    I nt ro t o Convent ional Fire Alarm Systems

    1

    I ntroduct ion t o

    ConventionalFire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    2/117

    I nt ro t o Convent ional Fire Alarm Systems

    2

    Course Descr ipt ionu This two-hour introductory course is forindividuals with little or no experience in the firealarm industry. The course covers the basic buildingblocks of modern conventional and addressable firealarm systems.

    u It covers the primary and secondary functions ofa fire alarm control panel, various initiating and

    notification devices, digital communicators,waterflow alarm and sprinkler monitoring.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    3/117

    I nt ro t o Convent ional Fire Alarm Systems

    3

    Course Cont ent su Basic Elements of a Fire Alarm System

    u Supplementary Functions

    u Physical Elements of Fire

    u Initiating Devices

    u Notification Appliances

    u Water Flow and Sprinkler Monitoring

    u Types of Control Panels

    u Design Issues

    u Notification Appliance Circuit (NACs)

    u Supplementary Circuit Wiring

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    4/117

    I nt ro t o Convent ional Fire Alarm Systems

    4

    Life Safety!

    What is t hepurpose of a Fire

    Alarm System?

    Detect, Alert and Evacuate.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    5/117

    I nt ro t o Convent ional Fire Alarm Systems

    5

    Basic Fire

    Lets examine the

    components that make abasic Fire AlarmCont rol System .

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    6/117

    I nt ro t o Convent ional Fire Alarm Systems

    6

    Main Cont rolleru The brains of the system.

    u

    Provides power to thesystem, monitors inputs andcontrols outputs through

    various circuits.

    u Performs other functions asrequired by the appropriatecode.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    7/117

    I nt ro t o Convent ional Fire Alarm Systems

    7

    Element s of a Cont rol PanelMain Cont roller, Pow er, I nput s and Out put s

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    8/117

    I nt ro t o Convent ional Fire Alarm Systems

    8

    Primary ( AC)

    Secondary (DC)

    Requ i res t w o Pow er Sou r ces Element s of a Cont rol Panel

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    9/117

    I nt ro t o Convent ional Fire Alarm Systems

    9

    Smoke Detector

    Manual Pull Station

    A fire alarmsystem can havea variety ofinput devices.

    Elements of a Cont rol PanelI n p u t s

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    10/117

    I nt ro t o Convent ional Fire Alarm Systems

    10

    Inputs

    u I nit iat ing Device A system component that

    originates transmission of a change of statecondition, such as a smoke detector, manual firealarm box, supervisory switch, etc....

    u I nit iat ing Device Circuit ( I DC)A circuit towhich automatic or manual initiating devices areconnected where the signal received does notidentify the individual device operated.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    11/117

    I nt ro t o Convent ional Fire Alarm Systems

    11

    Horns

    Strobes

    Elements of a Cont rol PanelO u t p u t s

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    12/117

    I nt ro t o Convent ional Fire Alarm Systems

    12

    Outputs

    u Not if icat ion Appliance A fire alarm systemcomponent such as a bell, horn, speaker, light,

    or text display that provides audible, tactile, orvisible output, or any combination thereof.

    u Not if icat ion Appliance Circuit A circuit orpath directly connected to a notificationappliance.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    13/117

    I nt ro t o Convent ional Fire Alarm Systems

    13

    The Basic System

    Secondary (DC)

    Primary ( AC)

    Outputs

    Inputs

    Main Cont rol ler

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    14/117

    I nt ro t o Convent ional Fire Alarm Systems

    14

    Supplement ary Operat ionsu Elevator Capture

    u Equipment Shutdown

    uAir Handling Shutdownu Damper Control

    u Extinguishing SystemInterface

    u Event Printing

    u Display Monitor Interface

    u Door Holding Devices

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    15/117

    I nt ro t o Convent ional Fire Alarm Systems

    15

    Supplement ary Operat ionsu Remot e Signal Annunciat ion - Provides

    critical system status and basic control capabilityfrom a more convenient location than where thecontrol panel might be located.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    16/117

    I nt ro t o Convent ional Fire Alarm Systems

    16

    Remote AnnunciatorsRZA-5X

    Remote Zone

    Annunciator

    LCD-80F LiquidCrystal Display

    Graphic

    Annunciator

    (Custom)

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    17/117

    I nt ro t o Convent ional Fire Alarm Systems

    17

    DACTsUDACT UniversalDigital CommunicatorTransmitter

    Dedicated DACT"daughterboard"

    411UD Slave/StandAlone DACT

    Integral Onboard DACT

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    18/117

    I nt ro t o Convent ional Fire Alarm Systems

    18

    Basic Fire Alarm TechnologySignal I nit iation & I nit iating Devices

    What is

    t he

    threat?

