experimental optimization of cooling tower fan control ... · pdf fileexperimental...
TRANSCRIPT
hA~IAT~fI j Form Approved
AD' A239 333 IINATO PAGE 0MB No. 070.4-0188U... 'itO o a e 1 nour Per rsocnse. including the time for reviewing instruchions. searchng existing oats sources.
I and ren'@.ewq the ColfeCtion of informiation Send comnments regarding tfhis burden estimate or any other aspect of thisgtnis burden, to Washington Headquarters Sermces. Dretorate for informa.tion Operations and Reports. 12 15 Jefferson
to the Office of Management and Budget. PaperwOrk Reduction Profect (0704-0183). Washington, DC 20503
1. A%2*.L ,. .. * REPORT DATE 3.* REPORT TYPE AND DATES COVERED
II THESIS /Ml QM4. TITLE AND SUBTITLE S. FUNDING NUMBERS
Experimental Optimization of Cooling Tower FanControl Based on Field Data
6. AUTHOR(S)
David L. Herman, Captain
7. PERFORMING ORGANIZATION NAME(S) AND ADDRESS(ES) 8. PERFORMING ORGANIZATIONREPORT NUMBER
AFIT Student Attending: Georgia Institute of AFIT/CI/CIA-91-OO2Technology
9. SPONSORING/ MONITORING AGENCY NAME(S) AND ADORE SS(U)f 10. SPONSORING/ MONITORING>' j:AGENCY REPORT NUMBER
AFIT/ClWright-Patterson AFB OH 45433-6.583AUO&9iA UG'
11. SUPPLEMENTARY NOTES
1 2a. DISTRIBUTION / AVAILABILITY STATEMENT 12b. DISTRIBUTION CODE
Approved for Public Release IAW 190-1Distributed UnlimitedERNEST A. HAYGOOD, 1st Lt, USAFExecutive Officer
13. ABSTRACT (Maximum 200 words)
91-07328
14. SUBJECT TERMS 15. NUMBER OF PAGES1 24____________________________________________
16. PRICE CODE
17. SECURITY CLASSIFICATION 18. SECURITY CLASSIFICATION 19. SECURITY CLASSIFICATION 20. LIMITATION OF ABSTRACT]OF REPORT OF THIS PAGE OF ABSTRACT
NSN 7540-01-280-5500 U , Standard Form 298 (Rev 2-89i'-t ic;~O b, 4rNY Sid I IQ*S
EXPERIMENTAL OPTIMIZATION OF COOLING TOWERFAN CONTROL BASED ON FIELD DATA
A THESISPresented to
The Academic Faculty
by
David Laurence Herman
In Partial Fulfillmentof the Requirements for the Degree
Master of Science in Mechanical Engineering
Georgia Institute of TechnologyApril 1991
EXPERIMENTAL OPTIMIZATION OF COOLING TOWERFAN CONTROL BASED ON FIELD DATA
APPROVED:
Samuel V. Shelton, Chairman
ppe//
Date Approved by Chairman , ' /
ACKNOWLEDGEMENTS
I would like to thank Dr. Sam Shelton for sharing his time and knowledge on
this study during the past 18 months. His guidance and enthusiasm made it possible
for me to complete this project.
I would also like to thank Dr. Bill Wepfer and Dr. Scott Patton for serving on
my advisory committee and reviewing my work. Additional thanks to the U.S. Air
Force for granting me the opportunity to attend graduate school and funding my
education.
Finally, I would like to thank my mother and father. Their love and support
are unconditional, and without it, nothing I do would be possible.
oii11
TABLE OF CONTENTS
LIST OF TABLES vi
LIST OF FIGURES vii
LIST OF ABBREVIATIONS ix
SUMMARY xii
CHAPTER I INTRODUCTION 1
1.1 Background 11.2 Objectives 51.3 Proposed Study 6
CHAPTER II FIELD EXPERIMENT 8
2.1 Chilled Water System 82.2 Operation 9
2.2.1 Chiller Control 92.2.2 Cooling Tower Fan Control 10
2.3 Data Acquisition System 152.4 Data Acquisition Methodology 17
CHAPTER III SIMULATION MODEL 21
3.1 Crossflow Cooling Tower Model 213.1.1 Calculation of Tower Coefficient 233.1.2 Tower Fan Model 24
3.2 Chiller Model 273.2.1 Manufacturer's Performance Specificatior. 283.2.2 Evaporator Model 293.2.3 Condenser Model 323.2.4 Compressor Model 35
3.3 Analytical Model Simulations 39
iv
3.3.1 Weather Data 393.3.1.1 Simulation 1 393.3.1.2 Simulation 2 40
3.3.2 Building Load Profile 41
CHAPTER IV RESULTS 45
4.1 Daily Data 454.2 Statistical Analysis 514.3 Hourly Data 614.4 Analytical Model 75
4.4.1 Simulation 1 754.4.2 Simulation 2 82
CHAPTER V CONCLUSIONS AND RECOMMENDATIONS 88
5.1 Conclusions 885.2 Recommendations 90
APPENDIX A FIELD DATA 92
APPENDIX B SIMULATION RESULTS 113
BIBLIOGRAPHY 122
V
LIST OF TABLES
Table 2.1. Minimum-Maximum Tower Fan Control Strategy 12
Table 2.2. Single Set Point Tower Fan Control Strategy 14
Table 2.3. Tracer Analog Inputs 16
Table 2.4. Tracer Trend Log Reports 17
Table 2.5. Tower Fan Current 20
Table 3.1. Normalized Manufacturer's Performance Data 28
Table 3.2. Simulation Variables 40
Table 3.3. Experimental Weather Data 41
Table 4.1. Summary of Field Data 48
vi
LIST OF FIGURES
Figure 1.1. Subsystem of Optimization Studies 2
Figure 2. 1. Schematic of Peachtree Plaza Chilled Water Plant 9
Figure 3.1. Cooling Tower Coefficient 25
Figure 3.2. Cooling Tower Fan Horsepower vs. Tower Air Flow Rate 26
Figure 3.3. Chiller Schematic 27
Figure 3.4. Normalized Evaporator UA vs. Load 31
Figure 3.5. Normalized Condenser UA vs. Water Flow Rate/# Passes 34
Figure 3.6. Compressor Isentropic Efficiency 37
Figure 3.7. Part Load Efficiency 38
Figure 3.8. Experimental Building Load Profile 42
Figure 3.9. Simulation 1 Building Load Profile 43
Figure 3.10. Simulation 2 Building Load Profile 44
Figure 4.1. Daily Average Chiller Efficiency at Each Set Point
Temperature 49
Figure 4.2. Daily Average Cooling Tower Fan Efficiency at Each Set Point
Temperature 50
vii
Figure 4.3. Daily Average Total System Efficiency at Each Set Point
Temperature 51
Figure 4.4. 95% Confidence Intervals for Daily Average Chiller Efficiency
at Each Set Point Temperature 55
Figure 4.5. 95% Confidence Intervals for Daily Average Cooling Tower
Fan Efficiency at Each Set Point Temperature. 56
Figure 4.6. 95% Confidence Intervals for Daily Average Total System
Efficiency at Each Set Point Temperature 57
Figure 4.7. 90% Confidence Intervals for Daily Average Total System
Efficiency at Each Set Point Temperature 58
Figure 4.8. 80% Confidence Intervals for Daily Average Total System
Efficiency at Each Set Point Temperature 59
Figure 4.9. 50% Confidence Intervals for Daily Average Total System
Efficiency at Each Set Point Temperature 60
Figure 4.10. Chiller Efficiency vs. Part Load for 85 'F Ent CW Set Point
Temperature 62
Figure 4.11. Chiller Efficiency vs. Part Load for 80 *F Ent CW Set Point
Temperature 63
Figure 4.12. Chiller Efficiency vs. Part Load for 75 'F Ent CW Set Point
Temperature 64
viii
Figure 4.13. Chiller Efficiency vs. Part Load for 70 OF Ent CW Set Point
Temperature 65
Figure 4.14. Chiller Efficiency vs. Part Load for Each Ent CW Set Point
Temperature 66
Figure 4.15. Tower Fan Efficiency vs. OSA Temp Bin for 85 °F Ent CW Set
Point Temperature 69
Figure 4.16. Tower Fan Efficiency vs. OSA Temp Bin for 80 °F Ent CW Set
Point Temperature 70
Figure 4.17. Tower Fan Efficiency vs. OSA Temp Bin for 75 OF Ent CW Set
Point Temperature 71
Figure 4.18. Tower Fan Efficiency vs. OSA Temp Bin for 70 OF Ent CW Set
Point Temperature 72
Figure 4.19. Tower Fan Efficiency vs. OSA Temp Bin for Each Ent CW Set
Point Temperature 73
Figure 4.20. Total System Efficiency vs. Part Load for Each Ent CW Set
Point Temperature 74
Figure 4.21. Actual Part Load Efficiency 78
Figure 4.22. Chiller Efficiency Comparison to Daily Field Results 79
Figure 4.23. Tower Fan Efficiency Comparison To Daily Field Results 80
Figure 4.24. Total System Efficiency Comparison to Daily Field Results 81
Figure 4.25. Predicted Monthly Chiller Energy 84
ix
Figure 4.26. Predicted Monthly Fan Energy 85
Figure 4.27. Predicted Monthly Total System Energy 86
Figure 4.28. Predicted Yearly Eiergy 87
x
LIST OF ABBREVIATIONS
A - current
cP, - constant specific heat of liquid water
CHW - chilled water
CHWR - chilled water supply
CHWS - chilled water return
CW - condenser water
CWR - condenser water return
CWS - condenser water supply
ENT - entering
fda - cooling tower coefficient
GPMc - flow rate of the condenser water
GPME - flow rate of the evaporator water
k - cooling tower constant
KW c - chiller energy demand
KWF - cooling tower fan energy demand
KWT - total system energy demand
KWHc - chiller energy consumption
xi
KWHF - cooling tower fan energy consumption
KWHT - total system energy consumption
LMTD- - log mean temperature difference of the condenser
LMTDE - log mean temperature difference of the evaporator
LVG - leaving
rii- mass flow rate of dry air per unit area of tower face exposed to theair flow
ri CHW - mass flow rate of the chilled water through the evaporator
mcw - mass flow rate of the condenser water through the condenser
- mass flow rate of the liquid water per surface area exposed to waterflow
n - tower exponent
OSA - outside air
PF - power factor
PL - part load fraction
QC - condenser heat flow rate
QE - evaporator heat flow rate
UAc - overall conductance of the condenser
UAE - overall conductance of the evaporator
V - voltage
ATcrfw - temperature drop of the chilled water flowing through the evaporator
xii
-Tcw temperature rise of the condenser water flowing through thecondenser
11-t compressor isentropic efficiency at full load including electric motorefficiency
77wa - compressor part load efficiency
Additional subscripts used:
actual - relating to the experimental data
model - relating to the analytical model
Units:
BTUH - British thermal unit per hour
F - Fahrenheit
GPM - gallon per minute
KW - kilowatt
KWH - kilowatt-hour
RT - refrigeration ton (1 RT = 12,000 Btu/h)
xiii
SUMMARY-
Energy costs continue to play an important role in the decision-making process
for building design and operation. Since the chiller, cooling tower fans, and
associated pumps consume the largest fraction of energy in a heating, ventilating, and
air-conditioning (HVAC) system, the control of these components is of major
importance in determining building energy use. A significant control parameter for
the chilled water system is the minimum entering condenser water set point
temperature at which the cooling tower fans are cycled on and off. Several studies
have attempted to determine the optimum value for this minimum set point
temperature, but direct measurements are not available to validate these studies.
The purpose of this study was to experimentally determine the optimum
minimum entering condenser water set point temperature from field data based on
minimum energy consumption and to validate a chilled water system analytical model
previously developed in earlier work. The total chiller system electrical consumption
(chiller and cooling tower fan energy) was measured for four entering condenser
water set point temperatures (70, 75, 80, and 85 'dF). The field results were
compared to results obtained using an analytical model previously developed in a
thesis entitled "Optimized Design of a Commercial Building Chiller/Cooling Tower
System," written by Joyce. (
xlv
Based on total system energy for chiller part loads less than 50%, the field
results showed that the optimum for the system studied in this work corresponded
to an entering condenser water set point temperature of 85 'F. For part loads
greater than 50%, the optimum entering condenser water set point temperature was
found to be 80 'F. Although decreasing the entering condenser water set point
temperature further resulted in an increase in chiller efficiency, the chiller energy
savings were offset by the increase in tower fan energy consumption at lower set
points.
