ENERGY AUDITING IN THE COLLEGE CAMPUS
GROUP MEMBERS:
BINOY P B
SRUTHI C.K
RADHIKA A
SANJUSH S
SUJINI M
GUIDED BY :
SREEJITH KAsst Prof Dept of EEE
Tuesday, May 2, 2023
2
ABSTRACT An energy audit is an inspection, survey and analysis of energy flows for
energy conservation in a building, process or system to reduce the amount of energy input into the system without negatively affecting the output(s).
By identifying the sources of energy use in the college campus such as wastage of energy that can be found out and can be reduced or neglected.
Also by replacing the old inefficient items such as( fans, fluorescent lamp, motors etc...) by efficient ones.
By auditing we can save the wastage of energy resources and also we can reduce consumptions also.
Effective and concrete method to achieve rapid improvement in energy efficiency in buildings and industrial process.
First step in identifying opportunities to reduce energy expense.
Also called as Energy labeling , Energy assessment , Energy survey etc..
02/05/2023 3
INTRODUCTION
05/02/2023
4
It is a systematic procedure that
Obtain adequate knowledge of the existing energy consumption profile of the site.
Identifies the factors that affect on energy consumption.
Identifies and scales the cost effective energy saving opportunities.
Subject of energy consumption analysis are energy resources consumed in the industrial area, i.e.:
Electricity
Coal
Wood, wood chips/pellets
Fuels (petrol, oil, propane-butane).....
02/05/2023 5
AREAS OF ENERGY AUDITING
• Gas or other energy resources consuming appliances (furnaces, cleaning devices,..)
• Indoor/outdoor lighting,
• Measurement and regulation.
02/05/2023 6
05/02/2023
7
1. ADMINISTRATOR
2. OPERATING AGENT
3. ENERGY AUDITOR
4. AUDIT CLIENT
KEY PLAYERS OF AN ENERGY AUDITING PROGRAMME
Responsible body for the energy auditing program.
Sets the energy audit program goals.
Promotes energy audit on a general level.
Provide subsidies for energy audit.
02/05/2023 8
ADMINISTRATOR
Assists the administrator in developing auditing program.
Responsible for actual running of audit program.
Undertakes the monitoring of results , provides advice and training to auditors.
Take care of information transfer between administrator and auditor.
02/05/2023 9
OPERATING AGENT
The technical expert undertaking actual auditing work in the clients.
Responsible for actual marketing of energy audits to clients.
Receives finance from the administrator.
02/05/2023 10
ENERGY AUDITOR
The body , person or organization responsible for the energy cost of a building or an industrial site.
02/05/2023 11
AUDIT CLIENT
1. Start up meeting
2. Collecting the basic data
3. Field work
4. Analysis of collected and measured data
5. Reporting
6. Implementing some or all of the proposed energy saving measures02/05/2023 12
AUDIT PROCEDURE
02/05/2023 13
Tuesday, May 2, 2023
14
ENERGY CONSUMPTION FOR LAST YEAR
jan feb mar apr may june july aug sep oct nov dec0
100020003000400050006000
3955436845534107
344534223636377137734338
51305162
Consumption
Months
KWh
Tuesday, May 2, 2023
15
Above graph shows the previous year (2015) electricity bills.
We have supply voltage of 11KV.
We have average power factor of 0.92.
Energy charges as follows:- Normal time: 6.20 per KWh₹ Peak time : 9.30 per KWh₹ Off peak : 4.650 per KWh₹
Tuesday, May 2, 2023
16
LOAD CALCULATION
We have 7 blocks in college Main block Seminar hall block Canteen Fluid lab Civil workshop Mechanical lab Pump room
Tuesday, May 2, 2023
17
IN MAIN BLOCK WE HAVE....
