fire - egress

Upload: dhruv-gupta

Post on 04-Jun-2018

234 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/13/2019 Fire - Egress

    1/28

    CHAPTER 1. Literature review

  • 8/13/2019 Fire - Egress

    2/28

  • 8/13/2019 Fire - Egress

    3/28

    The variables that help to determine the most appropriate technology of life safety for a

    particular situation and about escape route definitions and its components & principles of design

    is briefly discussed in the book A complete guide to Fire & Buildings (ERIC.W.Marchant,

    1972). He discusses on some aspects of building design and their influence on the rescue of

    people in building fires and of the main techniques of rescue. Some case studies are included to

    illustrate some of the dangers inherent in common types of buildings. Author brings into light,

    more concepts of importance to life safety, like smoke load and enabling of smoke control

    techniques and some of the problems of smoke control in tall buildings are also discussed.

    1.2.2 Identification of means of egress componentsBukowski.R.W.(2008), documented current regulatory requirements for means of

    egress in fires, their origins and scientific basis, and the approaches used in US and in other

    countries, along with a review of the international code requirements for egress stairs. Author

    also explains on the scientific study of exit width based on ergonomics and the studies on the

    earliest of stair geometry. The paper questions the adequacy of the basic 22 inch dimensionsbeing used, owing to the increasing size and weight of a typical person especially in US. It also

    explains studies in tread geometry conducted by an architect in France named Francois Blondel

    and also reviews international code requirements for egress stairs. Where stairs are the primary

    means of vertical egress in fires and other emergencies such stairs shall be a minimum width of

    1400 mm (56 in). Where protected elevators are provided as the primary means of vertical egress

    in fires and other emergencies stairs shall be a minimum width of 1100 mm (44 in).

    Bukowski.R.W.(2008), in his paper throws light to the importance of incorporation of refuge

    floors in tall buildings in Asia. Horizontal transfer corridors designed as means of egress

    components shall be provided every 25 floors (generally on mechanical floors) to link all egressstairs and to provide the ability to safely move between stairs.

    Shimshoni 2007( cited in Collier.P.C.R, 2008) study shows that exit stairways wider than both

    the required 1120 mm and 1420 mm proposed for the NFPA documents are already being

    designed into major high-rise buildings. Designers are cautioned however, not to make the clear

    width between handrails larger than 1525 mm as extensive crowd use puts people in the middle

    of the stair beyond the reach of a handrail. Thus, 1725 mm is the largest nominal width

    recommended for exit stairways. Wide stairs of 1725 mm provide more people flow per width

    than narrower stairs. For example, a 1420 mm nominal width stair performs about 38% more

    effectivelyfor flowthan a traditional 1120 mm nominal width stair even though the former is

    only 27% wider (Collier.P.C.R, 2008).

    1.2.3 Principles of evacuation time and travel distanceCollier.P.C.R.(2008) in his study has demonstrated that with the changed demographics of the

    worldwide population, people have increased in size considerably in the period since provisions

    for egress and minimum exit widths were implemented for buildings and assembly areas on the

    basis of contemporary population mobility studies. The current situation is that the existing

  • 8/13/2019 Fire - Egress

    4/28

    egress provisions are unlikely to deliver the evacuation times required by fire safety designs.

    Suggested means of correcting this potentially serious shortfall in egress capacity go beyond the

    obvious solution of simply increasing exit widths which, apart from new buildings, would be

    considered uneconomic and impractical. His study reviews the existing minimum exit width

    requirements in the New Zealand Building Code (NZBC) Compliance Document C/AS1 (DBH

    2005) prompted by a recent paper by Fruin and Pauls (2007) expressing concern about current

    practices. The study focuses on cultural, anthropometric and mobility differences internationally,

    and with time the impact on the specification of minimum exit widths needed for emergency

    egress.

    Life safety features (United States Fire administration) describes the emergency evacuation plans

    and the purpose of it. The evacuation plan is tied directly to fire drills, which must occur in such

    occupancy on a regular basis; the building manager or owner should keep records to show

    compliance. Many fire departments hold open houses at their stations some time during National

    Fire Prevention Week, which is an excellent time to provide home fire safety information, but it

    takes place only once a year; fire safety must be presented on a continuing, year-round basis.

    Whereas Schanchenmayr.M.P., Quade.P.B & Douglas, (sep.1998) in their paper studies the

    evacuation requirements for train ways alone, addresses the train way egress requirements and

    provide recommendations and general guidelines for the application of the NFPA 130 egress

    element for a broader range of transit systems and modes, including commuter rail and light rail

    transit stations.

    1.2.4 Role of elevators in modern means of egressBukowski.R.W.(2008), emphasizes on the use of Protected Occupant Egress Elevators Where

    required, all elevators except any designated fire service elevator(s) shall be designed andarranged to permit their safe use for occupant evacuation. These occupant elevators shall be

    powered by normal and emergency power, with both power and control wiring protected by fire

    resistant construction at least equal to the fire resistance requirement applicable to the primary

    structural frame. Occupant egress elevators shall operate in a hoistway protected from the

    adverse effects of water and opening into a protected lobby on each floor that serves as an area of

    refuge while awaiting the elevator.