The trends predicted by the chilled water system analytical model are in close
agreement with the data obtained from the field results. Based on the total system
energy use for an entire year, the analytical model predicted an annual optimum
constant entering condenser water set point temperature of 85 °F, which is in
agreement with the field data. According to the results from the analytical model
simulation, the additional cost of lowering the entering condenser water set point
temperature from 85 °F to 70 'F would be approximately $25,000/year for the
1000 RT chiller studied in this work.
xv
CHAPTER I
INTROD. k;TION
1.1 Background
Energy costs continue to play an important role in the decision-making process
for building design and operation. Since the chiller, cooling tower fans, and
associated pumps consume the largest portion of energy in a heating, ventilating, and
air-conditioning (HVAC) system, the proper control of these components is
imperative in determining building energy costs. Numerous studies [Sud, 1984;
Hackner et al., 1984, 1985; Johnson, 1985; Lau et al., 1985; Braun, 19881 have been
performed to identify computer strategies to reduce the cost of operating the chilled
water plants of large commercial facilities.
To produce strategies to reduce energy costs, Lau et al. [1985] concentrated
on one subsystem of the entire chilled water system to simplify the problem. The
subsystem included the chiller, pumps, cooling tower, and condenser pumps (Figure
1. 1). Their objective was to find the proper control strategy that would result in
minimum power consumption for each combination of the wet-bulb temperature and
total chiller load. They developed computer models of the chilled water system to
study the energy conservation potential of various control strategies. They produced
empirical curve fits from actual field data for a specific chilled water system to
develop component models.
Z INOEPeNDeNr VARIABLES
1 wet Bullb T.emi ature
3 CONTROLLED VARIABLES ELECTRIC ODB NOTowng
1 Fan Star-9 1 Cooing Towe rams
Concienser
2 Conoens e Pumo Pi v$ 2 Coinw@ n
Flow3 P I way Purms
j N ~/l''
9f C01lra i !4 r le 5
Chi I lies iI
2. Total Cr1lIGl ! Water Loac
Figure 1.1. Subsystem of Optimization Studies [Lau et al., 1985]
Simulations involving cooling systems have been primarily used for equipment
selection and building design. Most of the control studies which have been
performed have been concerned with the local-loop control of an individual
component or subsystem needed to maintain a prescribed set point, rather than the
global determination of optimum set points that minimize operating costs. Global
optimum plant control has been studied by Sud [1984], Lau et al.[1985],Hackner et
al. [1984, 19851, and Johnson [1985].
2
Braun [1988] provided the most complete consideration of the optimized
design and control of central chiller plants. His central objective was optimal
control. The system optimization involved minimizing the total instantaneous energy
consumption without considering annual energy costs or capital costs.
The power consumption of the chiller is sensitive to the condensing water
temperature, which is in turn affected by both the condensing water and tower air
flow rates. Increasing either of these flows reduces the chiller power requirement but
at the expense of an increase in the pump or fan power consumption. At any given
load, chilled water set point temperature, and wet bulb temperature, there exists an
optimum operating point.
Hackner et al. [1985b] stated that the correct control strategy to minimize
energy use of the chiller/cooling tower subsystem is to minimize the sum of the
chiller plus cooling tower fan power consumption. They also showed, through the
use of computer simulations using various combinations of chilled water load, OSA
wet bulb temperatures, cooling tower fan speeds, and number of operating chillers,
it is often more energy efficient to turn off some of the tower fans to optimize
cooling tower fan status. Once the optimum cooling tower fan status is determined
at a given load, it will remain the optimum tower fan status for any OSA wet bulb
temperature unless the chiller power draw limit is reached [Hackner et al., 1985b].
Cascia [1988] illustrated how actual chiller plant performance data collected
from an energy managcment system cat be used to adapt chiller plant control to
3
optimize energy savings. He presented a direct digital control (DDC) algorithm to
optimize the condenser water temperature by minimizing the sum of the chiller and
cooling tower fan energy consumption. His strategy cycled cooling tower fans based
on the change in the total energy consumption of the chiller plant.
The following generalizations can be made about all the previous studies:
e They were based on computer model simulations to determine the energy
savings of the hypothesized control strategy. Minimal field data was reported to
validate the computer simulations.
0 They all identified control strategies for complex systems based on
computer control algorithms. The strategies were specific to a particular system
based on variable speed fans, variable speed pumps, and multiple chillers. Control
parameters included condenser water flow rate, tower air flow rate, and multiple
chiller control.
* They used field data to develop empirical component models for use in the
computer simulation. The curve fits were applicable only to the specific equipment
and site. The models were not based on fundamental equations of heat transfer and
thermodynamics.
In this study, the focus was on a single control parameter, the minimum
entering condenser water set point temperature. The minimum entering condenser
water set point temperature is the temperature at which the cooling tower fans were
cycled on and off. Referring to Figure 1.1, two of the three controlled variables
4
were constant, the condenser pump flow and the number of chillers. The fan status
was changed to maintain the minimum condenser water set point temperature. The
independent variables and the means of evaluating the control strategy remained the
same.
This study differed from the previous studies in several ways. Field data was
collected to validate the proposed control strategy. The analytical model used was
based on fundamental equations for the chilled water system components, not on
empirical relationships specific to a particular equipment or site.
The analytical model used in this study was developed by Weber [1988] and
modified by Joyce [1990]. Weber investigated design optimization techniques for the
condenser water flow rate and tower air flow rate involving condenser side
components of a central chilled water system. Joyce investigated methodologies for
the optimized design of a central chilled water plant based on annual operating costs,
capital construction costs, and simple payback analysis.
1.2 Objectives
One of the major factors that effects the energy consumption of the chilled
water system is the control of the cooling tower fans. The control point at which the
cooling tower fans are cycled on and off has a major impact on this energy
consumption. It not only affects the cooling tower fan energy use, but also the chiller
energy use. The overall goal of this study is to experimentally determine the global
5
optimum minimum entering condenser water set point temperature at which the
cooling tower fans are cycled on and off.
The proposed study will meet the following three objectives:
* Experimentally determine this global optimum from experimental field
data. As discussed in the previous section, several people have used analytical
models to determine the optimum control point, but there has been no experimental
field validation of these models.
* Compare the field results to results generated using an analytical chilled
water system model developed by Weber [1988] and Joyce [1990]. Using actual field
component performance data in the analytical model, the results from the model can
be compared to the actual field results to determine the accuracy of the model.
Using manufacturer's component performance data in the analytical model, the
results can be compared to actual field results to determine the accuracy of the
manufacturer's performance data.
* Use the validated analytical model with manufacturer's component
performance data to determine the annual optimum constant set point temperature
for an entire year.
1.3 Progosed Study
The proposed study was designed to meet the three stated objectives. It will
examine the effect of four entering condenser water set point temperatures on a
6
large chilled water system. Field data will be collected using the chilled water system
at the Westin Peachtree Plaza Hotel in Atlanta, Georgia. The study will utilize the
existing chilled water system, controls, and energy management system. The field
data will include the OSA temperature and humidity, the CHWS, CHWR, CWS, and
CWR temperatures, the chilled water flow, the chiller amperage, and the cooling
tower fan run times.
The field data will be used to calculate chiller, cooling tower fan, and total
system efficiencies where the efficiency is defined as the ratio of the energy
consumption to the chilled water load. These efficiencies have units of kilowatts
per refrigeration ton (KW/RT). Based on total system efficiency, the optimum
entering condenser water set point temperature will be determined.
Two simulations of the analytical model will be run. The first will use actual
field weather data and actual field chilled water system component performance data.
The second will use standard weather data and manufacturer's component
performance data.
7
CHAPTER II
FIELD EXPERIMENT
This study was performed at the Westin Peachtree Plaza Hotel, a large
1200 room convention hotel in Atlanta, Georgia. The study utilized the existing
chilled water system, controls, and energy management system. Data was
collected for twenty days from November 6, 1990 to November 25, 1990. A
detailed analysis of the system and experimental procedures will now be given.
2.1 Chilled Water System
A schematic of the chilled water plant at the Peachtree Plaza Hotel is
shown in Figure 2.1. Three chillers, two 750 refrigeration ton (RT) steam-driven
absorption chillers and one 1000 RT electric centrifugal chiller, supply chilled
water to the building. The two absorption chillers share a chilled water pump,
and each has an associated condenser water pump. The electric chiller has an
associated chilled water pump and condenser water pump.
Eight cooling tower fan cells that share a common sump cool condenser
water for the chillers. A common condenser water return pipe returns water to
each of the tower cells. An individual condenser water supply pipe runs to each
chiller directly from one of three tower cell sumps.
8
8 Cool ig TowrS CCon*Cted Oy d co'm'o SiwV)
CWS CWS CWS
Conoe"Ser water
Chi I ler I Cr ie, 2 Ch Ij"l 3
I Chi I Iea water
C,-fWS Puo CHflhR
C to ul 11 i" g)?
Cfror au i li mgl)
Figure 2.1. Schematic of Peachtree Plaza Chilled Water Plant
A Trane Tracer Energy Management System monitors numerous chilled
water system temperatures, flows, and currents. The Tracer system has the
capability to control the chillers, pumps, and cooling tower fans. However, during
this study, it only controlled the cooling tower fans.
2.2 Operation
2.2.1 Chiller Control
The electric chiller serves as the primary chiller for the hotel and runs
twenty-four hours per day except for hours during which free cooling is possible.
9
The boiler room operator manually sets the chilled water supply temperature at
the chiller control panel. The chiller has an economizer or free cooling mode
that is manually activated.
When the electric chiller reaches its maximum capacity, one absorption
chiller can be brought "on-line" manually by a boiler room operator. The electric
chiller will generally reach its maximum capacity at OSA tenipeiatures greater
than 85 'F. The second absorption chiller is available, but is only required
during heavy load conditions, such as during the summer months.
During this study, the chilled water supply (CHWS) temperature was set to
a constant value of 44 F for OSA temperatures above 42 'F. Below OSA
temperatures of 42 'F, the chiller was manually turned off to start free cooling. If
the chiller was deactivated, it was not until the OSA temperature reached 47 'F
that the chiller would be brought back "on-line". It should be noted that during
the period of this study, the electric chiller was never fully loaded, and, therefore,
the absorption chillers did not rin.
2.2.2 Cooline Tower Fan Control
One of the objectives of this study was to experimentally determine the
optimum entering condenser water set point temperature. Thus, a major focus
was placed on the control of the cooling tower fans. A control strategy was
desired to produce data to predict this optimum set point temperature. The
10
entering condenser water set point temperature is the cycling temperature for the
cooling tower fans.
The Trane Tracer Energy Management System is used to control the eight
cooling tower fans in this system. The system was configured with three digital
output relays which allowed for only on-off fan control. The eight fans are
grouped in three sets, one set of two fans and two sets of three fans.
Prior to this study, the fans were controlled using a "minimum-maximum"
control strategy which is outlined in Table 2.1. A set of fans was turned on when
the condenser water temperature returning to the cooling towers rose above a
specified set point temperature. The same set of fans was turned off when the
temperature dropped below a lower set point temperature.
This strategy presented several problems for determining an optimum set
point temperature. The condenser water temperature was not constant, but
fluctuated by approximately ± 20'F as the fans cycled on and off. This
"minimum-maximum" control strategy was a "first on, last off' strategy, that is the
longest running set of fans was turned off last. The first set of fans brought "on-
line" would often run continuously, while the other sets of fans would be
continuously cycling.
For the purposes of this study, a single entering condenser water set point
temperature was used to simplify the optimization procedure. This single set
point temperature was chosen to be the cycling temperature for the cooling tower
11
Table 2.1. Minimum-Maximum Tower Fan Control Strategy
FAN SET OFF (CWR TEMP)1 ON (CWR TEMP)2
1 78 80
2 85 87
3 94 96
'Fan set off if temperature drops below this temperature.2Fan set on if temperature rises above this temperature.
fans. To maintain similar operation times for each fan set, the first set of fans to
be brought "on-line" would be cycled off first. This "first on, first off' strategy
ensured that all three fan sets would be utilized equally. Obviously, this strategy
could lower maintenance costs for the fan sets.
