fire resistance of materials & structures - analysing the concrete structure
TRANSCRIPT
Fire Resistance of Materials & Structures 4th Homework – Concrete structrue
Date of Submission
2016
Submitted by
Seyed Mohammad Sadegh Mousavi
836 154
Submitted to
Prof. R. Felicetti
Prof. P. G. Gambarova
Dr. P. Bamonte
Structural Assessment & Residual Bearing
Capacity, Fire & Blast Safety
Civil Engineering for Risk Mitigation
Politecnico di Milano
[ 4 t h H o m e w o r k - C o n c r e t e S t r u c t u r e ]
Page 1 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Fire Resistance of Materials and Structures Prof. R. Felicetti, Prof. P.G. Gambarova and Dr. P. Bamonte
4th Homework - Concrete structure
The figure below shows the plan of a library room (see Homework 2), whose structural elements are to
be checked (in terms of bearing capacity, R criterion) in fire conditions. The dimensions of the room are
given in centimeters; the height of the room is 3.50 m.
The materials characteristics of the structural elements at room temperature are the following:
Concrete compressive strength: fck = 30 MPa
Yield stress of the reinforcing steel: fyk = 500 MPa
The thermal properties (conductivity, specific heat, and density) of the concrete are given in the Eurocode 2
(EN 1992-1-2); assume the lower bound of thermal conductivity and 0% moisture for F even, upper bound
and 1.5% for F odd (F = 3rd letter of the first name).
The two spans are L1 = 4 - L/100 and L2 = 4 + L/100 (in meters, L = 3rd letter of the last name). The room is
subjected to the following loads:
permanent load: Gk = 7.00 kN/m2
variable load: Qk = 2.00 kN/m2
The beam has a rectangular section, and its structural scheme is shown on the right-end side of the picture.
The center support represents the central column. The total depth of the section is h1 = 24 cm; the net
cover to the bars is 30 mm.
Page 2 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
(a) Design the critical beam sections at room temperature, by determining the reinforcement, and
then evaluate the fire endurance of the beam (with reference to the fire scenario studied in
Homework 2) by means of the 500°C isotherm method. Both the static and the kinematic
approach should be applied, and the differences between the two should be commented.
To ensure the ductility requirements at room temperature, the relative depth of the compression
zone must not be larger than x/d = 0.40.
Optional
Let us assume that the central column is removed: the new section and the corresponding structural scheme
are indicated in the figure below. The total depth h2 becomes 60 cm.
(b) Repeat step (a) for the new section and structural scheme, and comment on the possible
interaction with the boundaries.
L = 21 (U)
𝐿1 = 4 −𝐿
100= 3.79 𝑚
𝐿2 = 4 +𝐿
100= 4.21 𝑚
Page 3 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
The fire used in this case is the parametric fire in EuroCode 1. So concrete strength is 30 Mpa and steel
yield strength is 500 Mpa. On the other hand, thermal properties of the material are based on the EuroCode
2. Consideri other parameters such as thermal conductivity and specific heat, the upper bound and the
condition according to 1.5 % moisture content are considered respectively.
Figure 1 – General Scheme of the Beams
Loads
Permanent: Gk = 7.00 kN/m2
Variable: Qk = 2.00 kN/m2
The design of the beam is carried out based on static and kinematic mechanisms and for each condition
the fire endurance is determined. The temperature evolution within the member is modelled using
ABAQUS software and the decay of the bending moment resistance of the section is calculated based on
a 500 ̊C isotherm method.
Design of the critical beam sections at room temperature
(ULS) – Ultimate Moments Computations
Floor Loads
𝑃𝑈𝐿𝑆 = 𝛾𝐺𝐺𝑘 + 𝛾𝑄𝑄𝑘 = 1.35 × 7 (𝐾𝑁
𝑚2) + 1.5 × 2 (
𝐾𝑁
𝑚2) = 12.45 (
𝐾𝑁
𝑚2)
Contribution (Effective) width: we assume bending continuity between the two bays of the slab, this width
is: 2 ×5
8× 6 = 7.5 𝑚
Figure 2 – Bay width
Internal Forces (ULS)
𝑔𝑈𝐿𝑆 = 12.45 × 7.5 = 93.375 (𝐾𝑁
𝑚)
𝑞𝑈𝐿𝑆 = (1.5 × 2) × 7.5 = 22.5 (𝐾𝑁
𝑚)
Page 4 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
For designing the beam at room temperature, 3 critical combinations were considered:
1- Negative bending moment at the intermediate soppurt.
2- Max positive bending moment in the left span.
3- Max positive bending moment in the right span.
For reach to that aim, 3 different load cases were considere by selecting the load spans with variable loads
as following:
Figure 3 – Bending Moment Diagram Scheme
1st Combination – Negative Bending moment at the intermediate soppurt
Figure 4 – Max loaded at the intermediate soppurt
3 33 31 2
,11 2
93.375 3.79 93.375 4.21188.29 .
8( ) 8 3.79 4.21Ed
wL wLM KN m
L L
,1 11
1
188.29 93.375 3.79 127.262 3.79 2
EdM wL
R KNL
11
127.261.36
93.375
Rx
w
Page 5 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
2nd Combination – Max Loaded on the left side
Figure 5 – Max loaded on the left side
2 21
1 1,2, 1
93.375 1.36127.26 1.36 86.72 .
2 2Ed x
wxM R x KN m
,1 23
2
188.29 93.375 4.21
4.21 2151.83
2Ed
M wLR KN
L
3rd Combination – Max Loaded on the right side
Figure 6 – Max Loaded on the right side
32
151.831.63
93.375
Rx
w
2 22
3 2,3, 2
93.375 1.63151.83 1.63 123.44 .