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    19/117

    I nt ro t o Convent ional Fire Alarm Systems

    19

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    20/117

    I nt ro t o Convent ional Fire Alarm Systems

    20

    Aut omat ic Fire

    Detectors

    How do w e detectt he t hreat?

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    21/117

    I nt ro t o Convent ional Fire Alarm Systems

    21

    Aut omat ic Fire Detectors

    u Spot Detect ors provide detection concentrationin a particular location - Heat & Smoke Detectors.

    u Line Det ect ors provide continuous detectionalong a path - Thermal Cable & Beam Detectors.

    u Air Sampl ing Systems draw air through pipes toan enclosed chamber for testing. - (VESDA & DuctDetectors.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    22/117

    I nt ro t o Convent ional Fire Alarm Systems

    22

    u Photoelectric

    u Light-Scattering (Reflective)u Light-Obscuring (Beam)

    u Ionization

    u Thermal (heat)

    u Duct

    Aut omat ic Fire Detectors

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    23/117

    I nt ro t o Convent ional Fire Alarm Systems

    23

    Phot oelect r ic Smoke DetectorsLight -Scat t ering Type

    u These detectors use a Light-Emitting Diode

    (LED) that sends a beam of light into a darkchamber. A photo diode sits on the other side of apartition within the chamber.

    u Smoke particles entering the chamber deflect

    some of the light rays into the photocell. The photocell generates a current when exposed to light, andif the current reaches a certain level, the smokedetector alarms.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    24/117

    I nt ro t o Convent ional Fire Alarm Systems

    24

    Light Scat t er ing Pr incipalSensing Chamber

    LightEmitting

    Diode

    PhotoDiode

    Partition

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    25/117

    I nt ro t o Convent ional Fire Alarm Systems

    25

    Light Scat ter ing Pr incipal

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    26/117

    I nt ro t o Convent ional Fire Alarm Systems

    26

    u In a projected BeamDetector, alarms are

    generated by diffusing theprojected light beam by a

    specified percentage ofobscuration. Total beamblockage generally resultsin a trouble signal.

    Phot oelect r ic Smoke DetectorsLight Obscurat ion Type

    u Wire the receiver unit as a 4-wire detector (separatepower and sensing connections to the control panel).

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    27/117

    I nt ro t o Convent ional Fire Alarm Systems

    27

    Projected Beam Principal

    Transmitter Receiver

    Smoke from thefire in the protected

    area diffuses the

    intensity of the beam at the receiver

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    28/117

    I nt ro t o Convent ional Fire Alarm Systems

    28

    I onizat ion Smoke Detectors

    u These detectors contain a small amount ofradioactive material encapsulated in a metalchamber. Ionizing radiation develops a low, butsteady electrical current. Smoke particles enteringthe chamber disrupt the current and trigger thedetector's alarm.

    u Ion detectors react more quickly to fast flaming

    fires that give off little smoke.

    u Spot-type Detectors.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    29/117

    I nt ro t o Convent ional Fire Alarm Systems

    29

    DuctDetectors

    u Photoelectric detector mounted in housing

    outside the ductwork that has probes that

    extend into the duct to sample the air insidethe duct.

    u Primarily used as a smoke control device tocontrol the flow of air in ductwork.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    30/117

    I nt ro t o Convent ional Fire Alarm Systems

    30

    The i3 series is based on three guiding principles:I nstallation ease, I ntelligence, and I nstantinspection.

    uPlug-In Head/Base combination.uSmoothing algorithms

    uDrift compensation (automatically adjusts fordust accumulation, reducing nuisance alarms)

    uOptional Sensitivity Reader

    The i3 SeriesThis line of photoelectric smokedetectors by System Sensor consists of2- and 4-wire detectors, offered with or

    without a fixed 135

    temperaturethermal sensor.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    31/117

