effi+ - energie transfert thermique · ett quality organisation is certifi ed iso 9001:2008 (afnor...

46
EFFI+ www.ett.fr MADE IN FRANCE Single flow heat pump ENVIRONMENTAL CLIMATE CONTROL EQUIPMENT & SOLUTIONS

Upload: others

Post on 18-Mar-2020

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

EFFI+

www.ett.frMADE IN FRANCE

Single fl ow heat pump

ENVIRONMENTALCLIMATE CONTROLEQUIPMENT & SOLUTIONS

Page 2: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

2

■ General description ....................................................................................................................................... 03■ Operating principles ...................................................................................................................................... 04■ Description ........................................................................................................................................................... 05■ Control description ......................................................................................................................................... 07■ Main options ....................................................................................................................................................... 08

Technical features■ Type 106 – 108 – 109 – 110 – 112 ............................................................................................................. 09■ Type 213 – 215 – 217 – 218 – 220 – 222 ................................................................................................ 14■ Type 323 – 326 – 330 – 333 .......................................................................................................................... 19■ Type 434 – 438 – 443 ....................................................................................................................................... 24

Dimensions and connections■ Type 106 – 108 – 109 – 110 – 112 ............................................................................................................. 10■ Type 213 – 215 – 217 – 218 – 220 – 222 ................................................................................................ 15■ Type 323 – 326 – 330 – 333 .......................................................................................................................... 20■ Type 434 – 438 – 443 ....................................................................................................................................... 25

Arrangements■ Supply air downwards .................................................................................................................................. 28■ Supply air upwards.......................................................................................................................................... 29■ Supply air on side ............................................................................................................................................. 30

Auxiliaries■ Hot water coils ................................................................................................................................................... 31■ Water recovery coils ...................................................................................................................................... 33■ Electric heaters .................................................................................................................................................. 35

Options weight■ Options weight .................................................................................................................................................. 36

Gravity dampers option■ Pressure relief gravity dampers ............................................................................................................... 37

Sound level■ Sound level........................................................................................................................................................... 38

Installation accessories■ Roof curbs ............................................................................................................................................................. 39■ Feet ........................................................................................................................................................................... 44

Probes connection scheme■ Probes connection scheme ..................................................................................................................... 45

CONTENTS

ENERGIETRANSFERTTHERMIQUE

Page 3: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

3

ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual. 2015-06 - EFFI+ - 1

General description

• Machinery Directive 2006/42/EC - Operator's safety• Low Voltage Directive 2006/95/EC - Electricity• EMC Directive 2004/108/EC - Electromagnetic

Compatibility• 2009/142/EC Directive - Gas Appliances

• EN 1886 - Ventilation for buildings – Air Handling Units – Mechanical performance

• EN 60204-1 - Safety of machinery – Electrical equipment of machines

Moreover, each unit is delivered with an EC standard certifi cate of conformity and complies with the standards listed below:

All units are checked and inspected at the factory prior to shipment, a control certifi cate is issued for each unit.ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f).

We placed ease of operation at the heart of our units design:• The separated technical section facilitates service and control of the unit and allows measurement and

adjustment during operation.• The BEST controller is specifi cally designed for this application. It allows great fl exibility, thus optimum performance

of the ETT unit through a user-friendly interface, be it local or remote (with remote display, PC or BMS).

• Law: European directive 2008/98/EC of 19th November 2008:- The 26th point: "The polluter-pays principle is a guiding principle at European and international levels. The waste producer and the waste holder should manage the waste in a way that guarantees a high level of protection of the environment and human health."• Energy: ETT, innovator in Heat Transfer solutions.• Aluminium: a good choice for the planet!- aluminium is endlessly 100% recyclable.- recycling covers over 30% of aluminium needs.• Low polluting ETT manufacturing process:- selective sorting per job, all waste recycled. No paint, no use of water.- ISO 14001 Certifi cation (Environmental Management System).- Certifi cate of capability to handle refrigerants, reference number 637, according to Article R-543-106 of the French Environmental Code.

• Effi cient waste management:- Filtration: ETT units include "ecodesigned" air fi lters (selective sorting: frame - grille - media)

The ETT packaged unit is delivered ready to operate. Its full aluminium structure (frame & casing) ensures an excellent corrosion protection (20-year anti-corrosion guarantee).The ETT unit can be installed either on a rooftop or at ground level.ECODESIGN involves DECONSTRUCTION: ETT units are 98% recyclable (re-use and recycling rates based on EFFI+ 220).

Our technical choices have several impacts on the environment

100 % Aluminiumrecyclable

20-year guarantee against corrosion

2222222222222222222222222222222222220000000000000000000000000000000000000000000--------------------yyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyyeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaarrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrr gggggggggggggggggggggggggggggggggggggggggggggguuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaarrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrraaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaannnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnttttttttttttttttttttttttttttttttttttteeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeee aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaggggggggggggggggggggggggggggggggggggggggggggggggaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiinnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnsssssssssssssssssssssssssssssssssssssssttttttttttttttttttttttttttttttttttttt cccccccccccccccccccccccccccccccccccccccccccoooooooooooooooooooooooooooooooooooooooooooooorrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrooooooooooooooooooooooooooooooooooooooooooooosssssssssssssssssssssssssssssssssssssssiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiooooooooooooooooooooooooooooooooooooooooooooooooonnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn

Page 4: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

4

1 Fresh air 2 Return air 3 Supply air

Operating principles

The following operating modes are available:> heat pump> air conditioner> Free Cooling: cooling through

outside air, without thermodynamics

In these modes, the unit can operate:> in all recycling mode> in all fresh air mode> in mixing mode

The unit operates as a reversible heat pump:> source: outside air> treated fl uid: inside air

1

2 3

+ + _

1

2 3

+_

1

2 3

Heating mode

Cooling mode

Free Cooling mode

Heating mode: In winter, comfort temperature is maintained thanks to the thermodynamic system and the auxiliaries (optional).

Cooling mode: In summer, comfort temperature is maintained thanks to the thermodynamic system.

Free Cooling mode: In mid-season, comfort temperature is maintained using in priority the difference between outside air and inside air to cool the building.

Free Cooling allows considerable savings by delaying the use of thermodynamics.

Page 5: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

5

The ETT packaged unit comprises 3 different sections:

1 The external section allows thermal exchanges with the environment.

2 The separate technical section houses the refrigeration components, the electrical board and the control components.

3 The internal section ensures air change and air treatment.

Aluminium frame and casing:■ Rigid, compact and lightweight

packaged unit, perfectly weather-resistant, with a 20-year anti corrosion guarantee on casing.

■ Watertight fl oor with drainage outlets towards the border of the unit and connected to rubber siphons.

■ Aluminium vertical panels and roof, mounted on aluminium frame.

■ Access through large removable panels. Panels are closed with square locks. Doors tightness is ensured by fl exible gasket under compression, providing an ideal elasticity day after day (French standard NF EN 1886).

■ High performance free wheeling ventilation on supply air section to avoid losses due to pulley-belt transmissions, thus improving unit energy effi ciency.

■ Inner acoustic and thermal insulation on panels using 50 mm thickness M0 glass wool, in accordance with Public Access Buildings regulations (Article CH36).