    Bukowski, 2007( as cited in Collier.P.C.R.,2008) wrote in response to the potential need for

    more timely evacuation of occupants in tall buildings that new provisions allowing the use of

    elevators in certain situations prior to Phase I Emergency Recall Operation (as mandated by the

    Firefighters Emergency Operation provision of ASME A17.1 Safety Code for Elevators andEscalators) be put forward. Elevators remain usable after initiation of the building fire alarm

    system, provided that the elevators have not been recalled upon detection of smoke in the

    elevator lobbies, machine room or hoist ways. In such situations the elevators remain operable

    and are available for occupant evacuation. Similarly a new standard is proposed (ISO 2006) that

    suggests new technologies and strategies for evacuations using elevators coupled with means

    of providing information to people (evacuees) to make correct decisions in their use.

  • 8/13/2019 Fire - Egress

    5/28

    1.2.5 Studies on density and flow rateRoytman.M.Ya, (1969) in his book describes about the distinctive features of the movement of

    people during emergency evacuation and stages of evacuation, with brief descriptions on various

    terms & standards to be followed in Evacuation exits and routes. Approximate methods for

    calculating the permissible and actual evacuation times and building design requirements for safeevacuation of people are described. According to him the parameters characteristic of the

    movement of people include streams of people, width of streams, densities of streams of people,

    length of stride, speed of motion and traffic clearing capacity of an exit.

    Bukowski.R.W (2008), in his paper says that 1935 NBS report clearly stated the correlation

    between width and flow. The committee (Bukowski.R.W.,2008)agreed that, rates of 45

    persons per 22-inch unit per minute for travel down stairways, and 60 persons per 22-inch unit

    per minute through doorways, which had been in use on the basis of earlier observations, were

    sufficiently confirmed to warrant their retention in connection with the requirements under

    development. Paper also describes about effective space requirement and the concepts ofeffective width of a stair, as discussed by Pauls and Fruin in their publishing.

    Fruin and Pauls (2007) draw attention to concerns about current practices and methods of

    calculating egress capacity. In particular, they suggested that recent and ongoing demographic

    changes in the population warrant reconsideration of the long accepted and established beliefs,

    data and formulae that are the basis for design requirements in codes, standards and handbooks

    which are used for performance predictions affecting life safety in existing and proposed

    facilities. The basis of the established calculation methods subject to change are:

    Human body mass and sizes have increased significantly since the 1960s. The original basis used for determining the movement characteristics of the general

    population is not universally applicable. Studies of the movement of relatively fit

    commuter people that were used to measure egress characteristics may not be applicable

    to the general population who may not, on average, be so physically able.

    1.2.6 Methods for analysis of means of egressAccording to Bukowski.R.W.(2008), in the U.S., Australia and Japan, the design of egress

    systems are based on the population of the largest, single floor. In U.K., Spain, and China the

    number of floors served by the stair impacts the total number of people served by a stair of a

    given width. Yet in any performance analysis of an egress system in these or other countries,

    (Design and Construction of Building exits, 1935)regulators require a timed egress analysis to

    estimate Required Safe Egress Time (RSET) which is compared against Available Safe Egress

    Time (ASET). ASET is generally determined by fire modeling to estimate conditions in the

    egress path that might lead to injury or death.

  • 8/13/2019 Fire - Egress

    6/28

    Averill.J.D., Reneke.P. and Peacock.R.D, (2007), study identifies sources of uncertainty in

    RSET (required safe egress time) calculations, with focus on data and modeling. A model for

    efficiently calculating the range of egress solutions for a particular design is presented. The

    importance of the two central concepts of performance-based design, ASET (available safe

    egress time) and RSET (required safe egress time to achieve performance objectives. The

    limitations in quantity and quality in existing data sets for model inputs are validated. The paper

    sets out definite explanations for egress model theory with examples. The paper brings out three

    recommendations for future research. First, future data collections and model inputs should

    utilize distributions. Second, future data collections should focus on emergency evacuation data

    rather than fire drill data. Finally, modeling output should utilize cumulative distribution

    functions to visualize the range of egress solutions. (Bukowski.R.W., 2008)

    1.2.7 Occupant load and its calculationsBukowski.R.W.(2008), in his studies explains why the US designs exits for capacity and why

    the capacity is based on the population of a single floor. The building regulations from variouscountries and the methods used for egress is summarized and the factors influencing

    characteristics of egress stair design like minimum number of egress stairs provided, maximum

    travel distance to a stair, width of doors and passageways, interior finish, headroom, handrails etc

    are also discussed.

    Muha.T, 2012, in his research project Evaluating Occupant Load Factors for Business

    Operations recommends i) an increase in the value of the occupant load factor for general

    business use in the Life Safety Code from 100 ft2/person to 150ft2/person, and ii) a new

    category of business use in the form of high density business use spaces, such as call centers.

    This study investigates the origins of the 100ft2/person factor, previous occupant load studies,

    changes in office space planning and use, availability of office furnishings, and current officeoccupant load preferences, then recommends alternate occupant load factors and business use

    categories.

    Life safety features, discusses on the factors that determine occupant load, and how occupant

    load will determine the number of exits required from a room or building and their total width.

    Paper also explains on the method of calculating net and gross floor area for buildings with

    examples and also cited occupant load calculation examples.

    1.2.8

    Special requirements for healthcare and mass transit terminalsApplication Guidelines for the Egress Element of the Fire Protection Standard for Fixed

    Guideway Transit Systems (Schanchenmayr.M.P., Quade.P.B & Douglas, sep.1998)reviews The

    theoretical concepts that underlie the egress requirements supports a more enlightened

    application of the NFPA 130 Standard, particularly in non-conventional settings. The NFPA 130

    egress element is placed in a broader context in order to illustrate the overall intent of the egress

    requirements as well as their consistency with, and departure from, model building codes.

