Newcomb&&&&Boyd
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800
Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
TM
JOSEPH MYNHIERREG.#013741
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
80 JESSE HILL JR DRIVE SEATLANTA GA, 30303
ISSUED FORCONSTRUCTIONJUNE 27, 201617220005
CONSTRUCTION DOCUMENTS
EYE CLINIC RENOVATION
DRAWING INDEX
ARCHITECTURE & INTERIORS ELECTRICAL FIRE PROTECTION
FIRE ALARM
A-100 3RD FLOOR EXISTING PLAN & 3RD FLOOR LIFE SAFETY PLAN, & ICRA NOTESA-101 3RD FLOOR DEMOLITION PLAN & ALTERNATESA-102 3RD FLOOR REFLECTED CEILING PLAN ARCH PLANSA-102 INTERIOR FINISH PLANA-500 SCHEDULES, PARTITION TYPES, DETAILSA-600 INTERIOR ELEVATIONSA-601 INTERIOR ELEVATIONSA-800 DETAILS
E-000 ELECTRICAL LEGENDE-100 ELECTRICAL POWER THIRD FLOOR DEMOLITION PLANE-101 ELECTRICAL POWER THIRD FLOOR PLANE-200 ELECTRICAL LIGHTING THIRD FLOOR PLANE-300 ELECTRICAL SCHEDULESE-400 ELECTRICAL DETAILS
FA-000 FIRE ALARM LEGEND AND DETAILSFA-101 FIRE ALARM THIRD FLOOR PLAN
FP-000 FIRE PROTECTION LEGEND AND DETAILSFP-101 FIRE PROTECTION THIRD FLOOR PLAN
M-000 HVAC LEGEND AND GENERAL NOTESM-100 HVAC THIRD FLOOR DEMOLITION PLANM-101 HVAC THIRD FLOOR PLANM-200 HVAC CONTROLS, SCHEDULES, DETAILS
P-000 PLUMBING LEGENDS AND ABBREVIATIONSP-100 PLUMBING PRESSURE THIRD FLOOR DEMOLITION PLANP-101 PLUMBING PRESSURE THIRD FLOOR PLANP-200 PLUMBING WASTE THIRD FLOOR DEMOLTION PLANP-201 PLUMBING WASTE THIRD FLOOR PLANP-300 PLUMBING DETAILSMECHANICAL
PLUMBING
TO
LOBBY
OPEN
OPEN TO LOBBY
#7
CORRIDOR
CORRIDOR
HCT
HCT
HSK
S.U.
#22
#23
CORRIDOR
AUDIO
ABR
FAC
PEDS
SEC
AUDIO
AUDIO
COM
HCT
MED
COPIER
UNIT
MGR
ROOM
WORK
#57
WORK
RES/
WAITING
CLASSROOM
INV.
CORRIDOR
LOBBY
WAITING
RECPT.
INVESTIG.
ELEV
WAITING
CORRIDOR
#22
EXAM
CORRIDOR
EXAM
ELEC
COM
#23
RECPT.
HCT
HCT
#23
#23
NUR
S.U.
CORRIDOR
C.U.
EXAM
EXAM
EXAM
HCT
HCT
EXAM
WH
STRCH
HCT
HSK
STR
EXAM
LOUNGE
CONF.
W.
SOC
CORRIDOR
MED
FUND
EXAM
EXAM
UP
DN
UPDN
UPDN
FEC
FEC
LOBBY
ELEV
CLINIC BUILDING
ADDITION (PACKAGE 3)
TLT
INV.
TLT
CORRIDOR
STAIR 13
ELEV 9
ELEV 8
ELEV 4
ELEV 5
ELEV 7
ELEV 6
ELEV 3
ELEV 2
ELEV 1
DCL
STAIR 15
ELEV 10
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRT
CRTCRT
CRT
CRT
PS
FE
PS FE
PS
FE
FE
BREAKROOM
316
OCT.
318
PHYS.WORK 4
319
MANAGER
355
EXAM ROOM
308
DIAG.
314
DIAG.
315
DIAG.
333
DIAG.
334
DIAG.
335
DIAG.
337
CLEAN
336
MINORSURGERY
B-SCAN
342
SOILED
343
ELEC.
317
TLT
338
J/C
339
TLT
340
TLT
331
TLT
330
EXAM ROOM
309
LASER
323
EXAM ROOM
354
EXAM ROOM
353
EXAM ROOM
352
EXAM ROOM
351
EXAM ROOM
350
EXAM ROOM
349
EXAM ROOM
348
EXAM ROOM
347
EXAM ROOM
346
EXAM ROOM
328
EXAM ROOM
327
EXAM ROOM
326
EXAM ROOM
325
EXAM ROOM
324
EXAM ROOM
312
EXAM ROOM
311
EXAM ROOM
310
PHYS.WORK 1
345
OFFICE
332
PHYS.WORK 3
313
PHYS.WORK 2
329
EXAM ROOM
307
SWINGOFFICE
344
WAITING
301
TOIL.
303
CORRIDOR
305
TOIL.
304
CORRIDOR
306
CORRIDOR
320
CORRIDOR
341
CORRIDOR
322
CORRIDOR
321
TRAVEL DISTANCE 202'
TRAVEL DISTANCE 214'
STAIR 13 EXTERIORDISCHARGE , GROUND FLOOR
STAIR 14 DISCHARGE AT BASEMENTLEVEL, INTERIOR EGRESS CORRIDOR
1
XX
PROJECT INFORMATION:NAME: GRADY EYE CLINICADDRESS: 80 JESSE HILL JR DRIVE SE
ATLANTA, GA 30303PROJECT DESCRIPTION: RENOVATION TO 3RD FLOOR SUITE.
OWNER: GRADY HEALTHADDRESS: 80 JESSE HILL JR. DRIVE SE
ATLANTA, GA 30303
DESIGN PROFESSIONAL:ARCHITECT: BSA LIFESTRUCTURESADDRESS: 3348 PEACHTREE ROAD NE, SUITE 1460
ATLANTA, GA 30326CONTACT: JOSEPH I. MYNHIER 404-640-2682
CODE INFORMATION:2012 INTERNATIONAL BUILDING CODE WITH GEORGIA AMENDMENTS2012 INTERNATIONAL FIRE CODE WITH GEORGIA AMENDMENTS2012 INTERNATIONAL MECHANICAL CODE WITH GEORGIA AMENDMENTS2012 INTERNATIONAL PLUMBING CODE WITH GEORGIA AMENDMENTS2014 NATIONAL ELECTRICAL CODE2009 INTERNATIONAL ENERGY CONSERVATION CODE WITH GEORGIA SUPPLEMENTS AND AMENDMENTS2012 NFPA 101 - LIFE SAFETY CODE2010 ADA STANDARDS FOR ACCESSIBLE DESIGN2009 ICC ANSI A117.12014 FGI - GUIDELINES FOR DESIGN AND CONSTRUCTION OF
HOSPITALS AND OUTPATIENT FACILITIES.
BUILDING DATA (3RD K-WING ONLY):NO CHANGES FROM EXISITNG BUILDING DATA
RENOVATED AREA: 9,961 SQ. FT
OCCUPANCY: BCONSTRUCTION TYPE: TYPE IIFIRE COMPARTMENT AREA: 34,130FULL AUTO SPRINKLER SYSTEM YES
LIFE-SAFETY FEATURES:NO CHANGES WILL BE MADE TO THE EXISTING LIFE SAFETY FEATURES.ADDITIONAL EXIT LIGHTS AND EMERGENCY LIGHTS WILL BE ADDED ASREQUIRED BY CODE AS SHOWN IN THE LIFE SAFETY PLAN.
SPRINKLER SYSTEM THROUGH-OUTFIRE RATED SEPARATION WALLSFIRE RATED & SMOKE RESISTIVE CORRIDOR CONSTRUCTIONSMOKE DETECTORS & FIRE ALARM SYSTEMEMERGENCY LIGHTSEXIT LIGHTS
FIRE RESISTANCE RATING REQUIREMENTS:STRUCTURAL FRAME: 1 HOURBEARING WALLS:
EXTERIOR 1 HOURINTERIOR 1 HOUR
NON-BEARING WALL(S) + PARTITIONS:INTERIOR 0 HOURS
FLOOR CONSTRUCTION: 1 HOURSROOF CONSTRUCTION: 1 HOURSSHAFT ENCLOSURE: 2 HOURSEXIT CORRIDOR WALLS: 0 HOURS
CODE SUMMARY
COLUMN LINE
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
PLAN NOTE DESIGNATION
EXIT SYMBOLEXIT
ROOM
000
1
LIFE-SAFETY SYMBOLS LEGEND
WALL RATINGS
1-HOUR RATED FIRE BARRIER- (1H)
1-HOUR SMOKE BARRIER- (SB)
2-HOUR RATED FIRE BARRIER- (2H)
1-HOUR RATED FIRE + SMOKE BARRIER - (1HS)
2-HOUR RATED FIRE + SMOKE BARRIER - (2HS)
SMOKE PARTITION- (SP)
3K005
3K006
3K007
3K008
3K011
3K012
3K013
3K014
3K015
3K0183K021
3K022
3K024
3K025
3K026
3K027
3K028
3K031
3K032
3K033
3K034
3K047
3K0483K051
3K052
3K053
3K054
3K055
3K0653K0643K063
3K045
3K044
3K062 3K061 3K058
WAITING
3K002
CHARTSFILES
3K038
RECEPTION/ CASH.
3K0373K003
3K004
3K043
3K062 3K061 3K058
3K041
3K055
3K040
3K057
RECPT
3K042
RECPT
3K036
3K066
CORRIDOR
3K056
CORRIDOR
3K046
CORRIDOR
3K016
CORRIDOR
3K023
CORRIDOR
3K002
CORRIDOR
3K017
ICRMP NOTES
A. PRIOR TO CONSTRUCTION TO CONTRACTOR SHALL PERFORM ANINFECTION CONTROL RISK ASSESMENT TO DETERMINE THE SCOPE OFTHE ACTIVITY AND PROEJECT CLASS.
B. THE CONTRACTOR SHALL CREATE AND COORDINTE AN INFECTIONCONTROL RISK MANAGAMENT PLAN (ICRMP) WITH THE OWNER.
C. THE DETERMINED CLASS WILL DEFINE THE REQUIREMENTS AND SHALLINCLUDE THE REQUIRMENTS OF ALL LOWER CLASSES.
D. THE CONTRACTOR SHALL COMPLY WITH ALL THE OWNER'SREQUIREMENTS FOR ABOVE CEILING WORK THAT IS OUTSIDE THESCOPE OF WORK DEFINED IN THIS DOCUMENT.
E. THE CONTRACTOR SHALL SUBMIT THE LOCATION OF ALL TEMPORARYWALLS TO THE OWNER FOR APPROVAL.
F. THE CONTRACTOR SHALL COORDINATE THE SCEHDULE OF ALL PHASEDWORK WITH THE OWNER.
G. ALL DOOR THAT ACCESS AREAS OUTSIDE OF THE WORK AREA SHALL BESEALED , WELL MAINTAINED AND ANY DAMAGE REPAIRED IMMEDIATELYTO AVOID MIGRATION OF DUST INTO ADJOINING AREAS.
H. ALL TEMPORARY PARTITIONS SHALL MEET LOCAL CODE.I. ALL TEMPORARY CONSTRUCTION PARTITIONS SHALL BE LOCKED OR
SECURED AT ALL TIMESJ. THE CONTRACTOR SHALL MAINTAIN AL REQUIRED EXITS AND NFPA
INTERMINLIFE SAFETY MEASURES DURING CONSTRUCTION.
CLASS REQUIREMENTS
CLASS I
A. EXECUTE WORK BY METHODS TO MINIMIZE RAISNG DUST FROMCONSTRUCTION ACTIVITIES.
B. IMMEDIATELY REPLACE ANY CEILING TILE S DISPLACED FOR VISUALINSPECTION.
CLASS II
A. PROVIDE ACTIVE MEANS TO PREVENT AIR-BORNE DUST FROMDISPENSING INTO ATMOSPHERE.
B. WATER MIST WORK SURFACES TO CONTROL DUST WHILECUTTING.
C. SEAL UNUSED DOORS WITH DUCT TAPE.D. BLOCK AND SEAL AIR VENTS.E. WIPE WORK SURFACES WITH WET CLOTH.F. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORTING IN
TIGHTLY COVERED CONTAINERS.G. WET MOP AND/OR VACUUM BEFORE LEAVING WORK AREA.H. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA.I. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS
BEING PERFORMED.
CLASS III
A. NOTIFY/CONSULT GHS EPIDEMIOLOGY BEFORE CONSTRUCTIONBEGINS.
B. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TOPREVENT CONTAMINATION OF DUCT SYSTEM.
C. COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTIONBEGINS (REFER TO CLASS II BARRIERS).
D. MAINTAIN NEGATIVE AIR PRESSURE WITHIN THE WORK SITEUTILIZING 95% EFFICIENT FINAL FILTER EQUIPMENT AIR HANDLINGUNITS.
E. WET MOP/VACUUM AREA DAILYF. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORTING IN
TIGHTLY COVERED CONTAINERS.G. COVER TRANSPORT RECEPTACLES AND CARTSH. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETE
PROJECT IS THOROUGHLY CLEANED BY GHS ENVIRONMENTALSERVICES DEPARTMENT
I. REMOVE BARRIER MATERIAL S CAREFULLY TO MINIMIZESPREADING OF DIRT AND DEBRIS ASSOCIATED WITHCONSTRUCTION.
CLASS IV
A. NOTIFY/CONSULT GHS EPIDEMIOLOGY BEFORE CONSTRUCTIONBEGINS.
B. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TOPREVENT CONTAMINATION OF DUCT SYSTEM.
C. COMPLETE ALL CRITICAL BARRIERS BEFORE CONSTRUCTIONBEGINS (REFER TO CLASS II BARRIERS).
D. MAINTAIN NEGATIVE AIR PRESSURE WITHIN THE WORK SITEUTILIZING 95% EFFICIENT FINAL FILTER EQUIPMENT AIR HANDLINGUNITS.
E. SEAL ALL HOLES, PIPE CONDUITS, AND PUNCTURESAPPROPRIATELY
F. PERSONNEL MUST WEAR CLOTH OR PAPER COVERALLS THAT AREREMOVED EACH TIME THEY LEAVE THE WORK SITE.
G. ALL PERSONNEL ENTERING THE WORK SITE AREA REQUIRED TOWEAR SHOE COVERS. SHOE COVERS MUST BE CHANGES EACHTIME THE WORKER EXITS THE WORK SITE.
H. WET MOP/VACUUM AREA DAILYI. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORTING IN
TIGHTLY COVERED CONTAINERS.J. COVER TRANSPORT RECEPTACLES AND CARTSK. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETE
PROJECT IS THOROUGHLY CLEANED BY GHS ENVIRONMENTALSERVICES DEPARTMENT
L. REMOVE BARRIER MATERIAL S CAREFULLY TO MINIMIZESPREADING OF DIRT AND DEBRIS ASSOCIATED WITHCONSTRUCTION.
AREA: EYE CLINIC CLASS III
4" HEPA FILTER ANDLAMINAR FLOWDIFFUSER
DUSTWALL
TERMINAL FILTER HOUSING
FLEXIBLE DUCT
DUST MACHINE
12" HEPA FILTER
2" PRE-FILTER
TERMINAL UNIT DIAGRAM (N.T.S.)
Newcomb&&&&Boyd
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
D:\
Use
rs\J
Bo
yer\
Do
cum
ents
\172
2000
5-A
RC
H_B
SA
LS
_CE
NT
RA
L_v
2015
_JB
oye
r.rv
t
7/11
/201
6 11
:22:
27 A
M
17220005
JUNE 27, 2016
A100
THIRD FLOOR EXISITNGPLAN, LIFE SAFETY PLAN,AND ICRA NOTES
0000
ISSUED FORCONSTRUCTION
EYE CLINIC RENOVATION
1/16" = 1'-0"1
THIRD FLOOR LIFE SAFETY PLAN
GENERAL FINISH LIMITATIONS:
ALL FINISHED IN THIS PROJECT SHALL CONFORM TOTHE FOLLOWING REQUIREMENTS:A. EXITS AND ACCESS TO EXITS:
CLASS A OR B WALL AND CEILING FINISHESCLASS I OR II FLOOR FINISHES
B. ALL OTHER SPACESCLASS A,B, OR C WALL AND CEILING FINISHES
MEANS OF EGRESS:
PER 2012 NFPA LIFES SAFETY CODE
EGRESS CAPACITY AND COMPONENTS: REQ. PROVIDED
NUMBER OF EXITS (MIN) EXIST. (2) EXIST. (2)EXIT SEPERATION (MIN) EXIST. EXIST.COMMON PATH OF TRAVEL (MAX) N/A N/ATRAVEL DISTANCE (MAX) 300' 202'CORRIDOR WIDTH (MIN.) 44" 66"(MIN)
THIS PROJECT INCLUDES:
A MINOR RENOVATION OF THE 3RD FLOOR AREA K. THERENOVATION WILL CREATE (3) NEW EXAM ROOMS, ANOFFICE, A CLNICAL TRAILS ROOM, (4) NEW PHYSICIAN WORKAREAS, AND BREAK ROOM.
THE PROJECT CURRENTLY HAS A 1 HOUR FIRE SEPERATIONFROM ATRIUM AND A TWO HOUR FIRE SEPARATION FROMTHE ADJACENT BUSINESS USE FACILITY. ALL EXISTINGSEPARATIONS WILL REMAIN INTACT.
PROJECT / LIFE SAFETY NARRATIVE
1/8" = 1'-0"2
THIRD FLOOR EXISTING PLAN
NOTES- LIFE SAFETY PLAN* REFER TO SHEET A011 FOR GENERAL NOTES AND LEGENDS
1 EMERGENCY LIGHTING
MARK DATE DESCRIPTION
XX
GENERAL DEMOLITION NOTES
DEMOLITION SYMBOLS LEGEND
EXISTING COLUMN LINE
DEMOLITION NOTE DESIGNATION
EXISTING WALL TO REMAIN
EXISTING WALL TO BE REMOVED
EXISTING DOOR AND FRAME TO REMAIN
EXISTING DOOR AND FRAME TO BE REMOVED
EXISTING WINDOW AND FRAME TO REMAIN
EXISTING WINDOW AND FRAME TO BE REMOVED
1
A. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY PARTITIONS
AND TEMPORARY DOORS AS DEEMED NECESSARY BY THE
ARCHITECT, ENGINEER AND OWNER. THEY SHALL BE WELL
MAINTAINED AND ANY DAMAGE REPAIRED IMMEDIATELY TO AVOID
MIGRATION OF DUST INTO ADJOINING AREAS.
B. THE CONTRACTOR SHALL COORDINATE ALL DEMOLITION WORK IN
OCCUPIED SPACES AND SHALL NOTIFY THE OWNER TWO WEEKS
PRIOR TO COMMENCING WORK. SUCH SPACES ARE TO REMAIN
OCCUPIED DURING DEMOLITION AND ALL WORK SHALL BE
PERFORMED IN SUCH A MANNER TO MINIMIZE DISRUPTIONS TO
OCCUPANTS. PROTECT EXISTING FLOOR FINISHES FROM
CONSTRUCTION TRAFFIC THROUGH OCCUPIED AREAS. EXISTING
WALL, FLOOR AND CEILINGS FINISHES TO REMAIN SHALL BE
PROTECTED AND ANY DAMAGE RESULTING FROM DEMOLITION WORK
SHALL BE REPAIRED.
C. WHEN DEMOLITION CAUSES DAMAGE TO FLOOR, WALL OR CEILING
SURFACES THAT WILL REMAIN EXPOSED IN THE FINISHED WORK,
SUCH DAMAGE SHALL BE REPAIRED AS REQUIRED TO RECEIVE NEW
FINISHES.
D. THE CONTRACTOR SHALL COVER AND PROTECT OWNER'S
EQUIPMENT WHICH CANNOT BE REMOVED FROM THE PROJECT
AREA.
E. CONTRACTOR SHALL COORDINATE ALL DEMOLITION WITH ANY
PHASING REQUIRED TO COMPLETE THE WORK.
F. DEMOLITION FOR BUILDING SERVICES AND UTILITIES SHALL BE
PERFORMED BY THE TRADE RESPONSIBLE FOR THAT UTILITY. FOR
EXAMPLE, PLUMBING FIXTURES SHALL BE DEMOLISHED BY THE
MECHANICAL CONTRACTOR. OPENINGS FOR DEMOLISHED UTILITIES
SHALL BE INFILLED BY TRADE RESPONSIBLE FOR PIPING, DUCT OR
CONDUIT DEMOLITION. OPENINGS THROUGH FIRE-RATED
CONSTRUCTION SHALL BE PATCHED TO MATCH EXISTING
CONSTRUCTION OR BE FIRESTOPPED.
G. REMOVE EXISTING FLOOR AND BASE MATERIALS IN ALL AREAS
SCHEDULED TO RECEIVE NEW FLOOR AND BASE. REFER TO FINISH
DRAWINGS OR SCHEDULES. REMOVE FLOOR AND BASE ADHESIVES
AND PREPARE SURFACES AS REQUIRED TO RECEIVE NEW FINISHES.
MAKE DEMOLITION CLEAN AND COMPLETE IN A MANNER SUITABLE TO
ACCEPT NEW FINISHES AND/OR SURFACES.
H. REMOVE EXISTING WALL FINISHES ON ALL WALLS SCHEDULED TO
RECEIVE NEW FINISHES. REFER TO FINISH DRAWINGS FOR
LOCATIONS OF NEW FINISHES. REMOVE EXISTING WALL COVERINGS
AND ADHESIVES. PREPARE WALL SURFACES AS DETAILED IN
SPECIFICATIONS.
I. ALL EXISTING CEILING TILES AND GRID SCHEDULED TO BE
DEMOLISHED SHALL BE CAREFULLY REMOVED AND SALVAGED FOR
REUSE WHERE POSSIBLE IN AREAS SCHEDULED TO RECEIVE NEW
CEILINGS OR PATCH EXISTING CEILINGS AT NEW CONSTRUCTION.
1
7' - 8" +/-
VERIFY MULLION LOCATIONS
11' - 0" +/- 7' - 8" +/-
2
3
3
3
3
3
3 3
3
4 4 44
4
444
4
4
4 4 4
3
1 1
11
1
5
6 7
6 7
6 7
7
7
7
7 7 7
7
7
7
6
6
6
6
6
6
6
6
66
6
6
6
6
6
6
6
6
6 66
66
6 6 6 6
6
666
6
66
6
6
9
101010
10
11
11
11
11
11 12
12
12
LIMITS OF CONSTRUCTION
LIMITS OF CONSTRUCTION
LIMITS OF CONSTRUCTION
REMOVE EXISTING COUNTER
TOP, SINK AND BASE
CABINETS - ALT. NO. 1
TYPICAL EXAM ROOM(SINK IN CASEWORK)
TYPICAL FOR EXAM ROOMS 328, 347, 349, 352,
353 AND 354. ALTERNATE HAND SIMILAR
REMOVE EXISTING
WALL MOUNTED SINK
ALT. NO. 2
TYPICAL EXAM ROOM(WALL MOUTED SINK)
TYPICAL FOR EXAM ROOMS 310, 311, 312, 323,
324, 325, 326, 327, 348, 350 AND 351.
3K005
3K006
3K007
3K008
3K011
3K012
3K013
3K014
3K015
3K0183K021
3K022
3K024
3K025
3K026
3K027
3K028
3K031
3K032
3K033
3K034
3K047
3K0483K051
3K052
3K053
3K054
3K055
3K0653K0643K063
3K045
3K044
3K062 3K061 3K058
WAITING
3K002
CHARTS
FILES
3K038
RECEPTION
/ CASH.
