Quick Start Guide Warning Device LAL-**-GSM-Ex3 ENG Document No.: 45-3081A Edition: 03/2010 Copyright Pepperl+Fuchs www.pepperl-fuchs.com Pepperl+Fuchs GmbH Lilienthalstrasse 200 68307 Mannheim, Germany Tel. +49 621 776-0 Fax. +49 621 776-1000 Important The manual always takes priority over this quick start guide, which is only intended to provide a brief overview of the warning device functions. Refer to the manual for more detailed information about the warning device. The corresponding safety chapter in this manual is an integral component of this document. Make sure the information in the safety chapter is read and understood. Device Components Antenna Reset button Send/State button New Installation and Commissioning 1 2 3 4 5 6 7 8 9 * 0 # Insert the SIM card for the warning device in the cellular phone. Change the PIN code on the SIM card to the default PIN code 1 2 3 4. Further Configuration via cellular phone via SMS commands 1 2 3 4 5 6 7 8 9 * 0 # Insert the SIM card in the warning device. Insert the SIM card in the cellular phone. Switch on the warning device. Configure the SIM card. System OK / SMS flashes Save the telephone number of the warning device. OWN +XXYYYYYYY Sensor off Save the telephone number of the first recipient: PERSON1 +XXYYYYYYY Alarm off Save additional telephone numbers: PERSON2 +XXYYYYYYY PERSON3 +XXYYYYYYY System OK/SMS LED flashes 80 to 100 times or for one minute. System OK / SMS off Sensor lights up Alarm flashes Insert the SIM card in the warning device. Send an SMS command. SET TIME SET OWN +XXYYYYYYY Switch on the warning device. Telephone number of the warning device SET P1 +XXYYYYYYY Telephone number of PERSON1 Send additional telephone numbers for PERSON2 and PERSON3. System OK / SMS flashes Sensor off Alarm off System OK/SMS LED flashes. Do not press any buttons during the start phase! Normal indication system OK Indication if supply voltage too low Indication after alarm or error System OK / SMS lights up System OK / SMS off System OK / SMS off Sensor off Sensor off Sensor lights up Alarm off Alarm flashes once Alarm flashes 1 ... 5 times 1 x Battery voltage for warning device LAL-A8-GSM-Ex3 (battery version) is too low. 1 x Internal communication error – repairs required 2 x Network error – check transmission quality Change the battery. Restart if necessary. 3 x SIM card missing or inactive – insert SIM card or load up calling credit (Prepaid SIM card) 4 x SIM card locked – check PIN code 5 x Telephone number for OWN or PERSON1 is missing or incorrect Identify the cause, correct the error Restart if necessary. Oil Separator West SQ: 5 BL: 9.5 V Day: WED Time: 10:28 Save the sensor configuration 2 1 1 2 0 1 2 3 4 t Oil Separator West S1: OIL OK S2: LEVEL OK S3: SLUDGE OK SV: LOW Always check to ensure that the sensor specifications in the received status message correspond with the actual configuration. Configuration and Operating Instructions Programming the SIM Card Switch off the supply voltage before inserting or removing the SIM card. The warning device will not function and cannot be tested without a SIM card. When using your own cellular phone to configure the SIM card on the warning device, remember to store the information on the SIM card and not on the memory of the cellular phone. If you do not wish to configure the SIM card using a cellular phone, you have the option of using a USB SIM card reader for a PC. Always use uppercase letters, e. g., PERSON. Enter the corresponding country code in front of all telephone numbers (+44 for United Kingdom, +49 for Germany, etc.). Do not enter a space, 0 or 00 in front of the country code. Do not include any spaces or special characters in telephone numbers. Enter (a minimum of) PERSON1 with corresponding telephone number in the telephone book on the warning device SIM card or PERSON1 and PERSON2 or PERSON1, PERSON2 and PERSON3 Never program PERSON2 without any details. Changing the Battery for LAL-A8-GSM-Ex (Battery Version) Press the State/Send button for approx. 3 seconds after removing the old but before inserting the new battery. Test Mode If an LAL9-D-Ex sludge level sensor is connected, TestMode appears when the first SMS message is sent to the warning device. In test mode, the sludge level sensor responds immediately when an alarm status is active. Test mode remains active for about 10 minutes, after which the warning device switches back to normal mode automatically. Test mode can be activated for checking purposes, for example, by sending the SMS command SET TEST ON. Send the SMS command SET TEST OFF to deactivate test mode. Sensor 1 Sensor 2 Sensor 3 LAL-A6-GSM-Ex3 230 V AC LAL-A8-GSM-Ex3 Battery LAL-D2-GSM-Ex3 12 V DC ... 30 V DC Power supply: SIM card LED indicator System OK / SMS Sensor Alarm

