RESIDENTIAL ROOFING Espan 340™ / 470™ 0800 ROOFNZ (0800 766 369) www.metalcraftgroup.co.nz Architectural / Specification Enquiries Ph: 09 274 0408 Mobile: 027 603 1096 Email: [email protected] RREP 00 / 20 COVER SHEET 01 / 20 RIDGE FLASHING 02 / 20 SAWTOOTH RIDGE 03 / 20 SAWTOOTH EAVE 04 / 20 ROOF VALLEY 05 / 20 ROOF - CHANGE PITCH 06 / 20 EAVE WITH ROUND GUTTER 07 / 20 EAVE WITH SQUARE GUTTER 08 / 20 BARGE FLASHING 09 / 20 PARAPET WITH TRANSVERSE APRON 10 / 20 TRANSVERSE APRON 11 / 20 PARALLEL APRON 12 / 20 MAX. 85mm DIAMETER PIPE PENETRATION 13 / 20 OVER 85mm DIAMETER PIPE PENETRATION 14 / 20 3D RIDGE TO BARGE JUCTION 15 / 20 3D DUTCH GABLE 16 / 20 3D APRON 17 / 20 3D OVER 85mm DIAMETER PIPE PENETRATION 18 / 20 3D CHIMNEY PENETRATION 19 / 20 3D RIDGE/BARGE FLASHINGS 20 / 20 3D DUTCH GABLE FLASHINGS DETAIL LIST

Upload: others

Post on 24-Jul-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

RESIDENTIAL ROOFING

Espan 340™ / 470™

0800 ROOFNZ (0800 766 369)www.metalcraftgroup.co.nz

Architectural / Specification EnquiriesPh: 09 274 0408

Mobile: 027 603 1096Email: [email protected]

00 / 20 COVER SHEET01 / 20 RIDGE FLASHING02 / 20 SAWTOOTH RIDGE03 / 20 SAWTOOTH EAVE04 / 20 ROOF VALLEY05 / 20 ROOF - CHANGE PITCH06 / 20 EAVE WITH ROUND GUTTER07 / 20 EAVE WITH SQUARE GUTTER08 / 20 BARGE FLASHING09 / 20 PARAPET WITH TRANSVERSE APRON10 / 20 TRANSVERSE APRON11 / 20 PARALLEL APRON12 / 20 MAX. 85mm DIAMETER PIPE PENETRATION13 / 20 OVER 85mm DIAMETER PIPE PENETRATION14 / 20 3D RIDGE TO BARGE JUCTION15 / 20 3D DUTCH GABLE16 / 20 3D APRON17 / 20 3D OVER 85mm DIAMETER PIPE PENETRATION18 / 20 3D CHIMNEY PENETRATION19 / 20 3D RIDGE/BARGE FLASHINGS20 / 20 3D DUTCH GABLE FLASHINGS

DETAIL LIST

Page 2: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

PRE-FINISHED RIDGE CAP FLASHING

STOPENDS TO ROOF CLADDING

ROOF FRAMING

PURLIN

METALCRAFTESPAN™ROOFING

METALCRAFT ESPAN™CLIP SYSTEM WITH12G x 35mm SCREWSPERMEABLE

UNDERLAY,SHOWN DASHED

PRE-FINISHED POP RIVETBEDDED IN SILICONE ORPRE-FINISHED 8g WAFER-TEK SCREW

PRE-FINISHEDSECRET FLASHING

ALTERNATIVE OPTION - A

POP RIVET

ALTERNATIVE OPTION - B

5mm EXPANSION GAP AROUND

SECONDARYFLASHING

FOLDED

X

POP RIVETALTERNATIVESECRET FLASHING

5mm

GAP

5mm

GAP

5 mm

GAP

* ESPAN™ MIN. ROOF PITCH = 3°

3.0 0

°

5mm

GAP

X X

OPTIONAL SITUATION 1

1. LOW, MEDIUM, HIGH WIND ZONES2. ROOF PITCH ≥ 10°

MIN. 130mm(EXCLUDDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

X

PLEASE REFER TO E2 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.

ACCEPTABLE SOLUTION AS PER E2/AS1

CATEGORY A

1. NORMAL EXPOSURE2. ROOF PITCH > 10°

MIN. 130mmX

CATEGORY B

1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5kPa2. ROOF PITCH < 10°

MIN. 200mm

ALTERNATIVE SOLUTION AS PER MRM CODE OF PRACTICE

SITUATION 2

1. ALL ROOF PITCHES IN VERY HIGHWIND ZONE2. LOW, MEDIUM, HIGH WIND ZONESWHERE ROOF PITCH ≤ 10°

MIN. 200mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

SITUATION 3

1. FOR ALL ROOF PITCHES INEXTRA HIGH WIND ZONES

MIN. 200mm(EXCLUDING ANY SOFT EDGEOR TURN-DOWN TO ROOFING)

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

RIDGE FLASHING

01 / 202018

Page 3: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

PRE-FINISHED SAWTOOTHRIDGE CAP FLASHING.

