flowirl 8700(2)

77

Upload: srinivasan01981

Post on 14-Oct-2014

4.984 views

Category:

Documents


1.153 download

TRANSCRIPT

Page 1: FLOWIRL 8700(2)
Page 2: FLOWIRL 8700(2)

CONTENTS

1. Vortex Flowmeter Measuring Principle 1/1

2. System Installation & Startup 2/1-2/22

3. Vortex Flowmeter 3/1-3/2

4. Operation of Signel Converter 4/1-4/3

5. Description of keys 5/1-5/2

6. Program Function for various versions 6/1-6/25

7. Description of Program Menu Functions 7/1-7/5

8. Technical Data 8/1-8/7

9. Dimension & Weight 9/1-9/2

10. Functional Checks 10/1-10/2

11. Trouble Shooting 11/1-11/2

12. Do & Don’ts 12

0/1

Page 3: FLOWIRL 8700(2)

1/1

1. Measuring Principle

The Vortex flowmeter is used for measuring the flow velocity of fluids in pipelines. The measuring principle is based on thedevelopment of a Karman Vortex shedding street in the wake of a body built into the pipeline. In theory, this process enablesmeasurements to be carried out in turbulent flows with a Reynolds number Re>3000, but linear measurements are onlypossible where Re>20,000.

The periodic shedding of eddies occurs first from one side and then from the other side of a bluff body (Vortex-shedding body)installed perpendicular to the pipe axis. Vortex shedding generates a so-called “Karman Vortex Street” with alternatingpressure conditions whose frequency F is proportional to the flow velocity V. The non-dimentional Strouhal number S (primaryhead constant) describes the relationship between Vortex shedding frequency F (in Hz) width b of the body, and mean flowvelocity v (m/s)

F = b

vS *

The flexural vibration of the Vortex-shedding body is picked up in the primary head via sensors and analysed in the signalconverter. In the case of the gaseous, flowing media, the vibration frequency ranges between 10 and 7000 Hz.

To permit the mass rate of flow to be calculated from the volume rate of flow, either the medium pressure and the temperatureor the medium density at the installation location of the flowmeter must be known factors.

Karman Vortex Street

Page 4: FLOWIRL 8700(2)

Safety

2.1 Intended use

The vortex flowmeters manufactured by Forbes Marshall Pvt. Ltd. are used to

measure the flow of gases, vapors and liquids.

These flowmeters are particularly suitable for measuring:

• Clean liquids with low viscosity (< 10 cP)

• Hydrocarbons with low viscosity (< 10 cP)

• Water

• Chemicals with low corrosiveness

• Saturated steam

• Superheated steam, including CIP and SIP applications in the food industry

• Industrial gases

The meters are rated for the following flow velocities:

• From 0.3 to 9.0 m/s for liquids

• From 3.0 to 80 m/s for gases and vapors

Caution!

The operator shall bear sole responsibility for the use of the flowmeters in respect of suitability, intended use

and corrosion resistance of the materials used to the process product.

The manufacturer shall not be liable for any damage resulting from improper use or deployment contrary to

the prescribed purpose.

Do not use any abrasive or highly viscous media > 10 cP.

Note!

The sensors are fabricated from stainless steel 316 L DIN (1.4404).

In your project planning, please take account of the data given in the corrosion tables.

The pressure-loaded components have been designed and rated for stationary operation taking

account of maximum pressure and temperature.

External forces and moments, caused e.g. by pipe stresses, have not been taken into account.

Primarily, volumetric flow and temperature are measured, with pressure measurement as an

option. From these parameters the flowmeter calculates the mass flow or standard volumetric

flow using pre-programmed density data and then issues the measured values via various

communication interfaces.

i

2. System installation & Startup

2/1

Page 5: FLOWIRL 8700(2)

2.2 Certifications

• CRN approval pending

• IBR approval pending

2.3 Safety instructions from the manufacturer

The flowmeter has been built and tested in accordance with the current state-of-the-art design. It

complies with the relevant safety standards.

However, risks can occur if used improperly or contrary to the intended application. Therefore

please consistently observe all safety instructions given in this document.

2.3.1 Information concerning the documentation

In addition to the safety advice given in this documentation, national and regional safety

regulations and occupational health and safety provisions must also be observed.

2/2

Page 6: FLOWIRL 8700(2)

2.3.2 Display conventions

The following symbols are used to help you navigate this documentation more easily:

Danger!

These warning signs must be observed without fail. Even only partial disregarding such

warnings can result in serious health damage, damage to the flowmeter itself or to parts of

the operator’s plant.

Danger!

This symbol designates safety advice on handling electric current.

Information!

This symbol designates important information for the handling of the flowmeter.

Legal notice!

This symbol designates information on statutory directives and standards.

Handling

This symbol designates all instructions for actions to be carried out by the operator in the

specified sequence.

Consequence

This symbol designates all important consequences of the previous actions.

2.3.3 Safety instructions for the operator

Caution!

Meters from Forbes Marshall Pvt. Ltd. may only be installed, commissioned,

operated and maintained by properly trained and authorized personnel.

This document must be read and understood in its entirety by all users prior to installation,

commissioning, operation and maintenance of the flowmeter.

2/3

Page 7: FLOWIRL 8700(2)

Instrument Description

2.4 Scope of supply

Important information!

Please check the contents of the consignment for completeness and intactness.

Fig. 1: Scope of supply

1 Flowmeter

2 Bar magnet

3 Manual

4 Certificates, calibration certificate, parameter data sheet

2.5 Instrument versions

Flowirl 8700 come in the following versions:

• Converter with display

• Blind device

• Flanged sensor

• Sandwich design sensor

The following designs are available as options:

• with pressure sensor

• with shutoff valve for the pressure sensor

2/4

4

1

Page 8: FLOWIRL 8700(2)

2.5.1 Versions with flanged connection

The FLOWIRL 8700K compact unit consists of a VFS 8000 sensor and the VFC 700 converter, which to-

gether form a fixed mechanical unit.

