final report thermal
TRANSCRIPT
-
7/29/2019 Final Report Thermal
1/27
MEKELLE UNIVERSITY
ETHIOPIAN INSTITUTE OF TECHNOLOGY, EiT-M
DEPARTMENT OF MECHANICAL ENGINEERING
M.Sc. Program in Energy Technology
June, 2012
Course Title: Thermal System Design
Air Conditioning and Ventilation Assignment
Submitted to: Demiss A. (PhD) Prepared by: Alemnew Ebabu
Ashenafi K. (MSc.) Akatew Haile
Binyam Gebray
-
7/29/2019 Final Report Thermal
2/27
Assignment -1-
Design of ventilation system .
The Restaurant shown below is to be maintained at a constant environmental temperature of
22o
C for a plant operation of 12 hours per day.The Restaurant area is on the ground floor of anSingle storey building located at 51.7oNThe internal construction is lightweight partitions,
concrete hollow slab floors and suspended ceilings.it was desired to design a ventilation system
for the restaurant.
the following ste[ps are neccesary to be carried out the plan view of the restaurant is shown
belaow
Calculate Ventilation rates.
Decide on number of fans and grilles/diffusers.
Draw scale layout drawing and Position fan(s).
Lay out ductwork. Lay out grilles and diffusers.
Indicate flow rates on drawing. Size ductwork
Size fan Size grilles and diffusers
14.0 m
7.7
9.5
FemaleToilet
MaleToilet
Receptio
Entranc
10.0Lobby
Restaurant
3.5
Kitchen
2.7m
Cold
Store
Prep.
Room
PLAN
South
Height of wall to
eaves
Height of
ceiling at
-
7/29/2019 Final Report Thermal
3/27
Figure : the elevation plan view
Sn.
Design data for the restaurant
1 Occupants 70
2 Infiltration 1.0 ACH
3 Outside air temperature 28oC.
4 Area of window 2.8 m2
5 Total area of glass 28.0 m2
6 Area of glass facing South 28.0 m2
7 Area of wall facing South 28.0 m2
8 Floor area 140 m2
9 Room volume 623 m3
10 Building classification lightweight, fast response building
South
-
7/29/2019 Final Report Thermal
4/27
Table: ventilation system design data for occupancy, building category and exterior structure
dimensions
Ventilation requirements;
In this design it is proposed to ventilate the kitchen, the preparation room and the restaurant
and toilets separately using 4 exhaust fans the position of the fans its to be decided after the
longest path for which the maximum pressure drop occurs is determined the supply fan should be
as far as possible from the restaurant to avoid noise creation
All rooms the cheaper alternative is an extract system with replacement air coming in through
doors and operable windows. Fans should be located in accessible positions; in the corridor,
above ceilings. In-duct axial flow fans take up less space than centrifugal fans. Possible use ofwall mounted fan in Food Prep. Room. Upward with diffusers installed in suspended ceilings.
Use separate extract systems so that smoke will not spread from room to room through ducts.
Consider fire dampers in ducts. Fans are positioned as far away from Conference room and
restaurant as possible. Choose fans from catalogue with decibel levels less than 85dB if possible.