STOPENDS TO ROOF CLADDING

PERMEABLE UNDERLAY, SHOWNDASHED

PURLINMETALCRAFT ESPAN™CLIP SYSTEM WITH12G x 35mm SCREWS

ROOF OR WALL FRAMING

PERMEABLE WALL UNDERLAY,SHOWN DASHED

PRE-FINISHED POP RIVETBEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

METALCRAFT ESPAN™ ROOFING

5 m

m G

AP

5mm EXPANSION GAP AROUND

ALTERNATIVE OPTION - A

POP RIVET

FOLDED

ALTERNATIVE OPTION - B

POP RIVET

ALTERNATIVESECRET FLASHING

* ESPAN™ MIN. ROOF PITCH = 3°

3.0 0

°

METALCRAFT ESPAN™CLADDING ON CAVITY

Z

POP RIVET

X

5mm GAP

SEPERATE BATTEN ANDCLADDING AS REQUIREDWITH DPC

COMPRESSIBLEFOAM SEAL. REFERTO MRM CODE OFPRACTICE VERSIOM2.2/2012 FORREQUIREMENT

5mm GAP 5mm GAP

5mm

GAP

5mm

GAP

X X

SITUATION 1

1. LOW, MEDIUM, HIGH WIND ZONES,WHERE ROOF PITCH ≥ 10°

MIN. 130mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

MIN. 50mm

SITUATION 2

1. ALL ROOF PITCHES INVERY HIGHWIND ZONE2. LOW, MEDIUM AND HIGH WINDZONES WHERE ROOF PITCH ≤ 10°

MIN. 200mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

MIN. 70mm

X

Z

SITUATION 3

1.ALL ROOF PITCHES IN EXTRA HIGHWIND ZONE

MIN. 200mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

MIN. 90mm

CATEGORY A

1. NORMAL EXPOSURE2. ROOF PITCH >10°

MIN. 130mm

MIN. 50mm(VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm(VERTICALLY DOWN FACE - PROFILED)

CATEGORY B

1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°

MIN. 200mm

MIN. 75mm(VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)

X

Z

ACCEPTABLE SOLUTION AS PER E2/ASI

ALTERNATIVE SOLUTION AS PER MRM CODE OF PRACTICE

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

SAWTOOTH RIDGE

02 / 202018

Page 4: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

TIMBER FASCIA

SOFFIT LINING

METALCRAFT ESPAN™ ROOFING

PERMEABLE UNDERLAY, SHOWNDASHED

PURLIN

PRE-FINISHED SAWTOOTHRIDGE CAP FLASHING

METALCRAFT ESPAN™CLIP SYSTEM WITH12G x 35mm SCREWS

ROOF FRAMING

PRE-FINISHED POP RIVET BEDDED INSILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

Z

PRE-FINISHED 8g WAFER-TEKSCREW BEDDED IN SILICONE

HEMMED EDGE

STOPENDS TO ROOFCLADDING

ALTERNATIVE OPTION - A

POP RIVET

FOLDED

ALTERNATIVE OPTION - B

POP RIVET

ALTERNATIVESECRETFLASHING

Z

X

SECONDARY FLASHING

X* ESPAN™ MIN. ROOF PITCH = 3°

3.0 0

°

5mm EXPANSION GAP AROUND

5mm

GAP

DIRECT FIX

X

SITUATION 1

1. LOW, MEDIUM, HIGH WIND ZONES,WHERE ROOF PITCH ≥ 10°

MIN. 130mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

MIN. 50mm

SITUATION 2

1. ALL ROOF PITCHES INVERY HIGHWIND ZONE2. LOW, MEDIUM AND HIGH WINDZONES WHERE ROOF PITCH ≤ 10°

MIN. 200mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

MIN. 70mm

X

Z

SITUATION 3

1.ALL ROOF PITCHES IN EXTRA HIGHWIND ZONE

MIN. 200mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

MIN. 90mm

CATEGORY A

1. NORMAL EXPOSURE2. ROOF PITCH >10°

MIN. 130mm

MIN. 50mm(VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm(VERTICALLY DOWN FACE - PROFILED)

CATEGORY B

1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°

MIN. 200mm

MIN. 75mm(VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)