    I nt ro t o Convent ional Fire Alarm Systems

    31

    Manual I nit iat ing DevicesThe Manual Fire Alarm Pull Station

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    32/117

    I nt ro t o Convent ional Fire Alarm Systems

    32

    I nit iat ing DevicesManual Fire Alarm St at ions

    u Manually operated device used to

    initiate an alarm signal.u Single Act ion Stations require a single

    operation to activate it. Generally a pullingdown action.

    u

    Dual Act ion Stations require two distinctoperations. A set-up and an activating action.

    u Breakglass Stations have an inhibit devicethat must be damaged to activate the station(non-ADA compliant).

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    33/117

    I nt ro t o Convent ional Fire Alarm Systems

    33

    I nit iat ing DevicesManual Fire Alarm Stat ions

    u Opt ional Features

    u With and without key locks or hex key locks

    u Weatherproof models with special backboxes

    u With auxiliary contacts

    u Multiple languages, even dual languages.

    u With a pre-signal featureu With screw-terminal or pigtail connections

    u Conventional and Addressable

    u Metal or Polycarbonate

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    34/117

    I nt ro t o Convent ional Fire Alarm Systems

    34

    Single-Act ion Manual Stat ionSpring-loaded

    releasingswitch

    ResetKey

    ActuationHandle

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    35/117

    I nt ro t o Convent ional Fire Alarm Systems

    35

    Dual-Act ion Manual Stat ion

    Initial

    Pre-Actuator

    Actuator

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    36/117

    I nt ro t o Convent ional Fire Alarm Systems

    36

    Non Alarm Pull Stat ions

    I C i l Fi Al S

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    37/117

    I nt ro t o Convent ional Fire Alarm Systems

    37

    Heat DetectorsHeat detectors are the oldest type of automaticfire detection device. Not considered direct LifeSafety devices, these detectors do contributeto the detection of a fire.

    I C i l Fi Al S

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    38/117

    I nt ro t o Convent ional Fire Alarm Systems

    38

    Heat Detectorsu Fixed Detect ors alarm when the sensing elementreaches a certain set point. Two common ones have135 and 200-degrees F range. The Fixed element isgenerally a non-restorable type, and when activated, must bereplaced.

    u Rate- o f - Rise Detect ors respond when the rate oftemperature increase is greater than an allowable limit(15 degrees in 60 secs.) (placement in a stableenvironment) (e.g.. ovens, heating vents, etc.). The

    Rate-of-Rise element is restorable when conditions return tonormal.

    u Rate Com pensat ion will respond regardlessof therate of temperature rise.

    I t t C t i l Fi Al S t

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    39/117

    I nt ro t o Convent ional Fire Alarm Systems

    39

    Heat Det ect orsRate Compensation Type

    u Detector responds when the temperature of the

    surrounding air reaches a predetermined level,regardless of the rate oftemperature rise.

    u The system compensates for Thermal Lag.

    u During a slow rate of temperature rise there ismore time for heat to penetrate the inner element,which inhibits contact closure until the total devicereaches the rated temperature level.

    u During fast rate of increase, there is less time forheat to penetrate the inner element, which exertsless inhibiting effect, so contact closure is still

    obtained at the rated temperature.

    I t t C t i l Fi Al S t

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    40/117

    I nt ro t o Convent ional Fire Alarm Systems

    40

    Heat Detectors

    u

    DONT Paint Heat Det ect ors!!!

    u Why? Because Thermal Lag occurswhen the physical properties of the Heat

    detector cause it to lag behind the alarmcondition of the surrounding air.

    I t t C t i l Fi Al S t

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    41/117

    I nt ro t o Convent ional Fire Alarm Systems

    41

    Heat Det ectorsu Exhibit the lowest false alarm rate of all

    automatic fire detector devices,

    u Slowest-responding fire detection devices.

    u Best used in applications where

    u Fast-developing, large fires are expected.

    u Environment won't allow the use of other

    fire detection devices.u The speed of detection is not a prime

    consideration.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    42/117

    I nt ro t o Convent ional Fire Alarm Systems

    42

    Heat DetectorsHeat Sensitive Cable

    u A line-type initiating device whose sensing elementcomprises, in one type, two current-carrying wires

    held separated by heat-sensitive insulation whichsoftens at the rated temperature, thus allowing thewires to make electrical contact.

    u Installed at the exact point of risk to provide rapidlocalized detection of abnormal temperature rises(overloaded or short-circuited high voltage power

    wiring).