The strategy devised for this study used two control routines of the Tracer
Energy Management System. A direct digital control (DDC) algorithm
determined the required tower fan capacity to maintain the entering condenser
water set point temperature. Then, a process control language (PCL) routine
used the required capacity from the DDC algorithm to control the cooling tower
fans in order to maintain this set point temperature.
The DDC algorithm uses the following equation for proportional-integral-
derivative (PID) control:
12
dG=K, *dE+C, *E +KD *d( ) (2.1)
where dG - change in output
K= proportional gain
dE = change in error
KI = integral gain
E = error
dT = time interval
KD = derivative gain
d(dE/dT) = rate of change in error
The DDC algorithm adjusts the output from its current value to a new value
based on the calculated change in output [Trane, 1987].
As mentioned above, the DDC algorithm calculated the percent capacity of
cooling tower fans required to maintain the condenser water set point
temperature. The proportional gain, integral gain, derivative gain, and sampling
time are determined by trial and error. These parameters were determined by
minimizing the overshoot of the set point temperature and cycling only one set of
fans. For example, an OSA temperature might require that one set of fans run
continuously, while a second set of fans would cycle. The set of fans chosen to be
running and the set being cycled were rotated depending on run-time.
13
The output of the DDC algorithm which was the required cooling tower
fan capacity was used in a PCL routine to control the fans. In simulating a
continuous degree of control from 0% capacity (no fans on) to 100% capacity (all
fans on), four steps were established using a second PCL routine (Table 2.2). The
first PCL routine compared the required capacity (percent output) to the actual
tower fan capacity and then cycled a fan set on or off as required. In addition,
the control strategy used in this study compared the run times of the fan sets and
cycled the set with the longest run time off first.
Table 2.2. Single Set Point Tower Fan Control Strategy
FAN SETS ON ACTUALTOWER FAN CAPACITY(%)'
0 0
1 17
2 50
3 83
'PCL routine cycles one set of fans off or on respectively if requiredcapacity is less than or greater than actual capacity.
14
2.3 Data Acquisition System
The Trane Tracer Energy Management System served as the data
acquisition system. Table 2.3 gives a list of the analog input parameters. Using a
PCL routine, the parameters for Chiller #1 and the cooling tower fans were
monitored every minute. These data were then summed, and an average for each
hour was computed. The average hourly values were then stored in a "trend-log"
report for use in this study. These average hourly parameters are shown in
Table 2.4.
15
Table 2.3. Tracer Analog Inputs
ANALOG INPUT NAME
OUTSIDE AIR TEMP
OUTSIDE AIR HUMIDITY
CH-1 CHW LVG TEMP
CH-2 CHW LVG TEMP
CH-3 CHW LVG TEMP
COMMON CW LVG TEMP
CH-1 CW ENT TEMP
CH-2 CW ENT TEMP
COMMON CW LVG TEMP
CH-1 CHW FLOW
CH-2 CHW FLOW
CH-1 CURRENT (AMPS)
16
Table 2.4.. Tracer Trend Log Reports
TREND LOGS
AVG OSA TEMP
AVG OSA HUMIDITY
AVG CH-1 CHW LVG TEMP
AVG COMMON CHW RETURN TEMP
AVG CH-1 CW ENT TEMP
AVG COMMON CW LVG TEMP
AVG CH-1 CHW FLOW
AVG CH-1 CURRENT (AMPS)
FAN 3-6 RUN TIME
FAN 1-4-7 RUN TIME
FAN 2-5-8 RUN TIME
2.4 Data Acguisition Methodologv
This study examined four entering condenser water set point temperatures.
These set point temperatures were 70°F, 75°F, 80°F, 85°F. In collecting data, the
same set point temperature was maintained for a 24 hour period. At the end of
each 24 hour period, the Tracer automatically changed the set point temperature
at 12:01 am each day by using a PCL routine.
For each day, the average values were imported into a spreadsheet. From
these values, the chilled water load (RT), chiller energy demand (KWc), and
17
tower fan energy demand (KWF) were calculated. The chilled water load was
calculated using the following equation for the heat transfer rate through the
evaporator [Clifford, 1990]:
Qr=?hcttw*CP,. A TcHW (2.2)
where QE = chilled water load
ricuw = mass flow rate of the chilled water through the evaporator
AT = chilled water temperature rise through the evaporator
C= constant specific heat of water
The chilled water load had units of refrigeration tons (RT). The average value of
the chilled water load for each hour was assumed to be the refrigeration ton-
hours (RT-hours) produced by the chiller during that hour.
The energy used by the chiller (KWc) was calculated from the measured
average three phase current consumed by the chiller. This value was calculated
using the following expression [Baumeister, 1978]:
KWc V4 * V*A *PF (2.3)
where V = chiller voltage (470 V)
A = chiller current (amps)
PF = power factor
18
In this study, the power factor was assumed to be the commonly accepted value of
0.95. The hourly energy demand was considered to be the chiller energy use for
that hour (KWHc).
The energy consumed by the cooling tower fans was calculated using the
total time the cooling tower fans were in use. The hourly fan run-time for each
fan was multiplied by the electrical input in KW for each fan to calculate the
hourly energy use for each fan. The energy use for each fan was summed to
calculate the total fan energy use (KWHp). Each cooling tower fan is driven by
an 18 horsepower (HP) AC motor. This HP rating equates to an input of 22 KW
of electrical power, assuming a motor efficiency of 0.85. To validate this
assumption, the amperage of each tower fan motor was measured. The results of
these measurements and their corresponding calculated electrical input in KW are
shown in Table 2.5.
In this study, the parameters used to determine the optimum condenser
water set point temperature were the chiller efficiency, cooling tower fan
efficiency, and total system efficiency. Each efficiency was defined as the ratio of
the respective energy use to refrigeration ton-hours (RT-hours). This was
performed on both an hourly and daily basis. The efficiencies were in units of
KWH/RT-hour which is equivalent to KW/RT. The total system energy use
(KWHT) is the sum of the energy consumed by the chiller and the cooling tower
fans.
19
Table 2.5. Tower Fan Current
TOWER FAN # CURRENT (AMPS) KW DEMAND (KW)_
1 28 22.1
2 29 22.9
3 25 19.7
4 38 30.0
5 21 16.6
6 28 22.1
7 30 23.7
8 32 25.3
AVG 22.8
'Calculated using equation 2.3 (V =480 V).
20
CHAPTER III
SIMULATION MODEL
This study uses the analytical model for a chilled water system developed by
Weber [1988] and Joyce [1990]. A review this analytical model will now be given.
The complete system model consists of four component models. These component
models are a crossflow cooling tower model, an evaporator model, a condenser
model, and a compressor model. A brief outline of the development of each
component model is presented; however, the reader should consult Weber [1988]
and Joyce (19901 for the complete development. The modifications and additions to
these component models needed for this study will be given in detail.
3.1 Crossflow Cooling Tower Model
There are two generally accepted approaches to the modeling of cooling
towers. These two approaches, as outlined in the ASHRAE Equipment Handbook
[1988], are those based on the assumptions made by Merkel and those based on a
more detailed approach which makes few assumptions. The ASHRAE Equipment
Handbook [1988] uses the model developed by Merkel in its treatment of cooling
tower theory and presents a thorough explanation of the cooling tower
21
thermodynamic process. The cooling tower model developed by Weber[1988] and
Joyce [1990] uses a more detailed approach.
The principle elements and solution methodology of the cooling tower model
used in this study are as follows:
e A fundamental analysis of the mass and energy balances in the cooling
tower with mass diffusion and convective heat transfer as the driving forces is used.
This analysis results in three coupled partial differential equations.
* The three differential equations are solved by finite difference using the
Van Wijngaarden-Decker-Brent method [Press et al, 1986]. A finite difference grid
size of l0x10 is used in this study as recommended by Weber.
9 The correlation presented by Lowe and Christie [1961] is used to calculate
a volume transfer coefficient from a given cooling tower's tower coefficient (k) and
tower exponent (n). The tower coefficient and tower exponent are calculated from
manufacturer's performance data for a given cooling tower.
e The tower fan operation time required to maintain a minimum condenser
water supply temperature is then calculated.
22
3.1.1 Calculation of Tower Coefficient
The solution of the differential equations developed by Weber requires the
value of the tower coefficient (fda) as defined by Lowe and Christie [1961] where fd
is the water vapor mass transfer coefficient for the water droplet to air-vapor mixture
and a is the ratio of the surface area of the water droplets to the tower volume
where heat and mass transfer takes place. They showed this tower coefficient can
be expressed as a function of the mass flow rates of the air and water entering the
tower, the tower constant (k), and the tower exponent (n):
fda **( m _Y (3.1)
The tower constant and exponent are fixed for a given tower.
The values of the tower constant and exponent for the tower at the Peachtree
Plaza Hotel were obtained by calculating the tower coefficient at 14 operating points
given in manufacturer's performance specifications. In order to be compatible with
the tower model, the eight cells at the Peachtree Plaza Hotel were treated as a single
tower in the analytical model. The tower model used the inlet and outlet water
temperatures, the water and air flow rates, and the air inlet wet and dry bulb
temperatures from the manufacturer's specifications to calculate the tower
coefficient. The tower routine used a modified bisection method to iterate on the
tower coefficient value until the calculated water exit temperature matched the given
23
water exit temperature within 0.0001 'F. The calculated tower coefficients at each
operating point were used to plot the ratio of fda/ri,, versus the ratio of r,/n .
Linear regression was used to calculate the slope of the line or the tower exponent
and the intercept of the line or the tower constant (Figure 3.1). For the tower at the
Peachtree Plaza Hotel, using the manufacturer's specifications resulted in a tower
exponent (n) of 1.12983 and a tower constant (k) of 2.167380.
3.1.2 TowerFan Model
The tower model calculates the fan shaft power (HP) from the air flow rate
through the tower. A correlation of the fan shaft power to the air flow rate through
the tower was obtained from a curve fit of manufacturer's performance specifications
for the tower at the Peachtree Plaza Hotel. Figure 3.2 is a graph of In(cooling tower
fan HP) versus In(cooling tower cfm) for the Plaza's cooling tower. A reduction of
the curve fit formula similar to the one done by Weber [1988] shows horsepower as
a function of air flow rate raised to the 3.8 power. The theoretical value, as stated
by Weber, is 3.0.
24
COOLING TOWER COEFFICIENT10.0 __ _ _ __ _ _ _
5o.o ",,j, I I
S1.0 _ _U- __ _ _ _ _ _ _
0. 1 __ _ _ _ __ _ _j ij0. 1.0 10.0
Figure 3.1. Cooling Tower Coefficient
25
COOLING TOWER FAN HP VS CFM
12 5.5-z
cL 5.2-
2 .0
z4.84.5
14.4
42P
4.0-
3.8~13.0 13.2 13.4 13.6 13.8 14.0 14.2 14.4 14.5 14.8 15.0
LN(COCLTNG TOWER CPM)
Figure 3.2. Cooling Tower Fan Horsepower vs. Tower Air Flow Rate
26
3.2 Chiller Model
T T
Evaoor etc.-
Figure 3.3. Chiller Schematic [Weber, 1988]
The chiller component model developed by Weber (Figure 3.3) is composed
of three sub-component models; one for the evaporator, condenser, and compressor.
One of the advantages of this approach is that modifications made to any of the sub-
27
components can be accurately modeled and show the effects on the chiller
performance.
3.2.1 Manufacturer's Performance S1ecifications
Table 3.1. Normalized Manufacturer's Performance Data
PART ELECTRICAL Tcws GPMc Tc TE
LOAD POWER
(KW/RT) ('F) (GPM/RT) (-F) (OF)
1.000 0.6300 85 3 97.75 40.24
1.000 0.6840 92.5 3 105.38 40.24
1.000 0.5900 75 3 87.7 40.24
1.000 0.6200 85 5.948 93.61 40.24
1.000 0.6580 85 1.81 103.53 40.24
0.666 0.5976 85 3 93.2 41.03
0.334 0.7006 85 3 89.18 41.37
Tcnws =44°F, GPME =2.4 GPM/RT, ATcaw= 10F @ FULL LOAD
Weber obtained manufacturer's performance specifications for a 500 RT
chiller at various load levels, entering condenser water temperatures, and condenser
water flow rates. These data include compressor electrical power, condensing
temperature, and the evaporator suction temperature as shown in Table 3.1. For the
28
purposes of this study, the chiller load in RT, the electrical power in KW and the
condenser flow rate in GPM were normalized by the chiller size of 500 RT.