2 2Ed x
wxM R x KN m
Sections Combinations 𝑴𝑬𝒅(𝑲𝑵. 𝒎)
Support Combination 1 188.29
Left Span Combination 2 86.72
Right Span Combination 3 123.44
Applied Design Moment (at the support)
188.29 .Ed
M KN m
Page 6 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Materials (Concrete + Steel) used and their properties:
Concrete
The characteristic compressive strength = 𝒇𝒄𝒌 = 𝟑𝟎 𝑴𝑷𝒂 = 30 (𝑁
𝑚𝑚2)
The design value of compressive strength
𝒇𝒄𝒅 = 𝜶 ×𝒇𝒄𝒌
𝜸𝒄= 0.85 ×
30
1.6= 15.94 𝑀𝑃𝑎 = 𝟏𝟓. 𝟗𝟒 (
𝑁
𝑚𝑚2)
- The ultimate strain of concrete eCU=0.0035
- The strength reduction value a= 0.85
- The material factor of safety for concrete gc=1.6
Steel
The characteristic yield strength = 𝒇𝒚𝒌 = 𝟓𝟎𝟎 𝑴𝑷𝒂 = 500 (𝑁
𝑚𝑚2)
The design value of compressive strength
𝒇𝒚𝒅 =𝒇𝒚𝒌
𝜸𝒔=
500
1.15= 437.78 𝑀𝑃𝑎 = 437.78 (
𝑁
𝑚𝑚2)
- The elastic Modulus Es=200000 (𝑁
𝑚𝑚2)
- The ultimate strain of steel eCU=0.01
- The yield strain of steel 𝜺𝒚𝒅 =𝒇𝒚𝒅
𝑬𝒔= 0.00217
- The material factor of safety for steel reinforcement gs=1.15
The cross section geometric
Figure 7 – Cross Section Details
The Design Procedure
1st Assumption of computation of amount of longitudinal reinforcement in Tension & Compression zones
by the following formulas:
'
0.9
0.5
Eds
yd
s s
MA
f d
A A
Page 7 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Figure 8 – Assumptions of Reinforcements
Ductility Check
Basically the structures show 2 type of failures (Ductile & Brittle), and in case of safety and clear warming
prior to collapse by increased deflection, curvature & cracking, ductile failure should be considered in
design phase and must be preventing the brittle failure.The following figure (Fig. 5) shows 6 failure fields
and each 7 limit lines represents different limit states for the section.
Figure 9 – Failure Fields
The procedure was based on considering the maximum exploitation of the cross section by assuming the
ultimate steel strain (Point A, εs = εsu = 0.01), and the maximum compressive concrete strain (Point B, εc
= εcu = 0.0035) are reached and Piont C shows the yield strain of steel. For deisgning the beam, ductile
behavior is an important criteria that should be respect and so can fall into fields 2 or 3. On the other
hand, in field 2, the bottom reinforcement reaches the ultimate strain & failure is expected to happen in
ductile method. In field 3, concrete does reach ultimate strain, but steel has yielded and it is in the plastic
range. As a result, gradually ductile failure is to be expected.
According to the depth of the compressive zone, ductility requirement: 𝑦𝑛
𝑑= 𝜉 ≤ 0.4
Med (Soppurt)= 188.29
As= 22.91 25.4 10 Φ 18
As'= 11.46 12.7 5 Φ 18
Bars
Med (Left)= 86.72
As= 10.55 12.7 5 Φ 18
As'= 5.28 7.62 3 Φ 18
Bars
Med (Right)= 123.44
As= 15.02 15.24 6 Φ 18
As'= 7.51 10.16 4 Φ 18
Bars
Needed Selected
Page 8 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Due to this fact that tensile strength of concrete is neglected, resistance of concrete in tension zone is
ignored. Only considered the comprssion force developed in concrete. Depth of compressive zone should
be ≤ 0.4 d.
1st case – Cross section at span
Figure 10 – Cross Section at Span
2nd Case – Cross section at intermediate soppurt
Figure 11 – Cross Section at intermediate soppurt
According of the depth of compression, the position of Neutral Axis will be obtained. And also respecting
the ductility requirement, it maybe concluded at intermediate soppurt works in Field 3 while span secions
work in Field 2.
Failue Field 2 for the 1st case:
𝟎 < 𝝃 ≤ 𝟎. 𝟐𝟓𝟗𝒅
Concrete and also bottom reinforcement reach max strain, thus max exploitation of section resource is
achieved.
εcu = 0.0035, εsu = 0.01, 𝜺𝒚𝒅 =𝒇𝒚𝒅
𝑬𝒔
Factor for the equivalent stress block (β) 𝛃 = (𝟏. 𝟔 × 𝟎. 𝟖�̅�𝒄) × �̅�𝒄
Factor for the position of the concrete force (k) 𝒌 = (𝟎. 𝟑𝟑 + 𝟎. 𝟎𝟕)�̅�𝒄
�̅�𝒄 =𝜺𝒄
𝜺𝒄𝒖
By computation of this, we can know the ductile and brittle behavior, so it is important procedure to
determine the type of failure mechanism.
Page 9 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Strain Compatibility equations, for calculation of Neutral axis position in field 2:
0 < 𝜉 ≤ 0.259 𝑑
. 0.00350.259
0.0035 0.01cu su cu
nn n cu su
d dy d
y d y
1csu
,
.( )'
1su
s
in field 3:
𝟎. 𝟐𝟓𝟗 𝒅 < 𝝃 ≤ 𝟎. 𝟔𝟓𝟐 𝒅
0.00187
0.00350.652
0.0035ydcu
nn n yd
dy d
y d y
Max strain in conrete is reached at Point B:
εcu = 0.0035, εsu = 0.01, 𝜺𝒚𝒅 =𝒇𝒚𝒅
𝑬𝒔
β = 0.8, k = 0.4
Strain Compatibility equations, for calculation of Neutral axis position:
.(1 )cu s cusd d d
' .( )'
'cu s cu
sd d d
Concrete Cover Coefficient:
'
d
d
Stresses can be obtained used σ – ε constitutive models:
𝛔𝒄 = 𝒇𝒄𝒅 = 𝜶 ×𝒇𝒄𝒌
𝜸𝒄= 0.85 ×
30
1.6= 15.94 𝑀𝑃𝑎 = 15.94 (
𝑁
𝑚𝑚2)
𝛔𝒔 = 𝒇𝒚𝒅 =𝒇𝒚𝒌
𝜸𝒔=
500
1.15= 437.78 𝑀𝑃𝑎 = 437.78 (
𝑁
𝑚𝑚2)
𝛔′𝒔 = 𝐄𝒔 𝛆′𝒔
Concrete & reinforcement forces:
Concrete compression force C = - σcd × β × yn × b
Compression steel force C’ = - σs’ × As‘
Tension steel force T = σs × As
Page 10 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
2 Equilibrium conditions can be imposed:
Force Equlibrium
Rotation Equilibrium
Aim: Finding the value of inside ξ the ranges of each field (2 & 3) that will verify force equlibrium
condirion & checking MEd ≤ MRd
Using Excelsheets for reaching to this aim.