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    43/117

    I nt ro t o Convent ional Fire Alarm Systems

    43

    Heat Detect orHeat Sensit ive Cable

    Actuators

    Outer Insulation

    Protective Tape

    Heat SensitiveMaterial

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    44/117

    I nt ro t o Convent ional Fire Alarm Systems

    44

    Not if icat ion Appl iances Types

    u Audible - Horns, Bells, Sounders,

    Sirens, Chimes, Speakers.

    u Visual - Strobes

    u Physical - Bed shakers

    u Olfactory - Smell

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    45/117

    I nt ro t o Convent ional Fire Alarm Systems

    45

    Audible Devicesu Bells: Only used if they are only for

    fire, or have a distinctive sound fromother bell signaling devices. Often

    used as an external gong to indicatethe flow of water in the sprinklersystem.

    u Horns: Loud and distinctive output.Often used in high-noiseenvironments, such as manufacturingplants.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    46/117

    I nt ro t o Convent ional Fire Alarm Systems

    46

    Audible Devicesu Sounders: Electronic or mechanical

    audible devices, which are capable ofproducing a variety of tones. Often, the

    tone is selectable during installation ofthe device.

    u Chimes: Soft-toned appliances usedwhere loud noises could be disruptive toother operations. Generally used wherequalified personnel are continuously inattendance.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    47/117

    I nt ro t o Convent ional Fire Alarm Systems

    47

    Audible Devices

    u Sirens: Extremely loud devicesgenerally limited in use to outdoor

    or heavy industrial areas.

    u Speakers: Audible devices used inconjunction with voice evacuation

    messages. Life-Safety speakers arenot generally associated with Muzak

    systems.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    48/117

    I nt ro t o Convent ional Fire Alarm Systems

    48

    Audible Codesu Coded out put s are required in many applications.

    This can be accomplished by pulsing tones for

    different areas of the building, or zoning the outputs(floor above - floor below).

    u General alarm codes commonly used are MarchTime(110-120 ppm) or Temporalcode (ANSIEvacuation Code 3).

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    49/117

    I nt ro t o Convent ional Fire Alarm Systems

    49

    Visual

    Signaling

    Appliances

    Visual signaling appliances are used in high-noiseenvironments, in areas occupied by hearing-

    impaired individuals, or in areas where audibledevices may not be desired.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    50/117

    I nt ro t o Convent ional Fire Alarm Systems

    50

    VisualDevices

    Speaker/ St robe

    Chime/ St robe

    Horn/ St robe

    Strobe

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    51/117

    I nt ro t o Convent ional Fire Alarm Systems

    51

    Selectable-OutputVisual Devices

    u Selectable Candela Output (15 - 30 - 60 -75 - 110)

    u Selectable Operating Voltage (12 or 24 volts)

    u Offered in Strobe and

    Horn/Strobe combinations

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    52/117

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    53/117

    I nt ro t o Convent ional Fire Alarm Systems

    53

    Ful l-Wave Rect if ied Pow er

    24v

    0v

    42v

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    54/117

    I nt ro t o Convent ional Fire Alarm Systems

    54

    Fil t ered Regulated Pow er

    24v

    0v

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    55/117

    I nt ro t o Convent ional Fire Alarm Systems

    55

    Secondary Pow er

    u Direct Current - Clean, absolute filtered power

    u Supplies the system with operating power underthe loss of primary (AC) for at least 24 hours ofstandby (quiescence) followed by 5 minutes in

    alarm. Voice systems require 15 minutes in alarm.u Rated in AMP-HOURS (AH).

    u Must be calculated!

