flex ex system certification - rockwell automation · 2012. 2. 14. · 1 publication 1797-6.5.6 -...

252
FLEX Ex System Certification 1797 Series Reference Manual

Upload: others

Post on 25-Oct-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

FLEX Ex System Certification1797 Series

Reference Manual

Page 2: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.

Throughout this manual we may use notes to make you aware of safety considerations.

WARNINGIdentifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:• identify a hazard• avoid a hazard• recognize the consequence

SHOCK HAZARD Labels may be located on or inside the equipment to alert people that dangerous voltage may be present.

BURN HAZARD Labels may be located on or inside the equipment to alert people that surfaces may be dangerous temperatures.

Page 3: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Summary of Changes

Changed Items These items changed since the last printing of this FLEX Ex System Certification Reference Manual, publication 1797-6.5.6:

To help you find new and updated information in this release of the manual, we have included change bars as shown next to this paragraph.

Updated Information Page

1797-IE8H Section 45-2…45-4

1797-OE8H Section 48-2…48-4

1 Publication 1797-6.5.6 - June 2005

Page 4: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Summary of Changes 2

Notes:

Publication 1797-6.5.6 - June 2005

Page 5: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Preface

What Is Intrinsically Safe? According to Article 504 of the National Electrical Code, NFPA 70, an intrinsically safe (I/S) product is defined as one in which no spark or thermal effect generated during normal functioning and/or during specific fault conditions is able to ignite a given explosive atmosphere.

One example of an I/S product is FLEX Ex distributed I/O control.

What are Product Certifications?

A product certification is a guarantee that the product has been designed and manufactured with the required I/S specifications and protection. Considering the potential danger in hazardous locations, product certification is required for all I/S products.

Three Types of Product Certifications

In this reference manual, we describe three types of product certifications and how they relate to FLEX Ex products:

• CENELEC - European Electrotechnical Committee for Standardization. This is the standard in all European Union countries.

• UL and C-UL - Underwriters Laboratories (UL in the United States and C-UL in Canada)

• FM - Factory Mutual, another available certifying body in the United States

FLEX Ex products are certified to the appropriate CENELEC, UL, C-UL and FM standards, depending on the module.

What are Entity Parameters?

Entity parameters provide a system of quantifying and matching safe levels for voltage, current, inductance, and capacitance when connecting field devices and system devices together.

FLEX Ex uses entity parameters to quantify safe levels when connecting I/O modules to field devices. Inputs and outputs are specified with:

• open-circuit voltage (Uo or Voc)

• short-circuit current (Io or Isc)

• allowed capacitance (Co or Ca)

• allowed inductance (Lo or La)

Switched outputs are specified as if they were inputs.

Field devices using entity parameters are specified with:

• maximum input voltage (Ui or Vmax)

1 Publication 1797-6.5.6 - June 2005

Page 6: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Preface 2

• maximum input current (Ii or Imax)

• maximum internal capacitance (Ci)

• maximum internal inductance (Li)

In use, the sum of all the input Ci and Li in a control loop cannot exceed the Co and Lo. Also, the sum of all the Uo and Io cannot exceed the input Ui and Ii.

The following is a short explanation of how entity-based architectures help simplify IS system design.

Entity Parameters Example

An output channel and the valve it will drive are illustrated in the following figure. By comparing entity parameters, you can quickly determine the appropriate match.

In this example, the combination is compatible because the valve can withstand:

• Ui = 30V

• Ii = 165mA

These values are higher than what the 1797-IE8 can provide:

40052

cable length = 10m

268Ω21V

22Ω

+

sig

Ci<10pF/mLi<0.5uH/mR<0.1Ω/m

P/I transmitterEEx ia IIC T4

Ui=30VIi=165mACi=22.5nFLi=730uH

ModuleUoIoCaLa

< or =< or => or => or =

Total LoopUiIiCiLi

====

TransmitterUiIiCiLi

Distance Cable

+

+

(length * Ci per length)

(length * La per length)

ModuleUo<23.7VIo<92.5mACa=66nF

La=2.5mH

< or =< or => or => or =

Total LoopUi=30V

Ii=165mACi=22.6nFLi=735uH

====

TransmitterUi=30V

Ii=165mACi=22.5nFLi=730uH

Distance Cable

+

+

(10m * Ci=10pF/m)

(10m * La =0.5uH/m)

1797-IE8 Analog InputEEx ia/ib IIB/IIC T4

Uo<23.7VIo<93.5mA

IIBCa=560nFLa=10mH

IICCa=66nF

La=2.5mH

Publication 1797-6.5.6 - June 2005

Page 7: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Preface 3

• Uo = 23.7V

• Io = 93.5mA

In the same way, the valve is characterized by:

• Ci = 22.5nF

• Li = 730µH

These values are lower than what the 1797-IE8 allows:

• Co = 66nF

• Lo = 2.5mH

Intrinsic Safety Terminology

The following sections describe key terms used in this reference manual:

Hazardous Area Designation

A hazardous area is designated as any location in which a combustible material is or may be present in the atmosphere in sufficient concentration to produce an ignitable mixture.

The North American method identifies these areas by Class, Division, and Group while the IEC (CENELEC) designates these areas by Zone and Gas Group.

Recently, North America has adopted the Zone method of identifying hazardous locations as an option to the Division method.

Class Designation

Class identifies the type of hazardous atmosphere.

Class I Gas or vapor

Class II Dust

Class III Fiber or flying (no group designation)

Publication 1797-6.5.6 - June 2005

Page 8: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Preface 4

Division/Zone Designations

Division/Zone identifies the likelihood of a hazardous atmosphere being present.

Gas/Dust Groups

Hazardous locations are grouped according to their ignition properties.

Division Method(North America)

IEC Standard Zone Method

Ignitable mixture present continuously (long periods)

Division 1

Zone 0(Zone 20-Dust)

Ignitable mixture present intermittently Zone 1(Zone 21-Dust)

Ignitable mixture is not normally present Division 2 Zone 2(Zone 22-Dust)

Typical Gas IEC Gas Group North American Gas Group

Acetylene IIC A

Hydrogen IIC B

Ethylene IIB C

Propane IIA D

Methane1 I D1

Metal Dust - E

Coal Dust - F

Grain Dust - -

1 Mining applications under jurisdiction of MSHA.

Publication 1797-6.5.6 - June 2005

Page 9: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Preface 5

Use in North American Hazardous Locations

FLEX Ex modules are rated for installation in Class I Division 1 & 2, Groups A-D hazardous areas. They are also rated to connect to field devices that are located in Class I, II, or III, Groups A-G hazardous areas.

If FLEX Ex components are to be installed in a Class II or III location in your application, you can mount them in a suitable, dust-proof enclosure with the appropriate connectors, glans, and seals. For example, a NEMA 9 enclosure may be appropriate. The FLEX Ex modules are rated to connect to devices in Class II or III locations.

FLEX Ex modules are rated for installation in North American Class I Zone 1 & 2, Groups IIC, IIB, & IIA hazardous areas. They are also rated to connect to field devices that are located in North American Class I Zone 0, 1, & 2, Groups IIC, IIB, & IIA hazardous areas.

As always, observe local code requirements when applying your FLEX Ex application.

Use in CENELEC Hazardous Locations

FLEX Ex modules are rated for installation in European Zones 1, 2, and 22. They are also rated to connect to field devices that are located in European Zones 0, 1, 2, 21, and 22 hazardous areas. The FLEX Ex power supplies (1797-PS1E and -PS2E2) are rated for use in Zones 1 and 22.

If FLEX Ex components are to be installed in a European Zone method dust or fiber location in your application, you must mount them in an approved, dust-proof enclosure with the appropriate connectors, glans, and seals. Pepperl+Fuchs have three cabinets that are approved for use with FLEX Ex components in Zone 22 applications: IVK2-ISRPI-V8LC; IVK2-ISRPI-V8HYW; and IVK2-ISRPI-V16LC. P+F has offices in Twinsburg, Ohio, USA, and Mannheim, Germany. See their website at www.pepperl-fuchs.com.

As always, observe local code requirements when applying your FLEX Ex application.

Publication 1797-6.5.6 - June 2005

Page 10: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Preface 6

Methods of Protection

The following techniques are rated by methods of protection.

Temperature Category

The temperature category defines the maximum surface temperature of the device. Ratings are given with reference to 40oC ambient unless otherwise stated.

Technique

Symbol for Protection Method

Permitted Zone Permitted Division

Zone Division

IEC CENELEC NEC CEC

Oil Immersion Ex o EEx o AEx o Ex o 1 and 2 *

Pressurization Ex p EEx p AEx p Ex p Type X, Y, Z 1 and 2 1 (X, Y) and 2 (Z)

Powder Filling Ex q EEx q AEx q Ex q 1 and 2 *

Flameproof Ex d EEx d AEx d Ex d 1 and 2

Explosionproof XP 1 and 2

Increased Safety Ex e EEx e AEx e Ex e 1 and 2 *

Intrinsic SafetyDual FaultSingle Fault

Ex iaEx ib

EEx iaEEx ib

AEx iaAEx ib

Ex iaEx ib

IS0, 1, and 2

1 and 2

1 and 2

Non-IncendiveLimited EnergyNon-SparkingEnclosed BreakRestricted BreathingSimplified Pressurization

Ex nLEx nVEx nWEx nREx nP

EEx nLEEx nVEEx nWEEx nREEx nP

AEx nLAEx nVAEx nWAEx nRAEx nP

Ex nLEx nVEx nWEx nREx nP

NI 2 2

Encapsulation Ex m EEx m Aex m Ex m 1 and 2 *

* These protection methods are not recognized in the Division method. However, they may be suitable for some North American Division applications.

T1 450oC (842oF) T3A 180oC (356oF)

T2 300oC (572oF) T3B 165oC (329oF)

T2A 280oC (536oF) T3C 160oC (320oF)

T2B 260oC (500oF) T4 135oC (275oF)

T2C 230oC (446oF) T4A 120oC (248oF)

T2D 215oC (419oF) T5 100oC (212oF)

T3 200oC (392oF) T6 85oC (185oF)

The additional temperature categories highlighted above are for North America only.

Publication 1797-6.5.6 - June 2005

Page 11: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Preface 7

Understanding the Layout of this Manual

This reference manual consists of three sections:• CENELEC Certification Information• UL, C-UL Certification Information• FM Certification Information

CENELEC Certification Information

TIP The chapters in this document have been renumbered to include additional modules. If you were referred to a particular chapter from another document, use the tables below to determine the correct chapter number.

For Information On Refer to this Chapter

CENELEC Certification Information General CENELEC Certification Information 1

ControlNet Ex System 2

1797-TB3 FLEX Ex Terminal Base Unit 3

1797-TB3S FLEX Ex Terminal Base Unit 4

1797-IBN16 FLEX Ex 16 NAMUR Input Module 5

1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module 6

1797-IE8 FLEX Ex 8 Input Analog Module 7

1797-IE8H FLEX Ex 8 Input HART Analog Module 8

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter 9

1797-OE8 FLEX Ex 8 Output Analog Module 10

1797-OE8H FLEX Ex 8 Output HART Analog Module 11

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module 12

1797-IJ2 FLEX Ex Frequency Input Module 13

1797-PS1E FLEX Ex Power Supply 14

1797-PS2E2 FLEX Ex Power Supply 15

1797-ACNR15 ControlNet Ex Redundant Media Adapter 16

1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

17

1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector 18

1797-BCNR Redundant ControlNet Ex Barrier 19

Publication 1797-6.5.6 - June 2005

Page 12: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Preface 8

UL, cUL Certification Information

For Information On Refer to this Chapter

UL, cUL Certification Information General UL, C-UL Certification Information 20

ControlNet Ex System 21

1797-TB3 FLEX Ex Terminal Base Unit 22

1797-TB3S FLEX Ex Terminal Base Unit 23

1797-IBN16 FLEX Ex 16 NAMUR Input Module 24

1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module 25

1797-IE8 FLEX Ex 8 Input Analog Module 26

1797-IE8H FLEX Ex 8 Input HART Analog Module 27

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter 28

1797-OE8 FLEX Ex 8 Output Analog Module 29

1797-OE8H FLEX Ex 8 Output HART Analog Module 30

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module 31

1797-IJ2 FLEX Ex Frequency Input Module 32

1797-PS1N FLEX Ex Power Supply 33

1797-PS2N2 FLEX Ex Power Supply 34

1797-ACNR15 ControlNet Ex Redundant Media Adapter 35

1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

36

1797-BCNR Redundant ControlNet Ex Barrier 37

Publication 1797-6.5.6 - June 2005

Page 13: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Preface 9

FM Certification Information

For Information On Refer to this Chapter

FM Certification Information General FM Certification Information 38

ControlNet Ex System 39

1797-TB3 FLEX Ex Terminal Base Unit 40

1797-TB3S FLEX Ex Terminal Base Unit 41

1797-IBN16 FLEX Ex 16 NAMUR Input Module 42

1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module 43

1797-IE8 FLEX Ex 8 Input Analog Module 44

1797-IE8H FLEX Ex 8 Input HART Analog Module 45

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter 46

1797-OE8 FLEX Ex 8 Output Analog Module 47

1797-OE8H FLEX Ex 8 Output HART Analog Module 48

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module 49

1797-IJ2 FLEX Ex Frequency Input Module 50

1797-PS1N FLEX Ex Power Supply 51

1797-PS2N2 FLEX Ex Power Supply 52

1797-ACNR15 ControlNet Ex Redundant Media Adapter 53

1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

54

1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector 55

Publication 1797-6.5.6 - June 2005

Page 14: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Preface 10

Notes:

Publication 1797-6.5.6 - June 2005

Page 15: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Table of Contents

CENELEC Information

Chapter 1General CENELEC Certification Information

General Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1Installation in Zone 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Installation in Zone 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Electrostatic Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2European Community Directive Compliance . . . . . . . . . . . . . . . . . . 1-2

EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2LVD Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2ATEX Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3

Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3Attention: Avoid electrostatic charge.. . . . . . . . . . . . . . . . . . . . . . 1-3

About Zone 22 Junction Boxes (Cabinets) . . . . . . . . . . . . . . . . . . . . . 1-4

Chapter 2ControlNet Ex System ControlNet Ex System Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2

Describing the ControlNet Ex System Diagram . . . . . . . . . . . . . . . . 2-3Certified Equivalent ControlNet Ex System Diagram Items . . . 2-4

Installation in Zone 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5Installation in Zone 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5Electrostatic Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5

Attention: Avoid electrostatic charge.. . . . . . . . . . . . . . . . . . . . . . 2-5General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6

Chapter 31797-TB3 FLEX Ex Terminal Base Unit

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3

Chapter 41797-TB3S FLEX Ex Terminal Base Unit

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3

i Publication 1797-6.5.6 - June 2005

Page 16: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

ii

Chapter 51797-IBN16 FLEX Ex 16 NAMUR Input Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . . 5-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2CE/CENELEC I/O Entity Parameters (Each Channel) . . . . . . . . . 5-3

Chapter 61797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . . 6-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2CE/CENELEC I/O Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . 6-2

Chapter 71797-IE8 FLEX Ex 8 Input Analog Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . . 7-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2CE/CENELEC I/O Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . 7-3

Chapter 81797-IE8H FLEX Ex 8 Input HART Analog Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . . 8-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2CE/CENELEC I/O Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . 8-3

Chapter 91797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . . 9-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2CE/CENELEC I/O Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . 9-3

Publication 1797-6.5.6 - June 2005

Page 17: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

iii

Chapter 101797-OE8 FLEX Ex 8 Output Analog Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 10-1General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2CE, CENELEC I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . 10-2

Chapter 111797-OE8H FLEX Ex 8 Output HART Analog Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 11-1General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2CE, CENELEC I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . 11-2

Chapter 121797-IRT8 FLEX Ex Thermocouple/RTD Input Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 12-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-2CE/CENELEC I/O Entity Parameters. . . . . . . . . . . . . . . . . . . . . . 12-3

Chapter 131797-IJ2 FLEX Ex Frequency Input Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 13-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-2CE/CENELEC Input I/O Entity Parameters. . . . . . . . . . . . . . . . . 13-3

Channel 0 Frequency Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-3Channel 1 Frequency Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-4Channel 0 Gate Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-5Channel 1 Gate Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-5

Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-6

Chapter 141797-PS1E FLEX Ex Power Supply Installation in Zone 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1

Installation in Zone 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1Typical Wiring Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-2

Publication 1797-6.5.6 - June 2005

Page 18: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

iv

Chapter 151797-PS2E2 FLEX Ex Power Supply Installation in Zone 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-1

Installation in Zone 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-1Typical Wiring Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2

Chapter 161797-ACNR15 ControlNet Ex Redundant Media Adapter

Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-1Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-2

Chapter 171797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-1Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-2

Chapter 181797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector

General Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-1Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-3

Chapter 191797-BCNR Redundant ControlNet Ex Barrier

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-1Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-2Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-2

Publication 1797-6.5.6 - June 2005

Page 19: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

v

UL, C-UL Information

Chapter 20General UL, C-UL Certification Information

Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-1Installation in Division 1/Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-2Electrostatic Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-2Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-2

Attention: Avoid electrostatic charge.. . . . . . . . . . . . . . . . . . . . . 20-2

Chapter 21ControlNet Ex System ControlNet Ex System Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-2

Describing the ControlNet Ex System Diagram . . . . . . . . . . . . . . . 21-3Certified Equivalent ControlNet Ex System Diagram Items . . 21-4

Installation in Division 1/Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-5Electrostatic Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-6Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-6

Attention: Avoid electrostatic charge.. . . . . . . . . . . . . . . . . . . . . 21-6

Chapter 221797-TB3 FLEX Ex Terminal Base Unit

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-1Installation in Division 1/Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-2Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-3

Chapter 231797-TB3S FLEX Ex Terminal Base Unit

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-1Installation in Division 1/Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-2Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-3

Publication 1797-6.5.6 - June 2005

Page 20: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

vi

Chapter 241797-IBN16 FLEX Ex 16 NAMUR Input Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 24-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-3

Table 1: Entity Values for Field Device Connections . . . . . . . . 24-3Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 24-4

Chapter 251797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 25-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 25-3Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 25-4

Chapter 261797-IE8 FLEX Ex 8 Input Analog Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 26-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-3

Table 1: Entity Values for Field Device Connections . . . . . . . . 26-3Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 26-4

Publication 1797-6.5.6 - June 2005

Page 21: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

vii

Chapter 271797-IE8H FLEX Ex 8 Input HART Analog Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 27-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 27-3

Table 1: Entity Values for Field Device Connections . . . . . . . . 27-3Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 27-4

Chapter 281797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 28-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-3

Table 1: Entity Values for Field Device Connections . . . . . . . . 28-3Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 28-4

Chapter 291797-OE8 FLEX Ex 8 Output Analog Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 29-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 29-2Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 29-4

Publication 1797-6.5.6 - June 2005

Page 22: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

viii

Chapter 301797-OE8H FLEX Ex 8 Output HART Analog Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 30-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 30-2Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 30-4

Chapter 311797-IRT8 FLEX Ex Thermocouple/RTD Input Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 31-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-3

Table 1: Entity Values for Field Device Connections . . . . . . . . 31-3Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-5Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 31-5

Chapter 321797-IJ2 FLEX Ex Frequency Input Module

General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-1Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 32-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 32-3Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 32-4

Chapter 331797-PS1N FLEX Ex Power Supply Installation in Division 1/

Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-1Typical Wiring Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 33-2

Publication 1797-6.5.6 - June 2005

Page 23: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

ix

Chapter 341797-PS2N2 FLEX Ex Power Supply

Installation in Division 1/Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-1Typical Wiring Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-2UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 34-2

Chapter 351797-ACNR15 ControlNet Ex Redundant Media Adapter

Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-1Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-1General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-1UL, cUL Entity Parameters and Requirements . . . . . . . . . . . . . . . . 35-2

UL, C-UL I/O Entity Parameters and Requirements . . . . . . . . 35-2Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-2

Chapter 361797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-1Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-2UL, cUL Entity Parameters and Requirements . . . . . . . . . . . . . . . . 36-2

Chapter 371797-BCNR Redundant ControlNet Ex Barrier

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-1Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-2Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-2

Publication 1797-6.5.6 - June 2005

Page 24: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

x

FM Information

Chapter 38General FM Certification Information

Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-1Installation in Division 1/ Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . 38-2Electrostatic Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-3FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-3Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-3

Attention: Avoid electrostatic charge.. . . . . . . . . . . . . . . . . . . . . 38-3

Chapter 39ControlNet Ex System ControlNet Ex System Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39-2

Describing the ControlNet Ex System Diagram . . . . . . . . . . . . . . . 39-3Certified Equivalent ControlNet Ex System Diagram Items . . 39-4

Chapter 401797-TB3 FLEX Ex Terminal Base Unit

Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-1Installation in Division 1/Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-2Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-3

Chapter 411797-TB3S FLEX Ex Terminal Base Unit

Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-1Installation in Division 1/Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-1Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-2Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-2Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-3

Chapter 421797-IBN16 FLEX Ex 16 NAMUR Input Module

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 42-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42-2FM I/O Entity Parameters (Each Channel) . . . . . . . . . . . . . . . . . . . 42-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 42-2Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 42-4

Publication 1797-6.5.6 - June 2005

Page 25: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

xi

Chapter 431797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 43-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43-2FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 43-2Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43-3Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 43-3

Chapter 441797-IE8 FLEX Ex 8 Input Analog Module

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 44-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44-2FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 44-3Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 44-4

Chapter 451797-IE8H FLEX Ex 8 Input HART Analog Module

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 45-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45-2FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 45-3Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 45-4

Chapter 461797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 46-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-2FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 46-3Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 46-4

Publication 1797-6.5.6 - June 2005

Page 26: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

xii

Chapter 471797-OE8 FLEX Ex 8 Output Analog Module

Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 47-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-2FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 47-2Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-3Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 47-3

Chapter 481797-OE8H FLEX Ex 8 Output HART Analog Module

Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 48-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48-2FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 48-2Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48-3Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 48-3

Chapter 491797-IRT8 FLEX Ex Thermocouple/RTD Input Module

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 49-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49-2FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 49-2Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 49-4

Chapter 501797-IJ2 FLEX Ex Frequency Input Module

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-1Wiring to a 1797-TB3 or -TB3S Terminal Base Unit . . . . . . . . . . . . 50-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-2FM Input I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 50-2Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-4Table 3: Flexbus Entity Values for this Module. . . . . . . . . . . . . 50-4

Publication 1797-6.5.6 - June 2005

Page 27: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

xiii

Chapter 511797-PS1N FLEX Ex Power Supply Installation in Division 1/

Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-1Typical Wiring Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-2FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 51-2

Chapter 521797-PS2N2 FLEX Ex Power Supply

Installation in Division 1/Zone 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52-1Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52-1Typical Wiring Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52-2FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52-2

Table 1: Entity Values for Field Device Connections . . . . . . . . 52-2

Chapter 531797-ACNR15 ControlNet Ex Redundant Media Adapter

Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53-1Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53-1FM Entity Parameters and Requirements . . . . . . . . . . . . . . . . . . . . . 53-2

FM I/O Entity Parameters and Requirements. . . . . . . . . . . . . . 53-2Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53-2

Chapter 541797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54-1Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54-1Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54-2FM Entity Parameters and Requirements . . . . . . . . . . . . . . . . . . . . . 54-2

Chapter 551797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector

General Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55-1Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55-3Intrinsically Safe Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55-3

Publication 1797-6.5.6 - June 2005

Page 28: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

xiv

Notes:

Publication 1797-6.5.6 - June 2005

Page 29: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 1

General CENELEC Certification Information

General Installation FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

You will need to rotate the keyswitch (1) to the correct position depending on the module. Refer to the module’s installation instructions for more information. Do not change the position of the keyswitch after wiring the terminal base unit.

Make certain that you only connect terminal base units to other intrinsically safe system modules, adapters or power supplies to maintain the integrity of the intrinsically-safe backplane.

Remove cap plug and attach another intrinsically safe terminal base unit to the right of the terminal base unit (2) if required.

Do not remove the flexbus cover (8) on the right-most terminal base unit.

Label here or under here 40231

(1) keyswitch

(8) flexbus cover

(2) terminal base unit

41307

1 Publication 1797-6.5.6 - June 2005

Page 30: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1-2 General CENELEC Certification Information

Installation in Zone 1 Modules, adapters, and terminal base units must not be exposed to the environment. Provide a suitable enclosure. The modules, adapters, and terminal base units have a protection factor of IP20.

Installation in Zone 22 When the ControlNet Ex system is installed in Zone 22, all system components (except the coax cable and ControlNet Ex taps) must be installed in cabinets of the following type: IVK-ISRPI-V16LC; IVK-ISRPI-V8HYW; or IVK-ISRPI-V8LC. For more information on these cabinets, see page 1-4.

Electrostatic Charge Protect the system against electrostatic charge. Post a sign near each module: Attention! Avoid electrostatic charge. For your convenience, a sign which can be cut out and posted is included in this chapter.

European Community Directive Compliance

If this product has the CE mark it is approved for installation within the European Community or EEA regions. It has been designed and tested to meet the following directives.