3.2.2 Evaporator Model
The evaporator model proposed by Weber considered the evaporator to be
a flooded shell and tube heat exchanger. The following two expressions for the
evaporator heat transfer rate were employed in his model:
QE =M cr. * Cp *ATcH. (3.2)
QE=UA *LMD E (3.3)
where QE = the chilled water load
ricaw = mass flow rate of the chilled water through the evaporator
ATcw = the chilled water temperature rise through the evaporator
UAE = evaporator overall heat conductance
LMTDE = evaporator log mean temperature difference
Equation 3.2 allowed the temperature decrease of the chilled water flowing
through the evaporator tubes to be calculated for a given cooling load and chilled
water flow rate. For the purposes of this study, the chilled water flow rate and the
chilled water supply temperature were held constant. Equation 3.3 can then be
29
viewed as the relationship between the variation in the chilled water temperature to
the product of the overall evaporator conductance and the evaporator log mean
temperature difference (LMTDF). When the flow rate was held constant, Weber
showed that the UAE was only a function of the refrigeration capacity. This
relationship was also assumed to be correct in this study.
Using the normalized manufacturer's performance data shown in Table 3.1
and equations 3.2 and 3.3, the normalized evaporator conductance was calculated.
A plot of UAE versus part load is shown in Figure 3.4. A curve fit was made to
determine an expression for UAE as a function of part load (PL). This expression
was found to be:
UAE =268.23206 +2568.6836 * PL -1281.09948 * PL 2 (3.4)
where PL is the part load fraction (PL = Model Chiller Load/Nominal Chiller Size)
and UAE has units of BTUH/(°F * RT).
30
EVAPORATOR UA VS LOAD(NORMALIZED BY NOMINRL TONNRGE)
1600
1500-
1400 -1300
1200
1000-900
800
700L00
500w 400
300
20010000.0 0.2 0.4 0.6 0.8 1.0
PRRT LORO
Figure 3.4. Normalized Evaporator UA vs. Load
31
3.2.3 Condenser Model
The condenser model used by Weber also considered the condenser to be a
flooded shell and tube heat exchanger. The critical difference from the evaporator
model was that a variation in the number of condenser passes was permitted to
maintain a minimum water velocity in the tubes of the condenser. The heat transfer
rate in the condenser is given by an energy balance on the chiller as follows:
Qc-Q +KWc (3.5)
where Qc = condenser heat transfer rate
KWc = power consumption of the compressor
The expressions used to approximate the condenser performance were very similar
to those for the evaporator model and are given by:
QC-r C. •n * Ar (3.6)
QC-UA C * LMTD c (3.7)
where rcw= condenser water flow rate
ATcw = the temperature rise of the condenser water
UAc = overall conductance of the condenser
32
LMTDc = condenser log mean temperature difference
Unlike in the evaporator, where the chilled water flow rate is held constant,
the condenser water flow rate is allowed to vary. As a result, in the model by Weber
it was found that the UAc is a function of both the heat transfer rate and the velocity
of the condenser water. The velocity of the condenser water is proportional to the
condenser water flow rate divided by the number of passes in the condenser.
Using the normalized manufacturer's performance data shown in Table 3. 1
and equations 3.5 - 3.7, the normalized condenser conductance was calculate at
various loading and condenser water velocity conditions. A plot of UAc versus
condenser water velocity at various part loads is shown in Figure 3.5. A curve fit was
used to determine an expression for UAc as a function of part load and condenser
water velocity. The expression was found to be:
UA =121 7 .0966 8 +261.29712 * PL -384.41132 * PL 2
GPMC ) GPMC )2 (3.8)+802.5367 * ( PSE )-123.8789 * (PASS)PASSES PASSES
where GPMc has units of GPM/RT and UAc has units of BTUH/(°F * RT).
33
CONDENSER UA VS GPMI#PASSES(NORMRLIZED BY NOMINRL TONNRGE)
2600
PULL LORD .... ..............2400
S0.666 LORD .....
2200 0334 LORD.
2000 .
f 1800-LUcl'1600
Z 1400CZ)
1200
1000
800 ...0.0 0.3 0.6 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3.0
CONDENSER GPM/# PASSES
Figure 3.5. Normalized Condenser UA vs. Water Flow Rate/# Passes
34
3.2.4 Compressor Model
In the compressor model developed by Weber, the Carnot efficiency governing
the performance of the refrigeration devices was used with two efficiencies to
correlate the compressor performance based on manufacturer's performance data.
The values for these efficiencies were found using the manufacturer's data in Table
3.1. In the development of the compressor model, the compressor was assumed to
be adiabatic.
Weber used the Carnot cycle to develop the ideal, or Carnot based, kilowatts
per ton of cooling load. This assumed isentropic compression, constant temperature
heat rejection at To, and constant temperature heat addition at TE. Weber then
related the Carnot based KW/RT to the manufacturer's KW/RT using two
efficiencies, a compressor isentropic efficiency at design full load (n, .) and a
varying part load efficiency (1. d,,) based on the chiller load. The 77.,, is based
on input power to the electric motor, not the input power to the compressor shaft.
The part load efficiency accounts for the decrease in the efficiency of the compressor
at part load conditions. The equations for i, ,, and i, .. are found using
polynomial equation curve fits to the manufacturer's performance data in Table 3.1
(Figures 3.6 and 3.7). Since the manufacturer's design full loa.,. KW/RT for the
chiller at the Peachtree Plaza is 0.65 KW/RT, the equation found from Weber's
model data is multiplied by a ratio of the manufacturer's design KW/RT for the
35
model chiller to the manufacturer's KW/RT for the chiller at the Peachtree Plaza
(0.63/0.65). This resulting equation is plotted in Figure 3.6 and given below.
The model KW/RT is then determined by:
( KWKWRT (3.9)
where
KW T(-).. =[-c-.E-i] 3.517 (3.10)
RT T
(Tc and Tp are absolute temperatures and (KW/RT),x has units of KW/RT.)
=0.50013 +[1.5454 ((_) -0.3)] -[3.613 • ((.T).-0.3)1 ] (3.11)
([KW/RT]7I, x has units of KW/RT.)
1,..,,, ,f[4.5869* PL] -[8.16536*PL 1 +[6.65014*PL 1]-[2.07617*PL 4] (3.12)
(PL is the previously defined chiller part load fraction.)
36
COMPRESSOR ISENTROPIC EFFICIENCY~0.70
L 0 .6 5 -
LL
00
C 0
z~0.55
cnLU
a.' 0.50
0. 45'0.20 0.35 0.40 0.45 0.50
CRRNOT KW/RT
Figure 3.6. Compressor Isentropic Efficiency
37
PART LOAD EFFICIENCY VS LOAD
.00
0.89
S0.7z.;
-0.5
±0.5
0.2-
0.1
0.c0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.0 1.0
PRRT LORO
Figure 3.7. Part Load Efficiency
38
3.3 Analytical Model Simulations
Two simulations were performed using the complete chilled water system
analytical model. The first simulation used actual field weather data and actual field
chiler component performance data obtained at the Peachtree Plaza Hotel. The
second simulation used standard weather data in conjunction with the manufacturer's
chiller component performance data. Both simulations utilized manufacturer's
cooling tower performance data. Table 3.2 lists the variables required for each
simulation. Both simulations used building load profiles developed from measured
field data.
Using experimental data in simulation 1 and comparing the results to actual
field data can be used to validate the analytical model developed by Weber. Once
this analytical model is validated, using manufacturer's performance data and
standard weather data in simulation 2 permits an estimate of the yearly performance
of the system. Comparing simulation 2 results to actual field data shows how
accurately the manufacturer's performance data predict actual field performance.
3.3.1 Weather Data
3.3.1.1 Simulation 1: Weather data for simulation 1 are tabulated from the
twenty days of experimental data collected at the Peachtree Plaza Hotel. The dry
bulb temperature bins and mean coincident wet bulb (MCWB) temperatures were
the same as those used in the standard weather data given in U.S. Air Force Manual
39
Table 3.2. Simulation Variables
Variable Simulation 1 Simulation 2'
Nominal Chiller 900 RT 1000 RTTonnage
Chiller Efficiency 0.85 KW/RT 0.65 KW/RT
Evaporator GPM 2444 GPM' 2400 GPM
CHWS Temperature 44 OF' 44 OF
Condenser Passes* 2 2
Condenser GPM 3441 GPM' 3093 GPM
CWS Pipe Diameter* 12" 12"
CWS Set Point 70/75/80/85/90 OF 70/75/80/85/90 OF
HTower Fan CFM 1,036,960CFM2 1,036,960CFM
'Based on actual system design.
'Based on actual field component performance data.2Based on m-anufacturer's component performance data.
88-29 [1978]. The summary of data are shown in Table 3.3.
3.3.1.2 Simulation 2: Weather data used for simulation 2 are obtained from
the U.S. Air Force Manual 88-29. The total number of hours in each dry bulb 5 OF
temperature range, or "bin,"was used as the Peachtree Plaza Hotel chilled water
system operates twenty-four hours per day. A computer algorithm calculated the
total number of hours for each bin and the cumulative number of hours for each
month of the year.
40
Table 3.3. Experimental Weather Data
OSA TDB Bin MCWB Temperature Hours'
72 60 1
67 60 80
62 57 100
57 52 140
52 47 77
47 42 52
42 38 4
Total Number of Hours: 454
1Total number of mechanical cooling hours observed in OSA TDB bin.(Free cooling hours are excluded.)
3.3.2 Building Load Profile
The actual building load profile was found by plotting the average hourly
chiller tonnage (RT) versus the average hourly OSA temperature from the
experimental data (Figure 3.8). The building load profiles for simulation 1 and
simulation 2 are shown in Figures 3.9 and 3.10 respectively. The profile for
simulation 1 is normalized by a nominal chiller tonnage of 900 RT; whereas the one
for simulation 2 by a nominal tonnage of 1000 RT. Both profiles assume free cooling
to be used below an OSA temperature of 42 OF.
41
AVG TONS VS AVG OSA TEMPERATUPEC8ASEO ON HOURLY EXPERIMENTAL DATAD
Avg Hourly Tons CPT) (Thousanisj1
0 8
0 6
-~. J .
0.2
a 10 20 30 40 50 50 70 80 90 100Avg Hour-ly GSA Temp~er-ature
Figure 3.8. Experimental Building Load Profile
42
BUILDING COOLING LOAD VS OSA TEMPEPATUPE
CNOPMALIZED BY 900 NOMINAL RTD
Part Load Factor
0.6
0.5
0.4
02
0 1III I I I I
0 10 20 30 40 50 60 70 80 90 100OSA Dry Bulb Tefrerature CP#
Figure 3.9. Simulation 1 Building Load Profile
43
BUILDING COOLING LOAD VS OSA TEMPERATURE
CNORMALIZED BY 1000 NOMINAL RTD
Part Load Factor
08a
0.8
04
02
0 I I 1
0 10 20 30 40 50 s0 70 80 90 100
OSA Dry Bulb Temperature CFD
Figure 3.10. Simulation 2 Building Load Profile
44
CHAPTER IV
RESULTS
4.1 Daift Data
As discussed in Chapter II, data was collected for the twenty days from
November 6, 1990 to November 24, 1990. For each day, one of the four entering
condenser water set point temperatures (70, 75, 80, 85 'F) was maintained. The
hourly field data for each day is tabulated in Appendix 1. Table 4.1 gives a daily
summary of the field data.
A major objective of this study was to determine the optimum condenser
water set point temperature. In this work, the total system efficiency was chosen as
the criterion for determining this optimum. The "total system" was defined as the
combination of the chiller and the cooling tower fans. The chilled water pumps and
condenser water pumps were not considered since their energy use was constant for
all cases. The total system efficiency is defined as the ratio of the total system
energy use to the total refrigeration ton-hours and has units of KW/RT.