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    56/117

    t o t o Co e t o a e a Syste s

    56

    Relays and Contact su Form A - refers to a relay with contacts for common

    and normally open ONLY.

    u Form B - refers to a relay with contacts for commonand normally close ONLY.

    u Form C - refers to a relay with contacts for common,normally open, and normally closed.

    u Dry Cont act s -By magnetically controlling the stateof the contacts, the control panel is electricallyisolated (and thus protected) from power connectedto the contacts..

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    57/117

    y

    57

    Relays and Contact s

    When a relay is not active,the contacts are in theirnormalposition.

    Normally Closed

    Normally OpenCommon

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    58/117

    y

    58

    Relays and Contact s

    When the relay is activated,current passing through therelay coil magnetically

    influences the common"wiper", moving it to theopposite position.

    Normally Closed

    Normally OpeCommon

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    59/117

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    60/117

    y

    60

    In i t iat ingDevices

    SprinklerSystems

    Monitoring

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    61/117

    y

    61

    u Wet-Pipe Spr ink lerSystems use a vane-activated Water Flow Device

    (WFD) sized to the piping.The device reacts to achange in flow pressure of10 psi, which is theequivalent of one sprinkler

    head activating. Retarddevices inhibit falseactivation due to changes inwater supply pressure.

    Fire Spr inkler Systems

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    62/117

    62

    WaterflowDetectors

    Pressure

    Gauges

    TamperSwitches

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    63/117

    63

    u Dry-Pipe Spr inkler: An automatic sprinkler systemwhere all piping contains air under pressure. When a

    sprinkler head opens, the air is released and waterflows into the system and through any opensprinkler heads into the fire. This type of system isused when freezing of water in the pipes is aconcern.

    Fire Spr inkler Systems

    u Dry-Pipe Spr ink ler Systems use apressure switch. The device reacts to achange in pressure due to water fillingthe system.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    64/117

    64

    Sprink ler Monit oring

    u Sprink ler Systems have water feed controlvalves. These control valves shut off the water supplyto the sprinkler system and render it useless. A

    monitoring device should be attached to every criticalcontrol valve in the system, whether it's a gate valve,indicator valve, or butterfly valve. Whenever the valveis shut off, a supervisory alarm signal (as opposed to

    a Fire or Waterflow alarm) is generated.

    u The two most common types of SupervisoryTamper Switches are OSY and PIV.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    65/117

    65

    SprinklerMonitoringOS&Y

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    66/117

    66

    Sprink ler Monit oring

    PIV

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    67/117

    67

    The Systems

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    68/117

    68

    u Conventional (hard wired)u Fixed

    u Programmable

    u Addressable (multiplexed)

    u Intel l igent (analog data transfer)

    Types of

    Fire Alarm Cont rol Panels

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    69/117

    69

    u Simplest type of control unit.

    u Generally, a single circuit board contains powersupply, control, initiating and notification circuitry.

    u Some models use auxiliary circuit boards to performspecial functions.

    u Input/output devices connect to dedicated circuits.

    u Designated outputs occur when initiating signals are

    received.u Limited special functions and capabilities.

    Examples: Fire-Lite MS-2 and MS-4

    Convent ional Hard Wired Syst em

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    70/117

    70

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    71/117

    71

    AddressableSystem

    u Each device (detector, pull station) has a uniquenumber assigned to it called the address for reportingalarms and troubles.

    u Employs a Signaling Line Circuit (SLC) Loop along

    which all addressable input and output devices areconnected to the fire alarm control panel.

    u Addressable devices transmit an electronic message back tothe Control Unit representing their state (Normal, Alarm,Trouble) when polled by the Control Unit.

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    72/117

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    73/117

    73

    Addressable Pull Stat ionsAddressable

    Module

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    74/117

    74

    Typica lSLC

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    75/117

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    76/117

    76

    Soft w are Zoning

    u Floor-Above/Floor Below

    u Elevator Recall

    u Smoke Control

    u Ring-By-Zone

    u Door Locks (Card Access)

    u Cross Zoning

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    77/117

    77

    I nt ell igent System

    uAlways an Addressable System.

    u Processes detailed, analog data from

    detectors about smoke levels.

    u Can provide sensitivity data for each

    detector.

    u Employs Drift Compensation (self calibration)

    in it's detectors.

