National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org MEMORANDUM To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project Administrator Date: July 14, 2015 Subject: NFPA 909 First Draft TC FINAL Ballot Results (F2016) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. 26 Members Eligible to Vote 2 Members Not Returned (D. Nichols, J. Watts, Jr.) 20 Members Voted Affirmative on All Revisions 4 Members Voted Negative on one or more Revisions (D. Freeland, D. Moeller, C. Portway, M. Puchovsky) 0 Members Abstained on one or more Revisions The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each first revision. There are two criteria necessary for each first revision to pass ballot: (1) simple majority and (2) affirmative 2 /3 vote. The mock examples below show how the calculations are determined. (1) Example for Simple Majority: Assuming there are 20 vote eligible committee members, 11 affirmative votes are required to pass ballot. (Sample calculation: 20 members eligible to vote ÷ 2 = 10 + 1 = 11) (2) Example for Affirmative 2 /3: Assuming there are 20 vote eligible committee members and 1 member did not return their ballot and 2 members abstained, the number of affirmative votes required would be 12. (Sample calculation: 20 members eligble to vote 1 not returned 2 abstentions = 17 x 0.66 = 11.22 = 12 ) As always please feel free to contact me if you have any questions.

Upload: others

Post on 05-Jul-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

National Fire Protection Association

1 Batterymarch Park, Quincy, MA 02169-7471

Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org

M E M O R A N D U M

To: NFPA Technical Committee on Cultural Resources

From: Kelly Carey, Project Administrator

Date: July 14, 2015

Subject: NFPA 909 First Draft TC FINAL Ballot Results (F2016)

According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

26 Members Eligible to Vote

2 Members Not Returned (D. Nichols, J. Watts, Jr.)

20 Members Voted Affirmative on All Revisions

4 Members Voted Negative on one or more Revisions (D. Freeland, D. Moeller, C. Portway, M.

Puchovsky)

0 Members Abstained on one or more Revisions

The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of

the vote for each first revision.

There are two criteria necessary for each first revision to pass ballot: (1) simple majority and (2) affirmative 2/3

vote. The mock examples below show how the calculations are determined.

(1) Example for Simple Majority: Assuming there are 20 vote eligible committee members, 11 affirmative votes

are required to pass ballot. (Sample calculation: 20 members eligible to vote ÷ 2 = 10 + 1 = 11)

(2) Example for Affirmative 2/3: Assuming there are 20 vote eligible committee members and 1 member did not

return their ballot and 2 members abstained, the number of affirmative votes required would be 12. (Sample

calculation: 20 members eligble to vote – 1 not returned – 2 abstentions = 17 x 0.66 = 11.22 = 12 )

As always please feel free to contact me if you have any questions.

Page 2: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22+… 1/99

First Revision No. 102­NFPA 909­2015 [ Global Input ]

Replace the term "Wild fire (forest, range, urban)" with "Wildland fire (forest, brush, grass,ground) throughout the code (Figure 5.3.5.2 and Figure A.5.2.3).

Submitter Information Verification

Submitter Full Name:GREGORY HARRINGTONOrganization: NATIONAL FIRE PROTECTION ASSOCStreet Address:City:State:Zip:Submittal Date: Wed May 13 10:05:09 EDT 2015

Committee Statement

CommitteeStatement:

Terminology revised for consistency with Section 11.12, NFPA 1144, andFM 9­19 data sheet.

ResponseMessage:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.

Page 3: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22+… 2/99

Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 63­NFPA 909­2015 [ Section No. 1.2 ]

1.2* Purpose.This The purpose of this code shall prescribe minimum requirements for the protectionof be to prescribe a comprehensive program, consistent with the mission of theorganization, that protects cultural resource properties and their contents and collectionsfrom conditions or physical situations with having the potential to cause damage orloss.through a comprehensive protection program consistent with the organization’smission .1.2.1 This code shall prescribe minimum requirements for the protection of cultural resourceproperties and their contents and collections from conditions or physical situations withthe potential to cause damage or loss through a comprehensive protection programconsistent with the organization’s mission.1.2.2 Because of the special nature of cultural resource properties, this code shallsupplement existing codes and standards that apply specifically to buildings or portionsof buildings devoted to such use.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:

Page 4: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22+… 3/99

Submittal Date: Tue Apr 28 09:03:13 EDT 2015

Committee Statement

CommitteeStatement:

There are misplaced modifying phrases in the current language.It appears thecomprehensive protection program is to protect the losses. Text has beenrearranged for clarity. Deleted 1.2.2 because it is similar to 1.1.2.

ResponseMessage:Public Input No. 2­NFPA 909­2013 [Section No. 1.2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.

Page 5: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22+… 4/99

Wilson, Robert D.

First Revision No. 64­NFPA 909­2015 [ Section No. 1.6 ]

1.6* Enforcement.This code shall be administered and enforced by the authority having jurisdictiondesignated by the governing authority. (See Annex F for sample wording for enablinglegislation.)

Supplemental Information

File Name Description909_FR64_Attachment.docx New A.1.6

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 09:12:19 EDT 2015

Committee Statement

CommitteeStatement:

Proposed A.1.6 clarifies that the governing authority can include thegoverning body as defined in Ch. 3.

ResponseMessage:Public Input No. 3­NFPA 909­2013 [Section No. 1.6]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.

Page 6: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22+… 5/99

Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 66­NFPA 909­2015 [ Section No. 1.7 ]

5.2.8* Organization.The governing body shall identify a person or persons responsible for protection of thecultural resource property, its contents, collections, and operations.

Supplemental Information

File Name DescriptionFR­66_A.5.2.8.docx

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:

Page 7: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22+… 6/99

State:Zip:Submittal Date: Tue Apr 28 09:22:06 EDT 2015

Committee Statement

CommitteeStatement:

Section 1.7 is not an administrative topic as required by the Manual of Style forChapter 1. Move Section 1.7 and its annex to Section 5.2. Delete Sections 1.7.1and 1.7.2 because they are re­iterations of the definitions in Section 3.3.30 and3.3.76 respectively.

ResponseMessage:Public Input No. 4­NFPA 909­2013 [Section No. 1.7]Public Input No. 6­NFPA 909­2013 [New Section after 5.2.7]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, Luca

Page 8: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22+… 7/99

Norton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 1­NFPA 909­2015 [ Section No. 2.2 ]

2.2 NFPA Publications.National Fire Protection Association, 1 Batterymarch Park, Quincy, MA, 02169­7471.

NFPA 1, Fire Code, 2012 2015 edition.

NFPA 4, Standard for Integrated Fire Protection and Life Safety System Testing, 2015edition.

NFPA 10, Standard for Portable Fire Extinguishers, 2013 2017 edition.

NFPA 11, Standard for Low­, Medium­, and High­Expansion Foam, 2010 2016 edition.

NFPA 12, Standard on Carbon Dioxide Extinguishing Systems, 2011 2015 edition.

NFPA 12A, Standard on Halon 1301 Fire Extinguishing Systems, 2009 2015 edition.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 2016 edition.

NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2013 2016edition.

NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2012 2017edition.

NFPA 16, Standard for the Installation of Foam­Water Sprinkler and Foam­Water SpraySystems, 2011 2015 edition.

NFPA 17, Standard for Dry Chemical Extinguishing Systems, 2013 edition.

NFPA 17A, Standard for Wet Chemical Extinguishing Systems, 2013 2017 edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water­Based FireProtection Systems, 2011 2017 edition.

NFPA 30, Flammable and Combustible Liquids Code, 2012 2015 edition.

NFPA 31, Standard for the Installation of Oil­Burning Equipment, 2011 2016 edition.

NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials,2011 2016 edition.

NFPA 40, Standard for the Storage and Handling of Cellulose Nitrate Film, 2011 2016edition.

NFPA 42, Code for the Storage of Pyroxylin Plastic, 2002 edition.

NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, 2011 2015edition.

NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work,2009 2014 edition.

NFPA 54, National Fuel Gas Code, 2012 2015 edition.

Page 9: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22+… 8/99

NFPA 70®, National Electrical Code®, 2011 2017 edition.

NFPA 72®, National Fire Alarm and Signaling Code, 2013 2016 edition.

NFPA 75, Standard for the Fire Protection of Information Technology Equipment,2013 2016 edition.

NFPA 90A, Standard for the Installation of Air­Conditioning and Ventilating Systems,2012 2015 edition.

NFPA 90B, Standard for the Installation of Warm Air Heating and Air­ConditioningSystems, 2012 2015 edition.

NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial CookingOperations, 2011 2017 edition.

NFPA 101®, Life Safety Code®, 2012 2015 edition.

NFPA 110, Standard for Emergency and Standby Power Systems, 2013 2016 edition.

NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel–BurningAppliances, 2013 2016 edition.

NFPA 232, Standard for the Protection of Records, 2012 2017 edition.

NFPA 241, Standard for Safeguarding Construction, Alteration, and DemolitionOperations, 2013 edition.

NFPA 259, Standard Test Method for Potential Heat of Building Materials, 2013 edition.

NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire GrowthContribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels andWalls, 2011 2015 edition.

NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall andCeiling Interior Finish to Room Fire Growth, 2011 edition.