1st Condition – Soppurt (3rd Failure Field)
2nd Condition – Left Span (2nd Failure Field)
3rd Condition – Right Span (2nd Failure Field)
Σ F = C + C’ + T = 0
MRd = σc + β × yn × b × (d – k × yn) + σs’ × As‘× (d – d’)
Page 11 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Figure 12 – Bending moment & force equlibriums check of the section for different situations
As we can see on the top figure (Fig. 12), the moment equlibriums of different cases were satisfied, but,
with those positions of N.A that we considered the max values with respect to the boundary conditions of
2 fields, the force equlibriums were not satisfied and those values were negative which replies the
compression parts are too much, and so for satisfying the force equlibrium, the positions of N.A should
be changed, reduced and repeating the procedueres. What’s more, according to the force equlibrium is
very sensitive about the changing of position of N.A, the Solver add-in of excel used to find the exact
positions of N.A in different cases, then SF=0, as you can see in the next figure (Fig. 13).
fck= 30 N/mm2 fck= 30 N/mm2 fck= 30 N/mm2
fyk= 500 N/mm2 fyk= 500 N/mm2 fyk= 500 N/mm2
Es= 200000 N/mm2 Es= 200000 N/mm2 Es= 200000 N/mm2
Ecm= 32000 N/mm2 Ecm= 32000 N/mm2 Ecm= 32000 N/mm2
εcu= 0.0035 εcu= 0.0035 εcu= 0.0035
εsu= 0.01 εsu= 0.01 εsu= 0.01
γc= 1.5 γc= 1.5 γc= 1.5
γs= 1.15 γs= 1.15 γs= 1.15
h= 240 mm h= 240 mm h= 240 mm
d'= 30 mm d'= 30 mm d'= 30 mm
d= 210 mm d= 210 mm d= 210 mm
b= 600 mm b= 600 mm b= 600 mm
δ= 0.1429 mm δ= 0.1429 mm δ= 0.1429 mm
As= 2540 mm2 As= 1270 mm2 As= 1524 mm2
As'= 1270 mm2 As'= 762 mm2 As'= 1016 mm2
fcd= 15.94 N/mm2 fcd= 15.94 N/mm2 fcd= 15.94 N/mm2
fyd= 434.78 N/mm2 fyd= 434.78 N/mm2 fyd= 434.78 N/mm2
εyd= 0.0021739 εyd= 0.0021739 εyd= 0.0021739
ξ max(f.3)= 0.652 ξ max(f.2)= 0.259 ξ max(f.2)= 0.259
εs= 0.006329604 εc= 0.003058824 εc= 0.0032316
εs'= 0.0020958 N/mm2 εs'= 0.0011933 N/mm2 εs'= 0.001341 N/mm2
ε_cu= 1.808 ε_cu= 0.874 ε_cu= 0.9233024
σc= 15.94 N/mm2 σc= 15.94 N/mm2 σc= 15.94 N/mm2
σs= 434.78 N/mm2 σs= 434.78 N/mm2 σs= 434.78 N/mm2
σs'= 419.154 σs'= 238.655 σs'= 268.267
k= 0.4 k= 0.35 k= 0.3693210
β= 0.8 β= 0.79 β= 0.7952940
yn= 136.92 mm yn= 54.39 yn= 54.39
MRd= 258.41 KN/m MRd= 110.94 KN/m MRd= 127.62 KN/m
MEd= 188.29 KN/m MEd= 86.720 KN/m MEd= 123.44 KN/m
Σf=0 -475415.972 Σf=0 -39154.03999 Σf=0 -23586.62250
Moment EQ Check
Force EQ Check
SAFE MEd ≤ MRd
3rd Cond - Right Span (Field 2)
Material Properties
Material Factors
Cross Section Geometric
Assumed Bars
SAFE MEd ≤ MRd
Moment EQ Check
Force EQ Check Force EQ Check
1st Cond - Support (Field 3)
SAFE MEd ≤ MRd
2nd Cond - Left Span (Field 2)
Material Properties
Material Factors
Cross Section Geometric
Assumed Bars
Material Properties
Material Factors
Cross Section Geometric
Assumed Bars
Moment EQ Check
Page 12 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Figure 13 – The Final Position of N.A & Force Equlibrium Check
The new positions of N.A:
ξ1 (Field 3) = 0.356067244109769
ξ2 (Field 2) = 0.234234241633019
ξ3 (Field 2) = 0.244231128360258
Eventually, all the values of ξ < 0.4 that the ductility of section is satisfied.
Check the minimum reinforcement ratio
According to EN1992-1-1 6.2.2, 𝜌𝑤 should be not less than 𝜌𝑤,𝑚𝑖𝑛
𝝆𝒘,𝒎𝒊𝒏 =𝟎. 𝟎𝟖√𝒇𝒄𝒌
𝒇𝒚𝒌= 0.00087
,Soppurt
25400.02
210 600w
,
,Left
12700.01
210 600w
,
,Right
15240.012
210 600w
So, All the reinforcement ratios satisfied the requirement.
Thermal Analysis
Thermal analysis was done by the ABAQUS with neglecting the reinforcements in the model due this fact
the effects of it are very small and with respect to the volume of the concrete is negligible and also it was
demonstrated that the temperature in the centroid of the bars will not change.