3K0373K003
3K004
3K043
3K062 3K061 3K058
3K041
3K055
3K040
3K057
RECPT
3K042
RECPT
3K036
3K066
CORRIDOR
3K056
CORRIDOR
3K046
CORRIDOR
3K016
CORRIDOR
3K023
CORRIDOR
3K002
CORRIDOR
3K017
PHASE 1
PHASE 2
PHASE 1
PHASE 3
17 EXAMROOMSAVAILIBLE
14 EXAMROOMSAVAILIBLE
16 EXAMROOMSAVAILIBLE
16 EXAMROOMSAVAILIBLE
Newcomb&&&&Boyd
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
D:\
Use
rs\J
Bo
yer\
Do
cum
ents
\172
2000
5-A
RC
H_B
SA
LS
_CE
NT
RA
L_v
2015
_JB
oye
r.rv
t
7/11
/201
6 9:
25:3
3 A
M
17220005
JUNE 27, 2016
A101
THIRD FLOORDEMOLITION PLAN,PHASING PLAN ANDALTERNATES
0000
ISSUED FORCONSTRUCTION
EYE CLINIC RENOVATION
NOTES- DEMOLITION PLAN1 REMOVE EXISTING VIEW WINDOW.
2 CUT AND REMOVE EXISTING HOLLOW METAL AND GLASS VIEW WINDOW
AS REQUIRED FOR INSTALLTION OF NEW DOOR WITH SIDE VIEW
WINDOWS.
3 REMOVE EXISTING DOOR AND FRAME.
4 REMOVE EXISTING CASEWORK.
5 REMOVE PORTION OF EXISTING PARTITION AS REQUIRED FOR
INSTALLATION OF NEW CONSTRUCTION.
6 REMOVE FLOOR FINISH AND BASE COMPLETELY. REFER TO INTERIOR
FINISH DRAWINGS.
7 CAREFULLY REMOVE CEILING AND GRID COMPLETELY AND SALVAGE FOR
REINSTALLATION
9 SALVAGE DEMOLISHED TILE FOR USE IN PATCHED AREAS. ONLY REMOVE
WHOLE TILES.
10 REMOVE FLOOR FINISH COMPLETELY
11 REMOVE WOOD GUARDRAIL COMPLETELY AND SALVAGE FOR REUSE.
12 DEMOLISH EXISTING TILE IN THIS AREA TO A JOINT LINE
1/8" = 1'-0"2
THIRD FLOOR DEMOLITION PLAN - BP1
1/4" = 1'-0"3
TYPICAL EXAM DEMOLITION - ALT. NO. 1 1/4" = 1'-0"
4TYPICAL EXAM DEMOLITION - ALT. NO. 2
1/8" = 1'-0"1
PHASING PLAN
MARK DATE DESCRIPTION
C R
CR
CR
C R
CR
CR
BREAKROOM
316
OCT.
318
PHYS.WORK 4
319
MANAGER
355
EXAMROOM
308
DIAG.
314
DIAG.
315
DIAG.
333
DIAG.
334
DIAG.
335
DIAG.
337
CLEAN
336
MINORSURGERY
B-SCAN
342
SOILED
343
ELEC.
317
TLT
338
J/C
339
TLT
340
TLT
331
TLT
330
PO
D 3
PO
D 4
PO
D 2
PO
D 1
EXAMROOM
309
LASER
323
(36 SEATS)
A600
A601
1
EXAMROOM
354
EXAMROOM
353
EXAMROOM
352
EXAMROOM
351
EXAMROOM
350
EXAMROOM
349
EXAMROOM
348
EXAMROOM
347
EXAMROOM
346
EXAMROOM
328
EXAMROOM
327
EXAMROOM
326
EXAMROOM
325
EXAMROOM
324
EXAMROOM
312
EXAMROOM
311
EXAMROOM
310
PHYS.WORK 1
345
A60113
A601 9 A600 12
A601 5
OFFICE
332
ORTHO WAITING AREA
8
A60115
14
A601 10
12
11
PHYS.WORK 3
313
PHYS.WORK 2
329
A600
6
A600
4
A600
11
EXAMROOM
307
A600
1
A6012
A600
5
A601
6
SWINGOFFICE
344
CORRIDOR
300
WAITING
301
TOIL.
303
CORRIDOR
305
TOIL.
304
CORRIDOR
306
CORRIDOR
320
CORRIDOR
341
CORRIDOR
322
CORRIDOR
321
A600 2A6002
301A
301B301C
302
305B
305A
307
308
309
316
318
332
344
355
356
A600 8
A600 8
1 2 2 1
A6007A600 7
3
A6003
4
4
4
4
45
5
6
6
6
5
13
4
5
13
A600 14
10
2 7
13
A601 7
8
A6013
4
5
44
9' -
7"
9' -
7"
3' - 6" 3' - 6"
2' -
4"
2' -
4"
4 4
4 1/
4"
8' - 9 1/8" 10' - 11 3/4" 2' - 2"
3' -
0"
6' -
0"
12' - 0" 3' - 0"
EQ
.3'
- 0
"E
Q.
6' -
4 7
/8"
1313
4
3' -
0"
4' -
0"
4
4
13
5' - 2" 3' - 0"
3' -
9"
6' -
9"
99
7' -
11"
10' -
8"
7' -
11"
3' -
0"
10' - 3" +/-
10
10
10
10
10
10
10
10
10
10
10
10 10
10
10
10
10
10
10
10
10
10
CLINCALTRIALS
356
4 4
6' - 6"6' - 6"
5
11
12
12
12
A601
16
RECEPTION/ CASH
302
8
14
1
A000 2
3
4
XX
ARCHITECTURAL SYMBOLS LEGEND
NEW COLUMN LINE
SECTION INDICATOR
DETAIL INDICATORAREA OFDETAIL
DETAIL NUMBER
SHEET NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
PLAN NOTE DESIGNATION
EQUIPMENT DESIGNATION. REFERTO EQUIPMENT SCHEDULE.
CORNER GUARD (REFER TOFINISH PLANS)
WALL PROTECTION (REFER TOFINISH PLANS)
FLOOR DRAIN
ELEVATION TAG
TOILET ACCESSORY
FIRE EXTINGUISHER CABINET
F.D.
F.E.C.
CG
GENERAL ARCHITECTURAL NOTES
A101
1 SIM SIMILAR
1
A101
SIM
000
ROOM
000
1
1
A. REFER TO THE EQUIPMENT SCHEDULE ON SHEET Axxx FOR EQUIPMENTINFORMATION. COORDINATE BLOCKING AND MEP CONNECTIONS ASREQUIRED.
B. PROVIDE 18" MINIMUM ADA REQUIRED CLEARANCE ADJACENT TO STRIKEOF DOOR.
C. PAINTING CONTRACTOR SHALL LABEL, ABOVE CEILING, ALL FIRE RATEDWALL CONSTRUCTION AND SMOKE BARRIER WALL CONSTRUCTION INACCORDANCE WITH SPECIFICATION.
D. EXISTING WALL CONSTRUCTION CONSIST OF METAL STUDS, GYPSUMBOARD AND CERAMIC TILE.
CARD READERCR
316
318
319
355
308
314 315
333 334 335
337
336
342
343
317
338
339
340
331
330
309
323
354
353
352
351
350
349
348
347
346
328
327
326
325
324
312
311
310
345
332
313
329
307
344
300
301
303
305
304
306
320
341
322
321
1 1
1
1
1
2
2
2
2
2
2
1' -
2"
6" 6"
356
1' - 6" 2' - 6" 2' - 6" 1' - 6"
2' -
2"
OC OC
OC
OC
OC
OC
OC
OC
OC
OC OC
OC
ACT - 1
GENERAL REFLECTED CEILING NOTES
A. ALL LAY-IN ACOUSTICAL CEILINGS SHALL BE INSTALLED AT 8' - 10"ABOVE FINISH FLOOR, UNLESS NOTED OTHERWISE.
B. ALL LAY-IN ACOUSTICAL CEILINGS SHALL BE TYPE ACT1, UNLESSNOTED OTHERWISE.
C. ALL GYPSUM DRYWALL BULKHEADS AND SOFFITS SHALL BEINSTALLED AT 8' 2" ABOVE FINISH FLOOR, UNLESS NOTEDOTHERWISE.
D. REFER TO THIS SHEET FOR TYPICAL GYSUM BOARD SOFFIT ANDBULKHEAD DETAILS.
E. IN AREAS OF NEW CONSTRUCTION WHERE EXISTING CEILING ISBEING EXTEND OR PATCHED AT NEW CONSTRUCTION REUSESALVAGED CEILING TILE AND GRID REMOVED DURING DEMOLITION.
REFLECTED CEILING SYMBOLS
SUSPENDED LAY-IN CEILING SYSTEM
RECESSED "CAN" TYPE LIGHT FIXTURE OR PENDANT
CEILING MOUNTED EXIT LIGHT
CUBICLE CURTAIN TRACK AND CURTAIN
EMERGENCY LIGHT FIXTURE
2'x4' LIGHTING FIXTURE
2'x2' LIGHTING FIXTURE
RETURN AIR GRILLE
SUPPLY AIR GRILLE
SUPPLY AIR GRILLE
CEILING HEIGHT ABOVE FINISH FLOOR
DRYWALL BULKHEAD/CEILING
1'x4' LIGHTING FIXTURE
ACOUSTICAL CEILING TILE - TYPE
4' X4' SUSPENDED LAY-IN CEILING SYSTEM
EXHAUST AIR GRILLE
+9'-0"
NEW COUNTER TOP,BASE & WALLCABINETS - ALT. NO. 1
TYPICAL EXAM ROOM(SINK IN CASEWORK)
A6008
TYPICAL FOR EXAM ROOMS 328, 347, 349, 352,353 AND 354. ALTERNATE HAND SIMILAR
NEW COUNTER TOPSINK & BASE CABINET -ALT. NO. 2
TYPICAL EXAM ROOM(WALL MOUTED SINK)A600
15
TYPICAL FOR EXAM ROOMS 310, 311, 312, 323,324, 325, 326, 327, 348, 350 AND 351.
3-5/8" METAL STUDBRACING AT 16" O.C.EXTEND TOSTRUCTURE ABOVE
ACOUSTICALCEILINGSYSTEM
VA
RIE
S6"
5/8" TYPE 'X' GYP.BD. ON 3 5/8"METAL STUDSV
AR
IES
RE
F.
CLG
. PLA
N
VA
RIE
S R
EF
.C
LG. P
LAN
3 5/8" METAL STUDKICKERS 48" O.C.STAGGERED
CEILING -REF. FINISHSCHD.
5/8" TYPE 'X' GYP.BD. ON 3 5/8"METAL STUDFRAMING
VA
RIE
SR
EF
. RC
P
VA
RIE
SR
EF
. RC
P
3 5/8" METAL STUDKICKERS 48" O.C.STAGGERED
6"
CEILING - REF.FINISH SCHD.
3 5/8" METAL STUDKICKERS 48" O.C.STAGGERED
6"V
AR
IES
RE
F. R
CP
VARIES REF. RCP
CEILING -REF. FINISHSCHD.
5/8" TYPE 'X' GYP.BD. ON 3 5/8"METAL STUDFRAMING PARTITION -
REF. PLANFOR TYPEV
AR
IES
RE
F. R
CP
VA
RIE
SR
EF
. RC
P
REF. RCP
3 5/8" METAL STUDKICKERS 48" O.C.STAGGERED
6"
Newcomb&&&&Boyd
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
D:\
Use
rs\J
Bo
yer\
Do
cum
ents
\172
2000
5-A
RC
H_B
SA
LS
_CE
NT
RA
L_v
2015
_JB
oye
r.rv
t
7/11
/201
6 9:
25:4
8 A
M
17220005
JUNE 27, 2016
A102
THIRD FLOORREFLECTED CEILING ANDARCHITECTURAL PLANS
0000
ISSUED FORCONSTRUCTION
EYE CLINIC RENOVATION
1/8" = 1'-0"2
THIRD FLOOR ARCHITECTURAL PLAN -BP1
NOTES- ARCHITECTURAL PLAN1 COAT HOOKS - CFCI.
2 LOCKERS - OFCI.
3 PATCH EXISTING PARTITION WHERE GLASS AND HOLLOW METAL FRAMEWHERE REMOVED. PATCH WALL TO MATCH EXISTING MATERIALS ANDFINISHES.
4 ALIGN PARTITIONS. REFER TO DETAIL 4/A800
5 FURR OUT NEW WALL TO MATCH WIDTH OF THE EXISTING PARTITION.
6 DOOR FRAME SHALL ACCOMODATE 6" WALL THICKNESS
7 COAT RACK - CFCI.
8 PATCH EXISTING PARTITION WHERE DOOR AND FRAME WHERE REMOVED.MATCH EXISTING MATERIALS AND FINISHES.
9 EXISTING WATER COOLER TO REMAIN.
10 NEW WALL MOUNTED MONITOR - REF. ELECTRICAL DRAWINGS.
11 APPROXIMATE LOCATION FOR RELOCATED TIME CLOCK
12 FINISH EDGE OF EXISTING GUARD RAIL TO MATCH EXISTING.
13 ALIGN PARTITIONS.
14 PATCH FLOORING. SEE FINISH PLAN.
1/8" = 1'-0"1
THIRD FLOOR CEILING PLAN
NOTES- REFLECTED CEILING PLAN1 NEW GYPSUM BOARD SOFFIT AT 8' - 2" A.F.F. REF. THIS SHEET FOR TYPICAL
DETAILS.
2 PATCH EXISTING LAY-IN ACOUSTICAL CEILING AT NEW CONSTRUCTION.EXTEND INTO NEW WORK AREA AS REQUIRED. MATCH EXISTING.
1/4" = 1'-0"6
TYPICAL EXAM ROOM - ALT. NO. 1 1/4" = 1'-0"
7TYPICAL EXAM ROOM - ALT. NO. 2
1 1/2" = 1'-0"5
GYPSUM BOARD BULKHEAD DETAIL -TYPICAL
1 1/2" = 1'-0"4
GYPSUM BOARD SOFFIT DETAIL -TYPICAL
1 1/2" = 1'-0"3
GYPSUM BOARD SOFFIT DETAIL ATWALL - TYPICAL
MARK DATE DESCRIPTION
RB1
P1
VCT1
CORRIDOR321
a
f
RB1
P1
VCT1
BREAK ROOM316
a
e
RB1
P1
VCT1
OCT.318
RB1
P1
VCT1
PHYS. WORK 4319
RB1
P1
VCT1
MANAGER355
d
e
RB1
P1
VCT1
EXAM ROOM308
b
e
RB1
P1
VCT1
DIAG.314
c
e
RB1
P1
VCT1
DIAG.315
c
e
RB1
P1
VCT1
DIAG.333
c
e
RB1
P1
VCT1
DIAG.334
c
e
RB1
P1
VCT1
DIAG.335
c
e
RB1
P1
VCT1
DIAG.337
RB1
P1
VCT1
CLEAN336
RB1
P1
VCT1
MINORSURGERY
B-SCAN342
RB1
P1
VCT1
SOILED343
ETR
ETR
ETR
ELEC.317
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
RB1
P1
VCT1
EXAM ROOM309
b
e
RB1
P1
VCT1
LASER323
b
e
RB1
P1
SV1
WAITING301
a
RB1
P1
VCT1
EXAM ROOM354
d
e
RB1
P1
VCT1
EXAM ROOM353
d
e
RB1
P1
VCT1
EXAM ROOM352
d
e
RB1
P1
VCT1
EXAM ROOM351
d
e
RB1
P1
VCT1
EXAM ROOM350
b
e
RB1
P1
VCT1
EXAM ROOM349
b
e
RB1
P1
VCT1
EXAM ROOM348
b
e
RB1
P1
VCT1
EXAM ROOM347
b
e
RB1
P1
VCT1
EXAM ROOM346
b
eRB1
P1
VCT1
EXAM ROOM328
d
e
RB1
P1
VCT1
EXAM ROOM327
d
e
RB1
P1
VCT1
EXAM ROOM326
d
e
RB1
P1
VCT1
EXAM ROOM325
d
e
RB1
P1
VCT1
EXAM ROOM324
d
e
RB1
P1
VCT1
EXAM ROOM312
b
e
RB1
P1
VCT1
EXAM ROOM311
b
e
RB1
P1
VCT1
EXAM ROOM310
b
e
RB1
P1
VCT1
PHYS. WORK 1345
RB1
P1
VCT1
OFFICE332
RB1
P1
VCT1
PHYS. WORK 3313
RB1
P1
VCT1
PHYS. WORK 2329
RB1
P1
VCT1
EXAM ROOM307
b
e
RB1
P1
VCT1
SWINGOFFICE
344
RB1
P1
VCT1
CORRIDOR341
a
f
RB1
P1
VCT1
CORRIDOR320
a
f
RB1
P1
VCT1
CORRIDOR305
a
f
RB1
P1
VCT1
CORRIDOR306
a
f
ETR
ETR
ETR
TOIL.304
ETR
ETR
ETR
TOIL.303
TLT
331
TLT
330
TLT
340
TLT
338
RB1
P1
VCT1
CORRIDOR322
a
f
J/C
339
6" TYP.
A103
2
1' - 0" 1' - 0" 1' - 0" 1' - 0"
A103
3
6 6
7 7
2
2
2
2
2
2
2
4
4
4
4
4 5
5
5
5
5
2
2
2
2
2
2
3
3
33 3
3
8
8
6" TYP.
4' - 0"
4' -
0"
4' - 0"
4' -
0"
8
6" TYP.
4' -
0"
4' - 0"
9 9
4
10
1111
RB1
P1
VCT1
CLINCALTRIALS
356
b
e
GENERAL FINISH NOTES
FINISH REMARKS
FINISH LEGEND BLOCK
FINISH ABBREVIATIONS
ACT ACOUSTICAL CEILING TILECG CORNER GUARDDG DECORATIVE GLASSDP DECORATIVE PANELEP EPOXY PAINTETR EXISTING TO REMAINGB GYPSUM BOARDLVT LUXURY VINYL TILEP PAINTPL PLASTIC LAMINATEPME PATCH TO MATCH EXISTINGRB RUBBER BASERF RUBBER FLOORINGSC SEALED CONCRETE (SPEC 03300)SS SOLID SURFACESSK SOLID SURFACE SINKSV SHEET VINYLVCT VINYL COMPOSITION TILEVWC VINYL WALL COVERINGWP WALL PROTECTION
ROOM NAME
ROOM NUMBER
REMARKS COLUMN
FLOOR
BASE
WALL
NOTE: FINISHES INDICATED IN FINISH LEGEND BLOCKS ARE GENERAL OVERALLFINISHES FOR ROOM UNLESS OTHERWISE NOTED BY NOTE, REMARK, DETAIL,AND/OR ELEVATION.
A. PATTERN NAME, COLOR AND NUMBER FOR EACH MATERIAL ARE GIVENWHENEVER POSSIBLE ON THE FINISH PLAN. IT SHALL BE THERESPONSIBILITY OF THE CONTRACTOR TO BRING ANY DISCREPANCIESTO THE ATTENTION OF THE ARCHITECT/DESIGNER SO THAT THECORRECT MATERIAL IS INSTALLED.
B. PAINT ALL BULKHEADS, SOFFITS, AND DRYWALL CEILING SURFACES(P6) UNLESS NOTED OTHERWISE ON PLANS. ALL BULKHEADS, SOFFITS,AND DRYWALL CEILING SURFACES SHOULD BE FINISHED WITH THESAME MATERIAL AND OR COLOR ON ALL FACES AS SPECIFIED, UNLESSNOTED OTHERWISE.
C. REFER TO REFLECTED CEILING PLAN FOR ADDITIONAL CEILINGFINISHES.
D. ALL FLOORING MATERIAL SHALL BE ALIGNED WITH DOOR STOP.E. ALL DOOR AND WINDOW METAL TRIM SHALL BE PAINTED (DFP1) UNLESS
NOTED OTHERWISE.F. ALL INTERIOR DOORS SHALL BE STAINED TO MATCH EXISTING WOOD
DOORS.G. REFER TO DETAILS ON THIS SHEET FOR FLOOR TRANSITION DETAILS.H. ALL VERTICAL PLASTIC LAMINATE SURFACES TO BE (PL1) UNLESS
NOTED OTHERWISE. ALL HORIZONTAL PLASTIC LAMINATE WORKSURFACES AND BACKSPLASH TO BE (PL2) UNLESS NOTED OTHERWISE.
I. ALL SOLID SURFACE WORK SURFACES AND BACKSPLASH TO BE (SS1)UNLESS NOTED OTHERWISE.
J. THERE SHALL NOT BE PAINT CONDITIONS THAT OCCUR CAUSING FINISHOR COLOR TO TERMINATE ON AN OUTSIDE CORNER UNLESSSPECIFICALLY NOTED OTHERWISE. IF THIS CONDITION OCCURS BRING ITTO THE ATTENTION OF THE DESIGNER IMMEDIATELY.
K. ALL FLOORING TO BE INSTALLED PERPENDICULAR TO ROOM WALLSUNLESS NOTED OTHERWISE.
L. DRYWALL TO RECEIVE LEVEL 5 FINISH IN AREAS TO RECEIVE DARKCOLOR PAINT (P3) AND (P4). REFER TO PROJECT MANUAL DIVISION 9FOR FINISH LEVEL REQUIREMENTS FOR GYPSUM BOARD SURFACESUNLESS NOTED OTHERWISE.
M. DASHED IN FURNITURE TO BE OWNER FURNISHED, OWNER INSTALLED.N. PAINT ALL INTERIOR HOLLOW METAL DOORS (DFP1). REFER TO
SPECIFICATIONS FOR PAINT TYPE AND FINISH.O. PATCH AND MATCH EXISTING FINISHES AS NEEDED FOR NEW
CONSTRUCTION.P. PAINT ALL GRILLES, VENTS, ELECTRICAL PANELS, ACCESS PANELS,
ETC. TO MATCH ADJACENT WALL UNLESS NOTED OTHERWISE.Q. PROVIDE JOHNSONITE LEVEL SYSTEM OR EQUAL AS NEEDED FOR
SMOOTH TRANSITION BETWEEN FLOORING MATERIALS. SLOPE TO BE 1TO 20.
R. PAINT STEEL COLUMNS, BEAMS, STRUCTURE ETC. EXPOSED TO VIEW INFINISHED AREAS (P1) UNLESS NOTED OTHERWISE.
S. FINISH BEHIND FIXED EQUIPMENT SUCH AS CABINETRY, CASEWORK,CHALK AND TACK/MARKERBOARDS, LOCKERS ETC.
T. CONTRACTOR TO FIELD VERIFY THAT ALL EXISTING SOLID SURFACEWINDOW SILLS MATCH EACH OTHER. ANY WINDOW SILLS THAT DO NOTMATCH SHALL BE PROVIDED TO MATCH THE MAJORITY. PLEASECONTACT ARCHITECT FOR CLARIFICATION IF NEEDED.
U. RATED WALLS ARE NOT INDICATED, REFER TO ARCHITECTURALSHEETS FOR ALL WALL RATINGS.
V. CONTRACTOR TO FIELD VERIFY THAT ALL EXTERIOR WINDOW FRAMESMATCH EACH OTHER IN COLOR. ANY EXTERIOR WINDOW FRAMES THATDO NOT MATCH SHALL BE FINISHED AS NEEDED TO MATCH THEMAJORITY. PLEASE CONTACT ARCHITECT FOR CLARIFICATION IFNEEDED.
W. CONTRACTOR TO FIELD VERIFY THAT ALL EXISTING ROLLER SHADES ATEXTERIOR WINDOWS MATCH EACH OTHER. ANY ROLLER SHADE THATDOES NOT MATCH SHALL BE PROVIDED TO MATCH THE MAJORITY.PLEASE CONTACT ARCHITECT FOR CLARIFICATION IF NEEDED.
X. FOR AREAS WHERE EXISTING WOOD HANDRAIL WITH BUMPERS HASBEEN REMOVED, CONTRACTOR SHALL PROVIDE CUSTOM WOOD ENDCAP (AND BRACKETS IF REQUIRED.) WOOD SPECIES, STAIN COLOR ANDBUMPER INSERTS SHALL BE FINISHED TO MATCH EXISTING.
a. MULTIPLE FLOOR FINISHES OCCUR IN THIS AREA. RE: FINISH PLANACCENTS, THIS SHEET FOR ADDITIONAL INFORMATION.
b. INSTALL ACCENT (VCT2). REFER TO DETAIL 2/A102 FOR LAYOUT & TYPICALDIMENSIONS.
c. INSTALL ACCENT (VCT3). REFER TO DETAIL 3/A102 FOR LAYOUT & TYPICALDIMENSIONS.
d. INSTALL ACCENT (VCT4). REFER TO DETAIL 2/A102 FOR LAYOUT & TYPICALDIMENSIONS.
e. MULTIPLE WALL FINISHES OCCUR IN THIS AREA. RE: FINISH PLAN, THISSHEET FOR ADDITIONAL INFORMATION.
f. EXISTING WALL TILE TO REMAIN, NEW PAINT ABOVE.