EMC Directive

All system components are tested to meet the Council Directive 89/336/EEC Electromagnetic Compatibility (EMC), as amended by 92/31/EC and 93/68/EEC, by applying the following standards as appropriate:

• EN61000-6-4:2001, Electromagnetic Compatibility (EMC) - Part 6-4: Generic Standards - Emission Standard for Industrial Environments (Class A)

• EN61000-6-2:2001, Electromagnetic Compatibility (EMC) - Part 6-2: Generic Standards - Immunity for Industrial Environments

• EN61326:1997 + A1-A2, Electrical Equipment for Measurement, Control, and Laboratory Use - Industrial EMC Requirements

LVD Directive

All power supplies are tested to meet the Council Directive 73/23/EEC Low Voltage Directive, as amended by 93/68/EEC (LVD), by applying the following standards as appropriate:

• EN50178:1997, Electronic Equipment for Use in Power Installations

ATTENTION Modules, adapters, and terminal base units cannot be used in an intrinsically safe environment after they have been exposed to non-intrinsically safe signals.

Publication 1797-6.5.6 - June 2005

Page 31: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

General CENELEC Certification Information 1-3

ATEX Directive

All system components are tested to meet the Council Directive 94/9/EC Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres by applying the following standards, as appropriate:

• EN50014:1997 + A1-A2, Electrical Apparatus for Potentially Explosive Atmospheres

• EN50018:1995, Electrical Apparatus for Potentially Explosive Atmospheres - Flameproof Enclosure “d”

• EN50019:1996, Electrical Apparatus for Potentially Explosive Atmospheres - Increased Safety “e”

• EN50020:1994, Electrical Apparatus for Potentially Explosive Atmospheres - Intrinsic Safety “i”

• EN50021: 1999, Electrical Apparatus for Potentially Explosive Atmospheres - Type of Protection “n”

• EN50281-1-1:1998 + A1, Electrical Apparatus for Use in the Presence of Combustible Dust - Part 1-1: Protection by Enclosure

• EN50284:1999, Special requirements for construction, test and marking of electrical apparatus of equipment group II, category 1G

The power supply is tested to meet the Council Directive 76/117/EC Electrical Apparatus for Explosive Atmospheres by applying the following standards:

• EN50014:1977 + A1-A5, Electrical Apparatus for Potentially Explosive Atmospheres

• EN50018:1977 + A1-A3, Electrical Apparatus for Potentially Explosive Atmospheres - Flameproof Enclosure “d”

• EN50019:1977 + A1-A5, Electrical Apparatus for Potentially Explosive Atmospheres - Increased Safety “e”

• EN50020:1977 + A1-A5, Electrical Apparatus for Potentially Explosive Atmospheres - Intrinsic Safety “i”

Repair System components are not field-repairable. Any attempt to open a system component will void the warranty and the IS certification. If repair is necessary, return the system component to the manufacturer.

Attention: Avoid electrostatic charge.

Publication 1797-6.5.6 - June 2005

Page 32: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1-4 General CENELEC Certification Information

About Zone 22 Junction Boxes (Cabinets)

Pepperl+Fuchs junction boxes (type IVK2-ISRPI-V8LC, IVK2-ISRPI-V8HYW, or IVK2-ISPRI-V16LC) ensures the basic protection for the intrinsically safe apparatus of the FLEX Ex system for use in Zone 22. It corresponds with category 3D according to RL 94/9 EG and with the type label marked with the following information:

Pepperl+Fuchs GmbH68301 MannheimIVK2-ISRPI-V8LC (or IVK2-ISRPI-V8HYW or IVK2-ISRPI-V16LC)EX (Hexagon) II 3D IP54 T 70°CCESerial (manufacturing) numberModel

The maximum dissipation is limited to 60W for the IVK2-ISRPI-V8LC and IVK2-ISRPI-V8HYW junction boxes and 120W for the IVK2-ISRPI-V16LC junction box.

The maximum ambient temperature for the junction boxes complies with the internal dissipation. It must be guaranteed that the cabinet internal temperature 70°C is not exceeded (requirement to the installed FLEX Ex equipment). For example, the IVK2-ISRPI-V8LC junction box has a maximum ambient temperature of 45°C with maximum mounting.

All cable entries, which are not equipped with a cable, must be provided with a seal designated for it (IP54). Drillings in the housing, which are not used due to less assembly, must be closed seal (IP54).

Close the junction box with the provided key after the assembly and mounting. If the junction box must be opened for maintenance purposes during operation, exercise care to prevent dust from penetrating inside of the enclosure.

ATTENTION When installing, commissioning, operating, and maintaining devices with intrinsically safe circuits, the certificate of conformity of the devices, as well as the applicable national and local construction, installation, and operating regulations must be heeded (in Germany DIN EN 50020, DIN VDE 0165).

ATTENTION Repairs to devices having intrinsically safe circuitry may only be carried out by qualified personnel in accordance with the valid regulations (Elex V).

Publication 1797-6.5.6 - June 2005

Page 33: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 2

ControlNet Ex System

20125-M

Ex

PWR

1797-ACNR15

PWR

Adapter Bus Connectors Terminal Base KeyswitchFlexbus Connector

Ex I/O Module

Terminal Strips

Field PowerConnection Terminals

1 Publication 1797-6.5.6 - June 2005

Page 34: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

2-2 ControlNet Ex System

ControlNet Ex System Diagram

1

.

.

.

.

.

.

.

.

.

.

..

.

.

.

.

.

.

.

Safe

Are

a

CNet

Ex

trk tr

m

3067

0-M

Cont

rolN

et E

xta

p

The

Coax

Trun

k Ca

ble

is p

erm

itted

to h

ave

a m

axim

um le

ngth

of 1

,000

m w

ith o

nly

2 co

nnec

ted

Cont

rolN

et E

x Ta

ps d

ropp

ing

to o

nly 2

50m

with

the

max

imum

allo

wed

con

nect

ed C

ontro

lNet

Ex

Taps

of 4

8.

Haz

ardo

us A

rea

Zone

0

The

Cont

rolN

et E

x Sy

stem

is a

n in

trins

ical

ly s

afe

syst

em a

ccor

ding

to E

N 5

0039

. Whe

n in

stal

ling

the

syst

em, t

he c

ertif

icat

e of

con

form

ity a

nd th

e na

tiona

l ins

talla

tion

regu

latio

ns m

ust b

e he

eded

. The

co

mpo

nent

s of

the

Cont

rolN

et E

x sy

stem

and

the

inte

rcon

nect

ions

are

sho

wn

on th

e in

stal

latio

n dr

awin

g (A

-B P

ub. 1

797-

6.5.

6).

fiber

Ci <

60p

FCo

ntro

lNet

Ex

tap

Cont

rolN

et E

xta

p

Cont

rolN

et E

x ta

p

CNet

Ex

tap

trmCi

< 6

8pF

Li n

egl.

ChB

ChA

Uo=5

.4V,

Io=1

60m

A,F -

3>50

0kHz

Pow

er S

uppl

y Ui=

9.5V

, Ii=

1A,

Ci<1

20nF

, Li

=neg

ligib

le

coax

trun

k ca

ble

Ch1

The

ambi

ent t

empe

ratu

re ra

nge

of th

e Co

ntro

lNet

Ex

syst

em is

-20

to +

70o C.

Nod

e 4

... 4

8

Flex

bus

Uo=5

.4V,

Io

=400

mA,

Po

=2.1

6W,

Co=6

5 µF,

Lo=1

0 µH

For t

he tr

ansm

ittal

bet

wee

n th

e sa

fe a

rea

and

the

haza

rdou

s ar

ea o

nly

optic

al g

lass

-fibe

rs a

re

perm

itted

. The

dia

met

er o

f a s

ingl

e gl

ass-

fiber

mus

t be

>6um

. The

pow

er d

ensi

ty o

f the

tran

smitt

er

diod

e m

ust b

e <5

mW

/mm

2 .

Prot

ect t

he s

yste

m a

gain

st e

lect

rost

atic

cha

rge.

Pos

t a s

ign

near

the

mai

n co

mpo

nent

s of

the

syst

em:

Atte

ntio

n! A

void

ele

ctro

stat

ic c

harg

e.

1797

-ACN

R15/

* or

RS

D-GW

-Ex2

.CN

Uo=5

.4V,

Io

=160

mA,

F -

3>50

0kHz

75 O

hm1W

Ci n

egl.

Li n

egl.

ChB

ChA

Uo=5

.4V,

Io=1

60m

A,F -

3>50

0kHz

Pow

er S

uppl

y Ui=

9.5V

, Ii=

1A,

Ci< 1

20nF

, Li

=neg

ligib

le

Nod

e 3

Flex

bus

Uo=5

.4V,

Io

=400

mA,

Po

=2.1

6W,

Co=6

5 µF,

Lo=1

0 µH

1797

-ACN

R15/

* or

RS

D-GW

-Ex2

.CN

Uo=5

.4V,

Io

=160

mA,

F -

3>50

0kHz

Nea

r the

mai

n co

mpo

nent

s of

the

syst

em a

pla

te w

ith th

e sy

stem

mar

king

mus

t be

atta

ched

. If

the

syst

em is

inst

alle

d in

a c

abin

et th

e pl

ate

mus

t be

fixed

on

the

insi

de o

f the

cab

inet

doo

r.

*RG6

-CN

et is

def

ined

as:

Cabl

e Im

peda

nce

= 75

Ohm

+ o

r - 3

Ohm

Cabl

e Ca

paci

tanc

e < 5

.94n

F pe

r 100

mCa

ble

Resi

stan

ce >

9.08

Ohm

per

100

mCa

ble

Atte

nuat

ion

(-20

to +

70o C)

0.2

MHz

> 0

.93d

B/10

0m

5M

Hz >

1.3

9dB/

100m

0.5

MHz

> 0

.95d

B/10

0m

10M

Hz >

1.8

6dB/

100m

1M

Hz >

1.0

7dB/

100m

20M

Hz >

2.7

3dB/

100m

2M

Hz >

1.1

6dB/

100m

50M

Hz >

4.3

3dB/

100m

coax

trun

k ca

ble

Cabl

e ty

pe 1

189A

, 309

2A, o

r 30

92A

Blue

from

man

ufac

ture

r Be

lden

Wire

or t

ype

RG6-

CNet

*

Li <

560

nH

Li <

110

0uH

Li <

110

0uH

Nod

e 1

Haz

ardo

us A

rea

Zone

1

1797

-RPA

/* o

r RS

D-CF

A-Ex

.CN

Nod

e 2

1797

-RPF

M/*

or

RSD-

FC-E

x2.C

N 3

km17

97-R

PFM

/* o

r RS

D-FC

-Ex2

.CN

3km

fiber

Ch0

fiber

Ch1

fiber

Ch0

Uo=5

.4V,

Io=2

01m

A,F -

3>50

0kHz

Pow

er S

uppl

y Ui=

9.5V

, Ii=

1A,

Ci<1

20nF

, Li

=neg

ligib

le

CNet

1797

-BCN

R or

RS

-FB-

Ex2.

CN

Publication 1797-6.5.6 - June 2005

Page 35: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

ControlNet Ex System 2-3

Describing the ControlNet Ex System Diagram

A maximum of 48 ControlNet ExTM nodes may be connected together by 250m of coax cable and 48 taps. The distance increases to 1000m when you use only 2 taps. See the table below for more information.The fiber media of the 1797-RPFM can be installed in a hazardous location (Zone 0, 1 or 2) to connect two 1797-RPFM modules or they can be installed through different locations into the non-hazardous location to connect the 1797-RPFM with any approved associated apparatus.All cables and fiber media that are not light blue must be marked as IS using the 1797-EXMK marking kit or other locally approved IS identification and/or segregation method.During the installation of the ControlNet Ex system, all metallic parts must be isolated to prevent an earth connection (high voltage withstanding of isolating material must be > 500V ac).

System Diagram Name

Catalog Number Catalog Name Description

1797-RPA 1797-RPA ControlNet Ex Modular Repeater Adapter

Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx

1797-RPFM 1797-RPFM ControlNet Ex Fiber Repeater Module, Medium Distance

Allows connection of a maximum of two devices per 1797-RPA and is powered directly by 1797-RPA

1797-ACNR15 1797-ACNR15 Redundant Media ControlNet Ex Adapter

Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx -each one with two redundant output channels that are connected to different ControlNet Ex networks (coax cables and 1797-TPx)

1797-BCNR 1797-BCNR Redundant ControlNet Ex Barrier

Allows connection between ControlNet and ControlNet Ex networks

CNet Ex Tap Trm

1797-TCAP ControlNet Ex Tap (Dummy) Terminator

Represents one ControlNet Ex node and is a simple capacitor (56pF) with a coax connector

ControlNet Ex Tap

1797-TPx ControlNet Ex Coax Tap

Four types of connections available: S (straight t-tap), R (right angle t-tap), YS (straight y-tap), and YR (right angle y-tap) - a maximum of 48 taps can be connected together by coax trunk cable

CNet Ex Trk Trm

1797-XT ControlNet Ex Trunk Terminator

Simple resistor (75Ω) with coax connector that must be on each end of the ControlNet Ex coax trunk for termination

Coax Trunk Cable

1786-RG6 Quad-Shield, RG-6 75Ω Coax Trunk Cable

Maximum (functional) length between 2 1797-TPx is 3280ft (1000m) - each 1797-TPx reduces the (functional) coax cable length by 53.4ft (16.3m)

None None Standard Coax Trunk Cable BNC Couplers

Different standard cable couplers, 90o, 180o, etc.

Publication 1797-6.5.6 - June 2005

Page 36: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

2-4 ControlNet Ex System

Certified Equivalent ControlNet Ex System Diagram Items

You may use these items as equivalents for the items shown on the system diagram.

System Diagram Name Catalog Number Source

1797-RPA 1797-RPA Allen-Bradley

RSD-CFA-Ex.CN Pepperl+Fuchs

1797-RPFM 1797-RPFM Allen-Bradley

RSD-FC-Ex2.CN Pepperl+Fuchs

1797-ACNR15 1797-ACNR15 Allen-Bradley

RSD-GW-Ex2.CN Pepperl+Fuchs

1797-BCNR 1797-BCNR Allen-Bradley

RS-FB-Ex2.CN Pepperl+Fuchs

Coax Trunk Cable1 1786-RG6 Allen-Bradley

3092A2 Belden Wire & Cable Co.

3092A with blue jacket Belden Wire & Cable Co.

ControlNet Ex Tap 1797-TPx Allen-Bradley

RS-TPx-Ex Pepperl+Fuchs

CNet Ex Trk Trm 1797-XT Allen-Bradley

RS-XT-Ex Pepperl+Fuchs

CNet Ex Tap Trm 1797-TCAP Allen-Bradley

RS-TCAP-Ex Pepperl+Fuchs

1 In addition to these cable types, the following specification can be followed to allow additional types:Cable Impedance = 75Ω ± 3ΩCable Capacitance = <5.94nF per 100mCable Resistance = >9.08Ω per 100mCable Attenuation 0.2MHz > 0.93dB/100m 5MHz > 1.39dB/100m(-20 to +70oC) 0.5MHz > 0.95dB/100m 10MHz > 1.86dB/100m

1MHz > 1.07dB/100m 20MHz > 2.73dB/100m2MHz > 1.16dB/100m 50MHz > 4.33dB/100m

2 Belden Wire & Cable 1189A may be used, but with functional loss of communication distance and/or nodes.

Publication 1797-6.5.6 - June 2005

Page 37: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

ControlNet Ex System 2-5

Installation in Zone 1 Modules must not be exposed to the environment. Provide a suitable metal enclosure. A label with this system marking must be attached near the main components of the system. If the system is installed in a cabinet, this label must be fixed inside the cabinet.

Installation in Zone 22 When the ControlNet Ex system is installed in Zone 22, all system components (except the coax cable and ControlNet taps) must be installed in cabinets of the following type: IVK-ISRPI-V16LC; IVK-ISRPI-V8HYW; or IVK-ISRPI-V8LC. For more information on these cabinets, see page 1-4.

Electrostatic Charge Protect the system against electrostatic charge. Post a sign near each module: Attention! Avoid electrostatic charge. For your convenience, a sign which can be cut out and posted is included in this chapter.

Repair Modules are not field-repairable. Any attempt to open a module will void the warranty and the IS certification. If repair is necessary, return the module to the manufacturer.

ATTENTION Modules cannot be used in an intrinsically safe environment after they have been exposed to non-intrinsically safe signals.

0102

ControlNet Ex System

Allen-Bradley

Attention!Avoid electrostatic charging!

-200C <= Ambient Temperature <= +700C

1 Allen-Bradley Dr.Mayfield Hts., OH USA

DMT 99 ATEX E 065 XII (1) 2G SYST EEx ia/ib IIB/C T4

Attention: Avoid electrostatic charge.

Publication 1797-6.5.6 - June 2005

Page 38: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

2-6 ControlNet Ex System

General Specifications

ATTENTION When installing, commissioning, operating, and maintaining devices with intrinsically safe circuits, the certificate of conformity of the devices, as well as the applicable national and local construction, installation, and operating regulations must be heeded (in Germany DIN EN 50020, DIN VDE 0165).

ATTENTION Repairs to devices having intrinsically safe circuitry may only be carried out by qualified personnel in accordance with the valid regulations (Elex V).

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification II (1) 2G SYST EEx ia/ib IIB/IIC T4

Certificates DMT 99 ATEX E 065 X

Publication 1797-6.5.6 - June 2005

Page 39: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 3

1797-TB3 FLEX Ex Terminal Base Unit

General Information FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation You will need to rotate the keyswitch (1) to the correct position depending on the module. Refer to the module’s installation instructions for more information. Do not change the position of the keyswitch after wiring the terminal base unit.

Make certain that you only connect terminal base units to other intrinsically safe system modules or adapters to maintain the integrity of the intrinsically-safe backplane.

Do not remove the flexbus cover (8) on the right-most terminal base unit.

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 45 46 47 48 49 5044 51

42332

Label here(8) flexbus

cover

(1) keyswitch

41307

1 Publication 1797-6.5.6 - June 2005

Page 40: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

3-2 1797-TB3 FLEX Ex Terminal Base Unit

Inputs Do not apply any non-intrinsically safe signals to the terminal base.

When using as an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

The terminals in the terminal base unit may be electrically connected to each other by the insertion of FLEX Ex I/O modules. See the module installation instructions to determine this.

Description The 1797-TB3 terminal base has 36 wiring connections to/from a plug-in module. The use of each terminal depends on the module mounted in this base.

The 1797-TB3 terminal base also has connections for cold junction compensation and terminals designated for shield termination to chassis ground.

The terminal base is equipped with a factory-installed tab cover for the backplane bus connection. The tab cover may be removed only when the terminal base unit is connected to other terminal base units..

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety requirements.

ATTENTION • Make certain that you power the terminal base unit with an intrinsically safe power supply. Do not exceed the values listed in the specifications for the terminal base unit.

• Do not use the unused terminals on the terminal base unit. Using these terminals as supporting terminals can result in damage to modules and/or unintended operation of your system.

Wiring Connections for Terminal Base 1797-TB30 1 32 4 5 6 7 8 9 10 11 12 13 14 15

26 27 28 29 30 31 32 3325242322212019181716

44 45 46 47 48 49 50 5143424140393837363534

41252+V -V -V+V

A

B

C

No connections allowed to terminals 36 and 49

Publication 1797-6.5.6 - June 2005

Page 41: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-TB3 FLEX Ex Terminal Base Unit 3-3

Intrinsically Safe Specifications

For a full list of specifications, refer to the FLEX Ex Terminal Base Installation Instructions, publication 1797-5.1.

Terminals Assignments+34, -35, +50, -51, and 96

pinifemale I/O connectorpinsi30-32, 62-64, 94-96i

36, 49All Other Terminals

Only for intrinsically safe circuitsUi <10V dcIi <2.5ACi < 1nFLi NegligibleMust not be used for any connectionUi <30V dcIi <100mACi <1nFLi Negligible

Flexbus Connection Intrinsically Safe Ui <10V dcIi <400mACi <1nFLi Negligible

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification II 2G EEx ia IIC T4

Certificates DMT 98 ATEX E012 U

Publication 1797-6.5.6 - June 2005

Page 42: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

3-4 1797-TB3 FLEX Ex Terminal Base Unit

Notes:

Publication 1797-6.5.6 - June 2005

Page 43: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 4

1797-TB3S FLEX Ex Terminal Base Unit

General Information FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation You will need to rotate the keyswitch (1) to the correct position depending on the module. Refer to the module’s installation instructions for more information. Do not change the position of the keyswitch after wiring the terminal base unit.

Make certain that you only connect terminal base units to other intrinsically safe system modules or adapters to maintain the integrity of the intrinsically-safe backplane.

Do not remove the flexbus cover (8) on the right-most terminal base unit.

42333

Label here (8) flexbus cover

(1) keyswitch

41307

1 Publication 1797-6.5.6 - June 2005

Page 44: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

4-2 1797-TB3S FLEX Ex Terminal Base Unit

Inputs Do not apply any non-instrinsically safe signals to the terminal base.

When using as an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

The terminals in the terminal base unit may be electrically connected to each other by the insertion of FLEX Ex I/O modules. See the module installation instructions to determine this.

Description The 1797-TB3S terminal base has 36 wiring connections to/from a plug-in module. The use of each terminal depends on the module mounted in this base.

The 1797-TB3S terminal base also has connections for cold junction compensation and terminals designated for shield termination to chassis ground.

The terminal base is equipped with a factory-installed tab cover for the backplane bus connection. The tab cover may be removed only when the terminal base unit is connected to other terminal base units.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety requirements.

ATTENTION • Make certain that you power the terminal base unit with an intrinsically safe power supply. Do not exceed the values listed in the specifications for the terminal base unit.

• Do not use the unused terminals on the terminal base unit. Using these terminals as supporting terminals can result in damage to modules and/or unintended operation of your system.

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

18 19 20 21 22 23 3324 25 26 27 28 29 30 31 3217

35 36 37 38 47 48 49 5034 51

16

39 40 41 42 43 44 45 46

Wiring Connections for Terminal Base 1797-TB3S

41254

Row ARow BRow C

Label placed at top of wiring area

Row A

Row B

Row C

+V -V -V+VNo connections allowed to terminals 36 and 49

Publication 1797-6.5.6 - June 2005

Page 45: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-TB3S FLEX Ex Terminal Base Unit 4-3

Intrinsically Safe Specifications

For a full list of specifications, refer to the FLEX Ex Spring Clamp Terminal Base Installation Instructions, publication 1797-5.2.

Terminals Assignments+34, -35, +50, -51, and 96

pinifemale I/O connectorpinsi30-32, 62-64, 94-96i

36, 49All Other Terminals

Only for intrinsically safe circuitsUi <10V dcIi <2.5ACi < 1nFLi NegligibleMust not be used for any connectionUi <30V dcIi <100mACi <1nFLi Negligible

Flexbus Connection Intrinsically Safe Ui <10V dcIi <400mACi <1nFLi Negligible

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification II 2G EEx ia IIC T4

Certificates DMT 98 ATEX E012 U

Publication 1797-6.5.6 - June 2005

Page 46: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

4-4 1797-TB3S FLEX Ex Terminal Base Unit

Notes:

Publication 1797-6.5.6 - June 2005

Page 47: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 5

1797-IBN16 FLEX Ex 16 NAMUR Input Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 6 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs Each input can be operated from a NAMUR sensor or a mechanical contact (if mechanical inputs are used). Do not apply any non-intrinsically safe signals to this module.

When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

The channels in this module are electrically connected to each other and have a common plus-line.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

1 Publication 1797-6.5.6 - June 2005

Page 48: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

5-2 1797-IBN16 FLEX Ex 16 NAMUR Input Module

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 16 NAMUR Input Module Installation Instructions, publication 1797-5.7.

Row A

Row B

Row C

+V -V +V -V41504

+ -

Ch 0

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

+ -

Ch 1

+ -

Ch 2

+ -

Ch 3

+ -

Ch 4

+ -

Ch 5

+ -

Ch 6

+ -

Ch 7

+ -

Ch 8

+ -

Ch 9

+ -

Ch 10

+ -

Ch 11

+ -

Ch 12

+ -

Ch 13

+ -

Ch 14

+ -

Ch 15

No connection allowed to terminals 36 and 49

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Output (intrinsically safe) (16 position male/female flexbusconnector)

Ui < 5.8VIi < 400mALi = NegligibleCi = Negligible

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1ALi = NegligibleCi = Negligible

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4II (1D) (2D)

Certificates DMT 98 ATEX E 013 X

Publication 1797-6.5.6 - June 2005

Page 49: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IBN16 FLEX Ex 16 NAMUR Input Module 5-3

CE/CENELEC I/O Entity Parameters (Each Channel) Protection Group Allowed

CapacitanceAllowed Inductance

Lo/Ro Ratio

Uo < 14.5VIo < 15mAPo < 40mWCharacteristic: linear

EEx ia IIB 1µF 10mH 2.6mH/Ω

EEx ia IIC 300nF 2mH 0.65mH/Ω

Publication 1797-6.5.6 - June 2005

Page 50: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

5-4 1797-IBN16 FLEX Ex 16 NAMUR Input Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 51: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 6

1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 7 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Outputs Each output can operate a discrete field device. Do not apply any non-intrinsically safe signals to this module.

When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

40068

Row A

Row B

Row C

+ + + +- - - -

ch0 ch1 ch2 ch3

+V +V-V -VNo connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to 32, 36, 37, 38, 39, 46, 47, 48, 49

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

1 Publication 1797-6.5.6 - June 2005

Page 52: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

6-2 1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 24V dc Non-Isolated Source 4 Output Module Installation Instructions, publication 1797-5.6.