Table: restaurant rooms ventilation requirements as recommended by the Table B2.3 (CIBSE
1986)
ventilation requirements for restaurant rooms
Room or building type Recommended fresh air
supply rate
Recommended total air
supply rate(ACH)
Restaurant
Kitchen 10
Female toilet 8
Male toilet 8
-
7/29/2019 Final Report Thermal
5/27
Table: calculated ventilation rates for the rooms suggested requiring ventilation
The next is to calculate the fresh rate this was done by assuming that the outdoor air supply per
person should suit for a heavy smoking area this is because of the possibility that heavy smokers
may arrive as consumers at restaurants. And since we are dealing with restaurants it is fair to
assume a heavy smoking area with a recommended air supply rate per person of24 liters per
second. Therefore similarly like the ventilation requirements and assuming a peak of70 persons
the outdoor fresh air supply was found to be 1680
Table: recommended outdoor air supply rates
ROOMS volume(m3) Recommended (ACH) ventilation rate (m3/hr) ventilation rate(m3/s)
kitchen 217 35 7595 2.109722222
preparationroom 47.25 10 472.5 0.13125
male toilet 84 8 672 0.186666667
female
toilet 140 8 1120 0.311111111
restaurant 980 10 9800 2.722222222
12064.5 3.35125
Level of SmokingOutdoor air supply rate
(liter/s per person)
No smoking 8
Some smoking 16
Heavy smoking 24
Very heavy smoking 36
-
7/29/2019 Final Report Thermal
6/27
Table: calculated outdoor air supply rate
CALCULATING THE FRESH AIR RATE
occupants outdoor supply air(heavy smoking l/s/person) fresh air rate(l/s)
70 24 1680
Duct sizing
The recommended velocity for main duct and branch ducts for restaurants are 7.5m/s and 5m/s
respectively therefore by choosing a square duct with aspect ratio of 1 we can determine the
nearest standard sizes of the ducts and the following standard sizes were obtained for the main
duct and the branching ducts to the rooms which require ventilation.
As shown on the table below the main duct area is 0.45m
2
and the branching duct are also shownby considering a square duct the nearest standard sizes were determined for the rooms kitchen,
preparation room ,restaurant and toilets respectively
Table: standard size duct selection
Branching ducts(m2) Main duct area(m2) Square duct size(m)
Nearest
std.size(mm)
0.421944444 0.446833333 0.649572509 300*300mm
0.02625 0.162018517 150*150mm
0.037333333 0.193218357 150*150mm
0.062222222 0.249443826 150*150mm
0.668455932
500mm*500mm(std.)
-
7/29/2019 Final Report Thermal
7/27
Table : Recommended Duct velocities
Design tool duct sizer
BuildingAir Velocity (m/s)
Main Duct Branch
Domestic 3 2
Auditoria 4 3
Hotel bedroom, Conference hall 5 3
Private office, Library, Hospital ward 6 4
General office, Restaurant, Dept. store 7.5 5
Cafeteria, Supermarket, Machine room 9 6
Factory, Workshop 10-12 7.5
-
7/29/2019 Final Report Thermal
8/27
As t can be seen from the results of the duct sizer air at 370c and 23% relative humidity at 1
atm is assumed the results were found to be consistent with spreadsheet results moreover the
velocity pressure and the static pressure losses were found to be 0.749pa/m and 31.5pa for the
dynamic losses therefore the total head loss is given by
Total head loss= velocity pressure loss+ static head loss .
To compute the total pressure loss it is first necessary to identify the index run that is the longest
path of the duct work layout a suitable duct layout system is proposed next which roughly
identifies the longest path for which the highest pressure drop occurs and which is late used as a
selection criteria for the fan sizing.
Figure: rough duct layout system for the main and branching for the whole building to estimate
the index run
The duct layout can be laid out as shown above to roughly estimate the index run from the
supply side of the fan therefore the maximum run could be the duct system from the fan position
at the reception site to the branch duct for the preparation room which runs half the perimeter of
the whole building so it is estimated as 22m.
-
7/29/2019 Final Report Thermal
9/27
the next step is therefore to estimate the total static head loss for the index run which enables to
select the appropriate fan type by using the flow rate already obtained for their and the total
pressure earlier the pressure loss length was found as 0.79pa/m which gives
Total static pressure loss across the index run=22*0.79=31.5pa
Total pressure loss=static head loss dynamic head loss=49pa
from the calculations and from the table above showing the standard duct size selection
unequal size of branching ducts with duct dimensions ranging from150mm*150mm-
300*300mm were selected and 500mm*500mm standards size square duct were chosen .the
total pressure loss that the supply fan must overcome is found to be 49pa
Fan selection
Given the total pressure drop along the index run and the air flow rate for the main supply duct it
is possible to choose the appropriate fan from available catalogs from the above designcalculations the operation criteria was found to be 12064m
3/hr and 49pa.
