무정전전원공급장치

(Uninterruptible Power System)

사 양 서

iUPS33T 40 kVA

Ver.090407

Page 2: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

2/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

목 차

가. 적 용 범 위 .............................................................................................................................. 3

나. 적 용 규 격 .............................................................................................................................. 3

다. 환 경 조 건 .............................................................................................................................. 3

라. 시스템 주요 구성 .................................................................................................................... 3

마. 동작 개요 .................................................................................................................................. 31. 정상 시 운전 .................................................................................................................................................... 3

2. 정전 시 운전 .................................................................................................................................................... 4

3. 정전 회복 시 운전 .......................................................................................................................................... 4

4. 동기절체(바이패스 운전) ................................................................................................................................ 4

5. 유지보수용 수동 바이패스 운전 ................................................................................................................... 4

6. 병렬운전(옵션) ................................................................................................................................................. 4

바. 장비의 구성 및 사양에 대한 상세설명 .............................................................................. 41. 개요 .................................................................................................................................................................... 4

2. 주요 특징 .......................................................................................................................................................... 5

3. 구성 .................................................................................................................................................................... 6

4. 디스플레이 ........................................................................................................................................................ 7

5. 순변환부 및 충전장치(Rectifier/Charger) ................................................................................................. 9

6. 순변환부 제어 (Super Charger) .................................................................................................................. 9

7. 역변환부(INVERTER) ....................................................................................................................................... 9

8. 동기 절체부 ...................................................................................................................................................... 9

9. 제어회로부 ........................................................................................................................................................ 9

10. 보호장치 ...................................................................................................................................................... 10

11. 원격운용 및 상태 감시 ............................................................................................................................ 10

사. 전기적 특성 ............................................................................................................................ 10

아. 검 사 항 목 ...................................................................................................................... 11

자. 기 타 .................................................................................................................................... 12

차. 도 면 .................................................................................................................................... 13

Page 3: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

3/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

가. 적 용 범 위

본 장비는 상용 전원 또는 예비 전원의 전압, 주파수 변동 및 정전 시 계속 안정된 교류 전

원을 정해진 정전 보상 시간 동안 지속적으로 공급하는 정지형 무 정전, 정 전압 정 주파수

(C.V.C.F) 전원 장치에 대하여 적용합니다.

나. 적 용 규 격

• K.S (Korean industrial Standards)

• ANSI (American National Standards Ins)

• IEEE (Institute of Electrical and Electronic Engineers)

• Manufacturer’s Standard

• ISO 9001 KS A 9001

다. 환 경 조 건

1. 동작 온도 : 0 ~ 40˚C

2. 보관온도 : -15˚C ~ 50˚C

3. 상대 습도 : 95% 이하

4. 설치 장소 : 옥 내

5. 표 고 : 1000m 이하

라. 시스템 주요 구성

본 장치는 다음과 같은 주요 부분으로 구성되어 있습니다.

• 정류부 및 충전부

• 인버터 부

• 동기 절체 스위치부

• 제어부

• 디지탈 디스플레이 운영반

마. 동작 개요

1. 정상 시 운전

UPS 는 정상 작동 중에 과도전류가 없는 정밀 제어된 전력을 전산 부하 장비에 공급합

니다. 이때 메인 전원이 입력 컨버터에 공급되며 입력컨버터는 제어된 직류전력을 공급

하여 인버터를 동작시키고 동시에 배터리의 완전 충전상태를 유지시킵니다.

인버터는 이 직류전력을 교류전력으로 제어, 변환하여 부하에 공급합니다.

Page 4: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

4/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

2. 정전 시 운전

메인 전원공급의 장애시 인버터 입력 전력은 자동적으로 직접 연결된 배터리에 의하여

공급됩니다. 메인 전원이 회복되거나 대기상태에 있던 발전기 (GENERATOR SET)의 공급

이 준비되면 자동적으로 정류기에서 배터리 재충전을 위한 인버터 입력전력을 공급하게

되며. 만약 입력이 회복되지 않을 경우, 배터리의 방전한계에 다다르면 자동적으로 UPS

는 정지(셧다운) 절차를 수행합니다.