■ Floor acoustic and thermal insulation using 100 mm M0 rock wool with double skin.

■ 2-damper mixing box including a motorised fresh air damper with bird proof grid and a motorised return air damper to ensure the desired proportions and optimise "Free Cooling" economiser phases. Dampers have extruded aluminium blades with low pressure drop thanks to their plane wing profi le and a fl exible gasket which ensures excellent air tightness. The damper frame is made of tightness class 3 aluminium.

Description

Defrost optimisation:

Defrosting principle:� The condensation of humidity produces frost on the coil.� The concerned refrigeration system and propeller fan stop

operating (simultaneous defrosting cycles are banned).� The refrigeration system 4-way valve reverses: during defrosting, the

coil operates as a condenser.� Supply air downwards� Coil drying� The other refrigeration circuit continues to operate normally.

Page 6: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

6

Description

Air assembly:■ Filter assembly with easy-to-remove

eco-concept fi lters - 98 mm pleated media, effi ciency G4 95 % ASHRAE gravimetric test for longer lifetime and lower pressure drops, pressure switch for fouling control.

■ Free wheeling supply air fan. This technology avoids losses due to pulley-belt transmissions.

■ Each electronically commutated motor allows:

� reduced kickback during start-up when textile ducts are used (soft start mode);

� maximum rotation speed regulation according to pressure drops on site;

� reduced speed operation in free-cooling mode to save energy (VDP operation).

Energy and thermodynamic assembly:■ Refrigeration circuits compliant with

European Directive on pressure equipment (PED 97/23/EC).

■ R410A refrigerant.■ Direct expansion internal exchanger

with copper pipes and aluminium fi ns and frame, coupled with an expansion valve in heat pump mode. These nested exchangers improve SCOP and SEER in partial load. In addition, the air fl ow rate can be adjusted according to the required capacity, reducing signifi cantly ventilation energy consumption (VDP operation).

■ Direct expansion external exchanger with copper pipes and aluminium fi ns and frame, coupled with a thermostatic expansion valve in heat pump mode. External exchangers angled position and the separation by refrigerant circuit and by compressor ensure quick and effi cient defrosting.

■ Optimised defrosting thanks to the new design of the external section and the integration of a Ø 800 mm propeller fan with supply air downwards (optimised for ecodesign).

■ Tandem hybrid circuits, operation in part load reduces signifi cantly the number of defrost cycles and their duration.

2 expansion valves per circuit and per refrigeration cycle to optimise the effi ciency of each evaporator cycle and reduce energy consumption.

■ Independent refrigeration circuit: each refrigeration circuit has a propeller fan to ventilate the exchanger. The propeller fan consists of a ferrule, a high energy performance 5-blade aluminium propeller coupled with an IP54 motor with reinforced sealing, and a zinc-plated steel fan guard, with cataphoresis protection. The fan assembly is perfectly weather resistant. Thanks to this new designed fan, exchangers air fl ow rate increases by up to 15 % compared to standard fans, while keeping the same power input. New blades profi le results in lower compressors consumption thanks to lower HP and higher LP in the different operation modes.

■ Anti-acid fi lter drier.■ HP and LP switches.

■ Cycle reversal valve.

Page 7: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

7

Control description

Electrical assembly:■ Electrical board compliant with

European standards EN 15-100 and EN 60204-01, including:

� ETT controller with display.� Power switch with lockable

external handle for full load cut-off. Connection using standard universal cable. Optional copper/aluminium connection terminal blocks.

� 400-230-24 volts transformer for regulation and control circuits.

� Faults synthesis with pending dry contact on terminal.

� Numbered terminal blocks with disconnecting terminals for remote controls and transfers.

� Terminal block for compressors load shedding.

� Internal wiring numbered at both extremities using numbered ferrules.

� Ik3 breaking capacity of basis 10 kA.� All components protected by circuit

breakers.� Rated LV distribution voltage

compliant with French standards indicating 230/400V for the rated voltage French standards also set minimum and maximum acceptable values at the user supply point (10 mn average values) within a -10%/+10% range from rated values and maximum acceptable value of the voltage drop gradient to 2%. The voltage drop gradient represents the additional voltage drop created on a network point if 1 KW single-phase is added on this point.

Control assembly:■ CTN type temperature probes. Their

accuracy and liability have been tested and validated both at the factory and on site.

■ One or more BEST-type controllers (Building Energy Saving Technology) especially developed by ETT for this range of units. Programs are updated annually to add functions requested for some applications and optimise units electricity consumption.

The microprocessor, memory and controllers size are adapted to the chosen applications and options by integrating a program set-up in the factory out of 160 possible confi gurations. The controller is in a plastic box which guarantees a high mechanical protection and reduces electrostatic shocks threats.

Among other functions, the controller includes:

� On/Off with remote contact or vacancy contact.

� On/Off according to programmed schedule (2 time slots per day).

� Fault synthesis with dry contact for transfer to customer system.

� 2 setpoints (cooling and heating) according to the European directive 2002/91/EC.

� Security management (fi re thermostat, smoke detector, HP switch, etc.) and faults management.

� Optimisation and equalisation of compressors operating time.

� Economical analogue management of alternate fl ash-type defrost cycles for each refrigerant circuit using frost detection and end of defrosting through analogue probes, stop of the concerned exchanger ventilation, coil drying and starting of a new heating cycle in heat pump mode. External coils angled position and downward supply air fl ow help blowing water away from the coil, ensuring effi cient defrosting. In the case of multi-circuits units, simultaneous defrost cycles are banned to preserve comfort and energy savings.

� Economiser management (Free Cooling) through inside temperature analysis and comparison between return air and outside air temperatures.

� Compressors stages management giving priority to the highest COP and EER in part load.

� Out-of-frost restart.� Auxiliaries management (possibility

of banning according to outside temperature).

� Night energy consumption management with compressors' use limitation (night cooling).

� Written faults history (no code needed) with hour and outside temperature display.

� Operating hours counting (unit, compressors and auxiliaries).

� Air quality control with CO2 probe to optimise fresh air quantities to introduce, therefore limiting energy consumption.

Page 8: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

8

Main options

■ Double skin, 13/10 AG in internal section, 50 mm■ Motorised external damper for supply air (2006/42/EC Directive)■ Whistle shaped cowl for fresh air on the top

Frame - Casing

■ Technical section acoustic insulation using STOPFLAM fl exible fi re-proof polyurethane foam ■ Fresh air cowl sound insulation■ Compressors acoustic jackets

Acoustics

Thermodynamics ■ HP and LP pressure gauges■ Electronic expansion valves■ Operation in cooling mode only■ Refrigerant leak detection aid

■ 3-sequential stage electric heater■ Triac■ 2-row hot water coil with analogue freezestat■ Recovery coil on food cooling (water)■ Mounted progressive 3-way valve hot water■ Mounted stop valve + TA valve on inlet■ Vinyl coating on hot water coil■ Vinyl coating on thermodynamic coils

Thermal exchangers

Laying ■ Aluminium adjustable connection roof curb■ Aluminium adjustable adaptation roof curb■ Aluminium adjustable ventilated roof curb■ Aluminium ventilated adaptation roof curb■ Aluminium plenum for return air and supply air■ 200 or 400 mm aluminium feet