X

Z

ACCEPTABLE SOLUTION AS PER E2/ASI

ALTERNATIVE SOLUTION AS PER MRM CODE OF PRACTICE

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

SAWTOOTH EAVE

03 / 202018

Page 5: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

ROOF FRAMING

PURLIN

METALCRAFT ESPAN™ROOFING

METALCRAFT ESPAN™CLIP SYSTEM WITH 12G x35mm SCREWS

PERMEABLE UNDERLAYCONTINUOUS UNDER GUTTER IFCOPPER BASED TREATMENTS AREUSED

VALLEY BOARD

PREFINISHED VALLEY GUTTER

CC

B : CLEARANCE BETWEEN ROOFING

A : OVERALL VALLEY GUTTER WIDTH

MIN

. 20mm

MAX. 60mmMIN. 30mm

5mm EXPANSION GAP AROUND

MIN

. 10mm

GAP

C

MAX. 60mmMIN. 30mm

MIN

. 50m

m

MIN

. 50m

m

ALTERNATIVE OPTION - A

SITUATION 1

MAX. CATCHMENT 25m²MIN. ROOF PITCH 8°

MIN. 250mm

MIN. 50mm

MIN. 80mm

SITUATION 2

MAX. CATCHMENT 16m²MIN. ROOF PITCH 12.5°

160mm - 249mm

MIN. 40mm

MIN. 60mm

A

B

C

ACCEPTABLE SOLUTION AS PER E2/ASI

ALTERNATIVE SOLUTION AS PER MRM CODE OF PRACTICE

ROOF PITCH

8 - 12°

12 - 35°

> 35°

TYPE B

MIN. 75mm

MIN. 50mm

MIN. 50mm

TYPE C

MIN. 75mm

MIN. 70mm

MIN. 70mm

* ROOF PITCH FOR VALLEYS AS PER E2.

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

ROOF VALLEY

04 / 202018

Page 6: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

PURLIN

METALCRAFT ESPAN™ROOFING

METALCRAFT ESPAN™CLIP SYSTEM WITH 12G x35mm SCREWS

PURLIN

ROOF FRAMING

PRE-FINISHED CHANGE OF ROOFPITCH FLASHING

PERMEABLE UNDERLAYCONTINUOUS OVERFLASHING, SHOWN DASHED

PERMEABLE UNDERLAYCONTINUOUS UNDER FLASHING,SHOWN DASHED

10.0

MIN. 250mm

CLEARANCE

MIN. 10mm

X

METALCRAFT ESPAN™ CLIPSYSTEM WITH 12G x 35mm SCREWS

STST OR GALV. FLAT HEADNAIL FOR FLASHING

PRE-FINISHED POP RIVET BEDDED IN SILICONEOR PRE-FINISHED 8g WAFER-TEK SCREW

METALCRAFT ESPAN™ ROOFING.STOPENDS TO ROOF CLADDING

POP RIVET

FOLDED

ALTERNATIVE OPTION - A ALTERNATIVE OPTION - B

POPRIVET

ALTERNATIVESECRET FLASHING

* ESPAN MIN. ROOF PITCH = 3°

TM

45.0

5mm

GAP

5mm

GAP

5mm EXPANSION GAP AROUND

X X

SITUATION 1

1. LOW, MEDIUM, HIGH WIND ZONES2. ROOF PITCH ≥ 10°

MIN. 130mm(EXCLUDDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

X

PLEASE REFER TO E2 FOR FURTHER INFORMATION ON FLASHING COVER WIDTHS.

ACCEPTABLE SOLUTION AS PER E2/AS1

CATEGORY A

1. NORMAL EXPOSURE2. ROOF PITCH > 10°

MIN. 130mmX

CATEGORY B

1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5kPa2. ROOF PITCH < 10°

MIN. 200mm

ALTERNATIVE SOLUTION AS PER MRM CODE OF PRACTICE

SITUATION 2

1. ALL ROOF PITCHES IN VERY HIGHWIND ZONE2. LOW, MEDIUM, HIGH WIND ZONESWHERE ROOF PITCH ≤ 10°

MIN. 200mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

SITUATION 3

1. FOR ALL ROOF PITCHES INEXTRA HIGH WIND ZONES

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

ROOF - CHANGE PITCH

05 / 202018

Page 7: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

METALLINE™ QUAD GUTTER

METALLINE™ QUAD GUTTERINTERNAL BRACKET

SOFFIT LINING

TIMBER ROOF FRAMING

METALCRAFT ESPAN™ROOFING

PERMEABLE UNDERLAY,SHOWN DASHED

TIMBER PURLIN

REFER TO SHEET NO.10A/24FOR ALTERNATIVE FLASHINGOPTION.