CE/CENELEC I/O Entity Parameters

Signal output (+ to -) for ch 0 to ch 3 (terminals: 0-1; 4-5; 8-9; 12-13)

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Output (intrinsically safe) (16 position male/female flexbusconnector)

Ui < 5.8VIi < 400mALi = NegligibleCi = 1.35µF

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1ALi = NegligibleCi < Negligible

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4II (1D) (2D)

Certificates DMT 98 ATEX E 040 X

Protection Group Allowed Capacitance

Allowed Inductance

1797-OB4DUo = 27.4VIo = 110mA

EEx ia IIB 677nF 8mH

IIC 87nF 2mH

If concentrated capacitance and/or inductance are available, use the following values.

EEx ia IIB 150nF 5mH

IIC 30nF 2mH

Publication 1797-6.5.6 - June 2005

Page 53: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 7

1797-IE8 FLEX Ex 8 Input Analog Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 3 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs Each input can be operated from an analog field device signal. Do not apply any non-intrinsically safe signals to this module.

When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

The channels in this module are electrically connected to each other and have a common plus-line.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

1 Publication 1797-6.5.6 - June 2005

Page 54: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

7-2 1797-IE8 FLEX Ex 8 Input Analog Module

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Input Analog Module Installation Instructions, publication 1797-5.5.

Row A

Row B

Row C

+ -+ -+ -+ -

Ch 7Ch 6Ch 5Ch 4

+V -V +V -V40071

sigsigsigsig

No connection allowed

No connection allowed

Ch 7

+ -+ -+ -+ -

Ch 2Ch 1Ch 0

sigsigsigsig

Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Output (intrinsically safe) (16 position male/female flexbusconnector)

Ui < 5.8VIi < 400mALi = NegligibleCi < 1.35µF

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1ALi = NegligibleCi = Negligible

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4II (1D) (2D)

Certificates DMT 98 ATEX E 020 X

Publication 1797-6.5.6 - June 2005

Page 55: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8 FLEX Ex 8 Input Analog Module 7-3

CE/CENELEC I/O Entity Parameters

Measurement input (sig to -) for ch 0 to ch 7 (terminals: 1-2; 5-6; 9-10; 13-14; 18-19; 22-23; 26-27; 30-31)

Source output (+ to sig) for ch 0 to ch 7 (terminals: 0-1; 4-5; 8-9; 12-13; 17-18; 21-22; 25-26; 29-30)

Source output plus measurement input (+ to -) for ch 0 to ch 7 (terminals: 0-2; 4-6; 8-10; 12-14; 17-19; 21-23; 25-27; 29-31)

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 5VIo = 1mAPo = 1.3mW

EEx ia IIB 1000µF 1H

Ui = 28VIi = 93mACi and Li negligible

IIC 100µF 1H

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 23.7VIo = 92.5mAPo = 548mW

EEx ia IIB 560nF 10mHIIC 66nF 2.5mH

If concentrated capacitance and/or inductance are available, use the following values.

EEx ia IIB 320nF 10mHIIC 60nF 2mH

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 23.7VIo = 93.5mAPo = 555mW

EEx ia IIB 560nF 10mHIIC 66nF 2.5mH

If concentrated capacitance and/or inductance are available, use the following values.

EEx ia IIB 320nF 10mHIIC 60nF 2mH

Publication 1797-6.5.6 - June 2005

Page 56: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

7-4 1797-IE8 FLEX Ex 8 Input Analog Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 57: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 8

1797-IE8H FLEX Ex 8 Input HART Analog Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 3 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs Each input can be operated from an analog field device signal. Do not apply any non-intrinsically safe signals to this module.

When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

The channels in this module are electrically connected to each other and have a common plus-line.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

1 Publication 1797-6.5.6 - June 2005

Page 58: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

8-2 1797-IE8H FLEX Ex 8 Input HART Analog Module

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Analog Input Modules Installation Instructions, publication 1797-5.5.

Row A

Row B

Row C

+ -+ -+ -+ -

Ch 7Ch 6Ch 5Ch 4

+V -V +V -V40071

sigsigsigsig

No connection allowed

No connection allowed

Ch 7

+ -+ -+ -+ -

Ch 2Ch 1Ch 0

sigsigsigsig

Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Output (intrinsically safe) (16 position male/female flexbusconnector)

Ui < 5.8VIi < 400mALi = NegligibleCi < 1.35µF

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1ALi = NegligibleCi = Negligible

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4II (1D) (2D)

Certificates DMT 98 ATEX E 020 X

Publication 1797-6.5.6 - June 2005

Page 59: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8H FLEX Ex 8 Input HART Analog Module 8-3

CE/CENELEC I/O Entity Parameters

Measurement input (sig to -) for ch 0 to ch 7 (terminals: 1-2; 5-6; 9-10; 13-14; 18-19; 22-23; 26-27; 30-31)

Source output (+ to sig) for ch 0 to ch 7 (terminals: 0-1; 4-5; 8-9; 12-13; 17-18; 21-22; 25-26; 29-30)

Source output plus measurement input (+ to -) for ch 0 to ch 7 (terminals: 0-2; 4-6; 8-10; 12-14; 17-19; 21-23; 25-27; 29-31)

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 5VIo = 1mAPo = 1.3mW

EEx ia IIB 1000µF 1H

Ui = 28VIi = 93mACi and Li negligible

IIC 100µF 1H

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 23.7VIo = 92.5mAPo = 548mW

EEx ia IIB 560nF 10mHIIC 66nF 2.5mH

If concentrated capacitance and/or inductance are available, use the following values.

EEx ia IIB 320nF 10mHIIC 60nF 2mH

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 23.7VIo = 93.5mAPo = 555mW

EEx ia IIB 560nF 10mHIIC 66nF 2.5mH

If concentrated capacitance and/or inductance are available, use the following values.

EEx ia IIB 320nF 10mHIIC 60nF 2mH

Publication 1797-6.5.6 - June 2005

Page 60: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

8-4 1797-IE8H FLEX Ex 8 Input HART Analog Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 61: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 9

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 3 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs Each input can be operated from an analog field device signal. Do not apply any non-intrinsically safe signals to this module.

When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

The channels in this module are electrically connected to each other and have a common plus-line.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

1 Publication 1797-6.5.6 - June 2005

Page 62: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

9-2 1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Analog Input Modules Installation Instructions, publication 1797-5.5.

Row A

Row B

Row C

+ -+ -+ -+ -

Ch 7Ch 6Ch 5Ch 4

+V -V +V -V40071

sigsigsigsig

No connection allowed

No connection allowed

Ch 7

+ -+ -+ -+ -

Ch 2Ch 1Ch 0

sigsigsigsig

Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Output (intrinsically safe) (16 position male/female flexbusconnector)

Ui < 5.8VIi < 400mALi = NegligibleCi < 1.35µF

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1ALi = NegligibleCi = Negligible

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4II (1D) (2D)

Certificates DMT 98 ATEX E 020 X

Publication 1797-6.5.6 - June 2005

Page 63: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter 9-3

CE/CENELEC I/O Entity Parameters

Measurement input (sig to -) for ch 0 to ch 7 (terminals: 1-2; 5-6; 9-10; 13-14; 18-19; 22-23; 26-27; 30-31)

Source output (+ to sig) for ch 0 to ch 7 (terminals: 0-1; 4-5; 8-9; 12-13; 17-18; 21-22; 25-26; 29-30)

Source output plus measurement input (+ to -) for ch 0 to ch 7 (terminals: 0-2; 4-6; 8-10; 12-14; 17-19; 21-23; 25-27; 29-31)

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 5VIo = 1mAPo = 1.3mW

EEx ia IIB 1000µF 1H

Ui = 28VIi = 93mACi and Li negligible

IIC 100µF 1H

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 23.7VIo = 92.5mAPo = 548mW

EEx ia IIB 560nF 10mHIIC 66nF 2.5mH

If concentrated capacitance and/or inductance are available, use the following values.

EEx ia IIB 320nF 10mHIIC 60nF 2mH

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 23.7VIo = 93.5mAPo = 555mW

EEx ia IIB 560nF 10mHIIC 66nF 2.5mH

If concentrated capacitance and/or inductance are available, use the following values.

EEx ia IIB 320nF 10mHIIC 60nF 2mH

Publication 1797-6.5.6 - June 2005

Page 64: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

9-4 1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

Notes:

Publication 1797-6.5.6 - June 2005

Page 65: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 10

1797-OE8 FLEX Ex 8 Output Analog Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 4 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Outputs Each output channel can operate an analog field device. Do not apply any non-intrinsically safe signals to this module.

When using an intrinsically safe electrical apparatus according to EN50020, the European Community directives and regulations must be followed.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

41440

Row A

Row B

Row C

ch0 ch1 ch2 ch3

+V +V-V -V

+ + + +- - - -

ch4 ch5 ch6 ch7

+ - + - + - + -

No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

1 Publication 1797-6.5.6 - June 2005

Page 66: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

10-2 1797-OE8 FLEX Ex 8 Output Analog Module

General Specifications For a full list of specifications, refer to FLEX Ex 8 Analog Output Modules Installation Instructions, publication 1797-5.3.

CE, CENELEC I/O Entity Parameters

Signal output (+ to -) for ch 0 to ch 7 (terminals: 0-1; 4-5; 8-9; 12-13; 17-18; 21-22; 25-26; 29-30)

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Output (Intrinsically Safe)(16 pin male and femaleflexbus connector)

Ui < 5.8V dcIi < 400mALi = NegligibleCi < 1.35µF

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1ALi = NegligibleCi = Negligible

Operational Temperature -20 to +70oC (-4 to +158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4II (1D) (2D)

Certificates DMT 00 ATEX E 042 X

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 21VIo = 100mAPo = 520mW

EEx ia IIB 1.27µF 8mHIIC 188nF 2mH

If concentrated capacitance and/or inductance are available, use the following values.

EEx ia IIB 295nF 10mHIIC 70nF 2mH

Publication 1797-6.5.6 - June 2005

Page 67: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 11

1797-OE8H FLEX Ex 8 Output HART Analog Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 4 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Outputs Each output channel can operate an analog field device. Do not apply any non-intrinsically safe signals to this module.

When using an intrinsically safe electrical apparatus according to EN50020, the European Community directives and regulations must be followed.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

41440

Row A

Row B

Row C

ch0 ch1 ch2 ch3

+V +V-V -V

+ + + +- - - -

ch4 ch5 ch6 ch7

+ - + - + - + -

No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

1 Publication 1797-6.5.6 - June 2005

Page 68: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

11-2 1797-OE8H FLEX Ex 8 Output HART Analog Module

General Specifications For a full list of specifications, refer to FLEX Ex 8 Analog Output Modules Installation Instructions, publication 1797-5.3.

CE, CENELEC I/O Entity Parameters

Signal output (+ to -) for ch 0 to ch 7 (terminals: 0-1; 4-5; 8-9; 12-13; 17-18; 21-22; 25-26; 29-30)

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Output (Intrinsically Safe)(16 pin male and femaleflexbus connector)

Ui < 5.8V dcIi < 400mALi = NegligibleCi < 1.35µF

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1ALi = NegligibleCi = Negligible

Operational Temperature -20 to +70oC (-4 to +158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4II (1D) (2D)

Certificates DMT 00 ATEX E 042 X

Protection Group Allowed Capacitance

Allowed Inductance

Uo = 21VIo = 100mAPo = 520mW

EEx ia IIB 1.27µF 8mHIIC 188nF 2mH

If concentrated capacitance and/or inductance are available, use the following values.

EEx ia IIB 295nF 10mHIIC 70nF 2mH

Publication 1797-6.5.6 - June 2005

Page 69: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 12

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 2 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs Each input can be operated from a thermocouple (TC) or resistance temperature detector (RTD). Do not apply any non-intrinsically safe signals to this module.

When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

The channels in this module are electrically connected to each other and have a common plus-line.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

1 Publication 1797-6.5.6 - June 2005

Page 70: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

12-2 1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Thermocouple/RTD Input Module Installation Instructions, publication 1797-5.4.

Row A

Row B

Row C

Ch 7Ch 6Ch 5Ch 4

+V CJC -V

41505

Ch 7

+ L

Ch 2Ch 1Ch 0 Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

H - + LH - + LH - + LH -

+ LH - + LH - + LH - + LH -

-V CJCchassis GND for shield

chassis GND for shield

0+ 0- 1-1+

No connection allowed to terminals 36 and 49

+V

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Output (intrinsically safe) (16 position male/female flexbusconnector)

Ui < 5.8VIi < 400mALi = NegligibleCi < 1.35µF

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1ALi = NegligibleCi = Negligible

Operational Temperature -20 to +70oC (-4 to 158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4II (1D) (2D)

Certificates DMT 98 ATEX E 023X

Publication 1797-6.5.6 - June 2005

Page 71: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module 12-3

CE/CENELEC I/O Entity Parameters

Input circuits (+ to -) for ch0 to ch7 (terminals: 0-3; 4-7; 8-11; 12-15; 17-20; 21-24; 25-28; 29-32)

CJC circuits (+ to -) for CJC0 and CJC1 (terminals: 37, 39; 46, 48)

Input circuits (+ to -) for ch0 to ch7 and CJC circuits (+ to -) for CJC0 and CJC1 (terminals 0-3, 37, 39; 4-7, 37, 39; 8-11, 37, 39; 12-15, 37, 39; 17-20, 37, 39; 21-24, 37, 39; 25-28, 37, 39; 29-32, 37, 39; 0-3, 46, 48; 4-7, 46, 48; 8-11, 46, 48; 12-15, 46, 48; 17-20, 46, 48; 21-14, 46, 48; 25-28, 46, 48; 29-32, 46, 48)

Protection Group Allowed Capacitance

Allowed Inductance

Lo/Ro Ratio

Uo = 9VIo = 37mAPo = 83mW

EEx ia IIB 40µF 80mH 1.7mH/Ω

EEx ia IIC 4.9µF 20mH 0.4mH/Ω

Protection Group Allowed Capacitance

Allowed Inductance

Lo/Ro Ratio

Uo = 9VIo = 1mAPo = 3mW

EEx ia IIB 40µF 1H 63mH/Ω

EEx ia IIC 4.9µF 1H 15mH/Ω

Protection Group Allowed Capacitance

Allowed Inductance

Lo/Ro Ratio

Uo = 9VIo = 38mAPo = 86mW

EEx ia IIB 40µF 80mH 1.7mH/Ω

EEx ia IIC 4.9µF 20mH 0.4mH/Ω

Publication 1797-6.5.6 - June 2005

Page 72: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

12-4 1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 73: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 13

1797-IJ2 FLEX Ex Frequency Input Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 1 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs The frequency input module has 2 input channels. Each input can accept inputs from magnetic pickups or proximity probes. Each input channel has 2 input selections: frequency input or gate input. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other.

When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

1 Publication 1797-6.5.6 - June 2005

Page 74: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

13-2 1797-IJ2 FLEX Ex Frequency Input Module

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Frequency Input Module Installation Instructions, publication 1797-5.7.

Row A

Row B

Row C

+V -V

42334

3V V+

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

6V GND 50mV Sel

N500/50 mV

8V 8V N GND 6VV+ 3V

R0 NO R0 NC

-V

No connection allowed to terminals 19, 30, 36, 38, 39, 47, 48, 49

+VR0 COM R1 COM

50mV Sel

500/50 mV

Channel 0 Frequency Input Channel 1 Frequency Input

GND

GND 50mV Sel

N500/50 mV

8V 8V N 50mV Sel

500/50 mV

GND R1 NOR1 NC

Channel 0 Gate Input Channel 1 Gate Input

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Output (intrinsically safe) (16 position male/female flexbusconnector)

Uo < 5.8VIo < 400mALi = NegligibleCi < 2.64µF

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1ALi = NegligibleCi = Negligible

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4II (1D) (2D)

Certificates DMT 98 ATEX E 033 X

Publication 1797-6.5.6 - June 2005

Page 75: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IJ2 FLEX Ex Frequency Input Module 13-3

CE/CENELEC Input I/O Entity Parameters

Channel 0 Frequency Input

Field devices may only be connected to the terminals of one of the five following circuits. The terminals of the remaining four circuits must not be connected.

Namur/Contact(terminals 6-7)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 15mAPo = 30mW

EEx ia IIB 3.86µF 300mH 2.6mH/ΩIIC 620nF 80mH 0.65mH/Ω

Magnetic 500mV (terminals 5-3)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 10mAPo = 18mW

EEx ia IIB 3.86µF 600mH 4.15mH/ΩIIC 620nF 150mH 1.03mH/Ω

Magnetic 50mV (terminals 5-3, 6-4)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 10mAPo = 18mW

EEx ia IIB 3.86µF 600mH 4.15mH/ΩIIC 620nF 150mH 1.03mH/Ω

Vortex 6V(terminals 1, 2-3)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 26.5VIo = 82mAPo = 520mW

EEx ia IIB 730nF 8mH 0.26mH/ΩIIC 95nF 2mH 0.06mH/Ω

Vortex 3V(terminals 0, 2-3)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 26.5VIo = 82mAPo = 520mW

EEx ia IIB 730nF 8mH 0.26mH/ΩIIC 95nF 2mH 0.06mH/Ω

Publication 1797-6.5.6 - June 2005

Page 76: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

13-4 1797-IJ2 FLEX Ex Frequency Input Module

Channel 1 Frequency Input

Field devices may only be connected to the terminals of one of the five following circuits. The terminals of the remaining four circuits must not be connected.

Namur/Contact(terminals 9-8)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 15mAPo = 30mW

EEx ia IIB 3.86µF 300mH 2.6mH/ΩIIC 620nF 80mH 0.65mH/Ω

Magnetic 500mV (terminals 10-12)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 10mAPo = 18mW

EEx ia IIB 3.86µF 600mH 4.15mH/ΩIIC 620nF 150mH 1.03mH/Ω

Magnetic 50mV (terminals 10-12, 9-11)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 10mAPo = 18mW

EEx ia IIB 3.86µF 600mH 4.15mH/ΩIIC 620nF 150mH 1.03mH/Ω

Vortex 6V(terminals 14, 13-12)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 26.5VIo = 82mAPo = 520mW

EEx ia IIB 730nF 8mH 0.26mH/ΩIIC 95nF 2mH 0.06mH/Ω

Vortex 3V(terminals 15, 13-12

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 26.5VIo = 82mAPo = 520mW

EEx ia IIB 730nF 8mH 0.26mH/ΩIIC 95nF 2mH 0.06mH/Ω

Publication 1797-6.5.6 - June 2005

Page 77: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IJ2 FLEX Ex Frequency Input Module 13-5

Channel 0 Gate Input

Field devices may only be connected to the terminal of one of the three following circuits. The terminals of the remaining two circuits must not be connected.

Channel 1 Gate Input

Field devices may only be connected to the terminals of one of the three circuits. The terminals of the remaining two circuits must not be connected.

Namur/Contact(terminals 23-24)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 15mAPo = 30mW

EEx ia IIB 3.86µF 300mH 2.6mH/ΩIIC 620nF 80mH 0.65mH/Ω

Magnetic 500mV (terminals 22-20)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 10mAPo = 18mW

EEx ia IIB 3.86µF 600mH 4.15mH/ΩIIC 620nF 150mH 1.03mH/Ω

Magnetic 50mV (terminals 22-20, 23-21)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 10mAPo = 18mW

EEx ia IIB 3.86µF 600mH 4.15mH/ΩIIC 620nF 150mH 1.03mH/Ω

Namur/Contact(terminals 26-25)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 15mAPo = 30mW

EEx ia IIB 3.86µF 300mH 2.6mH/ΩIIC 620nF 80mH 0.65mH/Ω

Publication 1797-6.5.6 - June 2005

Page 78: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

13-6 1797-IJ2 FLEX Ex Frequency Input Module

Relay Outputs

Magnetic 500mV (terminals 27-29)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 10mAPo = 18mW

EEx ia IIB 3.86µF 600mH 4.15mH/ΩIIC 620nF 150mH 1.03mH/Ω

Magnetic 50mV (terminals 27-29, 26-28)

Protection Group Allowed Capacitance

Allowed Inductance

LoRo

Ratio

Uo = 14.7VIo = 10mAPo = 18mW

EEx ia IIB 3.86µF 600mH 4.15mH/ΩIIC 620nF 150mH 1.03mH/Ω

Relay Output (terminals 17, 18, 37 or 31, 32, 46)

Protection Group Internal Capacitance

Internal Inductance

Ui = 28VIi = 93mAPi = 651mW

EEx ia IIB Negligible NegligibleIIC Negligible Negligible

Publication 1797-6.5.6 - June 2005

Page 79: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 14

1797-PS1E FLEX Ex Power Supply

Installation in Zone 1 The 1797-PS1E power supply has a protection factor of IP65. Refer to the specifications table for the IS module type.

Installation in Zone 22 The housing type of the power supply is applicable for the use in Zone 22. It corresponds with the category 3D according to RL 94/9 EG and is marked with a type label accordingly. If the junction box must be opened for maintenance purposes during operation, the power supply must be free of dust deposits so that after the opening no dust penetrates inside.

Outputs When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

The channels in the power supply are electrically connected to each other and have a common +V line.

30686

1797-PS1E

ATTENTION The power supply cannot be used in an intrinsically safe environment after its outputs have been exposed to non-intrinsically safe signals.

IMPORTANT You cannot interconnect lines because of the intrinsic safety requirements.

1 Publication 1797-6.5.6 - June 2005

Page 80: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

14-2 1797-PS1E FLEX Ex Power Supply

Typical Wiring Configurations

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 85-250V AC In/Quad-Ex DC Out Power Supply Installation Instructions, publication 1797-5.33.

42489

10 11 12 13 14 15 16 171 2 4 5

3

chaGND

-+ -+

Vout

+V -V +V -V +V -V +V -V

Out 1 Out 2 Out 3 Out 4

Terminal Base Assignments

Vin

European AC Power Input IS Power Output

Specifications 1797-PS1E (Series A) 1797-PS1E (Series B)Inset Voltage Range 85 to 250V dcVoltage UO <9.5V

Current IO <1A

Co (IIC) <500 nF

Lo (IIC) <8 µH

Operational Temperature -20 to 70oC (-4 to 158oF)Agency Certification EEx de [ib] IIC T4 II 2G EEx de [ib] IIC T4

II 3D IP54 T90°CCertificates BVS 98.D.2055X DMT 02 ATEX E253 X

ATTENTION Once power has been applied, wait 15 minutes after disconnecting before opening cover.

Publication 1797-6.5.6 - June 2005

Page 81: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 15

1797-PS2E2 FLEX Ex Power Supply

Installation in Zone 1 The 1797-PS2E2 power supply has a protection factor of IP54. Refer to the specifications table for the IS module type.

Installation in Zone 22 The housing type of the power supply is applicable for use in Zone 22. It corresponds with the category 3D according to RL 94/9 EG and is marked with a type label accordingly. If the junction box must be opened for maintenance purposes during operation, the power supply must be free of dust deposits so that after the opening, no dust penetrates inside.

Outputs When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

The channels in the power supply are electrically connected to each other and have a common +V line.

30686

1797-PS2E2

ATTENTION The power supply cannot be used in an intrinsically safe environment after its outputs have been exposed to non-intrinsically safe signals.

IMPORTANT You cannot interconnect lines because of the intrinsic safety requirements.

1 Publication 1797-6.5.6 - June 2005

Page 82: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

15-2 1797-PS2E2 FLEX Ex Power Supply

Typical Wiring Configurations

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Power Supply Installation Instructions, publication 1797-5.8.

42489

10 11 12 13 14 15 16 171 2 4 5

3

chaGND

-+

Vin1

-+

Vin2

+V -V +V -V +V -V +V -V

Out 1 Out 2 Out 3 Out 4

Terminal Base Assignments

Vin1

European DC Power Input IS Power Output

Specifications 1797-PS2E2Inset Voltage Range 18 to 32V dcVoltage UO <9.5V

Current IO <1A

Co (IIC) <500 nF

Lo (IIC) <8 µH

Operational Temperature -20 to 70oC (-4 to 158oF)Agency Certification II 2G EEx de [ib] IIC T4

II 3D IP54 T90CCertificates DMT 02 ATEX E253 X

ATTENTION Once power has been applied, wait 15 minutes after disconnecting before opening cover.

Publication 1797-6.5.6 - June 2005

Page 83: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 16

1797-ACNR15 ControlNet Ex Redundant Media Adapter

Module Installation Use the redundant media adapter module to connect FLEX Ex modules to the ControlNet Ex network.

Inputs/Outputs Do not apply any non-intrinsically safe signals to the adapter.

When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

PWR

1797-ACNR15

3 2

41408

1 Publication 1797-6.5.6 - June 2005

Page 84: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

16-2 1797-ACNR15 ControlNet Ex Redundant Media Adapter

Intrinsically Safe Specifications

For a full list of specifications, refer to ControlNet Ex Redundant Media Adapter Installation Instructions, publication 1797-5.14.