Air handling ■ Filtration pressure gauges■ Analog air fl ow switch (AFC), air fl ow rate measurement and indication■ Filters fouling analog control (FFAC)■ Backed-up self-contained smoke detector■ Fan epoxy coating■ Supply air fan available pressure 400 Pa maxi■ Operation in all recycling or all fresh air mode (out of Public Access Buildings)■ G4 refi llable fi lters, 98 mm thickness■ 1 set of spare G4 fi lters, 98 mm thickness■ G1 metal fi lters (23 mm thickness) on fresh air■ F7 or F9 opacimetric fi lters, 98 mm thickness■ G4 + F7 or F9 double fi lters (48 + 48 mm)■ Pressure relief gravity dampers

Electricity ■ Total electrical energy metering according to 2002/91/EC■ Aluminium/copper connection terminal block (aluminium mandatory for power cables)■ Soft starter (compressors current soft starter)■ 230V/16 A single-phase socket in the technical section (separate power supply to be provided

by the installer)

■ Mini fresh air control using turret contacts (2 maximum)■ Year-round operation (compressor cooling mode operation authorisation with -5°C < outside

temp. < 15°C)■ Free Cooling banning based on specifi c humidity comparison■ Hygrometry probe (for external humidifi er control)■ Average room temperature (4 probes)■ ETT SRV (Variable Cooling System) control, compressor with electronic expansion valves

Control

Page 9: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

9

Technical features

NAME Unit 106 108 109 110 112

SPEC

IFIC

ATIO

NS

Rated air fl ow rate m3/h 6500 8000 9000 10000 12000

Mini air fl ow rate m3/h 4500 6000 7000 8000 10000

Maxi air fl ow rate m3/h 14000 14000 14000 14000 14000

COOLING MODE (1)

Net cooling capacity kW 31.4 39.4 42.4 47.3 53.2

Absorbed electrical power kW 9.7 13.8 15.1 18.0 22.1

Net EER kW/kW 3.24 2.85 2.81 2.63 2.41

Sensible/total capacity ratio 0.85 0.82 0.81 0.80 0.79

HEATING MODE (1)

Net heating capacity kW 31.5 41.2 44.2 50.7 57.8

Absorbed electrical power kW 8.6 11.2 12.1 14.3 17.0

Net COP kW/kW 3.65 3.67 3.66 3.54 3.41

Power stages 2

ELEC

TRIC

AL

CO

NN

ECTIO

N Maximum absorbed electrical power (2) kW 13.9 18.9 19.8 22.9 27

Total installed electrical power (2) (4) kW 19.9 24.5 25.2 27.9 31.2

Rated current (2) A 34 42 46 50 57

Starting current (2) A 88 129 131 160 174

FAN

SUPPLY AIR

Absorbed electrical power (1) kW 1.0 1.3 1.6 1.8 2.5

SFPv (EN 13779) kW/(m3/s) 0.56 0.59 0.62 0.66 0.76

GEN

ERA

L

EUROVENT Energy Effi ciency class in Heating mode A A A A A

Sound power level on supply air side (EUROVENT certifi ed) (1) dB(A) 76 79 81 83 88

Outside sound power level (EUROVENT certifi ed) (1) dB(A) 80 85 87 89 91

Resulting outside sound pressure at 10 m,reference 2x10-5 in free fi eld (1) dB(A) 52 57 59 61 63

Filters effi ciency G4

Filters dimensions & number mm(4x) 595*498*98(2x) 595*287*98

Mini / Maxi outside operating temperature in cooling mode

°C 15/45

Mini / Maxi internal coil inlet temperature in heating mode

°C -15/12

Unit weight excluding options (3) kg 675 675 675 690 690

Connection roof curb weight kg 90

Standard ventilated roof curb weight kg 130

Type 106 - 108 - 109 - 110 - 112

For installation accessories weight., please consult "Options weight".400 V - 50 Hz 3-phase power supply + earth without neutral(4) Power to be used for power cables selection

(1) EUROVENT conditions according to NF EN 14511 (October 2013)Cooling mode: 35°C DB -27°C DB 47% / 19°C WBHeating mode: 7°C DB - 20°C DB 60% / 15°C WB Out of defrost cycleExternal Static Pressure (ESP): 200 Pa(2) Out of electrical resistances

Page 10: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

10

Dimensions and connections

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 1700 mm on technical section side.

Length Width HeightCasing dimensions 3050 mm 1680 mm 1625 mm

Transport overall dimensions 3100 mm 1730 mm 1785 mm

Type 106 - 108 - 109 - 110 - 112

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR below

Nota :Nota : Fresh air cowls laying shall be made by the installer.

Page 11: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

11

Dimensions and connections Type 106 - 108 - 109 - 110 - 112

Nota :Nota : Fresh air cowls laying shall be made by the installer.

Length Width HeightCasing dimensions 3050 mm 1680 mm 1625 mm

Transport overall dimensions 3100 mm 1730 mm 1785 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on top

(propeller fan not shown) (propeller fan not shown)

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 1700 mm on technical section side.

Page 12: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

12

Dimensions and connections Type 106 - 108 - 109 - 110 - 112

Length Width HeightCasing dimensions 3050 mm 1680 mm 1625 mm

Transport overall dimensions 3100 mm 1730 mm 1785 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR below, return air on end

Nota :Nota : Fresh air cowls laying shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 1700 mm on technical section side.

Page 13: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

13

Dimensions and connections Type 106 - 108 - 109 - 110 - 112

Length Width HeightCasing dimensions 3050 mm 1680 mm 1625 mm

Transport overall dimensions 3100 mm 1855 mm 1785 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on side

Nota: Nota: - Fresh air cowls shall be fi tted by the installer.- Lateral box laying shall be made by the installer.- Supply air damper electrical connection shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 1700 mm on technical section side.

Page 14: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

14

Technical features

For installation accessories weight., please consult "Options weight".400 V - 50 Hz 3-phase power supply + earth without neutral(4) Power to be used for power cables selection

(1) EUROVENT conditions according to NF EN 14511 (October 2013)Cooling mode: 35°C DB -27°C DB 47% / 19°C WBHeating mode: 7°C DB - 20°C DB 60% / 15°C WB Out of defrost cycleExternal Static Pressure (ESP): 200 Pa(2) Out of electrical resistances

Type 213 - 215 - 217218 - 220 - 222

NAME Unit 213 215 217 218 220 222

SPEC

IFIC

ATIO

NS

Rated air fl ow rate m3/h 13000 15000 17000 18000 20000 22000

Mini air fl ow rate m3/h 10000 12000 14000 15000 19000 19000

Maxi air fl ow rate m3/h 23000 23000 23000 23000 23000 23000

COOLING MODE (1)

Net cooling capacity kW 57.8 67.3 77.5 81.5 89.2 98.9

Absorbed electrical power kW 18.0 22.4 27.6 30.3 36.0 42.6

Net EER kW/kW 3.21 3.01 2.81 2.69 2.48 2.32

Sensible/total capacity ratio 0.88 0.86 0.81 0.83 0.81 0.77

HEATING MODE (1)