Total no of lights: 440 each 36 watt Total no of fans: 406 each 60 watt Projectors: 3 each 165watt Computers : 25 each 150 watt Exhaust : 8 each 50watt Photostat machine: 2 each 900 watt Power sockets : 21 max output 1k watt Ordinary sockets : 242 max output 100 watt Water cooler: 2 each 200watt
Tuesday, May 2, 2023
18
Total lamp load= 440*36= 15.84kw Total fan load= 406*60= 24.36kw Projector load= 3*165= .495kw Total computer load= 150*25= 3.75kw Total exhaust fan load= 8*50= .24kw Photostat machine= 2*900= 1.8kw Water cooler= 2*200= .4kw
Total load= 46.88KW
Tuesday, May 2, 2023
19
IN SEMINAR HALL BLOCK
Total no of lights: 183 each 36w Total no fans: 145 each 60w Total no of sockets: 106 max 100w Total no of computers: 150 each 150w Projectors: 1 each 165w
Total Load = 48.53kw
Tuesday, May 2, 2023
20
Machine load in EEE lab= 64.4kw Machine load in Mech lab= 23.57kw
Total load = 136.7kw
Tuesday, May 2, 2023
21
IN CANTEEN
Total no of lights: 25 each 36w Total no of fans: 20 each 60w Refrigerator: 2 each approx 400w Freezer 1 having 900w Grinder: 1 having 1.5KW Mixer: 1 having .75KW
TOTAL LOAD= 6.05KW
Tuesday, May 2, 2023
22
IN CIVIL LAB.....
No of tube lights: 48 each 36watt No of fans: 14 each 60 watt No of sockets: 23 each max 100watt No of power sockets: 6 each max 1kw Total Machine Load: 8.541KW
Total load= 19.4089KW
Tuesday, May 2, 2023
23
IN FLUID LAB....
No of tube lights: 35 each 36watt No of fans: 11 each 60watts No of sockets: 31 each max100watts Total Machine load: 14.73KW
Total Load= 19.75KW
Tuesday, May 2, 2023
24
IN MECHANICAL LAB...
No of tube lights: 19 each 36watts No of fans: 6 each 60watts No of sockets: 15 each max 100watts Total Machine load: 5.34KW
TOTAL LOAD= 7.88KW
Tuesday, May 2, 2023
25
Water pump having 5HP ie 3.7285KW From the observations and calculations total
connected load to our campus is 240.39 KilloWatts
Tuesday, May 2, 2023
26
SANKEY DIAGRAM
Tuesday, May 2, 2023
27
Tuesday, May 2, 2023
28
SELECTION OF BETTER LAMPS..!!!
In the campus we are using fluorescent lamps.
As compared with LED the lux produced by fluorescent lamp are low for same wattage.
Exterior lightining of our campus is done using LED’s.
Tuesday, May 2, 2023
29
Tuesday, May 2, 2023
30
ADVANTAGES OF LED OVER FLUORESCENT TUBES
Tuesday, May 2, 2023
31
CALCULATIONS OF ILLUMINATIONTo find number of light fittings ‘N’
N= (E*A)/(O*CU*MF)
N: No of fittings neededE: Required illumination (lux)A: Working Area (sq.m)O: Luminous flux produced per lamp( lumens)CU: Coefficient of utilizationMF: Maintenance factor
Tuesday, May 2, 2023
32
LUX CALCULATION
When lights are off and windows are closed
20 lux
When all lights are on and windows are closed
90 lux
When all lights are on and windows are opened
150 lux
When all lights are off and windows are opened
95 lux
Tuesday, May 2, 2023
33
Considering the seminar hall...
We have 16 tube lights each having 42 watts and lumens of 2100
Length of seminar hall= 26.6mBreadth of seminar hall= 9.8 mArea of seminar hall= 260.68 sq.m
a) In case of Tube lightsCost : 400per tube set & 50Rs per tubeWattage : 42 wattlumens : 2100life : 4000hrs
So, required no:of tube lights (42W) for seminar hall having area of 260.68sq.m isN=(150*260.68)/(2100*0.6*1)= 30 nos.
Tuesday, May 2, 2023
34
Required no of fittings: 30nos
Seminar hall is used 100hrs/month. (5Hrs per day for 5 days in a weak)
Total light load =1260Watts.
Consumption = 126KWhr per month.
For 126KWhr monthly charge will be Rs 780.