ControlNet Ex BNC (ChA and ChB) Oscillation powered by:Uo < 5.4V dcIo < 160mAac coupled with high-pass filter f-3 > 500kHz

Output (intrinsically safe) (16 position male/female flexbusconnector)

Uo < 5.8VIo < 400mAPo < 2.16WLo < 10µHCo < 65µF

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1APi < 9.5WLi = NegligibleCi < 120nF

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification II 2G EEx ib IIB/IIC T4

Certificates DMT 99 ATEX E 008 X

Publication 1797-6.5.6 - June 2005

Page 85: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 17

1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

Module Installation A maximum of two 1797-RPFM modules may be used with one 1797-RPA adapter.

Inputs/Outputs Do not apply any non-intrinsically safe signals to the adapter or fiber modules.

When using an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

1 32 4

+V +V-V -V

1797-RPA

PWR

REPEATERADAPTER

COMMSTATUS

MODULESTATUS

41163

1797-RPA

1797-RPFM

Recv XmitRecv Xmit

Chan 1 Chan 2

41267

1797-RPFM

1 Publication 1797-6.5.6 - June 2005

Page 86: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

17-2 1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

Intrinsically Safe Specifications

For a full list of specifications, refer to ControlNet Ex Modular Repeater Adapter and Fiber Repeater Module, Medium Distance Installation Instructions, publication 1797-5.15.

1797-RPA Specifications

ControlNet Ex BNC Oscillation powered by:Uo < 5.4V dcIo < 201mAac coupled with high-pass filter f > 500kHz

Output (intrinsically safe) (30 pin male TTL bus connector)

Manufacturer specific busUo < 5.4VIo < 201mAPo < 1.09WLo < 0.45µHCo < 71µF

Power Supply(+V, -V Intrinsically Safe)

Ui < 9.5V dcIi < 1APi < 9.5WLi = NegligibleCi < 120nF

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4

Certificates DMT 99 ATEX E 011 X

1797-RPM Specifications

Input (intrinsically safe) (30 pin female TTL bus connector)

Ui < 5.4VIi < 201mAPi < 1.1WLi < 15µHCi < 41µF

Output (intrinsically safe) (30 pin male TTL bus connector)

Uo < 5.4VIo < 201mAPo < 1.1WLo < 0.45mHCo < 71µF

Fiber Optic TransmitterCh1 & Ch 2

Optical Peak Output PowerP optical < 1mW

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification II (1) 2G EEx ia/ib IIB/IIC T4

Certificates DMT 99 ATEX E 011 X

Publication 1797-6.5.6 - June 2005

Page 87: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 18

1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector

General Installation The 1797-CEC and -BIC must not be exposed to the environment. These modules have a protection factor of IP20. Provide a suitable metal enclosure. If these modules are to be installed into a Zone 2 area, then ensure that this enclosure has a protection class of IP54.

Make certain that you only connect the FLEX Ex backplane connector to other intrinsically safe system modules to maintain the integrity of the intrinsically-safe backplane.

QUALITY

B-AAllen-Bradley

1797 - CEC

FLEXBUS CONNECTOR

1 2 43

+V -V +V -V

1797 - BIC

PWR

QUALITY

B-AAllen-Bradley

FLEXBUS ISOLATOR

428641797-CEC 1797-BIC

ATTENTION The 1797-BIC cannot be used as an associated apparatus after its FLEX Ex backplane connector has been exposed to non-intrinsically safe signals.

1 Publication 1797-6.5.6 - June 2005

Page 88: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

18-2 1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector

Inputs/Outputs Do not apply any non-intrinsically safe signals to the FLEX Ex backplane connector.

When using as an intrinsically safe electrical apparatus according to EN50020, the European directives and regulations must be followed.

ATTENTION For proper operation, cycle power to the 1797-BIC at the same time power is cycled to the associated adapter.

1794Adapter

1797CEC

1797BIC

1797 I/O & Base

1797 I/O & Base

1797 I/O & Base

1797 I/O & Base

1797 power supply

24V dc power supply

42754

Publication 1797-6.5.6 - June 2005

Page 89: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector 18-3

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Bus Isolator Installation Instructions, publication 1797-5.13.

1797-BIC Specifications

Output (Intrinsically Safe)(16 pin male and female flexbusconnector)

Uo < 5.75V dcIo < 400mAPo < 2.05WLo < 100µHCo < 39µF

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification II (2)G [EEx ib] IICII (2D)

Certificates DMT 00 ATEX E056 X

Declaration of Conformity

Directive 94/9 EC Zone 2II 3G EEx nA IIC T4 X

1797-CEC Specifications

Operational Temperature -20 to 70oC (-4 to 158oF)

Declaration of Conformity

Directive 94/9 EC Zone 2II 3G EEx nA IIC T4 X

Publication 1797-6.5.6 - June 2005

Page 90: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

18-4 1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector

Notes:

Publication 1797-6.5.6 - June 2005

Page 91: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 19

1797-BCNR Redundant ControlNet Ex Barrier

Description The ControlNet Ex barrier type 1797-BCNR functions as a galvanic isolation barrier for signal between the non-intrinsic ControlNet system an intrinsically-safe ControlNet Ex system. The 1797-BCNR is installed in the safe area.

Inputs/Outputs Do not apply any non-intrinsically safe signals to the intrinsically-safe side of the 1797-BCNR.

The BNC covers are provided with a cover plug. This cover plug can only be removed when a cable is connected. The IS connection must not be connected to any signals that exceed the intrinsically-safe values of the ControlNet Ex system.

1797-BCNR

Redundant CoaxMedia Barrier

41267a

1797-BCNR

1 Publication 1797-6.5.6 - June 2005

Page 92: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

19-2 1797-BCNR Redundant ControlNet Ex Barrier

Intrinsically Safe Specifications

The ControlNet Ex barrier type 1797-BCNR is an associated apparatus according to EN 50020. If the ControlNet Ex barrier is connected to intrinsically-safe circuits, the applicable national and local construction, installation, and operating regulations must be heeded (in Germany DIN EN 50020, DIN VDE 0165).

For a full list of specifications, refer to Redundant ControlNet Barrier Installation Instructions, publication 1797-5.1x.

Repair The ControlNet Ex barrier is not field-repairable. Any attempt to open this device will void the warranty and IS certification. If repair is necessary, return this device to the factory.

1797-BCNR Specifications

IS Output(BNC Connector in Blue Area)

Maximum open circuit voltage Uo is 7VMaximum current Io is 14mA (at the resonant frequency of 66kHz)

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification II (2) G [EEx ib] IIC

Certificates DMT 99 ATEX E065 X

0102

Publication 1797-6.5.6 - June 2005

Page 93: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 20

General UL, C-UL Certification Information

Module Installation FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

You will need to rotate the keyswitch (1) to the correct position depending on the module. Refer to the module’s installation instructions for more information. Do not change the position of the keyswitch after wiring the terminal base unit.

Make certain that you only connect terminal base units to other intrinsically safe system modules, adapters and power supplies to maintain the integrity of the intrinsically-safe system.

Remove cap plug and attach another intrinsically safe terminal base unit (2) to the right of the terminal base unit if required.

Do not remove the flexbus cover (8) on the right-most terminal base unit.

Label here or under here 40231

(1) keyswitch

(8) flexbus cover

(2) terminal base unit

41307

1 Publication 1797-6.5.6 - June 2005

Page 94: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

20-2 General UL, C-UL Certification Information

Installation in Division 1/Zone 1

Modules, adapters, and terminal base units must not be exposed to the environment. Provide a suitable enclosure.

Electrostatic Charge Protect the system against electrostatic charge. Post a sign near each module: Attention! Avoid electrostatic charge. For your convenience, a sign which can be cut out and posted is included in this chapter.

UL, C-UL I/O Entity Parameters

If this product has the UL/C-UL mark, it has been designed, evaluated, tested, and certified to meet the following standards:

• UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and III Division 1, Hazardous (Classified) Locations

• UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations

• UL 2279, Electrical Equipment for Use in Class I, Zone 0, 1, and 2 Hazardous (Classified) Locations

• UL 508, Industrial Control Equipment• CSA C22.2 No. 157-92, Intrinsically Safe and Non-Incendive

Equipment for Use in Hazardous Locations• CSA C22.2 No. 30-M1986, Explosion-Proof Enclosures for Use in

Class I Hazardous Locations• CSA-E79-0-95, Electrical Apparatus for Explosive Gas Atmospheres,

Part 0: General Requirements• CSA-E79-11-95, Electrical Apparatus for Explosive Gas Atmospheres,

Part 11: Intrinsic Safety “i”• CSA C22.2 No. 14-95, Industrial Control Equipment

Repair Modules are not field-repairable. Any attempt to open a module will void the warranty and the IS certification. If repair is necessary, return the module to the manufacturer.

ATTENTION Modules, adapters, and terminal base units cannot be used in an intrinsically safe environment after they have been exposed to non-intrinsically safe signals.

Attention: Avoid electrostatic charge.

Publication 1797-6.5.6 - June 2005

Page 95: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 21

ControlNet Ex System

20125-M

Ex

PWR

1797-ACNR15

PWR

Adapter Bus Connectors Terminal Base KeyswitchFlexbus Connector

Ex I/O Module

Terminal Strips

Field PowerConnection Terminals

1 Publication 1797-6.5.6 - June 2005

Page 96: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

21-2 ControlNet Ex System

ControlNet Ex System Diagram

.

1

.

.

.

.

.

..

.

.

.

.

..

.

1

Non

-Haz

ardo

us L

ocat

ion

4247

5

CNet

Ex

trk tr

mH

azar

dous

(Cla

ssifi

ed) L

ocat

ion

Clas

s I,

Zone

s 0,

1 a

nd 2

,Gr

oups

IIC,

IIB,

IIA

Clas

s I D

ivis

ion

1 an

d 2,

Grou

ps A

, B, C

, DCl

ass

II, D

ivis

ion

1 an

d 2,

Grou

ps E

, F, G

Clas

s III

, Div

isio

n 1

and

2

ChB

ChA

Pow

er S

uppl

y Vm

ax=9

.5V

Imax

=1A

Ci<=

120n

FLi

=0To

any

IS d

evic

e or

asso

ciat

ed a

ppar

atus

with

ent

ity c

once

pt

para

met

ers

ofVo

c=9.

5V a

nd Is

c=1A

.

Nod

e 4

... 4

817

97-A

CNR1

5An

y IS

dev

ice

with

ent

ityco

ncep

t par

amet

ers

(Vm

ax, I

max

, Ci,

Li)

appr

opria

te fo

r con

nect

ion

to a

ssoc

iate

d ap

para

tus

with

ent

ity c

once

pt

para

met

ers

liste

d in

Tabl

e 2.

Max

imum

dev

ices

=8.

Nod

e 1

1797

-RPA

Nod

e 2

1797

-RPF

M17

97-R

PFM

1786

-RPF

Mor

Any

asso

ciat

ed a

ppar

atus

whe

re th

e lig

ht e

mitt

ing

diod

e ou

tput

is

<5m

W/m

m2 .

CNet

Ex

trk tr

m

Cont

rolN

et

Ex ta

pCo

ntro

lNet

Ex

tap

The

ambi

ent t

empe

ratu

re ra

nge

of th

eCo

ntro

lNet

Ex

Syst

em is

-20o C

to +

70o C.

coax

trun

k ca

ble

Cont

rolN

et

Ex ta

p

coax

trun

k ca

ble

Cont

rolN

et

Ex ta

p

Haz

ardo

us (C

lass

ified

) Loc

atio

nZo

ne 1

or 2

, IIC

Clas

s I,

Zone

s 1

and

2, G

roup

s IIC

, IIB

, IIA

Clas

s I D

ivis

ion

1 an

d 2,

Gro

ups

A, B

, C, D

Clas

s II,

Div

isio

n 1

and

2, G

roup

s E,

F, G

Clas

s III

, Div

isio

n 1

and

2

CNet

Ex

trk tr

m

ChA

ChB

Pow

er S

uppl

y Vm

ax=9

.5V

Imax

=1A

Ci<=

120n

FLi

=0To

any

IS d

evic

e or

asso

ciat

ed a

ppar

atus

with

ent

ity c

once

pt

para

met

ers

ofVo

c=9.

5V a

nd Is

c=1A

.

Any

IS d

evic

e w

ith e

ntity

conc

ept p

aram

eter

s (V

max

, Im

ax, C

i, Li

)ap

prop

riate

for c

onne

ctio

nto

ass

ocia

ted

appa

ratu

s w

ith e

ntity

con

cept

pa

ram

eter

s lis

ted

in Ta

ble

2.M

axim

um d

evic

es=8

.

Haz

ardo

us (C

lass

ified

) Loc

atio

nCl

ass

I, Zo

ne 1

, Gro

ups

IIC, I

IB, I

IACl

ass

I, Di

visi

on 1

, Gro

ups

A, B

, C, D

Clas

s II

Divi

sion

1 G

roup

s E,

F, G

Clas

s III

Nod

e 3

1797

-ACN

R15

Ch1

Ch0 fib

er o

ptic

cab

le

Ch1

Ch0

Pow

er S

uppl

y Vm

ax=9

.5V

Imax

=1A

Ci<=

120n

FLi

=0To

any

IS d

evic

e or

asso

ciat

ed a

ppar

atus

with

ent

ity c

once

pt

para

met

ers

ofVo

c=9.

5V a

nd Is

c=1A

.

Publication 1797-6.5.6 - June 2005

Page 97: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

ControlNet Ex System 21-3

Describing the ControlNet Ex System Diagram

A maximum of 48 ControlNet ExTM nodes may be connected together by 250m of coax cable and 48 taps. The distance increases to 1000m when you use only 2 taps. See the table below for more information.

The fiber media of the 1797-RPFM can be installed in a hazardous location (Class I, Zones 0, 1, and 2; Class I, Division 1 and 2; Class II, Division 1 and 2; Class III, Division 1 and 2) to connect two 1797-RPFM modules or they can be installed through different locations into the non-hazardous location to connect the 1797-RPFM with any approved associated apparatus.

All cables and fiber media that are not light blue must be marked as IS using the 1797-EXMK marking kit or other locally approved IS identification and/or segregation method.

During the installation of the ControlNet Ex system, all metallic parts must be isolated to prevent an earth connection (high voltage withstanding of isolating material must be > 500V ac).

System Diagram Name

Catalog Number Catalog Name Description

1797-RPA 1797-RPA ControlNet Ex Modular Repeater Adapter

Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx

1797-RPFM 1797-RPFM ControlNet Ex Fiber Repeater Module, Medium Distance

Allows connection of a maximum of two devices per 1797-RPA and is powered directly by 1797-RPA

1797-ACNR15 1797-ACNR15 Redundant Media ControlNet Ex Adapter

Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx -each one with two redundant output channels that are connected to different ControlNet Ex networks (coax cables and 1797-TPx)

CNet Ex Tap Trm

1797-TCAP ControlNet Ex Tap (Dummy) Terminator

Represents one ControlNet Ex node and is a simple capacitor (56pF) with a coax connector

ControlNet Ex Tap

1797-TPx ControlNet Ex Coax Tap

Four types of connections available: S (straight t-tap), R (right angle t-tap), YS (straight y-tap), and YR (right angle y-tap) - a maximum of 48 taps can be connected together by coax trunk cable

CNet Ex Trk Trm

1797-XT ControlNet Ex Trunk Terminator

Simple resistor (75Ω) with coax connector that must be on each end of the ControlNet Ex coax trunk for termination

Coax Trunk Cable

1797-RG6 Quad-Shield, RG-6 75Ω Coax Trunk Cable

Maximum (functional) length between 2 1797-TPx is 3280ft (1000m) - each 1797-TPx reduces the (functional) coax cable length by 53.4ft (16.3m)

None None Standard Coax Trunk Cable BNC Couplers

Different standard cable couplers, 90o, 180o, etc.

Publication 1797-6.5.6 - June 2005

Page 98: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

21-4 ControlNet Ex System

Certified Equivalent ControlNet Ex System Diagram Items

You may use these items as equivalents for the items shown on the system diagram.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

System Diagram Name Catalog Number Source

1797-RPA 1797-RPA Allen-Bradley

RSD-CFA-Ex.CN Pepperl+Fuchs

1797-RPFM 1797-RPFM Allen-Bradley

RSD-FC-Ex2.CN Pepperl+Fuchs

1797-ACNR15 1797-ACNR15 Allen-Bradley

RSD-GW-Ex2.CN Pepperl+Fuchs

Coax Trunk Cable1 1797-RG6 Allen-Bradley

3092A2 Belden Wire & Cable Co.

3092A with blue jacket Belden Wire & Cable Co.

ControlNet Ex Tap 1797-TPx Allen-Bradley

RS-TPx-Ex Pepperl+Fuchs

CNet Ex Trk Trm 1797-XT Allen-Bradley

RS-XT-Ex Pepperl+Fuchs

CNet Ex Tap Trm 1797-TCAP Allen-Bradley

RS-TCAP-Ex Pepperl+Fuchs

1 In addition to these cable types, the following specification can be followed to allow additional types:Cable Impedance = 75Ω ± 3ΩCable Capacitance = <5.94nF per 100mCable Resistance = >9.08Ω per 100mCable Attenuation 0.2MHz > 0.93dB/100m 5MHz > 1.39dB/100m(-20 to +70oC) 0.5MHz > 0.95dB/100m 10MHz > 1.86dB/100m

1MHz > 1.07dB/100m 20MHz > 2.73dB/100m2MHz > 1.16dB/100m 50MHz > 4.33dB/100m

2 Belden Wire & Cable 1189A may be used, but with functional loss of communication distance and/or nodes.

Publication 1797-6.5.6 - June 2005

Page 99: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

ControlNet Ex System 21-5

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

If fiber optic cable is provided with a metal shield, it must be connected to a dedicated intrinsic safety ground in the non-hazardous location and tied back in the hazardous location or be connected to a ground in the hazardous location and tied back in the non-hazardous location.

The glass fiber must have a minimum diameter of 6µm.

For Class II, Division 1, Groups E, F, G and Class III, modules must be installed in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure. (The power supply does not need to be put into an additional enclosure. Refer to the power supply section of this manual for more information.)

Any combination of up to eight FLEX Ex I/O modules may be connected. This includes using 1794-CE3, 1797-CE3, 1794-CE1, and 1797-CE1 cables.

The ambient temperature range (Tamb) for this system is -20°C to 70°C.

Channel B is intended for a redundant connection and is identical to the channel A configuration.

Installation in Division 1/Zone 1

Modules must not be exposed to the environment. Provide a suitable enclosure.

ATTENTION Modules cannot be used in an intrinsically safe environment after they have been exposed to non-intrinsically safe signals.

Publication 1797-6.5.6 - June 2005

Page 100: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

21-6 ControlNet Ex System

Electrostatic Charge Protect the system against electrostatic charge. Post a sign near each module: Attention! Avoid electrostatic charge. For your convenience, a sign which can be cut out and posted is included in this chapter.

Repair Modules are not field-repairable. Any attempt to open a module will void the warranty and the IS certification. If repair is necessary, return the module to the manufacturer.

Attention: Avoid electrostatic charge.

Publication 1797-6.5.6 - June 2005

Page 101: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 22

1797-TB3 FLEX Ex Terminal Base Unit

General Information FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation You will need to rotate the keyswitch (1) to the correct position depending on the module. Refer to the module’s installation instructions for more information. Do not change the position of the keyswitch after wiring the terminal base unit.

Make certain that you only connect terminal base units to other intrinsically safe system modules or adapters to maintain the integrity of the intrinsically-safe backplane.

Installation in Division 1/Zone 1

Do not remove the flexbus cover (8) on the right-most terminal base unit.

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 45 46 47 48 49 5044 51

42332

Label here(8) flexbus

cover

(1) keyswitch

41307

1 Publication 1797-6.5.6 - June 2005

Page 102: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

22-2 1797-TB3 FLEX Ex Terminal Base Unit

Inputs Do not apply any non-instrinsically safe signals to the terminal base.

The terminals in the terminal base unit may be electrically connected to each other by the insertion of FLEX Ex I/O modules. See the module installation instructions to determine this.

Description The 1797-TB3 terminal base has 36 wiring connections to/from a plug-in module. The use of each terminal depends on the module mounted in this base.

The 1797-TB3 terminal base also has connections for cold junction compensation and terminals designated for shield termination to chassis ground.

The terminal base is equipped with a factory-installed tab cover for the backplane bus connection. The tab cover may be removed only when the terminal base unit is connected to other terminal base units..

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety requirements.

ATTENTION • Make certain that you power the terminal base unit with an intrinsically safe power supply. Do not exceed the values listed in the specifications for the terminal base unit.

• Do not use the unused terminals on the terminal base unit. Using these terminals as supporting terminals can result in damage to modules and/or unintended operation of your system.

Wiring Connections for Terminal Base 1797-TB30 1 32 4 5 6 7 8 9 10 11 12 13 14 15

26 27 28 29 30 31 32 3325242322212019181716

44 45 46 47 48 49 50 5143424140393837363534

41252+V -V -V+V

A

B

C

No connections allowed to terminals 36 and 49

Publication 1797-6.5.6 - June 2005

Page 103: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-TB3 FLEX Ex Terminal Base Unit 22-3

Intrinsically Safe Specifications

For a full list of specifications, refer to the FLEX Ex Terminal Base Installation Instructions, publication 1797-5.1.

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification Class I Division 1 & 2 Groups A-D T4Class I Zone 1 & 2 AEx ia IIC T4Class II Division 1 Groups E, F, G; Class III1

Certificates UL Certificate Number 99.19699

1 For Class II Division 1 Groups E, F, G; Class III, modules must be installed in a UL listed Type 4, 4X, 6, 6P, 9, or 12K enclosure.

Class I Division 1 HazardousC US

Publication 1797-6.5.6 - June 2005

Page 104: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

22-4 1797-TB3 FLEX Ex Terminal Base Unit

Notes:

Publication 1797-6.5.6 - June 2005

Page 105: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 23

1797-TB3S FLEX Ex Terminal Base Unit

General Information FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation You will need to rotate the keyswitch (1) to the correct position depending on the module. Refer to the module’s installation instructions for more information. Do not change the position of the keyswitch after wiring the terminal base unit.

Make certain that you only connect terminal base units to other intrinsically safe system modules or adapters to maintain the integrity of the intrinsically-safe backplane.

Installation in Division 1/Zone 1

Do not remove the flexbus cover (8) on the right-most terminal base unit.

42333

Label here (8) flexbus cover

(1) keyswitch

41307

1 Publication 1797-6.5.6 - June 2005

Page 106: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

23-2 1797-TB3S FLEX Ex Terminal Base Unit

Inputs Do not apply any non-instrinsically safe signals to the terminal base.

The terminals in the terminal base unit may be electrically connected to each other by the insertion of FLEX Ex I/O modules. See the module installation instructions to determine this.

Description The 1797-TB3S terminal base has 36 wiring connections to/from a plug-in module. The use of each terminal depends on the module mounted in this base.

The 1797-TB3S terminal base also has connections for cold junction compensation and terminals designated for shield termination to chassis ground.

The terminal base is equipped with a factory-installed tab cover for the backplane bus connection. The tab cover may be removed only when the terminal base unit is connected to other terminal base units.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety requirements.

ATTENTION • Make certain that you power the terminal base unit with an intrinsically safe power supply. Do not exceed the values listed in the specifications for the terminal base unit.

• Do not use the unused terminals on the terminal base unit. Using these terminals as supporting terminals can result in damage to modules and/or unintended operation of your system.

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

18 19 20 21 22 23 3324 25 26 27 28 29 30 31 3217

35 36 37 38 47 48 49 5034 51

16

39 40 41 42 43 44 45 46

Wiring Connections for Terminal Base 1797-TB3S

41254

Row ARow BRow C

Label placed at top of wiring area

Row A

Row B

Row C

+V -V -V+VNo connections allowed to terminals 36 and 49

Publication 1797-6.5.6 - June 2005

Page 107: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-TB3S FLEX Ex Terminal Base Unit 23-3

Intrinsically Safe Specifications

For a full list of specifications, refer to the FLEX Ex Spring Clamp Terminal Base Installation Instructions, publication 1797-5.2.

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification Class I Division 1 & 2 Groups A-D T4Class I Zone 1 & 2 AEx ia IIC T4Class II Division 1 Groups E, F, G; Class III1

Certificates UL Certificate Number 99.19699

1 For Class II Division 1 Groups E, F, G; Class III, modules must be installed in a UL listed Type 4, 4X, 6, 6P, 9, or 12K enclosure.

Class I Division 1 HazardousC US

Publication 1797-6.5.6 - June 2005

Page 108: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

23-4 1797-TB3S FLEX Ex Terminal Base Unit

Notes:

Publication 1797-6.5.6 - June 2005

Page 109: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 24

1797-IBN16 FLEX Ex 16 NAMUR Input Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 6 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs Each input can be operated from a NAMUR sensor or a mechanical contact (if mechanical inputs are used). Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a common plus-line.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+V -V +V -V41504

+ -

Ch 0

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

+ -

Ch 1

+ -

Ch 2

+ -

Ch 3

+ -

Ch 4

+ -

Ch 5

+ -

Ch 6

+ -

Ch 7

+ -

Ch 8

+ -

Ch 9

+ -

Ch 10

+ -

Ch 11

+ -

Ch 12

+ -

Ch 13

+ -

Ch 14

+ -

Ch 15

No connection allowed to terminals 36 and 49

1 Publication 1797-6.5.6 - June 2005

Page 110: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

24-2 1797-IBN16 FLEX Ex 16 NAMUR Input Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 16 NAMUR Input Module Installation Instructions, publication 1797-5.7.