Fig. 2: FLOWIRL 8700, flanged units with display

1 Version with temperature sensor

2 Version with temperature sensor and optional pressure sensor

2.5.2 Sandwich versions

Sandwich-type flowmeters have a centering ring to facilitate installation.

Fig. 3: FLOWIRL 8700, sandwich-type meters with display

1 Version with temperature sensor

2 Version with temperature sensor and optional pressure sensor

2/5

1 2

1 2

Page 9: FLOWIRL 8700(2)

2.5.3 Instrument description

Fig. 4: FLOWIRL 8700, description

1 VFC 700 converter

2 Cable gland, gray, standard design

3 Pressure sensor, optional

4 VFS 8000 sensor

5 Centering ring

2/6

5

Page 10: FLOWIRL 8700(2)

2.6 Nameplate

Important information!

Before installing the flowmeter, make sure that the information given on the nameplate

complies with the ordering data.

Fig. 5: FLOWIRL 8700 nameplate

1 Type of meter

2 Manufacturer

3 Connection data: nominal diameter and pressure rating

4 Electrical connection data

Sr. No. PowerSupply 12-36Vdc

Tag No. OutputSignal 4-20 mA

MeterSize Pulse Passive

Output 0-24 Vdc100 mA max

Temp.Range -20 to 240ºC Meter Body SS316LRange Pressure

Nom.

K Factor P/M3

FORBES MARSHALL, INDIA

FLOWIRL 8700 K(1)

(2)

(3) (4)

2/7

Page 11: FLOWIRL 8700(2)

Mechanical Installation

2.7 General installation information

Caution!

Installation, assembly, start-up and maintenance may only be performed by appropriately

trained personnel. The regional occupational health and safety directives and safety

regulations must be observed without exception.

The following procedures have to be carried out before installing the flowmeter!

• Check the packing and the flowmeter itself for any damage.

• Check the contents of the consignment for completeness.

• Compare your order specification with the scope of delivery.

2.8 Storage

• Store the flowmeter in a dry and dust-free location.

• Avoid lasting direct exposure to the sun.

• Store the flowmeter in its original packing.

• The admissible storage temperatures are -40 °C to +80 °C for standard meters.

2/8

Page 12: FLOWIRL 8700(2)

2.9 Transport

• Use carrying straps for transport and lay them around the two process connections. 1

• Flowmeters must not be lifted by the converter housing for transport. 2

• Never lift the flowmeter by the pressure sensor. 3

• Do not use chains as these could damage the housing.

Fig. 7: Transport instructions

Caution!

There is a risk of injury due to equipment that is not secured properly. The center of gravity of

the equipment is often higher than the lug for attaching the lifting belts.

During transport, prevent the flowmeter from unintentional slipping or turning.

2/9

Page 13: FLOWIRL 8700(2)

2.10 Installation requirements

Important information!

For accurate volumetric flow measurement the flowmeter has to have a completely filled pipe and a fully

developed flow profile.

Please comply with the instructions regarding inlet and outlet pipe runs and installation position.

In the case of vibrations on the piping choose the installation site in such a way that the

vibrations are at their lowest in transverse direction to the flowmeter.

Caution!

When installing the flowmeter in the piping please observe the following points:

• Nominal diameter of connection pipe flange = nominal diameter of the meter!

• Use flanges with smooth holes, e.g. welding neck flanges.

• Carefully align the holes of the connecting flange and the flowmeter flange.

• Check the compatibility of the gasket with the process product.

• Make sure that the gaskets are arranged concentrically. The flange gaskets must not project

into the pipe cross-section.

• The flanges have to be concentric.

• There must not be any pipe bends, valves, flaps or other internals in the immediate inlet run.

• Sandwich-type flowmeters may only be installed using a centering ring.

• Never install the flowmeter directly behind piston compressors or rotary piston meters.

• Do not lay signal cable directly next to cable for power supply.

2.10.1 General

• A sufficient distance around the flowmeter in all directions must be kept free to allow

servicing.

• Protect the flowmeter from direct exposure to the sun.

Fig. 8: General installation instructions

2/10

Page 14: FLOWIRL 8700(2)

2.10.2 Important installation instructions, liquid measurement

Fig. 9: Fundamental installation advice

1 Prohibited: Installing upstream of a run-out, as there is a risk of a partially filled pipe

2 Prohibited: Installing in a downpipe, risk of partially filled pipe

3 Prohibited: Installing in an upper pipe bend, risk of gas bubbles forming

4 Recommended: Installing in the bottom pipe bend

5 Recommended: If the meter is installed in a downpipe, it is absolutely essential to install a riser

pipe directly after it.

6 Recommended: Installing the flowmeter in a vertical riser pipe

7 Recommended: Installing the flowmeter in an inclined riser pipe

Caution!

Gas bubbles can cause cavitation leading to inaccurate measurement.

2/11

Page 15: FLOWIRL 8700(2)

2.10.3 Important installation instructions, vapor and gas measurement

Fig. 10: Fundamental installation advice

1 Prohibited: Installing the flowmeter in the lower pipe bend, risk of condensate formation

2 Recommended: Installing the flowmeter in the top pipe bend

Caution!

Condensate can lead to cavitation and inaccurate measurement.

2.10.4 Important installation instructions, piping with control valves

Important information!

To ensure trouble-free and accurate measurement, Forbes Marshall Pvt. Ltd. recommends not installing the

flowmeter behind a control valve. There is a risk of turbulence occurring that falsifies the

measuring result.