Net heating capacity kW 58.7 70.7 83.5 88.9 99.5 112.3

Absorbed electrical power kW 15.9 19.3 23.1 24.9 29.2 34.3

Net COP kW/kW 3.69 3.67 3.61 3.58 3.41 3.28

Power stages 4

ELEC

TRIC

AL

CO

NN

ECTIO

N Maximum absorbed electrical power (2) kW 25.5 30.7 36.6 39.2 47.1 54.1

Total installed electrical power (2) (4) kW 37.6 42.3 47.5 49.8 56.9 62.9

Rated current (2) A 63 71 83 89 98 109

Starting current (2) A 157 186 198 232 270 281

FAN

SUPPLY AIR

Absorbed electrical power (1) kW 2.1 2.5 3.0 3.2 3.8 4.5

SFPv (EN 13779) KW/(m3/s) 0.58 0.60 0.63 0.64 0.68 0.73

EUROVENT Energy Effi ciency class in Heating mode A A A A A B

GEN

ERA

L

Sound power level on supply air side (EUROVENT certifi ed) (1) dB(A) 79 81 83 85 87 89

Outside sound power level (EUROVENT certifi ed) (1) dB(A) 82 86 89 90 93 94

Resulting outside sound pressure at 10 m,reference 2x10-5 in free fi eld (1) dB(A) 54 58 61 62 65 66

Filters effi ciency G4

Filters dimensions & number mm (6x) 595*498*98(3x) 595*287*98

Mini / Maxi outside operating temperature in cooling mode

°C 15/45

Mini / Maxi internal coil inlet temperature in heating mode

°C -15/12

Unit weight excluding options (3) kg 1135 1145 1145 1145 1170 1185

Connection roof curb weight kg 135

Standard ventilated roof curb weight kg 215

Page 15: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

15

Dimensions and connections Type 213 - 215 - 217218 - 220 - 222

Length Width HeightCasing dimensions 4620 mm 2200 mm 1690 mm

Transport overall dimensions 4670 mm 2250 mm 1850 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR below

Nota :Nota : Fresh air cowls laying shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 16: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

16

Dimensions and connections Type 213 - 215 - 217218 - 220 - 222

Length Width HeightCasing dimensions 4620 mm 2200 mm 1690 mm

Transport overall dimensions 4670 mm 2250 mm 1850 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on top

(propeller fan not shown) (propeller fan not shown)

Nota :Nota : Fresh air cowls laying shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 17: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

17

Dimensions and connections Type 213 - 215 - 217218 - 220 - 222

Length Width HeightCasing dimensions 4620 mm 2200 mm 1690 mm

Transport overall dimensions 4670 mm 2250 mm 1850 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR below, return air on end

Nota :Nota : Fresh air cowls laying shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 18: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

18

Dimensions and connections Type 213 - 215 - 217218 - 220 - 222

Length Width HeightCasing dimensions 4620 mm 2200 mm 1690 mm

Transport overall dimensions 4670 mm 2375 mm 1850 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on side

Nota: Nota: - Fresh air cowls shall be fi tted by the installer.- Lateral box laying shall be made by the installer.- Supply air damper electrical connection shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 19: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

19

Technical features

NAME Unit 323 326 330 333

SPEC

IFIC

ATIO

NS

Rated air fl ow rate m3/h 23000 26000 30000 33000

Mini air fl ow rate m3/h 18000 22000 27000 27000

Maxi air fl ow rate m3/h 35000 35000 35000 35000

COOLING MODE (1)

Net cooling capacity kW 100.2 114.4 131.5 147.3

Absorbed electrical power kW 33.3 40.7 52.8 63.5

Net EER kW/kW 3.01 2.81 2.49 2.32

Sensible/total capacity ratio 0.87 0.82 0.80 0.77

HEATING MODE (1)

Net heating capacity kW 104.4 123.6 147.1 167.1

Absorbed electrical power kW 28.2 34.1 43.1 51.3

Net COP kW/kW 3.71 3.63 3.41 3.26

Power stages 6

ELEC

TRIC

AL

CO

NN

ECTIO

N Maximum absorbed electrical power (2) kW 46.5 53.7 65.6 81.3

Total installed electrical power (2) (4) kW 68.2 74.6 85.2 99.4

Rated current (2) A 114 128 149 168

Starting current (2) A 212 243 292 340

FAN

SUPPLY AIR

Absorbed electrical power (1) kW 4.1 4.7 5.7 6.5

SFPv (EN 13779) KW/(m3/s) 0.64 0.65 0.68 0.70

EUROVENT Energy Effi ciency class in Heating mode A A A B

GEN

ERA

L

Sound power level on supply air side (EUROVENT certifi ed) (1) dB(A) 82 83 85 87

Outside sound power level (EUROVENT certifi ed) (1) dB(A) 87 90 94 96

Resulting outside sound pressure at 10 m,reference 2x10-5 in free fi eld (1) dB(A) 59 62 66 68

Filters effi ciency G4

Filters dimensions & number mm (6x) 595*595*98(3x) 595*498*98

Mini / Maxi outside operating temperature in cooling mode °C 15/45

Mini / Maxi internal coil inlet temperature in heating mode °C -15/12

Unit weight excluding options (3) kg 1910 1910 1925 1970

Connection roof curb weight kg 160

Standard ventilated roof curb weight kg 230

For installation accessories weight, please consult "Options weight".400 V - 50 Hz 3-phase power supply + earth without neutral(4) Power to be used for power cables selection

(1) EUROVENT conditions according to NF EN 14511 (October 2013)Cooling mode: 35°C DB -27°C DB 47% / 19°C WBHeating mode: 7°C DB - 20°C DB 60% / 15°C WB Out of defrost cycleExternal Static Pressure (ESP): 200 Pa(2) Out of electrical resistances

Type 323 - 326 - 330 - 333

Page 20: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

20

Dimensions and connections

Length Width HeightCasing dimensions 6335 mm 2200 mm 2130 mm

Transport overall dimensions 6385 mm 2250 mm 2180 mm

Type 323 - 326 - 330 - 333

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR below

Nota :Nota : Fresh air cowls laying shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 21: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

21

Dimensions and connections Type 323 - 326 - 330 - 333

Length Width HeightCasing dimensions 6335 mm 2200 mm 2130 mm

Transport overall dimensions 6385 mm 2250 mm 2180 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on top

(propeller fan not shown)(propeller fan not shown)

Nota :Nota : Fresh air cowls laying shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 22: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

22

Dimensions and connections Type 323 - 326 - 330 - 333

Length Width HeightCasing dimensions 6335 mm 2200 mm 2130 mm

Transport overall dimensions 6385 mm 2250 mm 2180 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR below, return air on end

Nota :Nota : Fresh air cowls laying shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 23: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

23

Dimensions and connections Type 323 - 326 - 330 - 333

Length Width HeightCasing dimensions 6335 mm 2200 mm 2130 mm

Transport overall dimensions 6385 mm 2375 mm 2180 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on side

Nota: Nota: - Fresh air cowls shall be fi tted by the installer.- Lateral box laying shall be made by the installer.- Supply air damper electrical connection shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2200 mm on technical section side.