Plotting the chiller efficiency, cooling tower fan efficiency, and total system
efficiency as a function of the four set point temperatures (Figures 4.1, 4.2, 4.3)
shows clearly the following trends. For the chiller energy consumption, the chiller
efficiency initially decreased as the set point temperature decreased from 85 'F to
45
75 *F. The chiller efficiency, however, then increased with further set point
temperature decreases. The tower fan energy consumption (the energy use per RT-
hour produced, KWF/RT) increased as the set point temperature decreased. The
total system efficiency showed the same trends as the chiller, first increasing as the
set point temperature was lowered from 85 *F to 80 *F, followed by an increase in
efficiency as the set point was further decreased. Although the chiller was more
efficient at a set point temperature of 75 "F, the total system efficiency was
maximized at an 80 *F set point temperature. This fact is explained by the large
increase in fan energy consumption from 80 'F to 75 *F outweighing the energy
savings in chiller energy for this temperature range.
These trends are consistent with known chiller operation [Trane, 19891.
Lowering the condenser water temperature lowers the head pressure on the
condenser and consequently increases the chiller efficiency. The energy used by the
chiller is used to compress the refrigerant gas from low pressure in the evaporator
to high pressure in the condenser. Decreasing the condenser water temperature will
lower the saturation temperature in the condenser, thereby decreasing the pressure
differential between the evaporator and the condenser. This pressure differential
decrease reduces the work required by the compressor and the energy consumption
of the compressor. The total result is to lower the chiller efficiency (KWc/RT).
As seen in the experimental data, there are limitations to lowering the
condenser water temperature. A minimum pressure differential is required between
46
the evaporator and the condenser to assure adequate refrigerant flow through the
orifice acting as the throttling device. If this minimum pressure differential is not
maintained, insufficient refrigerant is returned to the evaporator resulting in low
evaporation pressures. As the level of the liquid refrigerant drops, the evaporator
tubes are no longer fully covered, causing a decrease in the effective surface area
used to evaporate the refrigerant. This decrease will result in a reduction of the
chiller efficiency.
47
Table 4.1. Summary of Field Data
DATE SET AVG OSA TONHRS AVG TON CHILLER FAN TOTAL CHILLER FAN TOTALPOINT TERP (RT) KWH KWH KWH KW/RT KW/RT KW/RT
6 NOV 85 56.1 12261 511 12174 318 12492 0.9929 0.0259 1.018810 NOV 85 48.8 9124 380 10722 4 10726 1.1751 0.0004 1.175514 NOV 85 60.7 13921 580 13244 585 13829 0.9514 0.0420 0.993418 NOV 85 58.0 7464 574 6847 216 7063 0.9517 0.0292 0.980922 NOV 85 62.9 12251 510 12476 648 13124 1.0184 0.0529 1.0713AVG 57.3 11004 511 11093 354 11447 1.0179 0.0301 1.0480
7 NOV 80 60.1 12688 529 12243 700 12943 0.9649 0.0551 1.020011 NOV 80 58.1 7709 514 7117 355 7471 0.9880 0.0460 1.034015 NOV 80 61.4 13870 578 12809 957 13766 0.9235 0.0690 0.992519 NOV 80 58.8 9491 527 9187 399 9586 0.9695 0.0421 1.011723 NOV 80 61.1 13003 542 12462 857 13319 0.9584 0.0659 1.0243AVG 59.9 11352 538 10764 654 11417 0.9609 0.0556 1.0165
8 NOV 75 54.4 11619 484 11535 766 12301 0.9928 0.0659 1.058712 NOV 75 59.4 12261 511 11794 951 12745 0.9619 0.0776 1.039516 NOV 75 63.0 15153 631 12871 1502 14373 0.8494 0.0991 0.948520 NOV 75 61.8 12200 508 11900 1154 13054 0.9754 0.0946 1.070024 NOV 75 58.7 11915 496 11645 832 12478 0.9774 0.0699 1.0473AVG 59.5 12630 526 11949 1041 12990 0.9514 0.0814 1.0328
9 NOV 70 48.2 10112 421 10746 927 11673 1.0627 0.0917 1.154313 NOV 70 57.6 12831 535 11866 1352 13218 0.9248 0.1054 1.030217 NOV 70 53.0 12627 526 11676 1056 12732 0.9247 0.0937 1.008321 NOV 70 61.0 11924 497 11595 1951 13456 0.9724 0.1636 1.136025 NOV 70 61.7 12627 526 11695 1438 13133 0.9261 0.1139 1.0400AVG 56.3 12024 501 11516 1345 12842 0.9621 0.1117 1.0738
48
<W/RT VS ENT CW SET POINT
CCHI LLERD
KW/ RT1 .1 0 I- -" ' , , , . ,.. ............ ... ................ . .......*- ----- --------------.--*- -----------
11 8 .... ................. ............. ......*...0 8. ..*. .... ........... ...... . ... " ------
1 .0 6 -. ..*. .................................... ...................
1 0 4 ... .*. ... .. .... ...... .... ........1 .... .. .. ........* --- .... .. ...... - - , -....... .
1 0 2 9 0 ----*- ------ ---* * *. .....*. .... .. .... ............... ... ...
0 75 ... 0. 8 5.. 1-* - ......" ' " , -
0 ~ ~ ~ ~ ~ N 98 ......... W....... .... S ET..... ......... ............P O I N T.............. .......... .. .....
Fiur 4.1. Daily...A.era....Chiller... Efficiency...at..Each..Set..Point..Temperature..
L ----- ................. 4..
KW/RT VS ENT CW SET POINT
CTOWEP FANSD
KW/ PT
0 . 1 7 ...................... 7.................................................8...............
0 .10 ~ ~ ~ E N CW--- SET..........................................I.........................T.......
0igur 4 ..................2............ Daily A..e..age Cooling Tower. ..a..Efficiency ...at ..Each..Set.. Point
T em p e...........ratu re,,....... .. ....... ....................................
0 , 4 - .......... .............................................. ......5 0 ..
<W/RT VS ENT C'V SET POINT
CTOTAL SYSTEMJ
KW/ PT
1 10 ......................................... ......... ..... ..........................................................................................................................
"1 0 6 ........... . . . . . . . . .. . . . . . . ......... ................................................................................ .........................................
01 . 6
1 0 ....... ......... ......... ......... ........ ......... ......... ......... ..................... ... ........-- ---I--*........
0 2 . ......................... ...... ........ ............................................ . . . ............... ... ... ... ............ . . . .. . .. .. . ... . . . . . . .
,--------',.........- .. .......................... .... .. . .0 9 8 ............. *.......... * **................. *......- -*... .... .... *.............. .... ... .... .... .... ....... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0 9 4 . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ............................. ........... - *........................ ............................-- --- - - -- -
0 9 2 - . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .............................................. ................................. .... ........... .................. - -
0.90 -1 1 1
70 75 80 85
ENT CW SET POINT
Figure 4.3. Daily Average Total System Efficiency at Each Set Point Temperature
4.2 Statistical Analysis
Statistical inference is the expression used to describe a process by which
information from sample data is used to draw conclusions about the population from
which the sample was selected. One of the techniques of statistical inference is
called "parameter estimation", which is estimating the parameter of interest to be
within a calculated range. In this study, the parameters of interest are the chiller
51
efficiency, the cooling tower fan efficiency, and the total system efficiency. To meet
the first objective of the study, the efficiencies at each of the four entering condenser
water set points should be statistically independent. One method of examining this
statistical independence is the use of "confidence intervals".
The confidence interval is the measure of the variation in the data. The
unknown parameter then lies in the observed interval with a given confidence. The
size of the observed confidence interval is an important measure of the quality of the
information obtained from the sample. The larger the confidence interval, the more
certain the interval actually contains the true value of the parameter. However, the
larger intervals provide less information about the true value of the parameter. The
most information is obtained when a relatively small interval has a high degree of
confidence.
The construction of the confidence interval assumes the population is normally
distributed. Tuve and Domholdt [1966] state four criteria for determining whether
the assumption of normal distribution is appropriate. The criteria are as follows:
0 The values comprise a population of some size or a fairly large and
representative sample from the total population.
* The deviations from the average in this representative sample are small,
random, and uncoupled and are due to a variety of causes.
* The range of values from highest to lowest looks reasonable.
52
- An examination of the highest and lowest values shows no significant bias
or skew.
The data collected in this study are assumed to meet these criteria.
To find the confidence interval for the mean of a normal distribution from a
random sample of size n where the population variance is unknown, the sample
mean, X, and the sample variance, S2, are employed in the following equation:
'- <L <Y1+ " (4.1)
Fn Vn
where t.12,.-, is the t-distribution from Table IV in the Appendix of Hines and
Montgomery [1990].
Figures 4.4 - 4.6 show the chiller, cooling tower fan, and total syscem
efficiencies as functions of the four entering condenser water set point temperatures
with 95% confidence intervals. From the definition, the mean efficiency for the
entire population of possible efficiencies at each set point is between the upper and
lower limits of the interval with a confidence of 95%. This statement can also be
interpreted as, the mean lies within the interval 95% of the time. In this case, the
high confidence produces a large interval.
Figures 4.6 - 4.9 show the total system efficiency as a function of the four set
point temperatures with decreasing confidence levels. Since the size of the
confidence interval measures the precision of the estimation, the precision is
inversely related to the size of confidence interval. Simply stated, the large
53
confidence intervals are less precise than small confidence intervals. Therefore, it
is highly desirable to obtain a confidence interval that is small enough for decision-
making purposes that also has adequate confidence. In Figure 4.9, a set point
temperature of 80 *F has a lower total system efficiency than 70 'F with 50%
confidence.
The conclusions drawn from the experimental data are therefore believed to
be valid, despite the large confidence intervals at higher confidence levels. It is
difficult to obtain measurements with high confidence in the systems studied here,
since many variables affect the overall efficiency. More measurements must be
performed if one wishes to reduce the variation resulting in smaller confidence
intervals at higher confidence levels.
54
CHILLER KW/RT VS ENT CW SET POINT
C95% CONFIDENCE INTERVALD
rI,'/ PT1 1 6 ....... ........ *........**... ... ... .... ... ... ....... ... ... ... .......................................................................................................... ..
1 . 1 2 .. . ... . . . .. . . . .. .. . .. . ... . . ... . . . .. .. . .. . . . ......................................... ................................................ ... . . .
1 0 8 ................................................................................................................................................................................. .
"1 0 0 ... ....................................................... ............................................................... . .. . . . . ............. .. .. . . ....... ...... .
0 9 2 ... . . ...... ............... ................... .. . . . ................................................................................................................ .
0 8 8 .......................... ............................... .............................................................................................................. ........
1084
0, 8,4
70 75 80 85
ENT CW SET POINT
Figure 4.4. 95 % Confidence Intervals for Daily Average Chiller Efficiency at EachSet Point Temperature
55
TOWER FAN KW/PT VS ENT CW SET POINT
C95% CONFIDENCE INTERVALD
KW/ PT
0.15 0 .... -----------5............................................................. ... .... .................
0.-140 ..* .. . ... ................................................................ I.......................
001 5..................... .. ... ................................ ........ ........... ........ ...
01101.............................. ...
0 005 1
70 75 s0 e5
ENT OW SET POINT
Figure 4.5. 95 % Confidence Intervals for Daily Average Cooling Tower FanEfficiency at Each Set Point Temperature.
56
TOTAL SYSTEM KW/RT VS ENT CW SET
C95% CONFIDENCE INTERVALD
KW/ PT
19. ...............................---- ---................... *.......................
0.92 . .... ---- .................................... ................. I-------............ ...........
0 88............................................................................... ............
0.84 ________________________________________
70 75 80 85
ENT CW SET POINT
Figure 4.6. 95 % Confidence Intervals for Daily Average Total System Efficiencyat Each Set Point Temperature
57
TOTAL SYSTEM KW/RT VS ENT CW SET
C90% CONFIDENCE INTEPVALD
KW/ P~T
.......: T.... i ........... ....--- ......---.---
0 .88 .. ...... *....... .................... ................---............. -------............ .. ... ....
0 84 111
70 75 s0 85
ENT OW SET POINT
Figure 4.7. 90% Confidence Intervals for Daily Average Total System Efficiencyat Each Set Point Temperature
58
TOTAL SYSTEM KW/RT VS ENT CW SET
C80% CONEIDENCE INTEPVALD
<~W/ PT1 1 5 .................. . ..................... ...................... ....... . .........