Concrete properties
Density (ρ) - weight per unit mass of the material (kg/m3)
According to the Eurocode 2 Part 1&2 (2004)
𝜌(𝑡) = 𝜌(20 ℃) 𝐹𝑜𝑟 20 ℃ ≤ 𝑡 ≤ 115 ℃
𝜌(𝑡) = 𝜌(20 ℃) ∙ (1 −0.02(𝑡 − 115)
85) 𝐹𝑜𝑟 115 ℃ < 𝑡 ≤ 200 ℃
𝜌(𝑡) = 𝜌(20 ℃) ∙ (0.98 −0.03(𝑡 − 200)
200) 𝐹𝑜𝑟 200 ℃ < 𝑡 ≤ 400 ℃
𝜌(𝑡) = 𝜌(20 ℃) ∙ (0.95 −0.07(𝑡 − 400)
800) 𝐹𝑜𝑟 400 ℃ < 𝑡 ≤ 1200 ℃
The following graph represent the concrete density with respect to the equations for different
temperatures that mentioned in the previous page and plotted in excel code.
ξ max(f.3)= 0.652 ξ max(f.2)= 0.259 ξ max(f.2)= 0.259
ξ (f.3)= 0.3560672441 ξ (f.2)= 0.2342342416 ξ (f.2)= 0.2442311284
Σf=0 0.00000 Σf=0 0.00000 Σf=0 0.00000
Force EQ Check Force EQ Check Force EQ Check
Page 13 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Figure 14 – Concrete Density graph
Specific Heat (c) - amount of heat required to heat unit mass of the material by one degree (J/kg.K).
According to the Eurocode 2 Part 1&2 (2004)
𝑐𝑝(𝑡) = 900 (𝐽
𝐾𝑔 𝐾⁄ ) 𝐹𝑜𝑟 20 ℃ ≤ 𝑡 ≤ 100 ℃
𝑐𝑝(𝑡) = 900 + (𝑡 − 100) (𝐽
𝐾𝑔 𝐾⁄ ) 𝐹𝑜𝑟 100 ℃ < 𝑡 ≤ 200 ℃
𝑐𝑝(𝑡) = 1000 +𝑡 − 200
2 (
𝐽𝐾𝑔 𝐾⁄ ) 𝐹𝑜𝑟 200 ℃ < 𝑡 ≤ 400 ℃
𝑐𝑝(𝑡) = 1100 (𝐽
𝐾𝑔 𝐾⁄ ) 𝐹𝑜𝑟 400 ℃ < 𝑡 ≤ 1200 ℃
Concrete is assumed with 0% of moisture. Because according to the discussion during the class, if there
is moist inside the concrete the graph of the temperature versus time is different. But in the following
graph the increasing in the trend happened due to vaporization of the water that called latent heat.
2075
2125
2175
2225
2275
2325
2375
2425
20 150 280 410 540 670 800 930 1060 1190
DEN
SITY
(K
G/M
3)
TEMPERATURE (℃)
CONCRETE - DENSITY
Page 14 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Figure 15 – Concrete Specific Heat graph
Conductivity (λ) - rate of heat transferred per unit thickness of material per unit temperature difference
(W/m.K). EN1992-1-2 proposes lower and upper limit of thermal conductivity. Regarding the maximum
and minimum formulas for thermal conductivity in the Eurocode 2, the average value of these formulas
considered as a reference value for the concrete thermal conductivity in the ABAQUS code.
According to the Eurocode 2 Part 1-2 (2004) – MAX & MIN Conductivity
𝜆𝑐𝑚𝑎𝑥(𝑡) = 2 − 0.2451 (
𝑡
100) + 0.0107 (
𝑡
100)
2
𝜆𝑐𝑚𝑖𝑛(𝑡) = 1.36 − 0.136 (
𝑡
100) + 0.0057 (
𝑡
100)
2
Figure 16 – Concrete Conductivity graph (Average Value)
850
900
950
1000
1050
1100
1150
20 150 280 410 540 670 800 930 1060 1190
SPEC
IFIC
HEA
T (J
/KG
K)
TEMPERATURE (℃)
CONCRETE - SPECIF IC HEAT
0.2
0.6
1.0
1.4
1.8
20 145 270 395 520 645 770 895 1020 1145
CO
ND
UC
TIV
ITY
(W/M
K)
TEMPERATURE (C)
C O N C R E T E - T H E R M A L C O N D U C T I V I T Y ( A V E R A G E V A L U E )
Page 15 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
The procedures of the cross section implementation in the ABAQUS is almost the same as exercise 1 and
we will mentioned the differences in the following. In this case, the Parametric Fire obtained from exercise
2 was used, for the linear temp depending openings.