Fig. 11: Fundamental installation advice

1 Not recommended: Installing the flowmeter directly behind control valves

2 Recommended: Installing the flowmeter upstream of the control valve, distance DN 20

i

2/12

Page 16: FLOWIRL 8700(2)

2.10.5 Preferred installation location

Fig. 12: Preferred installation locations

1 Above a horizontal pipe

2 Below a horizontal pipe

3 On a vertical pipe

Note!

Depending on installation position you will have to turn round the display and/or the

connection housing.

2.10.6 Turning the display

Danger!

All work on the flowmeter electrics may only be carried out by appropriately trained

personnel. The regional occupational health and safety directives and safety regulations must

be observed without exception.

If the flowmeter is installed in a vertical pipe run, you will have to turn the display by 90°;

if installed below a pipe, turn 180°.

• Switch off the power supply to the flowmeter.

• Unscrew the cover in front of the display from the connection housing.

• Pull the display carefully a few centimeters out of the anchor fitting and turn it to the required

position.

• Press the display back onto the spacer pins, until it clicks firmly into place.

• Turn the cover with gasket back onto the housing and tighten it by hand.

i

2/13

Page 17: FLOWIRL 8700(2)

2.10.7 Turning the converter housing

Danger

All work on the flowmeter electrics may only be carried out by appropriately trained

personnel. The regional occupational health and safety directives and safety regulations must

be observed without exception.

Turning the converter housing

• Switch off the power supply to the flowmeter.

• Loosen the four screws on the underside of the connection housing.

• Lift the connection housing and turn it to the required position in 90° stages.

• Screw the connection housing back on tightly.

Fig. 13: Loosen screws

1 Allen screws on connection housing

Caution!

Do not damage the electrical cable by overtightening.

Do not undo the electrical plug connection.

1

2/14

1

Page 18: FLOWIRL 8700(2)

2.10.8 Insulation

Caution!

The area above the converter support must not be thermally insulated.

The thermal insulation 2 may only extend to the maximum height 1 shown below up to the

connecting screws of the sensor.

Fig. 14: Thermal insulation on connection piece

Caution!

The thermal insulation 1 may only extend as far as the bend in the pressure measurement piping 2.

Fig. 15: Thermal insulation on measurement piping

1 Insulation

2 Maximum height of insulation

2/15

(1)

(2)

Page 19: FLOWIRL 8700(2)

2.11 Inlet and outlet runs

2.11.1 Minimum inlet runs

Fig. 16: Minimum inlet runs

1 General inlet run without without flow disturbances atleast 20 DN

2 After a control valve > 50 DN

3 After a pipe diameter reduction > 20 DN

4 After a single 90° bend > 20 DN

5 After a double bend 2x90° > 30 DN

6 After a double three-dimensional 2x90° bend > 40 DN

DN is meter diameter

2/16

Page 20: FLOWIRL 8700(2)

2.11.2 Flow straightener

If, due to the type of installation, the required inlet runs are not available, FORBES MARSHALL PVT. LTD.

recommends using flow straighteners. Flow straighteners are installed

between two flanges in front of the flowmeter and shorten the required inlet run.

Fig. 17: Stilling well

1 Straight inlet run upstream of flow straighteners > 2DN

2 Flow straightener

3 Straight pipe section between flow straigtener and flowmeter > 8DN

4 Minimum straight outlet run 5DN

2.11.3 Minimum outlet runs

Fig. 18: Minimum outlet runs

1 General outlet run in front of pipe widening, pipe bends, control valves etc. > 5 DN

2 In front of metering points > 5 … 6 DN

Important information!

The interior of the pipe at the metering points must be free of burrs and other flow impediments.

The flowmeter has an internal temperature sensor. It must be located > 5 DN away from

extraneous temperature sensors. Use sensors that are as short as possible to avoid disturbing

the flow profile.

2/17

Page 21: FLOWIRL 8700(2)

2.12 Installation

2.12.1 General installation instructions

Caution!

Installation, assembly, start-up and maintenance may only be performed by appropriately

trained personnel. The regional occupational health and safety directives and safety

regulations must be observed without exception.

The following procedures have to be carried out before installing the flowmeter in the piping:

• Remove all transport locks and protective coverings from the flowmeter.

• Make sure that the gaskets have the same diameter as the piping.

• Make sure that the flowmeter is in the correct flow direction. This is indicated by an

arrow on the sensor housing.

Caution !

On metering points with varying thermal loads the flowmeters are to be mounted with stress

bolts (DIN 2509). Stress bolts and/or nuts and bolts are not included in the scope of delivery.

Make absolutely certain that the measuring flanges are sitting concentrically.

When preparing the metering point, keep in mind the exact installed length of the flowmeter.

The dimensions are given in Section 8 “Technical Data”.

Fig. 19: Preparing the metering point

1 Installed length of flowmeter + thickness of gaskets.

2/18

1

Page 22: FLOWIRL 8700(2)

Caution!

The inside diameters of the connection pipe flange, of the flowmeter and of the gaskets must

be the same! The gaskets must not project into the pipe cross-section.

Fig. 20: Preparing the metering point

1 Inside diameter connection pipe

2 Inside diameter flange and gasket

3 Inside diameter of meter

2/19

Page 23: FLOWIRL 8700(2)

2.12.2 Installing instruments in sandwich design

Fig. 21: Installation using centering ring

1 Sandwich design sensor

2 Centering ring

3 Bolts with fixing nuts

4 Hole A

5 Hole B

6 Gasket

Install the flowmeter as follows:

• Push the first bolt through hole 5 of both flanges.

• Screw on the nuts with washers at both ends of the bolt but do not tighten them.