METALCRAFT ESPAN™ CLIPSYSTEM WITH 12G x 35mm SCREWS

STST OR GALV. FLAT HEAD NAIL FORFLASHING

PRE-FINISHED 8g WAFER-TEK SCREW

ALTERNATIVE OPTION - A

* ESPAN™ MIN. ROOF PITCH = 3°

3 .0 0°

ALTERNATIVE OPTION - B

5mm EXPANSION GAP AROUND

MIN.125mm

OR AS REQUIREDMIN. 50mm

TIMBER FASCIA

MIN. 125mm

OR AS REQUIREDMIN. 50mm

SNOW STRAP ASREQUIRED

OVE

RLA

P

MIN

. 35m

m

OVE

RLA

P

MIN

. 35m

m

EAVE FLASHING REQUIRED WHEN ALL OF THEFOLLOWING CONDITIONS ARE MET:- ROOF PITCH ≤ 3°, AND- SOFFIT WIDTH ≤ 100mm, AND- WIND ZONES = VERY HIGH OR EXTRA HIGH OR- ENGINEER SPECIFIC DESIGN- MRM RECOMMENDS TO USE IN AREAS EXPOSED TO CONTAMINATORS SUCH AS SEA SALT OR INDUSTRIAL POLLUTANTS

MIN. 125mm

OR AS REQUIREDMIN. 50mm

METALLINE™ FASCIA

OVE

RLA

P

MIN

. 35m

m

*DETAILS APPLY TO ALL METALCRAFT GUTTERS

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

EAVE WITH ROUND GUTTER

06 / 202018

Page 8: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

BOX GUTTER 125 WITHEXTERNAL BRACKET

METALCRAFT ESPAN™ROOFING

PERMEABLE UNDERLAY,SHOWN DASHED

STST OR GALV. FLAT HEADNAIL FOR FLASHING

PRE-FINISHED EAVEFLASHING ALTERNATIVEOPTION

METALCRAFT ESPAN™ CLIPSYSTEM WITH 12G x 35mm SCREWS

TIMBER PURLIN

PRE-FINISHED 8g WAFER-TEK SCREW

* ESPAN™ MIN. ROOF PITCH = 3°

3 .0 0° MIN. 125mm

OR AS REQUIREDMIN. 50mm

5mm EXPANSION GAP AROUND

ALTERNATIVE OPTION - A ALTERNATIVE OPTION - B

METALLINE™ FASCIA

MIN. 125mm

OR AS REQUIREDMIN. 50mm

MIN. 125mm

OR AS REQUIREDMIN. 50mm

5mm GAPPRE-FINISHED FLASHING

OVE

RLA

P

MIN

. 35m

m

OVE

RLA

P

MIN

. 35m

m

OVE

RLA

P

MIN

. 35m

m

EAVE FLASHING REQUIRED WHEN ALL OF THEFOLLOWING CONDITIONS ARE MET:- ROOF PITCH ≤ 3°, AND- SOFFIT WIDTH ≤ 100mm, AND- WIND ZONES = VERY HIGH OR EXTRA HIGH OR- ENGINEER SPECIFIC DESIGN- MRM RECOMMENDS TO USE IN AREAS EXPOSED TO CONTAMINATORS SUCH AS SEA SALT OR INDUSTRIAL POLLUTANTS

*DETAILS APPLY TO ALL METALCRAFT GUTTERS

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

EAVE WITH SQUARE GUTTER

07 / 202018

Page 9: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

PERMEABLE UNDERLAY,SHOWN DASHED

PURLIN

PRE-FINISHED 12gx55mmWAFER-TEK WITH WASHER

BARGE BOARD

METALCRAFT ESPAN™ ROOFING

PRE-FINISHED POP RIVET BEDDED IN SILICONEOR PRE-FINISHED 8g WAFER-TEK SCREW

5mm

GAP

FOR SET OUT TO BE SYMMETRICAL

THIS DIMENSION TO BE EQUAL ON BOTH SIDES OF ROOF BARGE

FOLDED METALCRAFTESPAN™ ROOFING

5 GAP

20

15

ALTERNATIVE OPTIONBIRDS BEAK EDGE

5mm

GAP

ALTERNATIVE OPTION - A

Z

5mm

GAP

ALTERNATIVE OPTION - C

FOLDED 'U' CHANNEL FOLDED 'U' CHANNEL

BARGE BOARD5m

m G

AP

ALTERNATIVE OPTION - B

FOLDED 'U' CHANNEL

Z

Z

DIRECT FIX

SITUATION 1

1. LOW, MEDIUM, HIGH WIND ZONESWHERE ROOF PITCH ≥ 10°

AT LEAST TWO CRESTS

MIN. 50mm

SITUATION 2

1. ALL ROOF PITCHES IN VERY HIGHWIND ZONE2. LOW, MEDIUM AND HIGH WNDZONES WHERE ROOF PITCH ≤ 10°

AT LEAST TWO CRESTS

MIN. 70mm

Y

Z

SITUATION 3

1.ALL ROOF PITCHES IN EXTRAHIGH WIND ZONE.