NFPA 505, Fire Safety Standard for Powered Industrial Trucks Including TypeDesignations, Areas of Use, Conversions, Maintenance, and Operations, 2013 edition.

NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films,2010 2015 edition.

NFPA 703, Standard for Fire Retardant–Treated Wood and Fire­Retardant Coatings forBuilding Materials, 2012 2015 edition.

NFPA 731, Standard for the Installation of Electronic Premises Security Systems,2011 2017 edition.

NFPA 750, Standard on Water Mist Fire Protection Systems, 2010 2015 edition.

NFPA 780, Standard for the Installation of Lightning Protection Systems, 2011 2017edition.

NFPA 914, Code for Fire Protection of Historic Structures, 2010 2015 edition.

NFPA 1123, Code for Fireworks Display, 2010 2014 edition.

NFPA 1144, Standard for Reducing Structure Ignition Hazards from Wildland Fire, 2013edition.

NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, 2012 2015 edition.

NFPA 2010, Standard for Fixed Aerosol Fire­Extinguishing Systems, 2010 2015 edition.

Submitter Information Verification

Page 10: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22+… 9/99

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 07:57:29 EDT 2015

Committee Statement

CommitteeStatement:

Updates NFPA referenced standards through the Fall 2016 revision cycle. Alsoadds new reference to NFPA 4 based on other first revisions.

ResponseMessage:Public Input No. 27­NFPA 909­2014 [Section No. 2.2]Public Input No. 10­NFPA 909­2014 [Chapter 2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.

Page 11: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 10/99

Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 2­NFPA 909­2015 [ Section No. 2.3.1 ]

2.3.1 ASTM Publications.ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA19428­2959.

ASTM E 84 E84 , Standard Test Method for Surface Burning Characteristics of BuildingMaterials, 2012 2015 .

ASTM E 119, E119Standard Tests Methods for Fire Tests of Building Construction andMaterials, 2012 2014

ASTM E 136 E136 , Standard Test Method for Behavior of Materials in a Vertical TubeFurnace at 750 Degrees C, 2009b 2012 .

ASTM E 1591 E1591 , Standard Guide for Obtaining Data for Deterministic Fire GrowthModels,2007 2013 .

ASTM E 2652, E2652Standard Test Method for Behavior of Materials in a Tube Furnacewith a Cone­shaped Airflow Stabilizer, at 750 Degrees C, 2009a 2012 .

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 08:42:26 EDT 2015

Committee Statement

Committee Statement: Updates ASTM referenced publications to current editions.Response Message:Public Input No. 41­NFPA 909­2014 [Section No. 2.3.1]

Ballot Results

This item has passed ballot

Page 12: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 11/99

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 3­NFPA 909­2015 [ Section No. 2.3.2 ]

Page 13: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 12/99

2.3.2 UL Publications.Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062­2096.

ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials,2011 Revised 2014 .

ANSI/UL 723, Standard for Test for Surface Burning Characteristics of BuildingMaterials, 2008, Revised 2010 2013 .

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 08:53:28 EDT 2015

Committee Statement

Committee Statement: Both UL Standards were updated and revised.Response Message:Public Input No. 47­NFPA 909­2015 [Section No. 2.3.2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.

Page 14: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 13/99

Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 4­NFPA 909­2015 [ Section No. 2.4 ]

2.4 References for Extracts in Mandatory Sections.NFPA 1, Fire Code, 2012 2015 edition.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 2016 edition.

NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work,2009 2014 edition.

NFPA 72®, National Fire Alarm and Signaling Code, 2013 2016 edition.

NFPA 90A, Standard for the Installation of Air­Conditioning and Ventilating Systems,2012 2015 edition.

NFPA 101®, Life Safety Code®, 2012 2015 edition.

NFPA 731, Standard for the Installation of Electronic Premises Security Systems,2011 2017 edition.

NFPA 805, Performance­Based Standard for Fire Protection for Light Water ReactorElectric Generating Plants, 2010 2015 edition.

NFPA 914, Code for Fire Protection of Historic Structures, 2010 2015 edition.

NFPA 921, Guide for Fire and Explosion Investigations, 2011 2017 edition.

NFPA 1141, Standard for Fire Protection Infrastructure for Land Development inWildland, Rural, and Suburban Areas, 2012 2017 edition.

NFPA 1451, Standard for a Fire and Emergency Service Vehicle Operations TrainingProgram, 2013 edition.

NFPA 5000®, Building Construction and Safety Code®, 2012 2015 edition.

Submitter Information Verification

Page 15: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 14/99

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 08:55:41 EDT 2015

Committee Statement

CommitteeStatement:

Updates NFPA referenced standards through the Fall 2016 revisioncycle.

Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, Luca

Page 16: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 15/99

Norton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 8­NFPA 909­2015 [ Section No. 3.3.5.1 ]

3.3.5.1 Fire Barrier.A continuous membrane or a membrane with discontinuities created by protectedopenings with a specified fire protection rating, where such membrane is designed andconstructed with a specified fire resistance rating to limit the spread of fire, that alsorestricts the movement of smoke . [101,2012 2015 ]

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 09:36:09 EDT 2015

Committee Statement

Committee Statement: Extract update.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative All

Page 17: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 16/99

Allshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 101­NFPA 909­2015 [ Section No. 3.3.9 ]

3.3.9 Collections.Prehistoric and , historic, or religious objects, works of art, scientific specimens,religious objects, archival documents, archeological sites and artifacts, library media,and cultural materials assembled according to some rational scheme and maintained forthe purpose of preservation, research, study, exhibition, publication, or interpretation.

Submitter Information Verification

Submitter Full Name:GREGORY HARRINGTONOrganization: NATIONAL FIRE PROTECTION ASSOCStreet Address:City:State:Zip:Submittal Date: Wed May 13 09:47:22 EDT 2015

Committee Statement

Page 18: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 17/99

CommitteeStatement:

Definition revised to include outdoor collections and reworded for clarity.

Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 17­NFPA 909­2015 [ Section No. 3.3.26 ]

Page 19: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 18/99

3.3.26 Fire Model.Mathematical prediction of fire growth, environmental conditions, and potential effects onstructures, systems, or components based on the conservation equations and orempirical data. [805,2010 2015 ]

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 09:48:30 EDT 2015

Committee Statement

Committee Statement: Extract update.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.

Page 20: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 19/99

Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 67­NFPA 909­2015 [ Section No. 3.3.41 ]

See FR­100 3.3.41 Impairment.A shutdown of a protection system or a portion thereof. An abnormal condition where asystem, component, or function is out of order, and the condition can result in thesystem or unit not functioning when required. [ 72 , 2016]3.3.41.1* Emergency Impairment.An abnormal condition where a system, component, or function is out of order due to anunexpected deficiency. [ 72 , 2016]3.3.41.2* Planned Impairment.An abnormal condition where a system, component, or function is out of service due towork that has been planned in advance. [ 72 , 2016]

Supplemental Information

File Name Description909_FR67_Attachment.docx New A.3.3.41.1 and A.3.3.41.2

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 09:30:09 EDT 2015

Committee Statement

Committee Current definition does not cover all types of impairments. Impairments involve

Page 21: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 20/99

Statement: more than system shutdown. This definition is extracted from NFPA 72.ResponseMessage:

Public Input No. 19­NFPA 909­2014 [New Section after 3.3.41]Public Input No. 18­NFPA 909­2014 [Section No. 3.3.41]Public Input No. 20­NFPA 909­2014 [New Section after 3.3.41]Public Input No. 23­NFPA 909­2014 [New Section after A.3.3.41]Public Input No. 24­NFPA 909­2014 [New Section after A.3.3.41]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

Page 22: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 21/99

First Revision No. 47­NFPA 909­2015 [ Section No. 3.3.83.4 ]

3.3.83.4 Fire Protection System.Any fire alarm device or system, or fire extinguishing device or system, or theircombination thereof , that is designed and installed for detecting, controlling, orextinguishing a fire or otherwise alerting occupants, or the fire department, or both, that afire has occurred. [1141,2012 2017 ]

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 10:34:05 EDT 2015

Committee Statement

Committee Statement: Extract update.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, Grant

Page 23: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 22/99

Doyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 48­NFPA 909­2015 [ Section No. 3.3.83.5 ]

3.3.83.5 Sprinkler System.A system that consists of an integrated network of piping designed in accordance withfire protection enginering engineering standards that includes a water supply source, awater control valve, a waterflow alarm, and a draing and is commonly activated by heatfrom a fire, discharging water over the fire area drain. The portion of the sprinkler systemabove ground is a network of specifically sized or hydraulically designed piping installedin a building, structure, or area, generally overhead, and to which sprinklers are attachedin a systematic pattern. The system is commonly activated by heat from a fire anddischarges water over the fire area. [13,2013 2016 ]

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 10:37:31 EDT 2015

Committee Statement

CommitteeStatement:

Extract update. ***NOTE NOT ALL UNDERLINED TEXT IS NEW ­SYSTEM ERROR***

Page 24: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 23/99

ResponseMessage:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 70­NFPA 909­2015 [ Section No. 7.4.2 ]

Page 25: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 24/99

7.4.2 As a minimum, records of the following shall be kept:

(1) The protection plan

(2) Training of staff and volunteers, including fire evacuation drills, damage limitation,and use of portable fire extinguishers

(3) Testing Inspection , inspection testing , and maintenance reports for all fire safetyequipment and systems, including records of actions taken to correct deficiencies

(4) As­built plans, specifications, wiring and layout diagrams, and acceptance testreports for all fire protection systems (e.g., fire detection and alarm systems,automatic fire suppression systems)

(5) Inspection reports by local code enforcement officials, the authority havingjurisdiction, local fire service officials, and insurance loss control representatives,including records of actions taken to correct deficiencies identified during eachinspection

(6) Fire protection systems actuation and alarm reports that include information on thecause of the alarm or activation, the response, and any corrective action(s) taken

(7) Full reports of all fire incidents, including the cause, extent of damage, response,and recovery activities

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 13:47:41 EDT 2015

Committee Statement

CommitteeStatement:

Editorial change to list Inspection, testing, and maintenance as used in theITM standards such as NFPA 25.