• Mount the second bolt through the holes 4.

• Place the sensor between the two flanges.

• Insert the gaskets between sensor and flanges and align them.

• Check that the flanges are sitting concentrically.

• Install the remaining bolts, nuts and washers. But do not tighten the nuts yet.

• Turn the centering ring anti-clockwise and align the flowmeter.

• Check that the gaskets are concentric, they must not project into the pipe.

• Now tighten all nuts bit by bit alternately across the diagonal.

2/20

Page 24: FLOWIRL 8700(2)

2.12.3 Installing instruments in flange design

Fig. 22: Mounting flanged-type flowmeters

1 Flanged sensor

2 Bolts with fixing nuts

3 Gasket

Install the flowmeter as follows:

• Fix the flowmeter to one side of a flange using bolts and fixing nuts.

• Insert the gaskets between sensor and flange and align them.

• Check that the gaskets are concentric, they must not project into the pipe.

• Install the gasket, bolts and fixing nuts on the other flange side.

• Align the meter and the gaskets so that they are concentric.

• Now tighten all nuts bit by bit alternately across the diagonal.

2/21

Page 25: FLOWIRL 8700(2)

2.13 Start-up

• Check that the system has been correctly installed as described in Sections 2.

• Before the initial start-up check that the following details on the name plate agree with the data specified in the report of

settings for the signal converter. If not, reprogramming will be necessary. Refer to Convertor manual.Meter size Fct. 3.1.1K-Factor Fct. 3.1.2

• The flowmeter is ready for service in 15 minutes (waiting time) after switching on the power source. Increase the flow velocityslowly and steadily.

• Avoid abrupt changes in pressure in the pipeline.

• If the process product is steam, condensate may form initially and cause faulty measurements when the system isstarted up for the first time.

• When powered, the signal converter normally operates in the measurement mode. The power-on sequence to themeasurement mode is as follows:

‘TEST’ is displayed for approx. 3 seconds followed by ‘VORTEX FLOW CONVERTER’ the instrument type followed by ‘VerX.Y.Z’ the software version of the instrument.

Then the instrument operates in the measurement mode where it displays the parameter being measured.

2/22

Page 26: FLOWIRL 8700(2)

3. VORTEX FLOW METER

The Flowirl 8700 is a new generation state-of-the-art design signal convertor.

3.1 Basic Features

2-wire loop powered convertor 24 V DC supply (4-20 mA)

Temperature measurement as standard

Online density compensation and mass flow calculations for saturated steam or water

4-20 mA programmable current output

Pulse output programmable and scalable by user

Optional 16x64 dot matrix LCD display with 3 button keypad and magnetic pin programming

All measured and calculated parameters such as flow, temperature, mass flow, etc. are fully programmable.

Notch Filter Algorithm for predicting correct Vortex frequency for improved vibration and noise immunity

Power-on preamplifier diagnostics

User-friendly integer totalizer

Simple single level user-friendly menu

Compatible with all existing flow heads

Optional separated version available

HART compatible

3.2 Connection Diagram

Connection to loop power supply

In case of functional extra low voltages (24 V DC), protective separation in conformity with VDE 400 Part 410, or anequivalent national standard, must be ensured.

Ensure that the screw thread of the round cover on the terminal box is well greased at all times.

Connection to power - Flowirl 8700

3/1

-Pout

++24v

-I Loop

++ 24v

4

3

2

1

Page 27: FLOWIRL 8700(2)

Current and pulse outputs are galvanically isolated and can, therefore, be simultaneously connected to a receiver instrumentwhich is grounded or separately connected to two receiver instruments.

Ensure that the 24 V, 4-20 mA loop is grounded at one point only (i.e. either at the input of the signal convertor or at theinput of the indicator, or at the output of the power supply). Do not ground the loop at more than one point.

3.2.1 Current Output

The current output is galvanically isolated from the pulse output and sensors.

The maximum load at terms.

Max. load in RB = UB -- 12 V*

< 1200 Ω

3.2.2 Pulse Output

The pulse output is galvanically isolated

Pulse output is passive. The maximum frequency is 0.5 Hz only. The conversion factor can be set in Fct. 1.4.1Function P.

This is an open collector connection for active electronic counters EC or EMC, input voltage is 5-36V, max. load currentis 100 mA, and the max. collector power is 250 mW.

* 12 V should be present at terminal 1 & 2

20 mA

3/2

Page 28: FLOWIRL 8700(2)

4. Operation of the signal convertor

4.1 General

4.1.1 Starting up signal convertor

When the power is switched ON to the signal convertor, it displays “TEST”, VFC XXX and “Ver X.Y.Z” and then goes to the

measurement mode. In this initial sequence, carries out self diagnostics to check the preamplifier section, sensor integrity

and then loads the configuration data from the non-voIatile memory.The first measured parameter displayed is the one being

displayed when the power supply was switched off the last time. It is possible to enter the programming mode by pressing the

key.

4.1.2 Measurement Mode

In the measurement mode, the parameters that the convertor measures/computes are shown on the display in the appropriate

units. As per the configuration, the display can be either in the non-cyclic/cyclic mode. In the non-cyclic mode of display, use

key to see the next parameter or error message on the display. In the cyclic mode, the display shows all the parameters

one after another, wherein each parameter/ error message is displayed for about 6 seconds.

4.1.3 Error Handling

The convertor can detect errors during the power-on diagnostics as well as when in the normal measurement mode.

If one or more errors are present, the vertical bar in the top left corner of the display (in the measurement mode) starts

blinking. If enabled, the error information is shown on the display interleaved between the display of two parameters. The first

line displays the total number of errors and the second line displays the error message. Refer to the list of Error Messages.