Figure 17 – Radiation & Convections of the surfaces
Figure 18 – Details of the Radiation & Convections of the Surfaces
Page 16 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
500 °C Isotherm
As you can see in the following table (Fig. 19), the position of 500 °C isotherm was extracted
approximately by defining a vertical path & temperature, was plotted with distance for each 30 min fire
duration. In addtition, the temperature of top & bottom steel reinforcement was found at each 30 minutes
of fire duration, in order to find out the steel properties decay at each step. It worth to mention that the
upper reinforcement had always a temperature less than 130°C. (Fig. 20)
Figure 19 – The temperature distribution among the Cross Section
Figure 20 – Postion of 500°C isotherm for different time & temperatures
Time 30 min 60 min 90 min 120 min 150 min 180 min 210 min 240 min
Distance [m] [°C] [°C] [°C] [°C] [°C] [°C] [°C] [°C]
0 1047.88 1211.54 1255.75 1279.97 1296.15 1303.63 1316.89 1231.19
0.0025 919.742 1127.34 1189.68 1223.69 1246.24 1256.64 1275.15 1206.27
0.005 808 1045.01 1124.11 1167.69 1196.58 1209.87 1233.56 1179.65
0.0075 712.646 966.471 1059.58 1112.14 1147.13 1163.3 1192.14 1151.48
0.01 631.523 893.085 997.161 1057.48 1098.12 1117.02 1150.87 1122.02
0.0125 562.094 825.477 937.696 1004.37 1049.99 1071.35 1109.88 1091.58
0.015 502.173 763.753 881.586 953.332 1003.12 1026.66 1069.42 1060.4
0.0175 450.085 707.608 828.993 904.611 957.875 983.227 1029.74 1028.8
0.02 404.483 656.487 779.986 858.432 914.444 941.319 991.063 997.083
0.0225 364.292 609.916 734.41 814.846 872.985 901.085 953.551 965.462
0.025 328.651 567.414 692.066 773.815 833.549 862.618 917.343 934.191
0.0275 296.885 528.511 652.719 735.248 796.132 825.958 882.499 903.427
0.03 268.442 492.803 616.122 699.016 760.699 791.08 849.076 873.335
0.0325 242.881 459.95 582.032 664.971 727.153 757.959 817.049 844.056
0.035 219.853 429.652 550.234 632.963 695.42 726.498 786.426 815.623
0.0375 199.05 401.641 520.545 602.864 665.38 696.643 757.189 788.118
0.04 180.219 375.709 492.75 574.5 636.935 668.291 729.255 761.584
0.0425 163.297 351.637 466.708 547.76 610.005 641.356 702.595 735.992
0.045 148.196 329.243 442.274 522.529 584.458 615.776 677.146 711.363
0.0475 134.798 308.388 419.296 498.666 560.212 591.446 652.824 687.696
0.05 122.978 288.935 397.674 476.089 537.2 568.282 629.593 664.931
0.0525 112.61 270.755 377.318 454.721 515.321 546.232 607.401 643.055
0.055 103.555 253.743 358.114 434.457 494.491 525.221 586.164 622.055
0.0575 95.6604 237.816 339.964 415.215 474.658 505.166 565.836 601.884
0.06 88.4913 222.894 322.803 396.942 455.767 486.017 546.385 582.488
0.0625 81.9424 208.897 306.571 379.58 437.744 467.734 527.753 563.846
0.065 75.9633 195.756 291.197 363.059 420.528 450.261 509.884 545.941
0.0675 70.5082 183.424 276.618 347.317 404.082 433.539 492.736 528.728
0.07 65.5354 171.889 262.779 332.308 388.374 417.522 476.283 512.165
0.0725 61.0064 161.137 249.638 317.996 373.351 402.183 460.492 496.217
0.075 56.8856 151.143 237.16 304.341 358.969 387.492 445.321 480.87
0.0775 53.1402 141.878 225.304 291.299 345.187 373.405 430.731 466.1
0.08 49.7398 133.312 214.03 278.833 331.975 359.886 416.693 451.875
Concrete temperature
Page 17 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
As a result, the approximate position of 500 °C isotherm and temperatures of the top & bottom
reinforcements are as the following:
Figure 21 – The approcimate position of 500°C isotherm
Figure 22 – The top & Bottom Reinforcements temperatures
Figure 23 – Temp Evolution along the vertical line for different Fire durations
Time 30 min 60 min 90 min 120 min 150 min 180 min 210 min 240 min
x - Distance [cm] 1.5 2.95 3.95 4.75 5.5 5.8 6.5 7.2
574.5 636.935 668.291 729.255 761.584Temp [°C] at Bottom
Reinforcement180.219 375.709 492.75
500°C Isotherm [Approximately]
68.89 81.60 109.09 128.55Temp [°C] at Top
Reinforcement20.04 22.60 32.52 48.87
0
100
200
300
400
500
600
700
800
0 40 80 120 160 200 240
TEM
PER
ATU
RE
[°C
]
TIME [MIN]
Reinforcement Temperature
Top ReinforcementsBottom Reinforcements
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
0 0.03 0.06 0.09 0.12 0.15 0.18 0.21 0.24
Temperature Evolution Through the Vertical Line for Differents Fire Durations
30 min
60 min
90 min
120 min
150 min
180 min
210 min
240 min
500 °C Isotherm
Page 18 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
This simplified method is based on using an effective (reduced) depth for the concrete section by assuming
that the concrete with temperature higher than 500°C has no compressive strength (lost of mechanical
properties) and with lower than 500°C has no change in its compressive strength. The temperature at the
bottom steel (tension in spans and compression at the support) was found in order to compute the decay
in the steel properties; the elastic modulus and the yield strength.
Decay of mechanical properties of reinforcement
According to the class of reinforcement (Class N-Normal Ductility) and it’s hot-rolled.
Figure 24 – Coeeficient Ks(θ) allowing for decrese of charactristic strength (fyk) of tension & compression reinforcements (Class N)
Figure 25 – Decay table of mechanical properties of reinforcement
Figure 26 – Class N values for the parameters of the stress-strain relationship of hot rolled reinforcing at elevated temps
Temperature [°C] fyd,q [MPa] Es,q [MPa] Temperature [°C] fyd,q [MPa] Es,q [MPa]
0 20 500.0 200000 20.0 500.0 200000
30 180.22 500.0 183956.2 20.0 500.0 200000
60 375.71 500.0 144858.2 22.6 500.0 200000
90 492.75 398.0 121450.0 32.5 500.0 200000
120 574.50 274.5 76790.0 48.9 500.0 200000
150 636.94 190.7 48703.4 68.9 500.0 200000
180 668.29 153.1 37415.2 81.6 500.0 200000
210 729.26 97.4 23659.6 109.1 500.0 198181.4
240 761.58 78.0 21073.3 128.5 500.0 194290.2
Bottom TopTime
[min]
Reinforcement temperature
hot rolled hot rolled
20 1 1
100 1 1
200 1 0.9
300 1 0.8
400 1 0.7
500 0.78 0.6
600 0.47 0.31
700 0.23 0.13
800 0.11 0.09
900 0.06 0.07
1000 0.04 0.04
1100 0.02 0.02
1200 0 0
fsy,q/fyk Es,q/EsSteel
Temperature [°C]
Page 19 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Evaluation of the fire endurance of the beam
Bearing capacity of the beam in fire is check by 2 methods:
Static Method
Kinematic Method
With the same concept of the load combinations at room temp, 3 bending moment were computed by
SAP2000 for 3 critical section (Left & Right spans and at the Support)
Sections 𝑴𝑬𝒅(𝑲𝑵. 𝒎)
Support 142.66
Left Span 69.91
Right Span 92.73
Figure 27 – Bending Moments
The Static Method
According to this method, we can compute the resisting bending moment for each section at different time
steps (every 30 minutes) by the same way used for the design at room temperature, but considering the
changes due to the raise in the temperature in the bottom steel properties and in the effective concrete
section. It worth to mention that even if the effective depth is used for the strain compatibility relation and
for the concrete force computation, still the depth used for the deliver arm of the steel reinforcement is
the initial depth. The excel spreadsheet produced and provided in the report computes at each time step,
the location of the neutral axis that satisfies the equilibrium, then computes the resistant moment.
