정 (전압 및 주파수 변동, 순시

전압강화, SURGE, 순간정전 등 )으로 인한 부하기기의 오 동작, 중요한 DATA 의 유실

및 파손 등 시간 및 경제적으로 막대한 손실을 초래하게 되었습니다.

Page 5: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

5/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

이에 iUPS 는 최신 전력전자 기술인 IGBT(Insulated Gate Bipolar, Transistor.)에 의한 순

시전압 제어방식인 정현파 펄스 폭 변조 (SINE WAVE PULSE WIDTH MODULATION)방

식으로 이러한 전원의 불안정을 말끔히 해소하여 어떠한 조건에서도 부하기기에 양질

의 전원을 공급하며 사용이 용이하도록 설계 제작된 무정전 전원 장치입니다.

본 장비는 C.V.C.F (Constant Voltage Constant Frequency)로 입출력의 전압 주파수에 관

계없이 출력은 전압은 1% 이내 주파수는 0.5% 이내로 안정화되는 VFI(Voltage &

Frequency Independent)UPS로 입력 조건에 영향을 받지 않고 재 출력하는 UPS입니다.

2. 주요 특징

1. IGBT 는 높은 주파수에서 대 전력을 SWITCHING 할 수 있는, 견고하고 사용이 용이

하며, 고효율, 저소음, 소형, 경량화를 실현하는데 원동력이 된 최신 전력소자로

MosFET 의 고입력 IMPEDANCE, 고속 SWITCHING 성능과 Bipolar Transistor 의 고

전도 특성 (Low Saturation Voltage), 고전압/대전류 처리능력을 조합하였으며 전압

신호에 의해 ON/OFF 상태를 제어하기 때문에 Drive 회로가 간단해지고 소모전력

이 적습니다.

2. 반도체소자는 모듈화로 구성하여 유지보수가 용이하며 또한 반도체소자의 소손을

최소화 할 수 있습니다.

3. 모듈에 온도센서 부착 모듈의 온도 감지에 의한 팬을 컨트롤하여 팬의 수명과 소음

을 줄였습니다.

4. 대형 전면 LCD 표시창과 상태 표시 LED 가 있어 장비의 이상여부와 전원에 대한

사항을 쉽게 확인 할 수 있습니다.

5. 이벤트 기록으로 유지보수 편리

6. 내부 회로의 보호를 위한 고속 FUSE를 장착하여 반도체 소자를 보호하였습니다.

7. 부하량에 따라 팬 속도가 조절됨으로 팬 수명이 증가되며 노이즈 소음이 적습니다.

8. 에너지 절약을 위한 ECO 모드를 지원하여 효율을 97%까지 올릴 수 있습니다.

9. 고속 DSP 기술과, 병렬기술을 지원하여 신뢰성이 증대됩니다.

Page 6: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

6/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

10. 높은 입력 역률로 필요 요구되는 입력 전력이 작아 비용이 절감됩니다.

11. EMC(전자파) 규격을 따른 설계

3. 구성

3.1 입/출력 연결 단자

본 입출력 차단기는 터미널단자로 이루어져 있으며 장비 전면 하부에 위치해 있습니다.

입력 연결과 출력 케이블은 그림과 같이 배치되어 있으며, 입력 3 상 4 선식 과 출력 3 상

4선식, 배터리를 연결 할 수 있도록 UPS 전면 하단 아래에 설치됩니다.

3.1.1 iUPS 33T 20/30Kva 내부 차단기 및 단자대 구성

단자대블록

Battery극성체크보드

고정기구

}}} BATTERY-+

GNDINPUTLCAL BLN

OUTPUT GNDLCAL BLN

N FB 4(OUTPUT)

2:1

SIGNAL RS232/485

BYPASS

UPS

Maintenance Switch

1、This switch is conven ience for maintena nce,and shall be on "UPS"status when UPSworks normal.2、This switch is operated only by profess ionaltechnician, should be operated as following:

(1)、UPS → Maintenance:①、Press "OFF" key in the front-panel of UPS.②、Turn the maintenance switch to the "BYPASS".③、Turn off all "NFB" of theUPS.

(2)、Maintenance → UPS:①、Turn on all "NFB" of the UPS.②、Turn the maintenance switch to the "UPS".③、Press "ON" key in the front-panel of UPS.

Wa rni ng!

1、This switch is convenience for maintenance,and shall be on "UPS"status when UPSworks normal.2、This switch is operated only by professionaltechnician, should be operated as fo llowing :

(1)、UPS→ Maintenance:①、Press "OFF"key in the front-panel of UPS.②、Turn the maintenance switch to the"BYPASS".③、Turn off all"NFB"of theUPS.