3. 정전 회복 시 운전

발전기전원 또는 상용전원이 다시 공급되면 충전부는 자동으로 기동 되어 역 변환부에

전력을 공급하는 동시에 자동으로 충전시킵니다.

4. 동기절체(바이패스 운전)

스태틱 인버터의 장애시, 무순단 스태틱 절체 스위치가 자동으로 활성화되어 장애가 생

긴 인버터를 차단시킴과 동시에 시스템 부하에 연속적으로 급전합니다. 시스템 과부하

나 부하에 대한 불규칙(혹은 불량의) 출력이 나타나는 경우에도 역시 자동절체 모드로

작동하게 되며, 이 경우 장애가 해결되면 시스템은 자동적으로 원래의 정상운전(온라인

모드)으로 복귀합니다.

5. 유지보수용 수동 바이패스 운전

UPS 시스템 시험시 부하로부터 격리하거나 유지보수로 인하여 부하에서 제거하여야 할

때에, 유지보수 바이패스는 부하를 인버터에서 메인으로 (혹은 반대방향으로) 자유로이

전환합니다.

6. 병렬운전(옵션)

본 시스템은 2 대 이상 동일 용량의 출력을 COMMON 하여 부하측에 전원을 공급합니

다. 병렬 연결되는 UPS는 고속 통신 버스로 연결되어 부하를 균등하게 분담합니다.

어느 한 장비의 고장시 잔여 UPS 가 제어를 인계받아 출력의 끊어짐 없이 전원을 공급

합니다.

바. 장비의 구성 및 사양에 대한 상세설명

1. 개요

최근에 들어 첨단산업의 핵심인 전자산업의 급속한 발달로 인하여 각종 반도체소자들

이 더욱 소형화, 정밀화 됨으로써 이에 따른 전원의 불안정 (전압 및 주파수 변동, 순시

전압강화, SURGE, 순간정전 등 )으로 인한 부하기기의 오 동작, 중요한 DATA 의 유실

Page 5: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

5/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

및 파손 등 시간 및 경제적으로 막대한 손실을 초래하게 되었습니다.

이에 iUPS 는 최신 전력전자 기술인 IGBT(Insulated Gate Bipolar, Transistor.)에 의한 순

시전압 제어방식인 정현파 펄스 폭 변조 (SINE WAVE PULSE WIDTH MODULATION)방

식으로 이러한 전원의 불안정을 말끔히 해소하여 어떠한 조건에서도 부하기기에 양질

의 전원을 공급하며 사용이 용이하도록 설계 제작된 무정전 전원 장치입니다.

본 장비는 C.V.C.F (Constant Voltage Constant Frequency)로 입출력의 전압 주파수에 관

계없이 출력은 전압은 1% 이내 주파수는 0.5% 이내로 안정화되는 VFI(Voltage &

Frequency Independent)UPS로 입력 조건에 영향을 받지 않고 재 출력하는 UPS입니다.

2. 주요 특징

1. IGBT 는 높은 주파수에서 대 전력을 SWITCHING 할 수 있는, 견고하고 사용이 용이

하며, 고효율, 저소음, 소형, 경량화를 실현하는데 원동력이 된 최신 전력소자로

MosFET 의 고입력 IMPEDANCE, 고속 SWITCHING 성능과 Bipolar Transistor 의 고

전도 특성 (Low Saturation Voltage), 고전압/대전류 처리능력을 조합하였으며 전압

신호에 의해 ON/OFF 상태를 제어하기 때문에 Drive 회로가 간단해지고 소모전력

이 적습니다.

2. 반도체소자는 모듈화로 구성하여 유지보수가 용이하며 또한 반도체소자의 소손을

최소화 할 수 있습니다.

3. 모듈에 온도센서 부착 모듈의 온도 감지에 의한 팬을 컨트롤하여 팬의 수명과 소음

을 줄였습니다.

4. 대형 전면 LCD 표시창과 상태 표시 LED 가 있어 장비의 이상여부와 전원에 대한

사항을 쉽게 확인 할 수 있습니다.