Upload: vungoc

Post on 09-Jul-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Quick Start Guide

Warning DeviceLAL-**-GSM-Ex3

ENG

Document No.: 45-3081AEdition: 03/2010

Copyright Pepperl+Fuchswww.pepperl-fuchs.com

Pepperl+Fuchs GmbHLilienthalstrasse 20068307 Mannheim, GermanyTel. +49 621 776-0Fax. +49 621 776-1000

ImportantThe manual always takes priority over this quick start guide, which is only intended to provide a brief overview of the warning device functions. Refer to the manual for more detailed information about the warning device.

The corresponding safety chapter in this manual is an integral component of this document. Make sure the information in the safety chapter is read and understood.

Device Components

AntennaResetbutton

Send/Statebutton

New Installation and Commissioning

1 2 34 5 67 8 9

* 0 #

Insert the SIM card for the warning device in the cellular phone.

Change the PIN code on the SIM card to the default PIN code 1 2 3 4.

Further Confi guration

via cellular phone via SMS commands

1 2 34 5 67 8 9

* 0 #

Insert the SIM card in the warning device.

Insert the SIM card in the cellular phone.

Switch on the warning device.

Confi gure the SIM card. System OK / SMS fl ashes

Save the telephone number of the warning device. OWN +XXYYYYYYY

Sensor off

Save the telephone number of the fi rst recipient:PERSON1 +XXYYYYYYY

Alarm off

Save additional telephone numbers: PERSON2 +XXYYYYYYY PERSON3 +XXYYYYYYY

System OK/SMS LED fl ashes 80 to 100 times or for one minute.

System OK / SMS off

Sensor lights up

Alarm fl ashes

Insert the SIM card in the warning device.

Send an SMS command.

SET TIME

SET OWN +XXYYYYYYY

Switch on the warning device.Telephone number of the warning device

SET P1 +XXYYYYYYY

Telephone number of PERSON1Send additional telephone numbers for PERSON2 and PERSON3.System OK / SMS fl ashes

Sensor off

Alarm off

System OK/SMS LED fl ashes.Do not press any buttons during the start phase!

Normal indicationsystem OK

Indication if supply voltage too low

Indication after alarm or error

System OK / SMS lights up System OK / SMS off System OK / SMS off

Sensor off Sensor off Sensor lights up

Alarm off Alarm fl ashes once Alarm fl ashes 1 ... 5 times

1 x Battery voltage for warning device LAL-A8-GSM-Ex3 (battery version) is too low.

1 x Internal communication error – repairs required

2 x Network error – check transmission quality

Change the battery.Restart if necessary.

3 x SIM card missing or inactive – insert SIM card or load up calling credit (Prepaid SIM card)

4 x SIM card locked – check PIN code

5 x Telephone number for OWN or PERSON1 is missing or incorrect

Identify the cause, correct the errorRestart if necessary.

Oil Separator West

SQ: 5BL: 9.5 VDay: WEDTime: 10:28

Save the sensor confi guration

2

1

1

2

0 1 2 3 4 t

Oil Separator West

S1: OIL OKS2: LEVEL OKS3: SLUDGE OKSV: LOW

Always check to ensure that the sensor specifi cations in the received status message correspond with the actual confi guration.

Confi guration and Operating Instructions

Programming the SIM Card• Switch off the supply voltage before inserting or removing the SIM card.

• The warning device will not function and cannot be tested without a SIM card.

• When using your own cellular phone to confi gure the SIM card on the warning device, remember to store the information on the SIM card and not on the memory of the cellular phone.

• If you do not wish to confi gure the SIM card using a cellular phone, you have the option of using a USB SIM card reader for a PC.

• Always use uppercase letters, e. g., PERSON.

• Enter the corresponding country code in front of all telephone numbers (+44 for United Kingdom, +49 for Germany, etc.). Do not enter a space, 0 or 00 in front of the country code.

• Do not include any spaces or special characters in telephone numbers.

• Enter (a minimum of) PERSON1 with corresponding telephone number in the telephone book on the warning device SIM card orPERSON1 and PERSON2 orPERSON1, PERSON2 and PERSON3

Never program PERSON2 without any details.

Changing the Battery for LAL-A8-GSM-Ex (Battery Version)• Press the State/Send button for approx. 3 seconds after removing the old but

before inserting the new battery.

Test Mode• If an LAL9-D-Ex sludge level sensor is connected, TestMode appears when the

fi rst SMS message is sent to the warning device. In test mode, the sludge level sensor responds immediately when an alarm status is active.