  • 8/13/2019 Fire - Egress

    7/28

    Schanchenmayr.M.P., Quade.P.B & Douglas, (sep.1998) throws light into the following

    concerns:

    Insufficient industry understanding of NFPA 130 emergency egress element. The definitions, instructions, and sample calculations published with the NFPA 130

    Standard do not adequately guide practitioners and have led to inconsistent application of

    the NFPA 130 egress element, potentially leading to overly conservative design solutions

    or to inadequate designs that are extremely costly to remedy retroactively.

    Although the NFPA 130 Standard technically addresses only rail rapid transit modes anddoes not cover requirements for ... passenger railroad systems including those which

    provide commuter services. Despite this widespread practice, no guidance is offered for

    the application of the NFPA 130 Standard for non-rapid transit systems and facilities

    The NFPA 130 Standard contains minimum design criteria with regard to emergencyegress only; however, in the absence of standard specifications for transit stations,

    designers frequently view the NFPA 130 requirements as the principal design guidelines

    for transit stations. This application often occurs without sufficient understanding of the

    relationship between the NFPA 130 Standard and the underlying requirements of the

    NFPA 101 Code.

    The book provides an overview and detailed technical discussion of the NFPA 130 egress

    requirements as they apply to transit stations, evacuation requirements for train ways, application

    guidelines and sample calculations.

    1.2.9 Social behaviors in emergency situationsChu and Law (2012), in their paper A Computational Framework Incorporating Human

    Behaviors for Egress Simulation talks about a comprehensive review of various social theories

    about crowd behaviors. Social scientists and disaster management researchers have been

    studying human behaviors in emergency situations and have developed a variety of theories

    about crowd behaviors in emergency situations. Examples of prevalent theories on crowd

    behaviors include the panic theory (Le Bon, 1960), the decision-making theory (Mintz, 1951),

    the normative theory (Aguirre et al., 2011; McPhail, 1991; Turner and Killian, 1987), the

    affiliative theory (Mawson, 2005; Sime, 1983), and the place script theory (Donald and Canter,

    1990). Earlier theories in crowd behavior suggest that people tend to behave individually and

    show non-adaptive behaviors in dangerous situations. For example, the panic theory suggests

    that people become panicked in an emergency situation and act irrationally. In contrast, the

    decision-making theory argues that people act rationally to achieve a better outcome in the

    situation. Recent theories, on the other hand, emphasize the sociality of the crowd (such as pre

  • 8/13/2019 Fire - Egress

    8/28

    existing social relationships or emerging identity during an emergency situation) in explaining

    the occupants reactions in past accidents.

    Different social theories explain human behaviors in emergencies using different mechanisms

    and variables. In order to systematically study different social theories and incorporate them

    into a computational framework, we classify the theories into three behavior categories; namely,

    individual, group, and crowd. As is evidenced from the selected prevailing social theories on

    human behaviors, social characteristics of individuals play an important role in determining their

    behaviors during emergencies. It is conjectured that human behaviors in egress is influenced at

    three levels: individual experience, social group, and crowd interactions. The staged

    representation of social effects forms the basis in the design of our egress simulation

    framework.(Chu and Law, 2012)

    Hoskin, (2004) investigated emergency egress considerations of stadia by examining occupant

    characteristics and discussing how effective crowd management can be used to improve

    evacuation procedures in his paper Crowd characteristics and egress at Stadia. The findings are

    based on recent research on fire protection and evacuation procedures of stadia venues primarily

    in New Zealand. To the authors knowledge the research that this paper is based on is the sum

    total of high density crowd egress studies performed on the New Zealand populous, in order to

    test the appropriateness of recommended occupant densities used to calculate egress capacities

    for such venues in New Zealand. Hoskin also discusses about the potential components of a

    stadium evacuation that differs from normal egress.

    Safe egress is one of the key design issues identified by facility planners, manager and

    inspectors. Computational tools are now available for the simulation and design of emergency

    evacuation and egress. However, these tools rely heavily on assumptions about human individual

    and social behaviors, which have been found to be oversimplified, inconsistent and even

    incorrect. Furthermore, the behaviors are usually incorporated into the computational model in

    an ad hoc manner. Xiaoshan.P et al., (2004) presents a framework for studying human and social

    behavior from the perspectives of human decision-making and social interaction and to

    incorporate such behavior systematically in a dynamic computational model suitable for

    emergency egress analysis through his paper on Human and Social Behavior in Computational

    Modeling and Analysis of Egress.

    Xiaoshan.P et al., (2004) , in their study discusses briefly on the topics - human and social

    behavior and crowd dynamics, Non-adaptive crowd behavior (According to the author existing

    theories on crowd behavior in emergency situation can be classified into three basic categories:

    (1) panic , (2) decision-making , and (3) urgency levels. ), Computational models etc. According

    to the author Social behaviors are complex phenomena emerged from the interactions among a

    group of autonomous agents. The paper describes that the prototype system can demonstrate

  • 8/13/2019 Fire - Egress

    9/28

    social emergent phenomena including competitive, queuing, and herding behaviors, and bi-

    directional crowd flow.

    1.2.10 Egress simulation models and human behavior modelingGrosshandler et al., 2005 (As mentioned in Chu and Law (2012)) describes the system

    framework and the features currently incorporated in the prototype, through implementing

    several well-studied social behaviors in the prototype model, and study the effects of such social

    behaviors on an evacuation scenario based on the historical fire accident at the Station Nightclub

    in Warwick, Rhode Island.