0 92
o 88
70 75 s0 95
ENT OW SET POINT
Figure 4.8. 80% Confidence Intervals for Daily Average Total System Efficiencyat Each Set Point Temperature
59
TOTAL SYSTEM K'N/PT VS ENT CW SET
C50% CONFWDENCE INTEPVALD
rKW/ PT1 16 ...... .... .....
0 96
0 9 2 ---- - ----... ....
0 68 -- --
0,6 1
70 75 80 35
ENT CW SET POINT
Figure 4.9. 50% Confidence Intervals for Daily Average Total System Efficiencyat Each Set Point Temperature
60
4.3 Hourly Data
Due to the large variation in daily data, the hourly field data was examined.
The data was disaggregated by hourly average OSA dry bulb temperature and hourly
average chiller tonnage (RT). The OSA temperature was disaggregated using 5 *F
temperature bins as in the standard weather data. The average chiller tonnage was
disaggregated into 50 RT bins. The chiller efficiency, cooling tower fan efficiency,
and the total system efficiencies were calculated as described in Section 2.4, Data
Acquisition Methodology. Each efficiency was defined as the respective hourly energy
use divided by the hourly RT-hours of chilled water load and had the units of
KW/RT.
The chiller efficiency is known to be a function of the chiller chilled water
load and the entering condenser water set point temperature. It was found that by
plotting the KWc versus the chiller load for each temperature bin and at each
entering condenser water set point temperature, a smooth curve was generated
(Figures 4.10 - 4.13). Figure 4.14 summarizes these data by using a second order
curve fit for each set point temperature.
Figure 4.14 shows that the optimum entering condenser water set point
temperature based solely on chiller energy consumed is 70 'F. This differs from the
daily data results, which showed an optimum of 75 'F. This difference is due to the
chiller efficiency being a function of both chiller loading as well as the set point
temperature.
61
CHILLER KWIRT VS LOAD(85 ENT CW TEMP)
1 .5
0 42 A 47 C 5257 + 62 o 67
1 .3
11 o
3=3
0.9
0.8300 350 400 450 500 550 600 650 700 750RVG RT
Figure 4.10. Chiller Efficiency vs. Part Load for 85 *F Ent CW Set PointTemperature
62
CHILLER KWIRT VS LOAD(80 ENT CW TEMP)
o 42 o 52 57
.4 + 52 o 67
.2 - \
1.1-
0.8300 350 400 450 500 550 600 650 700 750
RVG RT
Figure 4.11. Chiller Efficiency vs. Part Load for 80 *F Ent CW Set PointTemperature
63
CHILLER KWIRT VS LOAD(75 ENT CW TEMP)
.5 A 47 a3 52 57
F + 62 0 57
:3 .0
0.9-
0.8"o
0.7 -300 350 400 450 500 550 600 650 700 750
RVG RT
Figure 4.12. Chiller Efficiency vs. Part Load for 75 *F Ent CW Set PointTemperature
64
CHILLER KWIRT VS LOAD(70 ENT CW TEMP)
15
0 42 A47 o 52
0 ~57 + 62 o 671 .3
1.2-
1.0
0.9
0 8
0.7300 350 400 450 500 550 600 650 700 750
RVG RT
Figure 4.13. Chiller Efficiency vs. Part Load for 70 'F Ent CW Set PointTemperature
65
CHILLER KWIRT VS LOAD.5
85 ENT- 80 ENT .. 75 ENT-1.4
70 ENT-
1. 3
3C 14.0
0.7300 350 400 450 500 550 600 650 700 750
AVG RT
Figure 4.14. Chiller Efficiency vF. Part Load for Each Ent GW Set PointTemperature
66
In the daily data, the chiller loading varied during each day. Ideally, this
variance and tne daily average for each day would be the same. However, the data
show this situation was not the case. For example, the average daily chiller tonnage
(RT) at 75 OF is 526 RT, whereas the average tonnage at 70 OF is 501 RT. The
hourly data removes the effect of variation in the efficiency due to changing load.
Although the variation in efficiency due to changing load is small compared to the
efficiency change due to changing set point temperature, the varying load causes
scatter in the daily data and accounts for the difference in the optimum between
daily and hourly data.
The data show there are two competing effects which to contribute to the
overall increase in the measure of chiller efficiency as part load is decreased. As
part load decreases, the compressor operates less efficiently causing an increase in
the required KW/RT to operate the compressor. In ontrast, the evaporator
temperature (TE) increases and the condenser temperature (Tc) decreases causing
the pressure difference between the evaporator and condenser to decrease as the
chiller loading decreases. This decrease in the pressure rise across the compressor
results in less KW/RT to operate the compressor as described previously in Section
4. A,Daily Data. The combined effect causes the chiller KW/RT to initially decrease
as the loading decreases and then to increase. The effect of the compressor
inefficiencies is much larger than, and quickly overcomes, the effect due to the
67
temperature difference. In Figure 4.14, the initial decrease in KW/RT is not
evident due to no data being available at full load condition.
The cooling tower fan operation time is a function of OSA temperature and
entering condenser water set point temperature. Although the cooling tower
performance is more directly a function of OSA wet bulb temperature, the accuracy
of the humidity sensor at the Peachtree Plaza was questionable and could not be
calibrated; therefore, the OSA dry bulb temperature is used to correlate the cooling
tower fan performance. It was found that by plotting the KWF/RT as a function of
OSA temperature bin for each refrigeration ton bin and at each set point
temperature, a straight line was generated (Figures 4.15 - 4.18). Figure 4.19 shows
a linear regression curve fit for each set point temperature. As expected considering
cooling tower performance, the tower fan efficiency (KWF/RT) increases as the
entering condenser water set point temperature is decreased.
The total system efficiency is known to be a function of the chiller chilled
water lead, the OSA temperature, and the entering condenser water set point
temperature. Plotting the KWT/RT as a function of the chiller load for each
temperature bin and at each entering condenser water set point temperature
generated a smooth curve using a second order curve fit for each set point
temperature (Figure 4.20).
68
TOWER FAN KWIRT VS OSA TEMP(85 ENT CW TEMP)
0.20
0.18 - o 300 TONS a 350 TONS 0 400 TONS
0.15 - 450 TONS + 500 TONS 0 550 TONS
C.14 - 600 TONS n 550 TONS 0 700 TONS
0.22 A 750 TONS
0. 0
z0.08
0.06
0.02[ - +::°
0.O0-42 47 52 57 62 67
OSR TEMP BIN
Figure 4.15. Tower Fan Efficiency vs. OSA Temp Bin for 85 °F Ent CW Set PointTemperature
69
TOWER FAN KW/RT VS OSA TEMP(80 ENT CW TEMP)
0.28 - 300 TONS a 350 TONS o 400 TONS
0.24 450 TONS + 500 TONS o 550 TONS
600 TONS v 650 TONS 0 700 TONS0.20
A 750 TONS
0.16
0.08 -
0.04 F0.001-°
42 47 52 57 62 67OSR TEMP BIN
Figure 4.16. Tower Fan Efficiency vs. OSA Temp Bin for 80 'F Ent CW Set PointTemperature
70
TOWER FAN KWIRT VS OSA TEMP(75 ENT CW TEMP)
0.28 0 300 TONS A 350 TONS 0 400 TONS
0.24 - 450 TONS + 500 TONS o 550 TONS
600 TONS a 650 TONS 0 700 TONS0.20
a 750 TONS
0.16
N
S0.12-
0.04
0.0042 47 52 57 62 67
OSR TEMP BIN
Figure 4.17. Tower Fan Efficiency vs. OSA Temp Bin for 75 'F Ent CW Set PointTemperature
71
TOWER FAN KWIRT VS OSA TEMP(70 ENT CW TEMP)
0.28 0 300 TONS a 350 TONS 0 4C0 TONS
0.24 - 450 TONS .500 TONS o 550 TONS
6C0 TONS u 650 TONS 0 700 TONS
0.20 -
0.120
.08"
0.04~
0.00'42 47 52 57 52 67
OSR TEMF BIN
Figure 4.18. Tower Fan Efficiency vs. OSA Temp Bin for 70 °F Ent CW Set PointTemperature
72
TOWER FAN KWIRT VS OSA TEMP0.28- 85 ENT -80 ENT 75 ENT --
0.24 - 70 ENT-"
0.20
S0.12 -------
---- ------
... .. .. ... ... .
0.0042 47 52 57 62 67- 72
Q9; TEMP BIN
Figure 4.19. Tower Fan Efficiency vs. OSA Temp Bin for Each Ent CW Set PointTemperature
73
TOTAL SYSTEM KWIRT VS LOAD.5
1. 5 ENT- 75 ENT--
7 80OENT.. 70 ENT-
1.3-
0.9 ......
0.7300 350 400 450 500 550 600 650 700 750
RVG RT
Figure 4.20. Total System Efficiency vs. Part Load for Each Ent CW Set PointTemperature
74
The resulting curves in Figure 4.20 show an optimum entering condenser
water set point temperature of 85 'F below 450 RT and an optimum of 80 *F above
450 RT. This result indicates the benefit of varying the set point temperature with
the chiller load, the OSA temperature, or possibly both. The ideal control strategy
would be to vary the set point temperature based on chiller load and OSA
temperature.
4.4 Analytical Model
4.4.1 Simulation I
As described in Chapter III, simulation 1 used measured weather data and
measured chiller component performance data obtained at the Peachtree Plaza Hotel
in the chilled water system analytical model used in this study. The operating
parameters are shown in Table 3.3. The compressor model was changed to more
accurately reflect field chiller performance data.
In the compressor model, the isentropic efficiency predicted by the analytical
model, i%,, , was adjusted by a ratio of the manufacturer's full load design
efficiency (0.65 KW/RT in this case) to the actual full load chiller efficiency at
standard conditions (85 'F entering CW temperature, 45 *F CHWS temperature) as
reflected in the field data. Since no full load efficiency data was collected, the full
load chiller efficiency was assumed to be 0.85 KW/RT which was the chiller
efficiency at the greatest load measured (750 RT) at a set point temperature of
75
85 'F. This assumption seems reasonable since the part load efficiency does not
change significantly above a part load of 80%. To summarize, the ratio used in this
study was 0.65/0.85.
The part load efficiency, %., was also adjusted to agree with the measured
decrease in compressor efficiency with decreasing loads. The actual part load
efficiency, .,., is given as:
(KW/R) , -, L"SA'-" (4.2)- (KWIRT)3", * %,,w ,,,, em mo,*,
The model isentropic efficiency, 7,,, ,d,, was then calculated as described above.
The actual isentropic efficiency, -6 ,, was calculated using field data at three part
load conditions (300, 600, and 700 or 750 RT) for each set point. Then, the data was
analyzed to produce an empirical expression for 7, by using a second order
polynomial curve fit to the data points (Figure 4.21).
The data clearly show that the manufacturer's part load efficiency is optimistic.
The fact that the part load efficiency can be well represented as a function of the
part load parameter only shows the validity of the chiller model.
The results of simulation 1 are shown graphically in Figures 4.22 - 4.24
(Numerical results are included in Appendix 2). The results for the chiller and total
system efficiencies produced by this simulation closely approximate the field data
results.
76
The simulation results for the tower fan efficiency differ from the measured
data in this work. This difference can be explained by the fact that the cooling tower
is performing less efficiently than the specification given by the manufacturer. The
original fill material in the cooling tower cells at the Peachtree Plaza was replaced.
The new fill material causes the water to fall in sheets rather than droplets, and
results in a less efficient cooling process.
77
PART LOAD COMPRESSOR EFFICIENCY(RCTURL)
I .0 - - - -- - - - - -
0.9 -
0.7"I5
o.- I. 80LLIj /.,
0.5 / 75//LL 75
LU 0.4 c: /70
0 / MODELS0.2 -
0.1 "
0. 00.0 0.1 0.2 0.J 0.4 0.5 0.6 0.7 0.8 0.9 1.0
PRRT LORD
Figure 4.21. Actual Part Load Efficiency
78
KW/RT VS ENT CW SET POINT
CCHf LLEPJ
Kw/ AT
1 .0 8 .. .. .......... ... .... . I. ... .... ...... .... ...... ..... ....... .. .... .......
o *6
70 75 80 85 90
ENT CW SET POINT
X~ ACTUAL 9 SIMULATION 1 46 SIMULATION 2
Figure 4.22. Chiller Efficiency Comparison to Daily Field Results
79
KW/PT V'S ENT CW SET POINT
CTOWER FANSD
KW/ PT
0 7 5----- .. ... ... ...... ... . 8 5.. ............