AT LEAST TWO CRESTS

MIN. 90mm

CATEGORY A

1. NORMAL EXPOSURE2. ROOF PITCH >10°

ONE RIB (TRAPEZOIDAL & TRAY)2 CORRUGATIONS

MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm (VERTICALLY DOWN FACE - PROFILED)

CATEGORY B

1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°

ONE RIB, TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS

MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm (VERTICALLY DOWN FACE - PROFILED)

Y

Z

ALTERNATIVE SOLUTION AS PER MRM CODE OF PRACTICE

ACCEPTABLE SOLUTION AS PER E2/ASI

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

BARGE FLASHING

08 / 202018

Page 10: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

METALCRAFT ESPAN™ CLIPSYSTEM WITH 12G x 35mm SCREWS

PERMEABLEUNDERLAY, SHOWNDASHED

PRE-FINISHED PARAPETCAP FLASHING

PERMEABLE UNDERLAY TOPROVIDE SEPARATION OF METALCAPPING AND TIMBER, SHOWNDASHED

PURLIN

PRE-FINISHED POP RIVETBEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEKSCREW

METALCRAFT ESPAN™ ROOFING

PERMEABLE UNDERLAY, SHOWNDASHED

WALL FRAMINGROOF FRAMING

TIMBER NOG FORFIXING APRONFLASHING

CONTINUOUS TIMBER PACKING

MIN

. 5.0

Z

GN

STST OR GALV.FLAT HEAD NAILFOR FLASHING

PRE-FINISHEDSELFDRILLING/TAPPINGSCREW WITHRUBBER WASHER

PRE-FINISHED APRON FLASHING.NOTCHED EDGE OVER ESPAN™RIBS. REFER TO SHEET NO. 01A/24FOR ALTERNATIVE OPTION.

POP RIVET

ALTERNATIVE SECRETFLASHING

ALTERNATIVE OPTION - A ALTERNATIVE OPTION - B

POP RIVET

FOLDED

* ESPAN™ MIN. ROOF PITCH = 3°

3.0 0

°

5mm

GAP

5mm

GAP

L

5mm EXPANSION GAP AROUND

METALCRAFTESPAN™CLADDING ONCAVITY

POP RIVET

LL

5mm

GAP

5mm GAP

SITUATION 1

1. LOW, MEDIUM, HIGH WIND ZONES,WHERE ROOF PITCH ≥ 10°

MIN. 35mm

MIN. 75mm

MIN. 130mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

MIN. 50mm

SITUATION 2

1. ALL ROOF PITCHES IN VERY HIGHWIND ZONE2. LOW, MEDIUM, & HIGH WINDZONES WHERE ROOF PITCH ≤ 10°

MIN. 35mm

MIN. 75mm

MIN. 200mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

MIN. 70mm

G

N

L

Z

SITUATION 3

1. ALL ROOF PITCHES IN EXTRAHIGH WIND ZONE

MIN. 35mm

MIN. 75mm

MIN. 200mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

MIN. 90mm

CATEGORY A

1. NORMAL EXPOSURE2. ROOF PITCH >10°

25mm

MIN. 50mm + HEM OR 75mm(VERTICALLY UP FACE - SMOOTH)MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - PROFILED)

MIN. 150mm

MIN. 50mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 75mm (VERTICALLY DOWN FACE - PROFILED)

CATEGORY B

1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°

25mm

MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - SMOOTH)MIN. 100mm + HEM OR 125mm(VERTICALLY UP FACE - PROFILED)

MIN. 200mm

MIN. 75mm (VERTICALLY DOWN FACE - SMOOTH)MIN. 100mm(VERTICALLY DOWN FACE - PROFILED)

G

N

L

Z

ALTERNATIVE SOLUTION AS PER MRM CODE OF PRACTICE

ACCEPTABLE SOLUTION AS PER E2/ASI

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

PARAPET WITH TRANSVERSE APRON

09 / 202018

Page 11: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

GN

STOPENDS TO ROOF CLADDING

ROOF FRAMING

PERMEABLE UNDERLAY,SHOWN DASHED

PVC CAVITY CLOSER

WALL CLADDING ON CAVITY

CANT STRIP PACKER

NOG FOR FIXING APRONFLASHING

STST OR GALV. FLAT HEADNAIL FOR FLASHING

METALCRAFT ESPAN™ CLIP SYSTEMWITH 12G x 35mm SCREWS

METALCRAFT ESPAN™ ROOFING

PRE-FINISHED POP RIVETBEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

PRE-FINISHED APRONFLASHING

EXTRA PERMEABLE UNDERLAYOVER FLASHING, SHOWNDASHED

PURLIN

NOTCHED EDGE OVER ESPAN™RIBS. REFER TO SHEET NO. 14A/24FOR ALTERNATIVE OPTION.