Figure: fan performance curves for various models obtained from catalog
-
7/29/2019 Final Report Thermal
10/27
the fan performance curve for the model 634-b model is suitable for the air flow rate and total as
as shown by the red lines corresponding to the flow rate and total pressure losses obtained from
calculations 12604m3/hr and 49pa.
Table; product specification of fans type cc 630
For more comprehensive design one can look at the power requirements and noise conditions byreferring to the specifications provided in the above table the model we have chosen has a noise
generation of71db which is acceptable for the restaurant compared to 85db limit.
-
7/29/2019 Final Report Thermal
11/27
AC System Design for the Assembly Hall
Introduction
An air conditioning system is used to give comfort for humans by creating favorable conditions
in residence places, working environments, assembly halls etc. The system does this byhumidifying or dehumidifying the air and maintaining the temperature level of the air. During
the process heat is either supplied or extracted from an area. The cooling is done using a simple
refrigeration cycle.
Air conditioners and refrigerators work on the same principle. Instead of cooling just the small,
insulated space inside of a refrigerator, an air conditioner cools a room, a whole house, or anentire business. Air conditioners use refrigerants that can be easily converted from a gas to a
liquid and back again. This chemical is used to transfer heat from the air inside of a home to the
outside air.
The air conditioning unit has three main parts. These are a compressor, a condenser and an
evaporator. The compressor and condenser are usually located on the outside air portion of theair conditioner. The evaporator is located inside the house.
The working fluid arrives at the compressor as a cool, low-pressure gas. The compressorsqueezes the fluid. This packs the molecule of the fluid closer together. The closer the molecules
are together, the higher its energy and its temperature.
The working fluid leaves the compressor as a hot, high pressure gas and flows into the
condenser. When the working fluid leaves the condenser, its temperature is much cooler and ithas changed from a gas to a liquid under high pressure. The liquid goes into the evaporator
through a very tiny, narrow hole. On the other side, the liquid's pressure drops. When it does it
begins to evaporate into a gas.
As the liquid changes to gas and evaporates, it extracts heat from the air around it. The heat in
the air is needed to separate the molecules of the fluid from a liquid to a gas. The evaporator has
metal fins to help in exchange the thermal energy with the surrounding air. By the time theworking fluid leaves the evaporator, it is a cool, low pressure gas. It then returns to the
compressor to begin its trip all over again. Connected to the evaporator is a fan that circulates the
air inside the house to blow across the evaporator fins. Hot air is lighter than cold air, so the hotair in the room rises to the top of a room.
There is a vent there where air is sucked into the air conditioner and goes down ducts. The hot air
is used to cool the gas in the evaporator. As the heat is removed from the air, the air is cooled. Itis then blown into the house through other ducts usually at the floor level.
-
7/29/2019 Final Report Thermal
12/27
In selecting a suitable air conditioning system for a particular application, consideration is given
to the following:
System constraints : Cooling load, Zoning requirements, Heating and ventilation
Architectural Constraints : Size and appearance of terminal devices, acceptable noise
level, Space available to house equipment and its location relative to the conditioned
space, acceptability of components in the conditioned space
Financial Constraints : Capital cost, Operating cost, Maintenance cost
Figure: Basic refrigeration cycle used in air conditioning systems
Air conditioning systems are categorized in three main parts. These are: central plants, room air
conditioning units and fan coil units. In central plant air conditioning units, there is one source of
conditioned air which is distributed in different parts through a network of ducts. Room air
conditioning units use refrigerant to give cooling effects for a room. Fan coil air conditioning
types use chilled water instead of refrigerant to produce conditioned air.
Figure: Central air conditioning system
-
7/29/2019 Final Report Thermal
13/27
Room air conditioning units fall into two main categories: These are split type with indoor and
outdoor unit and window/wall units with evaporator at inside and condenser at the outside face.
Split Room air conditioning units: Split air conditioners have two main parts, the outdoor unit
is the section which generates the cold refrigerant gas and the indoor unit uses this cold
refrigerant to cool the air in a space.
The outdoor unit uses a compressor and air cooled condenser to provide cold refrigerant to a
cooling coil in the indoor unit. A fan then blows air across the cooling coil and into the room.