    In their paper Chu and Law (2012), describes the basic framework and the implementation of

    several social behaviors, which are based on recent social science studies about human response

    in emergency situations. Simulation results from the prototype reveals that social behaviors

    exhibited by the evacuating crowd can lead to changes in the overall egress time and pattern. By

    representing the virtual agents and the environment specific to evacuation situation, the researchaddresses the issues in incorporating human and social behaviors in egress simulation.

    In this paper, Chu and Law have described an ongoing research effort in developing a modular

    and flexible computational framework to incorporate human and social behavioral models for

    egress simulations. In the following, they discuss the results for possible effects of social

    behaviors on evacuation and then an overall framework for the multi-agent based simulation

    system. The three most common approaches based on the systems virtual representation of the

    building environment and the occupants are the particle systems, cellular automata and agent-

    based systems.

    Due to the high variability of human behaviors in different situations, a single

    behavioral theory may not be sufficient to explain the response of people in differentemergency scenarios. A flexible simulation platform, which can account for various

    social theories in different emergency scenarios, is therefore desirable. The ability to

    model social behavioral theories in a computational program not only provides more

    realistic simulation results, but also provides a means to test and validate the

    corresponding behavioral theories.(Chu and Law, 2012)

    Xiaoshan.P et al., (2004) through their paper, presented a crowd simulation model that takes

    into account human and social behavior. According to them the three main reasons for

    developing computer simulation for crowd behaviors: 1) to test scientific theories and

    hypotheses; 2) to test design strategies; 3) to create phenomena about which to theorize. Each

    crowd setting (i.e., crowd attributes and physical environment) is unique. A full understanding of

    non adaptive crowd behaviors normally requires exposing real people to the specific

    environment for obtaining empirical data, which is difficult since such environments are often

    dangerous in nature. In addition to study crowd behavior based on observations and historical

    records, computer simulation is a useful alternative that can provide valuable information to

    evaluate a design, to help planning process, and for dealing with emergencies.

  • 8/13/2019 Fire - Egress

    10/28

    1.3 SummaryThis chapter gives a list of literature that is available and will be used in the seminar. The

    literature has been divided into various topics and in each topic, the corresponding literatureavailable have been discussed.

    The salient points that have been covered in literature, is further discussed on each chapters and

    its sub sections. The study on literature has helped in formulating survey and in supporting the

    case studies.

  • 8/13/2019 Fire - Egress

    11/28

    CHAPTER 2. Components of means of egress and their planning principles2.1 Means of egress

    Means of egress is a continuous and unobstructed way of travel from any point in a building or

    structure to a place of comparative safety.An exit may be a doorway; corridor, passageway(s) to

    an internal staircase, or external staircase, or to a VERANDAH or terrace(s), which have access to

    the street, or to the roof of a building or a refuge area. An exit may also include a horizontal exit

    leading to an adjoining building at the same level. Lifts and escalators shall not be considered as

    exits. Every exit, exit access or exit discharge shall be continuously maintained free of all

    obstructions or impediments to full use in the case of fire or other emergency.

    2.1.1

    Components: Exit, Exit access, Exit door, Exit dischargeExitis that portion of a means of egress that is separated from all other spaces of a building or

    structure by construction or equipment as required to provide a protected way of travel to the exit

    discharge. A Horizontal Exit is a way of passage from one building to an area of refuge in

    another building on approximately the same level, or a way of passage through or around a fire

    barrier to an area of refuge on approximately the same level in the same building that affords

    safety from fire and smoke originating from the area of incidence and areas communicating

    therewith.

    Exit Access isthat portion of a means of egress that leads to an exit and Exit Dischargeis that

    portion of a means of egress between the termination of an exit and a public way. A door or

    access point along the path of egress travel from an occupied room, area or space where the path

    of egress enters an intervening room, corridor, unenclosed exit access stair or unenclosed exit

    access ramp, is termed as Exit access door.

    2.1.2 Common path of travelThe common path of egress travel, or CPET, is defined in the IBC as: That portion of exit

    access which the occupants are required to traverse before two separate and distinct paths of

    egress travel to two exits are available. Paths that merge are common paths of travel. Common

    paths of egress travel shall be included within the permitted travel distance.

  • 8/13/2019 Fire - Egress

    12/28

    Common Path of Travel is that portion of exit access that must be traversed before two separate

    and distinct paths of travel to two exits are available. A common path of travel shall be permitted

    for the first 20 ft (6100 mm) from any point where the common path serves any number of

    occupants, and for the first 75 ft (23 m) from any point where the common path serves not more

    than 50 occupants.Dead-end corridors shall not exceed 20 ft (6100 mm). Common path of travel

    shall not exceed 100 ft (30 m) in a building protected throughout by an approved, supervised

    automatic sprinkler system. Common path of travel shall not exceed 75 ft (23 m) in a building

    not protected throughout by an approved, supervised automatic sprinkler system.[NFPA]

    2.1.1 Common path of egress travel

    2.1.3 Travel distanceThe distance to be travelled from any point in a building to a protected escape route, external

    escape route or final exit (NFPA). Although not specifically defined in the International Building

    Code (IBC), travel distance is described in Section 1016.1 (2009 IBC) as, the maximum length

    of exit access travel, measured from the most remote point within a story along the natural and

    unobstructed path of egress travel to an exterior exit door at the level of exit discharge, an

    entrance to a vertical exit enclosure, an exit passageway, a horizontal exit, an exterior exit

    stairway or an exterior exit ramp, [which] shall not exceed the distances given in Table 1016.1.