ResponseMessage:Public Input No. 12­NFPA 909­2014 [Section No. 7.4.2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Page 26: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 25/99

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 51­NFPA 909­2015 [ Section No. 8.3.5.2.1 ]

Page 27: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 26/99

8.3.5.2.1 Approved, listed, delayed­egress locking systems shall be permitted to be installed ondoor assemblies serving low and ordinary hazard contents in buildings protectedthroughout by an approved, supervised automatic fire detection system in accordancewith NFPA 72, National Fire Alarm and Signaling Code , or an approved, supervisedautomatic sprinkler system in accordance with NFPA 13, Standard for the Installation ofSprinkler Systems , and where permitted by the authority having jurisdiction, providedthat all of the following criteria are met:

(1) The door leaves shall unlock in the direction of egress upon actuation of one of thefollowing:

(a) Approved, supervised automatic sprinkler system in accordance with NFPA13, Standard for the Installation of Sprinkler Systems

(b) Not more than one heat detector of an approved, supervised automatic firedetection system in accordance with NFPA 72, National Fire Alarm andSignaling Code

(c) Not more than two smoke detectors of an approved, supervised automatic firedetection system in accordance with NFPA 72, National Fire Alarm andSignaling Code

(2) The door leaves shall unlock in the direction of egress upon loss of powercontrolling the lock or locking mechanism.

(3) An irreversible process shall release the lock in the direction of egress within 15seconds, or 30 seconds where approved by the authority having jurisdiction, uponapplication of a force to the release device under all of the following conditions:

(a) The force shall not be required to exceed 67 N (15 lbf).

(b) The force shall not be required to be continuously applied for more than 3seconds.

(c) The initiation of the release process shall activate an audible signal in thevicinity of the door opening.

(d) Once the lock has been released by the application of force to the releasingdevice, relocking shall be by manual means only.

(4) A readily visible, durable sign in letters not less than 25 mm (1 in.) high and notless than 3.2 mm (1∕8 in.) in stroke width on a contrasting background that reads asfollows shall be located on the door leaf adjacent to the release device in thedirection of egress:

PUSH UNTIL ALARM SOUNDSDOOR CAN BE OPENED IN 15 SECONDS

(5) The egress side of doors equipped with delayed­egress locks shall be providedwith emergency lighting in accordance with Section 7.9 of NFPA 101 .[ 101: 7.2.1.6.1.1]The egress side of doors equipped with delayed­egress locks shall be providedwith emergency lighting in accordance with Section 7.9 of NFPA 101 .[ 101: 7.2.1.6.1.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]

Page 28: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 27/99

Street Address:City:State:Zip:Submittal Date: Thu Apr 16 13:20:43 EDT 2015

Committee Statement

Committee Statement: Extract update.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, Chris

Page 29: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 28/99

Puchovsky, Milosh T.Wilson, Robert D.

First Revision No. 71­NFPA 909­2015 [ New Section after 8.3.5.2.2 ]

8.3.5.3 Access­Controlled Egress Door Assemblies.Where provided, access­controlled egress door assemblies shall comply with NFPA101 .

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 13:51:09 EDT 2015

Committee Statement

CommitteeStatement:

The FR provides a reference to NFPA 101 for access­controlled egress doorassemblies where they are used.

ResponseMessage:Public Input No. 7­NFPA 909­2014 [New Section after 8.3.5.2.2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, Nicholas

Page 30: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 29/99

Brady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 103­NFPA 909­2015 [ New Section after 8.4 ]

8.5* Vacant Areas.Structures or portions thereof that are vacant shall be included in the vulnerabilityassessment required by Section 8.1.

Supplemental Information

File Name Description909_FR103_Attachment.docx New Sec. A.8.5

Submitter Information Verification

Submitter Full Name:GREGORY HARRINGTONOrganization: NATIONAL FIRE PROTECTION ASSOCStreet Address:City:State:Zip:Submittal Date: Wed May 13 10:10:28 EDT 2015

Committee Statement

Page 31: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 30/99

CommitteeStatement:

New provision adds requirement and guidance on including vacant areas in thesecurity vulnerability assessment.

ResponseMessage:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

Page 32: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 31/99

First Revision No. 104­NFPA 909­2015 [ Section No. 9.7.1 [Excluding

any Sub­Sections] ]

The project team shall identify conditions that could contribute to the loss of property,including but not limited to the structure, site, and collections, by fire; foreseeablecrimes; deliberate acts of third parties, staff, or visitors; or other events with the potentialto cause damage or loss in the areas affected by the project.

Submitter Information Verification

Submitter Full Name:GREGORY HARRINGTONOrganization: NATIONAL FIRE PROTECTION ASSOCStreet Address:City:State:Zip:Submittal Date: Wed May 13 10:42:12 EDT 2015

Committee Statement

CommitteeStatement:

Revision expands provision to include outdoor collections andarchaeological sites.

ResponseMessage:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, Grant

Page 33: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 32/99

Doyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 72­NFPA 909­2015 [ Section No. 9.12.13.3 ]

9.12.13.3* Corrosion Protection.Preaction and dry pipe systems shall be designed to minimize the risk of corrosion inaccordance with the requirements of 9.12.13.3.1 through 9.12.13.3.6.5.9.12.13.3.1* Branch lines shall be pitched at least 4 mm/m (1∕2 in. per 10 ft), and mains shall bepitched at least 2 mm/m (1∕4 in. per 10 ft).9.12.13.3.2 Auxiliary Drains.Auxiliary drains shall be provided at all dry system low points in accordance withNFPA 13 .9.12.13.3.2.1* Auxiliary drains shall be provided at all low points in accordance with preaction systemlow points in accordance with the NFPA 13 , Standard for the Installation of SprinklerSystems , requirements for dry pipe systems and preaction systems whether thepreaction system piping subject to freezing or not .9.12.13.3.2.2 Auxiliary drains shall be opened and water drained periodically, be operated inaccordance with the requirements of NFPA 25Standard for the Inspection, Testing, andMaintenance of Water­Based Fire Protection Systems .9.12.13.3.3* Where steel pipe is used in dry pipe and preaction systems, the provisions of NFPA13 , Standard for the Installation of Sprinkler Systems , shall be applied assuming itshall be assumed that the water supplies and environmental conditions that contributeto unusual corrosive properties, and a plan shall be developed to address pipingcorrosion .

Page 34: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 33/99

9.12.13.3.4 A corrosion protection plan shall be developed to address piping corrosion inaccordance with NFPA 13 .9.12.13.3.5 Sprinkler piping and fittings shall be inspected annually for signs of corrosion, leakage,and physical damage, in accordance with NFPA 25, Standard for the Inspection,Testing, and Maintenance of Water­Based Fire Protection Systems .9.12.13.3.6* Interior corrosion inspections of system piping and valves An internal corrosionevaluation of system piping shall be conducted at intervals not to exceed 5 years. Thepiping inspection shall include a physical inspection of the piping interior near thesprinkler riser and the removal of at least one end cap from a system main. Wherepitting, nodules, tubercles, or carbuncles are present, an obstruction investigation shallbe conducted in accordance with the requirements of NFPA 25 , Standard for theInspection, Testing, and Maintenance of Water­Based Fire Protection Systems . Repairsshall be made as necessary.9.12.13.3.6.1 The evaluation shall include an internal inspection of the piping condition near thesprinkler riser and the opening of the flushing connection on a system main.9.12.13.3.6.2 Alternative nondestructive examination methods shall be permitted.9.12.13.3.6.3 Where the inspection or examinations required by 9.12.13.3.6.1 or9.12.13.3.6.3 reveal that pitting, nodules, tubercles, or carbuncles are present, anobstruction investigation shall be conducted in accordance with the requirements ofNFPA 25 .9.12.13.3.6.4 Repairs shall be made as necessary.9.12.13.3.6.5 Nonmetallic pipe shall not be required to be inspected internally.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 13:59:50 EDT 2015

Committee Statement

Committee Statement: Text revised to clarify its intent.Response Message:Public Input No. 13­NFPA 909­2014 [Section No. 9.12.13.3]

Ballot Results

This item has passed ballot

Page 35: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 34/99

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 69­NFPA 909­2015 [ New Section after 9.12.16 ]

9.12.17* Testing of Integrated Systems.Integrated fire protection and life safety systems shall be tested in accordance withNFPA 4 .