    Examples: Fire-Lit e MS-9200,MS-9200UD & MS-9600.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    78/117

    78

    Design and Applicat ion

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    79/117

    79

    Design I ssues

    u Device Select ion

    u Photo vs. Ion, line versus spot.

    u What is are the total costs of one type versus another?

    u How does the environment affect device selection?

    u Does the device meet code specifications and code?

    u Placement of Devices (where do you place smokedetectors, pull stations, notification appliances)?

    u Calculations (how do you calculate battery size and

    NAC voltage drops?).u Programming (how will you accomplish your non-

    general alarm events?).

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    80/117

    80

    Spot Detector Placement

    u Total (complete) Coverage includes all rooms,halls, storage areas, basements attics, lofts, spaces

    above suspended ceilings, and other subdivisions

    and accessible spaces as well as the inside of allclosets, elevator shafts, enclosed stairways,dumbwaiter shafts and chutes.

    NFPA 72 2002 Section 5.5.2.1

    Exception - inaccessible areas that DO NOT containcombustible materials do not require smoke detection

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    81/117

    81

    Spot Detector Placement

    u Part ial Coverage calls for smoke detection in allcommon areas and work spaces, such as corridors,

    lobbies, storage rooms, equipment rooms, and other

    tenantless spaces.

    The building owner must understand that a fire

    alarm system may not detect a fire that developswithin any area without smoke detection until thatfire has reached proportions that may seriouslycompromise the safe evacuation of occupants andthe timely notification of fire responders.

    CAUTI ON!

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    82/117

    82

    Spot Detector Placement

    Smoke

    Detector

    30

    21

    Typical area

    of room protection

    Maximumradius of

    protection

    Spot detector

    placement isbased on centralmounting of adetector in a 30 X30 room. No areamay be more than

    21 from thedetector.

    21

    30

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    83/117

    83

    Spot Detector Placement

    SmokeDetector

    10

    21

    Room Maximumradius ofprotection

    Note that in this

    application, twodetectors are notrequired becauseall areas within theroom are within 21feet of the

    detector.

    41

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    84/117

    84

    15 15

    15 15

    30

    30

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    85/117

    85

    Heat Detector SpacingCeiling Height

    (feet)

    Percent (% ) ofList ed Spacing

    0 -10

    10-1212-14

    14-16

    16-18

    18-20

    20-22

    22-24

    24-26

    26-28

    28-30

    100

    9184

    77

    71

    64

    58

    52

    46

    40

    34

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    86/117

    86

    I nit iat ing DevicesManual Fire Alarm Pull Stations

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    87/117

    87

    Manual Fire Alarm Stat ionsMount ing Locat ions

    u Manual fire alarm stations shall be located within5 feet of the exit doorway opening of each floor.

    u Grouped openings over 40 feet in width requirepull stations on either side of the opening.

    u Additional pull station will be installed no morethan 200 linear feet apart.

    u Each manual fire alarm station shall beconspicuous, unobstructed, and accessible, and ofa contrasting color to the background on whichthey are mounted.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    88/117

    88

    Manual Fire Alarm Stat ions

    u NFPA 72 - Mount pull station so that operablepart is 42" to 54" from the floor.

    u ADA Accessibil it y Guidelines

    u Forw ard reach: If access is only from aforward approach, mount 15-48.

    u

    Side reach: If clear space allows a parallelapproach, mount 9-54. If side reach is overan obstruction, use forward reach rules.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    89/117

    89

    Manual Fire Alarm Stat ions

    The height is measured from the floor to the

    point of actuation.

    48 Inches

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    90/117

    90

    Designing w it hNot if icat ion Appliances

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    91/117

    91

    ADA vs NFPA

    u Conflicts exist between ADA and

    NFPA guidelines regardingrequirements for notification

    appliances in fire alarm systems.u If the specifications call for ADA

    compliance, it is a federal law whichmust be obeyed.

    u It is believed that newly-revisedADA Accessibility Guidelines willreference NFPA 72 2002.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    92/117

    92

    Ambient Noise

    u Am bien t No ise Leve l the level of noisearound us, or encircling us. Often referred

    to as background noise.u Decibe ls (dB) Sound pressure is rated in

    decibels, which is a unit for measuringrelative loudness.

    u dBA - A dB scale referenced to theminimum pressure that can be detected bythe human ear.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    93/117

    93

    Ambient Noise

    u 1 dBA (faintest audible sound)

    Remember the hearing test?

    u 50 d BA Typical conversation

    u 80 d BA Alarm Clock

    u 130 dBA (painful ear damage possible).