Annual Energy consumption charge= Rs 9360
For every 3 year we have to replace two tube lights from an tube set.So we have to replace 60 tubes in an year from seminar hall.Replacement cost = Rs 3000 per year
Tuesday, May 2, 2023
35
Annual energy cost = Rs 9360Installation cost = 30*400= Rs 12000
So for 1st year Approx Rs 21,360 while using tube lights.
For 2nd year Rs 21360 + Rs9360= Rs 30720 (ie previous year cost plus this year consumption)
For 3rd year Rs 30720 + Rs 9360 + Rs 3000 = Rs 43080 (i.e. Previous year cost + this year consumption + replacement cost)
Tuesday, May 2, 2023
36
b) In case of LED
Cost : 500Rs per led bulbWattage : 18wattlumens : 1800life : 50000hrs
So, required no:of led bulb (18W) for seminar hall having area of 260.68sq.m is
N=(150*260.68)/(1800*0.6*1)= 34 nos.
Required no of fittings: 34nos
Seminar hall is used 100hrs/month.
Tuesday, May 2, 2023
37
Total light load = 612Watts
Consumption = 61.2KWhr per month
For 126KWh monthly charge will be Rs 380aprox
Annual consumption charge will be Rs 4560
Installation cost 500*34= Rs 17000
So for 1st year approx Rs 21,560
For 2nd year total cost = Rs 21560+Rs 4560 = Rs 26120
Tuesday, May 2, 2023
38
For 3rd year total cost = Rs 26120 + Rs 4560 = Rs 30680 As compared with tube lights initial cost of LED’s are high.
So by replacing tube lights with LED’s we can reduce the monthly consumption by half.
We will get back profits after 1 years & 1 months.
Tuesday, May 2, 2023
39
REPLACING WHOLE TUBES BY LED’STotal no:of tube lights: 750
Wattage: 42wattCost : 400 per Tube set & 50 per an tube lightLife : 4000hrs (approx 6 months)Usage : 5hrs a day for 5 days in a week
ie 100hrs per month
Total load : 42*750= 31.5KW
Monthly consumption= 3150KWh
Tuesday, May 2, 2023
40
SEB’s charge Rs 6.20 (approx) per Unit
Charge for monthly consumption is Rs 19530
For an year, energy charges will be Rs 234360
For every 3 year we have to replace all tube lights by once because of its life so its cost Rs 37500
Energy charge + Replacement cost = Rs 233760 per year
Installation cost = 750*400= Rs 300,000
So for 1st year total cost = Rs 534360
So for 2nd year total cost= Rs 534360 + Rs 234360 = Rs 768720 ( ie previous year cost plus this years cost)
Tuesday, May 2, 2023
41
Using LED’sWattage : 18wattsCost : 500per led bulbLife : 50000hrs Usage : 100hrs per month
Total load : 18*750= 13.5KW
Monthly consumption= 1350KWh
Charge for monthly consumption= Rs 8370(6.20per unit)
Annual consumption charge= Rs 100440
Tuesday, May 2, 2023
42
Installation cost : 500*750= Rs 375,000
For the 1st year total cost= Rs 475,440
For 2nd year total cost= Rs 475,440 + Rs 100440 = Rs 575,880
So by replacing tube lights with LED’s we can reduce the monthly consumption by half.
We will get back profits after approx 8 months.