    (Ronald L. Geren, 2009)

    In essence, it is the total distance an occupant must cover to reach an exit as defined by the IBC

    (See Figure). The concern with travel distance is to ensure that occupants can reach an exterior

  • 8/13/2019 Fire - Egress

    13/28

    door or protected exit enclosure without having to take an extremely long path to get there, thus

    reducing the occupants exposure to a potential hazard.(Ronald L. Geren, 2009)

    2.1.2 Determining travel distance

    Table 1016.1 provides the limitations on travel distance based on occupancy and the installation

    of a sprinkler system. For most non-sprinklered occupancy groups, this distance is 200 feet. With

    a sprinkler system installed, this distance increases to 250 feet, but for B occupancies, it

    increases to 300 feet. Non-sprinklered Groups F-2, S- 2, and U are limited to 300 feet (400 feet

    when sprinklered). Group I and H occupancies have various travel distances listed, but are

    limited to only sprinklered buildings, since these occupancies are required to be sprinklered.

    (Ronald L. Geren, 2009)

    According to NBC, Exits shall be so located that the travel, distance on the floor shall not exceed

    the distance given in Table 22. The travel distance to an exit from the dead end of a corridor shall

    not exceed half the distance specified in Table 22, except in assembly and institutional

    occupancies in which case it shall not exceed 6 m. Whenever more than one exit is required for

    any room space or floor of a building, exits shall be placed as remote from each other as possible

    and shall be arranged to provide direct access in separate directions from any point in the area

    served.

  • 8/13/2019 Fire - Egress

    14/28

    NFPA 101 states, the travel distance to an exit shall be measured on the floor or other walking

    surface as follows:

    (1) Along the centerline of the natural path of travel, starting from the most remote point subject

    to occupancy

    (2) Curving around any corners or obstructions, with a 12 in. (305 mm) clearance there from

    (3) Terminating at one of the following:

    (a) Center of the doorway

    (b) Other point at which the exit begins

    (c) Smoke barrier in an existing detention and correctional occupancy

  • 8/13/2019 Fire - Egress

    15/28

    2.2 Minimum width & Clear widthAccording to NFPA, The width of an exit passageway shall be sized to accommodate the

    aggregate required capacity of all exits that discharge through it, unless one of the following

    conditions applies, Where an exit passageway serves occupants of the level of exit discharge as

    well as other stories, the capacity shall not be required to be aggregated.

    In new construction, the minimum width of any exit passageway into which an exit stair

    discharges, or that serves as a horizontal transfer within an exit stair system, shall meet the

    following criteria:

    (1) The minimum width of the exit passageway shall be not less than two-thirds of the width of

    the exit stair.

    (2) Where stairs are credited with egress capacity in accordance with 7.3.3.2, the exit

    passageway width shall be sized to accommodate the same capacity as the stair, with such

    capacity determined by use of the capacity factors in Table 7.3.3.1.

    NBC, states that all required exits that serve as egress from hospital or infirmary sections shall be

    not less than 2 m in clear width including patient bedroom doors to permit transportation of

    patients on beds, litters, or mattresses. The minimum width of corridors serving patients

    bedrooms in buildings shall be 2400 mm. For detailed information on recommendations for

    buildings and facilities for the physically handicapped, reference may be made to good practice

    2.3 Staircases2.3.1 Staircase construction

    All buildings, which are 15 m in height or above, and all buildings used as educational,

    assembly, institutional, industrial, storage, and hazardous occupancies and mixed occupancies

    with any of the aforesaid occupancies, having area more than 500 m2 on each floor shall have a

    minimum of two staircases. They shall be of enclosed type; at least one of them shall be on

    external walls of buildings and shall open directly to the exterior, interior open space or to an

    open place of safety. Further, the provision or otherwise of alternative staircases shall be subject

    to the requirements of travel distance being complied with.

  • 8/13/2019 Fire - Egress

    16/28

    2.3.1.1 Internal staircasesInternal stairs shall be constructed as a self contained unit with an external wall of the building

    constituting at least one of its sides and shall be completely enclosed. A staircase shall not be

    arranged round a lift shaft.Hollow combustible construction shall not be permitted.

    2.3.1.2 External staircasesAn external staircase is desirable to be provided for high rise buildings. External stairs, when

    provided shall always be kept in sound operable conditions. All external stairs shall be directly

    connected to the ground. The route to the external stairs shall be free of obstructions at all times.

    Entrance to the external stairs shall be separate and remote from the internal staircase. No

    external staircase, used as a fire escape, shall be inclined at an angle greater than 45 from the

    horizontal.

    2.3.1.3 Codal provisions on staircasesN

    o: FEATURES INTERNAL STAIRCASE EXTERNAL STAIRCASE

    1Material of

    construction

    Shall be constructed ofnoncombustible materials

    throughout.

    No combustible material shall be

    used for decoration/wall panelingin the staircase.

    The external stairs shall be constructed

    of noncombustible materials, and any

    doorway leading to it shall have therequired fire resistance.

    Unprotected steel frame staircase will

    not be

    accepted as means of escape. However,steel staircase

    in an enclosed fire rated compartment

    of 2 h will be accepted as means of

    escape.

    2 Minimum width

    External stairs shall have straight flight

    not less

    than 1250 mm wideThe use of spiral staircase shall be

    limited to low occupant load and to abuilding not exceeding 9 m

    in height. A spiral stair case shall be not

    less than 1500 mm in diameter and shall

    be designed to give adequateheadroom.

  • 8/13/2019 Fire - Egress

    17/28

    3 Stair dimensions

    The minimum width of treadwithout nosing

    shall be 250 mm for internalstaircase of residential buildings.