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    94/117

    94

    Typical Ambient Noise LevelsBusiness Occupan cies 55 dBA

    Edu cat ion al Occupan cies 45 dBA

    I ndust r ia l Occupanc ies 80 dBA

    I nst i t u t iona l Occupanc ies 50 dBA

    Mercant i le Occupan cies 40 dBAPiers and Wat er -Sur round ed St r uc tur es 40 dBA

    Places of Assem bly 55 dBA

    Resident ia l Occupan cies 35 dBA

    St orag e Occupan cies 30 dBA

    Thor ough fares , H igh Densi ty Urban 70 dBA

    Thor oughf ares , Med ium Densi ty Urban 55 dBAThorou ghfares , Rura l and Subur ban 40 dBA

    Tow er Occupancies 35 dBA

    Undergroun d St r uc tur es and

    Windowless Bu i ld ings

    40 dBA

    Vehicles and Vessels 50 dBA

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    95/117

    95

    Operat ing Modes

    u Pub l ic Mode Audible or visible signalingto occupants or inhabitants of the areaprotected by the fire alarm system.

    u Pr iv a te Mode Audibleor visible signaling onlyto those persons directlyconcerned with the

    implementation anddirection of emergencyaction initiation and procedure in the areaprotected by the fire alarm system.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    96/117

    96

    Audible Devices - Publ ic Modeu NFPA: 15 dB above average ambient

    sound level or 5 dB above maximum 60-second sound level, whichever is greater

    (minimum of 75 dBA to a maximum of120 dBA).

    u ADA: I f provided, 15 dB above averageambient sound level or 5 dB above

    maximum 60-second sound level,whichever is greater (maximum of 120dBA).

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    97/117

    97

    Audible Devices - Pr ivate Mode

    u NFPA: Minimum of 45 dBA, maximum of120 dBA, at least 10 dB above average

    ambient sound level or 5 dB abovemaximum 60-second sound level,whichever is greater.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    98/117

    98

    Visual Signaling Appliance

    u Above 105 dbA: When the average ambientsound level is greater than 105 dbA, visualsignaling appliances are required.

    u Indoor concertsu Drop forge shops

    u Printing presses

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    99/117

    99

    Visual SignalingADA Requirement s

    u Americans w it h Disabilit ies Act sets provisionsfor visual appliances:

    u Intensity minimum of 75 cd in non-sleeping areas,and 110 cd in sleeping areas.

    u Lamp shall be a Xenon strobe type or equivalent.

    u The color shall be clear or nominal white.u Pulse duration 0.2 sec. with a 40% duty cycle.

    u Flash Rate 1 - 3 per second (1-3 Hz).

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    100/117

    100

    Wall-Mount ed Appliances

    NFPA

    u Wall mounted devicesshall have their bottoms atheights above the finishedfloor of not less than 80inches, and not greaterthan 96 inches.

    u Maximum separation ofappliances shall not exceed100 feet.

    ADA

    u The appliance shall be placed80 inches above the highestfloor level within the space, or6 inches from the ceiling,whichever is lower.

    u Devices shall be no morethan 50 ft. apart.

    u

    In large areas withoutobstructions 6 ft. above thefloor, devices may be spaced amaximum of 100 feet apart.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    101/117

    101

    Visual Device I nstallat ion

    96"

    80"

    At least 80"

    At

    least

    6"

    NFPA

    ADA 96"

    80"

    At least 80"

    At

    least

    6"

    NFPA

    ADA

    Strobe Horn/Strobe

    At least 90"

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    102/117

    102

    Synchronization

    u Visual Synchron izat ion reduces the effect on those

    who are prone to suffer seizures from Epilepsy.

    u Required when two or more appliances are in thesame field of view.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    103/117

    103

    Synchronization

    u Synchronization is effectedvia two means - a remotemodule or circuitry built intothe fire alarm control panel.

    u Built- in control panelcircuitry is highly desirable.