5. 이벤트 기록으로 유지보수 편리

6. 내부 회로의 보호를 위한 고속 FUSE를 장착하여 반도체 소자를 보호하였습니다.

7. 부하량에 따라 팬 속도가 조절됨으로 팬 수명이 증가되며 노이즈 소음이 적습니다.

8. 에너지 절약을 위한 ECO 모드를 지원하여 효율을 97%까지 올릴 수 있습니다.

9. 고속 DSP 기술과, 병렬기술을 지원하여 신뢰성이 증대됩니다.

Page 6: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

6/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

10. 높은 입력 역률로 필요 요구되는 입력 전력이 작아 비용이 절감됩니다.

11. EMC(전자파) 규격을 따른 설계

3. 구성

3.1 입/출력 연결 단자

본 입출력 차단기는 터미널단자로 이루어져 있으며 장비 전면 하부에 위치해 있습니다.

입력 연결과 출력 케이블은 그림과 같이 배치되어 있으며, 입력 3 상 4 선식 과 출력 3 상

4선식, 배터리를 연결 할 수 있도록 UPS 전면 하단 아래에 설치됩니다.

3.1.1 iUPS 33T 40Kva 내부 차단기 및 단자대 구성

}}} INPUTOUTPUT BATTERY-+

GNDN LA LB LCLCAL BLN

!

2:1

BYPASS

UPS

RS232/485SIGNAL

1、This switch is convenience for maintenance,and shall be on "UPS"status when UPSworks normal.2、This switch is operated only by professionaltechnician, should be operated as following:

(1)、UPS → Maintenance:①、Press "OFF" key in the front-panel of UPS.②、Turn the maintenance switch to the"BYPASS".③、Turn off all "NFB" of theUPS.

(2)、Maintenance → UPS:①、Turn on all "NFB" of theUPS.②、Turn the maintenance switch to the"UPS".③、Press "ON" key in the front-panel of UPS.

Warning!

Maintenance Switch

1、This switch is convenience for maintenance,and shall be on "UPS"status when UPSworks normal.2、This switch is operated only by professionaltechnician, should be operated as following:

(1)、UPS → Maintenance:①、Press "OFF" key in the front-panelof UPS.②、Turn themaintenanceswitch to the"BYPASS".③、Turnoff all "NFB" of theUPS.

(2)、Maintenance → UPS:①、Turnonall "NFB" of theUPS.②、Turn themaintenanceswitch to the "UPS".③、Press "ON"key in the front-panelof UPS.

Warning!

커버 제거

RS232/RS485통신포트

시그널 통신포트

병렬통신포트

Bypass차단기

Battery차단기

Battery극성 체크보드

접 지 DC 입력AC 입력AC 출력

단자대 블록

수동 바이패스스위치(병렬모드시사용안함)

주전원차단기

출력차단기

(OUTPUT)

N FB 4(POWER)

N FB 3

(BYPA SS)

N FB 2 N FB 1(BAT.)

3.2 입/출력 차단기 선정

Page 7: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

7/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

용량(kVA) 입력 전압(표준) 최대전류(A) 차단용량(A)

40 240V/415V 3상 4선식 98 125

용량(kVA) 출력 전압(표준) 최대전류(A) 차단용량(A)

40 240V/415V 3상 4선식 48 60

* 주) 본 전류용량은 돌입전류 제외

3.3 입/출력 케이블 선정

용량(kVA) 입력 전압 Line 케이블

(mm2)

중성선 케이블

(mm2)

접지선 케이블

(mm2)

40 240V/415V 3상 4선식 25 26 10

용량(kVA) 출력 전압 Line 케이블

(mm2)

중성선 케이블

(mm2)

접지선 케이블

(mm2)

40 240V/415V 3상 4선식 25 25 10

3.4 배터리 케이블 선정(배터리 전압 300-410V상에서)

용량(kVA) 최대전류(A) 케이블(mm2)

40 120 50

3.5 입/출력 단자대 구성

N LA LB LCGNDOUTPUT

N LA LB LCINPUT GND

+ -BATTERY

출력선(LA)

출력선(LB)

출력선(LC)

접지

입력 중선선(N)

출력 중선선(N)

출력선(LA)

출력선(LB)

입력 선(LC)

접지

DC 입력 +

DC 입력 -

4. 디스플레이

4.1 LCD 표시부

본 장치는 푸시버튼을 사용하고 백라이트를 채용한 알파-뉴머릭 LCD(Liquid Crystal

Display)가 제공됩니다.