    This shall be 300 mm for

    assembly, hotels, educational,institutional, business and otherbuildings. The treads shall be

    constructed and maintained in a

    manner to prevent slipping.

    External stairs shall have 250 mm

    treads

    The maximum height of riser shall

    be 190 mmfor residential buildings and 150

    mm for other buildings and the

    number shall be limited to 15 per

    flight.

    The maximum height of risers shall berisers

    not more than 190 mm. The number of

    risers shall be

    limited to 15 per flight.

    5 Mid- Landing

    The minimum headroom in apassage underthe landing of a staircase and under

    the staircase shall be 2.2 m.

    All landings of floor shall havefloor indicating boards prominently

    indicating the number of floor as

    per bye-laws.

    6 Handrail

    Handrails shall be provided at a

    height of

    1000 mm to be measured from the

    base of the middle of the treads to

    the top of the handrails.Balusters/railing shall be provided

    such that the width of staircasedoes not reduce

    Handrails shall be of a height not less

    than

    1000 mm and not exceeding 1200 mm.

    There shallbe provisions of balusters with

    maximum gap of150 mm.

    8Openings into

    staircases

    Care shall be taken to ensure that nowall

    opening or window opens onto or close

    to an external

  • 8/13/2019 Fire - Egress

    18/28

    stairs.

    9

    Entry to staircase (

    Door , Direction of

    opening, Entrancelobby)

    No living space, store or other firerisk shall

    open directly into the staircase orstaircases.

    Entrance to the external stairs shall be

    separateand remote from the internal staircase.

    External exit door of staircase

    enclosure atground level shall opendirectly to the openspaces or

    through a large lobby, if necessary.

    The main and external staircasesshall be

    continuous from ground floor to

    the terracelevel.

    2.3.2 Pressurization of staircasesThough in normal building design, compartmentation plays a vital part in limiting the spread of

    fire, smoke will readily spread to adjacent spaces through the various leakage openings in the

    compartment enclosure, such as cracks, openings around pipes ducts, airflow grills and doors, as

    perfect sealing of all these openings is not possible. It is smoke and toxic gases, rather than

    flame, that will initially obstruct the free movement of occupants of the building through the

    means of escape (escape routes). Hence the exclusion of smoke and toxic gases from the

    protected routes is of great importance.

    Pressurization is a method adopted for protected escape routes against ingress of smoke,

    especially in high-rise buildings. In pressurization, air is injected into the staircases, lobbies or

    corridors, to raise their pressure slightly above the pressure in adjacent parts of the building. As a

    result, ingress of smoke or toxic gases into the escape routes will be prevented. The

    pressurization of staircases shall be adopted for high rise buildings and building having mixed

    occupancy/ multiplexes having covered area more than 500 m2. The pressure difference for

    staircases shall be as under:

  • 8/13/2019 Fire - Egress

    19/28

    If possible, the same levels shall be used for lobbies and corridors, but levels slightly lower may

    be used for these spaces if desired. The difference in pressurization levels between staircase and

    lobbies (or corridors) shall not be greater than 5 Pa. Pressurization system may be of two types:

    a) Single-stage, designed for operation only in the event of an emergency, and

    b) Two-stage, where normally a level of pressurization is maintained in the protected escape

    routes and an increased level of pressurization can be brought into operation in an emergency.

    2.4 RampRamps shall comply with all the applicable requirements for stairways regarding enclosure,

    capacity and limiting dimensions except for special uses and occupancies. The slope of a ramp

    shall not exceed 1 in 10. In certain cases steeper slopes maybe permitted but in no case greater

    than 1 in 8. For all slopes exceeding 1 in 10 and wherever the use is such as to involve danger of

    slipping, the ramp shall be surfaced with approved non-slipping material.

    2.5 Fire TowerFire towers are the preferred type of escape route for storeyed buildings and these shall be

    considered as the safest route for escape. Their number, location and size shall depend on the

    building concerned, and its associated escape routes. In high rise buildings with over 8 storeys or

    24 m in height, at least one required means of egress shall preferably be a fire tower. The fire

    towers shall be constructed of walls with a 2 h fire resistance rating without openings other than

    the exit doorways, with platforms, landings and balconies having the same fire-resistance rating.

  • 8/13/2019 Fire - Egress

    20/28

    2.6 Occupant loadOccupant Load is for determining the exits required, the number of persons within any floor area

    or the occupant load shall be based on the actual number of occupants, but in no case less than

    that specified in Table 20, NBC. Occupant load in dormitory portions of homes for the aged,

    orphanages, insane asylums, etc, where sleeping accommodation is provided, shall be calculated

    at not less than 7.5 m2 gross floor area/person. The gross floor area shall include, in addition to

    the main assembly room or space, any occupied connecting room or space in the same storey or

    in the storeys above or below, where entrance is common to such rooms and spaces and they are

    Available for use by the occupants of the assembly place. No deductions shall be made in the

    gross area for corridors, closets or other sub-divisions; the area shall include all space serving the

    particular assembly occupancy.

  • 8/13/2019 Fire - Egress

    21/28

    2.7 Occupant load of mezzanine floorThe occupant load of a mezzanine floor discharging to a floor below shall be added to that floor

    occupancy and the capacity of the exits shall be designed for the total occupancy load thus

    established.