FINISH FLOOR MATERIAL LEGEND
VCT1
VCT2
VCT3
VCT4
FINISH PER ROOM FINISH TAG
INDICATES MATERIAL DIRECTION
4' - 0" 2' - 7 1/2"
1' -
9"
4' -
0"
EXAMROOM
311
1
DIAG.
335
1' - 5" 4' - 0"
4' -
0"
1' -
7 1
/4"
1
PROVIDE TROWELABLE UNDERLAYMENT AS REQUIREDTO ALLOW FOR FLUSH AND LEVEL TRANSITION.
METAL DIVIDER STRIP
CONCRETE SLAB - LEVEL ASREQUIRED
SVVCT
Newcomb&&&&Boyd
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
D:\
Use
rs\J
Bo
yer\
Do
cum
ents
\172
2000
5-A
RC
H_B
SA
LS
_CE
NT
RA
L_v
2015
_JB
oye
r.rv
t
7/11
/201
6 9:
25:5
9 A
M
17220005
JUNE 27, 2016
A103
THIRD FLOOR INTERIORFINISH PLAN
0000
ISSUED FORCONSTRUCTION
EYE CLINIC RENOVATION
1/8" = 1'-0"1
THIRD FLOOR FINISH PLAN
,
MARK: MANUFACTURER: STYLE: NUMBER: COLOR: SIZE: COMMENTS: CONTACT:
FLOOR FINISH
SV1 ARMSTRONG FLOORING REJUVENATIONS - TIMBERLINE 37357 OAK SOLID HEAT WELD SEAMS SARAH JENKINS, 816.604.8532, [email protected]
SV2 ARMSTRONG FLOORING REJUVENATIONS - STONERUN 34362 TRAVERTINI BURBS HEAT WELD SEAMS SARAH JENKINS, 816.604.8532, [email protected]
VCT1 ARMSTRONG FLOORING STANDARD EXCELON - IMPERIAL TEXTURE 51858 SANDRIFT WHITE 12" x 12" SARAH JENKINS, 816.604.8532, [email protected]
VCT2 ARMSTRONG FLOORING STANDARD EXCELON - IMPERIAL TEXTURE 51372 TEA GARDEN GREEN 12" x 12" SARAH JENKINS, 816.604.8532, [email protected]
VCT3 ARMSTRONG FLOORING STANDARD EXCELON - IMPERIAL TEXTURE 51804 EARTHSTONE GREIGE 12" x 12" SARAH JENKINS, 816.604.8532, [email protected]
VCT4 ARMSTRONG FLOORING STANDARD EXCELON - IMPERIAL TEXTURE 51943 CAYENNE RED 12" x 12" SARAH JENKINS, 816.604.8532, [email protected]
WALL BASE
RB1 JOHNSONITE TRADITIONAL COVE BASE 80 STONE 4" H LAURA KNIGHT, 913.608.6230, [email protected]
WALL FINISH
P1 SHERWIN WILLIAMS SW7011 NATURAL CHOICE
P2 SHERWIN WILLIAMS SW6122 CAMELBACK
P3 SHERWIN WILLIAMS SW2826 COLONIAL REVIVAL GREEN STONE
P4 SHERWIN WILLIAMS SW7508 TAVERN TAUPE
P5 SHERWIN WILLIAMS SW6471 HAZEL
P6 SHERWIN WILLIAMS SW7007 CEILING BRIGHT WHITE
CASEWORK / MILLWORK
PL1 WILSONART 7935-07 SHAKER CHERRY MELISSA MARMON, 913.484.2691, [email protected]
PL2 WILSONART 4793 WINDSWEPT MELISSA MARMON, 913.484.2691, [email protected]
SS1 CORIAN - ANTARCTICA HARLLMARK BUILDING SUPPLIES, 800.642.2246
MISCELLANEOUS
DFP1 SHERWIN WILLIAMS DOOR FRAME PAINT SW7037 BALANCED BEIGE
INT. DOORS - - - STAIN TO MATCH EXISTING
TF1 MAHARAM TEK-WALL 398650–002 SHEER LESLIE HUCKLA, 913.387.9668, [email protected]
WTR WINDOW TREATMENT MATCH EXISTING - MATCH EXISTING
1/4" = 1'-0"2
ENL. FINISH PLAN - TYP. EXAM RM. 1/4" = 1'-0"
3ENL. FINISH PLAN - TYP. DIAG.
NOTES- FINISH PLAN** NOT ALL NOTES APPEAR ON EACH SHEET
1 ACCENT VCT. RE: ROOM FINISH TAG FOR SPECIFIC COLOR.
2 ACCENT PAINT (P2).
3 ACCENT PAINT (P3).
4 ACCENT PAINT (P4).
5 ACCENT PAINT (P5).
6 ACCENT SHEET VINYL (SV2)
7 LINE OF MATERIAL TRANSITION.
8 INSTALL TILE LAYOUT BASED ON THIS ACCENT CENTERED IN CORRIDOR.
9 ALIGN EDGE OF VCT WITH FINISHED FACE OF WALL.
10 PAINT CORRIDOR SIDE OF NEW FRAME TO MATCH EXISTING PAINT COLOR.
11 PAINT INTERIOR SIDE OF NEW FRAME (DFP1).
6" = 1'-0"4
FLOORING TRANSITION - RESILIENT TORESILIENT
MARK DATE DESCRIPTION
UN
LES
S N
OT
ED
OT
HE
RW
ISE
01 04BORROWED LIGHT
A1.1
SEE SCHEDULE
VARIES2"
SEE SCHEDULE
VARIES 2"
VA
RIE
S S
EE
SC
HE
DU
LE2"
2"
SEE SCHEDULE
VARIES2"
2' - 0" 2"
UN
LES
S N
OT
ED
OT
HE
RW
ISE
VA
RIE
S S
EE
SC
HE
DU
LE2"
4"
FLUSHGLASS
B2.4
SEE SCHEDULE
VARIES
1' -
0"
8"
GLASS GLASS
8" 8"
FRAMES DOORS
SEALANT AT PERIMETER
HOLLOW METAL FRAME - REF.SCHED. (PAINT)
DOOR - REF. SCHED.
2"
1/2" 1/2"
U.O
.N.
6" T
YP
.
1 9/16" VARIES 1 15/16"
REFER TO WALL TYPES FORWALL WIDTH
JAMB ANCHOR MIN. (3) PERJAMB SEALANT ALL AROUNDPERIMETER - BOTH SIDES
DOUBLE STRUCTURALSTUDS TO STRUCTUREABOVE
REFER TO WALL TYPE FOR WALL WIDTH
DOUBLE METAL STUDS
SEALANT AT PERIMETER
HOLLOW METAL FRAME - REF.SCHED. (PAINT)
DOOR - REF. SCHED.
1 9/16" VARIES 1 15/16"
1/2" 1/2"
2"5/
8"
JAMB
HEAD / JAMB
SEE PLAN
VARIES
JAMB ANCHOR MIN. (3) PERAT JAMB
CONTROLJOINT TRIM
PACK TIGHTW/ SAFING
30'-0" MAX. 30'-0" MAX.
1/2" MAX.
REFER TO SPECIFICATIONS FOR MORE INFORMATION
16 GA. 6" STEELSTUD BOX HEADER
STL ANCHORSTRAP @ JAMBS
TEMPERED GLASS
HOLLOW METAL FRAME -PAINT
HEAD (JAMB SIM.)
SILL
REF. PLAN FORPARTITION TYPE
RE
F. I
NT
ER
IOR
ELE
VA
TIO
NS
1/2"
2"
1/2"
COORDINATE WITHGLASS THICKNESS
CONT. SEALANTAT PERIMETER
APPLIED HOLLOWMETAL GLAZING STOP
1 5/8" 3/4" VARIES
REF. PLAN FOR PARTITION TYPE
STL ANCHOR STRAP @ JAMBS
HEAD (JAMB SIM.)
SILL
COORDINATE WITH GLASSTHICKNESS
APPLIED HM GLAZING STOP
METAL STUD BOX HEADER @ HEAD -DBL. 18 GA. STUDS AT JAMB
FLOOR CLIP 12 GA. W/ 3/8" DIA.EXPANSION ANCHORS 4'-0" O.C.
1/2" 1/2"
2"
1 5/8" 3/4" VARIES
VA
RIE
S -
RE
F. S
CH
ED
.4"
FINISH BASE - REF. FINISH DWGS.
FOR P-TYPE
REF. PLAN
HOLLOW METAL FRAME
CONT. SEALANT @PERIMETER - TYP.
GLASS
HOLLOW METAL FRAME
DOOR
MULLION AT DOOR
GENERAL WALL TYPE NOTES
A. DIMENSIONS IN PLAN AND ELEVATION ARE TAKEN TO THE FACE OF FINISHDRYWALL, FACE OF EXPOSED MASONRY, CONCRETE, OR CENTER LINE OFCOLUMN, UNLESS NOTED OTHERWISE.
B. ALL INTERIOR WALLS SHALL BE TYPE 'B3' UNLESS NOTED OTHERWISE. ALLFURRING SHALL BE WALL TYPE 'A3' UNLESS NOTED OTHERWISE.
C. PROVIDE FULL HEIGHT STRUCTURAL STUDS TO THE STRUCTURE ABOVE ATALL CORNERS, AT DOOR AND BORROWED LIGHT FRAMES, JAMBS, ANDBEHIND ALL WALL MOUNTED EQUIPMENT AND/ OR CASEWORK.
D. ALL WALLS SHALL BE TREATED AS SOUND RESISTANT WALLS (UNLESSNOTED OTHERWISE). SEAL AROUND ALL PENETRATIONS AND INSTALLSOUND ATTENTION BATTS FULL HEIGHT. FIT INSULATION TIGHT AROUNDDUCT AND PIPE PENETRATIONS. ALL SOUND RESISTANT WALLS WITHSOUND ATTENUATION BATTS SHALL HAVE ACOUSTICAL SEALANT UNDERBOTTOM RUNNER TRACK.
E. ALL STUDS SHALL BE AT 16" O.C. UNLESS NOTED OTHERWISE.
1. INDICATES ENTIRE WALL CONSTRUCTION TO STOP 6" ABOVE FINISHEDCEILING.
2. INDICATES GYPSUM BOARD ON ONE SIDE TO STOP 6" ABOVE FINISHEDCEILING.
3. INDICATES PARTIAL HEIGHT WALL.
a. INDICATES NO SOUND ATTENTION BLANKETSb. INDICATES ADDITIONAL LAYER OF 5/8" GYPSUM BOARD OVER WALL.
WALL TYPE SYMBOL
X1.1x
INDICATES CONSTRUCTION TYPE
NUMERICAL INDICATION OF STUD/MASONRY SIZE
SUFFIX INDICATES MODIFICATIONS TO WALLCONSTRUCTION HEIGHT
SUFFIX INDICATES HORIZONTALMODIFICATIONS
WALL TYPES SUFFIX
Ax WALL PARTITION1 1/2" = 1'-0"
BASE SECTION
PLAN SECTION
HEAD SECTION
Bx WALL PARTITION1 1/2" = 1'-0"
BASE SECTION
PLAN SECTION
HEAD SECTION
01 TYP. METAL STUD PARTITION HEAD DETAIL1 1/2" = 1'-0" NON-BEARING
PARALLEL TO RIBS OF DECK PERPENDICULAR TO RIBS OF DECK
AX-'X'=METAL STUD SIZEA2-2 1/2" METAL STUDSA3-3 5/8" METAL STUDSA6-6" METAL STUDS
BASE: REFER TO FINISHDRAWINGS
FLOOR: REFER TO FINISHDRAWINGS
1/2" SEALANT SPACE
STEEL STUD RUNNER TRACK.STUDS SCREWED AT BOTTOM
FLOOR SLAB
5/8" GYPSUM WALL BOARD
METAL STUDS (REFERTO CHART BELOW)
DEFLECTION TRACK
BOTTOM OF STRUCTURE
FASTEN GYPSUM BOARDTO STUDS NOT TO THETOP TRACK
BX-'X'=METAL STUD SIZEB2-2 1/2" METAL STUDSB3-3 5/8" METAL STUDSB6-6" METAL STUDS
BASE: REFER TO FINISHDRAWINGSFLOOR: REFER TO FINISHDRAWINGS
1/2" SEALANT SPACEFLOOR SLAB
STEEL STUD RUNNERTRACK. STUDS SCREWEDON EA. SIDE AT BOTTOM
BOTTOM OF STRUCTURE
1/2" SEALANT SPACE(FIRESTOP SYSTEM ATRATED PARTITIONS)
DEFLECTION TRACK
FASTEN GYPSUM BOARDTO STUDS NOT TO THETOP TRACK
METAL STUDS (REFER TOCHART BELOW)
1/2" SEALANT SPACE
SOUND ATTENUATION BATTS
SOUND ATTENUATIONBATTS
METAL DECK. REFER TO STRUCTURALDRAWINGS.
METAL EDGE TRIM WHEREEXPOSED TO VIEW.
FASTEN STEEL RUNNER TO METAL DECK. FRICTION FIT METAL STUDS TODEFLECTION TRACK AND FASTEN GYPSUM BOARD TO STUDS. DO NOTFASTEN TO DEFLECTION TRACK. MAINTAIN GAP BETWEEN STEELDEFLECTION TRACK AND METAL STUD/GYPSUM BOARD TO ACCOMMODATESTRUCTURAL DEFLECTION.
COMPRESSED SAFING INSULATION.(FIRESTOPPING AT RATEDPARTITIONS)
STEEL RUNNER WITH MIN. 2" FLANGES
CONTINUOUS ACOUSTIC SEALANTBOTH SIDES. (FIRESTOPPING ATRATED PARTITIONS)
REFER TO PARTITION TYPES FORWALL CONSTRUCTION.
A2- 3 1/8" WALLA3- 4 1/4" WALLA6- 6 5/8" WALL
16 GAUGE HORIZONTALSTEEL STRAPS AT 32"O.C. VERTICALLY.ANCHOR TO EACH STUD.
1 1/
2"1/
2"
CONTINUOUS 20 GA. SHEET METALFILLER FASTENED TO DECK WITHWIDTH TO SPAN 3 RIBS MIN.
COPE GYPSUM BOARD AROUNDMETAL DECK PROFILE.
1/2"
1"
VARIES
VARIES
5/8"
1"
5/8" GYPSUM BOARD ONEACH SIDE OF STUDS
B2- 3 3/4" WALLB3- 4 7/8" WALLB6- 7 1/4" WALL
VARIESVARIESVARIES
VARIES 5/8"5/8"
Newcomb&&&&Boyd
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
D:\
Use
rs\J
Bo
yer\
Do
cum
ents
\172
2000
5-A
RC
H_B
SA
LS
_CE
NT
RA
L_v
2015
_JB
oye
r.rv
t
7/11
/201
6 9:
26:0
9 A
M
17220005
JUNE 27, 2016
A500
DOOR & FRAMESCHEDULE, DETAILS ANDPARTITION TYPES
0000
ISSUED FORCONSTRUCTION
EYE CLINIC RENOVATION
OPENING SCHEDULE & HW SET
OPENING # ROOM NAME
OPENING FRAME
HARDWARESET GLASS TYPE
ELEC.REQUIRED REMARKS
SIZE
MATERIAL ELEVATION MATERIAL ELEVATION DETAIL SETWIDTH HEIGHT301A WAITING 6' - 0" 7' - 10" WD B2.4 HM 01 1/A500 04 1/4" TEMPERED Yes CARD READER - MAG LOCK
301B WAITING 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 03 Yes CARD READER - MAG LOCK
301C WAITING 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 03 Yes CARD READER - MAG LOCK
302 RECEPTION / CASH 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 03 Yes CARD READER - MAG LOCK
305A CORRIDOR 3' - 0" 7' - 0" WD A1.1 HM 04 2/A500 03 1/4" TEMPERED Yes CARD READER - MAG LOCK
305B CORRIDOR 3' - 0" 7' - 0" WD A1.1 HM 04 2/A500 03 1/4" TEMPERED Yes CARD READER - MAG LOCK
307 EXAM ROOM 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 01 No
308 EXAM ROOM 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 01 No
309 EXAM ROOM 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 01 No
316 BREAK ROOM 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 01 No
318 OCT. 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 02 No
332 OFFICE 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 01 No
344 SWING OFFICE 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 01 No
355 MANAGER 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 01 No
356 CLINCAL TRIALS 3' - 0" 7' - 0" WD A1.1 HM 01 1/A500 01 No
3" = 1'-0"1
TYPICAL DOOR SET
3" = 1'-0"4
TYP. GB CONTROL JOINT DETAILS
3" = 1'-0"3
HOLLOW METAL VIEW WNDOW DETAIL 3" = 1'-0"
2BORROW LITE DETAIL
SEE SPECIFICATIONS FOR HARDWARE DESCRIPTIONS
MARK DATE DESCRIPTION
2' -
10"
2' -
4"
2' -
0"
10.3
10.4
10.5
10.6
6.6
9.1
6.4
6.5
6.7
6.912.2
6.10
3' - 0" 2' - 6"
2' - 6" 3' - 0" F
1' -
0"
1' -
6"
1' -
10"
2' -
10"
9.1
7' -
2"
8
A8006
A800
ELEVATION SYMBOL LEGEND
GENERAL ELEVATION NOTES
A. ALL DIMENSIONS ARE TAKEN TO THE FACE OF FINISHED MATERIAL.B. INSTALL WOOD BLOCKING TO STUDS TO SUPPORT ALL WALL-MOUNTED
CABINETRY AND EQUIPMENT AS REQUIRED.C. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO
CONSTRUCTING CABINETRY.D. ALL BASE CABINETS SHALL BE 2'-0" DEEP UNLESS NOTED OTHERWISE.E. ALL CASEWORK SHALL BE FINISHED IN PLASTIC LAMINATE UNLESS
NOTED OTHERWISE.F. PROVIDE FILLER PANELS AT ALL LOCATIONS WHERE CABINETRY ABUTS A
WALL.G. PROVIDE A 4" HIGH INTEGRAL BACK SPLASH ON ALL COUNTERS WITH
RECESSED SINKS. INSTALL SIDE SPLASHES WHERE THESE COUNTERSABUT A WALL.
H. PROVIDE ADJUSTABLE SHELVING WITHIN ALL WALL AND BASE CABINETRYAS SHOWN BY DASHED LINE.
I. PROVIDE 12" CLEAR INTERIOR DIMENSION ON ALL UPPER WALL CABINETSUNLESS NOTED OTHERWISE.
J. COORDINATE ALL WALL OUTLETS TO AVOID CONFLICT WITH CASEWORK.K. ALL WOOD GRAIN PLASTIC LAMINATE APPLIED TO CABINET DOOR AND
DRAWER FRONTS, GRAIN SHALL RUN VERTICALLY.
XX NEW COLUMN LINE
SECTION INDICATOR
DETAIL INDICATORAREA OFDETAIL
DETAIL NUMBER
SHEET NUMBER
ELEVATION NOTE DESIGNATION
A101
1 SIM SIMILAR
1
A101
SIM
1
1
A000 2
3
4 ELEVATION TAG
16.1
3' -
0"
3' - 6" 4' - 6"
KIOSK KIOSK
4' -
8"
3' -
6"
3' -
0"
8' - 0" +/- 3' - 6"4' - 6"
OPEN OPEN
8.5 8.5
OPEN
9.1 9.19.1
1
A800
1
A800
6.1
5
A800
5
A800
5.1 5.1
16
A600
6.12
2' - 0"4' - 0"2' - 0"
17
1
A8001
A800
16.1
8.5 8.5
9.1 9.19.1
6.1
6.2
OPEN OPEN
OPEN
16
A600
6.3
6.13
3' -
0"
4' -
2"
8.4
9.1
8.4
11 1/8"
2' - 2" 2' - 2" EQ.EQ.EQ.
12.112.1 10.2 10.2
8' -
2"
8' -
2"
9.3
8' - 9 1/8" 4 7/8"
7' -
2"
3' -
0"
4' -
2"
9.3
2
A800
3
A800
TYP.
TYP.
8.2 8.1 8.18.2 8.2 8.2
9.1 9.1
8.3 8.3
EXISTING WALL CONSTRUCTIONEXISTING WALL CONSTRUCTIONNEW WALL CONSTRUCTION
8.1
9.1
2' - 8" 2' - 8" 2' - 8" 2' - 8"
4' -
2"
3' -
0"
10' - 8"
8.4
9.1
7' -
2"
2
A800
3
A800
TYP.
EQ EQ EQ
4' -
2"
3' -
0"
7' -
2"
8.4
9.1
2
A800
3
A800
TYP.
2' -
6"
2' -
2"
2' -
6"
F 3' - 3" F
KNEE SPACE
6.3
9.1
6.2
3' - 7"
6.4
6.5
10
A800
8.4
9.1
8.4
4' -
2"
3' -
0"
EQ.EQ.EQ.
11 1/8"
4' - 3" +/-
5' -
2"
3' -
0"
8' - 0"
9.2
7' -
2"
2
A800
3
A800
TYP.
TYP.
3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0"
3' -
0"
4' -
2"
8.4
9.1
7' -
2"
3
A800
2
A800
TYP.
TYP.
1' - 0" 2' - 6"
5' -
0"
EQ. EQ.
1' - 0" 2' - 6" F
2' -
10"
1' -
10"
2' -
6"
6.6
9.1
6.4
6.5
6.7
10.1
6.8
NOTE: CASEWORK UNDERALT. NO. 1 - EXAM ROOMS328, 347, 349, 352, 353 & 354.
7
A800
6
A800
F 1' - 6" 3' - 2" 3' - 2" 3' - 2" 1' - 6" 1"
EXISTINGWINDOW
EXISTINGWINDOW
KNEE SPACE
6.3
9.1
6.2
6.5
6.11
6.5
2' -
6"
2' -
2"
2' -
6"
6.8 6.8
F 3' - 0" 3' - 0" 1"
6.11
10
A800
2' - 6"
2' -
10"
6.6
6.7
NOTE: LOWER SIDE SPLASHAT WINDOW SIDE TOACCOMODATE EXISTINGWINDOW SILL
9
A600
Sim
SIM.
A102
4 Sim
4" 6"
10"
1 1/
2"3'
- 4
1/2
"
3' -
6"
COUNTERTOPSUPPORT BRACKET
PROVIDE REMOVABLEACCESS PANEL
WALL BASE AS SCHEDULED
1/4" X 1/4" ROUTEDREVEAL, PAINT FLAT BLACK
P. LAM. ON 3/4"PARTICLEBOARD (PL1)
SOLID SURFACE TRANSACTIONTOP WITH EASED EDGES (SS1)
INTERIOR DECORATIVEPENDANT, REFER TOELECTRICAL DRAWINGS.
FABRIC WRAPPEDTACKBOARD (TF1)
P. LAM. (PL2) COUNTERTOP
3MM PVC EDGEBAND
1 1/
2"2'
- 4
1/2
"
2' -
6"
1' -
4"
6' -
6"
2' - 1"
EQ EQ
9"1'
- 6
"5
1/2"
1 1/
2"
4"
1' - 2"
1" 7" 1' - 5"
2' -
10"
2' - 1"SOLID SURFACE TOP
& SPLASH WITHUNDER MOUNT
SOLID SURFACE SINK
P. LAM APRON
P. LAM REMOVABLEPANEL
CONT. SEALANT
16 GA. METALSTRAP BACKING
WATER RESISTANTPLYWOOD SUBSTRATE
SUPPORT BRACKETBEYOND
FINISH BASESEE SCHEDULE
MAX1' - 1"
Newcomb&&&&Boyd
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
D:\
Use
rs\J
Bo
yer\
Do
cum
ents
\172
2000
5-A
RC
H_B
SA
LS
_CE
NT
RA
L_v
2015
_JB
oye
r.rv
t
7/11
/201
6 9:
26:2
1 A
M
17220005
JUNE 27, 2016
A600
INTERIOR ELEVATIONS
0000
ISSUED FORCONSTRUCTION
EYE CLINIC RENOVATION
3/8" = 1'-0"12
BREAK ROOM 316 - EAST
NOTES- INTERIOR ELEVATION5.1 IN-WALL STEEL SUPPORT TUBE - REF. DETAIL.