Page 24: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

24

Technical features Type 434 - 438 - 443

NAME Unit 434 438 443

SPEC

IFIC

ATIO

NS

Rated air fl ow rate m3/h 34000 38000 43000

Mini air fl ow rate m3/h 30000 36000 36000

Maxi air fl ow rate m3/h 46000 46000 46000

COOLING MODE (1)

Net cooling capacity kW 150.6 171.3 195

Absorbed electrical power kW 53.6 68.0 84.8

Net EER kW/kW 2.81 2.52 2.3

Sensible/total capacity ratio 0.84 0.81 0.77

HEATING MODE (1)

Net heating capacity kW 163.2 192.4 223.1

Absorbed electrical power kW 45 55.8 68.5

Net COP kW/kW 3.63 3.45 3.26

Power stages 8

ELEC

TRIC

AL

CO

NN

ECTIO

N Maximum absorbed electrical power (2) kW 70.3 84.7 108.8

Total installed electrical power (2) (4) kW 92.3 105.2 126.5

Rated current (2) A 158 184 212

Starting current (2) A 272 327 384

FAN

SUPPLY AIR

Absorbed electrical power (1) kW 5.9 6.0 8.9

SFPv (EN 13779) KW/(m3/s) 0.63 0.57 0.74

Energy Effi ciency class in Heating mode A A B

GEN

ERA

L

Sound power level on supply air side (1) dB(A) 86 89 92

Outside sound power level (1) dB(A) 91 94 97

Resulting outside sound pressure at 10 m,reference 2x10-5 in free fi eld (1) dB(A) 63 66 69

Filters effi ciency G4

Filters dimensions & number mm (9x) 595*595*98(3x) 595*498*98

Mini / Maxi outside operating temperature in cooling mode °C 15/45

Mini / Maxi internal coil inlet temperature in heating mode °C -15/12

Unit weight excluding options (3) kg 2185 2201 2270

Connection roof curb weight kg 195

Standard ventilated roof curb weight kg 270

For installation accessories weight., please consult "Options weight".400 V - 50 Hz 3-phase power supply + earth without neutral(4) Power to be used for power cables selection

(1) Cooling mode: 35°C DB - 27°C DB 47% / 19°C WBHeating mode: 7°C DB - 20°C DB 60% / 15°C WB Out of defrost cycleExternal Static Pressure (ESP): 200 Pa(2) Out of electrical resistances

Page 25: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

25

Dimensions and connections Type 434 - 438 - 443

Length Width HeightCasing dimensions 7340 mm 2350 mm 2700 mm

Transport overall dimensions 7390 mm 2400 mm 2860 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR below

Nota :Nota : Fresh air cowls laying shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2350 mm on technical section side.

Page 26: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

26

Dimensions and connections Type 434 - 438 - 443

Length Width HeightCasing dimensions 7340 mm 2350 mm 2700 mm

Transport overall dimensions 7390 mm 2400 mm 2860 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on top

(propeller fan not shown)(propeller fan not shown)

Nota :Nota : Fresh air cowls laying shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2350 mm on technical section side.

Page 27: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

27

Dimensions and connections Type 434 - 438 - 443

Length Width HeightCasing dimensions 7340 mm 2350 mm 2700 mm

Transport overall dimensions 7390 mm 2400 mm 2860 mm

Front view:

Top view:

Return air side view: Supply air side view:

SUPPLY AIR on side

Nota: Nota: - Fresh air cowls shall be fi tted by the installer.- Lateral box laying shall be made by the installer.- Supply air damper electrical connection shall be made by the installer.

1 Fresh air2 Return air3 Supply airA Access

Power supplyC Technical section

Provide 400 mm clearance (minimum) to allow air passage below the unit.

■ Provide a maintenance zone of 2350 mm on technical section side.

Page 28: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

28

SUPPLY AIR downwardsInstallation on roof curb or customer frame on roof.

Arrangement 1.1

1

1

1

1

1

1

1

1

1

1

2

2

2

2

2

2

2

2 2

2

3

3

33

3

3

33

3

3

Arrangement 1.2

Arrangement 1.4: with whistle shaped cowl (optional)

Arrangement 1.6

Arrangement 1.8

Arrangement 1.10

Arrangement 1.3

Arrangement 1.5: with whistle shaped cowl (optional)

Arrangement 1.7

Arrangement 1.9: with whistle shaped cowl (optional)

1 Fresh air 2 Return air 3 Supply air

Arrangements

Page 29: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

29

1

3

1 Fresh air 2 Return air 3 Supply air

Arrangement 2.1 Arrangement 2.2

Arrangement 2.4: with whistle shaped cowl (optional)

Arrangement 2.6

Arrangement 2.8

Arrangement 2.10

Arrangement 2.3

Arrangement 2.5: with whistle shaped cowl (optional)

Arrangement 2.7

Arrangement 2.9: with whistle shaped cowl (optional)

SUPPLY AIR upwardsInstallation on feet (400 mm minimum) or customer frame. Feet are optional. A supply air damper is necessary for units bigger than 10000 m3/h in Public Access Buildings.

3

1

2

1

2 3

1

2

3

1

2 3

1

2

3

1

2

3

1

2

3

2

1

3

2

1 3

22

Arrangements

2

Page 30: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

30

SUPPLY AIR on sideOpposite the technical section (with 400 mm feet minimum)

1 Fresh air 2 Return air 3 Supply air

Arrangement 3.1 Arrangement 3.2

Arrangement 3.4: with whistle shaped cowl (optional)

Arrangement 3.6

Arrangement 3.8

Arrangement 3.10

Arrangement 3.3

Arrangement 3.5: with whistle shaped cowl (optional)

Arrangement 3.7

Arrangement 3.9: with whistle shaped cowl (optional)