    2.8 Number of occupants per unit widthOccupants per unit exit width shall be in accordance with Table 21, NBC 2005

  • 8/13/2019 Fire - Egress

    22/28

    2.9 Capacity of egress elements2.9.1 Capacity of exit door

    Size of the exit door of exit way should be calculated accordingly keeping in view the travel

    distance as per Table 22 of NBC.

    2.9.2 Capacity of exit accessThe unit of exit width, used to measure the capacity of any exit, shall be 500 mm. A clear width

    of 250 mm shall be counted as an additional half unit. Clear widths less than 250 mm shall not be

    counted for exit width. Occupants per unit exit width shall be in accordance with Table 21 of

    NBC

    2.9.3 Capacity of exit dischargeDischarge through Areas on Level of Exit Discharge shall not more than 50 percent of the

    required number of exits, and not more than 50 percent of the required egress capacity, shall

    discharge through areas on the level of exit discharge, unless otherwise permitted in 7.7.2.1 and

    7.7.2.2 and provided that the criteria of 7.7.2.3 through 7.7.2.7 also are met.

    7.7.2.1 One hundred percent of the exits shall be permitted to discharge through areas on the

    level of exit discharge in detention and correctional occupancies

    7.7.2.2 In existing buildings, the 50 percent limit on egress capacity shall not apply if the 50

    percent limit on the required number of exits is met.

    7.7.2.3 The discharge specified in 7.7.2 shall lead to a free and unobstructed way to the exterior

    of the building, and such way shall be readily visible and identifiable from the point of discharge

    from the exit.

    7.7.2.4 The level of discharge shall be protected throughout by an approved automatic sprinkler

    system in accordance with, or the portion of the level of discharge used for discharge shall be

    protected by an approved automatic sprinkler system in accordance with Section 9.7 and shall be

    separated from the non-sprinklered portion of the floor by a fire resistance rating meeting the

    requirements for the enclosure of exits.

  • 8/13/2019 Fire - Egress

    23/28

    The requirement of 7.7.2.4 shall not apply where the discharge area is a vestibule or foyer that

    meets all of the following criteria:

    (1) The depth from the exterior of the building shall be not more than 10 ft (3050 mm), and the

    length shall be not more than 30 ft (9140 mm).

    (2) The foyer shall be separated from the remainder of the level of discharge by construction

    providing protection not less than the equivalent of wired glass in steel frames.

    (3) The foyer shall serve only as means of egress and shall include an exit directly to the outside.

    2.9.4 Capacity of staircasesThe effective capacity of stairways has been shown by research to be proportional to the

    effective width of the stairway, which is the nominal width minus 12 in. (305 mm). This

    phenomenon, and the supporting research, were described in the chapter, Movement of People,

    in the first, second, and third editions of the SFPE Handbook of Fire Protection Engineering and

    was also addressed in Appendix D of the 1985 edition of NFPA 101, among several other

    publications. In 1988, this appendix was moved to form Chapter 2 of the 1988 edition of NFPA

    101M, Alternative Approaches to Life Safety. (This document was later designated as NFPA

    101A, Guide on Alternative Approaches to Life Safety, and this chapter remained in thedocument through the 1998 edition.) In essence, the effective width phenomenon recognizes that

    there is an edge or boundary effect at the sides of a circulation path. It has been best examined in

    relation to stairway width, where the edge effect was estimated to be 6 in. (150 mm) on each

    side, but a similar phenomenon occurs with other paths, such as corridors and doors, although

    quantitative estimates of their edge effect are not as well established as they have been for

    stairways, at least those stairways studied in Canada during the late 1960s through the 1970s in

    office building evacuation drills and in crowd movement in a variety of buildings with assembly

    occupancy.

    More recent studies have not been performed to determine how the edge effect might be

    changing (or has changed) with demographic changes to larger, heavier occupants moving more

    slowly, and thus swaying laterally, to maintain balance when walking. The impact of such

  • 8/13/2019 Fire - Egress

    24/28

    demographic changes, which are significant and influential for evacuation flow and speed of

    movement on stairs, for example, has the effect of increasing the time of evacuation in a way that

    affects all stair widths, but will be most pronounced for nominal widths less than 56 in. (1422

    mm).

    Without taking into account occupant demographic changes in the last few decades that affect

    evacuation performance, especially on stairs, the formula for enhanced capacity of stairways

    wider than 44 in. (1120 mm) assumes that any portion of the nominal width greater than 44 in.

    (1120 mm) is as effective proportionally as the effective width of a nominal 44 in. (1120 mm)

    stair, that is, 32 in. (810 mm). Thus, the denominator (0.218) in the equation is simply the

    effective width of 32 in. (810 mm) divided by the capacity of 147 persons that is credited, by the

    0.3 in. (7.6 mm) capacity factor in Table 7.3.3.1, to the corresponding nominal width, 44 in.

    (1120 mm). The resulting permitted stairway capacities, based on occupant load of single stories

    (in accordance with 7.3.1.4), for several stairway widths are shown in Table below.

    2.10 Exit access ventilation2.10.1 Natural ventilation2.10.2 Mechanical ventilation

    2.11 Exit Discharge Lobby2.12 Exit marking

    The exit sign with arrow indicating the way to the escape route shall be provided at a suitable

    height from the floor level on the wall and shall be illuminated by electric light connected to

  • 8/13/2019 Fire - Egress

    25/28

    corridor circuits. All exit way marking signs should be flush with the wall and so designed that

    no mechanical damage shall occur to them due to moving of furniture or other heavy

    equipments. Further, all landings of floor shall have floor indicating boards prominently

    indicating the number of floor as per bye-laws.