Page 8: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

8/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

PHASE

BYPASS

INVERTER

OVERLOAD

BAT.LOW

FAULT

RECTIFIER

WELCOME TO USEMODEL :iUPS3340T

INPUT :380V/60Hz

OUTPUT:380V/60Hz>>>>>>>>>>==========

OFFON

4.1.1 UPS 시스템의 메인 컨트롤 패널은 LCD 백라이트 디스플레이를 통해 다음의 측

정값을 표시합니다.

메인 입력 전압/주파수

UPS 출력 전압/주파수/부하 사용량(%)

배터리에 충전전압

4.2 조작부

UPS 시스템의 메인 컨트롤 버튼은 다음을 표시하고 제어할 수 있습니다.

ON/OFF 버튼 : INVERTER ON/OFF 제어

SELECT : 화면 상/화이동

파라미터 아이템 설정 : 동일 화면에서 여러가지 아이템 설정

설정확인 버튼 : 파라미터 설정

화면전환 버튼 : 화면 되로 넘김, 백라이트 OFF시 다시킴

4.3 LED 표시부

UPS 는 LED 로 장비의 동작 상태 및 이상시 알라음과 함께 FAULT 에 LED 가 점등되

어 사용자에게 장비의 이상 여부를 알려줍니다.

PHASE :경보/ UPS 메인 입력/바이패스 비정상시 LED ON

RECTIFIER : 동작상태/ 정류부 동작상시 LED ON

INVERTER : 동작상태/ 인버터 동작시 LED ON

BYPASS : 경보/ UPS가 현재 바이패스 상태시 LED ON

BAT. LOW : 경보/ 배터리 저전압 시 LED ON / 평상시 OFF

FAULT : 경보/ 정류부, 인버터 또는 바이패스 비정상시 LED ON

Page 9: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

9/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

5. 순변환부 및 충전장치(Rectifier/Charger)

본 장치는 Clean input Rectifier 정류부로, 방열판, 콘덴서, 조립용 각종부품 등으로 구

성하며 단상 전파정류 회로를 이용한 정류부로서 교류를 직류로 변환시켜 역 변환부에

공급함과 동시에 충전 장치는 축전지를 최적의 조건으로 충전시키는 기능으로 제작되

었습니다.

6. 순변환부 제어 (Super Charger)

Super Charger 는 축전지의 과충전을 방지하고 90%까지의 급속충전(Equalizing) 및 일

정부분 이상 충전 시 배터리의 오버 충전 및 과 방전을 위하여 LIMIT

CHAGING(Floating)을 하는 방식으로 배터리의 수명을 타사보다 30% 이상 연장 시키는

방식입니다..

7. 역변환부(INVERTER)

본 장치는 IGBT (Insulated Gate Bipolar Transistor) 모듈, 방열판, 각종 조립용 부품으로

구성된 고주파 스위칭 방식으로 정류부로부터 정류된 직류 전원을 IGBT 모듈에 공급하

고 검출 장치로부터 정현파를 검출하여 정현파 펄스폭변조 (SINE PWN)방식의

INVERTER 로서 직류 전력을 공급하며 본 장치를 보호하기 위하여 직류 입력측에 반도

체 보호용 고속 퓨즈를 구비하여 제작하였습니다.

8. 동기 절체부

본 장치는 INVERTER 고장 및 과부하 시를 대비하여 BY-PASS (상용 전원) 및 INVERTER

측에 각각 설치하여 연동 동작되도록 하는 구조로서 위상차에 의해 발생되는 돌입 전

류를 방지하기 위하여 순수한 반도체 소자로 구성 되며 과부하로 인하여 BYPASS LINE

으로 절체된 경우 과부하 상태가 해제되고 INVERTER 가 정상 동작하게 되면 INVERTER

로 자동 재 절체 되도록 함으로서 부하는 가급적 양질의 안정된 INVERTER 전원을 공

급 받도록 제작되어 있습니다.