4.1.4 Programming or menu mode

All the configuration/settings/test functions in the form of a menu function x.x.x are accessible in the programming mode.

The operator can view or alter the present settings, data values by the use of functions available in this mode.

All changes made in the programming mode are stored in the non-volatile memory after exiting the menu and have appropriate

effect on the operation of the signal convertor. While being programmed (i.e. while in the menu), the instrument will stop

making further measurements and the current output will be frozen to the last value, the pulse output will also stop.

4/1

Page 29: FLOWIRL 8700(2)

Error messages in the measurement mode

Error message (display second line)

Ty p e Description

NO SIGNAL

LOW FREQ

LOW FLOW

HIGH FREQ

HlGH FLOW

INV. CONFIG

Corrective action required

Actual flow rate

higher than q max.

Configuration data

in non-volatile memory

is not valid.

Check flow rate q min else call Krohne Marshall Service. >

Check flow rate < q max else call Krohne Marshall Service.

Corrective action depends on application process. If the flow

rate exceeds the max. value it may damage the sensor

physically .

Converter will continue to display actual flow rate. However,

accuracy of measurement may suffer.

Check entire configuration again. If error persists call Krohne

Marshall Service.

Flow rate lower

than minimum flow

rate q min.

Vortex frequency

too high

Vortex frequency

too low

No signal from

the vortex sensor

No flow through the primary or check for any other errors during.power-on diagnostics. If sensor problem, contact Krohne Marshall Service.

4/2

4.1.5 Error messages

AMP FAIL Pre-amplifier section has failed Contact Forbes Marshall Service.

CHECK INST Flow signal quality is bad Check that 1) Flow rate>q min if OK. 2) Check for

excessive pipe vibration and upstream flow disturbances.

LOW SIGNAL Vortex signal amplitude too Check that 1) Flow rate>q min if OK contact

l ow Forbes Marshall Service.

HIGH SIGNAL Vortex sensor signal This occurs in cases of high density medium.

amplitude too high Check 1) Flow rate < qmax, if OK contact Forbes Marshall Service.

LOW.TEMP.PHY. Operating temp. lower than Take corrective action depending on the process.

physical limit

HIGH.TEMP.PHY Operating temp. higher than Take corrective action immediately. Will cause damage to the

physical limit primary as well as to signal convertor!

T.SENS.SHORT Temp. sensor/wires short Indicates a fault in the temperature sensor.

circuit Contact Forbes Marshall Service.

T.SENS.OPEN Temp. sensor open circuit

Checked duringPower on

Forbes

Forbes

Forbes

Forbes

Page 30: FLOWIRL 8700(2)

4.1.6 Operating elements

Caution: To avoid damage to the electronics, be certain that the area around the meter is dry before removing the electronics

compartment cover.

The operating elements are accessible after removing the cover of the electronics section using the special wrench.

Caution: Do not damage the screw thread, never allow dirt to accumulate, and make sure it is well greased at all times.

Display, first line

Keys for programming the signal convertor, refer to section 5.1 for the functions of the keys.

Magnetic Hall Effect switches

4/3

FLOWIRL 8700

Page 31: FLOWIRL 8700(2)

5/1

l. All changes made in programing mode are stored in non volatile memory upon quitting menu.

2. VFC 095 stops measurement when in programming mode.

Important

3.2 Description of Keys

Displaying measuredparameters/errormessagesEnter programmingmode

Measuring mode level1 2

Select function Select function displayedEnter the function. Then continue as under datalevelReturn to sub-menulevel or main menu level after choosing YES/NOwith keyConfirm functionselected

Data level

Options

Stores edited value/string temporarily.Continue with further data entry, if any,or return to function level.

Numerical/alpha-numerical values

Scroll through option Change the

flashingdigit/character Change flashing (cursor) position

22

Select scroll position

5. Description of Keys

5.1 Menu structure

but holds the last measured output current.

2. Vortex Flow Converter stops measurement when inprogramming mode, but holds the last measured outputcurrent.

Page 32: FLOWIRL 8700(2)

5.2 Functionality of keys

The cursor position is indicated by an “inverse video” character.

To start operator control

Measuring mode Operator control mode

Please note when ‘Yes’ is set under the entry code of Fct.3.2.2 then on pressing the key will prompt you to enter the Entry

Code 1 which is fixed. Here, the software is modified in such a way that the key is taken as the first key out of the nine and

you have to enter the remaining eight keys in the sequence This will take you to the function level.

To go to the next function

1.

Pressing the key will result in scrolling through all the functions sequentially as given in the menu level chart. Here the right

most digit of the function goes on incrementing.

2.

Pressing the key when the middle digit is selected will result in an increment of that second LSB. Logically, the function

should go to Fct.1.2.1. However, Functions 1.2.1 up to 1.2.5 do no exist on the menu level chart. Hence, on pressing the key,

the function will go directly to Fct.1.2.6

3.

Here pressing the key results in incrementing the left most digit. Logically, the function should go to Fct.2.1.1. However,

since Fct.2.1.1 does not exist on the menu level chart, the function will go to the next function which is Fct.2.1.2

To select the function

To modify any menu, first make that function available on the display. Then press the key to confirm the function selected.

Next, press the key to enter that function. To scroll through the different options available, use the key. To select the

option chosen, press the key. You are then prompted with the CONT YES/NO. On selecting YES, you will proceed to the

next menu level. If you select NO, it will update the data you entered and will go to the measuring mode.

70.00

m3/hr

1.1.1

MEAS_INST.

1.1. 1 1.1.2

MEAS_INST. MAX_FLOW

1.1. 1 1.2. 6

MEAS_INST. ERROR_MSG.