    The floor indication board shall be placed on the wall immediately facing the flight of stairs and

    nearest to the landing. It shall be of size not less than 0.5 m x 0.5 m.

    2.12.1 Type2.12.2 Size2.12.3 Placement

    2.13 IlluminationThat part of emergency lighting which is provided to ensure that the escape route is illuminated

    at all material times, for example, at all times when persons are on the premises, or at times the

    main lighting is not available, either for the whole building or for the escape routes.

    The floors of areas covered for the means of exit shall be illuminated to values not less than 1 ft

    candle (10 LUX) at floor level. In auditoriums, theatres, concert halls and such other places of

    assembly, the illumination of floor exit/access maybe reduced during period of performances to

    values not less than 1/5 ft candle (2 lux).

    According to NFPA 101, for the purposes of Illumination of means of egress, exit access shall

    include only designated stairs, aisles, corridors, ramps, escalators, and passageways leading to an

    exit. For the purposes of this requirement, exit discharge shall include only designated stairs,

    aisles, corridors, ramps, escalators, walkways, and exit passageways leading to a public way.

    Illumination of means of egress shall be continuous during the time that the conditions of

    occupancy require that the means of egress be available for use. Artificial lighting shall be

    employed at such locations and for such periods of time as are necessary to maintain the

    illumination to the minimum criteria values herein specified. Automatic, motion sensortype

    lighting switches shall be permitted within the means of egress, provided that the switchcontrollers are equipped for fail-safe operation, the illumination timers are set for a minimum 15-

    minute duration, and the motion sensor is activated by any occupant movement in the area served

    by the lighting units.

  • 8/13/2019 Fire - Egress

    26/28

    2.13.1 SourceIllumination of means of egress shall be from a source considered reliable by the authority

    having jurisdiction. Battery-operated electric lights and other types of portable lamps or lanterns

    shall not be used for primary illumination of means of egress. Battery-operated electric lights

    shall be permitted to be used as an emergency source to the extent permitted.

    2.13.2 Alternate source2.13.3 Illumination level

    The floors and other walking surfaces within an exit and within the portions of the exit access

    and exit discharge designated in 7.8.1.1 shall be illuminated as follows:

    (1) During conditions of stair use, the minimum illumination for new stairs shall be at least 10 ft-

    candle (108 lux), measured at the walking surfaces.

    (2) The minimum illumination for floors and walking surfaces, other than new stairs during

    conditions of stair use, shall be to values of at least 1 ft-candle (10.8 lux), measured at the floor.

    (3) In assembly occupancies, the illumination of the walking surfaces of exit access shall be at

    least 0.2 ft-candle (2.2 lux) during periods of performances or projections involving directed

    light.

    (4)*The minimum illumination requirements shall not apply where operations or processes

    require low lighting levels.

    Required illumination shall be arranged so that the failure of any single lighting unit does not

    result in an illumination level of less than 0.2 ft-candle (2.2 lux) in any designated area.

    The equipment or units installed to meet the requirements of Section 7.10 also shall be permitted

    to serve the function of illumination of means of egress, provided that all requirements of Section

    7.8 for such illumination are met.

    2.13.4 Illumination intensity2.14 Refuge area

    2.14.1 RequirementFor buildings more than 24m in height, refuge area of 15m2 or an area equivalent to 0.3m2 per

    person to accommodate the occupants of two consecutive floors, whichever is higher, shall be

    provided as under.

    The refuge area shall be provided on the periphery of the floor or preferably on a cantilever

    projection and open to air at least on one side protected with suitable railings.

  • 8/13/2019 Fire - Egress

    27/28

    a) For floors above 24m and up to 39m, one refuge area on the floor immediately above 24 m.

    b) For floors above 39m, one refuge area on the floor immediately above 39m and so on after

    every 15m. Refuge area provided in excess of the requirements shall be counted towards FAR.

    2.14.2Location

    2.14.3 Access2.14.4 Connectivity2.14.5 Protection2.14.6 Illumination

    2.14.7Marking

    2.15 Horizontal exitAccording to NFPA 101, Horizontal exit is a way of passage from one building to an area of

    refuge in another building on approximately the same level, or a way of passage through or

    around a fire barrier to an area of refuge on approximately the same level in the same building

    that affords safety from fire and smoke originating from the area of incidence and areas

    communicating therewith. Horizontal exits shall be permitted to be substituted for other exits

    where the total egress capacity and the total number of the other exits (stairs, ramps, dooropenings leading outside the building) is not less than half that required for the entire area of the

    building or connected buildings, and provided that none of the other exits is a horizontal exit,

    unless otherwise permitted.

    The width of horizontal exit shall be same as for the exit door ways. A horizontal exit shall be

    equipped with at-least one fire/ smoke door of minimum one hour fire resistance of self closing

    type. Further, it is required to have direct connectivity to the fire escape staircase for evacuation.

    For buildings more than 24m in height, refuge area of 15m2 or an area equivalent to 0.3m2 per

    person to accommodate the occupants of two consecutive floors, whichever is higher, shall be

    provided. Where there is a difference in level between connected areas for horizontal exits,

    ramps, not more than 1 in 10 m slope shall be provided; steps shall not be used. Doors in

    horizontal exits shall be operable at all times from both sides.

  • 8/13/2019 Fire - Egress

    28/28

    2.15.1 Requirement2.15.2 Minimum width2.15.3 Access2.15.4 Protection2.15.5 Marking2.15.6 Illumination

    2.16 Exit door hardware2.17 Fire Check Door2.18 Means of egress: Underground Structures

    INSERT