9. 제어회로부

제어 회로부는 논리회로를 구동하기 위한 보조 전원기 및 역 변환부의 제어부와 상태

표시 경보부, 동기절체 제어부 등으로 구성되며 POWER SUPPLY 는 축전지에서 직접

공급받아 고성능 스위칭 방식에 의한 DC/DC CONVERTER 방식을 사용함으로써 절체,

또는 가동시 오 동작이 배제되고 본 장치 내부에서 발생되는 과도전압 및 불시의 순간

정전 시에도 제어 회로가 안정되게 동작되도록 제작되었습니다.

Page 10: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

10/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

10. 보호장치

본 장치에는 입력측의 저전압, 과전류, 과전압, 써지등에 대한 보호장치를 구비하며 출

력측 단락, 동기절체 스위치 작동 시에 나타나는 전압 및 전류와 써지를 흡수할 수 있

는 기능을 구비합니다.

11. 원격운용 및 상태 감시

본 장치는 RS232C DB-9 가 기본 제공되며 UPS 에서 1:1 감시가 용이합니다. 포함되어

있는 모니터링 소프트웨어는 장비의 각종 정보를 실시간으로 체크 및 확인이 가능하며

이벤트 및 알람 내역이 저장되어 이를 확인 및 프린트 할 수 있으며 알람 발생시 담당

자에게 이메일 통보기능과 정전시 컴퓨터 및 UPS 자동 셧다운 기능을 가집니다.

1) SNMP 카드(선택사양) - 국제 표준 UPS MIB 를 사용하는 SNMP (simple network

management protocol) 카드를 사용하여 UPS 를 TCP/IP 네트워크에 연결할 수 있습

니다. SNMP 어댑터는 플러그인 카드, 외부 SNMP 박스, 프록시 에이전트 PC 등의

형태로 제공될 수 있습니다.

2) UPS 데이터 보호 소프트웨어 - Windows95/98/NT, UNIX, Novell, OS/2 등 주요 운영

체계와 호환되는 UPS 데이터 보호 소프트웨어를 사용할 수 있습니다.

사. 전기적 특성

구 분 특 성

모 델 iUPS-33T/ iUPS-33TB

용 량(kVA) 40

냉 각 방 식 강 제 풍 냉 식

사 용 정 격 100 % 연속 사용

정류부

및충전

제어방식 3상 위상전파

사용소자 SCR

인버

터부

제어식 고주파 (60 Khz ) 순시 제어 PWM 방식

사용자 IGBT (Insulated gate Bipolar Transistor)

ST/SW절체방식 무순단 동기 절체

상 수 3상 4선식

정 격 전 압 380/220V ±20%

주 파 수 60Hz(54-66)

Page 11: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

11/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

배터리 타입 무보수무누액 장수명(10년)

배터리 수량 29Blocks

배터리 용량 125AH

설치 유형 외부 cabinet

배터리 정격전압 348VDC

충전 전류 20A

상 수 3상 4선식

정 격 전 압 380/220V

전압안정도 ±2 % 이내

정격주파수 60HZ ±0.2%

과도전압변동 ± 5 % 이내

과도응답속도 16 Ms 이내 (± 2 % 이내로 복귀 기준)

출력 전압 조정 220V,230V

파 형 왜 율 THD 3 % 이하 (LINER 부하 100% 기준)

과 부하 내량 125 %이하 15분간/ 150% 1분간

역 율 0.8Lag. 이상

소 음 65 dBA 이하(벽으로부터 1m)

종합효율 90 % 이상

동기

절체

동기절체시간 4 ms 이내

절 체 조 건 인버터 비 정상시

직류 저 전압시

출력 과 부하시

수동 절체시

도 장 5Y 7/1

통신포트 Dry contact,RS232/495포트, SNMP 아답터(옵션)