1.1.1

MEAS_INST. I_TEST

5/2

2.1.2

Page 33: FLOWIRL 8700(2)

6. Program functions for various versions

6.1 Program Organization and Programming Chart for GAS Ver 7.X.Y.

6/1

Fct. 1.1.1 MEAS_INST

Fct. 1.1.2 M A X _ F L O W

Fct. 1.1.3 MIN_FLOW

Fct. 1.1.4 TIMECONST

Fct. 1.2.6 ERROR_MSG

Fct. 1.2.7 CYCLE_DISP

Fct. 1.3.2 RANGE-I

Fct. 1.4.1 FUNCTION_P

Fct. 2.1.2 T E S T _ I

Fct. 2.1.3 T E S T _ P

Fct. 3.1.1 NOM_DIA

Fct. 3.1.2 K_FACTOR

Fct. 3.2.2 CODE 1

Fct. 3.2.4 LOCATION

Fct. 3.2.5 TOT. VALUE

Fct. 3.2.6 TOT. ON/OFF

Fct. 3.27 POLL ADDRESS

Fct. 3.3.4 SET GAIN

Fct. 3.5.1 FLUID

Fct. 3.5.2 MEDIUM

Fct. 3.5.4 TEMP. OP.

Fct. 3.5.5 PRES. OP.

Fct. 3.5.6 DENS. OP.

Fct. 3.5.7 TEMP. NORM.

Fct. 3.5.8 PRES. NORM.

Fct. 3.5.9 DENS. NORM.

Fct. 3.5.10 % GAS. MIX

Fct. 3.5.11 % REL. HUM.

Fct. 3.6.1 T_SENSOR

Fct. 3.6.2 P_SENSOR

Fct. 3.7.1 P_EXCIT. V

Fct. 3.7.2 P_SEN. P1V1

Fct. 3.7.3 P_SEN. P2V2

Fct 3.7.4 EX.P. RANGE

Fct. 3.9.1 FAD UNIT

Fct. 3.9.2 SUCT. TEMP.

Fct. 3.9.3 ATM. PRESS .

Fct. 3.9.4 FIL. P. DROP

Fct. 3.9.5 INLET RH

Fct. 3.9.6 ACTUAL RPM

Fct. 3.9.7 RATED RPM

Fct. 3.9.8 OUTLET RH

ACTUAL DISPLAY

ACCESS

TO

SETTINGS

OR

DATA

POSSIBLE

AT

THIS

LEVEL

ONLY

MEASURING MODE LEVEL FUNCTION LEVEL DATA LEVEL

MenuLevels :-

Page 34: FLOWIRL 8700(2)

6.1.1 Program function description

The program functions are given in a numeric order as follows:

• Function number and title

• Description of the function

When you enter any numeric value in the floating point format, the accuracy of viewing any floating point value entered is +0.003% . The precision of the measured variable depends on the choice of precision (position of decimal point) while enteringthe operating value of that parameter.

Fct. 1.1.1 MEAS. INST. measuring instrument typeSet the instrument to measure the volumetric or thenormalized volumetric or the mass flow rate as per the options:

• VOLUME • NORM.VOLUME • MASS

Usually, this function is used once initially. If you need to change the basic measurement type later on, you should check/reprogram all the flow rate and the totalizer related functions such as -

• MAX.FLOW • MIN.FLOW • FLOW UNITS• TOTAL.UNITS • 4 mA FLOW • 20 mA FLOW• RANGE F • TOT. VALUE Fct. 1.1.2 MAX.FLOW maximum flow rate

Enter the maximum flow rate desired. The max. flow should be within the measuring range for the given primary data (3.1.xfunctions) and the application data (3.5.x functions).

The current output range (4-20 mA) corresponds to the 0% flow (Q0%) and the 100% flow (Q100%) respectively.

If the flow rate exceeds the MAX FLOW, an error HIGH FLOW is annunciated on the display with an error symbol flashing atthe top left corner.

The base units are m3/hr, nm3/hr and kg/hr respectively for Volume, Norm. Volume and Mass. For units other than thespecified units, replace the base unit with the user unit by changing the literal text. Also, enter the coefficient of that particularunit with respect to the basic unit depending on the measuring instrument type that you have selected.

Refer to the formula given:

User Unit *A1 coeff.+A0 offset = Base unit

Example: If the user unit is litre/hr

A1 coeff. = Base unit/ user unit = 1/1000 = 0.001

A0 offset = 0

Fct. 1.2.6 ERROR MSG. display of error messages Fct. 1.1.3 MIN. FLOW minimum flow rate

Enter the minimum flow rate in the same units as for the max.flow above. The min. flow should be within the measuring rangefor the given primary data (3.1.X functions) and the application data (3.5.X functions). If the flow is below the min. flow then anerror LOW FLOW is annunciated on the display with an error symbol flashing at the top left corner.

Note: This value cannot be zero for Vortex flowmeters. This value is normally set to the minimum flow rate (determined fromthe sizing) for the size of the primary used.

6/2

Page 35: FLOWIRL 8700(2)

Fct. 1.1.4 TIMECONST. time constant for flow rate

Enter a low-pass filter time constant in seconds to be applied to the flow rate. A value of zero indicates that the low-pass filteris not to be applied. With this function, it is possible to compromise between a steady indication (on the display/currentoutput) and the response time (to flow changes). It should normally be within 0-20 sec. The factory set value is 2 sec. Youmay increase it if you observe abnormal fluctuations on display.

Fct. 1.2.6 ERROR MSG. display of error messages

Choose YES so that the error messages appear between the display of parameters in the normal measuring mode, otherwiseselect NO.