• Test mode remains active for about 10 minutes, after which the warning device switches back to normal mode automatically. Test mode can be activated for checking purposes, for example, by sending the SMS command SET TEST ON. Send the SMS command SET TEST OFF to deactivate test mode.

Sen

sor

1

Sen

sor

2

Sen

sor

3

LAL-A6-GSM-Ex3 230 V ACLAL-A8-GSM-Ex3 BatteryLAL-D2-GSM-Ex3 12 V DC ... 30 V DC

Power supply:

SIM card

LED indicator

System OK / SMS

Sensor

Alarm

LED Indicator

The LEDs do not light up.

System OK / SMS off

Sensor off

Alarm off

The warning devices LAL-A8-GSM-Ex3 (battery version) and LAL-D2-GSM-Ex3 (DC version) are operating in sleep mode (energy-saving).

Press the State/Send button for approx. 4 seconds. The current status is displayed.

No active alarms or errors

System OK / SMS lights up

Sensor off

Alarm off

SMS message sent System OK / SMS flashes once

Sensor off

Alarm off

Previous alarms or errors

System OK / SMS flashes

Sensor off

Alarm off

An alarm or error occurred previously – identify the cause, correct the error.

Briefly press the Reset button once. System OK/SMS LED lights up.

Communication via SMS

1 2 34 5 67 8 9

* 0 #

Status of SensorsSEND SSTATUS

Oil Separator West

S1: OIL OKS2: LEVEL OKS3: SLUDGE OKSV: LOW

S1, S2, S3 Sensor 1, sensor 2 and sensor 3

SV Supply voltage OK or LOW (only on warning device LAL-A8-GSM-Ex3 (battery version))

Status of the Warning DeviceSEND DSTATUS

Oil Separator West

SQ: -81 dBmBL: 9.14 VDay: THUTime: 07:09TestMode

SQ Signal strength 2 ... 10 (best value 10) orSignal strength -50 dBM ... -100 dBM (best value -50 dBM)

BL Battery voltage (only on warning device LAL-A8-GSM-Ex3 (battery version))

Day Displays the day when the SMS message was sent

Time Displays the time when the SMS message was sent

TestMode only when sludge level sensor LAL9-D-Ex is connected

Current ConfigurationSEND SETUP

Oil Separator West

OWN: +4940496097PERSON1: +4930941335PERSON2: +49178155054MDELAY: 0STATUS: WED. 12:00

OWN Telephone number of the warning device

PERSON1 Telephone number of PERSON1

PERSON2 Telephone number of PERSON2

PERSON3 Telephone number of PERSON3

MDELAY

Measured delay in sleep mode (energy-saving) (only with warning devices LAL-A8-GSM-Ex3 (battery version) and LAL-D2-GSM-Ex3 (DC version)); 0, 5, 10 ... Minutes

STATUS Time of the continuous status message, day of the week and time specified

Setting the TimeSET TIME

Oil Separator West

OWN: +4940496097PERSON1: +4930941335PERSON2: +49178155054MDELAY: 0STATUS: WED. 12:00

Adjust the time on the warning device (e. g., when changing to daylight saving time)

SMS Counter Overflow

Oil Separator West

SMS LIMIT ERROR

More than 5 SMS messages/hour. The warning device stops sending SMS messages. Reset the SMS counter with:

RESET SMS COUNTER

Alarm or error indication for sensors

System OK / SMS off

Sensor flashes 1 ... 3 times

Alarm flashes 1 ... 3 times

Sensor LED

1 x Sensor 1

2 x Sensor 2

3 x Sensor 3

Alarm LED

1 x Sensor in alarm

2 x Sensor error

3 x Communication error between sensor and warning device

The oil/petrol separator, sensor and associated installation must be checked and repaired or replaced if necessary.

Fault indication for SIM card or warning device

System OK / SMS off

Sensor lights up

Alarm flashes 1 ... 5 times

1 x Internal communication error – repairs required

2 x Network error – check transmission quality

3 x SIM card missing or inactive – insert SIM card or load up calling credit (Prepaid SIM card)

4 x SIM card locked – check PIN code

5 x Telephone number for OWN or PERSON1 is missing or incorrect

Identify the cause, correct the error

Battery or SMS warning

System OK / SMS off

Sensor off

Alarm flashes once or twice

1 x Battery voltage for warning device LAL-A8-GSM-Ex3 (battery version) is too low – change the battery

2 x SMS limit error – Identify the cause, correct the error, reset the SMS counter

Briefly press the Reset button once. The SMS counter is reset.