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

Publication 1797-6.5.6 - June 2005

Page 111: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IBN16 FLEX Ex 16 NAMUR Input Module 24-3

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(-) 14.5 15 - - A, B, IIC 0.3 80.0

C, E, IIB 0.9 320.0

D, F, G, IIA 2.4 640.0

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- IBN16Allen-BradleyB-A

7 PWR6543210 98 1110 1312 1514

6

16 Point NAMUR Input Module

6

FLEX Ex NAMUR Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42060

Publication 1797-6.5.6 - June 2005

Page 112: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

24-4 1797-IBN16 FLEX Ex 16 NAMUR Input Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

Hazardous (Classified) LocationClass I, Zone 0 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class III

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 5.8V; Isc < 400mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 9.5V; Isc < 1A.

To any IS device with Entity Concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 2.

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

29(+)30(-)

1797-IBN16

16

Shield Connection Only

50

51

35

34

Female Bus ConnectorVmax=5.8VImax=400mACi=0Li=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

3340414243444531(+)

32(-)

25(+)26(-)27(+)28(-)

21(+)22(-)23(+)24(-)

17(+)18(-)19(+)20(-)

12(+)13(-)14(+)15(-)

8(+)9(-)10(+)11(-)

4(+)5(-)6(+)7(-)

0(+)1(-)2(+)3(-)

ch8

ch9

ch10

ch11

ch12

ch13

ch14

ch15

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1.

42061

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-GIIC, IIB, IIA

3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-GIIC, IIB, IIA

0 0

Publication 1797-6.5.6 - June 2005

Page 113: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IBN16 FLEX Ex 16 NAMUR Input Module 24-5

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IBN16, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 36-39, and 46-49 shall not be connected.

Any combination of up to eight channels may be connected in parallel and connected to simple apparatus in a hazardous location. If two channels are connected in parallel, the total cable inductance must be limited to 20mH for Groups A and B, 80mH for Groups C and E, and 160mH for Groups D, F, and G. If eight channels are connected in parallel, the total cable inductance must be limited to 2mH for Groups A and B, 8mH for Groups C and E and 16mH for Groups D, F, and G.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

The ambient operating temperature (Tamb) for this product is -20°C to 70°C.

Suitable for Class II, Division 1, Groups E, F, G and Class III when mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

Publication 1797-6.5.6 - June 2005

Page 114: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

24-6 1797-IBN16 FLEX Ex 16 NAMUR Input Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 115: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 25

1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 7 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Outputs Each output can operate a discrete field device. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

40068

Row A

Row B

Row C

+ + + +- - - -

ch0 ch1 ch2 ch3

+V +V-V -VNo connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to 32, 36, 37, 38, 39, 46, 47, 48, 49

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

1 Publication 1797-6.5.6 - June 2005

Page 116: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

25-2 1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 24V dc Non-Isolated Source 4 Output Module Installation Instructions, publication 1797-5.6.

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1: Each channel is wired separately.• Wiring method 2: Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

Publication 1797-6.5.6 - June 2005

Page 117: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module 25-3

Table 1: Entity Values for Field Device Connections

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(-) 27.4 110.0 - - A, B, IIC 0.03 2.0

C, E, IIB 0.09 8.0

D, F, G, IIA 0.24 16.0

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- OB4DAllen-BradleyB-A

0 1 2 3 4 5 6 7 PWR

7

4 Point Source Output Module

FLEX Ex Discrete Output I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42058

Publication 1797-6.5.6 - June 2005

Page 118: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

25-4 1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-GIIC, IIB, IIA

3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-GIIC, IIB, IIA

1.35 0

Hazardous (Classified) LocationClass I, Zone 0 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class III

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 5.8V; Isc < 400mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 9.5V; Isc < 1A.

To any IS device with Entity Concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 2.

1797-OB4D

16

Shield Connection Only

50

51

35

34

Vmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0 (+)

Female Bus Connector

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1.

1 (-)

ch0

ch1

ch2

ch3

4 (+)5 (-)

8 (+)9 (-)

12 (+)13 (-)

42059

Publication 1797-6.5.6 - June 2005

Page 119: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module 25-5

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-OB4D, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 2, 3, 6, 7, 10, 11, 14, 15, 17-32, 36-39, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

The ambient operating temperature (Tamb) for this product is -20°C to 70°C.

Suitable for Class II, Division1, Groups E, F, G and Class III when mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

Publication 1797-6.5.6 - June 2005

Page 120: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

25-6 1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 121: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 26

1797-IE8 FLEX Ex 8 Input Analog Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 3 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs Each input can be operated from an analog field device signal. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a common plus-line.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+ -+ -+ -+ -

Ch 7Ch 6Ch 5Ch 4

+V -V +V -V40071

sigsigsigsig

No connection allowed

No connection allowed

Ch 7

+ -+ -+ -+ -

Ch 2Ch 1Ch 0

sigsigsigsig

Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

1 Publication 1797-6.5.6 - June 2005

Page 122: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

26-2 1797-IE8 FLEX Ex 8 Input Analog Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Input Analog Module Installation Instructions, publication 1797-5.5.

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

Publication 1797-6.5.6 - June 2005

Page 123: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8 FLEX Ex 8 Input Analog Module 26-3

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(sig) 23.7 92.5 - - A, B, IIC 0.06 2.0

C, E, IIB 0.18 8.0

D, F, G, IIA 0.48 16.0

1(sig), 2(-) 5 1.0 - - A, B, IIC 100 1000

C, E, IIB 300 1000

D, F, G, IIA 800 1000

0(+), 1(sig), 2(-) - - 23.7 93.5 A, B, IIC 0.06 2.0

C, E, IIB 0.18 8.0

D, F, G, IIA 0.48 16.0

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- IE8Allen-BradleyB-A

7 PWR0 1 2 3 4 5 6

3

8 CHANNEL ANALOG INPUT

FLEX Ex Analog Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42055

Publication 1797-6.5.6 - June 2005

Page 124: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

26-4 1797-IE8 FLEX Ex 8 Input Analog Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-GIIC, IIB, IIA

3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-GIIC, IIB, IIA

1.35 0

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 5.8V; Isc < 400mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 9.5V; Isc < 1A.

To any IS device with Entity Concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 2.

1797-IE8

16

Shield Connection Only

5051

35

34

Vmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0 (+)

Female Bus Connector

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1.

1 (sig)

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

2 (-)

4 (+)5 (sig)6 (-)8 (+)9 (sig)10 (-)

12 (+)13 (sig)14 (-)

17 (+)18 (sig)19 (-)

21 (+)22 (sig)23 (-)25 (+)26 (sig)27 (-)

29 (+)30 (sig)31 (-) 42056

Hazardous (Classified) LocationClass I, Zone 0 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class III

Publication 1797-6.5.6 - June 2005

Page 125: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8 FLEX Ex 8 Input Analog Module 26-5

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IE8, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

The ambient operating temperature (Tamb) for this product is -20°C to 70°C.

Suitable for Class II, Division1, Groups E, F, G and Class III when mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

Publication 1797-6.5.6 - June 2005

Page 126: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

26-6 1797-IE8 FLEX Ex 8 Input Analog Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 127: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 27

1797-IE8H FLEX Ex 8 Input HART Analog Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 3 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs Each input can be operated from an analog field device signal. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a common plus-line.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+ -+ -+ -+ -

Ch 7Ch 6Ch 5Ch 4

+V -V +V -V40071

sigsigsigsig

No connection allowed

No connection allowed

Ch 7

+ -+ -+ -+ -

Ch 2Ch 1Ch 0

sigsigsigsig

Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

1 Publication 1797-6.5.6 - June 2005

Page 128: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

27-2 1797-IE8H FLEX Ex 8 Input HART Analog Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Input Analog Module with Noise Filter Installation Instructions, publication 1797-5.31.

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

Publication 1797-6.5.6 - June 2005

Page 129: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8H FLEX Ex 8 Input HART Analog Module 27-3

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(sig) 23.7 92.5 - - A, B, IIC 0.06 2.0

C, E, IIB 0.18 8.0

D, F, G, IIA 0.48 16.0

1(sig), 2(-) 5 1.0 - - A, B, IIC 100 1000

C, E, IIB 300 1000

D, F, G, IIA 800 1000

0(+), 1(sig), 2(-) - - 23.7 93.5 A, B, IIC 0.06 2.0

C, E, IIB 0.18 8.0

D, F, G, IIA 0.48 16.0

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- IE8NFAllen-BradleyB-A

7 PWR0 1 2 3 4 5 6

3

8 CHANNEL ANALOG INPUT NOISE FILTER

FLEX Ex Analog Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42479

Publication 1797-6.5.6 - June 2005

Page 130: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

27-4 1797-IE8H FLEX Ex 8 Input HART Analog Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-GIIC, IIB, IIA

3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-GIIC, IIB, IIA

1.35 0

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 5.8V; Isc < 400mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 9.5V; Isc < 1A.

To any IS device with Entity Concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 2.

1797-IE8NF

16

Shield Connection Only

5051

35

34

Vmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0 (+)

Female Bus Connector

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field

1 (sig)

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

2 (-)

4 (+)5 (sig)6 (-)8 (+)9 (sig)10 (-)

12 (+)13 (sig)14 (-)

17 (+)18 (sig)19 (-)

21 (+)22 (sig)23 (-)25 (+)26 (sig)27 (-)

29 (+)30 (sig)31 (-) 42481

Hazardous (Classified) LocationClass I, Zone 0 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class III

Publication 1797-6.5.6 - June 2005

Page 131: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8H FLEX Ex 8 Input HART Analog Module 27-5

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IE8NF, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

The ambient operating temperature (Tamb) for this product is -20°C to 70°C.

Suitable for Class II, Division1, Groups E, F, G and Class III when mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

Publication 1797-6.5.6 - June 2005

Page 132: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

27-6 1797-IE8H FLEX Ex 8 Input HART Analog Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 133: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 28

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 3 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs Each input can be operated from an analog field device signal. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a common plus-line.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+ -+ -+ -+ -

Ch 7Ch 6Ch 5Ch 4

+V -V +V -V40071

sigsigsigsig

No connection allowed

No connection allowed

Ch 7

+ -+ -+ -+ -

Ch 2Ch 1Ch 0

sigsigsigsig

Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

1 Publication 1797-6.5.6 - June 2005

Page 134: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

28-2 1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Input Analog Module with Noise Filter Installation Instructions, publication 1797-5.31.

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

Publication 1797-6.5.6 - June 2005

Page 135: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter 28-3

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(sig) 23.7 92.5 - - A, B, IIC 0.06 2.0

C, E, IIB 0.18 8.0

D, F, G, IIA 0.48 16.0

1(sig), 2(-) 5 1.0 - - A, B, IIC 100 1000

C, E, IIB 300 1000

D, F, G, IIA 800 1000

0(+), 1(sig), 2(-) - - 23.7 93.5 A, B, IIC 0.06 2.0

C, E, IIB 0.18 8.0

D, F, G, IIA 0.48 16.0

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- IE8NFAllen-BradleyB-A

7 PWR0 1 2 3 4 5 6

3

8 CHANNEL ANALOG INPUT NOISE FILTER

FLEX Ex Analog Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42479

Publication 1797-6.5.6 - June 2005

Page 136: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

28-4 1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-GIIC, IIB, IIA

3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-GIIC, IIB, IIA

1.35 0

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 5.8V; Isc < 400mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 9.5V; Isc < 1A.

To any IS device with Entity Concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 2.

1797-IE8NF

16

Shield Connection Only

5051

35

34

Vmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0 (+)

Female Bus Connector

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field

1 (sig)

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

2 (-)

4 (+)5 (sig)6 (-)8 (+)9 (sig)10 (-)

12 (+)13 (sig)14 (-)

17 (+)18 (sig)19 (-)

21 (+)22 (sig)23 (-)25 (+)26 (sig)27 (-)

29 (+)30 (sig)31 (-) 42481

Hazardous (Classified) LocationClass I, Zone 0 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class III

Publication 1797-6.5.6 - June 2005

Page 137: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter 28-5

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IE8NF, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

The ambient operating temperature (Tamb) for this product is -20°C to 70°C.

Suitable for Class II, Division1, Groups E, F, G and Class III when mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

Publication 1797-6.5.6 - June 2005

Page 138: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

28-6 1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

Notes:

Publication 1797-6.5.6 - June 2005

Page 139: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 29

1797-OE8 FLEX Ex 8 Output Analog Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 4 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Outputs Each output channel can operate an analog field device. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

41440

Row A

Row B

Row C

ch0 ch1 ch2 ch3

+V +V-V -V

+ + + +- - - -

ch4 ch5 ch6 ch7

+ - + - + - + -

No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

1 Publication 1797-6.5.6 - June 2005

Page 140: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

29-2 1797-OE8 FLEX Ex 8 Output Analog Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Output Analog Module Installation Instructions, publication 1797-5.3.

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(-) 21.0 100.0 - - A, B, IIC 0.08 2.0

C, E, IIB 0.24 8.0

D, F, G, IIA 0.64 16.0

Publication 1797-6.5.6 - June 2005

Page 141: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-OE8 FLEX Ex 8 Output Analog Module 29-3

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- OE8Allen-BradleyB-A

OUT 1OUT 0 OUT 2 PWROUT 7OUT 6OUT 5OUT 4OUT 3

4

8 CHANNEL ANALOG OUTPUT

FLEX Ex Analog Output I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42013

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 5.8V; Isc < 400mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 9.5V; Isc < 1A.

To any IS device with Entity Concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 2.

1797-OE816

Shield Connection Only

50

51

35

34

Vmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0 (+)Female Bus Connector

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field 1 (-)

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

4 (+)5 (-)

12 (+)13 (-)

17 (+)18 (-)

21 (+)22 (-)

25 (+)26 (-)

29 (+)30 (-)

42484

8 (+)9 (-)

Hazardous (Classified) LocationClass I, Zone 0 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class III

Publication 1797-6.5.6 - June 2005

Page 142: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

29-4 1797-OE8 FLEX Ex 8 Output Analog Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IE8, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36-39, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

The ambient operating temperature (Tamb) for this product is -20°C to 70°C.

Suitable for Class II, Division1, Groups E, F, G and Class III when mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-GIIC, IIB, IIA

3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-GIIC, IIB, IIA

1.35 0

Publication 1797-6.5.6 - June 2005

Page 143: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 30

1797-OE8H FLEX Ex 8 Output HART Analog Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 4 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Outputs Each output channel can operate an analog field device. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

41440

Row A

Row B

Row C

ch0 ch1 ch2 ch3

+V +V-V -V

+ + + +- - - -

ch4 ch5 ch6 ch7

+ - + - + - + -

No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

1 Publication 1797-6.5.6 - June 2005

Page 144: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

30-2 1797-OE8H FLEX Ex 8 Output HART Analog Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Output Analog Module Installation Instructions, publication 1797-5.3.

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(-) 21.0 100.0 - - A, B, IIC 0.08 2.0

C, E, IIB 0.24 8.0

D, F, G, IIA 0.64 16.0

Publication 1797-6.5.6 - June 2005

Page 145: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-OE8H FLEX Ex 8 Output HART Analog Module 30-3

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- OE8Allen-BradleyB-A

OUT 1OUT 0 OUT 2 PWROUT 7OUT 6OUT 5OUT 4OUT 3

4

8 CHANNEL ANALOG OUTPUT

FLEX Ex Analog Output I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42013

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 5.8V; Isc < 400mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 9.5V; Isc < 1A.

To any IS device with Entity Concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 2.

1797-OE816

Shield Connection Only

50

51

35

34

Vmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0 (+)Female Bus Connector

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field 1 (-)

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

4 (+)5 (-)

12 (+)13 (-)

17 (+)18 (-)

21 (+)22 (-)

25 (+)26 (-)

29 (+)30 (-)

42484

8 (+)9 (-)

Hazardous (Classified) LocationClass I, Zone 0 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class III

Publication 1797-6.5.6 - June 2005

Page 146: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

30-4 1797-OE8H FLEX Ex 8 Output HART Analog Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IE8, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36-39, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

The ambient operating temperature (Tamb) for this product is -20°C to 70°C.

Suitable for Class II, Division1, Groups E, F, G and Class III when mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-GIIC, IIB, IIA

3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-GIIC, IIB, IIA

1.35 0

Publication 1797-6.5.6 - June 2005

Page 147: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 31

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 2 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs Each input can be operated from a thermocouple (TC) or resistance temperature detector (RTD). Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a common plus-line.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

1 Publication 1797-6.5.6 - June 2005

Page 148: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

31-2 1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Thermocouple/RTD Input Module Installation Instructions, publication 1797-5.4.

Row A

Row B

Row C

Ch 7Ch 6Ch 5Ch 4

+V CJC -V

41505

Ch 7

+ L

Ch 2Ch 1Ch 0 Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

H - + LH - + LH - + LH -

+ LH - + LH - + LH - + LH -

-V CJCchassis GND for shield

chassis GND for shield

0+ 0- 1-1+

No connection allowed to terminals 36 and 49

+V

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Operational Temperature -20 to +70oC (-4 to 158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

Publication 1797-6.5.6 - June 2005

Page 149: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module 31-3

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device ConnectionsWiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(H), 2(L), 3(-)

9.0 37.0 - - A, B, IIC 4.9 20.0

C, E, IIB 14.7 80.0

D, F, G, IIA 39.2 160.0

37, 38, 39 (CJC0)

or46, 47, 48

(CJC1)

9.0 1.0 - - A, B, IIC 4.9 1000.0

C, E, IIB 14.7 1000.0

D, F, G, IIA 39.2 1000.0

0(+), 1(H), 2(L), 3(-)

37, 38, 39 (CJC0)

or46, 47, 48

(CJC1)

- - 9.0 38.0 A, B, IIC 4.9 20.0

C, E, IIB 14.7 80.0

D, F, G, IIA 39.2 160.0

Publication 1797-6.5.6 - June 2005

Page 150: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

31-4 1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- IRT8Allen-BradleyB-A

7 PWR6543210

2

8 Point RTD/Thermocouple mV Input ModuleFLEX Ex Temperature Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42020

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 5.8V; Isc < 400mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 9.5V; Isc < 1A.

To any IS device with Entity Concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 2.

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7 29(+)30(H)

1797-IRT8

16

Shield Connection Only

50

51

35

34

Female Bus ConnectorVmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

3340414243444531(L)

32(-)

25(+)26(H)27(L)28(-)

21(+)22(H)23(L)24(-)

17(+)18(H)19(L)20(-)

12(+)13(H)14(L)15(-)

8(+)9(H)10(L)11(-)

4(+)5(H)6(L)7(-)

0(+)1(H)2(L)3(-)

37 38 39 46 47 48

CJC0 CJC1

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values

42021

Hazardous (Classified) LocationClass I, Zone 0 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class III

Publication 1797-6.5.6 - June 2005

Page 151: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module 31-5

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IRT8, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 36 and 49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

The ambient operating temperature (Tamb) for this product is -20°C to 70°C.

Suitable for Class II, Division1, Groups E, F, G and Class III when mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-GIIC, IIB, IIA

3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-GIIC, IIB, IIA

1.35 0

Publication 1797-6.5.6 - June 2005

Page 152: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

31-6 1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 153: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 32

1797-IJ2 FLEX Ex Frequency Input Module

General Information Modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

Module Installation Rotate keyswitch on terminal base unit clockwise to position 1 as required for this type of module. Do not change the position of the keyswitch after wiring the terminal base unit.

Inputs The frequency input module has 2 input channels. Each input can accept inputs from magnetic pickups or proximity probes. Each input channel has 2 input selections: frequency input or gate input. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+V -V

42334

3V V+

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

6V GND 50mV Sel

N500/50 mV

8V 8V N GND 6VV+ 3V

R0 NO R0 NC

-V

No connection allowed to terminals 19, 30, 36, 38, 39, 47, 48, 49

+VR0 COM R1 COM

50mV Sel

500/50 mV

Channel 0 Frequency Input Channel 1 Frequency Input

GND

GND 50mV Sel

N500/50 mV

8V 8V N 50mV Sel

500/50 mV

GND R1 NOR1 NC

Channel 0 Gate Input Channel 1 Gate Input

1 Publication 1797-6.5.6 - June 2005

Page 154: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

32-2 1797-IJ2 FLEX Ex Frequency Input Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Frequency Input Module Installation Instructions, publication 1797-5.7.

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib[ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

Publication 1797-6.5.6 - June 2005

Page 155: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IJ2 FLEX Ex Frequency Input Module 32-3

Table 1: Entity Values for Field Device Connections

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel

6, 7;9, 8;

23, 2426, 25

14.7 15.0 - - A, B, IIC 0.62 80.0

C, E, IIB 1.82 320.0

D, F, G, IIA 4.96 640.0

1 and 2 Any one channel

5, 3;10, 12;22, 20;27, 29

14.7 10.0 - - A, B, IIC 0.62 150.0

C, E, IIB 1.82 600.0

D, F, G, IIA 4.96 1200.0

1 and 2 Any one channel

5, 3, 6, 4;10, 12, 9, 11;

22, 20, 21, 23;27, 29, 26, 28

14.7 10.0 - - A, B, IIC 0.62 150.0

C, E, IIB 1.82 600.0

D, F, G, IIA 4.96 1200.0

1 and 2 Any one channel

0, 2, 3;1, 2, 3;

14, 12, 13;15, 12, 13

26.5 82.0 - - A, B, IIC 0.095 2.0

C, E, IIB 0.285 8.0

D, F, G, IIA 0.76 16.0

Wiring Method

Channel Terminals Vmax (V)

Imax (mA)

Groups Ci (µF)

Li (mH)

1 and 2 Any one channel

17, 18, 37or

31, 32, 46

28 93.0 A, B, IIC 0.0 0.0

C, E, IIB 0.0 0.0

D, F, G, IIA 0.0 0.0

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- IJ2Allen-BradleyB-A

7 PWR6543210

1

2 Point Frequency Input ModuleFLEX Ex Frequency Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42066

Publication 1797-6.5.6 - June 2005

Page 156: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

32-4 1797-IJ2 FLEX Ex Frequency Input Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 5.8V; Isc < 400mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 9.5V; Isc < 1A.

To any IS device with Entity Concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 2.

1797-IJ2

16

Shield Connection Only

50

51

35

34

Vmax=5.8VImax=400mACi=2.64µFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0Female Bus Connector

1234567

89101112131415

2021222324

2526272829

Vmax=28VImax=93mACi=0Li=0

Vmax=28VImax=93mACi=0Li=0

17 18 37 31 32 46

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 28V; Isc < 93mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 28V; Isc < 93mA.

ch0Freq. In

ch1Freq. In

ch0Gate

ch1Gate

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field

42057

Hazardous (Classified) LocationClass I, Zone 0 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Groups IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G; Class III

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-GIIC, IIB, IIA

3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-GIIC, IIB, IIA

2.64 0

Publication 1797-6.5.6 - June 2005

Page 157: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IJ2 FLEX Ex Frequency Input Module 32-5

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IJ2, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 19, 30, 36, 38-39, and 47-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

The ambient operating temperature (Tamb) for this product is -20°C to 70°C.

Suitable for Class II, Division1, Groups E, F, G and Class III when mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

Publication 1797-6.5.6 - June 2005

Page 158: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

32-6 1797-IJ2 FLEX Ex Frequency Input Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 159: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 33

1797-PS1N FLEX Ex Power Supply

Installation in Division 1/Zone 1

The 1797-PS1N power supply has a protection factor of IP66. Refer to the specifications table for the IS module type.

Outputs The channels in the power supply are electrically connected to each other and have a common +V line.

Typical Wiring Configurations

ATTENTION The power supply cannot be used in an intrinsically safe environment after its outputs have been exposed to non-intrinsically safe signals.

IMPORTANT You cannot interconnect lines because of the intrinsic safety requirements.

41256

+V -V +V -V +V -V +V -V-+chaGND

-+

Out 1 Out 2 Out 3 Out 4Vin2Vin1

1 2 3 4 5 10 11 12 13 14 15 16 17

Terminal Base Assignments

North America DC Power Input IS Power Output10 11 12 13 14 15 16 17

1 Publication 1797-6.5.6 - June 2005

Page 160: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

33-2 1797-PS1N FLEX Ex Power Supply

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 85-250V AC In/Quad-Ex DC Out Power Supply Installation Instructions, publication 1797-5.34.

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Specifications 1797-PS1NInset Voltage Range 85 to 250V acOperational Temperature

-20 to 70oC (-4 to 158oF)

Agency Certification Class I Division 1 Groups A, B, C, DClass II Division 1 Groups E, F, G

Class IIICertificates UL Certificate Number 99.19699

C US

ATTENTION Once power has been applied, wait 15 minutes after disconnecting before opening cover.

Model Wiring Method

Channel Terminals Voc (V)

Isc (A)

Groups Ca (µF)

La (µH)

PS1N 1 and 2 Any one channel e.g. ch1

10(+), 11(-) 9.5 1.0 A, B 0.5 8

C, E 1.5 32

D, F, G 4.0 64

Publication 1797-6.5.6 - June 2005

Page 161: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-PS1N FLEX Ex Power Supply 33-3

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70, Article 504 or the CEC CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70, Article 501 or the CEC CSA C22.1, Part 1, Section 18.