Fct. 1.2.7 CYCLE DISP. cyclic/non-cyclic display

YES means the display will cycle automatically. This means a measured parameter is shown in the selected units for about6 seconds and then the next parameter in the display cycle is shown for 6 seconds and so on. NO (non-cyclic display) meansthe parameter is continuously shown on the display (to see other parameters or to change setting use the key). You maysee error messages in between the changeover from one parameter to next if error(s) are present and Fct. 1.2.6 ERRORMSG. is YES.

Fct. 1.3.2 RANGE I current output range selection

Here one selects one of the three possible range options. To set the current output as 4-20 mA with/without an errorindication on the current output. When a range with a suffix of 22E or 3.55E is selected then it means that the current outputwill give 22 mA or 3.55 mA error output if any error(s) are present in the instrument. The range options are listed below:

• 4-20

• 4-20/22E • 4-20/3.55E

Fct. 1.4.1 FUNCTION P Pulse output

Choose YES to make the pulse output active. NO makes the pulse output inactive (0 Hz).

Limits: The max. frequency of the pulse output is 0.5 Hz. To ensure that the pulse output does not exceed 0.5 Hz at max.flow, the coefficient in totalizer units can be adjusted. The pulse output will be an exact replica of the integer value of theinternal totalizer. If the flow rate exceeds in such a way that the pulse rate exceeds 0.5 Hz then the pulse output will be erratic.

For Example:

For a flow rate of 360 kg/hr, pulses will be 360 pulses/hr. as the pulse output is exact replica of integer totalizer. So the freq.of the pulses will be 0.1 Hz. This is within given limits. But for flowrate of 3600 kg/hr., pulses will be 3600 pulses/hr. The freq.becomes 1 Hz. This is not within the specified limits. In this case, A1 coeffecient should be adjusted in func. 3.2.5 Tot. value.This should be selected such that the freq. of the pulse o/p lies below .5 Hz. If this factor is selected as 0.1 then the frequencyof the pulse output will become 10 times less. i.e. 0.1 Hz. which lies in given limits. Please note that the same factor will getapplied to Integer totalizer also.

Fct. 2.1.2 TEST I current output test

Caution: During this test, the current output will change to the test values so appropriate actions should be taken dependingon how the current output is used.

• 4 mA • 8 mA • 12 mA

• 16 mA • 20 mA

Place the current meter in series with the current loop. Selecting any value given above will cause that current to flow so thatyou can check it on the meter. Select CONT. YES to test other current values or CONT.NO to end. When the menu functionfinishes, the normal current value depending on the flow rate and the programming of the current output function will berestored.

6/3

Page 36: FLOWIRL 8700(2)

Fct. 2.1.3 TEST P pulse output testCaution: When this test is initiated, the pulse output will run at the repetitive rate of 0.5003 Hz. So, appropriate actionsshould be taken depending on how the pulse output is used.

When the menu function finishes, the normal frequency value depending on the flow rate and the programming of thefrequency output functions will be restored.

Connect the electromechanical counter to the pulse output. (Refer to the connection diagram.) Select CONT.YES to test thefrequency value or CONT.NO to end. Selecting CONT.YES, will cause the pulse output to run at 0.5003 Hz.

Fct. 3.1.1 NOMINAL. DIA nominal diameter

Select which DIN/ANSI size primary is used with the instrument from the options listed below. The options available are:

• 10-20 • 25 • 40-50 • 80-200

The sizes under the group are as follows:

10-20 : DN10, ANSI 3/8”DN15, ANSI 1/2”DN20, ANSI 3/4”

25 : DN25, ANSI 1”

40-50 : DN40, ANSI 1.5”DN50, ANSI 2”

80-200 : DN80, ANSI 3”DN100, ANSI 4”DN150, ANSI 6”DN200, ANSI 8”

Fct. 3.1.2 K-FACTOR k-factor of the primary

Enter the primary constant k-factor value. This value is stamped on the instrument label in units of pulses/m3.

SIZE K-factorMin K-factor Max K-factor

DN 15/ANSI 1/2” 264932 314324DN 25/ANSI 1” 78394 93870DN 40/ANSI 1.5” 19841 22520DN 50/ANSI 2” 8652 9904DN 80/ANSI 3” 2660 3042DN 100/ANSI 4” 1169 1342DN 150/ANSI 6” 299 352

Fct. 3.2.2 ENTRY.CODE.1 entry code 1 password

Select YES if the password should be checked to access the menu. Use the 9-digit password to prevent configurationchanges by an unauthorized person. Answering NO means the password is not required to enter the menu. Refer to Section5.2

Fct. 3.2.4 LOCATION installation locationEnter an alphanumeric string up to 10 characters to describe the location of the installation. This input has no bearing on theperformance of the instrument in any way and it merely serves as a means of identification.

Fct. 3.2.5 TOT.VALUE totalizer valueHere the unit and coefficient of the totalizer can be set. This coeff can also be a scaling factor for the pulse output and thetotalizer value. The totalizer value can be preset using this function. The internal totalizer is an integer totalizer and has afixed roll-over value 4294967295.

6/4

Page 37: FLOWIRL 8700(2)

This function can also be used to reset the totalizer (to zero). The options available are:

• YES • NO

To reset totalizer: Select RESET YES as a double confirmation. To keep the totalizer unchanged select RESET NO.

Fct. 3.2.6 TOT. ON/OFF totalizer on/offSelect the option TOT. ON to start/restart the totalizer and select the option TOT. OFF to stop the totalizer. Stopping thetotalizer means the flow will not be accumulated till the time the totalizer is turned on again and the previous value will remainunchanged.

Fct. 3.2.7 POLL ADDRESSEnter Polling Address for HART Communications.

Fct. 3.3.4 SET GAIN Gain settingThe gain of the signal preamplifier can be changed to alter the sensitivity of the Vortex amplifier. The values available are:

• 1 • 1.5 • 2

• 3 • 6 • 11

• 16

The factory set value is 11 for gases.