The indoor unit can either be ceiling mounted (cassette unit), floor mounted or duct type.
Figure: Split air conditioning units
Window/Wall Units: Window or wall units are more compact than split units since all the plant
items are contained in one box. Window units are installed into an appropriate hole in the
window and supported from a metal frame.
-
7/29/2019 Final Report Thermal
14/27
Wall units like the one shown below are built into an external wall and contain all the necessary
items of equipment to provide cool air in summer and some may even provide heating in winter.
Figure: wall air conditioning units
-
7/29/2019 Final Report Thermal
15/27
Objective
The main objective of this project work is to design air conditioning system for an assembly hall.
Given Parameters
Number of people: 375
Building height: 6 meters
Number of windows: 6
Window size: 2x4 meters
Orientation of windows: south east and south west
Basic Steps for Design
Air conditioning is required in buildings which have a high heat gain and as a result a high
internal temperature. The heat gain may be from solar radiation and/or internal gains such as
people, lights, business machines etc.
If the inside temperature of a space rises to above 25 oC then air conditioning is necessary to
maintain comfort levels. This internal temperature (around 25oC) may change depending on a
number of variables such as:
type of building
location of building
duration of high internal temperature
Expected comfort conditions.
degree of air movement
percentage saturation
Cooling load or heating load determination is based on annual climate data, building data and
occupancy data. The climate data should include monthly dry bulb temperature, wet bulb
temperature, average solar radiation, relative humidity etc.
The building data includes floor area, building height to determine the total volume of the space.
In addition to this, a number of building parameters are required for heating or cooling load
calculation.
The occupancy data are important for heating/cooling load determination. The flow rate
requirement of conditioned air at different parts of a room also depends on this parameter.
-
7/29/2019 Final Report Thermal
16/27
Figure: Air conditioning system design flow process chart
Cooling Load Determination
The load on an air-conditioning system can be divided into the following sections:
1. Sensible Transmission through glass.
2. Solar Gain through glass.
3. Internal Heat gains
-
7/29/2019 Final Report Thermal
17/27
4. Heat gain through walls.
5. Heat gain through roof.
6. Ventilation and/ or infiltration gains.
The heat gain through the glass windows is divided into two parts since there is a heat gain due totemperature difference between outside and inside and another gain due to solar radiation shining
through windows.
Heat gains through solid ground floors are minimal and can be neglected.
Sensible Transmission Through Glass
This is the Solar Gain due to differences between inside and outside temperatures. In very warmcountries this can be quite significant. This gain only applies to materials of negligible thermal
capacity i.e. glass.
Qg = Ag . Ug (To- Tr) .
Where;
Qg = Sensible heat gain through glass (W)
Ag = Surface area of glass (m2)
Ug = 'U' value for glass (W/m2 oC)
To = outside air temperature (oC)..
Tr = room air temperature (oC)
Solar Gain Through Windows
This gain is when the sun shines though windows. The cooling loads per metre squared window
area have been tabulated in stanadrds. for various; locations, times, dates and orientations. Thesefigures are then multiplied by correction factors for; shading and air node correction factor.
Heat load is determined as follows;
Qsg = Fc . Fs . qsg . Ag
Where: Qsg = Actual cooling load (W)
Qsg = Tabulated cooling load (W/m2)
Fc = Air node correction factor from Table
Fs = Shading factor.
Ag = Area of glass (m2)
-
7/29/2019 Final Report Thermal
18/27
Internal Heat Gains
Internal gains can account for most heat gain in buildings. These gains are from occupants,
lights, equipment and machinery, as detailed in the figure below. Occupants Sensible and latent
heat gains can be obtained from tables.
Figure: Internal heat gains for a building
Table: Internal heat gains from occupants at different activity levels
Conditions Typical building
Sensible
Heat Gain
(Watts)
Latent Heat Gain
(Watts)
Seated very light workOffices, hotels,
apartments70 45
Moderate office workOffices, hotels,
apartments75 55
Standing, light work;
walking
Department store, retail
store 75 55
Walking standing Bank 75 70
Sedentary work Restaurant 80 80
Light bench work Factory 80 140
-
7/29/2019 Final Report Thermal
19/27
Heat Gain Through Walls
This is the unsteady-state heat flow through a wall due to the varying intensity of solar radiation
on the outer surface.