6.1 SOLID SURFACE TRANSACTION TOP.
6.2 METAL COUNTER TOP SUPPORT BRACKET - TYPICAL.
6.3 25" DEEP PLASTIC LAMINATE COUNTERTOP (PL2) WITH SIDE AND BACKSPLASHES, AS INDICATED.
6.4 PLASTIC LAMINATE (PL1) WALL CABINET.
6.5 PLASTIC LAMINATE (PL1) SOFFIT PANEL.
6.6 25" DEEP SOLID SURFACE COUNTERTOP (SS1) WITH INTEGRAL SIDE ANDBACK SPLASHES, AS INDICATED.
6.7 A.D.A. ACCESSIBLE PLASTIC LAMINATE (PL1) SINK CABINET WITHREMOVABLE FRONT PANEL.
6.8 PLASTIC LAMINATE (PL1) DRAWER UNIT.
6.9 PLASTIC LAMINATE (PL1) WALL CABINET WITH MICROWAVE SHELF.INTERIOR PLASTIC LAMINATE SHALL MATCH EXTERIOR FACE.
6.10 PLASTIC LAMINATE (PL1) BASE CABINET.
6.11 PLASTIC LAMINATE (PL1) WALL CABINET WITH OPEN ADJUSTABLESHELVES. INTERIOR PLASTIC LAMINATE SHALL MATCH EXTERIOR FACE.
6.12 1/4" ROUTED REVEAL, PAINT FLAT BLACK.
6.13 FABRIC WRAPPED TACKBOARD (TF1) BELOW TRANSACTION TOP, ABOVEWORKSURFACE.
8.1 NEW GLASS AND HOLLOW METAL FRAME WINDOW UNIT. MATCH HEAD,MULLION, SILL HEIGHTS AND PROFILE OF EXISTING WINDOW UNITS.
8.2 EXISTING GLASS AND HOLLOW METAL FRAME WINDOW UNIT.
8.3 SCHEDULED WOOD AND GLASS DOOR & HOLLOW METAL FRAME. REFERTO OPENING SCHEDULE.
8.4 1/2" BUTT-GLAZED TEMPERED GLASS IN CONTINUOUS ALUMINUMCHANNEL.
8.5 1/2" CLAMPED IN PLACE TEMPERED GLASS. POLISH EXPOSED EDGES OFGLAZING TO BE SMOOTH.
9.1 FINISH BASE - REF. INTERIOR FINISH DRAWINGS.
9.2 GYPSUM BOARD SIGNAGE NICHE - SIGNAGE BY OWNER.
9.3 GYPSUM BOARD BULKHEAD/SOFFIT. REF. CEILING PLANS FOR MOREINFORMATION.
10.1 MINI MONITOR.
10.2 LOCKERS - OFCI.
10.3 PAPER TOWEL DISPENSER - OFOI.
10.4 SOAP DISPENSER - OFOI.
10.5 MICROWAVE - OFOI.
10.6 REFRIGERATOR - OFOI.
12.1 COAT HOOKS - OFCI. PROVIDE BLOCKING IN WALL AS REQUIRED.
12.2 COAT RACK - OFCI. PROVIDE BLOCKING IN WALL AS REQUIRED.
16.1 LIGHT FIXTURE - REF. ELECTRICAL DRAWINGS.
17
3/8" = 1'-0"4
WAITING 301 - NORTH
3/8" = 1'-0"6
RECEPTION / CASHIER 302 - SOUTH
3/8" = 1'-0"11
CORRIDOR 305 - SOUTH
3/8" = 1'-0"1
CORRIDOR 300 - NORTH 3/8" = 1'-0"
2
CORRIDOR 300 - EAST (WEST SIM. OPP.HAND)
3/8" = 1'-0"3
WAITING 301 - WEST 3/8" = 1'-0"
5
WAITING 301 - NORTH AT GLASSPARTITION
3/8" = 1'-0"7
RECEPTION / CASHIER 302
3/8" = 1'-0"10
RECEPTION / CASHIER 302 - NORTH
3/8" = 1'-0"13
BREAK ROOM 316 - SOUTH
3/8" = 1'-0"8
TYPICAL EXAM ROOM (OPP. HAND SIM.)
3/8" = 1'-0"14
CLINICAL TRIALS 356 - EAST 3/8" = 1'-0"
15TYPICAL EXAM SINK - ALT. NO. 2
1" = 1'-0"16
SECTION AT RECEPTION COUNTER
3/4" = 1'-0"9
HANDICAP SINK
MARK DATE DESCRIPTION
8.5
9.1
OPEN 8.5
5
A800
TYP.
5.1 5.1
1
A800
TYP.
3' - 0"
5' -
2"
3' -
0"
1
A800TYP.
8.5
9.1 F 1' - 6" 3' - 0" 3' - 0" 1' - 6"
2' -
6"
2' -
2"
2' -
6"6.2
9.1
6.3
KNEE SPACE
ComputerMonitor
ComputerMonitor
6.8 6.8
6.5
6.116.4 6.4
3' - 0" 3' - 0" 3' - 0" F
10
A800
9
A800
F1' - 6"3' - 6"
6.2
9.1
6.3
KNEE SPACE
ComputerMonitor
6.8
2' -
6"
2' -
2"
2' -
6"
3' - 6"3' - 6"F
6.5
6.11 6.4
9
A800
10
A800 ELEVATION SYMBOL LEGEND
GENERAL ELEVATION NOTES
A. ALL DIMENSIONS ARE TAKEN TO THE FACE OF FINISHED MATERIAL.B. INSTALL WOOD BLOCKING TO STUDS TO SUPPORT ALL WALL-MOUNTED
CABINETRY AND EQUIPMENT AS REQUIRED.C. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS PRIOR TO
CONSTRUCTING CABINETRY.D. ALL BASE CABINETS SHALL BE 2'-0" DEEP UNLESS NOTED OTHERWISE.E. ALL CASEWORK SHALL BE FINISHED IN PLASTIC LAMINATE UNLESS
NOTED OTHERWISE.F. PROVIDE FILLER PANELS AT ALL LOCATIONS WHERE CABINETRY ABUTS A
WALL.G. PROVIDE A 4" HIGH INTEGRAL BACK SPLASH ON ALL COUNTERS WITH
RECESSED SINKS. INSTALL SIDE SPLASHES WHERE THESE COUNTERSABUT A WALL.
H. PROVIDE ADJUSTABLE SHELVING WITHIN ALL WALL AND BASE CABINETRYAS SHOWN BY DASHED LINE.
I. PROVIDE 12" CLEAR INTERIOR DIMENSION ON ALL UPPER WALL CABINETSUNLESS NOTED OTHERWISE.
J. COORDINATE ALL WALL OUTLETS TO AVOID CONFLICT WITH CASEWORK.K. ALL WOOD GRAIN PLASTIC LAMINATE APPLIED TO CABINET DOOR AND
DRAWER FRONTS, GRAIN SHALL RUN VERTICALLY.
XX NEW COLUMN LINE
SECTION INDICATOR
DETAIL INDICATORAREA OFDETAIL
DETAIL NUMBER
SHEET NUMBER
ELEVATION NOTE DESIGNATION
A101
1 SIM SIMILAR
1
A101
SIM
1
1
A000 2
3
4 ELEVATION TAG
5.15
A800
TYP.
5.1
8.5
9.1
OPEN8.5
1
A800
3' - 0"
8.5
9.1
1
A800
8.5
F 1' - 6" 2' - 9" 2' - 9" 1' - 6"
6.2
9.1
6.3
KNEE SPACE
2' -
6"
2' -
2"
2' -
6"
ComputerMonitor
6.8 6.8
6.5
6.116.4 6.4
3' - 0" 3' - 0" 3' - 0" F
9
A80010
A800
6.2
9.1
6.3
KNEE SPACE
3' - 3" 1' - 6" F
2' -
6"
2' -
2"
2' -
6"
ComputerMonitor
6.8
6.5
6.116.4
F 3' - 0" 3' - 0"
10
A800
5.1 5.15
A800
TYP.
8.5
9.1
OPEN8.5
1
A800TYP.
3' - 11" 3' - 6" 1' - 6" 3' - 6"
2' -
6"
2' -
2"
2' -
6"
F 3' - 3" 3' - 3" 3' - 3" F
6.86.2
9.1
6.3
KNEE SPACE
6.5
6.11 6.116.4
ComputerMonitor
10
A8009
A800
3' - 6"1' - 6"F
2' -
6"
2' -
2"
2' -
6"
F3' - 3"3' - 0"
6.5
6.11 6.4
6.86.2
9.1
6.3
KNEE SPACE
ComputerMonitor
9
A800
10
A800SIM. SIM.
5.15
A800
TYP.
3' - 0" 3' - 3" F
2' -
6"
2' -
2"
2' -
6"
3' - 6"1' - 6"F
6.5
6.116.4
6.86.2
9.1
6.3
KNEE SPACE
10
A8009
A800
3' - 0"3' - 3"F
3' - 6" 1' - 6" F
2' -
6"
2' -
2"
2' -
6"
6.5
6.116.4
6.8 6.2
9.1
6.3
KNEE SPACE
ComputerMonitor
9
A800
10
A800 SIM. SIM.
3' - 6" 1' - 6" F
2' -
6"
2' -
2"
2' -
6"
3' - 3" 3' - 3" F
6.5
6.11 6.4
6.8 6.2
9.1
6.3
KNEE SPACE
ComputerMonitor
9
A80010
A800
EXISTING TILE
EXISTING WOODGUARD RAIL
17
4
A800
Sim
Newcomb&&&&Boyd
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
D:\
Use
rs\J
Bo
yer\
Do
cum
ents
\172
2000
5-A
RC
H_B
SA
LS
_CE
NT
RA
L_v
2015
_JB
oye
r.rv
t
7/11
/201
6 9:
26:3
2 A
M
17220005
JUNE 27, 2016
A601
INTERIOR ELEVATIONS
0000
ISSUED FORCONSTRUCTION
EYE CLINIC RENOVATION
3/8" = 1'-0"1
PHYS WORK 1 - 345 - EXTERIOR - NORTH 3/8" = 1'-0"
2PHYS WORK 1 - 345 - EXTERIOR - WEST
3/8" = 1'-0"3
PHYSICIANS WORK 1 - 345 - EAST 3/8" = 1'-0"
4PHYSICIANS WORK 1 - 345 - NORTH
NOTES- INTERIOR ELEVATION5.1 IN-WALL STEEL SUPPORT TUBE - REF. DETAIL.
6.1 SOLID SURFACE TRANSACTION TOP.
6.2 METAL COUNTER TOP SUPPORT BRACKET - TYPICAL.
6.3 25" DEEP PLASTIC LAMINATE COUNTERTOP (PL2) WITH SIDE AND BACKSPLASHES, AS INDICATED.
6.4 PLASTIC LAMINATE (PL1) WALL CABINET.
6.5 PLASTIC LAMINATE (PL1) SOFFIT PANEL.
6.6 25" DEEP SOLID SURFACE COUNTERTOP (SS1) WITH INTEGRAL SIDE ANDBACK SPLASHES, AS INDICATED.
6.7 A.D.A. ACCESSIBLE PLASTIC LAMINATE (PL1) SINK CABINET WITHREMOVABLE FRONT PANEL.
6.8 PLASTIC LAMINATE (PL1) DRAWER UNIT.
6.9 PLASTIC LAMINATE (PL1) WALL CABINET WITH MICROWAVE SHELF.INTERIOR PLASTIC LAMINATE SHALL MATCH EXTERIOR FACE.
6.10 PLASTIC LAMINATE (PL1) BASE CABINET.
6.11 PLASTIC LAMINATE (PL1) WALL CABINET WITH OPEN ADJUSTABLESHELVES. INTERIOR PLASTIC LAMINATE SHALL MATCH EXTERIOR FACE.
6.12 1/4" ROUTED REVEAL, PAINT FLAT BLACK.
6.13 FABRIC WRAPPED TACKBOARD (TF1) BELOW TRANSACTION TOP, ABOVEWORKSURFACE.
8.1 NEW GLASS AND HOLLOW METAL FRAME WINDOW UNIT. MATCH HEAD,MULLION, SILL HEIGHTS AND PROFILE OF EXISTING WINDOW UNITS.
8.2 EXISTING GLASS AND HOLLOW METAL FRAME WINDOW UNIT.
8.3 SCHEDULED WOOD AND GLASS DOOR & HOLLOW METAL FRAME. REFERTO OPENING SCHEDULE.
8.4 1/2" BUTT-GLAZED TEMPERED GLASS IN CONTINUOUS ALUMINUMCHANNEL.
8.5 1/2" CLAMPED IN PLACE TEMPERED GLASS. POLISH EXPOSED EDGES OFGLAZING TO BE SMOOTH.
9.1 FINISH BASE - REF. INTERIOR FINISH DRAWINGS.
9.2 GYPSUM BOARD SIGNAGE NICHE - SIGNAGE BY OWNER.
9.3 GYPSUM BOARD BULKHEAD/SOFFIT. REF. CEILING PLANS FOR MOREINFORMATION.
10.1 MINI MONITOR.
10.2 LOCKERS - OFCI.
10.3 PAPER TOWEL DISPENSER - OFOI.
10.4 SOAP DISPENSER - OFOI.
10.5 MICROWAVE - OFOI.
10.6 REFRIGERATOR - OFOI.
12.1 COAT HOOKS - OFCI. PROVIDE BLOCKING IN WALL AS REQUIRED.
12.2 COAT RACK - OFCI. PROVIDE BLOCKING IN WALL AS REQUIRED.
16.1 LIGHT FIXTURE - REF. ELECTRICAL DRAWINGS.
17
3/8" = 1'-0"5
PHYS. WORK 2 - 329 - EXTERIOR - EAST 3/8" = 1'-0"
6PHYS. WORK 2 - 329 - EXTERIOR - SOUTH
3/8" = 1'-0"7
PHYSICIANS WORK 2 - 329 - EAST 3/8" = 1'-0"
8PHYSICIANS WORK 2 - 329 - SOUTH
3/8" = 1'-0"9
PHYS. WORK 3 - 313 - EXTERIOR 3/8" = 1'-0"
10PHYS. WORK 3 - 313 - EAST
3/8" = 1'-0"11
PHYS. WORK 3 - 313 - NORTH
3/8" = 1'-0"13
PHYS WORK 4 - 319 - EXTERIOR 3/8" = 1'-0"
14PHYS. WORK 4 - 319 - SOUTH
3/8" = 1'-0"12
PHYS WORK 3 - 313 - SOUTH
3/8" = 1'-0"15
PHYSS. WORK 4 - 319 - WEST 3/8" = 1'-0"
16EXISTING WALL TO NEW WALL (TYP.)
MARK DATE DESCRIPTION
1/4"
1/2" BUTT GLAZED TEMPEREDGLASS IN ALUM. FRAME
GLAZING CHANNEL BELOW
FACE OF PARTN. AS SCHEDULED
CLEAR STRUCTURAL SILICONESEALANT. BOTH SIDE OF GLASS.SEAL FULL PERIMETER AIR TIGHT.
CLEAR STRUCTURAL SILICONESEALANT. BOTH SIDE OF GLASS.
HEAVY GLASS FACEPLATE CLAMP
HEAVY GLASS FACEPLATE CLAMP
5/8" GYP. BOARD ON 3 5/8"METAL STUDS @ 16" O.C.
BASE; REFER TO FINISHDRAWINGS
2x4 NOMINAL WOOD BLOCKING
1/2" DECORATIVE GLASS -REFER TO FINISH SCHEDULE
HARDWOOD WALL CAP - PAINTTO MATCH WALL COLOR
EQ.EQ.
SEE REFLECTED CEILINGPLANS 8"
5' -
2"
3' -
0"
FINISH FLOOR
6" BOX METAL STUD BOXHEADER
8"5'
- 2
"3'
- 0
"
TY
PIC
AL
6"1/
2"3/
4"1/
2"
TY
PIC
AL
6"
1/2"
TYPICAL
6"
TYPICAL
6" 1/2"
TYPICAL
6"
2" X 2" X 1/8" CLIPANGLE WELDED TOTUBE STEEL. ANCHORTO SLAB WITH 1/4" RND.EXPANSION BOLTS
3" X 3" X 1/8" TUBESTEEL FULL HEIGHTOF PARTITION
1/2" 4 7/8" 1/2"
ELEVATION SECTION
5
A800
1/2" OPENING AT TOP,BOTTOM AND SIDES. NOCAULK.
5/8" GYP. BD. ON 3 5/8"METAL STUDS 16" O.C.
2" X 2" X 1/8" CLIPANGLE WELDED TOTUBE STEEL. ANCHORTO SLAB WITH 1/4" RND.EXPANSION BOLTS
3" X 3" X 1/8" TUBESTEEL FULL HEIGHTOF PARTITION
WOOD CAPABOVE
1/2"
4 7/
8"1/
2"
8"
SPOT WELD STUDS TOTUBE STEEL BOTH SIDES
WOOD CAPABOVE
5/8" GYP. BOARD ON 3 5/8"METAL STUDS @ 16" O.C.
BASE; REFER TO FINISHDRAWINGS
2x4 NOMINAL WOOD BLOCKING
1/2" TEMPERED GLASS -REFER TO FINISH SCHEDULE
HARDWOOD WALL CAP - PAINTTO MATCH WALL COLOR
EQ.EQ.
SEE REFLECTED CEILINGPLANS
4' -
2"
3' -
0"
FINISH FLOOR
6" BOX METAL STUD BOXHEADER
1/2" 4 7/8" 1/2"
CONTINUOUS ALUMINUMCHANNEL BASE
CLEAR STRUCTURAL SILICONESEALANT BOTH SIDES OF GLASSSEAL FULL PERIMETER AIR-TIGHT
CONTINUOUS ALUMINUMCHANNEL BASE
CLEAR STRUCTURAL SILICONESEALANT BOTH SIDES OF GLASSSEAL FULL PERIMETER AIR-TIGHT
9"1'
- 6
"5
1/2"
1 1/
2"
4"
1' - 2"
1" 7" 1' - 5"
RE
F. E
LEV
.R
EF
. ELE
V.
2' -
10"
2' - 1"
SOLID SURFACE TOP& SPLASH WITHUNDER MOUNTSOLID SURFACE SINK
P. LAM APRON
P. LAM REMOVABLEPANEL
FINISH FLOORSEE SCHEDULE
CONT. SEALANT
16 GA. METALSTRAP BACKING
WATER RESISTANTPLYWOOD SUBSTRATE
SUPPORT BRACKETBEYOND
FINISH BASESEE SCHEDULE
P. LAM. FILLER
CEILING SYSTEM - REF.CEILING PLAN
P. LAM WALL CABINETWITH ONE ADJ. SHELF
WIRE PULL - TYP.
WHITE MELAMINEINTERIOR - TYP.
P. LAM. ADJ.SHELF
PARTITION - REF.PLAN FOR TYPE
6" - 16 GA. METALSTRAP BACKING, TYP.
MIN. 13" CLEARINSIDE DIM.
2"
3/4"
1' - 3"
7' -
2"
TY
PIC
AL
VA
RIE
S
AD. HELF SUPPORTPIN HOLES - TYP..
CL OF DR TO WALL
MAX1' - 1"
6" 16 GA. METALSTRAP BACKING -TYP.
CONT. SEALANT - TYP.
REF. PLAN FORPARTITION TYPE
FINISH BASE - REF.FINISH DWGS.
WHITE MELAMINEINTERIOR - TYP.
P. LAM. DRAWER
WIRE PULL, TYP.
SOLID SURFACECOUNTER TOP WITHINTEGRAL SPLASH -EASE EDGES
2' - 1"
VA
RIE
S2'
- 6
"1'
- 1
0"2'
- 1
0"
1"
2' - 0"
4"
1 1/
2"
EQ
.E
Q.
EQ
.E
Q.
4"
CEILING SYSTEM - REF.CEILING PLAN
WIRE PULL - TYP.
ADJ. SHELF SUPPORTPINE HOLES - TYP.
WHITE MELAMINEINTERIOR - TYP.
P. LAM. ADJ. SHELF
PARTITION - REF.PLAN FOR TYPE
P. LAM WALL CABINETWITH ONE ADJ. SHELF
6" - 16 GA. METALSTRAP BACKING, TYP.
MIN. 13" CLEARINSIDE DIM.
2"
1' - 3"
P. LAM. FILLERPANEL 3/4"
7' -
2"
CEILING SYSTEM - REF.CEILING PLAN
SOLID SURFACECOUNTER TOPWITH INTEGRALBACK AND SIDESPLASH
P. LAM. DRAWERUNIT
FINISH FLOOR - REF.FINISH DRAWINGS
6" - 16 GA. METALSTRAP BACKING, TYP.
CONT. SEALANT
WHITE MELAMINEINTERIOR - TYP.
FINISH BASE -REF. FINISH DRAWINGS
P. LAM. DOOR
P. LAM. ADJUSTABLESHELF
4"
2' -
10"
3"
6" 1 1/
2"
4"
2' - 0"
2' - 1"
1"
WIRE PULL - TYP.
3MM PVC EDGE
WHITE MELAMINEINTERIOR - TYP.
P. LAM.MICROWAVE SHELF
PARTITION - REF.PLAN FOR TYPE
P. LAM WALLCABINET WITHMICROWAVE SHELF
6" - 16 GA. METALSTRAP BACKING, TYP.
MIN. 13" CLEARINSIDE DIM.
1' -
10"
1' -
6"
1' -
0"
VA
RIE
S
1' - 3"
P. LAM. SIDEPANELS AT SHELF
MICROWAVE BYOWNER VERIFY SIZE
1' - 7"
P. LAM. FILLERPANEL 3/4"
7' -
2"
P. LAM. FILLER
ADJ. SHELFSUPPORTPINE HOLES -TYP.
FINISH FLOOR - REF.FINISH DRAWINGS
WHITE MELAMINEINTERIOR - TYP.
P. LAM. ADJ. SHELF
PARTITION - REF.PLAN FOR TYPE
6" - 16 GA. METALSTRAP BACKING, TYP.
CONT. SEALANT
FINISH BASE -REF. FINISH DRAWINGS
OPEN P. LAM WALLCABINET WITHADJ. SHELVES
6" - 16 GA. METALSTRAP BACKING, TYP.
2' -
6"
2' -
2"
2' -
6"
VA
RIE
S
2"
METAL COUNTERTOP SUPPORTBRACKET
CEILING SYSTEM - REF.CEILING PLAN
PLASTIC LAMINATECOUNTER TOP ANDSPLASH W/ 3MMPVC EDGE
7' -
2"
6" - 16 GA. METALSTRAP BACKING, TYP.
1 1/
2"
2' - 1"
PROVIDE GROMMITSIN COUNTER TOP ASNEEDED. VERIFYLOCATIONS WITH OWNER
CONT. SEALANT - TYP.
4"E
Q.
EQ
.6"
1 1/
2"
VA
RIE
S2'
- 6
"2'
- 2
"2'
- 6
"
6" 16 GA. METALSTRAP BACKING -TYP.
REF. PLAN FORPARTITION TYPE
FINISH BASE - REF.FINISH DWGS.
WHITE MELAMINEINTERIOR - TYP.
P. LAM. DRAWER
WIRE PULL, TYP.
3"
2' - 0"
P. LAM. FILLER
WIRE PULL - TYP.
ADJ. SHELFSUPPORTPINE HOLES -TYP.
WHITE MELAMINEINTERIOR - TYP.
P. LAM. ADJ. SHELF
PARTITION - REF.PLAN FOR TYPE
P. LAM WALLCABINETWITH ONEADJ. SHELF
6" - 16 GA. METALSTRAP BACKING, TYP.