Supplemental Information

Page 36: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 35/99

File Name Description909_FR69_Attachment.docx New A.9.12.17

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 13:10:31 EDT 2015

Committee Statement

CommitteeStatement:

Most facilities have integrated fire protection and life safety systems the requiretesting as a part of the acceptance process. NFPA 4 provides the requirements forsuch testing.

ResponseMessage:Public Input No. 28­NFPA 909­2014 [New Section after 9.12.16]Public Input No. 46­NFPA 909­2014 [New Section after A.9.14.26.1.2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, Cindy

Page 37: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 36/99

Harrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 74­NFPA 909­2015 [ Section No. 9.12.21 ]

9.12.22* Lightning Protection.A lightning protection system, where required, shall be designed, installed, andmaintained in accordance with NFPA 780, Standard for the Installation of LightningProtection Systems .

Supplemental Information

File Name Description909_FR75_Attachment.docx New A.9.12.21

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 14:19:23 EDT 2015

Committee Statement

CommitteeStatement:

The proposed annex text provides the user of the standard with information on thesource of risk assessment procedures which may be used to determine whenlightning protection should be provided.

ResponseMessage:Public Input No. 49­NFPA 909­2015 [New Section after A.9.12.19]

Page 38: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 37/99

Public Input No. 48­NFPA 909­2015 [Section No. 9.12.21]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 76­NFPA 909­2015 [ Section No. 9.12.23.4.1.4(C) ]

Page 39: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 38/99

(C) Where the automatic fire suppression is provided by automatic fire sprinkler systems,the systems shall be wet pipe, single interlock preaction, or single non­interlockpreaction systems.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 14:22:04 EDT 2015

Committee Statement

Committee Statement: The correct system types are "single interlock" and "non­interlock".Response Message:Public Input No. 15­NFPA 909­2014 [Section No. 9.12.23.4.1.4(C)]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.

Page 40: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 39/99

Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 77­NFPA 909­2015 [ Section No. 9.12.24.5.1 ]

9.12.25.5.1* Temporary walls and exhibit components shall not interfere with the following:

(1) Coverage for fire alarm notification appliances

(2) Operation of fire alarm manual station or automatic detection device

(3) Spacing of and location of automatic fire sprinklers

(4) Operation of other automatic fire suppression system

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 14:22:41 EDT 2015

Committee Statement

CommitteeStatement:

Spacing is only one consideration. Sprinkler operating area, obstructions tospray pattern, and other considerations also apply.

ResponseMessage:Public Input No. 16­NFPA 909­2014 [Section No. 9.12.24.5.1]

Ballot Results

This item has passed ballot

Page 41: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 40/99

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 52­NFPA 909­2015 [ Section No. 9.14.13.1.2.1 ]

9.14.13.1.2.1 Where detectors are installed for signal initiation during construction, they shall becleaned and verified to be operating in accordance with the listed sensitivity, or theyshall be replaced prior to the final commissioning acceptance test of the system.[72:17.7.1.11.1]

Page 42: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 41/99

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 13:35:36 EDT 2015

Committee Statement

Committee Statement: Extract update.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.

Page 43: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 42/99

Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 53­NFPA 909­2015 [ Section No. 9.14.13.1.2.2 ]

9.14.13.1.2.2 Where detectors are installed but not operational during construction, they shall beprotected from construction debris, dust, dirt, and damage in accordance with themanufacturer’s recommendations and verified to be operating in accordance with thelisted sensitivity, or they shall be replaced prior to the final commissioning acceptancetest of the system. [72:17.7.1.11.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 13:36:57 EDT 2015

Committee Statement

Committee Statement: Extract update.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Page 44: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 43/99

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 78­NFPA 909­2015 [ Section No. 9.14.13.3.2 ]

9.14.13.3.2 Class I manual dry standpipes manual standpipes shall be permitted where approved bythe authority having jurisdiction.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 14:29:24 EDT 2015

Committee Statement

Page 45: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 44/99

CommitteeStatement:

Class I manual standpipe systems, regardless if wet or dry, rely exclusively on thefire department connection to supply the system demand and therefore should onlybe permitted with AHJ approval.

ResponseMessage:Public Input No. 8­NFPA 909­2014 [Section No. 9.14.13.3.2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned22 Affirmative All0 Affirmative with Comments2 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisWilson, Robert D.

Negative with CommentMoeller, Donald C. Manual standpipes should be allowed in any low­rise building, even without approval of theAHJ. (See section 5.4.1.1 of NFPA 14). I think the original section was to allow dry standpipes

Page 46: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 45/99

where they might otherwise be wet. I don't think the intent of the committee is to requireautomatic standpipe water supply unless specifically approved otherwise.Puchovsky, Milosh T. As a result of the ballot circulation, I change my vote to "Negative" on FR­78 based on thecomments provided by Don Moeller in his negative vote.

First Revision No. 79­NFPA 909­2015 [ Section No. 9.14.13.5.1 ]

9.14.13.5.1 Portable fire extinguishers listed for the purpose, shall be located, mounted, andmaintained in provided in accordance with NFPA 10, Standard for Portable FireExtinguishers .

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 14:31:24 EDT 2015

Committee Statement

CommitteeStatement:

Portable fire extinguishers are required to be listed and labeled by NFPA 10.Stating “listed for the purpose” is confusing and unnecessary.

ResponseMessage:Public Input No. 30­NFPA 909­2014 [Section No. 9.14.13.5.1]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Page 47: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 46/99

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 80­NFPA 909­2015 [ Section No. 9.14.13.5.2 ]

9.14.13.5.2* At least one Not less than one portable fire extinguisher listed for the purpose, shall beaccessible as required by 9.14.13.5.1 shall be provided on each floor near each usablestairway.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 14:31:44 EDT 2015

Committee Statement

Page 48: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 47/99

CommitteeStatement:

Extinguishers are required to be installed throughout the building by 9.14.13.5.1.This paragraph is only referring to one of those extinguishers.

Portable fire extinguishers are required to be listed and labeled by NFPA 10.Stating “listed for the purpose” is confusing and unnecessary.

ResponseMessage:Public Input No. 31­NFPA 909­2014 [Section No. 9.14.13.5.2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

Page 49: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 48/99

First Revision No. 81­NFPA 909­2015 [ Section No. 9.14.13.5.3 ]

9.14.13.5.3 Fire extinguishers, listed for the purpose Portable fire extinguishers shall be accessibleand protected from accidental damage.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 14:32:10 EDT 2015

Committee Statement

CommitteeStatement:

Portable fire extinguishers are required to be listed and labeled by NFPA 10.Stating “listed for the purpose” is confusing and unnecessary.

ResponseMessage:Public Input No. 32­NFPA 909­2014 [Section No. 9.14.13.5.3]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, Grant

Page 50: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 49/99

Doyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 82­NFPA 909­2015 [ Section No. 9.14.25.5 ]

9.14.25.5* A portable fire extinguisher, listed for the purpose, shall be located within 9 m (30 ft) ofall portable heating devices. The travel distance from all portable heating devices to notless than one portable fire extinguisher complying with NFPA 10 shall not exceed 9 m(30 ft).

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 14:53:51 EDT 2015

Committee Statement

CommitteeStatement:

Extinguishers are required to be installed throughout the building by 9.14.13.5.1.This requirement is for an additional extinguisher for portable heating equipment.

ResponseMessage:Public Input No. 34­NFPA 909­2014 [Section No. 9.14.25.5]

Page 51: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 50/99

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 83­NFPA 909­2015 [ Section No. 9.14.26.1.2 ]

Page 52: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 51/99

9.14.26.1.2* Fire extinguishers, listed for the purpose, shall be located as required in 16.7.1.6 ofNFPA 1, Fire Code .

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:15:42 EDT 2015

Committee Statement

CommitteeStatement:

Portable fire extinguishers are required to be listed and labeled by NFPA 10.Stating “listed for the purpose” is confusing and unnecessary.

ResponseMessage:Public Input No. 35­NFPA 909­2014 [Section No. 9.14.26.1.2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.

Page 53: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 52/99

Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 85­NFPA 909­2015 [ Section No. 11.4.5 ]

11.4.5 Air plenums Plenums and void spaces shall not be used for storage and shall be keptclean and free of combustibles.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:19:24 EDT 2015

Committee Statement

CommitteeStatement:

The term "plenum" is defined as a "compartment or chamber to which one or moreair ducts are connected and that forms part of the air distribution

system." The term "air plenum" is not defined. Also, NFPA 90A, which regulatesplenums, states that plenums shall not be used for storage.

ResponseMessage:Public Input No. 42­NFPA 909­2014 [Section No. 11.4.5]

Ballot Results

This item has passed ballot

26 Eligible Voters

Page 54: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 53/99

2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 86­NFPA 909­2015 [ Section No. 11.4.8.1 ]

11.4.8.1 Combustible packing materials, such as shredded paper, Styrofoam™ foamedpolystyrene packing material (“peanuts”), plastic, and excelsior, shall be stored in metalcontainers with self­closing covers.

Submitter Information Verification

Page 55: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 54/99

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:21:56 EDT 2015

Committee Statement

CommitteeStatement:

Styrofoam is the trade mark for foamed polystyrene by Dow. The genericterm is "foamed polystyrene".