1

2

3

1

2

3

1

3

1

2 3

1

2 3

1

2 3

1

2

3

1

23

1

2

3

1

23

Arrangements

2

Page 31: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

31

Top view Principle

Dimensions Unit 106 - 108 - 109110 - 112

213 - 215 - 217218 - 220 - 222 323 - 326 - 330 - 333 434 - 438 - 443

A mm 795 1250 1300 1800

B mm 185 200 200 200C mm 95 135 135 120Ø mm 40/49 40/49 40/49 40/49

Auxiliary: Hot water coils

SCHEMATIC DIAGRAM

CONNECTION

+ / -

BE

C

Ø de raccordement

A B

C

Connec� on Ø

Op� on

Air fl ow way

Hot w

ater

coi

l

Page 32: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

32

CAPACITIES

With +10°C air inlet temperature on coils

Optional: stop valve on outlet and TA regulating valve on inlet

Unit 106 108 109 110 112 213 215 217 218 220 222

Water regime 90/70°C

Maxi power (kW) kW 78 90 98 105 119 158 175 190 198 212 226

Maxi fl ow rate m3/h 3.4 4 4.3 4.6 5.2 7 7.7 8.4 8.7 9.3 9.9

3WV + coil pressure drop mWC 0.7 0.95 1 1.2 1.6 4.2 5.2 6.2 6.5 7.5 8.1

Water regime 80/60°C

Maxi power (kW) kW 66 76 82 88 99 134 148 162 168 180 192

Maxi fl ow rate m3/h 2.9 3.3 3.6 3.9 4.4 5.9 6.5 7.1 7.4 7.9 8.4

3WV + coil pressure drop mWC 0.5 0.71 0.75 0.9 1.05 3.1 3.9 4.6 4.9 5.5 6.1

Unit 323 326 330 333 434 438 443

Water regime 90/70°C

Maxi power (kW) kW 177 193 212 226 190 205 222

Maxi fl ow rate m3/h 7.8 8.4 9.3 9.9 8.4 9 9.8

3WV + coil pressure drop mWC 5.3 6.2 7.5 8.1 6.1 7 8

Water regime 80/60°C

Maxi power (kW) kW 151 164 180 192 162 174 189

Maxi fl ow rate m3/h 6.6 7.2 7.9 8.4 7.1 7.7 8.3

3WV + coil pressure drop mWC 4 4.7 5.5 6.2 4.7 5.3 6.1

Unit 106 108 109 110 112 213 215 217 218 220 222

Water supply 90/70°C

Stop and TA valves pressure drop

(opened by 3 turns)mWC 0.8 1.1 1.3 1.5 1.8 3.1 3.8 4.5 4.8 5.6 6.2

Water supply 80/60 °C

Stop and TA valves pressure drop

(opened by 3 turns)mWC 0.6 0.8 0.9 1.0 1.3 2.3 2.7 3.3 3.5 4.0 4.5

Unit 323 326 330 333 434 438 443

Water supply 90/70°C

Stop and TA valves pressure drop

(opened by 3 turns)mWC 3.9 4.6 5.5 6.3 4.5 5.2 6.1

Water supply 80/60 °C

Stop and TA valves pressure drop

(opened by 3 turns)mWC 2.8 3.3 4.0 4.5 3.2 3.8 4.4

Auxiliary: Hot water coils

Page 33: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

33

Dimensions Unit 106 - 108 - 109110 - 112

213 - 215 - 217218 - 220 - 222

323 - 326330 - 333

434 - 438443

A mm 180 202 251 250

B mm 415 551 614 335

C mm 329 367 367 385

D mm 450 480 630 700

E mm 700 700 800 1230

F mm 1625 1690 2130 2700

G mm 1400 1480 2130 2450

H mm 1680 2200 2200 2350

Ø mm 40 x 49 50 x 60 66 x 76 66 x 76

+ / -

RE

CU

P

+ / -

RE

CU

PØ de raccordement

B A

E

D

C

E

D

Ø de raccordement

G

C H

F

GA

B

H

F

Top view Side view

Auxiliary: Water recovery coils

SCHEMATIC DIAGRAM

CONNECTION

Connec� on Ø

Connec� on Ø

Reco

very

Reco

very

Page 34: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

34

Auxiliary: Water recovery coils

CAPACITIES

Unit 106 108 109 110 112 213 215 217 218 220 222

Water supply35/70°C

Air inlet+10°C / 70 %

Maxi power (kW) kW 16.6 18.7 20.0 21.1 23.2 32.4 35.1 37.5 38.6 40.8 42.8

Maxi fl ow rate m3/h 2.9 3.2 3.4 3.6 4.0 5.9 6.0 6.5 6.7 7.0 7.4

Valves (3WV + TA) + coilpressure drop

mWC 2.0 2.4 2.70 2.9 3.2 3.0 3.3 3.4 3.5 3.9 4.3

Coil outlet supply air conditions

°C/%RH 20/ 37

19.2/ 39

18.7/ 40

18.3/ 41

17.6/ 43

19.4/ 38

18.8/ 40

18.3/ 41

18.1/ 41

17.6/ 42

17.3/ 43

Water supply35/70°C

Air inlet+20°C / 50 %

Maxi power (kW) kW 8.0 9.3 10.0 10.5 11.6 16.8 18.1 19.3 19.9 21.0 22.0

Maxi fl ow rate m3/h 1.4 1.6 1.7 1.8 2.0 2.9 3.1 3.3 3.4 3.6 3.8

Valves (3WV + TA) + coilpressure drop

mWC 0.9 1.0 1.1 1.2 1.4 1.2 1.3 1.5 1.5 1.7 1.5

Coil outlet supply air conditions

°C/%RH 24.8/ 37

24.5/ 38

24.3/ 38

24.1/ 39

23.8/ 40

24.8/ 38

24.5/ 38

24.3/ 39

24.1/ 39

23.9/ 39

23.7/ 40

Unit 323 326 330 333 434 438 443

Water supply35/70°C

Air inlet+10°C / 70 %

Maxi power (kW) kW 35.3 37.6 40.3 44.0 66.2 70.0 74.5

Maxi fl ow rate m3/h 6.1 6.5 6.9 8.6 11.4 12.1 12.8

Valves (3WV + TA) + coilpressure drop

mWC 2.6 2.4 2.7 2.0 3.5 3.9 4.3

Coil outlet supply air conditions

°C/%RH 17.5/ 43

17.1/ 44

16.6/ 46

16.5/ 45

17.7/ 42

17.3/ 43

16.9/ 45

Water supply35/70°C

Air inlet+20°C / 50 %

Maxi power (kW) kW 15.8 18.5 20.4 21.4 34.0 35.9 38.1

Maxi fl ow rate m3/h 3.1 3.6 4.0 4.2 5.9 6.2 6.6

Valves (3WV + TA) + coilpressure drop

mWC 1.1 1.3 1.3 1.0 1.6 1.8 1.6

Coil outlet supply air conditions

°C/%RH 23.4/ 41

23.5/ 40

23.3/ 41

23.2/ 41

24.0/ 39

23.7/ 40

23.5/ 40

Page 35: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

35

Total capacity

(kW)Current

(A)1st

stage 2nd

stage 106 108 109 110 112 213 215 217 218 220 222 323 326 330 333 434 438 443 Weight (kg)

9 13.0 3 6 • • • • • • • • • • • • • • • • • • 9 12 17.3 3 9 • • • • • • • • • • • • • • • • • • 915 21.7 6 9 • • • • • • • • • • • • • • • • • • 1018 26.0 6 12 • • • • • • • • • • • • • • • • • • 1121 30.3 6 15 • • • • • • • • • • • • • • • • • • 824 34.6 9 15 • • • • • • • • • • • • • • • • • • 1227 39.0 9 18 • • • • • • • • • • • • • • • • • • 1530 43.3 12 18 • • • • • • • • • • • • • 1633 47.6 12 21 • • • • • • • • • • • • • 1536 52.0 15 21 • • • • • • • • • • • • • 1639 56.3 15 24 • • • • • • • • • • • • • 1642 60.6 18 24 • • • • • • • • • • • • • 1945 65.0 18 27 • • • • • • • • • • • • • 2048 69.3 21 27 • • • • • • • 1954 77.9 21 33 • • • • • • • 2260 86.6 21 39 • • • • • • • 2363 90.9 27 36 • • • • • • • 2672 103.9 27 45 • • • 2581 116.9 27 54 • • • 32

Nota: An additional coil can be mounted in the supply air duct or on the fresh air inlet for higher capacities. Please consult us.