Tuesday, May 2, 2023
43
ENERGY SAVINGS BY AUTOMATIC CONTROLLED FANS
1) Energy savings by controlled fans and conventionally controlled fans= 60w x operating hours (per day per fan) =60W x 10 hours/day =600Wh/day/fan
Energy cost per day per fan =0.6 x 6.20= Rs3.72/- Cost of Energy consumption for 602 fans per day
=Rs3.72x602 = Rs22400/-Annual Cost of Energy consumption by regulator controlled fans
=Rs22400x288days =Rs 645120 -----(1)
Tuesday, May 2, 2023
44
2) Automatic Controlled Fans Can Be Operating Based On User Requirement May Reduce The Operating Time
Let us operate the fans on need basis as remote control is available, it will reduce the operating hours (Assume that the wattage is same) =60W x 7 hr
= 420 Wh/day =0.42 kWh/day = 0.42 x 6.20 = RS 2.6/day
Annual Energy consumption by automatic controlled fan = 2.6x602x288= Rs. 450777-------------(2)
Tuesday, May 2, 2023
45
Cost saving (1)-(2) = Rs 194343
Total cost of additional unit automatic operating switch = Rs.400 x602
=Rs240800
Payback period = 240800/194343=Approx 1 year 2 months
Tuesday, May 2, 2023
46
ENERGY SAVING IN XEROX MACHINEWhich Consume The Energy As Follows Power Consumption of Xerox M/C in Non Operating
Mode = 1x100W =100W (sleep mode)
Energy Saving for Approximate Sleepy Mode Hours For 2hours In A Day =100W x 2hr/day
= 200Wh/Day
Tuesday, May 2, 2023
47
Energy in kWh = 200/1000 = 0.2kWh/day
Energy for a Month = 0.2kWh x 24days =4.8kWh
Units Monthly Energy Cost =4.8x 6.20 =Rs29.76/-
Annual Energy Cost Saving = Rs29.76x12 =Rs 357.12/-
So avoid sleep mode on xerox machines to save Rs 357.12/- per year
Tuesday, May 2, 2023
48
In the campus we are using fluorescent lamps.
As compared with LED the lux produced by fluorescent lamp are low for same wattage.
Exterior lightining of our campus is done using LED’s which is fine.
Tuesday, May 2, 2023
49
POWER FACTOR CALCULATION
We have calculated the pf of pump set with the help of an pf meter.
A 3phase 400V delta connected motor having .79 lag power factor.
Tuesday, May 2, 2023
50
DISADVANTAGES OF LOW PF Large Line Losses (Copper Losses)
Large kVA rating and Size of Electrical Equipments
Greater Conductor Size and Cost
Poor Voltage Regulation and Large Voltage Drop
Low Efficiency
Penalty from Electric Power Supply Company on Low Power factor
Tuesday, May 2, 2023
51
METHODS FOR POWER FACTOR IMPROVEMENT
The following devices and equipment are used for Power Factor Improvement.
Static CapacitorSynchronous CondenserPhase Advancer
Tuesday, May 2, 2023
52
1. Static Capacitor Most of the power system loads are inductive that take
lagging current which decrease the system power factor. For Power factor improvement purpose, Static capacitors are connected in parallel with those devices which work on low power factor.
These static capacitors provides leading current which neutralize (totally or approximately) the lagging inductive component of load current (i.e. leading component neutralize or eliminate the lagging component of load current) thus power factor of the load circuit is improved
Tuesday, May 2, 2023
53
2. Synchronous Condenser When a Synchronous motor operates at No-Load and
over-exited then it’s called a synchronous Condenser. Whenever a Synchronous motor is over-exited then it provides leading current and works like a capacitor.
When a synchronous condenser is connected across supply voltage (in parallel) then it draws leading current and partially eliminates the re-active component and this way, power factor is improved. Generally, synchronous condenser is used to improve the power factor in large industries.
Tuesday, May 2, 2023
54
3. Phase Advancer Phase advancer is a simple AC exciter which is connected on
the main shaft of the motor and operates with the motor’s rotor circuit for power factor improvement. Phase advancer is used to improve the power factor of induction motor in industries.
As the stator windings of induction motor takes lagging current 90° out of phase with Voltage, therefore the power factor of induction motor is low. If the exciting ampere-turns are excited by external AC source, then there would be no effect of exciting current on stator windings. Therefore the power factor of induction motor will be improved. This process is done by Phase advancer
Tuesday, May 2, 2023
55
ENERGY STAR
Tuesday, May 2, 2023
56
ENERGY STAR products are independently certified to save energy without sacrificing features or functionality. Saving energy helps prevent climate change. Look for the ENERGY STAR label to save money on your energy bills and help protect our environment.
The ENERGY STAR label has undergone a process of inspections, testing, and verification to meet strict requirements set by the BEE. ENERGY STAR certified homes use 15-30% less energy than typical new homes while delivering better comfort, quality, and durability.
Improve financial performance and reduce carbon emissions with EPA's strategic energy management approach.