For mounting of the power supply, conduit runs must have sealing fittings connected within 6 inches of enclosure.

Ch4Ch3Ch2

Ch1

1 2 3 4 5

1716151413121110

11

12

Nonhazardous Location

Hazardous (Classified) Location1797-PS1N

Class I, Division 1, Groups A, B, C, DClass II, Division 1, Groups E, F, G

Class III, Division 1

power supply

Hazardous (Classified) LocationClass I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, GClass III Division 1

nonintrinsically safe wiring intrinsically safe wiring

To any IS device with entity concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with entity concept parameters listed in Table 1: Entity Values for Field Device Connections.

42101

Publication 1797-6.5.6 - June 2005

Page 162: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

33-4 1797-PS1N FLEX Ex Power Supply

The wiring contained within the nonintrinsically safe wiring compartment and the intrinsically safe wiring compartment shall be separated from each other. Care must be taken to guarantee the separation of nonintrinsically safe and intrinsically safe wiring. The partitions within the power supply provide the necessary isolation for the electronics and the wiring, however, extreme care must be taken to guarantee wires are contained within their appropriate compartment and cannot contact any of the electronics.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

Cable must be rated at a minimum of 100°C.

WARNING: Keep cover tightly closed when circuits are live.

After disconnecting power supply, wait fifteen minutes before removing cover.

No live maintenance.

The ambient temperature (Tamb) for this product is -20°C to 70°C.

Feed through power connection for 1797-PS1N.

11

12

Publication 1797-6.5.6 - June 2005

Page 163: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 34

1797-PS2N2 FLEX Ex Power Supply

Installation in Division 1/Zone 1

The 1797-PS2N2 power supply has a protection factor of IP66. Refer to the specifications table for the IS module type.

Outputs The channels in the power supply are electrically connected to each other and have a common +V line.

Typical Wiring Configurations

ATTENTION The power supply cannot be used in an intrinsically safe environment after its outputs have been exposed to non-intrinsically safe signals.

IMPORTANT You cannot interconnect lines because of the intrinsic safety requirements.

Terminal Base Assignments

+V -V +V -V +V -V +V -VL2L1chaGND

L2L1

Out 1 Out 2 Out 3 Out 4VoutVin

1 2 3 4 5 10 11 12 13 14 15 16 1710 11 12 13 14 15 16 17IS Power OutputNorth America AC Power Input

1 Publication 1797-6.5.6 - June 2005

Page 164: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

34-2 1797-PS2N2 FLEX Ex Power Supply

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Power Supply Installation Instructions, publication 1797-5.12.

UL, C-UL I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).

Table 1: Entity Values for Field Device Connections

Specifications 1797-PS2N2Inset Voltage Range 19 to 32V dcOperational Temperature

-20 to 70oC (-4 to 158oF)

Agency Certification Class I Division 1 Groups A, B, C, DClass II Division 1 Groups E, F, G

Class III

Certificates UL Certificate Number 99.19699

C US

ATTENTION Once power has been applied, wait 15 minutes after disconnecting before opening cover.

Model Wiring Method

Channel Terminals Voc (V)

Isc (A)

Groups Ca (µF)

La (µH)

PS2N2 1 and 2 Any one channel e.g. ch1

10(+), 11(-) 9.5 1.0 A, B 0.5 8

C, E 1.5 32

D, F, G 4.0 64

Publication 1797-6.5.6 - June 2005

Page 165: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-PS2N2 FLEX Ex Power Supply 34-3

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70, Article 504 or the CEC CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70, Article 501 or the CEC CSA C22.1, Part 1, Section 18.

For mounting of the power supply, conduit runs must have sealing fittings connected within 6 inches of enclosure.

Ch4Ch3Ch2

Ch1

1 2 3 4 5

1716151413121110

11

12

Nonhazardous Location

Hazardous (Classified) Location1797-PS2N2

Class I, Division 1, Groups A, B, C, DClass II, Division 1, Groups E, F, G

Class III, Division 1

power supply

Hazardous (Classified) LocationClass I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, GClass III Division 1

nonintrinsically safe wiring intrinsically safe wiring

To any IS device with entity concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with entity concept parameters listed in Table 1: Entity Values for Field Device Connections.

42101

Publication 1797-6.5.6 - June 2005

Page 166: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

34-4 1797-PS2N2 FLEX Ex Power Supply

The wiring contained within the nonintrinsically safe wiring compartment and the intrinsically safe wiring compartment shall be separated from each other. Care must be taken to guarantee the separation of nonintrinsically safe and intrinsically safe wiring. The partitions within the power supply provide the necessary isolation for the electronics and the wiring, however, extreme care must be taken to guarantee wires are contained within their appropriate compartment and cannot contact any of the electronics.

WARNING: Substitution of components may impair intrinsic safety.AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.

Cable must be rated at a minimum of 100°C.

WARNING: Keep cover tightly closed when circuits are live.

After disconnecting power supply, wait fifteen minutes before removing cover.

No live maintenance.

The ambient temperature (Tamb) for this product is -20°C to 70°C.

Redundant power supply connection for model 1797-PS2N2.

11

12

Publication 1797-6.5.6 - June 2005

Page 167: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 35

1797-ACNR15 ControlNet Ex Redundant Media Adapter

Module Installation Use the redundant media adapter module to connect FLEX Ex modules to the ControlNet Ex network.

Inputs/Outputs Do not apply any non-intrinsically safe signals to the adapter.

General Specifications For a full list of specifications, refer to ControlNet Ex Redundant Media Adapter Installation Instructions, publication 1797-5.14.

For Class II Division 1 Groups E, F, G and Class III, modules must be installed in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

PWR

1797-ACNR15

3 2

41408

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

1 Publication 1797-6.5.6 - June 2005

Page 168: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

35-2 1797-ACNR15 ControlNet Ex Redundant Media Adapter

UL, cUL Entity Parameters and Requirements

UL, C-UL I/O Entity Parameters and Requirements

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

See the ControlNet Ex System chapter on page 21-1.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Publication 1797-6.5.6 - June 2005

Page 169: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 36

1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

Module Installation A maximum of two 1797-RPFM modules may be used with one 1797-RPA adapter.

Inputs/Outputs Do not apply any non-intrinsically safe signals to the adapter or repeater module.

1 32 4

+V +V-V -V

1797-RPA

PWR

REPEATERADAPTER

COMMSTATUS

MODULESTATUS

41163

1797-RPA

1797-RPFM

Recv XmitRecv Xmit

Chan 1 Chan 2

41267

1797-RPFM

1 Publication 1797-6.5.6 - June 2005

Page 170: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

36-2 1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

Intrinsically Safe Specifications

For a full list of specifications, refer to ControlNet Ex Modular Repeater Adapter and Fiber Repeater Module Installation Instructions, publication 1797-5.15.

For Class II Division 1 Groups E, F, G and Class III, modules must be installed in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.

UL, cUL Entity Parameters and Requirements

See the ControlNet Ex System chapter on page 21-1.

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification 1797-RPAClass I Division 1 Groups A-D T4Class I Zone 1 AEx ib IIC T4

Class II Division 1 Groups E, F, G; Class III

1797-RPFMClass I Division 1 Groups A-D T4Class I Zone 1 AEx ib [ia] IIC T4

Class II Division 1 Groups E, F, G; Class III

Certificates UL Certificate Number 99.19699

C US

Publication 1797-6.5.6 - June 2005

Page 171: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 37

1797-BCNR Redundant ControlNet Ex Barrier

Description The ControlNet Ex barrier type 1797-BCNR functions as a galvanic isolation barrier for signal between the non-intrinsic ControlNet system an intrinsically-safe ControlNet Ex system. The 1797-BCNR is installed in the safe area.

Inputs/Outputs Do not apply any non-intrinsically safe signals to the intrinsically-safe side of the 1797-BCNR.

The BNC covers are provided with a cover plug. This cover plug can only be removed when a cable is connected. The IS connection must not be connected to any signals that exceed the intrinsically-safe values of the ControlNet Ex system.

1797-BCNR

Redundant CoaxMedia Barrier

41267a

1797-BCNR

1 Publication 1797-6.5.6 - June 2005

Page 172: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

37-2 1797-BCNR Redundant ControlNet Ex Barrier

Intrinsically Safe Specifications

The ControlNet Ex barrier type 1797-BCNR is an associated apparatus according to EN 50020. If the ControlNet Ex barrier is connected to intrinsically-safe circuits, the applicable national and local construction, installation, and operating regulations must be heeded (in Germany DIN EN 50020, DIN VDE 0165).

For a full list of specifications, refer to Redundant ControlNet Barrier Installation Instructions, publication 1797-5.1x.

Repair The ControlNet Ex barrier is not field-repairable. Any attempt to open this device will void the warranty and IS certification. If repair is necessary, return this device to the factory.

1797-BCNR Specifications

IS Output(BNC Connector in Blue Area)

Maximum open circuit voltage Uo is 7VMaximum current Io is 14mA (at the resonant frequency of 66kHz)

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification II (2) G [EEx ib] IIC

Certificates DMT 99 ATEX E xxx X

0102

Publication 1797-6.5.6 - June 2005

Page 173: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 38

General FM Certification Information

Module Installation FLEX Ex I/O modules must be used with a 1797-TB3 or -TB3S intrinsically safe terminal base unit.

You will need to rotate the keyswitch (1) to the correct position depending on the module. Refer to the module’s installation instructions for more information. Do not change the position of the keyswitch after wiring the terminal base unit.

Make certain that you only connect terminal base units to other intrinsically safe system modules, adapters or power supplies to maintain the integrity of the intrinsically-safe system. You may use the 1794-CE1 and/or 1794-CE3 cables with the FLEX Ex system.

Remove cap plug and attach another intrinsically safe terminal base unit (2) to the right of the terminal base unit if required.

Do not remove the flexbus cover (8) on the right-most terminal base unit.

Label here or under here 40231

(1) keyswitch

(8) flexbus cover

(2) terminal base unit

42480① ③

1 Publication 1797-6.5.6 - June 2005

Page 174: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

38-2 General FM Certification Information

I/O module capacitance value is cumulative. Ci (total) = Ci (I/O module 1) + Ci (I/O module 2) + ... Ci (I/O module 8) + Ccable (Ccable = 100pf). Ci (total) must be less than 30µF (when the 1797-ACNR15 is used) or 39.67µF (when the 1797-BIC is used). The limitation of 8 I/O modules per adapter is a functional limitation. Refer to table 3 of the appropriate module for Ci values. Note: Any combination of up to eight FLEX Ex I/O modules meets this requirement. (This includes 1794-CE3, 1797-CE3, 1794-CE1, and 1797-CE1 cables.)

In any of the above diagrams, terminal bases without modules may be connected.

This general FM certification information must be used in conjunction with the appropriate module certification information.

Installation in Division 1/ Zone 1

Modules, adapters, and terminal base units must not be exposed to the environment. Provide a suitable enclosure.

1 2 3 4

5678 42488

connecting cable 1794-CE1 or -CE3

ATTENTION Modules, adapters, and terminal base units cannot be used in an intrinsically safe environment after they have been exposed to non-intrinsically safe signals.

Publication 1797-6.5.6 - June 2005

Page 175: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

General FM Certification Information 38-3

Electrostatic Charge Protect the system against electrostatic charge. Post a sign near each module: Attention! Avoid electrostatic charge. For your convenience, a sign which can be cut out and posted is included in this chapter.

FM I/O Entity Parameters If this product has the FM mark, it has been designed, evaluated, tested, and certified to meet the following standards:

• FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous (Classified) Locations General Requirements

• FM C1. No.3610:1999, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified) Locations

• FM C1. No.3615:1989, Explosionproof Electrical Equipment General Requirements

• FM C1. No.3810:1989, 1995, Electrical and Electronic Test, Measuring and Process Control Equipment

• ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment

Repair Modules are not field-repairable. Any attempt to open a module will void the warranty and the IS certification. If repair is necessary, return the module to the manufacturer.

Attention: Avoid electrostatic charge.

Publication 1797-6.5.6 - June 2005

Page 176: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

38-4 General FM Certification Information

Notes:

Publication 1797-6.5.6 - June 2005

Page 177: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 39

ControlNet Ex System

20125-M

Ex

PWR

1797-ACNR15

PWR

Adapter Bus Connectors Terminal Base KeyswitchFlexbus Connector

Ex I/O Module

Terminal Strips

Field PowerConnection Terminals

1 Publication 1797-6.5.6 - June 2005

Page 178: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

39-2 ControlNet Ex System

ControlNet Ex System Diagram

.

1

.

.

.

.

.

..

.

.

.

.

..

.

1

Non

-Haz

ardo

us L

ocat

ion

4247

6

CNet

Ex

trk tr

m

Haz

ardo

us (C

lass

ified

) Loc

atio

n

Clas

s I,

Zone

0, 1

, 2Gr

oup

IIC, I

IB, I

IACl

ass

I Div

isio

n 1,

Grou

ps A

, B, C

, DCl

ass

II, D

ivis

ion

1,Gr

oups

E, F

, GCl

ass

III, D

ivis

ion

1

ChB

ChA

Vmax

=9.5

VIm

ax=1

ACi

=0Li

=0

Nod

e 4

... 4

817

97-A

CNR1

5

Nod

e 1

1797

-RPA

Nod

e 2

1797

-RPF

M17

97-R

PFM

1786

-RPF

Mor

CNet

Ex

trk tr

m

Cont

rolN

et

Ex ta

pCo

ntro

lNet

Ex

tap

coax

trun

k ca

ble

Cont

rolN

et

Ex ta

p

coax

trun

k ca

ble

Cont

rolN

et

Ex ta

p

Haz

ardo

us (C

lass

ified

) Loc

atio

n

Clas

s I,

Zone

1, 2

Gro

up II

C, II

B, II

ACl

ass

I Div

isio

n 1,

Gro

ups

A, B

, C, D

Clas

s II,

Div

isio

n 1,

Gro

ups

E, F,

GCl

ass

III, D

ivis

ion

1CNet

Ex

trk tr

m

ChA

ChB

For c

onne

ctio

n to

othe

r I/O

mod

ules

, ref

er to

Ge

nera

l FM

Cer

tific

atio

n In

form

atio

n on

pag

e 38

-1.

Haz

ardo

us (C

lass

ified

) Loc

atio

n

Clas

s I,

Zone

1, G

roup

IIC

Clas

s I D

ivis

ion

1, G

roup

s A,

B, C

, D

Nod

e 3

1797

-ACN

R15

Ch1

Ch0 fib

er o

ptic

cab

le

Ch1

Ch0

Vmax

=9.5

VIm

ax=1

ACi

=0Li

=0

The

ambi

ent t

empe

ratu

re ra

nge

of th

eCo

ntro

lNet

Ex

Syst

em is

-20o C

to +

70o C.

Any

asso

ciat

ed a

ppar

atus

whe

re

the

light

em

ittin

g di

ode

outp

ut is

<5

mW

/mm

2 or t

otal

<1m

W.

Any

asso

ciat

ed a

ppar

atus

whe

re

the

light

em

ittin

g di

ode

outp

ut is

<5

mW

/mm

2 or t

otal

<1m

W.

Any

asso

ciat

ed a

ppar

atus

whe

re

the

light

em

ittin

g di

ode

outp

ut is

<5

mW

/mm

2 or t

otal

<1m

W.

From

FM

ap

prov

ed17

97-P

S1N

, -P

S2N

, or

-PS2

N2

From

FM

app

rove

d17

97-P

S1N

, -PS

2N, o

r -P

S2N

2

Vmax

=9.5

VIm

ax=1

ACi

=0Li

=0For c

onne

ctio

n to

othe

r I/O

mod

ules

, ref

er to

Ge

nera

l FM

Cer

tific

atio

n In

form

atio

n on

pag

e 38

-1.

11

From

FM

app

rove

d17

97-P

S1N

, -PS

2N, o

r -P

S2N

2

Publication 1797-6.5.6 - June 2005

Page 179: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

ControlNet Ex System 39-3

Describing the ControlNet Ex System Diagram

A maximum of 48 ControlNet ExTM nodes may be connected together by 250m of coax cable and 48 taps. The distance increases to 1000m when you use only 2 taps. See the table below for more information.

The fiber media of the 1797-RPFM can be installed in a hazardous location (Class I, Zones 0, 1, and 2; Class I, Division 1 and 2; Class II, Division 1 and 2; Class III, Division 1 and 2) to connect two 1797-RPFM modules or they can be installed through different locations into the non-hazardous location to connect the 1797-RPFM with any approved associated apparatus.

All cables and fiber media that are not light blue must be marked as IS using the 1797-EXMK marking kit or other locally approved IS identification and/or segregation method.

During the installation of the ControlNet Ex system, all metallic parts must be isolated to prevent an earth connection (high voltage withstanding of isolating material must be > 500V ac).

System Diagram Name

Catalog Number Catalog Name Description

1797-RPA 1797-RPA ControlNet Ex Modular Repeater Adapter

Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx

1797-RPFM 1797-RPFM ControlNet Ex Fiber Repeater Module, Medium Distance

Allows connection of a maximum of two devices per 1797-RPA and is powered directly by 1797-RPA

1797-ACNR15 1797-ACNR15 Redundant Media ControlNet Ex Adapter

Represents one ControlNet Ex node and must be connected to a coax trunk cable by 1797-TPx -each one with two redundant output channels that are connected to different ControlNet Ex networks (coax cables and 1797-TPx)

CNet Ex Tap Trm

1797-TCAP ControlNet Ex Tap (Dummy) Terminator

Represents one ControlNet Ex node and is a simple capacitor (56pF) with a coax connector

ControlNet Ex Tap

1797-TPx ControlNet Ex Coax Tap

Four types of connections available: S (straight t-tap), R (right angle t-tap), YS (straight y-tap), and YR (right angle y-tap) - a maximum of 48 taps can be connected together by coax trunk cable

CNet Ex Trk Trm

1797-XT ControlNet Ex Trunk Terminator

Simple resistor (75Ω) with coax connector that must be on each end of the ControlNet Ex coax trunk for termination

Coax Trunk Cable

1797-RG6 Quad-Shield, RG-6 75Ω Coax Trunk Cable

Maximum (functional) length between 2 1797-TPx is 3280ft (1000m) - each 1797-TPx reduces the (functional) coax cable length by 53.4ft (16.3m)

None None Standard Coax Trunk Cable BNC Couplers

Different standard cable couplers, 90o, 180o, etc.

Publication 1797-6.5.6 - June 2005

Page 180: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

39-4 ControlNet Ex System

Certified Equivalent ControlNet Ex System Diagram Items

You may use these items as equivalents for the items shown on the system diagram.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

WARNING: Substitution of components may impair intrinsic safety.

System Diagram Name Catalog Number Source

1797-RPA 1797-RPA ⑦ Allen-Bradley

RSD-CFA-Ex.CN ⑦ Pepperl+Fuchs

1797-RPFM 1797-RPFM ⑦ Allen-Bradley

RSD-FC-Ex2.CN ⑦ Pepperl+Fuchs

1797-ACNR15 1797-ACNR15 ⑦ Allen-Bradley

RSD-GW-Ex2.CN ⑦ Pepperl+Fuchs

Coax Trunk Cable1 1797-RG6 Allen-Bradley

3092A2 Belden Wire & Cable Co.

3092A with blue jacket Belden Wire & Cable Co.

ControlNet Ex Tap 1797-TPx Allen-Bradley

RS-TPx-Ex Pepperl+Fuchs

CNet Ex Trk Trm 1797-XT Allen-Bradley

RS-XT-Ex Pepperl+Fuchs

CNet Ex Tap Trm 1797-TCAP Allen-Bradley

RS-TCAP-Ex Pepperl+Fuchs

1 In addition to these cable types, the following specification can be followed to allow additional types:Cable Impedance = 75Ω ± 3ΩCable Capacitance = <5.94nF per 100mCable Resistance = >9.08Ω per 100mCable Attenuation 0.2MHz > 0.93dB/100m 5MHz > 1.39dB/100m(-20 to +70oC) 0.5MHz > 0.95dB/100m 10MHz > 1.86dB/100m

1MHz > 1.07dB/100m 20MHz > 2.73dB/100m2MHz > 1.16dB/100m 50MHz > 4.33dB/100m

2 Belden Wire & Cable 1189A may be used, but with functional loss of communication distance and/or nodes.

Publication 1797-6.5.6 - June 2005

Page 181: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

ControlNet Ex System 39-5

If fiber optic cable is provided with a metal shield, it must be connected to a dedicated intrinsic safety ground in the non-hazardous location and tied back in the hazardous location or be connected to a ground in the hazardous location and tied back in the non-hazardous location.

The glass fiber must have a minimum diameter of 6µm.

The ControlNet Ex tap must be connected directly to the module (no additional cable may be connected).

Must be FM approved.

Total coax trunk cable length is limited to 1000m (3280 ft) with up to 2 ControlNet Ex taps connected and to 250m (820 ft) with the maximum allowed ControlNet Ex taps of 48. For ControlNet Ex taps between 2 and 48 use: 1000m (3280 ft) - 16.3m (53.4 ft) x (number of taps - 2) to find the maximum allowed cable length.

Power supplies are suitable for mounting in Class I, Division 1, Groups B-D or Class I, Zone 1, Group IIC.

The maximum number of 1797-ACNR15 modules that can be connected to one system is 47.

The maximum number of 1797-RPA modules that can be connected to one system is 47.11

Publication 1797-6.5.6 - June 2005

Page 182: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

39-6 ControlNet Ex System

Notes:

Publication 1797-6.5.6 - June 2005

Page 183: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 40

1797-TB3 FLEX Ex Terminal Base Unit

Module Installation You will need to rotate the keyswitch (1) to the correct position depending on the module. Refer to the module’s installation instructions for more information. Do not change the position of the keyswitch after wiring the terminal base unit.

Make certain that you only connect terminal base units to other intrinsically safe system modules or adapters to maintain the integrity of the intrinsically-safe backplane.

Installation in Division 1/Zone 1

Do not remove the flexbus cover (8) on the right-most terminal base unit.

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 45 46 47 48 49 5044 51

42332

Label here(8) flexbus

cover

(1) keyswitch

41307

1 Publication 1797-6.5.6 - June 2005

Page 184: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

40-2 1797-TB3 FLEX Ex Terminal Base Unit

Inputs Do not apply any non-instrinsically safe signals to the terminal base.

The terminals in the terminal base unit may be electrically connected to each other by the insertion of FLEX Ex I/O modules. See the module installation instructions to determine this.

Description The 1797-TB3 terminal base has 36 wiring connections to/from a plug-in module. The use of each terminal depends on the module mounted in this base.

The 1797-TB3 terminal base also has connections for cold junction compensation and terminals designated for shield termination to chassis ground.

The terminal base is equipped with a factory-installed tab cover for the backplane bus connection. The tab cover may be removed only when the terminal base unit is connected to other terminal base units..

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety requirements.

ATTENTION • Make certain that you power the terminal base unit with an intrinsically safe power supply. Do not exceed the values listed in the specifications for the terminal base unit.

• Do not use the unused terminals on the terminal base unit. Using these terminals as supporting terminals can result in damage to modules and/or unintended operation of your system.

Wiring Connections for Terminal Base 1797-TB30 1 32 4 5 6 7 8 9 10 11 12 13 14 15

26 27 28 29 30 31 32 3325242322212019181716

44 45 46 47 48 49 50 5143424140393837363534

41252+V -V -V+V

A

B

C

No connections allowed to terminals 36 and 49

Publication 1797-6.5.6 - June 2005

Page 185: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-TB3 FLEX Ex Terminal Base Unit 40-3

Intrinsically Safe Specifications

For a full list of specifications, refer to the FLEX Ex Terminal Base Installation Instructions, publication 1797-5.1.

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib [ia] IIC T4

Certificates FM Certificate Number 3009806FM

Publication 1797-6.5.6 - June 2005

Page 186: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

40-4 1797-TB3 FLEX Ex Terminal Base Unit

Notes:

Publication 1797-6.5.6 - June 2005

Page 187: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 41

1797-TB3S FLEX Ex Terminal Base Unit

Module Installation You will need to rotate the keyswitch (1) to the correct position depending on the module. Refer to the module’s installation instructions for more information. Do not change the position of the keyswitch after wiring the terminal base unit.

Make certain that you only connect terminal base units to other intrinsically safe system modules or adapters to maintain the integrity of the intrinsically-safe backplane.

Installation in Division 1/Zone 1

Do not remove the flexbus cover (8) on the right-most terminal base unit.

42333

Label here (8) flexbus cover

(1) keyswitch

41307

1 Publication 1797-6.5.6 - June 2005

Page 188: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

41-2 1797-TB3S FLEX Ex Terminal Base Unit

Inputs Do not apply any non-instrinsically safe signals to the terminal base.

The terminals in the terminal base unit may be electrically connected to each other by the insertion of FLEX Ex I/O modules. See the module installation instructions to determine this.

Description The 1797-TB3S terminal base has 36 wiring connections to/from a plug-in module. The use of each terminal depends on the module mounted in this base.

The 1797-TB3S terminal base also has connections for cold junction compensation and terminals designated for shield termination to chassis ground.