    u Audib le Synchronizat ion permits theproper sounding of evacuation coding.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    104/117

    104

    Dist r ibuted NACsu Use of a remote power supply can save previous

    voltage in the run from the control panel to thestart of a Notification Appliance Circuit.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    105/117

    105

    Wir ing Standards

    u NFPA 72 establishes standards of

    performance for various wiring styles forInitiation Circuits, Notification ApplianceCircuits and Signaling Line Circuit (SLC)Loop wiring.

    u For Initiating Device Circuits Styles B & D.

    u For Notification Appliance Circuits Styles Y & Z.u For SLC Loops Styles 4,6, & 7.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    106/117

    106

    u 2-wire circuit originates at the control unit,

    interconnects all devices in parallel fashion

    and terminates with an End-Of-LineResistor.

    uA wire break results in a loss of all devices

    past the break.u No branch tapping allowed.

    Style B/ Style Y(Class-B type circui t s)

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    107/117

    107

    Class B-Type Circuit

    FACP

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    108/117

    108

    Style D/ St yle Z(Class-A t ype circui t s)

    u Wiring originates at the control unit,

    interconnects all devices in parallel fashionand returns to the control unit.

    u Return circuit monitors line voltage. Ifvoltage missing, return line will feed

    current to devices from its connections.u No branch tapping allowed.

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    109/117

    109

    Class A-Type Circuit

    FACP

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    110/117

    110

    u 4-wire Smoke Detectors are devices that receivepower from a source other than the InitiatingDevice Circuit.

    u They may be wired inStyle B or St yle D, andare supervised with anend-of-line power

    supervision relay for lossof operating current.

    4 Wire Smoke Detectors

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    111/117

    111

    4 Wire Detectors4-wire Smoke Detectors wired Style B

    InitiatingZone

    4-WireDetectorPower

    IDC (+)

    IDC (-)

    +24VDC

    Common

    UL Listed

    PowerSupervisoryRelay

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    112/117

    112

    Questions?

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    113/117

    113

    Thank You

    for At t ending!

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    114/117

    114

    Terminologyu FACP - Fire Alarm Cont rol Panel.

    u FACU - Fire Alarm Cont rol Unit .

    u FCC - Federal Communicat ions Commission

    u UL - Underw rit ers Laboratories

    u NFPA - National Fire Prot ect ion Agency.u AHJ, LAHJ - Aut hori t y Having Jur isdict ion, Local AHJ

    u ADAAG - Americans w it h Disabili t ies Act Accessibi lit yGuidelines.

    u PoC - Products of Combustion

    u LED - Light Emit t ing Diode

    u I DC - I nit iating Device Circuit

    u NAC - Notif icat ion Appliance Circuit

    u ELR, EOL - End of Line Resistor

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    115/117

    115

    Terminology

    u NEC - Nat ional Electr ical Code (NFPA 70)

    u NEMA - Nat ional Elect rical Manufacturing Association

    u EI A - Elect ronics I ndustry Association

    u Cd - Candela

    u dB, dBA - Decibelsu FWR - Full Wave Rect if ied

    u ANSI - American National Standards I nst it ute

    u PI V - Post I ndicator Valve

    u

    OS&Y - Out side Stem and Yoke Valvesu SFPE - Society f or Fire Prot ect ion Engineers

    u Shall - I ndicates a mandatory requirement

    u Should - I ndicates a recommendation or advisement

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    116/117

    116

    References

    u NFPA 70 - National Electrical Code

    u NFPA 72 - National Fire Alarm Code

    u NFPA 101 - Life Safety Code

    u National Electrical Code Handbook, NFPA

    u Life Safety Code Handbook, NFPA

    u Fire Protection Handbook, NFPA

    u Fire Alarm Signaling Systems, NFPA

    I nt ro t o Convent ional Fire Alarm Systems

  • 8/2/2019 Fire Alarm Systems El Benaa Com

    117/117

    Addi t ional References

    u Guide for Proper Use of System Smoke Detectors,System Sensor.

    u Guide for Proper Use of Smoke Detectors in Duct

    Applications, System Sensor.u Guide for Proper Use of Projected Beam Smoke

    Detectors, System Sensor.

    u Strobe Compliance Reference Guide, System

    Sensor.