Tuesday, May 2, 2023
57
Tuesday, May 2, 2023
58
Tuesday, May 2, 2023
59
STAR RATING OF BUILDING
The Star Rating Program for buildings is based on actual performance of the building in terms of specific energy usage (kWh/sq.m/year).
In our campus yearly consumption is approx 49660KWh, having a build up area of 15000sq.m.
EPI= 49660KWh/15000sq.m/1year = 3.31.
Tuesday, May 2, 2023
60
As per ECBC standards shown in the table given above our campus is labelled as 5 star building.
EPI (KWh/sq.m/year) Star Label
80-70 1 Star
70-60 2 Star
60-50 3 Star
50-40 4 Star
Below 40 5 Star
Tuesday, May 2, 2023
61
ENERGY CONSERVATIONSElectricity Distribution System
Optimise the tariff structure with utility supplier Schedule your operations to maintain a high load factor Shift loads to off-peak times if possible. Minimise maximum demand by tripping loads through a demand
controller Use standby electric generation equipment for on-peak high load
periods. Correct power factor to at least 0.90 under rated load conditions.
Tuesday, May 2, 2023
62
Consider on-site electric generation or cogeneration.
Export power to grid if you have any surplus in
your captive generation.
Check utility electric meter with your own meter. Shut off unnecessary computers, printers, and
copiers at night.
Tuesday, May 2, 2023
63
Motors Properly size to the load for optimum efficiency.
(High efficiency motors offer of 4-5% higher efficiency than standard motors)
Use energy-efficient motors where economical. Use synchronous motors to improve power factor. Check alignment. Provide proper ventilation (For every 10ºC increase
in motor operating temperature over recommended peak, the motor life is estimated to be halved)
Tuesday, May 2, 2023
64
Check for under-voltage and over-voltage conditions.
Balance the three-phase power supply. (An imbalanced voltage can reduce 3 - 5% in motor input power)
Demand efficiency restoration after motor rewinding. (If rewinding is not done properly, the efficiency can be reduced by 5 - 8%).
Tuesday, May 2, 2023
65
Drives Use variable-speed drives for large variable loads. Use high-efficiency gear sets.
Check belt tension regularly.
Use flat belts as alternatives to v-belts. Use synthetic lubricants for large gearboxes. Shut them off when not needed.
Tuesday, May 2, 2023
66
Pumps Operate pumping near best efficiency point.
Modify pumping to minimize throttling. Use booster pumps for small loads requiring higher
pressures. Repair seals and packing to minimize water waste. Balance the system to minimize flows and reduce pump
power requirements.
Tuesday, May 2, 2023
67
RECOMMENDATIONS & SUGGESTIONS
Replacing Fluorescents lamps with Led’s.
Turn off lights and fans when not in use.
Static capacitor banks are recommended to place parallel with the pump to increase the power factor.
Reschedule the time table to reduce the maximum demand.
Good light ventilation and Air ventilation to classrooms may solve the problem of Energy Consumption.
Tuesday, May 2, 2023
68
Walls should be painted with bright coloured paints (enamel) to get more brightness
Outside lightening of the campus should be placed bit more higher.
Use pumps on the off peak time so that we can reduce the consumption cost. If the securities are available. Fill the tank when once pumps are started.
Tuesday, May 2, 2023
69
Shutdown the computers instead of putting sleep mode when not in use.
Turnoff the Photostat machine instead of putting in sleep mode when not in use.
Fans running without capacitor or under rated capacitor will draw more current therefore use of correct rated capacitor will reduce the power consumption.
Tuesday, May 2, 2023
70
Recommended to use solar water cooler in place of conventional one
All major equipments should run with good power factor and the integration of Instrument to read the P. F online should be made mandatory. Therefore immediate care can be taken to improve the power factor.
Tuesday, May 2, 2023
71
CONCLUSION The Proposed project gives strong warning to the consumer not
only in terms of the energy bills also the energy crisis in the near future to all sectors of people.
This project’s recommendations reduces the around 15-20% of the energy and 25-30% of cost reduction excluding some issues takes more payback period.
There is a scope of improvement to include the advanced lighting scheme to reduce further 10% of the cost