The terminal base is equipped with a factory-installed tab cover for the backplane bus connection. The tab cover may be removed only when the terminal base unit is connected to other terminal base units.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety requirements.

ATTENTION • Make certain that you power the terminal base unit with an intrinsically safe power supply. Do not exceed the values listed in the specifications for the terminal base unit.

• Do not use the unused terminals on the terminal base unit. Using these terminals as supporting terminals can result in damage to modules and/or unintended operation of your system.

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

18 19 20 21 22 23 3324 25 26 27 28 29 30 31 3217

35 36 37 38 47 48 49 5034 51

16

39 40 41 42 43 44 45 46

Wiring Connections for Terminal Base 1797-TB3S

41254

Row ARow BRow C

Label placed at top of wiring area

Row A

Row B

Row C

+V -V -V+VNo connections allowed to terminals 36 and 49

Publication 1797-6.5.6 - June 2005

Page 189: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-TB3S FLEX Ex Terminal Base Unit 41-3

Intrinsically Safe Specifications

For a full list of specifications, refer to the FLEX Ex Spring Clamp Terminal Base Installation Instructions, publication 1797-5.2.

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib [ia] IIC T4

Certificates FM Certificate Number 3009806FM

Publication 1797-6.5.6 - June 2005

Page 190: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

41-4 1797-TB3S FLEX Ex Terminal Base Unit

Notes:

Publication 1797-6.5.6 - June 2005

Page 191: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 42

1797-IBN16 FLEX Ex 16 NAMUR Input Module

Inputs Each input can be operated from a NAMUR sensor or a mechanical contact (if mechanical inputs are used). Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a common plus-line.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+V -V +V -V41504

+ -

Ch 0

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

+ -

Ch 1

+ -

Ch 2

+ -

Ch 3

+ -

Ch 4

+ -

Ch 5

+ -

Ch 6

+ -

Ch 7

+ -

Ch 8

+ -

Ch 9

+ -

Ch 10

+ -

Ch 11

+ -

Ch 12

+ -

Ch 13

+ -

Ch 14

+ -

Ch 15

No connection allowed to terminals 36 and 49

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

1 Publication 1797-6.5.6 - June 2005

Page 192: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

42-2 1797-IBN16 FLEX Ex 16 NAMUR Input Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 16 NAMUR Input Module Installation Instructions, publication 1797-5.7.

FM I/O Entity Parameters (Each Channel)

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Table 1: Entity Values for Field Device Connections

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib/[ia] IIC T4

Certificates FM Certificate Number 3009806FM

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(-) 14.5 15 - - A, B 0.3 80.0

C, E 0.9 320.0

D, F, G 2.4 640.0

1797- IBN16Allen-BradleyB-A

7 PWR6543210 98 1110 1312 1514

6

16 Point NAMUR Input Module

6

FLEX Ex NAMUR Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42060

Publication 1797-6.5.6 - June 2005

Page 193: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IBN16 FLEX Ex 16 NAMUR Input Module 42-3

IMPORTANT A terminal base may or may not have an I/O module installed.

Hazardous (Classified) LocationClass I, Zone 0 Group IICClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Group IICClass I, Div. 1 Groups A, B, C, D

For connection to other modules, refer to the General FM Certification Information on page 38-1.

From FM approved devices, 1797-PS1N, -PS2N, or -PS2N2.

For connection to other modules, refer to the General FM Certification Information on page 38-1.

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

29(+)30(-)

1797-IBN16

16

Shield Connection Only

50

51

35

34

Female Bus ConnectorVmax=5.8VImax=400mACi=0Li=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

3340414243444531(+)

32(-)

25(+)26(-)27(+)28(-)

21(+)22(-)23(+)24(-)

17(+)18(-)19(+)20(-)

12(+)13(-)14(+)15(-)

8(+)9(-)10(+)11(-)

4(+)5(-)6(+)7(-)

0(+)1(-)2(+)3(-)

ch8

ch9

ch10

ch11

ch12

ch13

ch14

ch15

Any Simple Apparatus or FM approved device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1:

42477

Publication 1797-6.5.6 - June 2005

Page 194: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

42-4 1797-IBN16 FLEX Ex 16 NAMUR Input Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IBN16, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 36-39, and 46-49 shall not be connected.

Any combination of up to eight channels may be connected in parallel and connected to simple apparatus in a hazardous location. If two channels are connected in parallel, the total cable inductance must be limited to 20mH for Groups A and B, 80mH for Groups C and E, and 160mH for Groups D, F, and G. If eight channels are connected in parallel, the total cable inductance must be limited to 2mH for Groups A and B, 8mH for Groups C and E and 16mH for Groups D, F, and G.

WARNING: Substitution of components may impair intrinsic safety.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-G 0 0

Publication 1797-6.5.6 - June 2005

Page 195: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 43

1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

Outputs Each output can operate a discrete field device. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

40068

Row A

Row B

Row C

+ + + +- - - -

ch0 ch1 ch2 ch3

+V +V-V -VNo connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to 32, 36, 37, 38, 39, 46, 47, 48, 49

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

1 Publication 1797-6.5.6 - June 2005

Page 196: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

43-2 1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 24V dc Non-Isolated Source 4 Output Module Installation Instructions, publication 1797-5.6.

FM I/O Entity Parameters Wiring Methods

• Wiring method 1: Each channel is wired separately.• Wiring method 2: Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Table 1: Entity Values for Field Device Connections

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib/[ia] IIC T4

Certificates FM Certificate Number 3009806FM

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(-) 27.4 110.0 - - A, B, 0.105 3.0

C, E 0.315 9.0

D, F, G 0.840 24.0

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- OB4DAllen-BradleyB-A

0 1 2 3 4 5 6 7 PWR

7

4 Point Source Output Module

FLEX Ex Discrete Output I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42058

Publication 1797-6.5.6 - June 2005

Page 197: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module 43-3

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-G 1.35 0

Hazardous (Classified) LocationClass I, Zone 0 Group IICClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Group IICClass I, Div. 1 Groups A, B, C, D

For connection to other modules, refer to the General FM Certification Information on page 38-1.

1797-OB4D

16

Shield Connection Only

50

51

35

34

Vmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0 (+)

Female Bus Connector

Any Simple Apparatus or FM approved device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field

1 (-)

ch0

ch1

ch2

ch3

4 (+)5 (-)

8 (+)9 (-)

12 (+)13 (-)

42478

For connection to other modules, refer to the General FM Certification Information on page 38-1.

From FM approved devices, 1797-PS1N, -PS2N, or -PS2N2.

Publication 1797-6.5.6 - June 2005

Page 198: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

43-4 1797-OB4D FLEX Ex 24V dc Non-Isolated Source 4 Output Module

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-OB4D, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 2, 3, 6, 7, 10, 11, 14, 15, 17-32, 36-39, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.

Publication 1797-6.5.6 - June 2005

Page 199: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 44

1797-IE8 FLEX Ex 8 Input Analog Module

Inputs Each input can be operated from an analog field device signal. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a common plus-line.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+ -+ -+ -+ -

Ch 7Ch 6Ch 5Ch 4

+V -V +V -V40071

sigsigsigsig

No connection allowed

No connection allowed

Ch 7

+ -+ -+ -+ -

Ch 2Ch 1Ch 0

sigsigsigsig

Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

1 Publication 1797-6.5.6 - June 2005

Page 200: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

44-2 1797-IE8 FLEX Ex 8 Input Analog Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Input Analog Module Installation Instructions, publication 1797-5.5.

FM I/O Entity Parameters Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib/[ia] IIC T4

Certificates FM Certificate Number 3009806FM

Publication 1797-6.5.6 - June 2005

Page 201: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8 FLEX Ex 8 Input Analog Module 44-3

Table 1: Entity Values for Field Device Connections

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(sig) 23.7 92.5 - - A, B 0.15 4.0

C, E 0.45 12.0

D, F, G 1.20 32.0

1(sig), 2(-) 5 1.0 - - A, B 100 1000

C, E 300 1000

D, F, G 800 1000

0(+), 1(sig), 2(-) - - 23.7 93.5 A, B 0.15 4.0

C, E 0.45 12.0

D, F, G 1.20 32.0

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- IE8Allen-BradleyB-A

7 PWR0 1 2 3 4 5 6

3

8 CHANNEL ANALOG INPUT

FLEX Ex Analog Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42055

Publication 1797-6.5.6 - June 2005

Page 202: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

44-4 1797-IE8 FLEX Ex 8 Input Analog Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-G 1.35 0

Hazardous (Classified) LocationClass I, Zone 0 Group IICClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Group IICClass I, Div. 1 Groups A, B, C, D

For connection to other modules, refer to the General FM Certification Information on page 38-1.

1797-IE8

16

Shield Connection Only

5051

35

34

Vmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0 (+)

Female Bus Connector

Any Simple Apparatus or FM approved device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field

1 (sig)

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

2 (-)

4 (+)5 (sig)6 (-)8 (+)9 (sig)10 (-)

12 (+)13 (sig)14 (-)

17 (+)18 (sig)19 (-)

21 (+)22 (sig)23 (-)25 (+)26 (sig)27 (-)

29 (+)30 (sig)31 (-) 42056

For connection to other modules, refer to the General FM Certification Information on page 38-1.

From FM approved devices, 1797-PS1N, -PS2N, or -PS2N2.

Publication 1797-6.5.6 - June 2005

Page 203: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8 FLEX Ex 8 Input Analog Module 44-5

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IE8, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.

Publication 1797-6.5.6 - June 2005

Page 204: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

44-6 1797-IE8 FLEX Ex 8 Input Analog Module

Notes:

Publication 1797-6.5.6 - June 2005

Page 205: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 45

1797-IE8H FLEX Ex 8 Input HART Analog Module

Inputs Each input can be operated from an analog field device signal. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a common plus-line.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+ -+ -+ -+ -

Ch 7Ch 6Ch 5Ch 4

+V -V +V -V40071

sigsigsigsig

No connection allowed

No connection allowed

Ch 7

+ -+ -+ -+ -

Ch 2Ch 1Ch 0

sigsigsigsig

Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

1 Publication 1797-6.5.6 - June 2005

Page 206: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

45-2 1797-IE8H FLEX Ex 8 Input HART Analog Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Input Analog Module Installation Instructions, publication 1797-5.5.

FM I/O Entity Parameters Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Table 1: Entity Values for Field Device Connections

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib/[ia] IIC T4

Certificates FM Certificate Number 3009806FM

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(sig), 2(-) 24.4 92.5 - - A, B 0.12 4.0

C, E 0.35 12.0

D, F, G 0.95 32.0

1(sig), 2(-) 24.4 92.5 28 110 A, B 0.12 4.0

C, E 0.35 12.0

D, F, G 0.95 32.0

1797- IE8HAllen-BradleyB-A

7 PWR0 1 2 3 4 5 6

8

8 CHANNEL ANALOG INPUT

FLEX Ex Analog Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42055

Publication 1797-6.5.6 - June 2005

Page 207: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8H FLEX Ex 8 Input HART Analog Module 45-3

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus

IMPORTANT A terminal base may or may not have an I/O module installed.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-D 1.35 0

Hazardous (Classified) LocationClass I, Zone 0 Group IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Group IICClass I, Div. 1 Groups A, B, C, D

For connection to other modules, refer to the General FM Certification Information on page 38-1.

1797-IE8H

16

Shield Connection Only

5051

35

34

Vmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0 (+)

Female Bus Connector

Any Simple Apparatus or FM approved device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field Device Connections.

1 (sig)

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

2 (-)

4 (+)5 (sig)6 (-)8 (+)9 (sig)10 (-)

12 (+)13 (sig)14 (-)

17 (+)18 (sig)19 (-)

21 (+)22 (sig)23 (-)25 (+)26 (sig)27 (-)

29 (+)30 (sig)31 (-) 42056

For connection to other modules, refer to the General FM Certification Information on page 38-1.

From FM approved devices, 1797-PS1N, -PS2N, or -PS2N2.

Publication 1797-6.5.6 - June 2005

Page 208: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

45-4 1797-IE8H FLEX Ex 8 Input HART Analog Module

are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IE8H, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.

Publication 1797-6.5.6 - June 2005

Page 209: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 46

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

Inputs Each input can be operated from an analog field device signal. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a common plus-line.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+ -+ -+ -+ -

Ch 7Ch 6Ch 5Ch 4

+V -V +V -V40071

sigsigsigsig

No connection allowed

No connection allowed

Ch 7

+ -+ -+ -+ -

Ch 2Ch 1Ch 0

sigsigsigsig

Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

1 Publication 1797-6.5.6 - June 2005

Page 210: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

46-2 1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Input Analog Module with Noise Filter Installation Instructions, publication 1797-5.31.

FM I/O Entity Parameters Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib/[ia] IIC T4

Certificates FM Certificate Number 3009806FM

Publication 1797-6.5.6 - June 2005

Page 211: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter 46-3

Table 1: Entity Values for Field Device Connections

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(sig) 23.7 92.5 - - A, B 0.15 4.0

C, E 0.45 12.0

D, F, G 1.20 32.0

1(sig), 2(-) 5 1.0 - - A, B 100 1000

C, E 300 1000

D, F, G 800 1000

0(+), 1(sig), 2(-) - - 23.7 93.5 A, B 0.15 4.0

C, E 0.45 12.0

D, F, G 1.20 32.0

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- IE8NFAllen-BradleyB-A

7 PWR0 1 2 3 4 5 6

3

8 CHANNEL ANALOG INPUT NOISE FILTER

FLEX Ex Analog Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42479

Publication 1797-6.5.6 - June 2005

Page 212: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

46-4 1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-G 1.35 0

Hazardous (Classified) LocationClass I, Zone 0 Group IICClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zones 1 Group IICClass I, Div. 1 Groups A, B, C, D

For connection to other modules, refer to the General FM Certification Information on page 38-1.

1797-IE8NF

16

Shield Connection Only

5051

35

34

Vmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0 (+)

Female Bus Connector

Any Simple Apparatus or FM approved device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field

1 (sig)

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7

2 (-)

4 (+)5 (sig)6 (-)8 (+)9 (sig)10 (-)

12 (+)13 (sig)14 (-)

17 (+)18 (sig)19 (-)

21 (+)22 (sig)23 (-)25 (+)26 (sig)27 (-)

29 (+)30 (sig)31 (-) 42483

For connection to other modules, refer to the General FM Certification Information on page 38-1.

From FM approved devices, 1797-PS1N, -PS2N, or -PS2N2.

Publication 1797-6.5.6 - June 2005

Page 213: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter 46-5

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IE8NF, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.

Publication 1797-6.5.6 - June 2005

Page 214: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

46-6 1797-IE8NF FLEX Ex 8 Input Analog Module with Noise Filter

Notes:

Publication 1797-6.5.6 - June 2005

Page 215: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 47

1797-OE8 FLEX Ex 8 Output Analog Module

Outputs Each output channel can operate an analog field device. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

41440

Row A

Row B

Row C

ch0 ch1 ch2 ch3

+V +V-V -V

+ + + +- - - -

ch4 ch5 ch6 ch7

+ - + - + - + -

No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

1 Publication 1797-6.5.6 - June 2005

Page 216: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

47-2 1797-OE8 FLEX Ex 8 Output Analog Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Output Analog Module Installation Instructions, publication 1797-5.3.

FM I/O Entity Parameters Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Table 1: Entity Values for Field Device Connections

Operational Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib/[ia] IIC T4

Certificates FM Certificate Number 3009806FM

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(sig) 21.0 100.0 - - A, B 0.20 3.5

C, E 0.60 10.5

D, F, G 1.60 28.0

1797- OE8Allen-BradleyB-A

OUT 1OUT 0 OUT 2 PWROUT 7OUT 6OUT 5OUT 4OUT 3

4

8 CHANNEL ANALOG OUTPUT

FLEX Ex Analog Output I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42013

Publication 1797-6.5.6 - June 2005

Page 217: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-OE8 FLEX Ex 8 Output Analog Module 47-3

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

IMPORTANT A terminal base may or may not have an I/O module installed.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-G 1.35 0

Hazardous (Classified) LocationClass I, Zone 0 Group IICClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Group IICClass I, Div. 1 Groups A, B, C, D

For connection to other modules, refer to the General FM Certification Information on page 47-1.

1797-OE8

16

Shield Connection Only

50

Male Bus Connector

33404142434445

0 (+)

Female Bus Connector

Any Simple Apparatus or FM approved device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1:

1 (-)

ch1

ch2

ch3

ch4

ch5

ch6

4 (+)5 (-)

8 (+)9 (-)

12 (+)13 (-)

17 (+)18 (-)

21 (+)22 (-)

25 (+)26 (-)

42056

29 (+)30 (-)

51

35

34

ch0

ch7

Vmax=9.5VImax=1ACi=0Li=0

Vmax=5.8VImax=400mACi=1350nFLi=0

For connection to other modules, refer to the General FM Certification Information on page 38-1.

From FM approved devices, 1797-PS1N, -PS2N, or -PS2N2.

Publication 1797-6.5.6 - June 2005

Page 218: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

47-4 1797-OE8 FLEX Ex 8 Output Analog Module

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-OE8, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36-38, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.

Publication 1797-6.5.6 - June 2005

Page 219: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 48

1797-OE8H FLEX Ex 8 Output HART Analog Module

Outputs Each output channel can operate an analog field device. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

41440

Row A

Row B

Row C

ch0 ch1 ch2 ch3

+V +V-V -V

+ + + +- - - -

ch4 ch5 ch6 ch7

+ - + - + - + -

No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

1 Publication 1797-6.5.6 - June 2005

Page 220: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

48-2 1797-OE8H FLEX Ex 8 Output HART Analog Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex 8 Output Analog Module Installation Instructions, publication 1797-5.3.

FM I/O Entity Parameters Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Table 1: Entity Values for Field Device Connections

Operational Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib/[ia] IIC T4

Certificates FM Certificate Number 3009806FM

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(sig) 21.0 100.0 - - A, B 0.20 3.5

C, E 0.60 10.5

D, F, G 1.60 28.0

1797- OE8HAllen-BradleyB-A

OUT 1OUT 0 OUT 2 PWROUT 7OUT 6OUT 5OUT 4OUT 3

4

8 CHANNEL ANALOG OUTPUT

FLEX Ex Analog Output I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42013

Publication 1797-6.5.6 - June 2005

Page 221: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-OE8H FLEX Ex 8 Output HART Analog Module 48-3

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

IMPORTANT A terminal base may or may not have an I/O module installed.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-D 1.35 0

Hazardous (Classified) LocationClass I, Zone 0 Group IIC, IIB, IIAClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Group IICClass I, Div. 1 Groups A, B, C, D

For connection to other modules, refer to the General FM Certification Information on page 48-1.

1797-OE8H

16

Shield Connection Only

50

Male Bus Connector

33404142434445

0 (+)

Female Bus Connector

Any Simple Apparatus or FM approved device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1:

1 (-)

ch1

ch2

ch3

ch4

ch5

ch6

4 (+)5 (-)

8 (+)9 (-)

12 (+)13 (-)

17 (+)18 (-)

21 (+)22 (-)

25 (+)26 (-)

42056

29 (+)30 (-)

51

35

34

ch0

ch7

Vmax=9.5VImax=1ACi=0Li=0

Vmax=5.8VImax=400mACi=1350nFLi=0

For connection to other modules, refer to the General FM Certification Information on page 38-1.

From FM approved devices, 1797-PS1N, -PS2N, or -PS2N2.

Publication 1797-6.5.6 - June 2005

Page 222: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

48-4 1797-OE8H FLEX Ex 8 Output HART Analog Module

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-OE8H, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36-38, and 46-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.

Publication 1797-6.5.6 - June 2005

Page 223: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 49

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

Inputs Each input can be operated from a thermocouple (TC) or resistance temperature detector (RTD). Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other and have a common plus-line.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

Ch 7Ch 6Ch 5Ch 4

+V CJC -V

41505

Ch 7

+ L

Ch 2Ch 1Ch 0 Ch 3

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

H - + LH - + LH - + LH -

+ LH - + LH - + LH - + LH -

-V CJCchassis GND for shield

chassis GND for shield

0+ 0- 1-1+

No connection allowed to terminals 36 and 49

+V

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

1 Publication 1797-6.5.6 - June 2005

Page 224: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

49-2 1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Thermocouple/RTD Input Module Installation Instructions, publication 1797-5.4.

FM I/O Entity Parameters Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Table 1: Entity Values for Field Device Connections

Operational Temperature -20 to +70oC (-4 to 158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib/[ia] IIC T4

Certificates FM Certificate Number 3009806FM

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel e.g. ch0

0(+), 1(H), 2(L), 3(-)

9.0 37.0 - - A, B 3.0 20.0

C, E 9.0 60.0

D, F, G 24.0 160.0

37, 38, 39 (CJC0)

or46, 47, 48

(CJC1)

9.0 1.0 - - A, B 3.0 1000.0

C, E 9.0 1000.0

D, F, G 24.0 1000.0

0(+), 1(H), 2(L), 3(-)

37, 38, 39 (CJC0)

or46, 47, 48

(CJC1)

- - 9.0 38.0 A, B 3.0 20.0

C, E 9.0 60.0

D, F, G 24.0 160.0

Publication 1797-6.5.6 - June 2005

Page 225: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IRT8 FLEX Ex Thermocouple/RTD Input Module 49-3

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- IRT8Allen-BradleyB-A

7 PWR6543210

2

8 Point RTD/Thermocouple mV Input ModuleFLEX Ex Temperature Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42020

Hazardous (Classified) LocationClass I, Zone 0 Group IICClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Group IICClass I, Div. 1 Groups A, B, C, D

For connection to other modules, refer to the General FM Certification Information on page 38-1.

ch0

ch1

ch2

ch3

ch4

ch5

ch6

ch7 29(+)30(H)

1797-IRT8

16

Shield Connection Only

50

51

35

34

Female Bus ConnectorVmax=5.8VImax=400mACi=1350nFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

3340414243444531(L)

32(-)

25(+)26(H)27(L)28(-)

21(+)22(H)23(L)24(-)

17(+)18(H)19(L)20(-)

12(+)13(H)14(L)15(-)

8(+)9(H)10(L)11(-)

4(+)5(H)6(L)7(-)

0(+)1(H)2(L)3(-)

37 38 39 46 47 48

CJC0 CJC1

Any Simple Apparatus or FM approved device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1:

42485

For connection to other modules, refer to the General FM Certification Information on page 38-1.

From FM approved devices, 1797-PS1N, -PS2N, or -PS2N2.

Publication 1797-6.5.6 - June 2005

Page 226: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

49-4 1797-IRT8 FLEX Ex Thermocouple/RTD Input Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IRT8, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 36 and 49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-G 1.35 0

Publication 1797-6.5.6 - June 2005

Page 227: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 50

1797-IJ2 FLEX Ex Frequency Input Module

Inputs The frequency input module has 2 input channels. Each input can accept inputs from magnetic pickups or proximity probes. Each input channel has 2 input selections: frequency input or gate input. Do not apply any non-intrinsically safe signals to this module.

The channels in this module are electrically connected to each other.

Wiring to a 1797-TB3 or -TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.

IMPORTANT When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.

Row A

Row B

Row C

+V -V

42334

3V V+

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

6V GND 50mV Sel

N500/50 mV

8V 8V N GND 6VV+ 3V

R0 NO R0 NC

-V

No connection allowed to terminals 19, 30, 36, 38, 39, 47, 48, 49

+VR0 COM R1 COM

50mV Sel

500/50 mV

Channel 0 Frequency Input Channel 1 Frequency Input

GND

GND 50mV Sel

N500/50 mV

8V 8V N 50mV Sel

500/50 mV

GND R1 NOR1 NC

Channel 0 Gate Input Channel 1 Gate Input

ATTENTION Do not use any unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module and/or unintended operation of your system.

1 Publication 1797-6.5.6 - June 2005

Page 228: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

50-2 1797-IJ2 FLEX Ex Frequency Input Module

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Frequency Input Module Installation Instructions, publication 1797-5.7.

FM Input I/O Entity Parameters

Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Table 1: Entity Values for Field Device Connections

Operating Temperature -20 to +70oC (-4 to +158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib/[ia] IIC T4

Certificates FM Certificate Number 3009806FM

Wiring Method

Channel Terminals Voc (V)

Isc (mA)

Vt (V)

It (mA)

Groups Ca (µF)

La (mH)

1 and 2 Any one channel

6, 7;9, 8;

23, 2426, 25

14.7 15.0 - - A, B 0.65 130.0

C, E 1.95 390.0

D, F, G 5.20 1040.0

1 and 2 Any one channel

5, 3;10, 12;22, 20;27, 29

14.7 10.0 - - A, B 0.65 300.0

C, E 1.95 900.0

D, F 5.20 2400.0

1 and 2 Any one channel

5, 3, 6, 4;10, 12, 9, 11;

22, 20, 21, 23;27, 29, 26, 28

14.7 10.0 - - A 0.65 300.0

C, E 1.95 900.0

D, F, G 5.20 2400.0

1 and 2 Any one channel

0, 2, 3;1, 2, 3;

14, 12, 13;15, 12, 13

26.5 82.0 - - A, B 0.13 4.5

C, E 0.39 13.5

D, F, G 1.04 36.0

Wiring Method

Channel Terminals Vmax (V)

Imax (mA)

Groups Ci (µF) Li (mH)

1 and 2 Any one channel

17, 18, 37or

31, 32, 46

28 93.0 A, B 0 0

C, E 0 0

D, F, G 0 0

Publication 1797-6.5.6 - June 2005

Page 229: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-IJ2 FLEX Ex Frequency Input Module 50-3

IMPORTANT A terminal base may or may not have an I/O module installed.