Auxiliary: Electric heaters

SCHEMATIC DIAGRAM

AVAILABLE CAPACITIES (in kW)

+ / -

Batteries électriquesElectric heaters

Page 36: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

36

Options weight (kg)

Options 106 108 109 110 112 213 215 217 218 220 222 323 326 330 333 434 438 443

Frame - CasingUnit with Vertical (V) or Lateral (L) supply air

55 75 105 105

Motorised external damper for supply air (2006/42/EC Directive)

10 15 20 20

Dampers removal -20 -42 -51 -67

50 mm double skin 40 60 80 110

Fresh air cowl 9 19 23 16

Acoustics

Technical section soundproofi ng 2.3 3 4.5 6

Compressors acoustic jackets 2 4 6 8

Air handlingPressure relief gravity dampers (return air below)

22 32 39 -

Thermal exchangers

2-row hot water coilwith 3WV with water 40 60 60 60

Recovery hot water coil with 3WV with water (cowl, stop and TA valves included)

92 138 175 283

Year-round kit 1.4 2.8 4.2 5.6

Laying

Aluminium ventilated roof curb 130 215 230 270

Aluminium connection roof curb 90 135 160 195

Roof curb side insulation 7 9 11 11

Page 37: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

37

Option: Pressure relief gravity dampers

Overpressure management:> Supply air must sometimes be extracted due to building tightness.

> This solution avoids overpressure in the building.

> Gravity dampers remain closed when not in use (unit stopped or operating in all recycling mode)

> They open in Free Cooling mode.

■ Passive exhaust

■ Backdraft function

■ Aluminium frame and blades

■ Suitable for standard EFFI+ casing

■ Available for EFFI+ series 106 to 333

■ Possible arrangements: 1.1 and 2.1

Description:

Type 106 - 108 - 109110 - 112

213 - 215 - 217218 - 220 - 222 323 - 326- 330 - 333

Return air below 22 32 39

Return air on top 33 59 70

Option weight with fresh air cowl (kg):

Page 38: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

38

Supply air fan: Available pressure: 200 Pa

Return air side: Available pressure: 200 Pa

FREQUENCY BAND Hz ► 63 125 250 500 1000 2000 4000 8000

FanGeneral level

Lw (dB(A))FLOW RATE(m3/h) ▼

106 6500 33.2 49.1 60.6 68.5 72.2 70.1 64.8 60.9 76.0108 8000 35.8 47.9 62.4 71.6 74.7 73.8 67.8 65.9 79.0109 9000 37.5 48.6 63.9 73.5 76.4 76.0 69.7 68.8 81.0110 10000 39.5 50.6 65.8 75.3 77.8 78.5 72.0 71.7 83.0112 12000 44.4 56.3 70.7 79.9 81.8 84.0 77.8 77.3 88.0213 13000 36.6 52.9 63.9 71.5 75.3 73.2 67.8 63.8 79.0215 15000 38.0 51.9 65.1 73.6 77.0 75.5 69.9 66.9 81.0217 17000 39.7 51.6 66.3 75.5 78.6 77.8 71.7 70.0 83.0218 18000 41.5 52.6 67.9 77.5 80.4 80.0 73.7 72.8 85.0220 20000 43.5 54.4 69.7 79.4 82.0 82.4 75.9 75.5 87.0222 22000 45.5 56.8 71.8 81.3 83.6 84.6 78.2 77.9 89.0323 23000 40.8 60.0 67.9 74.3 78.5 75.8 70.3 65.9 82.0326 26000 41.1 58.4 68.3 75.5 79.4 77.1 71.6 67.4 83.0330 30000 42.1 57.7 69.5 77.5 81.2 79.2 73.9 70.0 85.0333 33000 43.9 57.7 71.0 79.5 83.0 81.4 75.8 72.9 87.0434 34000 42.7 54.4 69.2 78.5 81.6 80.8 74.7 73.2 86.0438 38000 45.5 56.8 71.8 81.3 83.6 84.6 78.2 77.9 89.0443 43000 48.5 59.6 74.8 84.4 86.8 87.5 81.0 80.7 92.0

FREQUENCY BAND Hz ► 63 125 250 500 1000 2000 4000 8000

FanGeneral level

Lw (dB(A))FLOW RATE(m3/h) ▼

106 6500 27.9 39.1 53.2 51.9 54.1 57.3 52.0 46.9 61.4108 8000 29.7 39.4 55.1 54.5 56.6 61.1 55.4 52.9 64.6109 9000 31.0 40.7 56.4 56.3 58.2 63.5 57.4 56.1 66.8110 10000 32.7 43.1 58.3 57.8 59.3 65.9 59.4 59.3 68.9112 12000 37.6 49.2 63.3 62.1 62.9 71.3 64.1 65.2 74.0213 13000 30.8 43.1 56.0 54.9 57.3 60.3 54.8 49.5 64.3215 15000 32.5 42.5 57.9 56.8 58.9 62.8 57.4 53.4 66.6217 17000 33.4 43.2 58.9 58.4 60.4 65.2 59.3 57.1 68.7218 18000 35.0 44.7 60.4 60.3 62.2 67.5 61.4 60.1 70.8220 20000 36.7 46.8 62.3 62.0 63.7 69.8 63.4 63.1 72.9222 22000 38.7 49.4 64.4 63.7 65.1 72.0 65.4 65.6 75.0323 23000 33.0 51.4 58.0 57.4 60.6 62.8 56.6 50.6 67.0326 26000 34.5 49.0 59.6 58.8 61.4 64.1 58.3 52.8 68.1330 30000 37.1 47.6 62.4 61.0 63.1 66.4 61.3 56.1 70.5333 33000 38.4 48.4 63.8 62.8 64.8 68.7 63.3 59.4 72.5434 34000 36.4 46.1 61.8 61.4 63.4 68.3 62.4 60.3 71.7438 38000 38.7 49.4 64.4 63.7 65.1 72.0 65.4 65.6 75.0443 43000 41.8 52.1 67.3 66.9 68.4 74.9 68.4 68.3 77.9

*Lw: sound power level (dB(A))

Sound level *

Page 39: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

39

Packaged roof curbAdjustable connection roof curb■ Compliant with French standard

NF P 84-206-1 (Grooved sheet metal roofi ng with waterproofi ng coating) and fi re-safety regulations for PAB.

■ The packaged aluminium roof curb is considerably lighter than galvanised steel constructions.

■ Adjustable angles compensate the roof slope. Other slope percentages are available on request (optional). Please confi rm the roof slope percentage and direction.

■ Cap fl ashing allows continuous insulation and waterproofi ng membrane (up to 100 mm thick) on roof curb external side as stipulated by 2002/91/EC Directive.

■ Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H=345 mm).

Packaged roof curbAdjustable ventilated roof curb■ Compliant with French standard NF

P 84-206-1 (Grooved sheet metal roofi ng with waterproofi ng coating) and fi re-safety regulations for PAB.

■ The packaged aluminium roof curb is considerably lighter than galvanised steel constructions.

■ Adjustable angles compensate the roof slope. Other slope percentages are available on request (optional). Please confi rm the roof slope percentage and direction.

■ 200 mm ventilated air space in accordance with French fi re-safety regulations for Public Access Buildings (PAB). The unit is mounted on 4 (or 6) bolted feet and water tightness is ensured by a foam gasket on supply air and return air duct frames.

■ The air space also provides sound insulation since it considerably reduces radiated noise from below the unit.