ResponseMessage:Public Input No. 43­NFPA 909­2014 [Section No. 11.4.8.1]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.

Page 56: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 55/99

Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 87­NFPA 909­2015 [ Section No. 11.5 ]

11.5* Smoking.Smoking shall be prohibited inside buildings except in designated areas that meet thefollowing requirements:

(1) Smoking areas shall be clearly and publicly identified.

(2) Smoking areas shall be provided with suitable ashtrays and other receptacles forthe proper disposal of smoking materials.

(3) Smoking areas shall be physically separated from the rest of the building with aminimum 1­hour fire resistance rating for walls, ceilings, and floors.

(4) A rated, fully charged, and operable portable fire extinguisher complying Portablefire extinguishers shall be provided in accordance with NFPA 10 with NFPA10Standard for Portable Fire Extinguishers shall be located at each designatedsmoking area.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:23:31 EDT 2015

Committee Statement

CommitteeStatement:

This requirement is for an additional extinguisher for the smoking area. The FRadds a reference to NFPA 10 rather than specifying the type and size ofextinguisher.

ResponseMessage:Public Input No. 36­NFPA 909­2014 [Section No. 11.5]

Ballot Results

Page 57: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 56/99

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 88­NFPA 909­2015 [ Section No. 11.7.2 ]

Page 58: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 57/99

11.7.2 Precautions.The following precautions shall be taken to control open flame and flame­producingdevices:

(1) All employees working around open flame or flame­producing devices shall betrained in the proper use and operation of the device and in emergency responseprocedures.

(2) Open flames and flame­producing devices shall be monitored constantly by atrained person.

(3) A fire extinguisher, listed for the purpose, shall be located within 9 m (30 ft) of thearea where open flames or flame­producing devices are in use. The travel distancefrom any area where open flames or flame­producing devices are in use to not lessthan one portable fire extinguisher complying with NFPA 10 shall not exceed 9 m(30 ft).

(4) Candles shall be kept a minimum of 1.25 m (4 ft) from combustible windowtreatments and wall or ceiling hangings.

(5) Fireplaces shall be covered with a fire screen when not used for cooking or similardemonstrations.

(6) Open flames within 31 m (100 ft) of the building shall not be left unattended.

(7) Open flames either inside or outside the building shall be extinguished prior toshutdown of the facility.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:25:57 EDT 2015

Committee Statement

CommitteeStatement:

The FR adds a reference to NFPA 10 rather than specifying the type andsize of extinguisher.

ResponseMessage:Public Input No. 37­NFPA 909­2014 [Section No. 11.7.2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments

Page 59: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 58/99

0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 105­NFPA 909­2015 [ New Section after 11.7.3.2 ]

11.7.3.3 Vegetation within 3050 mm (10 ft) of a chimney outlet shall be removed.

Submitter Information Verification

Submitter Full Name:GREGORY HARRINGTONOrganization: NATIONAL FIRE PROTECTION ASSOCStreet Address:City:State:Zip:

Page 60: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 59/99

Submittal Date: Wed May 13 10:46:59 EDT 2015

Committee Statement

Committee Statement: New provision for consistency with FM Data Sheet 9­19.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

Page 61: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 60/99

First Revision No. 89­NFPA 909­2015 [ Section No. 11.10 ]

11.10 Fire Proofing Structural Fire Protection .The fire safety manager shall inspect accessible structural fire proofing protectionregularly to ensure the material is in place and maintained in good condition.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:28:36 EDT 2015

Committee Statement

CommitteeStatement:

The FR replaces the term "fire proofing" with industry acceptedterminology.

Response Message:Public Input No. 44­NFPA 909­2014 [Section No. 11.10]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.

Page 62: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 61/99

Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 90­NFPA 909­2015 [ Section No. 11.11 ]

11.11* Lightning Protection.The fire safety manager shall ensure that the lightning protection system, whereinstalled, is inspected and maintained in good working condition by qualified personnel.(SeeNFPA 780, Standard for the Installation of Lightning Protection Systems .)

Supplemental Information

File Name Description909_FR90_Attachment.docx New A.11.11

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:31:15 EDT 2015

Committee Statement

CommitteeStatement:

The proposed annex text provides the user of the standard with information on thesource of risk assessment procedures which may be used to determine whenlightning protection should be provided.

Response

Page 63: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 62/99

Message:Public Input No. 50­NFPA 909­2015 [Section No. 11.11]Public Input No. 51­NFPA 909­2015 [New Section after A.11.6.1.2]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 106­NFPA 909­2015 [ Section No. 11.12.1 ]

Page 64: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 63/99

11.12.1* The governing body of a cultural resource property located in a wooded area orsurrounded by fire­prone vegetation or heavy brush shall incorporate the requirements ofNFPA 1144Standard for Reducing Structure Ignition Hazards from Wildland Fire , intothe fire safety management component of the protection plan.

Supplemental Information

File Name Description909_FR106_Attachment.docx New A.11.12.1

Submitter Information Verification

Submitter Full Name:GREGORY HARRINGTONOrganization: NATIONAL FIRE PROTECTION ASSOCStreet Address:City:State:Zip:Submittal Date: Wed May 13 10:51:48 EDT 2015

Committee Statement

CommitteeStatement:

New A.12.1 provides guidance on protection of archaeological sites andoutdoor collections from wildland fires.

ResponseMessage:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, Grant

Page 65: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 64/99

Doyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 97­NFPA 909­2015 [ Section No. 12.2.1 ]

12.2.1 Fire protection systems shall be inspected, tested, and maintained in accordance withthe manufacturer’s recommendations and the requirements of one of the following, asapplicable:

(1) The applicable code or standard from Table 9.12.14

(2) NFPA 4 , Standard for Integrated Fire Protection and Life Safety System Testing

(3) NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water­BasedFire Protection Systems

(4) NFPA 72, National Fire Alarm and Signaling Code

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Fri May 01 14:56:31 EDT 2015

Committee Statement

Page 66: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 65/99

CommitteeStatement:

NFPA 4 is a new standard that should be referenced in this code as mostfacilities have integrated systems that will require periodic testing.

ResponseMessage:Public Input No. 26­NFPA 909­2014 [Section No. 12.2.1]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned22 Affirmative All0 Affirmative with Comments2 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPuchovsky, Milosh T.Wilson, Robert D.

Negative with CommentFreeland, Deborah L. While I concur that the commissioning required by NFPA 4, the retroactivity requirement forexisting buildings, with the responsibility for obtaining documentation and generating testingprocedures resting on the owner, could be quite onerous for especially a historic cultural

Page 67: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 66/99

resource property, with limited resources.Portway, Chris NFPA 4 appears to require retroactive commissioning of existing systems, and relies onowners to produce information on old, existing systems (that sometimes simply does not exist).It also appears to require owners to have specific technical expertise, including the ability todevelop testing requirements. Representing an owner with numerous large and older culturalresource facilities, but also with very limited resources, these requirements may be veryburdensome. While NFPA 4 is a necessary improvement for integrated systems, I believe itneeds work in these specific areas.

First Revision No. 92­NFPA 909­2015 [ Section No. 12.11 ]

12.11 Fire Extinguishers.Portable fire extinguishers shall be inspected, tested, and maintained in accordancewith NFPA 10, Standard for Portable Fire Extinguishers .

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:36:19 EDT 2015

Committee Statement

CommitteeStatement:

The FR references NFPA 10 for inspection, testing and maintenancerequirements, which includes hydrostatic testing.

ResponseMessage:Public Input No. 38­NFPA 909­2014 [Section No. 12.11]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not Returned

Page 68: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 67/99

Nichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 93­NFPA 909­2015 [ Section No. 13.4.3 ]

13.4.3 Not less than one portable fire extinguisher, listed for the purpose, shall be locatedwithin 3 m 3050 mm (10 ft) of any cooking, food­ warming, or related operation and shallbe identified clearly.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:38:00 EDT 2015

Page 69: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 68/99

Committee Statement

CommitteeStatement:

Portable fire extinguishers are required to be listed and labeled by NFPA 10. Stating“listed for the purpose” is confusing and unnecessary. Added the word “food” forclarification.

ResponseMessage:Public Input No. 39­NFPA 909­2014 [Section No. 13.4.3]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

Page 70: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 69/99

First Revision No. 94­NFPA 909­2015 [ Section No. 13.4.4 ]

13.4.4 Fire extinguishers provided for the protection of cooking appliances that use combustiblecooking media (vegetable or animal oils and fats) shall be listed and labeled for Class Kfires and installed in accordance with NFPA 10, Standard for Portable FireExtinguishers .

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:39:08 EDT 2015

Committee Statement

Committee Statement: Clarification.Response Message:Public Input No. 40­NFPA 909­2014 [Section No. 13.4.4]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, Grant

Page 71: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 70/99

Doyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 100­NFPA 909­2015 [ Section No. A.3.3.41 ]

A.3.3.41 Impairment. Impairments can be classified as either of the following types:

Emergency, a condition where fire protection systems or equipment or a portionthereof is out of order due to an unexpected occurrence, such as a rupturedsprinkler pipe, or device or component failure

Preplanned, a condition where a fire protection system or equipment or a portionthereof is out of service due to work that has been planned in advance, such asmodifications to the water supply or sprinkler system piping

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Fri May 01 15:11:25 EDT 2015

Committee Statement

Page 72: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 71/99

CommitteeStatement:

Added definitions for emergency and planned impairments to the body ofthe standard.