1797- IJ2Allen-BradleyB-A

7 PWR6543210

1

2 Point Frequency Input ModuleFLEX Ex Frequency Input I/O Module

LEDs

Female Bus Connection

Field Wiring Terminals

Terminal Base

Terminal Base Key

Male Bus Connection

Key Position for Terminal Base Insertion

42066

Hazardous (Classified) LocationClass I, Zone 0 Group IICClass I, Div. 1 Groups A, B, C, DClass II, Div. 1 Groups E, F, GClass III, Div. 1

Hazardous (Classified) LocationClass I, Zone 1 Group IICClass I, Div. 1 Groups A, B, C, D

For connection to other modules, refer to the General FM Certification Information on page 38-1.

1797-IJ2

16

Shield Connection Only

50

51

35

34

Vmax=5.8VImax=400mACi=2.64µFLi=0

Vmax=9.5VImax=1ACi=0Li=0

Male Bus Connector

33404142434445

0Female Bus Connector

1234567

89101112131415

2021222324

2526272829

Vmax=28VImax=93mACi=0Li=0

Vmax=28VImax=93mACi=0Li=0

17 18 37 31 32 46

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 28V; Isc < 93mA.

To any intrinsically safe device or associated apparatus with Entity Concept parameters of Voc < 28V; Isc < 93mA.

ch0Freq. In

ch1Freq. In

ch0Gate

ch1Gate

Any Simple Apparatus or FM approved device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1:

Any Simple Apparatus or I.S. device with Entity Concept parameters (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1: Entity Values for Field

42486

For connection to other modules, refer to the General FM Certification Information on page 38-1.

From FM approved devices, 1797-PS1N, -PS2N, or -PS2N2.

Publication 1797-6.5.6 - June 2005

Page 230: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

50-4 1797-IJ2 FLEX Ex Frequency Input Module

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

Table 3: Flexbus Entity Values for this Module

Note: Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc or Vt and It of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1A, 20µJ, or 25mW.

Wiring methods must be in accordance with the National Electric Code, ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.

This module, 1797-IJ2, must be used with terminal base 1797-TB3 or 1797-TB3S.

Terminals 19, 30, 36, 38-39, and 47-49 shall not be connected.

WARNING: Substitution of components may impair intrinsic safety.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Terminals Vmax (V) Imax (mA)

Groups Ci (µF) Li (µH)

Female Bus Connector

5.8 400 A-G 2.64 0

Publication 1797-6.5.6 - June 2005

Page 231: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 51

1797-PS1N FLEX Ex Power Supply

Installation in Division 1/Zone 1

The 1797-PS1N power supply has a protection factor of IP66. Refer to the specifications table for the IS module type.

Outputs The channels in the power supply are electrically connected to each other and have a common +V line.

Typical Wiring Configurations

ATTENTION The power supply cannot be used in an intrinsically safe environment after its outputs have been exposed to non-intrinsically safe signals.

IMPORTANT You cannot interconnect lines because of the intrinsic safety requirements.

43306

+V -V +V -V +V -V +V -V+-

chaGND

+-

Out 1 Out 2 Out 3 Out 4VoutVin

1 2 3 4 5 10 11 12 13 14 15 16 17

Terminal Base Assignments

North America AC Power Input IS Power Output

1 Publication 1797-6.5.6 - June 2005

Page 232: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

51-2 1797-PS1N FLEX Ex Power Supply

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Power Supplies Installation Instructions, publication 1797-5.34.

FM I/O Entity Parameters Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Table 1: Entity Values for Field Device Connections

Specifications 1797-PS1NVoltage Range 85-250V ac or 120-250V dcOperational Temperature -20 to 70oC (-4 to 158oF)Agency Certification Mounting - Class I Division 1 Groups B-D T4

IS Power - Class I Division 1 Groups A-D T4Class I Zone 1 AEx [ib] IIC

Certificates FM Certificate Number 3009806

ATTENTION Once power has been applied, wait 15 minutes after disconnecting before opening cover.

FM

Wiring Method

Channel Terminals Voc (V)

Isc (A)

Groups Ca (µF)

La (µH)

1 and 2 Any one channel e.g. ch1

10(+), 11(-) 9.5 1.0 A, B 0.5 8

C, E 1.5 24

D, F, G 4.0 64

Publication 1797-6.5.6 - June 2005

Page 233: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-PS1N FLEX Ex Power Supply 51-3

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70, Article 504 (Divisions) or 505 (Zones).

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70, Article 501 (Divisions).

Conduit runs must have sealing fittings at the entry of the enclosure.

Ch4Ch3Ch2

Ch1

1 2 3 4 5

1716151413121110

Nonhazardous Location

Feed through to next power supply

85-250V ac and 120-250V dc power supply

Hazardous (Classified) LocationClass I, Division 1 Groups A, B, C, D

Class II, Division 1 Groups E, F, GClass III Division 1Class 1, Zone1 IIC

nonintrinsically safe wiring intrinsically safe wiring

To any FM approved device with entity concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with entity concept parameters listed in Table 1. 42487

Hazardous (Classified) Location1797-PS1N

Class I, Division 1, Groups B, C, DClass I, Zone 1, Group IIB + H2

Publication 1797-6.5.6 - June 2005

Page 234: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

51-4 1797-PS1N FLEX Ex Power Supply

The wiring contained within the nonintrinsically safe wiring compartment and the intrinsically safe wiring compartment shall be separated from each other. Care must be taken to guarantee the separation of nonintrinsically safe and intrinsically safe wiring. The partitions within the power supply provide the necessary isolation for the electronics and the wiring, however, extreme care must be taken to guarantee wires are contained within their appropriate compartment and cannot contact any of the electronics.

WARNING: Substitution of components may impair intrinsic safety.

Cable must be rated at a minimum of 100°C.

WARNING: Keep cover tightly closed when circuits are live.

After disconnecting power supply, wait fifteen minutes before removing cover.

No live maintenance.

Publication 1797-6.5.6 - June 2005

Page 235: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 52

1797-PS2N2 FLEX Ex Power Supply

Installation in Division 1/Zone 1

The 1797-PS2N2 power supply has a protection factor of IP66. Refer to the specifications table for the IS module type.

Outputs The channels in the power supply are electrically connected to each other and have a common +V line.

Typical Wiring Configurations

ATTENTION The power supply cannot be used in an intrinsically safe environment after its outputs have been exposed to non-intrinsically safe signals.

IMPORTANT You cannot interconnect lines because of the intrinsic safety requirements.

41256

+V -V +V -V +V -V +V -V-+chaGND

-+

Out 1 Out 2 Out 3 Out 4Vin2Vin1

1 2 3 4 5 10 11 12 13 14 15 16 17

Terminal Base Assignments

North America DC Power Input IS Power Output

1 Publication 1797-6.5.6 - June 2005

Page 236: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

52-2 1797-PS2N2 FLEX Ex Power Supply

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Power Supply Installation Instructions, publication 1797-5.12.

FM I/O Entity Parameters Wiring Methods

• Wiring method 1 - Each channel is wired separately.• Wiring method 2 - Multiple channels in one cable, providing each

channel is separated in accordance with the National Electric Code (NEC).

Table 1: Entity Values for Field Device Connections

Specifications 1797-PS2N2Voltage Range 18 to 32V dcOperational Temperature -20 to 70oC (-4 to 158oF)Agency Certification Mounting - Class I Division 1 Groups B-D T4

IS Power - Class I Division 1 Groups A-D T4Class I Zone 1 AEx [ib] IIC

Certificates FM Certificate Number 3009806

ATTENTION Once power has been applied, wait 15 minutes after disconnecting before opening cover.

FM

PS2N PS2N2 PS2N PS2N2

Wiring Method

Channel Terminals Voc (V)

Isc (A)

Groups Ca

(µF)Ca

(µF)La

(µH)La (µH)

1 and 2 Any one channel e.g. ch1

10(+), 11(-) 9.5 1.0 A, B 0.8 0.5 10 8

C, E 2.4 1.5 30 24

D, F, G 6.4 4.0 80 64

Publication 1797-6.5.6 - June 2005

Page 237: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-PS2N2 FLEX Ex Power Supply 52-3

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of Voc and Isc of the associated apparatus are less than or equal to Vmax and Imax of the intrinsically safe apparatus and the approved values of Ca and La of the associated apparatus are greater than Ci + Ccable and Li + Lcable respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70, Article 504 (Divisions) or 505 (Zones).

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70, Article 501 (Divisions).

Conduit runs must have sealing fittings at the entry of the enclosure.

Ch4Ch3Ch2

Ch1

1 2 3 4 5

1716151413121110

Nonhazardous Location

redundant connection

18-32V dc power supply

Hazardous (Classified) LocationClass I, Division 1 Groups A, B, C, D

Class II, Division 1 Groups E, F, GClass III Division 1

Class 1, Zone1 IIC

nonintrinsically safe wiring intrinsically safe wiring

To any FM approved device with entity concept parameters of (Vmax, Imax, Ci, Li) appropriate for connection to associated apparatus with entity concept parameters listed in Table 1. 42487

Hazardous (Classified) Location1797-PS2N2

Class I, Division 1, Groups B, C, DClass I, Zone 1, Group IIB + H2

Publication 1797-6.5.6 - June 2005

Page 238: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

52-4 1797-PS2N2 FLEX Ex Power Supply

The wiring contained within the nonintrinsically safe wiring compartment and the intrinsically safe wiring compartment shall be separated from each other. Care must be taken to guarantee the separation of nonintrinsically safe and intrinsically safe wiring. The partitions within the power supply provide the necessary isolation for the electronics and the wiring, however, extreme care must be taken to guarantee wires are contained within their appropriate compartment and cannot contact any of the electronics.

WARNING: Substitution of components may impair intrinsic safety.

Cable must be rated at a minimum of 100°C.

WARNING: Keep cover tightly closed when circuits are live.

After disconnecting power supply, wait fifteen minutes before removing cover.

No live maintenance.

Publication 1797-6.5.6 - June 2005

Page 239: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 53

1797-ACNR15 ControlNet Ex Redundant Media Adapter

Module Installation Use the redundant media adapter module to connect FLEX Ex modules to the ControlNet Ex network.

Inputs/Outputs Do not apply any non-intrinsically safe signals to the adapter.

Intrinsically Safe Specifications

For a full list of specifications, refer to ControlNet Ex Redundant Media Adapter Installation Instructions, publication 1797-5.14.

PWR

1797-ACNR15

3 2

41408

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib IIC T4

Certificates FM Certificate Number 3009806FM

1 Publication 1797-6.5.6 - June 2005

Page 240: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

53-2 1797-ACNR15 ControlNet Ex Redundant Media Adapter

FM Entity Parameters and Requirements

FM I/O Entity Parameters and Requirements

Table 2: Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module

See the General FM Certification Information chapter on page 38-1.

Terminals Vt (V) It (mA) Groups Ca (µF) La (µH)Male Bus Connector

5.8 400 A-G 3.0 3.0

Publication 1797-6.5.6 - June 2005

Page 241: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 54

1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

Module Installation A maximum of two 1797-RPFM modules may be used with one 1797-RPA adapter.

Inputs/Outputs Do not apply any non-intrinsically safe signals to the adapter or repeater module.

1 32 4

+V +V-V -V

1797-RPA

PWR

REPEATERADAPTER

COMMSTATUS

MODULESTATUS

41163

1797-RPA

1797-RPFM

Recv XmitRecv Xmit

Chan 1 Chan 2

41267

1797-RPFM

1 Publication 1797-6.5.6 - June 2005

Page 242: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

54-2 1797-RPA ControlNet Ex Modular Repeater Adapter and 1797-RPFM Fiber Repeater Module, Medium Distance

Intrinsically Safe Specifications

For a full list of specifications, refer to ControlNet Ex Modular Repeater Adapter and Fiber Repeater Module Installation Instructions, publication 1797-5.15.

FM Entity Parameters and Requirements

See the General FM Certification Information chapter on page 38-1.

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification Class I Division 1 Groups A-D T4Class I Zone 1 AEx ib IIC T4

Certificates FM Certificate Number 3009806FM

Publication 1797-6.5.6 - June 2005

Page 243: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Chapter 55

1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector

General Installation The 1797-CEC and -BIC must not be exposed to the environment. These modules have a protection factor of IP20. These modules shall be installed in an enclosure meeting the requirements of ANSI/ISA S82.02.01 or other applicable ordinary location standards.

Make certain that you only connect the FLEX Ex backplane connector to other intrinsically safe system modules to maintain the integrity of the intrinsically-safe backplane.

QUALITY

B-AAllen-Bradley

1797 - CEC

FLEXBUS CONNECTOR

1 2 43

+V -V +V -V

1797 - BIC

PWR

QUALITY

B-AAllen-Bradley

FLEXBUS ISOLATOR

428641797-CEC 1797-BIC

ATTENTION The 1797-BIC cannot be used as an associated apparatus after its FLEX Ex backplane connector has been exposed to non-intrinsically safe signals.

ATTENTION For proper operation, cycle power to the 1797-BIC at the same time power is cycled to the associated adapter.

1 Publication 1797-6.5.6 - June 2005

Page 244: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

55-2 1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector

I/O module capacitance value is cumulative. Ci (total) = Ci (I/O module 1) + Ci (I/O module 2) + ...Ci (I/O module 8). Ci (total) must be less than 39.67µF. The limitation of eight I/O modules per isolator is a functional limitation. The Ci values referred to here are for the female bus connector of the I/O modules and may be found in the appropriate I/O module block diagram.

Isolator Restriction

1797-BIC and -CEC Maximum of 8 I/O modules

1794Adapter

1797CEC

1797BIC

1797 I/O & Base

1797 I/O & Base

1797 I/O & Base

1797 I/O & Base

1797 power supply

24V dc power supply

42754

.

.

. .

.

.

. .

.

.

. .

.

.

. .

.

.

. .

.

.

. .

.

.

. .

.

.

. . .

Nonhazardous or Hazardous (Classified) LocationClass I, Zone 2, Group IIC orClass I, Division 2, Groups A-D

Nonhazardous or Hazardous (Classified) LocationClass I, Zone 1, Group IIC orClass I, Division 1, Groups A-D

42876

Diagram 1

.

.

. .

.

.

. .

.

.

. .

.

.

. .

.

.

. .

.

.

. .

Nonhazardous or Hazardous (Classified) LocationClass I, Zone 2, Group IIC orClass I, Division 2, Groups A-D

Nonhazardous or Hazardous (Classified) LocationClass I, Zone 1, Group IIC orClass I, Division 1, Groups A-D

42877

Diagram 2

Publication 1797-6.5.6 - June 2005

Page 245: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector 55-3

Inputs/Outputs Do not apply any non-intrinsically safe signals to the FLEX Ex backplane connector.

Intrinsically Safe Specifications

For a full list of specifications, refer to FLEX Ex Bus Isolator Installation Instructions, publication 1797-5.13.

1797-BIC Specifications

Output (Intrinsically Safe)(16 pin male and female flexbusconnector)

Vt < 5.75V dcIt < 398.25mACa < 39.67uFLa < 210uH

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification Nonincendive, use for Class I, Division 2 Groups A-D or Class I, Zone 2 Group IIC

Provides intrinsically safe outputs to Class I, Division 1 Groups A-D or Class I, Zone 1 Group IIC

Certificates FM Certificate Number 3010810

1797-CEC Specifications

Operational Temperature -20 to 70oC (-4 to 158oF)

Agency Certification Nonincendive, use for Class I, Division 2 Groups A-D or Class I, Zone 2 Group IIC

Certificates FM Certificate Number 3010810

FM

FM

Publication 1797-6.5.6 - June 2005

Page 246: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

55-4 1797-BIC Bus Isolator Module and 1797-CEC Flexbus Connector

Notes:

Publication 1797-6.5.6 - June 2005

Page 247: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Index

Numerics1797-ACNR15

inputs 16-1, 35-1, 53-1installation 16-1, 35-1, 53-1outputs 16-1, 35-1, 53-1specifications 16-2, 35-1, 53-1

1797-BCNR 19-1description 19-1, 37-1inputs 37-1outputs 19-1, 37-1repair 19-2, 37-2specifications 19-2, 37-2

1797-BICinputs 18-2, 55-3installation 18-1, 55-1outputs 18-2, 55-3specifications 18-3, 55-3

1797-CECinputs 18-2, 55-3installation 18-1, 55-1outputs 18-2, 55-3specifications 18-3, 55-3

1797-IBN16entity parameters 5-3, 24-3–24-5,

42-2–42-4inputs 5-1, 24-1, 42-1installation 5-1, 24-1specifications 5-2, 24-2, 42-2wiring 5-2, 24-1, 42-1

1797-IE8entity parameters 7-3, 26-3–26-5,

44-2–44-5inputs 7-1, 26-1, 44-1installation 7-1, 26-1specifications 7-2, 26-2wiring 7-2, 26-1, 44-1

1797-IE8Hentity parameters 8-3, 27-3–27-5,

45-2–45-5inputs 8-1, 27-1, 45-1installation 8-1, 27-1specifications 8-2, 27-2, 45-2wiring 8-2, 27-1, 45-1

1797-IE8NFentity parameters 9-3, 28-3–28-5,

46-2–46-5inputs 9-1, 28-1, 46-1installation 9-1, 28-1specifications 9-2, 28-2, 46-2wiring 9-2, 28-1, 46-1

1797-IJ2entity parameters 13-3–13-6, 32-2–

32-5, 50-2–50-4inputs 13-1, 32-1, 50-1installation 13-1, 32-1specifications 13-2, 32-2, 50-2wiring 13-2, 32-1, 50-1

1797-IRT8entity parameters 12-3, 31-3–31-5,

49-2–49-4inputs 12-1, 31-1, 49-1installation 12-1, 31-1specifications 12-2, 31-2, 49-2wiring 12-2, 31-2, 49-1

1797-OB4Dentity parameters 6-2, 25-2–25-5,

43-2–43-4installation 6-1, 25-1outputs 6-1, 25-1, 43-1specifications 6-2, 25-2, 43-2wiring 6-1, 25-1

1797-OE8entity parameters 10-2, 29-2–29-4,

47-2–47-4installation 10-1, 29-1outputs 10-1, 29-1, 47-1specifications 10-1, 29-2, 47-2wiring 10-1, 29-1, 47-1

1797-OE8Hentity parameters 11-2, 30-2–30-4,

48-2–48-4installation 11-1, 30-1outputs 11-1, 30-1, 48-1specifications 11-1, 30-2, 48-2wiring 11-1, 30-1, 48-1

1797-PS1Eoutputs 14-1specifications 14-2wiring 14-2zone 1 14-1zone 22 14-1

Publication 1797-6.5.6 - June 2005

Page 248: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

2

1797-PS1Nentity parameters 33-2–33-4, 51-2–

51-4outputs 33-1, 51-1specifications 33-2, 51-2wiring 33-1, 51-1zone 1 33-1, 51-1

1797-PS2E2outputs 15-1specifications 15-2wiring 15-2zone 1 15-1zone 22 15-1

1797-PS2N2entity parameters 34-2–34-4, 52-2–

52-4outputs 34-1, 52-1specifications 34-2, 52-2wiring 34-1, 52-1zone 1 34-1, 52-1

1797-RPA 54-1inputs 17-1, 36-1installation 17-1, 36-1, 54-1outputs 17-1, 36-1, 54-1specifications 17-2, 36-2, 54-2

1797-RPFMinputs 17-1, 36-1, 54-1installation 17-1, 36-1, 54-1outptus 36-1outputs 17-1, 54-1specifications 17-2, 36-2, 54-2

1797-TB3description 22-2, 40-2inputs 3-2, 22-2, 40-2installation 3-1, 22-1, 40-1specifications 3-3, 22-3, 40-3wiring 3-2, 22-2, 40-2zone 1 22-1, 40-1

1797-TB3Sdescription 23-2, 41-2inputs 4-2, 23-2, 41-2installation 4-1, 23-1, 41-1specifications 4-3, 23-3, 41-3wiring 4-2, 23-2, 41-2zone 1 23-1, 41-1

CCE/CENELEC

entity parameters 1-2installation 1-1system diagram 2-2–2-4

Eelectrostatic charge 1-2, 2-5, 20-2,

21-6, 38-3entity parameters

1797-IBN16 5-3, 24-3–24-5, 42-2–42-4

1797-IE8 7-3, 26-3–26-5, 44-2–44-51797-IE8H 8-3, 27-3–27-5, 45-2–

45-51797-IE8NF 9-3, 28-3–28-5, 46-2–

46-51797-IJ2 13-3–13-6, 32-2–32-5,

50-2–50-41797-IRT8 12-3, 31-3–31-5, 49-2–

49-41797-OB4D 6-2, 25-2–25-5, 43-2–

43-41797-OE8 10-2, 29-2–29-4, 47-2–

47-41797-OE8H 11-2, 30-2–30-4, 48-2–

48-41797-PS1N 33-2–33-4, 51-2–51-41797-PS2N2 34-2–34-4, 52-2–52-4CE/CENELEC 1-2FM 38-3UL, C-UL 20-2

Publication 1797-6.5.6 - June 2005

Page 249: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

3

Iinputs 19-1, 54-1

1797-ACNR15 16-1, 35-1, 53-11797-BCNR 19-1, 37-11797-BIC 18-2, 55-31797-CEC 18-2, 55-31797-IBN16 5-1, 24-1, 42-11797-IE8 7-1, 26-1, 44-11797-IE8H 8-1, 27-1, 45-11797-IE8NF 9-1, 28-1, 46-11797-IJ2 13-1, 32-1, 50-11797-IRT8 12-1, 31-1, 49-11797-RPA 17-1, 36-1, 54-11797-RPFM 17-1, 36-1, 54-11797-TB3 3-2, 22-2, 40-21797-TB3S 4-2, 23-2, 41-2

Ooutputs

1797-ACNR15 16-1, 35-1, 53-11797-BCNR 19-1, 37-11797-BIC 18-2, 55-31797-CEC 18-2, 55-31797-OB4D 6-1, 25-1, 43-11797-OE8 10-1, 29-1, 47-11797-OE8H 11-1, 30-1, 48-11797-PS1E 14-11797-PS1N 33-1, 51-11797-PS2E2 15-11797-PS2N2 34-1, 52-11797-RPA 17-1, 36-1, 54-11797-RPFM 17-1, 36-1, 54-1

Rrepair 1-3, 2-5, 20-2, 21-6, 38-3

1797-BCNR 19-2, 37-2

Sspecifications

1797-ACNR15 16-2, 35-1, 53-11797-BCNR 19-2, 37-21797-BIC 18-3, 55-31797-CEC 18-31797-IBN16 5-2, 24-2, 42-21797-IE8 7-2, 26-2, 44-21797-IE8H 8-2, 27-2, 45-21797-IE8NF 9-2, 28-2, 46-21797-IJ2 13-2, 32-2, 50-21797-IRT8 12-2, 31-2, 49-21797-OB4D 6-2, 25-2, 43-21797-OE8 10-1, 29-2, 47-21797-OE8H 11-1, 30-2, 48-21797-PS1E 14-21797-PS1N 33-2, 51-21797-PS2E2 15-21797-PS2N2 34-2, 52-21797-RPA 17-2, 36-2, 54-21797-RPFM 17-2, 36-2, 54-21797-TB3 3-3, 22-3, 40-31797-TB3S 4-3, 23-3, 41-3general 2-6

UUL, C-UL

entity parameters 20-2installation 20-1

Publication 1797-6.5.6 - June 2005

Page 250: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

4

Wwiring

1797-IBN16 5-2, 24-1, 42-11797-IE8 7-2, 26-1, 44-11797-IE8H 8-2, 27-1, 45-11797-IE8NF 9-2, 28-1, 46-11797-IJ2 13-2, 32-1, 50-11797-IRT8 12-2, 31-2, 49-11797-OB4D 6-1, 25-11797-OB4D1797-OE8 10-1, 29-1, 47-11797-OE8H 11-1, 30-1, 48-11797-PS1E 14-21797-PS1N 33-1, 51-11797-PS2E2 15-21797-PS2N2 34-1, 52-11797-TB3 3-2, 22-2, 40-21797-TB3S 4-2, 23-2, 41-2

Zzone 1 1-2, 2-5, 20-2, 21-5, 38-2

1797-PS1E 14-11797-PS1N 33-1, 51-11797-PS2E2 15-11797-PS2N2 34-1, 52-11797-TB3 22-1, 40-11797-TB3S 23-1, 41-1

zone 22 1-2, 2-51797-PS1E 14-11797-PS2E2 15-1

Publication 1797-6.5.6 - June 2005

Page 251: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

5

Notes:

Publication 1797-6.5.6 - June 2005

Page 252: FLEX Ex System Certification - Rockwell Automation · 2012. 2. 14. · 1 Publication 1797-6.5.6 - June 2005 Summary of Changes Changed Items These items changed since the last printing

Publication 1797-6.5.6 - June 2005 1 Supersedes Publication 1797-6.5.6 - April 2004 Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.