4.1 Sol-Air Temperature
In the calculation of this heat flow use is made of the concept of sol-air temperature, which is
defined as; the value of the outside air temperature which would, in the absence of all radiation
exchanges, give the same rate of heat flow into the outer surface of the wall as the actual
combination of temperature difference and radiation exchanges.
Teo = Ta + ( )
Where:
Teo = sol-air Temperature (oC)
Ta = outside air temperature (oC)
= absorption coefficient of surface
I = intensity of direct solar radiation on a surface at right angles (W/m2)
A = solar altitude (degrees)
n = wall-solar azimuth angle (degrees)
Is = intensity of scattered radiation normal to a surface (W/m2
)
hso = external surface heat transfer coefficient (W/m2oC)
4.2 Thermal Capacity
The heat flow through a wall is complicated by the presence of thermal capacity, so that some of
the heat passing through it is stored, being released at a later time. Thick heavy walls with a high
thermal capacity will damp temperature swings considerably, whereas thin light walls with a
small thermal capacity will have little damping effect, and fluctuations in outside surface
temperature will be apparent almost immediately.
Heat Gain Through Roof
The heat gain through a roof uses the same equation as for a wall as shown below.
Q+Roof = A U [( Tem - Tr) + f ( Teo - Tem)]
. I . cos a . cos n + Is
hso
-
7/29/2019 Final Report Thermal
20/27
Ventilation and/or Infiltration Gains
Heat load is found from;
Qsi = n . V (To- Tr) / 3
where Qsi = Sensible heat gain (W)
n = number of air changes per hour (h-1)
V = volume of room (m3)
To = outside air temperature (oC)
Tr = room air temperature (oC)
Infiltration gains should be added to the room heat gains. Recommended infiltration rates are 1/2
air change per hour for most air-conditioning cases. Ventilation or fresh air supply loads can be
added to either the room or central plant loads but should only be accounted for once.
Total Room Load From Heat Gains
Q total = Qg + Qsg + Qint. + QWall + Q Roof + Qsi
Cooling Load for the Assembly Hall
For determination of the cooling load of the assembly hall, we have taken the following data and
assumptions:
Data:
Number of People = 375
Number of windows = 6
Window size = 2x4 m
Orientation of windows = South east and south west
Average building height = 6 meters
-
7/29/2019 Final Report Thermal
21/27
Assumptions:
Infiltration = 0.8 air changes per hour
Building classification = medium weight
Building response = fast
External wall 'U' value = 0.45 W/m2o
C
External wall colour = light.
External wall decrement factor f = 0.7
Glass type & 'U' value = clear 5mm, double glazing, U = 2.80 W/m2oC
Lighting = 20 Watts / m2 floor area
Heat gain from equipments = 1000 Watts
Maximum outside temperature = 280C
Room maintained temperature = 220C
Area calculation:
Area of window = 2 x 4 = 8 m2.
Total area of glass = 8 x 6 No. windows = 48 m2.
Area of glass facing South = 48 m2
Area of wall facing South = 24 m x 6 m high = 96 m2
less glass
= 144 - 48 = 96 m2
Floor area = (92 + 20) m2.
Room volume = 112 x 6 = 672 m3.
Gains:
1. Sensible transmission through glass Qg = Ag Ug (To - Tr)
Qg = 48 x 2.8 (28 22)
Qg = 806.4 Watts
-
7/29/2019 Final Report Thermal
22/27
2. Solar Gain through glass Qsg = Fc Fs qsg Ag
Where:
Qsg = Actual cooling load (W)
Fc = Air node correction factor from forinternal blind, fast response - 0.91.