MIN. 13" CLEARINSIDE DIM.
2"
3/4"
1' - 3"
CEILING SYSTEM - REF.CEILING PLAN
P. LAM. COUNTERTOP AND BACKSPLASH WITH3MM PVC EDGE
EXISTINGNEW CONSTRUCTION
ALIGN
EXISTING TILE METAL TILE EDGING WITHSILICONE SEALANT
Newcomb&&&&Boyd
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2013Consulting Engineering GroupSuite 525303 Peachtree Center Avenue, NEAtlanta, Georgia 30303-1277T 404 730-8400F 404 730-8401
D:\
Use
rs\J
Bo
yer\
Do
cum
ents
\172
2000
5-A
RC
H_B
SA
LS
_CE
NT
RA
L_v
2015
_JB
oye
r.rv
t
7/11
/201
6 9:
26:4
0 A
M
17220005
JUNE 27, 2016
A800
DETAILS
0000
ISSUED FORCONSTRUCTION
EYE CLINIC RENOVATION
6" = 1'-0"3
DETAIL AT BUTT GLAZED GLASS WITHCONTINUOUS CHANNEL TOP ANDBOTTOM
1 1/2" = 1'-0"1
DETAIL AT HALF WALL WITH CLAMPED INPLACE GLASS
1 1/2" = 1'-0"5
HALF WALL PLAN 1 1/2" = 1'-0"
2
DETAIL AT HALF WALL WITH GLASS INALUMINUM TRACK
1" = 1'-0"6
CASEWORK SECTION AT HANDICAP SINKCABINET
1" = 1'-0"7
CASEWORK SECTION AT 4 DRAWERCABINET
1" = 1'-0"8
CASEWORK SECTION AT BASE CABINET& MICROWAVE SHELF
1" = 1'-0"10
CASEWORK SECTION AT SIT-DOWNCOUNTER TOP & WALL CABINET
1" = 1'-0"9
CASEWORK SECTION AT 3 DRAWERCABINET
6" = 1'-0"4
DETAIL AT EXISTING WALL TO NEWWALL
MARK DATE DESCRIPTION
J
GENERAL NOTES - APPLIES TO ALL E SERIES DRAWINGS:ELECTRICAL LEGEND: ABBREVIATIONS:
CIRCUITING LEGEND
NO ALLOWANCE WILL BE MADEFOR LACK OF KNOWLEDGE OFEXISTING CONDITIONS.
TELECOMMUNICATIONS LEGEND:
CARD READER.
1. ENGRAVE ALL DEVICES ON THE FACEPLATE WITH 1/4" TALL LETTERS WITH PANEL NAME AND CIRCUIT NUMBER.
2. PROVIDE UPDATED TYPED PANELBOARD SCHEDULES FOR ALL PANELS AFFECTED AND INSERT INTO PANELBOARD.
LAMINATE SCHEDULE PRIOR TO INSERTING INTO PANELBOARD.
3. LABEL JUNCTION BOXES ABOVE CEILINGS WITH CIRCUIT NUMBER AND SERVING PANEL.
4. PROVIDE GRADY A PDF COPY OF THE NEW UPDATED TYPED PANELBOARD DIRECTORY FOR ALL PANELS AFFECTED
DURING CONSTRUCTION.
5. FIELD VERIFY ALL EXISTING JUNCTION BOXES IN AREA OF CONSTRUCTION HAVE COVERS. ANY EXISTING JUNCTION
BOXES WITHOUT COVERS SHALL BE PROVIDED WITH A COVER, TRACED TO SERVING PANELBOARD, AND LABELED PER
DETAIL THIS DRAWING. PROVIDE UNIT PRICING FOR THIS SCOPE.
6. COORDINATE EXACT MOUNTING HEIGHTS AND ORIENTATION OF OUTLET BOXES WITH ARCHITECTURAL DETAILS
PRIOR TO INSTALLATION.
7. EXISTING EMPTY CONDUITS DISCOVERED IN AREA OF NEW CONSTRUCTION SHALL BE DEMOLISHED.
8. REPLACE EXISTING CIRCUIT BREAKERS BEING REUSED IN THIS PROJECT.
9. ALL EXIT SIGNS REMOVED DURING DEMOLITION SHALL BE TURNED OVER TO GRADY. ALL EXISTING EXIT SIGNS
CONTAIN A TRACKING NUMBER; PROVIDE NOTATION ON AS-BUILT DRAWINGS OF EXIT SIGN DEMOLISHED AND
TRACKING NUMBER ASSOCIATED WITH EACH EXIT SIGN. COORDINATE WITH GRADY AND OBTAIN NEW TRACKING
NUMBERS FOR NEW EXIT SIGNS INSTALLED. PROVIDE MACHINE PRINTED LABEL WITH NEW TRACKING NUMBER ON
ALL NEW EXIT SIGNS INSTALLED.
10. WALL SWITCHES AND OTHER DEVICES MOUNTED ON INTERIOR DOOR SWING SHALL BE MOUNTED 4" BEYOND THE
EDGE OF THE OPEN DOOR.
11. REFER TO MECHNICAL/PLUMBIMG/FIRE ALARM DRAWINGS FOR EXACT LOCATION OF EQUIPMENT REQUIRING
ELECTRICAL CONNECTIONS.
12. RECEPTACLES WITHIN 6'-0" OF EDGE OF SINKS SHALL BE GFCI TYPE.
13. CONTRACTOR SHALL REMOVE ALL UN-USED LOW VOLTAGE CABLES END TO END, AND RE-SUPPORT ALL ACTIVE
LOW VOLTAGE CABLES.
14. PRIOR TO DISCONNECTING POWER TO ANY SWITCHGEAR, SWITCHBOARDS, PANELBOARDS, OR MOTOR CONTROL
CENTERS, TRACE ALL CIRCUITS ORIGINATING FROM THE EQUIPMENT TO BE DISCONNECTED, AND PROVIDE GRADY
WITH A FLOOR PLAN SHOWING THE LOCATION OF ALL CONNECTED EQUIPMENT LIGHTING AND RECEPTACLES.
RACEWAYS
RACEWAY CONCEALED IN FLOOR OR UNDERGROUND.
RACEWAY CONCEALED IN CEILING CAVITY OR WALL.
RACEWAY EXPOSED TO VIEW UON.
RACEWAY HOMERUN TO PANEL, ONE ARROWHEAD PER CIRCUIT.
BOXES AND WIRING DEVICES
JUNCTION BOX, ABOVE CEILING.
J
S WALL SWITCH, SINGLE-POLE, SINGLE-THROW. MOUNT 48" AFF, UON.
4S
USS
IR
WALL SWITCH, OCCUPANCY SENSOR, DT = DUAL TECHNOLOGY, US = ULTRA SONIC TECHNOLOGY, IR =INFRARED TECHNOLOGY, LOAD RATING SHALL EXCEED TOTAL WATTS OF FIXTURES BEING CONTROLLED.MOUNT 48" AFF, UON.
JUNCTION BOX, WALL-MOUNTED. MOUNT 18" AFF, UNLESS OTHERWISE NOTED.
IRSDTS
USDT
CEILING MOUNTED OCCUPANCY SENSOR UON. LOAD RATING SHALL DOUBLE TOTAL WATTS OFFIXTURES BEING CONTROLLED UON. SUBSCRIPTS INDICATE MINIMUM SENSOR TECHNOLOGY TYPE. DT=DUAL TECHNOLOGY, US=ULTRA SONIC, & IR=INFRARED. MANUFACTURER SHALL PERFORM SYSTEMLAYOUT AND DETERMINE NUMBER OF SENSORS REQUIRED IN EACH SPACE. SYMBOL ON DRAWINGSINDICATES ONLY THAT THE ROOM HAS OCCUPANCY SENSOR CONTROL AND IS NOT TO BE USED FORDEVICE QUANTITY TAKE OFF. IN SPACES WITHOUT CEILING SENSOR SHALL BE PENDANT MOUNTED.
3S WALL SWITCH, 3-WAY, SINGLE-POLE, DOUBLE-THROW. MOUNT 48" AFF, UON.
WALL SWITCH, 4-WAY, DOUBLE-POLE, DOUBLE-THROW. MOUNT 48" AFF, UON.
HOSPITAL GRADE DUPLEX RECEPTACLE WALL-MOUNT 18" AFF/ARF, UON.
HOSPITAL GRADE DUPLEX GROUND FAULT RECEPTACLE WALL-MOUNT 18" AFF, UON.
HOSPITAL GRADE RECEPTACLE FOR FLAT PANEL TELEVISION. COORDINATE EXACT LOCATIONWITH ARCHITECT AND INSTALL RECEPTACLE IN TELECOM/POWER COMBINATION WALL BOX.WALL-MOUNT COMBINATION BOX 60" AFF.
HOSPITAL GRADE DUPLEX RECEPTACLE MOUNT HOTIZONTALLY ABOVE COUNTER.
DOUBLE DUPLEX HOSPITAL GRADE RECEPTACLE, WALL-MOUNT 18" AFF/ARF, UON.
WALL SWITCH, SINGLE-POLE, MOMENETARY CONTACT. MOUNT 48" AFF, UON.
DISCONNECTS
MOUNT 48" AFF, UON.30/3/20/3R DISCONNECT SWITCH, SIZE/POLES/FUSE/ENCLOSURE TYPE IF OTHER THAN NEMA 1.
PANELBOARDS
HOSPITAL GRADE DUPLEX GROUND FAULT RECEPTACLE MOUNT ABOVE COUNTER WITHHORIZONTAL ORIENTATION.
ABOVEABV
ABOVE FINISHED FLOOR/GRADE/RAISED FLOORAFF/AFG/ARF
ARCHITECT/ARCHITECTURALARCH
BELOWBEL
CONDUITC
CIRCUIT BREAKERCB
CIRCUITCKT
ELECTRICALELEC
EXISTING TO REMAINER
EXISTINGEX
EXISTING TO BE DEMOLISHEDED
FA FIRE ALARM
LUMINAIRELMNR
FLOORFL
GROUNDG
GROUND FAULT CIRCUIT INTERRUPTERGFCI
GFP
GRADEGR
HOT WATER CIRCULATINGHWC
HOA HAND-OFF-AUTOMATIC
HIGH PRESSURE SODIUMHPS
JUNCTION BOXJB
THOUSAND CIRCULAR MILLSkcmil
LIGHTINGLTG
MECHANICALMECH
OVERCURRENT PROTECTIONOCP
PHOTOCELLPC
PHASEPH OR ∅
PANELPNL
REMOTE CONTROLRC
RECEPTACLEREC
SPECIFICATIONSPEC
SPDT SINGLE-POLE DOUBLE-THROW
SWITCHSW
TELEPHONETELE
UNLESS OTHERWISE NOTEDUON
WEATHERPROOFWP
TAMPER PROOFTP
UNDERGROUNDUG
GROUND FAULT PROTECTION SYSTEMFOR EQUIPMENT PROTECTION
FLEXIBLE METAL CONDUITFMC
ISOLATED GROUNDIG
INTERMEDIATE METAL CONDUITIMC
A
A
A
LUMINAIRES
2' x 4' LUMINAIRE. LETTER INDICATES LUMINAIRE TYPE. SEE SCHEDULE.
2' X 2' LUMINAIRE. LETTER INDICATES LUMINAIRE TYPE. SEE SCHEDULE.
RECESSED DOWNLIGHT LUMINAIRE. LETTER INDICATES LUMINAIRE TYPE. SEE SCHEDULE.
EXIT LIGHT, CEILING-MOUNTED. DARKENED SECTIONS INDICATE FACES; ARROWS AS
INDICATED. LETTER INDICATES LUMINAIRE TYPE. SEE SCHEDULE.
2' X 4' LUMINAIRE FED FROM LIFE SAFETY BRANCH. LETTER INDICATES LUMINAIRE TYPE.
SEE SCHEDULE.
2' X 2' LUMINAIRE FED FROM LIFE SAFETY BRANCH. LETTER INDICATES LUMINAIRE TYPE.
SEE SCHEDULE.
A
A
1. POWER
INDICATES MOUNTING HEIGHT OTHER THAN STANDARD48"
UP-1A:9
INDICATES PANEL AND/OR CIRCUIT NUMBER
2. LIGHTING
P
14a,b
INDICATES SWITCHING
INDICATES CIRCUIT NUMBER
INDICATES LUMINAIRE TYPE
DUPLEX RECEPTACLE, CEILING-MOUNTED, FLUSH IN CEILING TILE.
SL
X
EXISTING DUPLEX RECEPTACLE WALL-MOUNT TO REMAIN.
EXISTING DUPLEX RECEPTACLE MOUNT HOTIZONTALLY ABOVE COUNTER TO REMAIN.
EXISTING DUPLEX RECEPTACLE WALL-MOUNT TO BE DEMOLISHED.
EXISTING DUPLEX GROUND FAULT RECEPTACLE WALL-MOUNT TO REMAIN.
EXISTING DUPLEX RECEPTACLE MOUNT HOTIZONTALLY ABOVE COUNTER TO BE DEMOLISHED.
EXISTING DUPLEX GROUND FAULT RECEPTACLE WALL-MOUNT TO BE DEMOLISHED.
EXISTING DOUBLE DUPLEX RECEPTACLE TO REMAIN.
EXISTING DUPLEX GROUND FAULT RECEPTACLE MOUNT ABOVE COUNTER TO REMAIN.
EXISTING DUPLEX GROUND FAULT RECEPTACLE MOUNT ABOVE COUNTER TO BE DEMOLISHED.
EXISTING DUPLEX RECEPTACLE, CEILING-MOUNTED, FLUSH IN CEILING TILE.TO BE DEMOLISHED.
SINGLE GANG BOX WITH A SINGLE GANG PLASTER RING MOUNTED 18" AFF, UNLESSOTHERWISE NOTED. EXTEND 3/4" CONDUIT UP TO ACCESSIBLE CEILING SPACE
EXISTING SURFACE MOUNTED PANELBOARD
GROUNDING
SYSTEM GROUND BUS BAR, WALL MOUNTED 18" AFF, UON.
TV
ER
ED
ER
ED
ER
ED
ER
ER
ED
ED
2D
CR
Newcomb&BoydCONSULTANTS AND ENGINEERS
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
37:5
8 P
M
17220005
JUNE 27, 2016
MBE
ROW E000
ELECTRICAL LEGEND
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
MARK DATE DESCRIPTION
ED
ER
ER ERER
ER
ERERER
ER
ED
ED
ED
ER
ERED
ED
ED
ED
ED
ED
ED
ED
ED
ED
ED ED ED
ED
ED
ED
ER
ED EDER ED ED ED
ER
EDER
ED
ER ER
ED
ED
ER
ER
ER
ER
E100
2
C3CEBA
C3CNBB C3CNBA
C3CLBA
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
38:0
5 P
M
17220005
JUNE 27, 2016
MBE
ROW E100
ELECTRICAL POWERTHIRD FLOORDEMOLITION PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
ELECTRICAL POWER THIRD FLOOR DEMOLITION PLAN
GENERAL NOTES:(THIS DRAWING ONLY)
1. DEMOLISH ELECTRICAL RECEPTACLE OUTLETS AS NOTED.
2. EXISTING HOMERUNS SHALL BE UTILIZED TO SERVED NEW ELECTRICAL INSTALLATIONIN AREA.
3. EQUIPMENT, APPARATUS, AND EXPOSED WIRING AND RACEWAYS RENDERED USELESSDUE TO CHANGES SHALL BE REMOVED.
4. WHERE EXISTING CEILINGS ARE REMOVED, LUMINAIRES, EXIST SIGNS, AND OTHERELECTRICAL POWER AND SIGNAL APPARATUS MOUNTED TO THE CEILING OR CEILINGSUPPORTS, INCLUDING ASSOCIATED RACEWAYS AND WRING, SHALL BE REMOVED.
5. MATERIAL AND EQUIPMENT WHICH HAS BEEN REMOVED SHALL NOT BE USED IN THENEW WORK, EXCEPT AS INDICATED HEREIN.
6. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND FEEDERS PASSINGTHROUGH RENOVATED AREAS AND SERVING UNDISTURBED AREAS.
7. CONCEALED WIRING AND RACEWAYS WHICH ARE EXPOSED BY THE REMOVAL OF WALLS,PARTITIONS, AND CEILINGS SHALL BE REMOVED. NEW CONCEALED WIRING ANDRACEWAYS SERVING EXISTING LOADS PRESENTLY SERVED BY REMOVED WIRING ANDRACEWAYS SHALL BE PROVIDED.
8. OTHER APPARATUS, WIRING, CONDUIT AND METAL MOLDING RENDERED USELESS DUETO CHANGES IN THE EXISTING BUILDING SHALL BE REMOVED WHERE EXPOSED TOVIEW, SHALL BECOME THE PROPERTY OF THE CONTRACTOR, AND SHALL BE REMOVEDFROM THE PREMISES.
9. ALL REMOVED EXIT SIGNS DURING DEMOLITION SHALL BE TURNED OVER TO GRADY. ALLEXISTING EXIT SIGNS CONTAIN A TRACKING NUMBER; PROVIDE NOTATION ON AS-BUILTDRAWINGS OF EXIT SIGNS DEMOLISHED AND TRACKING NUMBER ASSOCIATED WITH EACHSIGN.
MARK DATE DESCRIPTION
1/4" = 1'-0"2
ELECTRICAL POWER THIRD FLOOR DEMOLITION PLAN - RM 317
KEY NOTES:(THIS DRAWING ONLY)
REMOVE DISCONNECT FOR LASER.1
1
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D 2
D2D
2D
2D
2D
2D
2D
2D2D 2D
2D
2D2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D2D
2D
2D 2D
2D
2D
2D
2D
2D
J
J
BREAK
ROOM
316
OCT.
318
PHYS.
WORK 4
319
MANAGER
355
EXAM
ROOM
308
DIAG.
314
DIAG.
315
DIAG.
333
DIAG.
334
DIAG.
335
DIAG.
337
CLEAN
336
MINOR
SURGERY
B-SCAN
342
SOILED
343
RECEPTION
/ CASH.
302
ELEC.
317
TLT
338
J/C
339
TLT
340
TLT
331
TLT
330
EXAM
ROOM
309
LASER
323
EXAM
ROOM
354
EXAM
ROOM
353
EXAM
ROOM
352
EXAM
ROOM
351
EXAM
ROOM
350
EXAM
ROOM
349
EXAM
ROOM
348
EXAM
ROOM
347
EXAM
ROOM
346
EXAM
ROOM
328
EXAM
ROOM
327
EXAM
ROOM
326
EXAM
ROOM
325
EXAM
ROOM
324
EXAM
ROOM
312
EXAM
ROOM
311
EXAM
ROOM
310
PHYS.
WORK 1
345
OFFICE
332
PHYS.
WORK 3
313
PHYS.
WORK 2
329
EXAM
ROOM
307
SWING
OFFICE
344
CORRIDOR
300
WAITING
301
TOIL.
303
CORRIDOR
305
TOIL.
304
CORRIDOR
306
CORRIDOR
320
CORRIDOR
341
CORRIDOR
322
CORRIDOR
321
CLINCAL
TRIALS
356
EX EX EX
EX
EX
EX
EX
EX
EX
EX EX
E101
2
EX
EX20
2018
2222 18
EX
C3CNBB-20
C3CNBB-20
C3CNBB-20
C3CNBB-22
C3CNBB-20
C3CNBB-22
C3CNBB-22
C3CNBB-22
6
6
6
16 16
4
16
6
4
4
416
1212
12
12
EX
10
10
101010
10
10
EX17
17
17
1515
22
1414 14 14
EX
C3CNBB-24
EX14
14
EX
14
1818
16
14
C3CNBB-22
C3CNBB-20
C3CNBB-20
C3CNBB-20
CR
CR
CR
CR
CR
38
EX EX
COMMUNICATION NOTE:THIS AREA IS SERVEDFROM L-WING COMMROOM 3L043.
COMMUNICATION NOTE:THIS AREA IS SERVEDFROM J-WING COMMROOM 3J046.
ELEC.
317
C3CEBA
C3CNBB C3CNBA
C3CLBA
C3CLBA-13FA PANEL
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
38:1
3 P
M
17220005
JUNE 27, 2016
E101
ELECTRICAL POWERTHIRD FLOOR PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
ELECTRICAL POWER THIRD FLOOR PLAN
1/4" = 1'-0"2
ELECTRICAL ROOM 317
GENERAL NOTES:(THIS DRAWING ONLY)
1. ALL CIRCUITS SERVED FROM PANELBOARD C3CNBA, UNLESS OTHERWISE NOTED.
2. EXTEND EXISTING CIRCUITS TO SERVE NEW RECEPTACLES AS NOTED.
3. COORDINATE EXACT MOUNTING HEIGHT AND ORIENTATION OF OUTLET BOXESWITH ARCHITECTURAL DRAWING DETAILS PRIOR TO INSTALLATION.
5. PROVIDE SINGLE SIDED VERTICAL CABLE MANGER FOR RACKS IN COMM ROOMS.
6. PROVIDE (1) 4" EASY PATHSLEEVE AT EACH COMM ROOM FOR NEWCOMMUNICATION WIRING.
KEY NOTE:(THIS DRAWING ONLY)
EXTEND EXISTING ROOM CIRCUIT TO SERVE NEW ELECTRICAL OUTLETFOR MONITOR.
EXTEND EXISTING CORRIDOR CIRCUIT TO SERVE NEW ELECTRICALOUTLET IN CORRIDOR 305.
PROVIDE NEW CARD READER. MATCH EXISTING MANUFACTURER ANDTYPE. COORDINATE WITH APPROVED SUB CONTRACTOR. PROVIDE ALLNECESSARY WORK NEEDED TO COORDINATE THE INSTALL OF WIRING,DOOR CONTROLS, MAGNETIC LOCK, PROXIMITY SENSOR ANDCONNECTION WITH SMOKE DETECTOR AND FIRE ALARM SYSTEMS.DOORS SHALL RELEASE UPON ACTIVATION OF CARD READER, FIREALARM, SMOKE DETECTOR OR PROXIMITY SENSOR.
PROVIDE ELECTRICAL CONNECTION TO RELOCATED KRONOS TIMECLOCK. COORDINATE CONNECTION WITH TIME CLOCK.
REFER TO LOMBART OMEGA CABINET ELECTRICAL LAYOUTINSTRUCTIONS PROVIDED BY ARCHITECT FOR ADDITIONALINFRUSTRUCTURE FOR MEDICAL EQUIPMENT WITHIN THIS ROOM.
1
1
1
1
1
1
1
1
1
1 1
1
1
1
1
1
1
1
1
2
2
3
3
3 3
33
4
4
22
MARK DATE DESCRIPTION
5
5
5
5
SS
S
SS
S
S
S
S3
S 3
DT
DT
DT
DT
S S
DT DT
Sb
Sa
DT
DTDT
DT
DT
DT
BREAK
ROOM
316
OCT.
318
PHYS.
WORK 4
319
MANAGER
355
EXAM
ROOM
308
DIAG.
314
DIAG.
315
DIAG.
333
DIAG.
334
DIAG.
335
DIAG.
337
CLEAN
336
MINOR
SURGERY
B-SCAN
342
SOILED
343
RECEPTION
/ CASH.
302
ELEC.
317
TLT
338
J/C
339
TLT
340
TLT
331
TLT
330
EXAM
ROOM
309
LASER
323
EXAM
ROOM
354
EXAM
ROOM
353
EXAM
ROOM
352
EXAM
ROOM
351
EXAM
ROOM
350
EXAM
ROOM
349
EXAM
ROOM
348
EXAM
ROOM
347
EXAM
ROOM
346
EXAM
ROOM
328
EXAM
ROOM
327
EXAM
ROOM
326
EXAM
ROOM
325
EXAM
ROOM
324
EXAM
ROOM
312
EXAM
ROOM
311
EXAM
ROOM
310
PHYS.
WORK 1
345
OFFICE
332
PHYS.
WORK 3
313
PHYS.
WORK 2
329
EXAM
ROOM
307
SWING
OFFICE
344
CORRIDOR
300
WAITING
301
TOIL.
303
CORRIDOR
305
TOIL.