0 80
KW/RT VS ENT CW SET POINTCTOTAL SYSTEMJ
<W/ PT1 .2 -- -- .. .. .... ... ... ... ... .. .. ..... .. ... ... ..... .... .. .. ..... ......... .... .. ... ... .. ... .. .... .
7 0 ....... 8 0..... 8 5......... ... 9.*.... ...... 0... ----
ENT CW IE ON
~ACTUAL 9 SIMULATION I S5IMULATION 2
Figure 4.24. Total System Efficiency Comparison to Daily Field Results
81
4.4.2 Simulation 2
Simulation 2 used standard weather data and manufacturer's component data
as outlined in Chapter III. The analytical model was run as discussed in Chapter III.
The simulation calculated the monthly and yearly chiller, tower fan, and total system
energy use. The results of the simulation are shown graphically in Figures 4.25 - 4.28
(Numerical results are included in Appendix 2). The monthly energy use for
November was used to calculate chiller, tower fan, and total system efficiencies.
These efficiencies are also plotted on Figures 4.22- 4.24.
As illustrated in Figures 4.22,the manufacturer's data for chiller performance
is optimistic. The manufacturer's full load design efficiency is 0.65 KW/RT
compared to an actual full load efficiency of 0.85 KW/RT at standard rating
conditions. The part load compressor performance is also significantly less for
manufacturer and field data. Although the absolute chiller efficiency is
underpredicted by the analytical model when using manufacturer's data, the observed
trends for the simulation match the trends shown in the field data.
The monthly energy use profiles (Figures 4.26- 4.28) show that the sensitivity
due to the effect of changing the set point temperature is greater during the peak
cooling periods. Although the change in chiller energy due to decreasing set point
temperature is not significant, the energy penalty due to the increase in cooling tower
fan run-time is severe. Running away from the optimum set point during the
summer months results in a larger peak electrical demand than running at the
82
optimum. This peak could result in high electrical demand charges which are paid
throughout the year. The monthly energy use profile also further shows that the
condenser water set point temperature should be ideally varied based on chiller
loading and OSA temperature.
Looking at the yearly energy use in Figure 4.28, the chiller energy use
decreases for decreasing set point until 75 °F and then increases. The tower fan
energy use increases with decreasing set point. The total system energy use
decreases for decreasing set point until 85 °F and then increases. The decrease in
chiller energy use from 85 'F to 75 °F is overcome by the increase in tower fan
energy. The annual optimum constant entering condenser water set point
temperature based on total system energy use is 85 *F.
The yearly simulation results show that it is more advantageous to select a
higher entering condenser water set point temperature when considering the total
energy consumption of the system. This result is contrary to the customary practice
in the field. Operators tend to select lower set point temperatures to avoid perceived
problems in chiller operation. This practice is costly. In decreasing the set point
temperature from 85 °F to 70 °F, the total system energy use is predicted to increase
by 320,000 KWH/year. At an average cost of 8 C/KWH, the yearly increase in
energy cost would be $25,000.
83
MONTHLY CHILLEP ENEPGYCHILLEP ENEPGY CKWH) CThousandsD
400
300
200
100
JAN FEB MAP APP MAY JUN JUL AUG SEP OCT NOV DEC
MONT H
Figure 4.25. Predicted Monthly Chiller Energy
84
MONTHLY FAN ENERGYFAN ENEPGY CKWH) CThouSandSD
1401
120
100
80
40
20
0JAN FES MAP APP MAY JUN JUL AUG SEP OCT NOV DEC
MONTH
Figure 4.26. Predicted Monthly Fan Energy
85
MONTHLY TOTAL E--NERGOTOTAL ENEPGY CKWHD CThousandsD
500
400
300
200
100
JAN FEB MAP APP MAY JUN JUL AUG SEP OCT NOV DEC
MONTH
= 70 75 M 90 95 90
Figure 4.27. Predicted Monthly Total System Energy
86
YEARLY ENERGY
ENEPOY CKWH) CThousarnds)
'4000
2000
2000
0
CHILLEP FAN TOTAL
ENERGY TYPE
-075 80 85 30
Figure 4.28. Predicted Yearly Energy
87
CHAPTER V
CONCLUSIONS AND RECOMMENDATIONS
5.1 Conclusions
The following conclusions are drawn from this study:
* Based on the field data taken during twenty winter days, the optimum
constant entering condenser water set point temperature is 80 'F for winter months.
(No field data was taken during summer months.) Although greater chiller energy
savings are possible by lowering the set point temperature further, these savings are
outweighed by the significant increase in cooling tower fan energy use.
* Analysis of the data on an hourly basis illustrates the effects of both chiller
loading and entering condenser water set point temperature on the energy use.
Based on the total system energy consumed for part loads less than 50%, the
optimum entering condenser water set point temperature was found to be 85 'F; for
part loads greater than 50%, the optimum was found to be 80 'F.
• The chilled water system analytical model developed by Weber predicts
trends and optimums in agreement with the field data. A comparison between actual
field results and the results produced by a simulation based on field weather data
and field chiller component performance data confirms the validity of the analytical
model proposed by Weber. In contrast, the energy use from the simulation based on
88
standard weather data and manufacturer's performance data were found to be
optimistic when compared to actual field results. However, the general trends are
the same. The use of this model, therefore, will accurately predict the optimum set
point temperature, but the data show that the absolute energy use will be under
predicted.
* Using a constant entering condenser water set point temperature over the
entire year, the analytical model predicts the optimum set point temperature to be
85 OF based on total system energy use. A comparison between total energy use for
lower set points and 85 OF shows that lowering the set point further would cost
approximately $25,000/year for a 1000 RT chiller. In practice, the current tendency
to set condenser water set point temperatures lower should be avoided. The data
show the energy use penalty for set point temperatures above the optimum is less
than for set points below the optimum. Simply stated, when in doubt, choose the
higher entering condenser water set point temperature. However, the chiller
manufacturer's recommendation regarding the maximum condenser water set point
temperature should not be exceeded. This temperature is typically 85 OF - 95 OF.
0 The optimum condenser water set point temperature is of greater
importance in the summer months when the energy penalty for increased tower fan
run-time at lower set point temperatures is significantly greater. This result further
emphasizes the need to avoid the current practice of setting the condenser water set
point temperature as low as possible.
89
5.2 Recommendations
The results of this study have provoked questions which need further study.
The recommendations of the author for further study are as follows.
* More field data should be gathered for a greater variety of chiller loads,
OSA temperatures, and buildings.
* Since the cooling tower fan energy use is more directly related to OSA wet
bulb temperature, wet bulb temperature should be measured. The data should be
analyzed relative to the wet bulb temperature rather than the dry bulb temperature.
e The analysis of the data should be based on actual entering condenser
water temperature, rather than minimum set point temperature. The chiller
performance is known to be directly related to the actual water temperature entering
the condenser, and this temperature may be higher than the minimum set point
temperature during peak cooling periods. This correlation would be necessary to
develop a more accurate chiller performance map based on field data.
* In practice, cooling tower fans are controlled by the entering condenser
water temperature. However, it would be instructive to explore possible advantages
in controlling the cooling tower fans using the water temperature leaving the
condenser. For certain chiller load and OSA temperature combinations, the energy
consumed by the total system may be less for cooling tower fan control using a
leaving condenser water set point temperature.
90
* The field and simulation results suggest that the optimum control strategy
would vary the condenser water set point temperature based on OSA temperature
and chiller loading. A greater range of field data would show this dependence and
provide further information necessary to develop a general strategy to optimize the
chilled water plant.
91
o o
ooo- o5o-
.. . .. . . ... = - - -
-- - -- - -- --3-
. .. .. .. .. .I~C
. ! o o .
.. . . .. . . . .. . . .
- - -
.. . . . . . . . . . . .
- - ---- --- ---
-. -1
IJ ----
-- --- ----- ----- ------------ ---- ---- --3
if
-- ---------
--------
- ----- - -
----- -- --- - - - - - - - - - - - - -
.. . .. . . .. . .. . .
-
j
xi~
94
--!
-- - - -- - - - -- - - -
.---------- ~ - -
--- -- - ------ -- -
aIL U P4
2B ------------ s
IR4-
El a
96
........... ....
.....................
--- -- --
..... ............ ......
z.
---
Mi
al
I ~ 2:2S:2 332:: S:~:!all
-597
ii f R~I
4 4 4 4 4
..........
-- -- - -- -- - - ---
-- -- - -- -
...... . . . .. . . . .
t* -g -- 4.; .; - .. ;CC - -.
II
A Si A 2z2j ii-3 4-; -.. . . . . .. . . . . .
v i a iz NC-- ---- ---I ~
~9
-- -- - -- -- -
- -- -- 0 -P - . . -...
--------
...... .. . . .
------------ 5
~ --------------
-- - -- - -- - - ..... . ..
101
EIi -----------------
2.A
-- -- -- --
-- -- -- --.- - -
................
4 S--------------------------....
- g-a -
104
.. . . .. 4 4 4 . . .
~~~I~ aleooo -
4.4 44 .. . .