ALTERNATIVE OPTION - A

POP RIVET

FOLDED

* ESPAN™ MIN. ROOF PITCH = 3°

3.0 0

°

5mm

GAP

5mm

GAP

5mm EXPANSION GAP AROUND

POP RIVET

ALTERNATIVE OPTION - B

ALTERNATIVESECRET FLASHING

L L

L

5mm

GAP

SITUATION 1

1. LOW, MEDIUM, HIGH WIND ZONES,WHERE ROOF PITCH ≥ 10°

MIN. 35mm

MIN. 75mm

MIN. 130mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

SITUATION 2

1. ALL ROOF PITCHES IN VERY HIGHWIND ZONES2. LOW, MEDIUM, AND HIGH WINDZONES WHERE ROOF PITCH ≤ 10°

MIN. 35mm

MIN. 75mm

MIN. 200mm(EXCLUDING ANY SOFT EDGE ORTURN-DOWN TO ROOFING)

G

N

L

SITUATION 3

1. ALL ROOF PITCHES IN EXTRA HIGHWIND ZONE

MIN. 35mm

MIN. 200mm(EXCLUDING ANY SOFT EDGE OR TURN-DOWN TO ROOFING)

CATEGORY A

1. NORMAL EXPOSURE2. ROOF PITCH >10°

25mm

MIN. 50mm + HEM OR 75mm(VERTICALLY UP FACE - SMOOTH)MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - PROFILED)

MIN. 150mm

CATEGORY B

1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°

25mm

MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - SMOOTH)MIN. 100mm + HEM OR 125mm(VERTICALLY UP FACE - PROFILED)

MIN. 200mm

G

N

L

ALTERNATIVE SOLUTION AS PER MRM CODE OF PRACTICE

ACCEPTABLE SOLUTION AS PER E2/ASI

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

TRANSVERSE APRON

10 / 202018

Page 12: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

PRE-FINISHED APRON SECRETGUTTER FLASHING

PRE-FINISHED 12gx55mmWAFER-TEK WITH WASHER

PURLIN

PRE-FINISHEDAPRON FLASHING

WEATHERBOARDS WALLCLADDING ON CAVITY

CANT STRIP PACKER

PERMEABLE UNDERLAY OVERFLASHING, SHOWN DASHED

STST OR GALV. FLATHEAD NAIL FORFLASHING

NOG FOR FIXINGAPRON FLASHING

PVC CAVITY CLOSER

METALCRAFT ESPAN™ ROOFING

HEM PRE-FINISHEDFLASHING TO EDGE

PERMEABLE UNDERLAY,SHOWN DASHED

ROOF FRAMING

ALTERNATIVE OPTION - A

PRE-FINISHED POP RIVETBEDDED IN SILICONE OR PRE-FINISHED 8g WAFER-TEK SCREW

METALCRAFT ESPAN™ ROOFING

ALTERNATIVE OPTION - B

METALCRAFT ESPAN™ROOFING

5mm

GAP

5mm

GAP

FOLDED METALCRAFT ESPAN™ROOFING

PRE-FINISHED 12gx55mmWAFER-TEK WITH WASHER

M

GN

M M

SITUATION 1

1. LOW, MEDIUM, HIGH WIND ZONES,WHERE ROOF PITCH ≥ 10°

MIN. 35mm

MIN. 75mm

AT LEAST TWO CRESTS

SITUATION 2

1. ALL ROOF PITCHES INVERY HIGHWIND ZONE2. LOW, MEDIUM, AND HIGH WINDZONES WHERE ROOF PITCH ≤ 10°

MIN. 35mm

MIN. 75mm

AT LEAST TWO CRESTS

G

N

M

SITUATION 3

1. ALL ROOF PITCHES IN EXTRAHIGH WIND ZONE

MIN. 35mm

MIN. 75mm

AT LEAST TWO CRESTS

CATEGORY A

1. NORMAL EXPOSURE2. ROOF PITCH >10°

25mm

MIN. 50mm + HEM OR 75mm(VERTICALLY UP FACE - SMOOTH)MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - PROFILED)

ONE RIB (TRAPEZOIDAL & TRAY)2 CORRUGATIONS (CORRUGATE)

CATEGORY B

1. EXPOSED (HIGHER RISK) & WIND LOAD EXCEEDS 1.5 kPa.2. ROOF PITCH <10°

25mm

MIN. 75mm + HEM OR 100mm(VERTICALLY UP FACE - SMOOTH)MIN. 100mm + HEM OR 125mm(VERTICALLY UP FACE - PROFILED)

TWO RIBS (<20mm) (TRAPEZOIDAL & TRAY)3 CORRUGATIONS (CORRUGATE)

G

N

M

ALTERNATIVE SOLUTION AS PER MRM CODE OF PRACTICE

ACCEPTABLE SOLUTION AS PER E2/ASI

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 2

PARALLEL APRON

11 / 202018

Page 13: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

METALCRAFT ESPAN™ ROOFING

EPDM FLEXIBLE CONE SLEEVE

MALLEABLE FLANGE, SCREW ORRIVET FIXED, AND SEALED TOROOFING PROFILE. FIT NEOPRENEWASHERS TO ALL SCREW FIXINGS.FITTED ON 45° ANGLE IN PLAN.REFER TO MRM CODE OFPRACTICE VERSION 2 2/2012.