The constant applied bending moments (MEd) are compared with the resistant bending moments (MRd) at
each time step. When the resistant bending moment is less than the applied moment, the failure occurs
according to the static sectional method considered.
Calculations MRd in fire condition at different time step for the section:
Page 20 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Figure 28 – Resisting bending moment & force equlibrium of Support
Tim
eIn
itialt=
30
min
t= 6
0 m
int=
90
min
t= 1
20
min
t=1
50
min
t=1
80
min
t= 2
10
min
t=2
40
min
fck (N/m
m2)=
3030
3030
3030
3030
30
fyk (N/m
m2)=
500500
500500
500500
500500
500
Es' (N
/mm
2)=200000
200000200000
200000200000
200000200000
200000200000
fcd = α.fck25.5
25.525.5
25.525.5
25.525.5
25.525.5
εcu=0.0035
0.00350.0035
0.00350.0035
0.00350.0035
0.00350.0035
d' (mm
)=30.00
15.000.50
-9.50-17.50
-25.00-28.00
-35.00-42.00
d (mm
)=201
186171.5
161.5153.5
146143
136129
b (mm
)=600
600600
600600
600600
600600
δ (mm
)=0.15
0.080.00
-0.06-0.11
-0.17-0.20
-0.26-0.33
As (m
m2)=
25402540
25402540
25402540
25402540
2540
As' (m
m2)=
12701270
12701270
12701270
12701270
1270
dT=500 [m
m]=
0.0015.00
29.5039.50
47.5055.00
58.0065.00
72.00
d eff=210.00
195.00180.50
170.50162.50
155.00152.00
145.00138.00
T (reinfor.)=
20.00180.22
375.71492.75
574.50636.94
668.29729.26
761.58
fyd,θ=500
500500
398274.50
190.70153.10
97.4078
Es,θ=
200000183956.2
144858.2121450.00
76790.0048703.40
37415.2023659.60
21073.30
ξ =0.3222334305
0.29639874640.3012334264
0.31901259400.4480513227
0.55194727200.5995322262
0.67568819410.7181054793
ξ (Field) = Field 3
Field 3 Field 3
Field 3 Field 3
Field 3 Field 3
Field 3 Field 3
εs' (N/m
m2)=
0.001878850.00254771
0.003466130.00414537
0.004390570.00458582
0.004643080.00483306
0.00508686
σc (N/m
m2)=
25.525.5
25.525.5
25.525.5
25.525.5
25.5
σs (N/m
m2)=
500500
500500
500500
500500
500
σs'=375.77
468.67502.10
503.46337.15
223.34173.72
114.35107.20
k=0.40
0.400.40
0.400.40
0.400.40
0.400.40
β=0.80
0.800.80
0.800.80
0.800.80
0.800.80
yn (mm
)=64.77
55.1351.66
51.5268.78
80.5885.73
91.8992.64
MR
d (K
N.m
)=2
20
.41
21
2.4
12
04
.42
19
8.1
81
79
.28
16
0.7
21
51
.80
13
6.4
61
27
.53
ME
d (K
N.m
)=
Mom
ent E
Q C
heck
SA
FE
ME
d ≤
MR
d
SA
FE
ME
d ≤
MR
d
SA
FE
ME
d ≤
MR
d
SA
FE
ME
d ≤
MR
d
SA
FE
ME
d ≤
MR
d
SA
FE
ME
d ≤
MR
d
SA
FE
ME
d ≤
MR
d
No
t Safe
No
t Safe
Σf=
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
0
Ele
vate
d T
em
p fo
r the
So
pp
urt (F
ield
3)
14
2.6
6
Force E
Q C
heck
Page 21 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Figure 29 – Resisting bending moment & force equlibrium of Left Span
Tim
eInitial
t= 30 m
int=
60 min
t= 90 m
int=
120 min
t=150 m
int=
180 min
t= 210 m
int=
240 min
fck (N/m
m2)=
3030
3030
3030
3030
30
fyk (N/m
m2)=
500500
500500
500500
500500
500
ε su0.01
0.010.01
0.010.01
0.010.01
0.010.01
fcd = α.fck25.5
25.525.5
25.525.5
25.525.5
25.525.5
εc=0.002088
0.0021180.002211
0.0020410.001824
0.0016120.001490
0.0012700.001190
εcu=0.0035
0.00350.0035
0.00350.0035
0.00350.0035
0.00350.0035
ε_cu=0.59645
0.605040.63161
0.583140.52101
0.460560.42573
0.362780.33994
d' (mm
)=30
3030
3030
3030
3030
d (mm
)=210
210210
210210
210210
210210
b (mm
)=600
600600
600600
600600
600600
δ (mm
)=0.14286
0.142860.14286
0.142860.14286
0.142860.14286
0.142860.14286
As (m
m2)=
12701270
12701270
12701270
12701270
1270
As' (m
m2)=
762762
762762
762762
762762
762
dT=500 [m
m]=
0.0015.00
29.5039.50
47.5055.00
58.0065.00
72.00
d eff=210.00
195.00180.50
170.50162.50
155.00152.00
145.00138.00
T (reinfor.)=
20.00180.22
375.71492.75
574.50636.94
668.29729.26
761.58
fyd,θ=500
500500
398274.5
190.7153.1
97.478
Es,θ=
200000183956.2
144858.2121450.00
76790.0048703.40
37415.2023659.60
21073.30
ξ =0.1727036512
0.17475732890.1810406031
0.16950308120.1542281813
0.13881855180.1296814707
0.11266700600.1063270059
ξ (Field) = Field 2
Field 2 Field 2
Field 2 Field 2
Field 2 Field 2
Field 2 Field 2
εs' (N/m
m2)=
0.001728190.00182540
0.002109110.00157200
0.00073729-0.00029093
-0.00101600-0.00267959
-0.00343564
σc (N/m
m2)=
25.525.5
25.525.5
25.525.5
25.525.5
25.5
σs (N/m
m2)=
500.0500.0
500.0398.0
274.5190.7
153.197.4
78.0