all
-- - - -- - - - -- - - -
~-------------
-- - - -- - - -
-- - - - -
-- -- -- -
-s -z- zssss
-- z
-- -- - - - - - - - -
I
105
- ........... *
-----------------
--- -- --
-- - - - - -
----- ---- --- - - - -
------ ------
-7 --1 !--1!" !-
r" 0
;~ -p109
TMIN COMPUTER MODEL RESULTS: SIMULATION I(BASED ON EXPERIMENTAL DATA)(3441 GPM, 1036960 CFM, 900 NON TONS, 2 PASS CONDENSER, 12" PIPE DIAMETER)
(DATA USED IN FIGURES 4.22 - 4.24)
PREDICTEDBIN HOURS TONS TONERS
72 1 703.30 703.3067 80 636.14 50891.2062 100 568.98 56898.0057 140 501.82 70254.8052 77 434.65 33468.0547 52 367.49 19109.4842 4 300.33 1201.32
TOTAL TONERS: 232526
SIMULATION RESULTS:
SET KWHC/ KWHFI KW,'T/POIN. KWC KWHY KBTA, TONI TON' TONER
---------------------------------------70 216432.3 13917.6 230349.9 0.9308 0.0599 0.990675 219136.9 9226.0 228362.9 0.9424 0.0397 0.982180 221349.0 6171.3 227520.3 0.9519 0.0265 0.978585 230351.1 4174.4 234525.5 0.9906 0.0180 1.00869( 238399.3 2710.5 241109.8 1.0253 0.0117 1.0369
114
TKIN COMPUTER MODEL RESULTS: SIMULATION 2(BASED ON STANDARD WEATHER DATA; MANUFACTURER'S CHILLER DATA;)(.65 KWITON; ACTUAL BUILDING LOAD PROFILE)(3093 GPM, 1036960 CFM, 1000 NON TONS, 2 PASS CONDENSER, 12" PIPE DIAMETER)
(DATA USED IN FIGURES 4.25 - 4.27)
NUM COND WATER TEMP: 70CHILLER/
PUMP FAN CHILLER TOTAL FANMONTE ENERGY ENERGY ENERGY ENEG ENERGY
1 JAN 16138.41 7231.15 127441.90 150811.46 134673.052 FEB 17390.84 7967.60 140927.40 166285.84 148895.003 MAR 22686.81 13177.96 194040.20 229904.97 207218.164 APR 25263.23 29036.68 250631.20 304931.11 279667.885 KAY 26623.01 62944.45 307583.50 397150.96 370527.956 JUN 25764.20 102528.20 328855.70 457148.10 431383.907 JUL 26730.36 126483.80 350870.90 504085.06 477354.708 AUG 26587.22 120571.00 348967.00 496125.22 469538.009 SEP 25692.63 81922.63 307444.90 415060.16 389367.53
10 OCT 26229.39 35992.36 263858.50 326080.25 299850.8611 NOV 21935.36 13719.05 186866.70 222521.11 200585.7512 DEC 16675.16 6663.49 130005.70 153344.35 136669.19
TOTAL 277716.62 608238.38 2937493.60 3823449 3545732
115
TMIN COMPUTER MODEL RESULTS: SIMULATION 2(BASED ON STANDARD WEATHER DATA; MANUFACTURER'S CHILLER DATA;)(.65 KW/TON; ACTUAL BUILDING LOAD PROFILE)(3093 GPM, 1036960 CIM, 1000 NON TONS, 2 PASS CONDENSER, 12" PIPE DIAMETER)
(DATA USED I FIGURES 4.25 - 4.27)
MINIMUM COND WATER TEMP: 75CHILLER/
PUMP FAN CHILLER TOTAL FANMONTH ENERGY ENERGY ENERGY ENERGY ENERGY
I JAN 16138.41 4596.12 125247.40 145981.93 129843.522 FEB 17390.84 5151.60 138660.30 161202.74 143811.903 MAR 22686.81 8722.57 191369.60 222778.98 200092.174 APR 25263.23 19618.46 248713.70 293595.39 268332.165 MAY 26623.01 40321.51 307115.20 374059.72 347436.716 JUN 25764.20 66638.15 329239.50 421641.85 395877.657 JUL 26730.36 91452.79 351388.90 469572.05 442841.698 AUG 26587.22 82432.61 349636.30 458656.13 432068.919 SEP 25692.63 50801.53 307337.30 383831.46 358138.83
10 OCT 26229.39 23797.69 261962.00 311989.08 285759.6911 NOV 21935.36 9003.72 184256.10 215195.18 193259.8212 DEC 16675.16 4210.51 127697.40 148583.07 131907.91
TOTAL 277716.62 406747.27 2922623.70 3607088 3329371
116
ThIN COMPUTER MODEL RESULTS: SIMULATION 2(BASED ON STANDARD WEATHER DATA; KANUFACTURERIS CHILLER DATA;)(.65 KW/TON; ACTUAL BUILDING LOAD PROFILE)(3093 GPM, 1036960 CI'M, 1000 NOM TONS, 2 PASS CONDENSER, 12" PIPE DIAMETER)
(DATA USED IN FIGURES 4.25 - 4.27)
MINIMUM COND WATER TEMP: 80CHILLER/
PUMP FAN CHILLER TOTAL FANMONTH ENERGY ENERGY ENERGY ENERGY ENERGY
1 JAN 16138.41 2893.37 125765.10 144796.88 128658.472 FEB 17390.84 3330.96 139342.80 160064.60 142673.763 MAR 22686.81 5826.03 192621.10 221133.94 198447.134 APR 25263.23 13755.92 251405.80 290424.95 265161.725 MAY 26623.01 28060.48 311798.30 366481.79 339858.786 JUN 2'n4.20 43717.54 335233.20 404714.94 378950.747 JUT 26730.36 56778.35 358056.90 441565.61 414835.258 1Ic 26587.22 52525.93 356286.00 435399.15 408811.939 F. 25692.63 34278.84 312316.00 372287.47 346594.84
10 OCT 26229.39 16502.93 264884.60 307616.92 281387.53Al NOV 21935.36 6001.36 185432.50 213369.22 191433.8612 DEC 16675.16 2662.61 128178.60 147516.37 130841.21
TOTAL 277716.62 266334.32 2961320.90 3505372 3227655
117
T IN COMPUTER MODEL RESULTS: SIMULATION 2(BASED ON STANDARD WEATHER DATA; MANUFACTURER'S CHILLER DATA;)(.65 KW/TON; ACTUAL BUILDING LOAD PROFILE)(3093 GPM, 1036960 CFM, 1000 NOM TONS, 2 PASS CONDENSER, 12" PIPE DIAETER)
(DATA USED IN FIGURES 4.25 - 4.27)
MIIMUM COND WATER TEMP: 85CHILLER/
PUMP FAN CHILLER TOTAL FANMONTH ENERGY ENERGY ENERGY ENERGY ENERGY
1 JAN 16138.41 1861.16 128190.30 146189.87 130051.462 FEB 17390.84 2158.51 142116.00 161665.35 144274.513 MAR 22686.81 3902.48 196699.10 223288.39 200601.584 APR 25263.23 9813.58 257578.70 292655.51 267392.285 MAY 26623.01 20398.31 320559.60 367580.92 340957.916 JUN 25764.20 31092.65 345460.00 402316.85 376552.657 JUL 26730.36 39348.87 369203.20 435282.43 408552.078 AUG 26587.22 36869.73 367391.10 430848.05 404260.839 SEP 25692.63 24597.47 321329.80 371619.90 345927.27
10 OCT 26229.39 11736.50 271456.80 309422.69 283193.3011 NOV 21935.36 4034.52 189334.80 215304.68 193369.3212 DEC 16675.16 1706.28 130615.00 148996.44 132321.28
TOTAL 277716.62 187520.06 3039934.40 3505171 3227454
118
THIN COMPUTER MODEL RESULTS: SIMULATION 2(BASED ON STANDARD WEATHER DATA; MANUFACTURER'S CHILLER DATA;)(.65 KWITON; ACTUAL BUILDING LOAD PROFILE)(3093 GPM, 1036960 CFM, 1000 NON TONS, 2 PASS CONDENSER, 12" PIPE DIAMETER)
(DATA USED IN FIGURES 4.25 - 4.27)
MINIMUM COND WATER TEMP: 90CHILLER/
PUMP FAN CHILLER TOTAL FANMONTH ENERGY ENERGY ENERGY ENERGY ENERGY
1 JAN 16138.41 1153.75 132201.10 149493.26 133354.852 FEB 17390.84 1342.86 146635.50 165369.20 147978.363 MAR 22686.81 2544.76 203163.10 228394.67 205707.864 APR 25263.23 7037.00 266780.40 299080.63 273817.405 MAY 26623.01 15170.24 332995.40 374788.65 348165.646 JUN 25764.20 23111.73 359597.30 408473.23 382709.037 JUL 26730.36 28892.84 384514.60 440137.80 413407.448 AUG 26587.22 27266.38 382641.40 436495.00 409907.789 SEP 25692.63 18247.84 334008.20 377948.67 352256.04
10 OCT 26229.39 8377.66 281211.30 315318.85 289589.4611 NOV 21935.36 2653.82 195536.00 220125.18 198189.8212 DEC 16675.16 1050.83 134671.90 152397.89 135722.73
TOTAL 277716.62 136849.70 3153956.70 3568523 3290806
119
THIN COMPUTER MODEL RESULTS: SIMULATION 2(BASED ON STANDARD WEATHER DATA; MANUFACTURER'S CHILLER DATA;)(.65 KW/TON; ACTUAL BUILDING LOAD PROFILE)(3093 GPM, 1036960 CFM, 1000 NON TONS, 2 PASS CONDENSER, 12" PIPE DIAMETER)
(DATA USED IN FIGURE 4.28)
YEARLY YEARLY YEARLYSET CHILLER FAN TOTAL
POINT ENERGY ENERGY ENERGY
70 2937494 608238 354573275 2922624 406747 332937180 2961321 266334 322765585 3039934 187520 322745490 3153957 136850 3290806
120
TMIN COMPUTER MODEL RESULTS: SIMULATION 2(BASED ON STANDARD WEATHER DATA; MANUFACTURER'S CHILLER DATA;)(.65 KWiTON; ACTUAL BUILDING LOAD PROFILE)(3093 GPM, 1036960 CFM, 1000 MOK TONS, 2 PASS CONDENSER, 12" PIPE DIEER)
PREDICTED ENERGY USE FOR NOVEMBER(DATA USED IN FIGURES 4.22 - 4.24)
PREDICTEDBIN HOURS TONS TONERS
82 1 837.67 837.6777 6 770.50 4623.0272 25 703.34 17583.4867 54 636.17 34353.4062 92 569.01 52348.3357 111 501.84 55704.6852 113 434.679 49118.7347 117 367.514 42999.1442 94 300.349 28232.81
TOTAL 613 285802
SET KWHC/ vu/ KWHT/?ODT KWHC KWHF KWHT TONER TONE TONMR
70 186866.7 13719.1 200585.8 0.6538 0.0480 0.701875 184256.1 9003.7 193259.8 0.6447 0.0315 0.676280 185432.5 6001.4 191433.9 0.6488 0.0210 0.669885 189334.8 4034.5 193369.3 0.6625 0.0141 0.676690 195536.0 2653.8 198189.8 0.6842 0.0093 0.6935
121
BIBLIOGRAPHY
American Society of Heating, Refrigerating, and Air-Conditioning Engineers(ASHRAE). 1989. ASHRAE Handbook of Fundamentals. Atlanta:ASHRAE.
American Society of Heating, Refrigerating, and Air-Conditioning Engineers. 1988.ASHRAE Equipment Handbook. Atlanta: ASHRAE.
Baumeister, Theodore, ed. 1978. Mark's Standard Handbook for MechanicalEngineers. New York: McGraw-Hill Book Company.
Braun, J.E. 1988. "Methodologies for the Design and Control of Central CoolingPlants." Ph.D. Thesis. University of Wisconsin-Madison.
Braun, J.E.,Klein, S.A.,Beckman, W.A.,and Mitchell, J.W. 1989a. "Methodologiesfor Optimal Control of Chilled Water Systems without Storage," ASHRAETransactions. Vol. 95, Part 1.
Braun, J.E., Klein, S.A.,Mitchell, J.W.,and Beckman, W.A. 1989b. "Applicationsof Optimal Control to Chilled Water Systems without Storage." ASHRAETransactions. Vol. 95, Part 1.
Braun, I.E., Mitchell, J.W., Klein, S.A., and Beckman, W.A. 1987. "Performanceand Control Characteristics of Large Central Cooling Systems." ASHRAETransactions. Vol. 93, Part 1.
Cascia, M.A. 1988. "Optimizing Chiller Plant Energy Savings Using Adaptive DDCAlgorithms." ASHRAE Transactions. Vol. 94, Part 2.
Clifford, G. 1990. Modem Heating. Ventilating, and Air-Conditioning. New Jersey:Prentice Hall.
Hackner, R.J.,Mitchell, J.W.,and Beckman, W.A. 1984. "HVAC System Dynamicsand Energy Use in Buildings- Part I." ASHRAE Transactions. Vol. 90,Part 2B.
122
1985a. "HVAC System Dynamics and Energy Use in Buildings- Part II."
ASHRAE Transactions. Vol. 91, Part lB.
1985b. "System Dynamics and Energy Use." ASHRAE Journal. June 1985.
Hines, W.W. and Montgomery, D.C. 1990. Probability and Statistics in Engineeringand Management Science. New York: John Wiley & Sons.
Johnson, G.A. 1985. "Optimization techniques for a Centrifugal Chiller Plant Usinga Programmable Controller." ASHRAE Transactions. Vol. 91, Part 2.
Joyce, C.T. 1990. "Optimized Design of a Commercial Building Chiller/CoolingTower System." Master's Thesis. Georgia Institute of Technology.
Lau, A.S.,Beckman, W.A.,and Mitchell, J.W. 1985. "Development of ComputerizedControl Strategies for a Large Chilled Water Plant." ASHRAE Transactions.Vol. 91, Part lB.
Lowe, H.J. and Christie, D.G. 1961. "Heat Transfer and Pressure Drop Data onCooling Tower Packings, and Mode Studies of the Resistance of Natural-Draught Towers to Airflow." ASME Heat Transfer Proceedings. Paper 113.
Press, W.H.,Brian, P.F.,Teukolsky, S.A.,and Vetterling, W.T. 1989. NumericalRecipeg: The Art of Scientific Computing. Cambridge: CambridgeUniversity Press.
Sud, I. 1984. "Control Strategies for Minimum Energy Usage." ASHRAETransactions. Vol. 90, Part 2.
Trane Co., Inc. 1987. "Tracer 100 Building Management System ProgrammingGuide." Pamphlet EMTB-PG-1A.
Trane Co., Inc. 1989. "Chiller Plant System Performance." Engineering Newsletter.Vol. 18, No. 2. Trane Co., Inc. Lacrosse, Wisconsin.
Tuve, G.L. and Domholdt, J.C. 1966. Engineering Experimentation. New York:McGraw-Hill Book Company.
United States. Department of the Air Force. 1978. AFM 88-29: EngineeringWeather Data. Washington: GPO.
123