304
CORRIDOR
306
CORRIDOR
320
CORRIDOR
341
CORRIDOR
322
CORRIDOR
321
CLINCAL
TRIALS
356
A
AA
A A
A
AAA
A A A
A
A A
AA
A
A
A
A
AA
A A
AA
HHH
A A
A A
AA
A
A
A
A
A
A
A
A A
A
XX
X
b b
a a a
a a a
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
38:2
2 P
M
17220005
JUNE 27, 2016
MBE
ROW E200
ELECTRICAL LIGHTINGTHIRD FLOOR PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
ELECTRICAL LIGHTING THIRD FLOOR PLAN
GENERAL NOTES:(THIS DRAWING ONLY)
1. EXTEND EXISTING NORMAL POWER LIGHTING CIRCUIT TOSERVE NEW NORMAL POWER LUMINAIRES.
2. EXTEND EXISTING LIFE SAFETY CIRCUIT TO SERVE NEW EXIT SIGNS AND LIFE SAFETY LIGHTINGINSTALLED IN THIS PROJECT.
LUMINAIRE SCHEDULE
TYPE
A
H
X
MANUFACTURER
METALUX
LITHONIA
ALKCO
CHLORIDE
EMRGI-LITE
LIGHTGUARD
LITHONIA
CATALOG
SERIES
24EN
24EN-LD2-54-UNV--L840-CD-1
ZENTRO
11990 GW
RGLO-LED
STELX
LX/LXN
SLELX
EDG
LAMP QUANTITY
& TYPE
LED
MINIMUM CRI 85
4000K
COMPACT FLUORESCENT
DTT 4 PIN
3500K
LED LAMPS,
SUPPLIED BY
MANUFACTURER.
VOLTAGE/
DESIGN
WATTAGE
UNV
43
UNI
13W
UNV
5W PER
FACE
MOUNTING
METHOD
RECESSED,
CEILING
PENDANT
WALL, OR
CEILING PER
DRAWINGS
DESCRIPTION
2' x 4' RECESSED TROFFER LUMINAIRE WITH
FROSTED WHITE ACRYLIC DIFFUSER, AND
WHITE ALUMINUM FRAME.
PROVIDE FLANGED TRIM WHEN USED IN GYPSUM BOARD OR
PLASTER CEILINGS.
CYLINDRICAL SHADE WITH CRUSHED GLASS TEXTURE ACCENTED WITH INNER
LAYER OF SILVER. PENDENT HUNG WITH SIX FEET OF FIELD CUTTABLE
SUSPENSION CABLE. HANG LUMINAIRES WITH BOTTOM 6' 6" AFF.
WHITE/SILVER IN COLOR WITH SATIN NICKEL FINISH
DECORATIVE EDGE LIT ACRYLIC PANEL EXIT SIGN WITH SINGLE OR DOUBLE
FACED AS INDICATED ON THE DRAWINGS, RED LETTERS AND MIRROR
BACKGROUND, UNIVERSAL ARROWS, AND UNIVERSAL MOUNTING.
LUMINAIRE SHALL COMPLY WITH NFPA 101-2012 SECTION 7.10.
VISIBLE LED LAMPS ARE NOT ACCEPTABLE
INSTALL EXIST SIGN TRACKING NUMBER LABELS PROVIDED BY OWNER ON
EACH EXIT SIGN. COORDINATE WA1:G23ITH OWNER.
MARK DATE DESCRIPTION
Newcomb&BoydCONSULTANTS AND ENGINEERS
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
38:2
9 P
M
17220005
JUNE 27, 2016
MBE
ROW E300
ELECTRICAL SCHEDULES
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
CALCULATED AMPERES: 33 A
CONNECTED AMPERES: 35 A
Receptacle 11880 VA 92.09% 10940 VA
Power 500 VA 100.00% 500 VA CALCULATED LOAD: 11800 VA
Motor 360 VA 100.00% 360 VA CONNECTED LOAD: 12740 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED LOAD
PHASE TOTALS (kVA): 2.8 5.4 4.5
EXISTING LOAD 20 A 1 41 0.0 0.0 42 1 20 A SPARE
EXISTING LOAD 20 A 1 39 0.0 0.0 40 1 20 A SPARE
EXISTING LOAD 20 A 1 37 0.0 0.5 38 1 20 A KRONOS TIME CLOCK COR. 322
EXISTING LOAD 20 A 1 35 0.0 0.0 36 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 33 0.0 0.0 34 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 31 0.0 0.0 32 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 29 0.0 0.0 30 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 27 0.0 0.0 28 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 25 0.0 0.0 26 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 23 0.0 0.0 24 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 21 0.0 0.7 22 1 20 A REC RECEPTION/ CASH 302
EXISTING LOAD 20 A 1 19 0.0 0.5 20 1 20 A REC RECEPTION/ CASH 302
REC PHYS WORK 1 345 20 A 1 17 1.1 1.4 18 1 20 A REC RECEPTION/ CASH 302
REC SWING OFFICE 344 20 A 1 15 0.5 0.9 16 1 20 A REC BREAK ROOM 316
EXISTING LOAD 20 A 1 13 0.0 1.8 14 1 20 A REC WAITING RM 301
EXISTING LOAD 20 A 1 11 0.0 0.7 12 1 20 A REC OCT. 307
EXISTING LOAD 20 A 1 9 0.0 2.2 10 1 20 A REC PHY'S WORK 2, OFFICE 329,332
EXISTING LOAD 20 A 1 7 0.0 0.0 8 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 5 0.0 1.3 6 1 20 A REC PHY'S WORK 313
EXISTING LOAD 20 A 1 3 0.0 1.1 4 1 20 A REC DIAG 318
EXISTING LOAD 20 A 1 1 0.0 0.0 2 1 20 A EXISTING LOAD
LOAD DESCRIPTION
CBTRIP /POLES
CKT#
A B C CKT#
CBTRIP /POLES LOAD DESCRIPTION
NOTES:
WIRE: 4 SCCR: LOCATION: ELEC. 317
PHASES: 3 MAIN: 100A/3P MCB SECTIONS:
VOLTS: 120/208 Wye BUS: 225 A MOUNTING: SURFACE
EXISTING PANELBOARD "C3CNBA" SCHEDULE
CALCULATED AMPERES: 14 A
CONNECTED AMPERES: 14 A
Receptacle 4860 VA 100.00% 4860 VA CALCULATED LOAD: 5220 VA
Motor 360 VA 100.00% 360 VA CONNECTED LOAD: 5220 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED LOAD
PHASE TOTALS (kVA): 2.9 2.2 0.2
EXISTING LOAD 0 A 1 29 0.0 0.0 30 -- -- SPACE
EXISTING LOAD 0 A 1 27 0.0 0.0 28 -- -- SPACE
EXISTING LOAD 0 A 1 25 0.0 0.0 26 -- -- SPACE
EXISTING LOAD 0 A 1 23 0.0 0.2 24 1 20 A REC MICROWAVE BREAK RM 316
EXISTING LOAD 0 A 1 21 0.0 2.2 22 1 20 A REC EXAM RM 308,309
EXISTING LOAD 0 A 1 19 0.0 2.3 20 1 20 A REC EXAM RM 307,308
EXISTING LOAD 0 A 1 17 0.0 0.0 18 -- -- SPACE
EXISTING LOAD 0 A 1 15 0.0 0.0 16 1 20 A EXISTING LOAD
EXISTING LOAD 0 A 1 13 0.0 0.5 14 1 20 A EXISTING LOAD
EXISTING LOAD 0 A 1 11 0.0 0.0 12 -- -- --
EXISTING LOAD 0 A 1 9 0.0 0.0 10 -- -- --
EXISTING LOAD 0 A 1 7 0.0 0.0 8 3 40 A EXISTING LOAD
EXISTING LOAD 0 A 1 5 0.0 0.0 6 -- -- --
EXISTING LOAD 0 A 1 3 0.0 0.0 4 -- -- --
EXISTING LOAD 0 A 1 1 0.0 0.0 2 3 40 A EXISTING LOAD
LOAD DESCRIPTION
CBTRIP /POLES
CKT#
A B C CKT#
CBTRIP /POLES LOAD DESCRIPTION
NOTES:
WIRE: 4 SCCR: 10,000 LOCATION: ELEC. 317
PHASES: 3 MAIN: 100A/3P MCB SECTIONS: 1
VOLTS: 120/208 Wye BUS: 100 A MOUNTING: SURFACE
EXISTING PANELBOARD "C3CNBB" SCHEDULE
CALCULATED AMPERES: 1 A
CONNECTED AMPERES: 1 A
CALCULATED LOAD: 500 VA
Power 500 VA 100.00% 500 VA CONNECTED LOAD: 500 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED LOAD
PHASE TOTALS (kVA): 0.5 0.0 0.0
SPACE -- -- 29 0.0 30
SPACE -- -- 27 0.0 0.0 28 -- -- SPACE
SPACE -- -- 25 0.0 0.0 26 -- -- SPACE
SPACE -- -- 23 0.0 0.0 24 -- -- SPACE
SPACE -- -- 21 0.0 0.0 22 -- -- SPACE
SPACE -- -- 19 0.0 0.0 20 -- -- SPACE
SPACE -- -- 17 0.0 0.0 18 -- -- SPACE
SPACE -- -- 15 0.0 0.0 16 -- -- SPACE
FA PANEL ELEC RM 317 20 A 1 13 0.5 0.0 14 -- -- SPACE
EXISTING LOAD 20 A 1 11 0.0 0.0 12 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 9 0.0 0.0 10 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 7 0.0 0.0 8 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 5 0.0 0.0 6 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 3 0.0 0.0 4 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 1 0.0 0.0 2 1 20 A EXISTING LOAD
LOAD DESCRIPTION
CBTRIP /POLES
CKT#
A B C CKT#
CBTRIP /POLES LOAD DESCRIPTION
NOTES:
WIRE: 4 SCCR: 10,000 LOCATION: ELEC. 317
PHASES: 3 MAIN: 100A/3P MCB SECTIONS: 1
VOLTS: 120/208 Wye BUS: 100 A MOUNTING: SURFACE
EXISTING PANELBOARD "C3CLBA" SCHEDULE
MARK DATE DESCRIPTION
CONDUIT SUPPORT FOR SURFACE-MOUNTED PANELS ABOVE CEILING JUNCTION BOXES LABELS
FACE PLATE LABEL
TYPICAL DATA AND POWER BOX MOUNTING
3-WIRE 24V DC SENSORS
9CNBA-4
GROUNDING CONDUCTOR,
CONDUIT
∅NG
TAPPED HOLE IN BOX
WIRE NUT, TYPICAL
OUTLET BOX
GREEN
GROUNDING SCREW:#10-32 x 0.375" SLOTTEDHEXAGON HEAD, WASHERFACE SCREW, TYPICAL
HANDWRITTEN LABELPANEL-CIRCUIT NUMBER
NO SCALE
BBDPA-1
PANEL
-
CIR
CUIT
NUM
BER(S
)
PA
NE
L-
CIR
CU
IT N
UM
BE
R(S
)
NO SCALE
NO SCALE
J-BOXES FOR POWER - SEEELECTRICAL DRAWINGS FORQUANTITY, TYPE, SIZE, MOUNTINGHEIGHT, ETC.
J-BOXES FOR DATA - SEE TELECOMDRAWINGS FOR QUANTITY, TYPE,SIZE, MOUNTING HEIGHT, ETC.
NO SCALE
L
AO
D
ZONES, ASREQUIRED
LIGHTINGADDITIONAL
L
AO
D
OFFLOCAL
SWITCH
OFFLOCAL
SWITCH
POWERINPUT O
L
DA
OFFLOCAL
RED (LOAD)
CONTROL OUTPUT
SWITCH
24 V DCSENSOR
3-WIRECOMMON
24 V DC
RED (LINE)
POWER PACK
BLU
E
RE
D
BLA
CK
WHITE
BLACKHOT
WHITE (NEUTRAL)
3
4
1
5
2
3"
FINISHED FLOOR
6
CHANNEL STRUT, TYPICAL
FLOORFINISHED
36" MAXIMUM
6'-6"
DETAIL 3PANEL, SEESURFACE MOUNTED
36" MAXIMUM
CONDUIT STRAPS
THIS DRAWING
GROUNDING CONDUCTOR SHALL BE CONTINUOUS SO THAT REMOVAL OFDEVICE WILL NOT INTERFERE WITH CONDUCTOR CONTINUITY.
NOTES:
1.
TYPICAL RECEPTACLE DETAILNO SCALE
LEGIBLE HANDWRITTENLABEL IN BLACKPERMANENT MARKER ONJUNCTION BOX AND COVER.
FACEPLATE LABEL
ENGRAVED 0.25" TALLLETTERS.
DEVICE (I.E.SWITCH,RECEPTACLE,ETC.)
SERVING PANELBOARD-CIRCUIT NUMBER
NOTES:
1. LIGHTING ZONES SHALL HAVE LOCAL MANUAL OVERRIDE TO OFF. SWITCHES ARE
INDICATED ON THE FLOOR PLANS.
2. POWER PACKS SHALL BE LOCATED IN ACCESSIBLE LOCATIONS.
3. WHERE ROOMS CONTAIN 120V AND 277V LUMINAIRES PROVIDE POWER PACK(S) FOR
EACH VOLTAGE AND CONNECT TO COMMON OCCUPANCY SENSOR(S).
Newcomb&BoydCONSULTANTS AND ENGINEERS
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
38:3
5 P
M
17220005
JUNE 27, 2016
MBE
ROW E400
ELECTRICAL DETAILS
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
MARK DATE DESCRIPTION
S
S
I
S
S
L
S
S
L
S
S
S
L L L
SL
L
S SL
CSMMSE
CSMMSE
CI
I
FIRE ALARM WIRING DETAIL
SMOKECOMPARTMENT
SMOKE COMPARTMENT
SIMILAR
FIRE ALARM RISER DIAGRAM
BASEMENT
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
FOURTH FLOOR
FIFTH FLOOR
SIXTH FLOOR
SEVENTH FLOOR
EIGHTH FLOOR
NINTH FLOOR
GROUND FLOOR
TENTH FLOOR
ELEVENTH FLOOR
TWELFTH FLOOR
THIRTEENTH FLOOR
FOURTEENTH FLOOR
FIFTEENTH FLOOR
SIXTEENTH FLOOR
SEVENTEENTH FLOOR
EIGHTEENTH FLOOR
SIXTH FLOOR MEZZANINE
ELECTRICAL ROOM 3K058
FIRE ALARM LEGEND
AREA OF WORK
GENERAL NOTES AND CRITERIA:
THE WORK SHOWN ON THE FIRE ALARM DRAWINGS CONSTITUTES A PRELIMINARY PLAN OF THE NEW FIRE ALARM
SYSTEM. THE PURPOSE IS TO DEFINE THE SCOPE OF WORK, SHOW THE PRIMARY SYSTEM FEATURES AND
PERFORMANCE CRITERIA, AND ESTABLISH A LEVEL OF QUALITY FOR THE WORK. THESE DOCUMENTS ARE INTENDED
FOR REVIEW BY ALL AUTHORITIES HAVING JURISDICTION AND WILL BE THE BASIS OF A CONTRACT WITH A FIRE
ALARM PROVIDER. INSTALLATION SHOP DRAWINGS AND CALCULATIONS, BASED ON THE ACTUAL EQUIPMENT TO BE
INSTALLED SHALL BE PREPARED BY THE FIRE ALARM PROVIDER AND SUBMITTED FOR REVIEW BY ALL AUTHORITIES
PRIOR TO INSTALLATION. SHOP DRAWINGS AND CALCULATIONS SHALL SHOW ADDITIONAL DETAIL AS REQUIRED BY
NFPA 72-2013 AND THE PROJECT SPECIFICATIONS.
CONTRACT DOCUMENTS HAVE BEEN PREPARED BASED ON THE IBC CODE-2012, NFPA 101-2012
LIFE SAFETY CODE, NFPA 72 FIRE ALARM CODE 2013 AND, NFPA 70-2011 ELECTRICAL CODE,
THE HOSPITAL FACILITY FIRE ALARM DESIGN IS BASED ON RELOCATION AND PARTIAL EVACUATION OF BUILDING
OCCUPANTS AS DEFINED BY NFPA 72-2013. EVACUATION ZONES CORRESPOND TO THE BUILDING SMOKE COMPARTMENTS
AS NOTED ON THE DRAWINGS. ALL CIRCUITS NECESSARY FOR THE OPERATION OF AUDIBLE AND VISUAL NOTIFICATION
APPLIANCES SHALL BE PROTECTED UNTIL THEY ENTER THE EVACUATION ZONE WHICH THEY SERVE. PROTECTION SHALL
CONSIST OF CABLES INSTALLED IN METAL RACEWAY IN ACCORDANCE WITH NFPA 72-2013..
THE BUILDING IS FULLY PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN ACCORDANCE WITH NFPA 13. WHERE
CIRCUITS ARE PROTECTED, THE RACEWAY SHALL CONSIST OF EMT AND OUTLET OR PULL BOXES WITH METAL COVERS.
FIRE ALARM DEVICES SUCH AS SLC DEVICES OR NOTIFICATION DEVICES SHALL NOT BE CONNECTED TO THE PROTECTED
PORTION OF THE CIRCUIT. ATTACK BY FIRE WITHIN AN EVACUATION ZONE SHALL NOT IMPAIR CONTROL AND OPERATION
OF NOTIFICATION APPLIANCES OUTSIDE THE EVACUATION ZONE.
THE DATA AND AUDIO NETWORK BETWEEN EXISTING FIRE ALARM PANELS AND WORK STATIONS IS ARRANGED CLASS A
STYLE 7 AS DEFINED BY NFPA 72-2013. SIGNALING LINE CIRCUITS SHALL BE ARRANGED CLASS B STYLE 4 AND
SHALL BE SUB-DIVIDED USING TEE-TAPS AND ISOLATION MODULES. SIGNALING LINE CIRCUITS SHALL NOT BE TEE-TAPPED
OUTSIDE OF A THE CLOSET WHERE THE FACP IS LOCATED. NOTIFICATION APPLIANCE CIRCUITS SHALL BE ARRANGED CLASS B
CONTRACTOR TO FIELD VERIFY THE EXISTING FIRE ALARM AND DEMOLISH EXISTING FIRE ALARM DEVICES
WIRING J.BOXES ETC. EXISTING SIGNATURE SERIES TYPE INITIATING DEVICES SHALL REMAIN.
AND SHALL NOT BE TEE-TAPPED.
TC
NAC
FIRE ALARM PANEL ROOM
EXISTING FIRE ALARM FIELD PANEL EST-3
EXISTING NAC POWER SUPPLY FOR NOTIFICATION ZONE
TYPICAL NEW NAC POWER SUPPLY FOR NOTIFICATION ZONE
SIGNALING LINE CIRCUIT
ISOLATED PORTION OF SLC TO SMOKE ZONE 6-A
ISOLATED PORTION OF SLC TO SMOKE ZONE 6-B
CONTROL MODULE TO ACTIVATE NAC CIRCUITS
EXISTING NETWORK DATA COMMUNICATION AND AUDIO
TERMINAL CABINET
SPEAKER CIRCUIT TO SMOKE ZONE 6-A
SPEAKER CIRCUIT TO SMOKE ZONE 6-B
SMOKE ZONE BOUNDARY
HOMERUN EMT FROM FIRE ALARM CLOSET TO SMOKE ZONE
ISOLATE THE PORTION OF THE SLC CIRCUIT THAT SERVES EACHEVACUATION (SMOKE) ZONE.
NAC POWER SUPPLIES TYPICALLY CONTAIN 4 CLASS B CIRCUITS.EACH CIRCUIT SHALL SERVE NO MORE THAN ONE EVACUATION (SMOKE) ZONE.NAC POWER SUPPLIES SHALL SERVE ONLY ONE NOTIFICATION ZONE.
SLC CIRCUITS SHALL NOT BE TEE-TAPPED OUTSIDE OF THE FIRE ALARMPANEL ROOM.
IN A LARGE EVACUATION (SMOKE) ZONE WHERE A DEDICATED NAC POWERSUPPLY IS JUSTIFIED, THE CONTRACTOR MAY LOCATE THE NAC POWER SUPPLYWITHIN THE EVACUATION ZONE. THE POWER SUPPLY SHALL NOT SERVE OTHER ZONES.
FACP6
EST-3
TC
NEW SLC-CLASS B
NEW SPEAKER CIRCUIT
EXISTING
EXISTING
EXISTING
NEW (NAC) STROBE
FIRE ALARM IMPAIRMENT SHALL BE COORDINATED WITH THE HOSPITAL SAFETY OFFICIAL AND FIRE DEPARTMENT.
REPROGRAM THE FIRE ALARM SYSTEM AND TEST IN ACCORDANCE WITH NFPA72-2013..
SEE ARCHITECTURAL DRAWINGS FOR SMOKE COMPARTMENTS AND BOUNDARIES
PROVIDE (TVSS) FOR EACH FIRE ALARM POWER SUPPLY CONTROL PANEL
NO SCALE
DO NOT CONNECT DEVICES TO HOMERUN PORTION
FACP 6
FACP 4
FACP 5
FACP 7
FACP 8
FACP 9
FACP 1 FACP 3
FACP 10
FACP 11
FACP 12
FACP 2
EST-3 EST-3 EST-3
EST-3EST-3
EST-3
EST-3
EST-3
EST-3 EST-3
EST-3 EST-3
EXISTINGFIREWORKS
NO SCALE
NEW COMBINATION FIRE ALARM SPEAKER/STROBE LIGHT CEILING MOUNTED
NEW ELEVATOR SMOKE DETECTOR(SIGNATURE SERIES TYPE)
cd
FIRE ALARM POWER SUPPLY
DENOTES FIRE ALARM STROBE CANDELA RATING.
NEW DUCT SMOKE DETECTOR (SIGNATURE SERIES TYPE)
REMOTE LED DUCT SMOKE DETECTOR TEST STATION
NEW FIRE ALARM STROBE LIGHT CEILING MOUNTED
NEW FIRE ALARM SPEAKER CEILING MOUNTED
NEW PULL STATION (SIGNATURE SERIES TYPE)
NEW AREA SMOKE DETECTOR(SIGNATURE SERIES TYPE)
E
SMOKE DETECTORS IN CORRIDORS HAVE BEEN LOCATED APPROXIMATELY BASED ON
AN AREA DETECTOR WITH A LISTED SPACING OF 30'x30'. SPACING MAY BE MODIFIED
BASED ON NFPA 72-2013 AND THE FOLLOWING RESTRICTIONS:
(1) A SMOKE DETECTOR SHALL BE LOCATED WITHIN 5 FEET OF THE OPENING OF A
CROSS-CORRIDOR DOOR WHICH IS HELD OPEN.
(2) SMOKE DETECTORS SHALL BE ALIGNED WITH LIGHTS, SPRINKLER, AND DIFFUSERS.
(3) SMOKE DETECTORS SHALL BE LOCATED IN THE CENTER OF 2'x2' CEILING TILES.
(4) ADJUST THE LOCATION OF DETECTORS TO AVOID EXISTING CEILING-MOUNTED
EQUIPMENT.
(5) LOCATE SMOKE DETECTORS AT LEAST 3 FEET FROM THE EDGE OF AIR SUPPLY
DIFFUSERS AND RETURN AIR GRILLS.
(6) LOCATE A SMOKE DETECTOR WITHIN 21 FEET OF THE CENTER OF ELEVATOR DOORS.
SMOKE DETECTORS:
EXISTING FIREMAN PHONE TO REMAIN
FIRE ALARM TAMPER SWITCH
FIRE ALARM FLOW SWITCH
FIRE ALARM DOOR HOLDER
ISOLATION MODULE
FIRE ALARM DOOR HOLDER
EST-3 NEW FIRE ALARM CONTROL PANEL.
DH
PS
PS
J
R
9
10
13
8
7
6
J
J
J
J
J
R
R
14
J
9
10
13
14
1312
11
12
11
876
5
43
2
10
9
8
7
6
5
4
3
2
1
1
5
4
3
2
1
NEW FACP
EST-3
ES
T-3
NEW FACP - ROOM 3K058
Newcomb&BoydCONSULTANTS AND ENGINEERS
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
38:4
1 P
M
17220005
JUNE 27, 2016
FA000
FIRE ALARM LEGEND ANDDETAILS
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
MARK DATE DESCRIPTION
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
SL
SL
SL
SL
LL
L
L
L
SL
SL
SL
SL
SL
SL
LL
L
L
L
L
L
L
L
L
L
L L L
LL
BREAK
ROOM
316
OCT.