(2)、Maintenance → UPS:①、Turn onall "NFB" of theUPS.②、Turn the maintenance switch to the "UPS".③、Press "ON"key in the front-panel of UPS.

Maintenance SwitchWarning!

커버제거

비상전원스위치(병렬모드에선사용안함)

RS232/RS485통신포트

시그널 통신포트

병렬 통신포트

Bypass차단기

Battery차단기

AC 출력 DC 입력 접지 AC 입력 접지

주 전원차단기

출력차단기

(POW ER)

N FB 3 N FB 1(BAT.)(BYPASS)

N FB 2

3.1.2 iUPS 33T 40/50Kva 내부 차단기 및 단자대 구성

Page 7: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

7/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

}}} INPUTOUTPUT BATTERY-+

GNDN LA LB LCLCAL BLN

!

2:1

BYPASS

UPS

RS232/485SIGNAL

1、This switch is convenience for maintenance,and shall be on "UPS"status when UPSworks normal.2、This switch is operated only by professionaltechnician, should be operated as following:

(1)、UPS → Maintenance:①、Press "OFF" key in the front-panel of UPS.②、Turn the maintenance switch to the"BYPASS".③、Turn off all "NFB" of theUPS.

(2)、Maintenance → UPS:①、Turn on all "NFB" of theUPS.②、Turn the maintenance switch to the"UPS".③、Press "ON" key in the front-panel of UPS.

Warning!

Maintenance Switch

1、This switch is convenience for maintenance,and shall be on "UPS"status when UPSworks normal.2、This switch is operated only by professionaltechnician, should be operated as following:

(1)、UPS → Maintenance:①、Press "OFF" key in the front-panelof UPS.②、Turn themaintenanceswitch to the"BYPASS".③、Turnoff all "NFB" of theUPS.

(2)、Maintenance → UPS:①、Turnonall "NFB" of theUPS.②、Turn themaintenanceswitch to the "UPS".③、Press "ON"key in the front-panelof UPS.

Warning!

커버 제거

RS232/RS485통신포트

시그널 통신포트

병렬통신포트

Bypass차단기

Battery차단기

Battery극성 체크보드

접 지 DC 입력AC 입력AC 출력

단자대 블록

수동 바이패스스위치(병렬모드시사용안함)

주전원차단기

출력차단기

(OUTPUT)

N FB 4(POWER)

N FB 3

(BYPA SS)

N FB 2 N FB 1(BAT.)

3.2 입/출력 차단기 선정

용량(kVA) 입력 전압(표준) 최대전류(A) 차단용량(A)

20 240V/415V 3상 4선식 50 60

30 240V/415V 3상 4선식 73 100

40 240V/415V 3상 4선식 98 125

50 240V/415V 3상 4선식 122 150

용량(kVA) 출력 전압(표준) 최대전류(A) 차단용량(A)

20 240V/415V 3상 4선식 24 32

30 240V/415V 3상 4선식 36 60

40 240V/415V 3상 4선식 48 60

50 240V/415V 3상 4선식 63 100

* 주) 본 전류용량은 돌입전류 제외

3.3 입/출력 케이블 선정

Page 8: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

8/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

용량(kVA) 입력 전압 Line 케이블

(mm2)

중성선 케이블

(mm2)

접지선 케이블

(mm2)

20 240V/415V 3상 4선식 16 16 4

30 240V/415V 3상 4선식 16 16 4

40 240V/415V 3상 4선식 25 26 10

50 240V/415V 3상 4선식 35 35 10

용량(kVA) 출력 전압 Line 케이블

(mm2)

중성선 케이블

(mm2)

접지선 케이블

(mm2)

20 240V/415V 3상 4선식 10 10 4

30 240V/415V 3상 4선식 16 16 4

40 240V/415V 3상 4선식 25 25 10

50 240V/415V 3상 4선식 35 35 10

3.4 배터리 케이블 선정(배터리 전압 300-410V상에서)

용량(kVA) 최대전류(A) 케이블(mm2)

20 60 25

30 90 35

40 120 50

50 150 50

3.5 입/출력 단자대 구성

N LA LB LCGNDOUTPUT

N LA LB LCINPUT GND

+ -BATTERY

출력선(LA)

출력선(LB)

출력선(LC)

접지

입력 중선선(N)

출력 중선선(N)

출력선(LA)

출력선(LB)

입력 선(LC)

접지

DC 입력 +

DC 입력 -

4. 디스플레이

Page 9: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

9/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

4.1 LCD 표시부

본 장치는 푸시버튼을 사용하고 백라이트를 채용한 알파-뉴머릭 LCD(Liquid Crystal

Display)가 제공됩니다.