ResponseMessage:Public Input No. 22­NFPA 909­2014 [Section No. A.3.3.41]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

Page 73: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 72/99

First Revision No. 54­NFPA 909­2015 [ Section No. A.8.1.1 ]

A.8.1.1 NFPA 730, Guide for Premises Security , provides guidance on conducting securityvulnerability assessments and developing appropriate countermeasures.

As outlined in NFPA 730, a security vulnerability assessment (SVA) usually involves aseven­step process as follows:

Step 1: Formation of Team. The process should begin with the formation of a team ofpersonnel from all organizational areas. Commonly, the individual responsible for anorganization's security serves as team leader.

Step 2: Organization/Facility Characterization. Step 2 involves a characterization of anorganization and the facilities to be protected. It includes identification of assets (i.e.,people, property, information, and products); physical features and operations; laws,regulations, and corporate policies; social and political environment and internal activity(i.e., community resources, crime statistics, internal activities, and loss experience); andreview of “current layers of protection,” including both site security features and safetymeasures.

Step 3: Threat Assessment. The next step is conducting a threat assessment. Theprocess includes a classification of critical assets, identification of potential targets,consequence analysis (effect of loss, including any potential off­site consequence), andthe definition of potential threats (by identifying potential adversaries and what is knownabout them).

Step 4: Threat Vulnerability Analysis. The next step is conducting a threat vulnerabilityanalysis that identifies actual and potential threat scenarios and estimates a relativesecurity risk level. The relative security risk level is a function of determining theseverity of the consequences of an adversarial event, the potential for such an attack,and the likelihood of adversary success in carrying out the anticipated event or activity.

Step 5: Definition of Specific Security Countermeasures. In this step, specific securitycountermeasures are defined. All information from the preceding steps, includingcharacterization, threat assessment, and vulnerability analysis, is considered. Aneffective countermeasure is one that drives improvements in mitigating the definedthreats and results in a reduction in the security risk level.

With respect to the development of security countermeasures, and in consideration ofthe defined threats, the SVA team's efforts to strengthen the security layers ofprotection begins with a focus on the concentric circles of protection designmethodology, shown in Figure A.8.1.1.

Figure A.8.1.1 Concentric Circles of Protection. (Source: SafePlaceCorporation.) [730:Figure A.5.2.3(2 5 )]

Page 74: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 73/99

This methodology provides for protection of defined critical assets by considering thefollowing four primary protection elements of an effective protection plan design:

(1) Deter — discouraging an adversary from attempting an assault by reducing thelikelihood of a successful attack.

(2) Detect — determining that an undesirable event has occurred or is occurring.Detection includes sensing the event, communicating the alarm to an attendedlocation, and assessing the alarm.

(3) Delay — impeding adversary penetration into a protected area.

(4) Respond — counteracting adversary activity and interrupting the undesirable event.

Arson, theft, sabotage, or other malevolent acts can be prevented in two ways, by eitherdeterring the adversary or defeating the adversary. In the development of securitycountermeasures, it is important to understand that a properly designed andimplemented security program integrates people, procedures, and technologies for theprotection of assets. The use of technologies alone is not the solution.

The “new world” we live in poses a new challenge: the increased presence and threat ofadversarial attack. Our journey now involves an important dual approach, thecombination of today's security methodologies with traditional safety and riskmanagement practices to strengthen security layers of protection.

An effective security program, resulting from the completion and implementation of acomprehensive SVA, provides measurable benefits in the workplace for personnel (staff,guests, and visitors), in the protection of property, and in operations, resulting inenhanced business performance.

Step 6: Assessment of Risk Reduction. Taking into account the countermeasuresdefined in Step 5, this step reassesses the relative security risk levels developed inStep 4 and considers additional security risk reduction measures (securitycountermeasures) where appropriate.

Step 7: Documentation of Findings and Tracking of Implementation. Findings andrecommendations are documented in a report and the implementation of acceptedrecommendations is tracked.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Page 75: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 74/99

Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 13:41:50 EDT 2015

Committee Statement

Committee Statement: Extract update.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, Sheila

Page 76: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 75/99

Portway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 84­NFPA 909­2015 [ Section No. A.9.12.13 ]

A.9.12.13 See Table A.9.12.13 for known advantages and potential concerns associated withvarious types of automatic sprinkler systems, piping materials, and types of sprinklers.Table A.9.12.13 Considerations for Automatic Sprinkler System Types and Materials

Known Advantages Potential ConcernsTypes ofSystemsWet pipe Traditional high reliability

systems with water underpressure in piping at alltimes using heat­actuatedsprinklers; lowestmaintenance requirements ofall system types

Mechanical damage to sprinklers or piping inlow­ceiling areas, overheating, and freezingcan all result in discharge of water

Antifreeze Advantages of wet pipesystems with reducedconcern for freezing

Traditional antifreeze Antifreeze solutions arenow limited restricted to those that are listedfor use in fire sprinkler systems due toconcerns for combustibility of sprinkler spray,especially for small orifice sprinklers at highpressures

Dry pipe Air or nitrogen in pipingunder moderate pressure 2–3 bar [(30–40 psi) nominal]protects against freezing andprevents water discharge inthe event of small leaks

Air Reduced reliability due to increasedmaintenance requirements; 30% increase inwater demand; air in piping with residual watercan lead to premature corrosion of steel pipingsystems; mechanical damage to sprinklers orpiping will result in water flow; water supplymust be in a heated area

Preaction— single­interlock

Requires separate detectionsystem to activate beforewater is introduced to piping;protects against freezing andprevents discharge of waterin the event of mechanical orcorrosion damage tosprinklers or piping

Reduced reliability due to dependence onseparate detection system; air in piping withresidual water can lead to premature corrosionof steel piping systems; significantly higherlevel of regular maintenance

Preaction— double­interlock

Requires both detectionsystem and at least onesprinkler to activate beforewater is introduced to piping;best protection foroccupancies such asfreezers where water inpiping can alone be a

Slowest system response to fires; reducedreliability due to dependence on separatedetection system; air in piping with residualwater can lead to premature corrosion of steelpiping systems; significantly higher level orregular maintenance

Page 77: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 76/99

concernPreaction— non­interlock

Water entering piping withactivation of either detectionsystem or sprinklerincreases reliability overother types of preactionsystems while excludingwater in normal readycondition; protects againstfreezing

Does not provide added protection againstrelease of water in the event of mechanical orcorrosion damage to sprinklers for piping; air inpiping with residual water can lead topremature corrosion of steel piping systems

Preaction— pre­primed

Requires separate detectionsystem to activate to allowwater to enter piping inexcess of priming water,limiting potential discharge inthe event of mechanical orcorrosion damage tosprinklers or piping

Reduced reliability due to dependence onseparate detection system

Deluge Ability to quickly dischargelarge quantities of waterappropriate for specialhazards only

Activation results in water dischargethroughout protected area; air in piping withresidual water can lead to premature corrosionof steel piping systems

Water mist Can provide performancesimilar to traditional sprinklersystems using less water;smaller pipe sizes thansprinkler systems

No standard design method available; reducedreliability due to very small nozzle orifices andgreater number of required operatingcomponents; requires specialized installation;and maintenance personnel; nozzle dischargepressures higher for some systems; potentialfor physical damage to articles and property inclose proximity to nozzles

Types ofPipingMaterialsSteel —standardwall

Traditional strength andreliability

Corrosion concerns over time, especially withresidual water in pipe for dry and preactionsystems

Steel —thinwall

Reduced wall thickness andjoining with mechanicalfittings allows lower cost(wall thickness comparableto remaining wall outsidefitting for traditional threadedsystems)

Corrosion concerns over time, especially withresidual water in pipe for dry and preactionsystems; some concern that grooves placedon piping prevent complete drainage

Coppertube

Less susceptible tocorrosion than steel pipingsystems

More expensive than steel systems; firehazard of allowable joining methods

CPVC(chlorinatedpolyvinylchloride)

Not susceptible to corrosion;clean installation and fieldfabrication ideal for retrofit

Compatibility concerns, especially with regardto internal, and external exposures to materialscontaining plasticizers or hydrocarbons; mustbe in strict accordance with 9.12.13.4

Stainlesssteel

Highest High degree ofcorrosion resistance

Increased expense; corrosion concern withsprinkler seats unless stainless steelsprinklers also utilized

Types of

Page 78: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 77/99

SprinklersStandardresponse

Traditional strength andreliability against accidentaldischarge; leastmaintenance and lowesttesting requirements;

Lack of improved performance throughtechnological advancements in sprinklerthermal sensitivity

Quickresponse

Improved sensitivity allowsreaction to smaller fire andincreases effectiveness ofavailable water supplies

Reduced mass of sprinkler thermal elementmakes it somewhat more susceptible toaccidental discharge if proper care is not takenin handling and installation

Residential Combines increased thermalsensitivity of quick­responsesprinklers with high wallwetting appropriate fortypical small compartmentsof residential occupancies

Reduced mass of sprinkler thermal elementmakes it somewhat more susceptible toaccidental discharge if proper care is not takenin handling and installation; increasedinstallation requirements regardingobstructions, location, etc.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:18:30 EDT 2015

Committee Statement

CommitteeStatement:

Updated information added for antifreeze systems. Information added wherecurrently lacking to assist in user in making choices.