318
PHYS.
WORK 4
319
MANAGER
355
EXAM
ROOM
308
DIAG.
314
DIAG.
315
DIAG.
333
DIAG.
334
DIAG.
335
DIAG.
337
CLEAN
336
MINOR
SURGERY
B-SCAN
342
SOILED
343
RECEPTION
/ CASH.
302
ELEC.
317
TLT
338
J/C
339
TLT
340
TLT
331
TLT
330
EXAM
ROOM
309
LASER
323
EXAM
ROOM
354
EXAM
ROOM
353
EXAM
ROOM
352
EXAM
ROOM
351
EXAM
ROOM
350
EXAM
ROOM
349
EXAM
ROOM
348
EXAM
ROOM
347
EXAM
ROOM
346
EXAM
ROOM
328
EXAM
ROOM
327
EXAM
ROOM
326
EXAM
ROOM
325
EXAM
ROOM
324
EXAM
ROOM
312
EXAM
ROOM
311
EXAM
ROOM
310
PHYS.
WORK 1
345
OFFICE
332
PHYS.
WORK 3
313
PHYS.
WORK 2
329
EXAM
ROOM
307
SWING
OFFICE
344
CORRIDOR
300
WAITING
301
TOIL.
303
CORRIDOR
305
TOIL.
304
CORRIDOR
306
CORRIDOR
320
CORRIDOR
341
CORRIDOR
322
CORRIDOR
321
CLINCAL
TRIALS
356
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd0.5w
15cd0.5w
75cd0.5w 15cd
0.5w
15cd15cd
15cd
15cd15cd
75cd0.5w
15cd
15cd
15cd
15cd
15cd
15cd0.5w
15cd0.5w
75cd
15cd0.5w
15cd
15cd0.5w
15cd0.5w
15cd
NOTE:PLEASE COORDINATE FIRE ALARMDEVICE LOCATIONS WITH1- ARCHITECTURAL CEILING PLAN2- LIGHT FIXTURES3- SPRINKLER HEADS.
15cd
15cd
15cd
15cd 15cd 15cd
15cd 15cd 15cd
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
38:4
8 P
M
17220005
JUNE 27, 2016
FA101
FIRE ALARM THIRDFLOOR PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
FIRE ALARM THIRD FLOOR PLAN
MARK DATE DESCRIPTION
FIRE PROTECTION NOTES
1. THE HOSPITAL FIRE COMMAND CENTER AND FIRE DEPARTMENT SHALL BE ADVISED BEFORE
EXISTING SPRINKLER SYSTEM ARE TAKEN OUT OF SERVICE FOR TENANT IMPROVEMENTS.2. NEW SPRINKLER HEAD SHALL MATCH THE EXISTING BUILDING STANDARD.
3. SYSTEM INSTALLATION SHALL COMPLY WITH NFPA13-2013 AND LOCAL CODES.
4. REFER TO ARCHITECTURAL REFRACTED CEILING PLAN FOR EXACT HEAD LOCATIONS.
5. SPRINKLER SYSTEM MODIFICATION SHALL BE PERFORMED BY AN EXPERIENCE COMPANY.THE COMPANY SHALL HOLD A CURRENT COMPETENCY CERTIFICATE ISSUED BY THE STATE
OF GEORGIA
6. MECHANICAL ROOMS, ELECTRICAL ROOMS, STORAGE, LOCKER ROOMS AND LABS ARE
NEW RECESSED PENDENT SPRINKLER HEAD
CLASSIFIED AS ORDINARY HAZARD GROUP 1. SPRINKLER SPACING SHALL NOT BE MAXIMUM
OF 130 SQUARE FEET. DESIGN DENSITY SHALL BE 0.15 GPM PER SQUARE FOOT OVER THEMOST REMOTE 1500 SQUARE FEET. ALL REMAINING SPACES ARE CLASSIFIED AS LIGHT HAZARD
SPRINKLER SPACING SHALL BE A MAXIMUM OF 225 SQUARE FEET. DESIGN DENSITY SHALL BE0.10 GPM PER SQUARE FOOT OVER THE MOST REMOTE 1500 SQUARE FEET.
7. PROVIDE ONE SET OF FIRE PROTECTION SHOP DRAWING AND HYDRAULIC CALCULATIONS
TO THE STATE FIRE MARSHAL OFFICE AND THE GRADY HOSPITAL INSURANCE UNDERWRITER
FOR REVIEW AND APPROVAL.
FIRE PROTECTION LEGEND
NEW SPRINKLER PIPE
EXISTING SPRINKLER OUT-LET
NN SPRINKLER ARM-OVER
N
Newcomb&BoydCONSULTANTS AND ENGINEERS
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
38:5
5 P
M
17220005
JUNE 27, 2016
FP000
FIRE PROTECTIONLEGEND AND DETAILS
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
MARK DATE DESCRIPTION
BREAK
ROOM
316
OCT.
318
PHYS.
WORK 4
319
MANAGER
355
EXAM
ROOM
308
DIAG.
314
DIAG.
315
DIAG.
333
DIAG.
334
DIAG.
335
DIAG.
337
CLEAN
336
MINOR
SURGERY
B-SCAN
342
SOILED
343
RECEPTION
/ CASH.
302
ELEC.
317
TLT
338
J/C
339
TLT
340
TLT
331
TLT
330
EXAM
ROOM
309
LASER
323
EXAM
ROOM
354
EXAM
ROOM
353
EXAM
ROOM
352
EXAM
ROOM
351
EXAM
ROOM
350
EXAM
ROOM
349
EXAM
ROOM
348
EXAM
ROOM
347
EXAM
ROOM
346
EXAM
ROOM
328
EXAM
ROOM
327
EXAM
ROOM
326
EXAM
ROOM
325
EXAM
ROOM
324
EXAM
ROOM
312
EXAM
ROOM
311
EXAM
ROOM
310
PHYS.
WORK 1
345
OFFICE
332
PHYS.
WORK 3
313
PHYS.
WORK 2
329
EXAM
ROOM
307
SWING
OFFICE
344
CORRIDOR
300
WAITING
301
TOIL.
303
CORRIDOR
305
TOIL.
304
CORRIDOR
306
CORRIDOR
320
CORRIDOR
341
CORRIDOR
322
CORRIDOR
321
CLINCAL
TRIALS
356
N N
N
N
NN
N
N
NN
N
NNN
N
N N N
N
N
N
N
N
N
NN
NOTE:ALL SPRINKLER HEADS SHALL BE NEWDO NOT USE EXISTING SPRINKLER HEADS.
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
39:0
2 P
M
17220005
JUNE 27, 2016
FP101
FIRE PROTECTION THIRDFLOOR PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
FIRE PROTECTION THIRD FLOOR PLAN
MARK DATE DESCRIPTION
Newcomb&BoydCONSULTANTS AND ENGINEERS
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
39:0
9 P
M
17220005
JUNE 27, 2016
M000
HVAC LEGEND ANDGENERAL NOTES
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
HVAC LEGEND
PIPING, VALVES AND ACCESSORIES
HWS HOT WATER SUPPLY
HWR HOT WATER RETURN
BLIND FLANGE
HOSE END CONNECTION
PIPE CAP
DIRECTION OF FLOW
ELBOW - 90°
ELBOW - TURNED DOWN
ELBOW - TURNED UP
STRAINER
REDUCER - CONCENTRIC
REDUCER - ECCENTRIC
TEE
TEE OUTLET DOWN
TEE OUTLET UP
UNION OR FLANGE
CHECK VALVE
2-WAY CONTROL VALVE
EXISTING PIPING
EXISTING PIPING TO BE REMOVED
BUTTERFLY VALVE (2.5" AND LARGER)
FLOW CONTROL VALVE (M-MANUAL TYPE; A-AUTOMATIC TYPE)FA
NEEDLE VALVE
DUCTWORK AND AIR DISTRIBUTION
20X20 DUCT (FIRST DIMENSION IS SIDE SHOWN IN INCHES)
SUPPLY AIR DUCT SECTION
RETURN OR OUTSIDE AIR DUCT SECTION
EXHAUST AIR DUCT SECTION
INCLINED RISE (R) OR DROP (D), ARROW IN DIRECTION OF AIR FLOWR
TRANSITION
SPIN-IN FITTING WITH ROUND RIGID DUCT
90° BRANCH TAKEOFF
TRANSITION FROM RECTANGULAR TO ROUND DUCTWORK
MANUAL DAMPER (MD), BACKDRAFT DAMPER (BD), LOW LEAKAGEMANUAL DAMPER (LMD), OR CONTROL DAMPER (CD)
MD
CONTROL DAMPER
TURNING VANES
SIDEWALL SUPPLY GRILLE OR REGISTER WITH SIZE, TYPE, AND CFM
12X12 S-100
__________
SIDEWALL RETURN OR EXHAUST GRILLE OR REGISTER WITH SIZE,TYPE, AND CFM
12X12 R-100
__________
CEILING RETURN OR EXHAUST GRILLE OR REGISTER WITH SIZE,TYPE, AND CFM
18X18 R-600
__________
FLEXIBLE DUCT AND CEILING SUPPLY DIFFUSER WITH ROUNDNECK SIZE, TYPE, AND CFM
12"Ø S-600
__________
EXISTING DUCTWORK OR EQUIPMENT
EXISTING DUCTWORK OR EQUIPMENT TO BE REMOVED
24" x 24" CEILING RETURN GRILLE (R-EG UNLESS NOTED OTHERWISE)
FLEXIBLE DUCT
TERMINAL UNIT WITH REHEAT AND INLET DUCT TRANSITION ANDFLEXIBLE DUCT SHOWN
ROUND OR FLAT OVAL DUCTWORKØ
CONTROLS AND SENSORS
T TEMPERATURE SENSOR
ABBREVIATIONS
APD AIR PRESSURE DROP
ARCH ARCHITECT/ARCHITECTURAL
BCS BUILDING CONTROL SYSTEM
CFM CUBIC FEET PER MINUTE
CTE CONNECT TO EXISTING
EAT ENTERING AIR TEMPERATURE
EWT ENTERING WATER TEMPERATURE
EX EXISTING
FPM FEET PER MINUTE
GPM GALLONS PER MINUTE
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
NC NORMALLY CLOSED
NO NORMALLY OPEN
WG WATER GAUGE
WPD WATER PRESSURE DROP
GENERAL HVAC NOTES:
SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF GRILLES,REGISTERS AND DIFFUSERS.
PROVIDE LABELS FOR ALL PRESSURE SENSORS, TERMINAL UNITS AND DAMPERSLOCATED ABOVE THE CEILING. LOCATE LABELS ON THE CEILING GRID BELOW PRESSURESENSORS, TERMINAL UNITS AND FIRE & FIRE/SMOKE DAMPERS. ALL LABELS SHALLINDICATE THE EQUIPMENT TAG IN TYPED LETTERS.PRESSURE SENSOR LABELS SHALLALSO INDICATE THE TAG OF THE ASSOCIATED AHU. COORDINATE LABEL COLORS WITHTHE ARCHITECT.
ALL EQUIPMENT, DIFFUSERS AND GRILLES SHOWN TO BE DEMOLISHED SHALL BEREMOVED FROM THE SITE OR TURNED OVER TO GRADY FOR RECYCLING.
ALL EXISTING DUCTWORK AND PIPING THAT IS TO BE CONNECTED INTO, DEMOLISHED, ORMODIFIED SHALL BE FIELD VERIFIED AND CONFIRMED BEFORE COMMENCING WORK.EXISTING DUCTWORK AND PIPE SIZES SHOWN WERE TAKEN FROM ORIGINAL DESIGNDOCUMENTS.
SCHEDULE SHUT-DOWNS IN ACCORDANCE WITH GRADY PROCEDURES. ASSUME ALLSYSTEMS ARE 'LIVE' UNLESS OTHERWISE NOTED.
DEMOLITION SCOPE INCLUDES REMOVAL OF ALL EXISTING DUCT AND PIPING BACK TOLAST MAIN OR VALVE. THERE SHALL BE NO ABANDONED PIPE OR DUCT.
PROVIDE MANUAL BALANCING DAMPERS AT EVERY BRANCH TAKE-OFF TO DIFFUSERS ANDGRILLES.
SEE FLOW SCHEMATICS FOR PIPE SIZES NOT INDICATED ON THE DRAWINGS. MINIMUMPIPE SIZE SHALL BE 0.75", UNLESS SPECIFICALLY INDICATED OTHERWISE.
1.
2.
3.
4.
5.
6.
7.
8.
PROVISIONS TO KEEP THE AREA IN THE SCOPE OF WORK UNDERNEGATIVE PRESSURE DURING CONSTRUCTION:
PROVIDE TEMPORARY EXHAUST FAN(S) DUCTED TO OUTDOOR TO KEEP THE CONSTRUCTIONAREA UNDER NEGATIVE PRESSURE DURING COURSE OF RENOVATION.
PROVIDE AIRFLOW MONITORING DEVICES IN CONSTRUCTION BARRIERS TO SIGNAL WHENNEGATIVE PRESSURES ARE NOT MAINTAINED.
ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OFDUCT SYSTEM.
CLEANUP SHALL BE DONE BY VACUUMING WITH A HEPA-FILTERED FAN DEVICE.
SEE ARCHITECTURAL DRAWINGS AND GRADY'S STANDARDS FOR ADDITIONAL INFECTIONCONTROL PREVENTIVE MEASURES REQUIREMENT.
1.
2.
3.
4.
BALL VALVE (2" AND SMALLER)
T EXISTING THERMOSTAT
TWO-WAY CONTROL VALVE
SIGNAL FROM BCS SYSTEMBCS
SIGNAL TO BCS SYSTEMBCS
MARK DATE DESCRIPTION
5.
T
T
T
T
T
T
T
T
T
T
T
HWR
HWS
HWS
HWR
VR47-45
44X
20
VR47-44
VR47-43
VR47-37
VR47-38
40X
20
38X
20
VR47-36
VR47-33
VR47-32
VR47-41
VR47-34
VR47-39
1
1
VR47-45
VR47-44VR47-37
VR47-38
VR47-33
VR47-32
VR47-41
VR47-34
VR47-39
1
1
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
39:1
6 P
M
17220005
JUNE 27, 2016
M100
HVAC THIRD FLOORDEMOLITION PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
HVAC DUCTWORK THIRD FLOOR DEMOLITION PLAN 1/8" = 1'-0"
2HVAC PIPING THIRD FLOOR DEMOLITION PLAN
KEY NOTES: (THIS PART PLAN ONLY)
1 DEMOLISH TERMINAL UNIT AND ASSOCIATED CONTROLS.
KEY NOTES: (THIS PART PLAN ONLY)
1 DEMOLISH TERMINAL UNIT AND ASSOCIATED CONTROLS
MARK DATE DESCRIPTION
T
T
T
T
T
T
T
T T
HWR
HWS
HWS
HWR
BREAK
ROOM
316
OCT.
318
PHYS.
WORK 4
319
MANAGER
355
EXAM
ROOM
308
DIAG.
314
DIAG.
315
DIAG.
333
DIAG.
334
DIAG.
335
DIAG.
337
CLEAN
336
MINOR
SURGERY
B-SCAN
342
SOILED
343
RECEPTION
/ CASH.
302
ELEC.
317
TLT
338
J/C
339
TLT
340
TLT
331
TLT
330
EXAM
ROOM
309
LASER
323
EXAM
ROOM
354
EXAM
ROOM
353
EXAM
ROOM
352
EXAM
ROOM
351
EXAM
ROOM
350
EXAM
ROOM
349
EXAM
ROOM
348
EXAM
ROOM
347
EXAM
ROOM
346
EXAM
ROOM
328
EXAM
ROOM
327
EXAM
ROOM
326
EXAM
ROOM
325
EXAM
ROOM
324
EXAM
ROOM
312
EXAM
ROOM
311
EXAM
ROOM
310
PHYS.
WORK 1
345
OFFICE
332
PHYS.
WORK 3
313
PHYS.
WORK 2
329
EXAM
ROOM
307
SWING
OFFICE
344
CORRIDOR
300
WAITING
301
TOIL.
303
CORRIDOR
305
TOIL.
304
CORRIDOR
306
CORRIDOR
320
CORRIDOR
341
CORRIDOR
322
CORRIDOR
321
CLINCAL
TRIALS
356
44X
2038
X20
VR47-44
42X
18
44X
16VR47-37
40X
2440
X20
VR47-43
VR47-33
VR47-32VR47-36
VR47-41
VR47-34
VR47-39
11
1 3
13
4
2
13
2
1 3
1
12X10 VR47-38 CTE
CTE
CTE
MD
MD
MD
150
10X10 R-EG________
150
10X10 R-EG________
150
10X10 R-EG________8"Ø S-CF
150 (TYP 3)________
6"Ø S-CF
100________
CTE
VR47-45
12X10
CTE
CTE
400
12X12 R-EG________
120
10X10 R-EG________
8"Ø S-CF
200 (TYP 2)________
6"Ø S-CF
120________
MD
MD
BREAK
ROOM
316
OCT.
318
PHYS.
WORK 4
319
MANAGER
355
EXAM
ROOM
308
DIAG.
314
DIAG.
315
DIAG.
333
DIAG.
334
DIAG.
335
DIAG.
337
CLEAN
336
MINOR
SURGERY
B-SCAN
342
SOILED
343
RECEPTION
/ CASH.
302
ELEC.
317
TLT
338
J/C
339
TLT
340
TLT
331
TLT
330
EXAM
ROOM
309
LASER
323
EXAM
ROOM
354
EXAM
ROOM
353
EXAM
ROOM
352
EXAM
ROOM
351
EXAM
ROOM
350
EXAM
ROOM
349
EXAM
ROOM
348
EXAM
ROOM
347
EXAM
ROOM
346
EXAM
ROOM
328
EXAM
ROOM
327
EXAM
ROOM
326
EXAM
ROOM
325
EXAM
ROOM
324
EXAM
ROOM
312
EXAM
ROOM
311
EXAM
ROOM
310
PHYS.
WORK 1
345
OFFICE
332
PHYS.
WORK 3
313
PHYS.
WORK 2
329
EXAM
ROOM
307
SWING
OFFICE
344
CORRIDOR
300
WAITING
301
TOIL.
303
CORRIDOR
305
TOIL.
304
CORRIDOR
306
CORRIDOR
320
CORRIDOR
341
CORRIDOR
322
CORRIDOR
321
CLINCAL
TRIALS
356
VR47-38
VR47-45
TT
CTE
CTE
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
39:2
7 P
M
17220005
JUNE 27, 2016
M101
HVAC THIRD FLOOR PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
HVAC DUCTWORK THIRD FLOOR PLAN 1/8" = 1'-0"
2HVAC PIPING THIRD FLOOR PLAN
KEY NOTES: (THIS PART PLAN ONLY)
1
2
RELOCATED DIFFUSER.
RELOCATED THERMOSTAT.
REBALANCE EXISTING DIFFUSER FOR 250 CFM.
REBALANCE EXISTING DIFFUSER FOR 100 CFM.
3
4
MARK DATE DESCRIPTION
TERMINAL UNIT SCHEDULE
NO.
VR47-38
VR47-45
NOTES:
1. TYPE:
VV
CV
2. CAPACITY BASED ON 55° EAT FOR VV-R AND CV-R UNITS.
3. HOT WATER BASED ON 180°F EWT AND MAXIMUM 3' WPD.
4. SOUND POWER LEVELS IN dB re 10 pW, UNLESS AS SCHEDULED, SHALL BE WITHIN THE ARI 880-1998
TOLERANCES OF THE FOLLOWING LEVELS:
LEVELS BASED ON MAXIMUM PRIMARY CFM AND MINIMUM DIFFERENTIAL STATIC PRESSURE OF 1" WG
FOR VV AND CV UNITS. PROVIDE SOUND ATTENUATORS ON DISCHARGE AND PLENUM RETURN AIR
TO MEET THE SPECIFIED SOUND POWER LEVELS.
5. DIFFERENTIAL STATIC PRESSURE DROP ACROSS COMPLETE ASSEMBLY,
INCLUDING HEATING COIL, FOR ALL UNITS SHALL NOT EXCEED 0.3" WG APD.
6. THE DRAWINGS INDICATE THE DESIGN INTENT TO PROVIDE ACCESS TO HEATING COILS, CONTROL
PANELS, AND ACCESS DOORS. IF TERMINAL UNITS PROVIDED ARE CONFIGURED DIFFERENTLY, THE
ACCESS REQUIREMENTS SHALL BE ADJUSTED IN THE FIELD.
TYPE
(NOTE 1)
VV-R
VV-R
- VARIABLE VOLUME
- CONSTANT VOLUME
CASING RADIATED
DISCHARGE
LESS THAN 1000 CFM
1000 CFM OR MORE
PRIMARY CFM
MAXIMUM
550
520
MINIMUM
300
300
-
OCTAVE BAND
2
51
55
58
HOT WATER HEATING COIL
CAPACITY
MBH(NOTE 2)
11.3
11.3
R REHEAT
3
51
58
59
GPM(NOTE 3)
1.1
1.1
4
46
57
58
PIPE
RUNOUTSIZES, IN.
0.75
0.75
BCS PANEL
INPUT/OUTPUT SUMMARYTERMINAL UNITS
TERMINAL UNIT CONTROLLER
PRIMARY AIR FLOW
PRIMARY AIR VALVE CONTROL
SPACE TEMPERATURE
SUPPLY AIR TEMPERATURE
HOT WATER CONTROL VALVE
SY
ST
EM
GR
AP
HIC
DIS
PLA
Y
X
OUTPUTS
DIGITAL
ST
AR
T/S
TO
P
EN
AB
LE
/DIS
AB
LE
OP
EN
/CLO
SE
ANALOG
SE
TP
OIN
T A
DJU
ST
BC
S C
ON
TR
OL
X
X
INPUTS
DIGITAL
CU
RR
EN
T S
EN
SIN
G R
ELA
Y
DIF
FE
RE
NT
IAL P
RE
SS
UR
E S
WIT
CH
AU
XIL
IAR
Y C
ON
TA
CT
ALA
RM
CO
NT
AC
T
PU
LS
E C
ON
TA
CT
DA
MP
ER
/VA
LV
E S
WIT
CH
PO
SIT
ION
ANALOG
TE
MP
ER
AT
UR
E
X
X
RE
LA
TIV
E H
UM
IDIT
Y
PR
ES
SU
RE
AIR
FLO
W M
EA
SU
RE
ME
NT
X
ALARM
CA
RB
ON
DIO
XID
E L
EV
EL
HIG
H/L
OW
LIM
ITX
RU
N T
IME
TO
TA
LIZ
AT
ION
SE
NS
OR
FA
ILU
RE
X
CO
MM
UN
ICA
TIO
NS
FA
ILU
RE
X
FLO
W F
AIL
UR
E
X
BCS
PR
OP
OR
TIO
NA
L
PR
OP
OR
TIO
NA
L +
IN
TE
GR
AL
X
X
ENERGY MGMT.
TIM
E S
CH
ED
ULE
ST
AR
T/S
TO
P
OP
TIM
UM
ST
AR
T/S
TO
P
DA
Y/N
IGH
T S
ET
BA
CK
EC
ON
OM
IZE
RE
NE
RG
Y M
ET
ER
ING
AR
CH
IVA
L S
ER
VE
R
BA
S T
RE
ND
FA
ILU
RE
MO
DE
(S
EE
NO
TE
S 1
AN
D 2
)
L
L
NO
TE
S
3
HWR
HWS
C
H
TERMINAL
BCS
BCS
BCS
T
UNITFROM AHU
TBCS
TEMPERATURESPACE
ZONETYPICAL
NOTES:
1. FAILURE MODE: O - ON OR OPEN, C - OFF OR CLOSE, L - LAST COMMAND2. TERMINAL UNIT CONTROLS AND INTERFACES SHALL BE ARRANGED SO THAT EQUIPMENT CONTROLLED BY THE BCS OPERATES
3. PROVIDE TERMINAL UNIT BCS CONTROLLER WITH IDENTICAL CONTROL POINTS AND FUNCTIONS FOR EACH TERMINAL UNIT.
AS INDICATED ON FAILURE OF THE TERMINAL UNIT CONTROLLER FOR ANY REASON, INCLUDING LOGIC POWER SUPPLY FAILURE,
X
X
1. ON A DROP IN SPACE TEMPERATURE BELOW COOLING SETPOINT, EACH TERMINAL
UNIT CONTROLLER SHALL MODULATE THE PRIMARY AIR VALVE TO THE MINIMUM
FLOW.