PHASE

BYPASS

INVERTER

OVERLOAD

BAT.LOW

FAULT

RECTIFIER

WELCOME TO USEMODEL :iUPS3340T

INPUT :380V/60Hz

OUTPUT:380V/60Hz>>>>>>>>>>==========

OFFON

4.1.1 UPS 시스템의 메인 컨트롤 패널은 LCD 백라이트 디스플레이를 통해 다음의 측

정값을 표시합니다.

메인 입력 전압/주파수

UPS 출력 전압/주파수/부하 사용량(%)

배터리에 충전전압

4.2 조작부

UPS 시스템의 메인 컨트롤 버튼은 다음을 표시하고 제어할 수 있습니다.

ON/OFF 버튼 : INVERTER ON/OFF 제어

SELECT : 화면 상/화이동

파라미터 아이템 설정 : 동일 화면에서 여러가지 아이템 설정

설정확인 버튼 : 파라미터 설정

화면전환 버튼 : 화면 되로 넘김, 백라이트 OFF시 다시킴

4.3 LED 표시부

UPS 는 LED 로 장비의 동작 상태 및 이상시 알라음과 함께 FAULT 에 LED 가 점등되

어 사용자에게 장비의 이상 여부를 알려줍니다.

PHASE :경보/ UPS 메인 입력/바이패스 비정상시 LED ON

RECTIFIER : 동작상태/ 정류부 동작상시 LED ON

INVERTER : 동작상태/ 인버터 동작시 LED ON

Page 10: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

10/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

BYPASS : 경보/ UPS가 현재 바이패스 상태시 LED ON

BAT. LOW : 경보/ 배터리 저전압 시 LED ON / 평상시 OFF

FAULT : 경보/ 정류부, 인버터 또는 바이패스 비정상시 LED ON

5. 순변환부 및 충전장치(Rectifier/Charger)

본 장치는 Clean input Rectifier 정류부로, 방열판, 콘덴서, 조립용 각종부품 등으로 구

성하며 단상 전파정류 회로를 이용한 정류부로서 교류를 직류로 변환시켜 역 변환부에

공급함과 동시에 충전 장치는 축전지를 최적의 조건으로 충전시키는 기능으로 제작되

었습니다.

6. 순변환부 제어 (Super Charger)

Super Charger 는 축전지의 과충전을 방지하고 90%까지의 급속충전(Equalizing) 및 일

정부분 이상 충전 시 배터리의 오버 충전 및 과 방전을 위하여 LIMIT

CHAGING(Floating)을 하는 방식으로 배터리의 수명을 타사보다 30% 이상 연장 시키는

방식입니다..

7. 역변환부(INVERTER)

본 장치는 IGBT (Insulated Gate Bipolar Transistor) 모듈, 방열판, 각종 조립용 부품으로

구성된 고주파 스위칭 방식으로 정류부로부터 정류된 직류 전원을 IGBT 모듈에 공급하

고 검출 장치로부터 정현파를 검출하여 정현파 펄스폭변조 (SINE PWN)방식의

INVERTER 로서 직류 전력을 공급하며 본 장치를 보호하기 위하여 직류 입력측에 반도

체 보호용 고속 퓨즈를 구비하여 제작하였습니다.

8. 동기 절체부

본 장치는 INVERTER 고장 및 과부하 시를 대비하여 BY-PASS (상용 전원) 및 INVERTER

측에 각각 설치하여 연동 동작되도록 하는 구조로서 위상차에 의해 발생되는 돌입 전

류를 방지하기 위하여 순수한 반도체 소자로 구성 되며 과부하로 인하여 BYPASS LINE

으로 절체된 경우 과부하 상태가 해제되고 INVERTER 가 정상 동작하게 되면 INVERTER

로 자동 재 절체 되도록 함으로서 부하는 가급적 양질의 안정된 INVERTER 전원을 공

급 받도록 제작되어 있습니다.

9. 제어회로부

제어 회로부는 논리회로를 구동하기 위한 보조 전원기 및 역 변환부의 제어부와 상태

표시 경보부, 동기절체 제어부 등으로 구성되며 POWER SUPPLY 는 축전지에서 직접

공급받아 고성능 스위칭 방식에 의한 DC/DC CONVERTER 방식을 사용함으로써 절체,

Page 11: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

11/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

또는 가동시 오 동작이 배제되고 본 장치 내부에서 발생되는 과도전압 및 불시의 순간

정전 시에도 제어 회로가 안정되게 동작되도록 제작되었습니다.