■ 200 mm length double skin insulated supply and return air duct connections, with external aluminium mechanical protection.

■ Cable ducts below the unit for power cable and hot water coils piping.

■ The roof curb is insulated from below with 25 mm glass wool with a protection veil. The insulation is secured with aluminium clips welded on the sheet metal for a better fastening than gluing methods. Insulation limits thermal losses and avoids under-surface condensation.

■ Cap fl ashing allows continuous insulation and waterproofi ng membrane (up to 100 mm thick) on roof curb external side as stipulated by 2002/91/EC Directive.

■ Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H=345 mm).

■ Lifting lugs facilitate cranage.

Adapter interfaceon existing roof curb:■ Bespoke roof curb to be adapted

on any type of existing roof curbs or binding joists according to dimensions sent by the installer (see our particular clauses for this equipment).

The roof curb provides interfacing between the roof and the rooftop unit. It has been designed for easy assembly on the roof and simplifi ed unit laying.

Description

Installation accessories: Roof curbs

Page 40: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

40

WARNING: for this roof curb laying, the installer is responsible for the ten-year guarantee on roofi ng. Please indicate the roof slope and direction slope and direction when placing the order. Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H=345 mm). Roof curbs have to be back-drilled after mounting. Mastic application below unit frame.

mmDimensions

SERIES A B H Overall

widthOveralllength

Overallheight

Maxi slope (%)

106 - 108 - 109 110 - 112 1700 1970 600 1910 2180 630 4

213 - 215 - 217218 - 220 - 222 2220 2770 600 2430 2980 630 4

323 - 326 - 330 - 333 2220 3550 650 2430 3760 680 4

434 - 438 443 2370 3620 650 2580 3830 680 4

H

B

A

Adjustable connection roof curb

Installation accessories: Roof curbs

Page 41: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

41

mmDimensions

SERIES A B H Overall

widthOveralllength

Overallheight

Maxi slope (%)

106 - 108 - 109 110 - 112 1700 1970 600 1900 2170 830 4

213 - 215 - 217 218 - 220 - 222 2220 2770 600 2420 2970 830 4

323 - 236 - 330 333 2220 3550 650 2420 3750 880 4

434 - 438443 2370 3620 650 2570 3820 880 4

WARNING: for this roof curb laying, the installer is responsible for the ten-year guarantee on roofi ng. Please indicate the roof slope and direction when placing the order. Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H=345 mm). Roof curbs have to be back-drilled after mounting. The unit must be bolted to the roof curb. Mastic application below unit frame.

H

200

B

A

Adjustable ventilated roof curb

Installation accessories: Roof curbs

Page 42: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

42

* Available for fi lters but not in free heating.

WARNING: for this roof curb laying, the installer is responsible for the ten-year guarantee on roofi ng. Please indicate the roof slope and direction slope and direction when placing the order. Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H=345 mm). Roof curbs have to be back-drilled after mounting. Mastic application below unit frame.

mmDimensions

SERIES A B H Overall

widthOveralllength

Overallheight

Maxi slope (%)

106* - 108* - 109*110* - 112* 1700 2720 600 1910 2930 630 4

213 - 215 - 217 218 - 220 - 222 2220 3870 650 2430 4080 680 4

323 - 236 - 330 333 2220 4750 650 2430 4960 680 3.5

* Available for fi lters but not in free heating.

mmDimensions

SERIES A B H Overall

widthOveralllength

Overallheight

Maxi slope (%)

106* - 108* - 109* 110* - 112* 1700 2720 600 1900 2920 830 4

213 - 215 - 217 218 - 220 - 222 2220 3870 650 2420 4070 880 4

323 - 236 - 330 333 2220 4750 650 2420 4950 880 3.5

WARNING: for this roof curb laying, the installer is responsible for the ten-year guarantee on roofi ng. Please indicate the roof slope and direction when placing the order. Roof curbs are intended for steel decks up to 145 mm high and insulation up to 200 mm high (i.e. max. H=345 mm). Roof curbs have to be back-drilled after mounting. The unit must be bolted to the roof curb. Mastic application below unit frame.

For unit with "free heating" option or 300 mm fi lters

For unit with "free heating" option or 300 mm "box" fi lters

Adjustable connection roof curb

Adjustable ventilated roof curb

Installation accessories: Roof curbs

Page 43: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

43

Roof curbs are intended for a steel decks up to 145 mm high and insulation up to 200 mm high(i.e. max. H=345 mm).

Nota: One (for connection roof curb) or two (for ventilated roof curb) optional cover sheets can be added to protect the building from weather in the meantime between roof curb laying and unit laying.

Installation accessories: Roof curbsRoof curbs installation principle

50

100

Binding joist

Optional: side insulation

Connection roof curb

Unit frame

Waterproofi ng membrane

Sealant gasket between the frame and the roof curb on the periphery

Steel deck

Insulation

H15

0 m

ini

600

(or 6

50 a

ccor

ding

to th

e un

it)

Outer insulation shall be part of the waterproofi ng package (not supplied by ETT)

Page 44: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.Specifi cations and data in this document are not contractual.

44

Unit 106 108 109 110 112 213 215 217 218 220 222 323 326 330 333

Nr. of feet 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

Aluminium fi xed footUnitary weight: 1 kg

Installation accessories: Feet

Page 45: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

2015-06 - EFFI+ - 1ETT may change equipment technical data without prior notice.

Specifi cations and data in this document are not contractual.

45

3

2

1

1 Room probe: 1 shielded pair wire, 2 x 0.75 mm2 LIY-CY (maxi. length 100 lm)

CO2 probe: 2 shielded pairs wire, 4 x 0.75 mm2 LIY-CY (maxi. length 100 lm)

Hygrometry probe: 2 shielded pairs wire, 4 x 0.75 mm2 LIY-CY (maxi. length 100 lm)(optional)

2

3

Nota: - Please note that the value indicated can vary depending on probe location. For more representative results, do not install them:> Close to heat sources (spotlight, cooking appliances, glass wall, fl ues)> In draft zones (close to entrance, stockrooms, openings)> In dead zones (behind shelvings, in a corner)> Close to crowded areas (checkouts, fi tting rooms)

- For accurate measurements:> Probes must not be in the axis of the duct used for their wiring to avoid false air fl ow> Do not install control cables and power cables in the same duct (risk of electromagnetic

interference).

Probes connection principle

Page 46: EFFI+ - Energie Transfert Thermique · ETT Quality organisation is certifi ed ISO 9001:2008 (AFNOR Certifi cate no.1994/2016f). We placed ease of operation at the heart of our units

Des

ign:

201

5-06

- EF

FI +

- 1

- ETT

- D

ocum

ent p

rinte

d by

an

envi

ronm

enta

lly fr

iend

ly p

rinte

r usi

ng v

eget

able

bas

ed in

k on

PEF

C pa

per c

reat

ed fr

om s

usta

inab

ly-m

anag

ed fo

rest

.

www.ett.fr

ETT - Route de Brest - BP2629830 PLOUDALMEZEAU FRANCETel: +33 (0)2 98 48 14 22Fax: +33 (0)2 98 48 09 12Export Contact: +33 (0)2 98 48 00 70ETT Services: +33 (0) 2 98 48 02 22