σs'=345.64
335.79305.52
190.9256.62
-14.17-38.01
-63.40-72.40
k=0.23858
0.242020.25264
0.233260.20840
0.184220.17029
0.145110.13597
β=0.66972
0.675210.69143
0.660980.61645
0.567200.53617
0.475160.45145
yn (mm
)=36.27
36.7038.02
35.6032.39
29.1527.23
23.6622.33
MR
d (KN
.m)=
122.23122.31
122.5098.79
69.8549.82
40.6626.84
21.99
ME
d (KN
.m)=
Mom
ent EQ C
heckSA
FE
ME
d ≤ MR
d SA
FE
ME
d ≤ MR
d SA
FE
ME
d ≤ MR
d SA
FE
ME
d ≤ MR
d N
ot SafeN
ot SafeN
ot SafeN
ot SafeN
ot Safe
Σf=
00.0000000
0.00000000.0000000
0.00000000.0000000
0.00000000.0000000
0.00000000.0000000
Elevated T
emp for the L
eft Span (Field 2)
69.91
Force E
Q C
heck
Page 22 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Figure 30 – Resisting bending moment & force equlibrium of Right Span
Tim
eIn
itialt=
30
min
t= 6
0 m
int=
90
min
t= 1
20
min
t=1
50
min
t=1
80
min
t= 2
10
min
t=2
40
min
fck (N/m
m2)=
3030
3030
3030
3030
30
fyk (N/m
m2)=
500500
500500
500500
500500
500
ε su0.01
0.010.01
0.010.01
0.010.01
0.010.01
fcd = α
.fck25.5
25.525.5
25.525.5
25.525.5
25.525.5
εc=0.002131
0.0021680.002285
0.0021210.001921
0.0017160.001593
0.0013650.001280
εcu=0.0035
0.00350.0035
0.00350.0035
0.00350.0035
0.00350.0035
ε_cu=
0.608870.61940
0.652920.60602
0.548800.49015
0.455170.39009
0.36570
d' (mm
)=30
3030
3030
3030
3030
d (mm
)=210
210210
210210
210210
210210
b (mm
)=600
600600
600600
600600
600600
δ (mm
)=0.14286
0.142860.14286
0.142860.14286
0.142860.14286
0.142860.14286
As (m
m2)=
15241524
15241524
15241524
15241524
1524
As' (m
m2)=
10161016
10161016
10161016
10161016
1016
dT=
500 [mm
]=0.00
15.0029.50
39.5047.50
55.0058.00
65.0072.00
d eff=210.00
195.00180.50
170.50162.50
155.00152.00
145.00138.00
T (reinfor.)=
20.00180.22
375.71492.75
574.50636.94
668.29729.26
761.58
fyd,θ=500
500500
398274.5
190.7153.1
97.478
Es,θ=
200000183956.2
144858.2121450.00
76790.0048703.40
37415.2023659.60
21073.30
ξ =0.1756687018
0.17816458570.1860146279
0.17498918860.1611312814
0.14643178230.1374180497
0.12012937370.1134713893
ξ (Field) =
Field 2
Field 2
Field 2
Field 2
Field 2
Field 2
Field 2
Field 2
Field 2
εs' (N/m
m2)=
0.001867810.00198173
0.002320110.00183623
0.001134110.00024412
-0.00039581-0.00189194
-0.00258971
σc (N
/mm
2)=25.5
25.525.5
25.525.5
25.525.5
25.525.5
σs (N
/mm
2)=500.0
500.0500.0
398.0274.5
190.7153.1
97.478.0
σs'=
373.56364.55
336.09223.01
87.0911.89
-14.81-44.76
-54.57
k=0.24355
0.247760.26117
0.242410.21952
0.196060.18207
0.156040.14628
β=
0.677610.68411
0.703630.67582
0.637140.59204
0.562530.50241
0.47813
yn (mm
)=36.89
37.4139.06
36.7533.84
30.7528.86
25.2323.83
MR
d (K
N.m
)=1
45
.20
14
5.2
81
45
.49
11
7.1
98
2.7
55
8.9
94
8.1
43
1.7
72
6.0
2
ME
d (K
N.m
)=
Mom
ent E
Q C
heck
SA
FE
ME
d ≤
MR
d
SA
FE
ME
d ≤
MR
d
SA
FE
ME
d ≤
MR
d
SA
FE
ME
d ≤
MR
d
SA
FE
ME
d ≤
MR
d
No
t Safe
No
t Safe
No
t Safe
No
t Safe
Σf=
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
00
.00
00
00
0
92
.73
Fo
rce EQ
Ch
eck
Ele
vate
d T
em
p fo
r the
Rig
ht S
pan
(Fie
ld 2
)
Page 23 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
According to the last three previous tables ( Fig. 28, 29, 30), we can see the fact that the resistance of the
section at the intermediate soppurt is safe until around 210 min fire duration, however, the other 2 sections
(Left & Right) are safe less than about 120 min & 150 min respectively. As a result of Static method,
beam exposed to fire (Parametric Fire Scenario) is safe until 120 minutes fire duation.
The Kinematic Method
It is based on considering the redistribution of moments due to the exceedance of the resistant moments
at some sections, considering the global collapse for the beam. The number of plastic hinges for collapse
to happen is n+1 plastic hinges have to be formed (n = degree of redundancy of the structure), and in this
case is 1 time redundant and we need two plastic hinges, after which we have global collapse. The main
principle of kinematic approach is that computing all possible collapse mechanism and finds the most
possible one. The load used is the total load (permanent and variable) for the entire beam. Three collapse
configurations (kinematic admission is guaranteed) can be considered.