10. 보호장치

본 장치에는 입력측의 저전압, 과전류, 과전압, 써지등에 대한 보호장치를 구비하며 출

력측 단락, 동기절체 스위치 작동 시에 나타나는 전압 및 전류와 써지를 흡수할 수 있

는 기능을 구비합니다.

11. 원격운용 및 상태 감시

본 장치는 RS232C DB-9 가 기본 제공되며 UPS 에서 1:1 감시가 용이합니다. 포함되어

있는 모니터링 소프트웨어는 장비의 각종 정보를 실시간으로 체크 및 확인이 가능하며

이벤트 및 알람 내역이 저장되어 이를 확인 및 프린트 할 수 있으며 알람 발생시 담당

자에게 이메일 통보기능과 정전시 컴퓨터 및 UPS 자동 셧다운 기능을 가집니다.

1) SNMP 카드(선택사양) - 국제 표준 UPS MIB 를 사용하는 SNMP (simple network

management protocol) 카드를 사용하여 UPS 를 TCP/IP 네트워크에 연결할 수 있습

니다. SNMP 어댑터는 플러그인 카드, 외부 SNMP 박스, 프록시 에이전트 PC 등의

형태로 제공될 수 있습니다.

2) UPS 데이터 보호 소프트웨어 - Windows95/98/NT, UNIX, Novell, OS/2 등 주요 운영

체계와 호환되는 UPS 데이터 보호 소프트웨어를 사용할 수 있습니다.

사. 전기적 특성

Page 12: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

12/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

구 분 특 성

모 델 iUPS-33T

용 량(kVA) 50

냉 각 방 식 강 제 풍 냉 식

사 용 정 격 100 % 연속 사용

정류부

및충전

제어방식 3상 위상전파

사용소자 SCR

인버

터부

제어식 고주파 (60 Khz ) 순시 제어 PWM 방식

사용자 IGBT (Insulated gate Bipolar Transistor)

ST/SW절체방식 무순단 동기 절체

상 수 3상 4선식

정 격 전 압 380/220V ±20%

주 파 수 60Hz(54-66)

배터리 종류 무보수 무누액 장수명(10년) 랙마운트 형

배터리 수량 29Block*2set

설치 유형 Rack mount*3

배터리 정격전압 348VDC

충전 전류 20A

상 수 3상 4선식

정 격 전 압 380/220V

전압안정도 ±2 % 이내

정격주파수 60HZ ±0.2%

과도전압변동 ± 5 % 이내

과도응답속도 16 Ms 이내 (± 2 % 이내로 복귀 기준)

출력 전압 조정 220V,230V

파 형 왜 율 THD 3 % 이하 (LINER 부하 100% 기준)

과 부하 내량 125 %이하 15분간/ 150% 1분간

역 율 0.8Lag. 이상

소 음 65 dBA 이하(벽으로부터 1m)

종합효율 90 % 이상

동기 동기절체시간 4 ms 이내

Page 13: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_50kVA.pdf · 2012-09-23 · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/13 ct-u-iups33-kjs

무정전전원공급장치 사양서

(iUPS33T Series)

2012-09-24

13/13

CT-U-IUPS33-KJS IUPS33T_50KVA_SP

절체 절 체 조 건

인버터 비 정상시

직류 저 전압시

출력 과 부하시

수동 절체시

도 장 5Y 7/1

통신포트 Dry contact,RS232/495포트, SNMP 아답터(옵션)

제품 사이즈(W×D×H) 500×800×1180

제품 중량(kg) 400

아. 검 사 항 목

1. 입력 전압 변동 시험

2. 출력 전압 안정도 시험

3. 출력 파형 왜율(Distortion) 시험

4. 상태 표시 및 경보 표시 기능 시험

5. BY-PASS 절환 기능 시험

6. 출력 주파수 안정도 시험

7. 과도 전압 특성 시험

8. 부하 시험 및 효율 측정

10. 소음 측정

자. 기 타

1. 당사는 제작 승인 사양서에 의거하여 공급 제작한 제품에 대하여 기기의 시운전으로부

터 12 개월간 하자 보증을 하며 제작 부실로 인한 기간 내에 발생하는 모든 하자에 대

해 무상으로 신속히 보수 할 것을 약속합니다..

2. 본 기기에는 제작 회사명, 제작 년 월 일, 제작 번호, 전기적 특성이 기입 된 명판을

부착합니다.