제품 사이즈(W×D×H) 500×800×1180

제품 중량(kg) 380

* iUPS-33TB는 병렬가능 제품

아. 검 사 항 목

1. 입력 전압 변동 시험

2. 출력 전압 안정도 시험

3. 출력 파형 왜율(Distortion) 시험

4. 상태 표시 및 경보 표시 기능 시험

5. BY-PASS 절환 기능 시험

6. 출력 주파수 안정도 시험

Page 12: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

12/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

7. 과도 전압 특성 시험

8. 부하 시험 및 효율 측정

10. 소음 측정

자. 기 타

1. 당사는 제작 승인 사양서에 의거하여 공급 제작한 제품에 대하여 기기의 시운전으로부

터 12 개월간 하자 보증을 하며 제작 부실로 인한 기간 내에 발생하는 모든 하자에 대

해 무상으로 신속히 보수 할 것을 약속합니다..

2. 본 기기에는 제작 회사명, 제작 년 월 일, 제작 번호, 전기적 특성이 기입 된 명판을

부착합니다.

Page 13: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

무정전전원공급장치 사양서 (iUPS33T Series) 2012-09-24

13/16

CT-U-IUPS33-KJS ㈜크로스티이씨 IUPS33T_40KVA

차. 도 면

Page 14: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

SYNC

STATIC S/W

CO

OUTPUTTRANSFOMER

INVERTERRECTIFIER

CB3

L11CB1

AC INPUT3상 4선식 380V+N

BYPASS LINE(AUTO)CB2

CB5EMERGENCY LINE

FC +

OUTPUT LOAD3상 4선식 380/220V

CB4

RS232 1PORT

SNMP (OPTION)

TB1

TB2

TB3

BATTERY12V 125AH 29Blocks

3

2

1

0

REV. NO

PROJECT NAME

CUSTOMER

DATE REASON DRAWN BY C H K APPROVAL

Name of Sheet

Number of Sheet Page

CAD File Name

BD.vsd

1 OF 1

SCALE 1:1 REV 2009-04-08

DATA 2009-04-08

momo9kim88

R1

iUPS33T UPS SYSTEM BLOCK DIAGRAM

CT-U-BD-1001

FILTER FILTER

RPA(OPTION)

Page 15: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

ON OFF

RECTIFIER

FAULT

BAT.LOWOVERLOAD

INVERTERBYPASS

PHASE

500

1180

800

FRONT VIEW SIDE VIEW REAR VIEW

3

2

1

0

REV. NO

PROJECT NAME

CUSTOMER

DATE REASON DRAWN BY C H K APPROVAL

Name of Sheet

Number of Sheet Page

CAD File Name

IUPS33T_OV.vsd

1 OF 2

SCALE 1:1 REV 2009-04-08

DATA 2009-04-08

momo9kim88

R1

iUPS33T 40kVA outline view

Page 16: 무정전전원공급장치 - cross introcrossups.com/download/iUPS33T_40kVA.pdf · 2012. 9. 23. · 무정전전원공급장치 사양서 (iups33t series) 2012-09-24 3/16 ct-u-iups33-kjs

558 125

125

270

800 800

BATTERY DETAIL

370

370

370

SIDE VIEWFRONT OPEN VIEW

709

12NDF12545.0kg

12NDF15552.0kg

12NDF125:45.0kg×29=1305kg

800 800

1600

1945

BATTERY RACK #1 125AH 29Block

INSTALL FRONT VIEW

*본도면은 사이즈 및 설치의 이해를 돕기 위한 도면으로 실제 제품과 외형이 다소 차이가 날 수 있습니다.

3

2

1

0

REV. NO

PROJECT NAME

CUSTOMER

DATE REASON DRAWN BY C H K APPROVAL

Name of Sheet

Number of Sheet Page

CAD File NameRACK FOR ACME

BATTERY.vsd

1 OF 17

SCALE 1:15 REV 2009-04-07

DATA 2008-11-26

momo9kim88

R1

23" Rack 29BLCOK for 12NDF125(12V 125AH)