2. IF THE SPACE TEMPERATURE FALLS THROUGH THE SPACE TEMPERATURE
DEADBAND TO THE HEATING SETPOINT, THE TERMINAL UNIT CONTROLLER SHALL
MODULATE THE HOT WATER VALVE TO MAINTAIN HEATING SPACE TEMPERATURE
SETPOINT.
VARIABLE VOLUME SEQUENCE OF OPERATION:
TERMINAL UNIT CONTROLLER
COOLING SETPOINT ADJUST X
OPERATIONAL INTERLOCKS SHALL REMAIN IN EFFECT.
MINIMUMAIRFLOWSETPOINT
DEAD
AIRFLOWSETPOINT
MAXIMUM COOLINGAIRFLOW SETPOINTSUPPLY AIR
TEMPERATURE
HEATING LOOP COOLING LOOPBAND
1 CONTROL SCHEMATIC FOR TERMINAL UNITS WITH REHEATNO SCALE
VAV
INLET COLLAR
ENTRY DUCT
FLEX DUCT(36" MAXLENGTH)
HARD DUCTTRANSITION
TWO DIAMETERSMINIMUM LENGTHATINLET COLLAR SIZE
NOTES:
1. SIZE FLEX DUCT AND BRANCH DUCT TWO STANDARD DUCT SIZES LARGERTHAN TERMINAL UNIT INLET.
2 TERMINAL UNIT ENTRY DUCT DETAILNO SCALE
FOR 2-WAY VALVES
NOTES:1. PROVIDE SWING JOINTS AT SUPPLY AND RETURN CONNECTIONS TO
MAINS WHERE COIL RUNOUTS ARE LESS THAN 5'-0" LONG.2. THIS DETAIL ALSO APPLIES TO DUCT-MOUNTED HOT WATER COILS.3. LOCATE NEEDLE VALVES AS CLOSE TO COIL CONNECTIONS AS POSSIBLE.
COILHWS
HWRM
F
3 TERMINAL UNIT HOT WATER COILSNO SCALE
FLOWDIRECTION
FOR PIPING 2.5"AND SMALLER
FOR PIPING 3" AND LARGER
FULLSIZEPIPE
2" MAXIMUM
3" PIPE
FLOWDIRECTION
0.75"
0.75"
6"6"
4 MANUAL AIR VENTSNO SCALE
Newcomb&BoydCONSULTANTS AND ENGINEERS
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 2:
39:3
5 P
M
17220005
JUNE 27, 2016
M200
HVAC CONTROLS,SCHEDULES ANDDETAILS
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
MARK DATE DESCRIPTION
PLUMBING LEGEND
SYMBOLS
SOIL (S) OR WASTE (W) ABOVE FLOOR OR GRADE.
SOIL (S) OR WASTE (W) BELOW FLOOR OR GRADE.
VENT (V).
COLD WATER (CW).
HOT WATER (HW).
D INDIRECT DRAIN.
BASE CLEANOUT
STRAINER.
REDUCER - CONCENTRIC.
TYPE INDICATED ON SCHEDULE).
PRV-X PRESSURE REDUCING VALVE (X INDICATES THE PRV NUMBER;
CHECK VALVE.
GLOBE VALVE.
BALL VALVE.
TEMPERATURE AND PRESSURE RELIEF VALVE.
THERMOMETER (SEE SPECIFICATIONS FOR TYPE).
PRESSURE GAUGE.
A
AS INDICATED ON THE DRAWINGS).
WATER HAMMER ARRESTER (PDI SIZE A, B, C OR D
R
A-ATMOSPHERIC TYPE; D-DOUBLE CHECK VALVE TYPE).BACKFLOW PREVENTER (R-REDUCED PRESSURE TYPE;
ABBREVIATIONS
ABOVEABV
ABOVE CEILINGAC
ARCH ARCHITECT/ARCHITECTURAL
BEL BELOW
BF BELOW FLOOR
CLG CEILING
CONC CONCRETE
CONN CONNECT/CONNECTION
CONT CONTINUATION/CONTINUOUS
DOWNDN
DWG DRAWING
ELEC ELECTRICAL/ELECTRIC
EXP EXPOSED
FL FLOOR
GR GRADE
LV LAVATORY
MECH MECHANICAL
PDI PLUMBING AND DRAINAGE INSTITUTE
SPEC SPECIFICATION
SSTL STAINLESS STEEL
TEMP TEMPERATURE
TS TIGHT TO STRUCTURE
UC UNDERCOUNTER
VB VACUUM BREAKER
ABOVE FINISHED FLOOR/GRADEAFF/AFG
WC WATER CLOSET
CONNECT TO EXISTING.
WM WATER MACHINE
6. INSTALL PIPE I.D. WITH FLOW ARROWS AND INSULATION ON ALLDOMESTIC WATER PIPING SYSTEMS THROUGHOUT. LABEL ALL OTHERSYSTEMS COMPLETE WITH PIPE I.D. AND FLOW ARROWS.
GENERAL NOTES:
THESE DRAWINGS DO NOT PURPORT TO SHOW ALL EXISTINGUTILITIES.
INSULATE ALL DOMESTIC WATER PIPING THROUGHOUT THISRENOVATION.
MAKE ALL VALVES ACCESSIBLE THROUGHOUT THIS RENOVATION;INSTALL VALVE TAGS.
ANCHOR AND SECURE ALL PIPING IN CHASES AND WALLSTHROUGHOUT SO THAT NO MOTION OCCURS AFTER FINISHED WALLSARE INSTALLED.
5.
4.
3.
2.
1.
7. WHERE THE EXISTING STRUCTURE OR SURROUNDING INTERIOR ISDAMAGED DURING THIS RENOVATION, THE CONTRACTOR SHALL BERESPONSIBLE TO MAKE ALL NECESSARY REPAIRS TO MATCH EXISTING.
8. CONTRACTOR SHALL VERIFY THAT EXISTING WASTE AND WATER PIPINGSHALL BE OF AMPLE SIZE AT NEW WASTE AND WATER CONNECTIONPOINTS TO EXISTING.
9. PROVIDE AND INSTALL ESCUTCHEONS ON ALL VISIBLE PIPE PENETRATIONS
THROUGHOUT THIS PROJECT.
10. PROVIDE AND INSTALL ISOLATION BETWEEN DISSIMILAR METALS, SUCH AS
COPPER TO CAST IRON PIPING.
11. CONTRACTOR SHALL PROVIDE ALL TEMPORARY OPENINGS, PENETRATIONS
AND REPAIRS REQUIRED TO COMPLETE THE SCOPE OF WORK, TO INCLUDE
BUT NOT LIMITED TO CEILING REMOVAL, PATCHING AND REPLACEMENT
AND INSTALLATION OF DAMAGED TILES.
PRESSURE REDUCING VALVE ASSEMBLY SCHEDULE
NO.
PRV-1
NOTES:
1. TYPE: S L H
SERVICE
STANDARD LOW PRESSURE HIGH PRESSURE
TYPE
VALVE SIZE (IN.) AND SETTING (PSIG)
VALVE 1 VALVE 2 VALVE 3
WATER/ICE MACHINES L 0.5", 25 - -
BACKFLOW PREVENTER SCHEDULE
NO.
BFP-1
NOTES:
1. TYPE: D DOUBLE CHECK VALVE
RP REDUCED PRESSURE
LINE
SIZE, IN.
TYPE
(NOTE 1)GPM
PRESSURE
DROP, PSIGNOTES
0.5" D 1 - -
SERVICELOCATION
WATER/ICE MACHINESFACILITY
(MANUFACTURER NOTED FOR BASIS OF DESIGN ONLY).
MIXING VALVE SCHEDULE
NO.
MV-1
TYPE
(NOTE 1)SERVICE
DESIGN
GPM
MINIMUM CIRCULATING
FLOW RATE, GPM
PRESSURE DROP,
PSIG
TEMPERATURE
SETTING, °F
T,S FIXTURES 0.5 10 109° POWERS LF e480
NOTES
SINGLE VALVE
THERMOSTATICALLY CONTROLLED1. TYPE:
S
T
NOTES:
0.5
2. MANUFACTURER NOTED FOR BASIS OF DESIGN ONLY.
PLUMBING FIXTURE SCHEDULENO.
F1-F5F6
FIXTURE TYPE
NOT USED
PIPING CONNECTION SIZE
HW-
CW S OR W
STAINLESS STEEL SINK, ONE BOWL, UNDERMOUNT, ADA 0.5" 0.5" 1.5"
--
F11 ICE MAKER BOX 0.5"- -
WHERE AVAILABLE, EXISTING PIPING THAT REQUIRES A CONNECTION,
DEMOLITION OR MODIFICATION, SHALL BE FIELD VERIFIED BEFORE
COMMENCING WORK. CONTRACT DOCUMENTS OR AS-BUILT DRAWINGS
WERE REFERENCED TO INDICATE EXISTING PIPE SIZES.
EXISTING PLUMBING PIPING THAT REQUIRES DEMOLITION SHALL BE
REMOVED FROM THE SITE. UNLESS OTHERWISE NOTED, EXISTING
PIPING OR PIPE HANGERS SHALL NOT BE ABANDONED IN PLACE.
12.
WHERE EXISTING PIPING IS VERTICALLY ROUTED IN A CHASE OR WALL
WHICH SHALL BE DEMOLISHED, EXISTING PIPING SHALL OFFSET AND
ROUTE TO A NEW CHASE OR WALL TO AN ABOVE OR BELOW
RECONNECTION.
13.
EXISTING HOT AND COLD WATER PIPING SHALL NOT HAVE DEAD LEGSGREATER THAN (3) INCHES. PIPING BRANCHES SHALL PROPERLYTERMINATE WITH A VALVED AND CAPPED STUB.
14.
F7-F10 NOT USED - --
Newcomb&BoydCONSULTANTS AND ENGINEERS
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 3:
29:2
4 P
M
17220005
JUNE 27, 2016
P000
PLUMBING LEGEND,SCHEDULES ANDGENERAL NOTES
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
MARK DATE DESCRIPTION
SK
4
3
1
2
2
5
5
5
5
5
5
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 3:
29:3
1 P
M
17220005
JUNE 27, 2016
P100
PLUMBING PRESSURETHIRD FLOORDEMOLITION PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
PLUMBING PRESSURE THIRD FLOOR DEMOLITION PLAN
1
2
REMOVE EXISTING SINK AND TRIM; REMOVE EXISTINGWATER PIPING CONNECTIONS AND CAP BACK TO NEARESTACTIVE MAINS ABOVE CEILING.
REMOVE A SECTION OF EXISTING HOT AND COLD WATERPIPING FOR NEW WATER PIPING CONNECTIONS.
3 REMOVE EXISTING LAVATORY AND TRIM. REMOVE HOT ANDCOLD WATER PIPING CONNECTIONS AND TEMPORARILY CAPWATER PIPING BACK TO NEAREST ACTIVE MAINS ABOVE CEILINGFOR CONNECTIONS TO NEW SINK.
4 EXISTING PLUMBING EQUIPMENT AND PIPING IN THIS AREASHALL BE VERIFIED.
DEMOLITION NOTES:
5 EXISTING WATER PIPING SHALL REMAIN IN SERVICE.
DEMOLITION NOTES:
SEE DRAWING P101 FOR NEW WATER PIPING CONNECTIONSTO EXISTING WATER SYSTEM AND NEW FIXTURES ANDEQUIPMENT.
1.
MARK DATE DESCRIPTION
BREAK
ROOM
316
OCT.
318
PHYS.
WORK 4
319
MANAGER
355
EXAM
ROOM
308
DIAG.
314
DIAG.
315
DIAG.
333
DIAG.
334
DIAG.
335
DIAG.
337
CLEAN
336
MINOR
SURGERY
B-SCAN
342
SOILED
343
RECEPTION
/ CASH.
302
ELEC.
317
TLT
338
J/C
339
TLT
340
TLT
331
TLT
330
EXAM
ROOM
309
LASER
323
EXAM
ROOM
354
EXAM
ROOM
353
EXAM
ROOM
352
EXAM
ROOM
351
EXAM
ROOM
350
EXAM
ROOM
349
EXAM
ROOM
348
EXAM
ROOM
347
EXAM
ROOM
346
EXAM
ROOM
328
EXAM
ROOM
327
EXAM
ROOM
326
EXAM
ROOM
325
EXAM
ROOM
324
EXAM
ROOM
312
EXAM
ROOM
311
EXAM
ROOM
310
PHYS.
WORK 1
345
OFFICE
332
PHYS.
WORK 3
313
PHYS.
WORK 2
329
EXAM
ROOM
307
SWING
OFFICE
344
CORRIDOR
300
WAITING
301
TOIL.
303
CORRIDOR
305
TOIL.
304
CORRIDOR
306
CORRIDOR
320
CORRIDOR
341
CORRIDOR
322
CORRIDOR
321
CLINCAL
TRIALS
356
F6
F6A
F6A
F6A
1
0.5"
0.5"AC
2
F6
3
F11
CM
0.75"
0.75"
0.75"
1
1
10.75"
AC
4
5
6
6
6
6
6
6
6
6
6
6
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 3:
29:4
0 P
M
17220005
JUNE 27, 2016
P101
PLUMBING PRESSURETHIRD FLOOR PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
PLUMBING PRESSURE THIRD FLOOR PLAN
1
2
0.5" HOT AND COLD WATER DROP WITH MV-1 ASSEMBLY BELOWCOUNTER. SEE DETAIL 3/P300.
HOT AND COLD WATER PIPING CAPPED ABOVE CEILING.
3 0.5" HOT AND COLD WATER DROP; ROUTE 0.5" COLD WATERPIPING BELOW COUNTER TO COFFEE MAKER AND ICE MACHINE.SEE DETAIL 7/P300.
5
RENOVATION NOTES:
4 EXISTING COLD WATER PIPING CAPPED ABOVE CEILING.
DEMOLITION OF EXISTING PIPING AND ASSOCIATEDEQUIPMENT DOWNSTREAM OF THIS APPROXIMATELOCATION SHALL BE DETERMINED AFTER VERIFICATION OFEXISTING CONDITIONS.
6 EXISTING WATER PIPING.
MARK DATE DESCRIPTION
5
4
2
3
1
4
BF
AC
2
6
6
6
6
6
6
6
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 3:
29:4
8 P
M
17220005
JUNE 27, 2016
P200
PLUMBING WASTE THIRDFLOOR DEMOLITION PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
PLUMBING WASTE THIRD FLOOR DEMOLITION PLAN
1
2
REMOVE EXISTING SINK AND TRIM; REMOVE EXISTING WASTEAND VENT PIPING CONNECTIONS AND CAP BACK TO NEARESTACTIVE MAINS.
REMOVE A SECTION OF EXISTING VENT PIPING FOR NEW VENTPIPING CONNECTION.
3 REMOVE EXISTING LAVATORY AND TRIM. TEMPORARILY CAPEXISTING WASTE AND VENT PIPING ABOVE AND BELOW FLOORFOR NEW WASTE AND VENT PIPING CONNECTIONS TO NEW SINK.
4 REMOVE A SECTION OF EXISTING SANITARY/WASTE PIPINGFOR NEW WASTE PIPING CONNECTION.
5 EXISTING PLUMBING EQUIPMENT AND PIPING IN THIS AREASHALL BE VERIFIED.
DEMOLITION NOTES:
DEMOLITION NOTES:
SEE DRAWING P201 FOR NEW WASTE AND VENT PIPINGCONNECTIONS TO EXISTING DRAINAGE SYSTEM AND NEWFIXTURES AND EQUIPMENT.
6 EXISTING DRAINAGE AND VENT PIPING SHALL REMAIN INSERVICE.
1.
MARK DATE DESCRIPTION
BREAK
ROOM
316
OCT.
318
PHYS.
WORK 4
319
MANAGER
355
EXAM
ROOM
308
DIAG.
314
DIAG.
315
DIAG.
333
DIAG.
334
DIAG.
335
DIAG.
337
CLEAN
336
MINOR
SURGERY
B-SCAN
342
SOILED
343
RECEPTION
/ CASH.
302
ELEC.
317
TLT
338
J/C
339
TLT
340
TLT
331
TLT
330
EXAM
ROOM
309
LASER
323
EXAM
ROOM
354
EXAM
ROOM
353
EXAM
ROOM
352
EXAM
ROOM
351
EXAM
ROOM
350
EXAM
ROOM
349
EXAM
ROOM
348
EXAM
ROOM
347
EXAM
ROOM
346
EXAM
ROOM
328
EXAM
ROOM
327
EXAM
ROOM
326
EXAM
ROOM
325
EXAM
ROOM
324
EXAM
ROOM
312
EXAM
ROOM
311
EXAM
ROOM
310
PHYS.
WORK 1
345
OFFICE
332
PHYS.
WORK 3
313
PHYS.
WORK 2
329
EXAM
ROOM
307
SWING
OFFICE
344
CORRIDOR
300
WAITING
301
TOIL.
303
CORRIDOR
305
TOIL.
304
CORRIDOR
306
CORRIDOR
320
CORRIDOR
341
CORRIDOR
322
CORRIDOR
321
CLINCAL
TRIALS
356
F6
F6
F6
F6
3"
2"
2"
F61
2"
2"AC
BF
2
3
12" 2" AC
BF
1
1
1
AC
BF
42
43
5
6
5 6
6
5
6
65
Newcomb&BoydCONSULTANTS AND ENGINEERS
KJ L
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
KEYPLANPLAN NORTH
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 3:
29:5
7 P
M
17220005
JUNE 27, 2016
P201
PLUMBING WASTE THIRDFLOOR PLAN
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
1/8" = 1'-0"1
PLUMBING WASTE THIRD FLOOR PLAN
2
2" WASTE AND VENT.
EXISTING DRAINAGE PIPING CAPPED BELOW FLOOR.
3 EXISTING VENT PIPING CAPPED ABOVE CEILING.
4 DEMOLITION OF EXISTING PIPING AND ASSOCIATED EQUIPMENTUPSTREAM (DRAINAGE) OR DOWNSTREAM (VENT) OF THISAPPROXIMATE LOCATION SHALL BE DETERMINED AFTERVERIFICATION OF EXISTING CONDITIONS.
RENOVATION NOTES:
5 EXISTING DRAINAGE PIPING.
1
6 EXISTING VENT PIPING.
MARK DATE DESCRIPTION
PRESSURE REDUCING VALVE (PRV) ASSEMBLY
INSTALLATION IN HORIZONTAL PIPING
PIPE HANGER
WATER MACHINE/ICE MACHINE CONNECTION
PIPE THROUGH WALL-ABOVE GRADE
WALL CLEANOUT
PUBLIC LAVATORY/SINK MIXING VALVE
MAKER BOXREFRIGERATOR ICE
0.5" 120°F HW SUPPLY
0.5" CW SUPPLY
3/8" FLEXIBLE RISER
MIXING VALVE, MV-1
0.5" 109°F HWTO LAVATORY
3/8" FLEXIBLE RISER
COUPLING
LAVATORY AND FAUCET (FAUCETDESIGN MAY VARY FROM SPEC)
NOTES:
1. MV-1 FOR SINGLE FIXTURE PER MANUFACTURER'S REQUIREMENTS.
WASTE LINELENGTH TO SUIT
MAY EXTENDAS WASTE ORVENT PIPE
FOR WALLCONSTRUCTION; REFERTO ARCH'L DRAWINGS
PVC CLEANOUT TEE
CLEANOUTPLUG
COUNTERSUNKSCREW
CHROME WALLCOVER AND SCREW
1/8 BEND AND ENDOF LINE CLEANOUT
℄
METAL JACKET
SEALANT(BOTH SIDES)BACK UP
MATERIAL
1. INSTALL ESCUTCHEONS ON ALL VISIBLE PIPE WALL
NOTES:
ESCUTHEON
2. REFER TO ARCHITECTURAL DRAWINGS FOR EXTERIOR
NOTES:
1. INSTALL CLEANOUT AT THE BASE OF ALL STACKS.
COREDRILLED HOLE
INSULATION
ISOLATION VALVE
W/PET COCK
NO SCALE
GAUGE PORT
STRAINER
UNION
PRV
UNION
PRESSURE GAUGE
BRANCH VALVE
RISER
PET COCK
NOTES:
1. POSITION ALL PRESSURE GAUGES IN ANY ASSEMBLY TO BE
OBSERVED FROM THE SAME DIRECTION. (IN CHASE SPACE
NOTES:
0.5" CW SUPPLYIN WALL
0.5"
NOTE 2 (TYP)
1. INSTALL ASSEMBLY CLOSE AS POSSIBLE TO
BOTTOM OF CABINET AND ALONG BACK WALL.
2. BRACKET ASSEMBLY TO WALL OF CABINET AS REQUIRED
TO SUPPORT ALL PIPING AND VALVES AND TO PREVENT
MOVEMENT.
PRV
INSIDE OFCABINET BASE
NOTE 3
3. IN-LINE DOUBLE-CHECK BACKFLOW PREVENTER (WATTS, APOLLO, OR WILKINS, ASSE 1022 COMPLIANT, PER IPC 608.16.10).
PLUMBING FIXTURESTYLE, STRAIGHTSTOP VALVE (TYP)
CONNECT TOICE MACHINE OR
4. SOFT COPPER TUBING SIZED PER EQUIPMENT MANUFACTURER'S REQUIREMENTS.
NOTE 4
5. SET PRVs AT 25 PSIG.
A
STRAINER
NO SCALE
CONCRETE EXPANSIONBOLT CASING
0.625" HEX NUTS
WITH FLAT WASHERS,
GALVANIZED OR
ELECTRO-PLATED
0.625" ROD, STEEL,
GALVANIZED OR
ELECTRO-PLATED
STANDARD CLEVIS PIPE,
GALVANIZED OR
ELECTRO-PLATED FED
SPEC WW-H-171E, TYPE
I, OR MSS SP-69 TYPE I
120° INSULATIONPROTECTION SHIELD
NO SCALE
OR THRU ACCESS PANEL).
NO SCALE
PENETRATIONS.
WALL MATERIAL.
NO SCALE
COUNTER TOP(ICE MACHINE)
WATER MACHINE
NO SCALE
NOTES:
1. PIPING SHOWN IS CONCEALED IN WALL CONSTRUCTION.
2. CONNECTION BOX SHALL BE MINIMUM 24" ABOVE
3. PROVIDE ADEQUATE COILED 0.25" COPPER TUBING FOR
ICE MAKERCONNECTIONBOX
0.5"
A
NO SCALE
24" MIN
VALVE
SUPPLY FROMABOVE
FINISHED FLOOR
FINISHED FLOOR.
CONNECTION TO ICE MAKER.
1
P300 2
P3003
P300
4
P300
5
P300
6
P300
7
P300
Newcomb&BoydCONSULTANTS AND ENGINEERS
www.bsalifestructures.com
3340 Peachtree Road NE, Suite 1800Atlanta, GA 30326
ph 404.814.9090 fx 317.819.7288
DATE
COORD
DRAWN
APPROVED
CLIENT NO.PROJECT NO.
Copyright © 2016Consulting Engineering Group303 Peachtree Center Avenue, NESuite 525Atlanta, Georgia 30303-1277T 404 730-8400Contact:Kidane H. AbebeN&B PROJECT:16N088
C:\
Rev
it P
roje
cts\
ME
P_
Gra
dy
Eye
Clin
ic r
15_K
HA
.rvt
6/28
/201
6 3:
30:0
4 P
M
17220005
JUNE 27, 2016
P300
PLUMBING DETAILS
0000
ISSUE FORCONSTRUCTION
EYE CLINIC
MARK DATE DESCRIPTION