1st Collapse Mechanism
The postion of plastic hinge during time change will be obtained by the following equation:
1 1u u
u u
M Mx L
M M
69.91 142.663.79 1 1 1.38
142.66 69.91x m
The Ultimate Load:
1 1 12 2u u
fi
M Mq
L x L x L L x
69.91 1 1 142.66 12 2 73.28 /
3.79 1.38 3.79 1.38 3.79 3.79 1.38fiq KN m
Figure 31 – 1st Collapse Mechanism
The compatibility equation:
2.41𝜙2 = 1.38𝜙1 → 𝜙1 = 1.75 𝜙2
The Internal work:
21 12 22 221( ) 2.75iL M M M M
Page 24 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
The External Work:
1 2 2
1 13.79 3.79 1.75 4.57
2 21.38fi fi fie uL q q q
Kinematic Load amplifier:
1 1 2 2
2
2
4.57
2.75i
k
e fi
L
L
M M
q
1 2 1 22
2 4.57 73.28 334.9
2.75 2.75M M M M
2nd Collapse Mechanism
The postion of plastic hinge:
1 1u u
u u
M Mx L
M M
92.73 142.664.21 1 1 1.62
142.66 92.73x m
The Ultimate Load:
1 1 12 2u u
fi
M Mq
L x L x L L x
92.73 1 1 142.66 12 2 70.37 /
4.21 1.62 4.21 1.62 4.21 4.21 1.62fiq KN m
Figure 32 – 2nd Collapse Mechanism
The compatibility equation:
1.62𝜙3 = 2.59𝜙2 → 𝜙3 = 1.6 𝜙2
The Internal work:
3 3 22 2 23 2 2( ) 2.6iL M M M M
Page 25 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
The External Work:
3 2 2
1 14.21 4.21 2.59 5.46
2 2fi fi fie uL q q q
Kinematic Load amplifier:
2 3 22 2
25.46
2.6i
k
e fi
L
L
M M
q
32 3 2
2
2
5.46 70.37 384.21
2.6 2.75M M M M
3rd Collapse Mechanism
Due to amplification factor is rather high and it has very small external work, the failure mechanism for
this part is not considered.
Figure 33 – 3rd Collapse Mechanism
The next table reperesents the values of amplification factors for each mechanisms at different time steps:
Figure 34 – Values of μK
Time M1 = M Left M3 = M Right M2 = M Soppurt μK1 μK2
Initial 122.23 145.20 220.41 1.662 1.613
t= 30 min 122.31 145.28 212.41 1.639 1.593
t= 60 min 122.50 145.49 204.42 1.616 1.573
t= 90 min 98.79 117.19 198.18 1.403 1.355
t= 120 min 69.85 82.75 179.28 1.109 1.059
t=150 min 49.82 58.99 160.72 0.889 0.841
t=180 min 40.66 48.14 151.80 0.787 0.740
t= 210 min 26.84 31.77 136.46 0.628 0.583
t=240 min 21.99 26.02 127.53 0.561 0.518
Page 26 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
According to the Kinematic method, the beam is safe without collapse untill approximately 150 minutes
of fire duration. Moreover, µ K1 is always smaller than µ K2 that means the golbal collapse is governed
by the 2nd mechanism. It replies that the kinematic method alows for longer fire durations with no failure,
and this can be interpreted by the redistribution of moments that happens after the section reaches to its resistant
moment.
Figure 35 – Collapse Mechanisms
Comparision of Static Vs. Kinematic Approaches
There are several differences:
1. Static approach, which is called lower bound approach, the structure will collapse when MRd<Med.
2. Kinematic approach, which is called upper bound approach, the structure will collapse after it
cannot bearing any more load.
3. Due to the kinematic approach take the plastic hinge into cosideartion, the time to collapse for this
approach is longer than static approach.
4. According to the static method, it takes each section seperately. So, the structure will collapse
when the 1st section failed. In contrast, the collapse mechanism takes the beam as a whole for the
kinematic method.
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
0 30 60 90 120 150 180 210 240
Time [min]
Kinematic Approach
μK1 - 1st Failure Mechanism
μK2 - 2nd Failure Mechanism
Page 27 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Part b - Design the critical T-sections at room temperature
The conductivity, specific heat, density, fire scenario are all the same as before Abaqus software used to
calculate the temperature along the cross section. The temperature at last step is as follows:
Figure 36 – Temperature in the cross section at around 30 min (1800 sec)
Figure 37 – Temperature in the cross section at around 60 min (3600 sec)
Figure 38 – Temperature in the cross section at around 90 min (5400 sec)
Page 28 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
Figure 39 – Temperature in the cross section at around 120 min (7200 sec)
Figure 40 – Temperature in the cross section at around 150 min (9000 sec)
Figure 41 – Temperature in the cross section at around 180 min (10800 sec)
Page 29 of 29
Politecnico di Milano – Lecco Campus
Civil Engineering for Risk Mitigation
Prof. R. Felicetti & Prof. P. G. Gambarova & Dr. P. Bamonte
Seyed Mohammad Sadegh Mousavi (836154)
I define eight points (from A to H) to represent 8 different kinds of reinforcement respectively. The
reinforcement temperature of all types is in Error! Reference source not found..
Figure 42 – Types & positions of reinforcements
Figure 43 – Temperature of Reinforcements
The location of 500°C Isotherm from the side exposed to fire (bottom) at different time steps:
500°C isothermal line
Time [min] 30 60 90 120 150 180 210 240
Depth [mm] 15 29.5 40 48.8 58.2 67.5 77.5 87.5
Figure 44 –The postion of 500 °C Isotherm
-100
100
300
500
700
900
1100
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000
TEM
PER
ATU
RE
[°C
]
TIME [SEC]
Reinforcement temperature
type A
type B
type C
type D
type E
type F
type G
type H