Fs = Shading factor fast response 0.95.
qsg = 260 W/m2
Ag = Area of glass facing South (m2)
Qsg = 0.91 x 0.95 x 260 x 48
Qsg = 10788.96 Watts
3. Internal Qint. = Qint.
Qint. = Lights (20 W/m2 x 112) + 1000 W + People (375 x 100)
Qint. = 2240 + 1,000 + 37500
Qint. = 378,240 Watts
4. External wall Q Wall = A U [( Tem - Tr) + f ( Teo - Tem)]
Where:
Q = heat gain through wall at time q+f (Watts)
A = area of wall facing South (m2)
U = overall thermal transmittance given in question as 0.45 W/m2 o
C
Ttem = 240C
Tr
= constant dry resultant temperature (oC). Room dry bulb of 21oC is given
f = decrement factor for wall is given as 0.65
Tteo = 370C
-
7/29/2019 Final Report Thermal
23/27
Q+Wall = 96 x 0.45 [( 24 22) + 0.65 ( 37 24)]
Q+Wall = 451.44 Watts
5. Roof Q+Roof = Nil for intermediate floor
6. Ventilation Qsi = n V (to - tr) / 3
Qsi = 0.8x672 (28 22) / 3
Qsi = 1075.2 Watts
7. Q total = Qg + Qsg + Qint. + Q+Wall + Q +Roof + Qsi
Q total = 806.4 + 10788.96 + 378,240 + 451.44 + 0 + 1075.2
Q total = 391,362 Watts or 391.362KW
Air Flow Rate Determination
Once we have determined the cooling load of the building, For an Air Conditioning system the
supply air flow rate for cooling is found from the following formulae:
m = H / (Cp x (tr ts))
Where:
H = Sensible heat gain (kW)m = mass flow rate of air (kg/s)
Cp = Specific heat capacity of air (1.005 kJ/kg K)
tr = room temperature (oC)
ts = supply air temperature (oC)
m = H / (Cp x (tr ts))
= 391.362/ (1.005* (22 15)
= 55.63 kg/s
Mass flow rate is converted to a volume flow rate as follows:
Volume flow rate (m3/s) = mass flow rate (kg/s) / density of air (kg/m3)
= 55.63 (kg/s)/1.225 (kg/m3)
= 4.52 m3/s or 16,351 m3/h
-
7/29/2019 Final Report Thermal
24/27
Duct sizing
From the above table the recommended air velocity for a conference hall for the main and branch
ducts are highlighted and are 5m/s and 3m/s respectively. in order to be able to size the duct the
recommended 5m/s is first taken to dimension the duct with a flow rate of16,351 m3/hr.
Building
Air Velocity (m/s)
Main
DuctBranch
Domestic 3 2
Auditoria 4 3
Hotel bedroom,
Conference hall5 3
Private office, Library,
Hospital ward6 4
General office, Restaurant,
Dept. store7.5 5
Cafeteria, Supermarket,
Machine room9 6
Factory, Workshop 10-12 7.5
-
7/29/2019 Final Report Thermal
25/27
The duct characteristics were calculated using the duct sizer as shown in the above for the main
supply duct and it was found out that the static head loss per length was 0.103pa/m and the
dynamic pressure loss of15.2pa.
The next step would be to compute the total pressure loss and in turn find out the supply fan
Index run should be identified to calculate the total static head loss therefore 65m is assumed to
be the longest run to determine the total static head loss.
Hence total static pressure loss=index run*0.103pa/m
=65*0.056=3.64pa
Total pressure loss=6.7+15.2
=21.9pa
The duct sizes for the branching ducts can also be determine similarly using the e duct sizer and
the following results were found for the entrance air conditions assumed.
The equivalent diameter for the branching ducts are with a flow area of by assuming a square
duct and since for uniform air distribution the diffusers must supply equal flow rates the flow
rate pre each diffuser equals 16351/16=1022m3/hr and the recommended air velocity for the
branches for the conference halls is 3m/s this means that a flow area of
1022/3*3600m2=0.104m
2is the minimum duct area for the diffusers .by assuming square duct
which is 323mmduct and the nearest standard size duct cab be assumed with 300mm*300mm
16351 m3/hr
1022m3/hr
300mm*300mm
Square duct
-
7/29/2019 Final Report Thermal
26/27
-
7/29/2019 Final Report Thermal
27/27