ResponseMessage:Public Input No. 17­NFPA 909­2014 [Section No. A.9.12.13]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Page 79: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 78/99

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 73­NFPA 909­2015 [ Section No. A.9.12.13.3.2.1 ]

A.9.12.13.3.2.1 Additional auxiliary drainage should be provided, in accordance with NFPA 13 ,regardless of whether Due to the heightened concerns regarding the issues associatedwith corrosion, additional auxiliary drainage is needed for all preaction systemsregardless of whether or not the protected area is subject to freezing.

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 14:18:36 EDT 2015

Committee Statement

Page 80: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 79/99

CommitteeStatement:

Explanatory material for providing the additional draining for preaction systemseven if not in an area subject to freezing.

ResponseMessage:Public Input No. 14­NFPA 909­2014 [Section No. A.9.12.13.3.2.1]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

Page 81: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 80/99

First Revision No. 55­NFPA 909­2015 [ Section No. G.1.1 ]

N.1.1 NFPA Publications.National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169­7471.

NFPA 1, Fire Code, 2012 2015 edition.

NFPA 10, Standard for Portable Fire Extinguishers, 2013 2017 edition.

NFPA 11, Standard for Low­, Medium­, and High­Expansion Foam, 2010 2016 edition.

NFPA 12, Standard on Carbon Dioxide Extinguishing Systems, 2011 2015 edition.

NFPA 12A, Standard on Halon 1301 Fire Extinguishing Systems, 2009 2015 edition.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 2016 edition.

NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2013 2016edition.

NFPA 17, Standard for Dry Chemical Extinguishing Systems, 2013 2017 edition.

NFPA 17A, Standard for Wet Chemical Extinguishing Systems, 2013 2017 edition.

NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection,2013 2016 edition.

NFPA 22, Standard for Water Tanks for Private Fire Protection, 2013 edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water­Based FireProtection Systems, 2011 2017 edition.

NFPA 40, Standard for the Storage and Handling of Cellulose Nitrate Film, 2011 2016edition.

NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work,2009 2014 edition.

NFPA 70B, Recommended Practice for Electrical Equipment Maintenance, 2013 2016edition.

NFPA 72®, National Fire Alarm and Signaling Code, 2013 2016 edition.

NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2013 2016 edition.

NFPA 90A, Standard for the Installation of Air­Conditioning and Ventilating Systems,2012 2015 edition.

NFPA 92, Standard for Smoke Control Systems, 2012 2015 edition.

NFPA 101®, Life Safety Code®, 2012 2015 edition.

NFPA 101A, Guide on Alternative Approaches to Life Safety, 2013 2016 edition.

NFPA 204, Standard for Smoke and Heat Venting, 2012 2015 edition.

NFPA 220, Standard on Types of Building Construction, 2012 2015 edition.

NFPA 232, Standard for the Protection of Records, 2012 2017 edition.

NFPA 241, Standard for Safeguarding Construction, Alteration, and DemolitionOperations, 2013 edition.

NFPA 291, Recommended Practice for Fire Flow Testing and Marking of Hydrants,2013 2016 edition.

Page 82: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 81/99

NFPA 550, Guide to the Fire Safety Concepts Tree, 2012 2017 edition.

NFPA 551, Guide for the Evaluation of Fire Risk Assessments, 2013 2016 edition.

NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films,2010 2015 edition.

NFPA 730, Guide for Premises Security, 2011 2017 edition.

NFPA 731, Standard for the Installation of Electronic Premises Security Systems,2011 2017 edition.

NFPA 750, Standard on Water Mist Fire Protection Systems, 2010 2015 edition.

NFPA 780 , Standard for the Installation of Lightning Protection Systems , 2017 edition.

NFPA 914, Code for Fire Protection of Historic Structures, 2010 2015 edition.

NFPA 1221, Standard for the Installation, Maintenance, and Use of Emergency ServicesCommunications Systems, 2013 2016 edition.

NFPA 1600®, Standard on Disaster/Emergency Management and Business ContinuityPrograms, 2013 2016 edition.

NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, 2012 2015 edition.

Fire, Electrical, and Building Safety Resource, www.nfpa.org.

Fire Protection Handbook, NFPA, 2008.

Hall, J. R. “Non­Home Structure Fires by Equipment Involved in Ignition,” NFPA,Quincy, MA, 2012

Isner, M. S. “Investigation Report: Fire in Los Angeles Central Library Causes $22Million Loss.” Fire Journal 81, no. 2 (1987): 56–63, 72–79.

Rosenberg, P. A., Facility Security: New Threats, New Strategies, NFPA, Quincy, MA,2002.

SFPE Engineering Guide to Performance­Based Fire Protection: Analysis and Design ofBuildings. Quincy, MA.: National Fire Protection Association; Bethesda, MD.: Society ofFire Protection Engineers, 2000.

SFPE Handbook of Fire Protection Engineering, Quincy, MA: National Fire ProtectionAssociation; Bethesda, MD: Society of Fire Protection Engineers, 2008.

Willey, A. E. “The Charles Klein Law Library Fire, Philadelphia, Pennsylvania.” FireJournal 66, no. 6, (November 1972):15–22.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 13:48:57 EDT 2015

Committee Statement

Committee Statement: Updates referenced NFPA documents to current editions.

Page 83: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 82/99

Response Message:Public Input No. 11­NFPA 909­2014 [Chapter G]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 56­NFPA 909­2015 [ Section No. G.1.2.1 ]

Page 84: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 83/99

N.1.2.1 ANSI Publications.American National Standards Institute, Inc., 25 West 43rd Street, 4th floor, New York,NY 10036.

ANSI/BHMA A156.1, Butts and Hinges, 2000.

ANSI/BHMA A156.2, American National Standard for Bored and Preassembled Locksand Latches, 1996.

ANSI/BHMA A156.4, Door Controls — Closers, 2000.

ANSI/BHMA A156.5, Auxiliary Locks and Associated Products, 2001.

ANSI/BHMA A156.12, Interconnected Locks and Latches, 1999.

ANSI/BHMA A156.13, Mortise Locks and Latches Series 1000, 2002.

ANSI/BHMA A156.16, Auxiliary Hardware, 2002.

ANSI/BHMA A156.17, Self­Closing Hinges and Pivots, 2004.

ANSI/BHMA A156.23, Electromagnetic Locks, 2004.

ANSI/BHMA A156.24, Delayed Egress Locking Systems, 2003.

ANSI/BHMA A156.25, Electrified Locking Devices, 2002.

ANSI/BHMA A156.26, Continuous Hinges, 2000.

ANSI/BHMA A156.28, Recommended Practice for Keying Systems, 2000.

ANSI/BHMA A156.30, High Security Cylinders, 2003.

ANSI/BHMA A156.31, Electric Strikes and Frame Mounted Actuators, 2001.

ANSI/SDI A250.4, Test Procedure and Acceptance Criteria for Physical Endurance forSteel Doorsand Hardware Reinforcing, 2001.

ANSI/SDI A250.8, Recommended Specifications for Standard Steel Door Frames,2003.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 14:03:37 EDT 2015

Committee Statement

Committee Statement: Updates referenced ANSI publications to current editions.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters

Page 85: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 84/99

2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 57­NFPA 909­2015 [ Section No. G.1.2.2 ]

Page 86: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 85/99

N.1.2.1 ASTM Publications.American Society for Testing and Materials, 100 Barr Harbor Drive, WestConshohocken, PA 19428­2959.

ASTM E119, Standard Test Methods for Fire Tests of Building Construction andMaterials , 2014

ASTM E 1355 E1355 , Standard Guide for Evaluating the Predictive Capability ofDeterministic Fire Models, 2011 2012 .

ASTM E 1472 E1472 , Standard Guide for Documenting Computer Software for FireModels, 2007 (withdrawn 2011).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 14:18:50 EDT 2015

Committee Statement

Committee Statement: Updates referenced ASTM publications to current edition.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.

Page 87: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 86/99

Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 58­NFPA 909­2015 [ Section No. G.1.2.5 ]

N.1.2.7 UL Publications.Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062­2096.

ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2011.

ANSI/UL 294, Standard for Access Control System Units, 1999, revised 2010 2013 .

ANSI/UL 305, Standard for Panic Hardware, 1997, revised 2010 2012 .

ANSI/UL 437, Standard for Key Locks, 2000, revised 2008.

ANSI/UL 768, Standard for Combination Locks, 2006, revised 2010 2013 .

ANSI/UL 1034, Standard for Burglary­Resistant Electric Locking Mechanisms, 2011.

UL 634, Connectors and Switches for Use with Burglar­Alarm Systems , 2007.

UL 681, Standard for Installation and Classification of Burglar and Holdup AlarmSystems, 1999, revised 2001 2014 .