TIMBER PURLIN

PERMEABLE UNDERLAY, SHOWNDASHED

METALCRAFT ESPAN™ ROOFING

PIPE (PIPE DIAMETER ≤ 85mm)

EPDM FLEXIBLE CONE SLEEVE

PERMEABLE UNDERLAY, SHOWNDASHED

MALLEABLE FLANGE, SCREW ORRIVET FIXED, AND SEALED TOROOFING PROFILE. FIT NEOPRENEWASHERS TO ALL SCREW FIXINGS.FITTED ON 45° ANGLE IN PLAN.REFER TO MRM CODE OFPRACTICE VERSION 2 2/2012.

TIMBER PURLIN

* MIN. 3° FOR PIPEPENETRATION

ROOF FRAMING

ROOF FRAMING

THIS DETAIL IS APPLIED ONLY WHEN ALL OF THEFOLLOWING CONDITIONS ARE MET:- ROOF PITCH MIN.3°and MAX. 45°- PIPE DIAMETER MAX. 85mm- ALLOW PIPE PENETRATIONS TO BE SAME AS ROOFPITCH

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 5

MAX. 85mm DIAMETER PIPE PENETRATION

12 / 202018

Page 14: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

PIPE (85mm > PIPE DIAMETER ≤ 500mm)

EPDM FLEXIBLE CONE SLEEVE

MALLEABLE FLANGE, SCREW OR RIVET FIXED,AND SEALED TO ROOFING PROFILE. FITNEOPRENE WASHERS TO ALL SCREW FIXINGS.FITTED ON 45° ANGLE IN PLAN. REFER TO MRMCODE OF PRACTICE VERSION 2 2/2012.

PURLIN

PERMEABLE UNDERLAY, SHOWNDASHED

PRE-FINISHED POP RIVET BEDDEDIN SILICONE OR PRE-FINISHED 8gWAFER-TEK SCREW

PURLIN

ROOF FRAMING

ROOF FRAMING

PRE-FINISHEDROOF RIDGEFLASHING

METALCRAFTESPAN™ROOFING

5mm

GAP

5mm

GAP

NOGS BETWEEN PURLINS FOR PENETRATION

3.00°

* MIN. 3° FOR PIPE PENETRATION

THIS DETAIL IS APPLIED ONLY WHEN ALL OF THEFOLLOWING CONDITIONS ARE MET:- ROOF PITCH MIN.3° and MAX 45°- PIPE DIAMETER MAX 85mm- ALLOW PIPE PENETRATION TO BE SAME AS ROOFPITCH

FOLDED METALCRAFTESPAN™ ROOFING

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0 1 : 5

OVER 85mm DIAMETER PIPE PENETRATION

13 / 202018

Page 15: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

PRE-FINISHED RIDGE CAPFLASHING

METALCRAFT ESPAN™ROOFING

METALCRAFT ESPAN™ROOFING BARGE FLASHINGWITH SECRET GUTTER.

PURLIN

ROOF FRAMING

FASCIA BOARD

WALL CLADDING ON CAVITY

WALL FRAMING

* PLEASE REFER TO MRM CODE OFPRACTICE VERSION 2.2/2012 ANDRANZ HOW TO ON-SITE GUIDE METALROOF FLASHINGS FOR FURTHERINFORMATION ON FLASHING COVERWIDTHS.

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0

3D RIDGE TO BARGE JUCTION

14 / 202018

Page 16: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

PRE-FINISHED RIDGE FLASHING

METALCRAFT ESPAN™ ROOFINGTURN DOWN INTO GUTTERREFER TO EAVE DETAILS FORMINIMUM ROOF OVERHANG

PRE-FINISHED BARGE FLASHING

PRE-FINISHED APRONFLASHING

PRE-FINISHED HIP FLASHING

GUTTER

FASCIA BOARD

* PLEASE REFER TO MRM CODE OFPRACTICE VERSION 2.2/2012 AND RANZHOW TO ON-SITE GUIDE METAL ROOFFLASHINGS FOR FURTHER INFORMATIONON FLASHING COVER WIDTHS.