UL 2058, Outline of Investigation for High Security Electronic Locks, 2005.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 14:22:42 EDT 2015

Page 88: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 87/99

Committee Statement

Committee Statement: Updates referenced UL publications to current editions.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

Page 89: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 88/99

First Revision No. 59­NFPA 909­2015 [ Section No. G.1.2.7 ]

N.1.2.9 Other Publications.Before and After Disasters, Heritage Preservation, 2005.www.heritagepreservation.org/PDFS/Disaster.pdf.

Borenstein, S. W., Microbiologically Influential Corrosion Handbook, WoodheadPublishing Limited, 1994.

British Standard BS 7974, Application of Fire Safety Engineering Principles to theDesign of Buildings, British Standards Institution, London, UK, 2001.

Cotton, P. E., "Fire Tests of Library Book Stacks," report dated December 21, 1959.

Cutler, Harold R. , “Engineering Analysis of Compact Storage Fire Tests,” unpublishedreport prepared by Firepro, Inc. for the Library of Congress, 1979.

Dorge, Valerie, and Sharon L. Jones, compilers, Building an Emergency Plan: A Guidefor Museums and Other Cultural Institutions. The Getty Conservation Institute, 1999.www.getty.edu/conservation/publications/pdf_publications/emergency_plan.pdf.

Draft Paper on the Characteristics of RFID­Systems, The Association for AutomaticIdentification and Mobility, Warrendale, PA, 2000.

Field Guide to Emergency Response, Heritage Preservation, 1012 14th Street, NW,Suite 1200, Washington, DC 20005.

Field Manual FM­3­19.30, Physical Security, Headquarters, Department of the Army,2001.

Fire Safety Engineering Guidelines, Australian Building Codes Board, Canberra, ACT,2001.

Fontana, M. G., and Greene, N. D., Corrosion Engineering, McGraw Hill, 1978.

Guidelines for the Security of Rare Books, Manuscripts, and Other Special Collections,Association of College & Research Libraries, American Library Association, 50 EastHuron Street, Chicago, IL 60611­2795.

Hatchfield, P., Pollutants in the Museum Environment, London, Archetype PublicationsLtd., 85, 2002.

Honey, G., Electronic Access Control, Newnes, Oxford, UK, 2000.

Lougheed, G. D., J. R. Mawhinney, and J. O'Neill, "Full­Scale Fire Tests and theDevelopment of Design Criteria for Sprinkler Protection of Mobile Shelving Units." FireTechnology 30, no. 1 (1994).

McLane, B., and Aulner, C., CCTV Systems, Design & Installation, National TrainingCenter, Inc., Las Vegas, NV, 2004.

“A Legal Primer on Managing Museum Collections,” Malaro, Marie, second edition 1998.

Morris, J. The Library Disaster Preparedness Handbook . Chicago: American LibraryAssociation, 1986.

Pierce, C., Application & Design of CCTV, LeapFrog Training & Consulting, Davenport,IA, 2002.

Open for Business, Institute for Business and Home Safety, 2006. www.ibhs.org

“Risk and Insurance Management Manual for Libraries,” Mary Breighner and William

Page 90: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 89/99

Payton, edited by Jeanne Drewes, ALA 2005 ISBN 0­8389­8325­1.

Roberge, P. R., Handbook of Corrosion Engineering, McGraw Hill, 2000.

Sampson, R. L., A Practical Guide to Central Station Burglar Alarm Systems, CentralStation Alarm Association, Bethesda, MD, 1997.

Trinkley, Michael. Hurricane! Surviving the big one: a primer for libraries, museums andarchives, 2nd edition, Columbia, SC: Chicora Foundation; Atlanta, GA: SoutheasternLibrary Network, c1998.

Waters, P., “Procedures for Salvage of Water­Damaged Library Materials,” RestorationOfficer, Library of Congress, 1975. (Copies available upon request from the Library ofCongress, Washington, DC 20540.)

Wisconsin Administrative Code, Chapter 70. Historic Buildings.http://www.legis.state.wi.us/rsb/code/comm/comm070.html.

Wisconsin Historic Building Code, Madison, WI:Wisconsin Administrative Code.

World Heritage List, United Nations Educational, Scientific, and Cultural Organization,UNESCO World Heritage Centre, Paris, France, 2009.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 14:27:53 EDT 2015

Committee Statement

Committee Statement: Updates Internet links to other publications.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative All

Page 91: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 90/99

Allshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 60­NFPA 909­2015 [ Section No. G.2.1 ]

N.2.1 NFPA Publications.National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169­7471.

NFPA 20 , Standard for the Installation of Stationary Pumps for Fire Protection , 2013edition.

NFPA 70®, National Electrical Code®, 2011 2017 edition.

NFPA 80A, Recommended Practice for Protection of Buildings from Exterior FireExposures, 2012 2017 edition.

NFPA 291 , Recommended Practice for Fire Flow Testing and Marking of Hydrants ,2013 edition.

NFPA 1144, Standard for Reducing Structure Ignition Hazards from Wildland Fire, 2013edition.

Marchant, E. W. “Preventing Fire in Historic Buildings: The Acceptable Risk.” FireTechnology, 25, no. 2 (May 1989):165–176.

“Protecting Our Heritage, A Discourse on Fire Protection and Prevention in HistoricBuildings and Landmarks,” 2nd edition, 1970.

Page 92: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 91/99

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 14:37:32 EDT 2015

Committee Statement

CommitteeStatement:

Updates NFPA informational reference to current editions and deleteswhere not applicable.

ResponseMessage:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.

Page 93: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 92/99

Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 61­NFPA 909­2015 [ Section No. G.2.2 ]

N.2.2 ASTM Publications.ASTM International, 100 Barr Harbor Drive, West Conshohocken, PA 19428­2959.

ASTM E 84 E84 , Standard Test Method for Surface Burning Characteristics of BuildingMaterials, 2012 2014 .

ASTM E 136 E136 , Standard Test Method for Behavior of Building Materials in aVertical Tube Furnace at 750°C, 2011 2012 .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Thu Apr 16 14:45:02 EDT 2015

Committee Statement

Committee Statement: Updates informational ASTM publications to current editions.Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Page 94: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 93/99

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 62­NFPA 909­2015 [ Section No. G.3 ]

N.3 References for Extracts in Informational Sections.NFPA 4 , Standard for Integrated Fire Protection and Life Safety System Testing , 2015edition.

NFPA 72®, National Fire Alarm and Signaling Code, 2013 2016 edition.

NFPA 730, Guide for Premises Security, 2011 2017 edition.

NFPA 5000®, Building Construction and Safety Code®, 2012 2015 edition.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]Organization: [ Not Specified ]

Page 95: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 94/99

Street Address:City:State:Zip:Submittal Date: Thu Apr 16 14:47:39 EDT 2015

Committee Statement

CommitteeStatement:

Updates references for extracts in informational sections to currenteditions.

Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, Sheila

Page 96: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 95/99

Portway, ChrisPuchovsky, Milosh T.Wilson, Robert D.

First Revision No. 95­NFPA 909­2015 [ Section No. J.1 ]

I.1 Quarterly Cultural Resource Property Protection Self­Inspection Checklist.The checklist in Figure I.1 should be used as a reminder during the inspection. Itemsrequiring corrective action should be noted and reported to the responsible manager.Section 1 through Section 5 of the checklist can be used by the individual conductingthe inspection during a tour of the cultural resource property. Section 6 is an inspectionof records that should be accomplished by the fire safety manager and/or the securitymanager.Figure I.1 Cultural Resource Property Protection Self­Inspection Checklist.

Page 97: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 96/99

Page 98: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 97/99

DELETED

DELETED

Page 99: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 98/99

Supplemental Information

File Name Description909_FR95_Attachment.pdf Revised text

Submitter Information Verification

Submitter Full Name:Greg HarringtonOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Tue Apr 28 15:47:43 EDT 2015

Committee Statement

CommitteeStatement:

The proposed revision updates the terminology to reflect the terminology used in ULstandards and the NEC on the devices and to make it clear that surge protectivedevices should also be included in the checklist.

DELETED

DELETED

Page 100: First Draft Meeting PPT - NFPA › Assets › files › AboutTheCodes › 909 › 909...M E M O R A N D U M To: NFPA Technical Committee on Cultural Resources From: Kelly Carey, Project

7/14/2015 National Fire Protection Association Report

http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28%28CommentType%3D%22FR%22+or+CommentType%3D%22CN%22… 99/99

ResponseMessage:

Public Input No. 52­NFPA 909­2015 [Section No. J.1]

Ballot Results

This item has passed ballot

26 Eligible Voters2 Not Returned24 Affirmative All0 Affirmative with Comments0 Negative with Comments0 Abstention

Not ReturnedNichols, Daniel E.Watts, Jr., John M.

Affirmative AllAllshouse, Clare RayArtim, NicholasBrady, Eileen E.Coull, MichaelCrosby, GrantDoyle, Laura E.Finnegan, Daniel P.Fleming, Russell P.Freeland, Deborah L.Greczek, CindyHarrington, John C.Hubert, Daniel J.Kilby, MichaelLeber, A. M. FredLev­Alexander, NancyMoeller, Donald C.Moore, Wayne D.Morin, Kevin D.Nassi, LucaNorton, Thomas F.Palmer, SheilaPortway, ChrisPuchovsky, Milosh T.Wilson, Robert D.