WALL CLADDING ON CAVITY

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0

3D DUTCH GABLE

15 / 202018

Page 17: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

GUTTER

METALCRAFT ESPAN™ ROOFINGTURN DOWN INTO GUTTERREFER TO EAVE DETAILS FORMINIMUM ROOF OVERHANG

WALL CLADDING ON CAVITY

PRE-FINISHED APRON FLASHINGWITH SECRET GUTTER. REFERTO SHEET NO.11/20

PRE-FINISHED APRON DIVERTER

WALL CLADDING ON CAVITY

* PLEASE REFER TO MRM CODE OFPRACTICE VERSION 2.2/2012 AND RANZHOW TO ON-SITE GUIDE METAL ROOFFLASHINGS FOR FURTHER INFORMATIONON FLASHING COVER WIDTHS.

FASCIA BOARD

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0

3D APRON

16 / 202018

Page 18: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

PRE-FINISHED SOAKER FLASHING

EPDM FLEXIBLE CONE SLEEVE

MALLEABLE FLANGE, SCREW ORRIVET FIXED, AND SEALED TOROOFING PROFILE. FIT NEOPRENEWASHERS TO ALL SCREWFIXINGS. FITTED ON 45° ANGLE INPLAN. REFER TO MRM CODE OFPRACTICE VERSION 2 2/2012.

PRE-FINISHED ROOF RIDGEFLASHING

PIPE(85mm < PIPE DIAMETER ≤ 500mm)

METALCRAFT ESPAN™ ROOFING

METALCRAFT ESPAN™ ROOFINGBARGE FLASHING WITH SECRETGUTTER.

PRE-FINISHED SOAKER FLASHINGUNDER PRE-FINISHED ROOF RIDGEFLASHING

* PLEASE REFER TO MRM CODE OFPRACTICE VERSION 2.2/2012 ANDRANZ HOW TO ON-SITE GUIDE METALROOF FLASHINGS FOR FURTHERINFORMATION ON FLASHING COVERWIDTHS.

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0

3D OVER 85mm DIAMETER PIPE PENETRATION

17 / 202018

Page 19: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

METALCRAFT ESPAN™ROOFING TURN DOWN INTOGUTTER

PRE-FINISHED APRONSECRET GUTTER FLASHING.REFER TO SHEET NO.11/20

WALL CLADDING ON CAVITY

PREFINISHED VALLEY GUTTER

PURLINPRE-FINISHED SOAKERFLASHING

VALLEY BOARD

ROOF FRAMING

MIN

. 110

mm

UPS

TAN

D

MIN. 110mm UPSTANDPRE-FINISHED 1.6mmALUMINIUM WELDEDSOAKER FLASHING

* PLEASE REFER TO MRM CODE OFPRACTICE VERSION 2.2/2012 AND RANZHOW TO ON-SITE GUIDE METAL ROOFFLASHINGS FOR FURTHER INFORMATIONON FLASHING COVER WIDTHS.

DIVERTER FLASHING ONUPPER SIDE OF CHIMNEY

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0

3D CHIMNEY PENETRATION

18 / 202018

Page 20: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0

3D RIDGE/BARGE FLASHINGS

19 / 202018

OPTION 1

RIDGE CAPFLASHING

ADDITIONALSADDLEFLASHING

BARGEFLASHING

RIDGE CAPFLASHING

ADDITIONALSADDLEFLASHING

BARGEFLASHING

OPTION 2

* PLEASE REFER TO MRM CODE OFPRACTICE VERSION 2.2/2012 AND RANZHOW TO ON-SITE GUIDE METAL ROOFFLASHINGS FOR FURTHERINFORMATION ON FLASHING COVERWIDTHS.

Page 21: Espan 340™ / 470™€¦ · pre-finished change of roof pitch flashing permeable underlay continuous over flashing, shown dashed permeable underlay continuous under flashing, shown

(3) PRE-FINISHEDSADDLE FLASHING

(2) PRE-FINISHEDAPRON FLASHING

(1) PRE-FINISHED HIPFLASHING

Reference

DISCLAIMER:All details are to be used for indicative purposes only and the designer should consult both the MRM codeof practice version 2.2 /2012, E2 and all other relevant building codesDetails of the supporting mechanisms are indicative only. Compliance of the supporting mechanisms is theresponsibility of the designer. Construction detail can vary for wall cladding. The underlay is detailed as asingle line for simplicity and is indicative only. Building paper type and method of installation should complywith underlay manufacturers recommendations and NZBC regulations.

RESIDENTIAL ROOFINGEspan 340™ / 470™

RREP

* - PLEASE REFER TO MRM CODE OF PRACTICE VERSION 2.2 /2012 AS MINIMUM PITCH WILL INCREASE DEPENDING ON SHEET LENGTH.

ScaleDate Sheet

Rev: R0

3D DUTCH GABLE FLASHINGS

20 / 202018

* PLEASE REFER TO MRM CODE OFPRACTICE VERSION 2.2/2012 AND BRANZHOW TO ON-SITE GUIDE METAL ROOFFLASHINGS FOR FURTHER INFORMATION ONFLASHING COVER WIDTHS.