Fct. 3.5.1 FLUID fluid type

Select whether the process medium is gas (including air), mixture of gases, wet gas

• GAS • GAS MIX • WET GAS

The operating density should be entered for GAS and Wet Gas, where the medium selected is none.

Fct. 3.5.2 MEDIUM process medium

Select the medium from the options given below. If the medium used is not included in the option list, select

-NONE-.For all the mediums except -NONE-, the instrument software calculates the density of the medium from P&Tconditions that is required for meter sizing, mass flow and normalized flow computations. However, for unsupported medium,the user has to supply the density at the operating P&T and the density at the normal P&T (latter for the normalized flowonly).Options for fluid GAS:

• AIR • AMMONIA • ARGON• I-BUTANE • N-BUTANE • CO• CO2 • ETHANE • ETHYLENE• HEXANE • HYDROGEN • H2S• METHANE • NEON • NITROGEN• OXYGEN • I-PENTANE • N-PENTANE• PROPANE • XENON • -NONE-

(CO is carbon monoxide, CO2 is carbon dioxide, -NONE- is none of the above)

Options for fluid WET GAS:• AIR • AMMONIA • ARGON• I-BUTANE • N-BUTANE • CO• CO2 • ETHANE • ETHYLENE• HEXANE • HYDROGEN • H2S• METHANE • NEON • NITROGEN• OXYGEN • I-PENTANE • N-PENTANE• PROPANE • XENON • -NONE-

6/5

Page 38: FLOWIRL 8700(2)

Fct. 3.5.4 TEMP. OPR operating temperature

Enter the mean (average) operating temperature of the medium. This parameter is very important since it is involved in thedensity calculation.

When the temperature sensor is not present, the value given here is used in flow computations for all mediums except NONE.The internal set unit for the temperature is DEG. C. To have some other unit, all the literal characters, coefficient and offsetmust be entered.

Example: User unit is Deg.F and base unit is Deg.C.

Referring to the formula given in Function 1.1.2,

Deg.C =0.55 Deg.F –17.77

Therefore, A1 coeff. = 0.55

A0 offset = -17.77

Fct. 3.5.5 PRES. OPR operating pressure

Enter the mean (average) operating pressure of the medium. This parameter is very important since it is involved in the densitycalculation.

The internal set unit for pressure is Pascal. Enter all the characters, coefficients, and offset to obtain other units desired.Refer to the example given in Fct.3.5.4.

Fct. 3.5.6 DENS. OPR. density at operating P&T

Enter the density of the medium at the operating pressure and temperature conditions. The basic unit is Kg/m3. Other unitscan be programmed using the coefficient in the conversion table.

Fct. 3.5.7 TEMP. NORM normal temperature

Enter the value for the normal/base/reference temperature.

This value is usually 00C or 200C. The unit options for this value are the same as in FCT. 3.5.4

Fct. 3.5.8 PRES. NORM normal pressure

Enter the value for the normal/base/reference pressure. This value is usually 1 atm. The unit options for this value are thesame as in Fct. 3.5.5

Fct. 3.5.9 DENS.NORM. density at normal P&T

Enter the density of the medium at normal pressure and temperature conditions. The basic unit is Kg/m3. Other units can beprogrammed using the coefficient in the conversion table.

Fct. 3.5.10 %GAS MIX %of gases

Select the components of the gas mixture. Enter the mole fraction percentage of gases present in the mixture of gases. Thelist of gases available is given below. For the components not present in the mixture, keep the percentages as zero. Thesum of the percentages of the gas components should be equal to 100 ± 0.1

List of gases for fluid GAS MIX:

• AMMONIA • ARGON • I-BUTANE• N-BUTANE • CO • CO2• ETHANE • ETHYLENE • HEXANE• HYDROGEN • H2S • METHANE• NEON • NITROGEN • OXYGEN• I-PENTANE • N-PENTANE • PROPANE• XENON

6/6

Page 39: FLOWIRL 8700(2)

Fct. 3.5.11 % REL HUM Relative humidity

Enter the relative humidity of the moist gas in the range of zero to hundred.

Fct. 3.6.1 T-SENSOR temperature sensor

Select YES if the temperature sensor is present elseselect NO.

Fct. 3.6.2 P-SENSOR pressure sensor

Here the selection of the internal, or external pressure sensor can be done. The options available are :

• EXTERNAL P• NONE• INTERNAL P

Fct. 3.7.1 P_EXCIT.V

Enter the excitation voltage given to the pressure sensor bridge. This is to make calibration data independent of electronics.

Fct. 3.7.2 P_SEN P1V1 calibration point 1

Enter the pressure value (in one of the units same as in Fct. 3.5.5) and the corresponding millivolt value.

Fct. 3.7.3 P_SEN P2V2 calibration point 2

Enter the pressure value (the same unit assumed as in Fct. 3.7.2) and the corresponding millivolt value.

Fct. 3.7.4 EX. P. RANGE external pressure sensor range.

Enter the external pressure sensor range for 4 mA & 20 mA. The default values are

• 0 AT 4 mA• 6 AT 20 mA

Fct. 3.9.1 FAD UNIT units for FAD

Select the unit for the display of the parameter FAD Volume flow. (FAD flow is vol. flow as calculated by meter at thesuction side of compressor).

• FAD M3/HR • FAD M3/MIN • FAD M3/SEC• FAD L/HR • FAD L/MIN • FAD L/SEC• FAD CUFT/H • FAD CUFT/M • FAD CUFT/S• FAD FT3/H • FAD FT3/M • FAD FT3/S• SPECIAL

Here the selection of the FAD Flow disply can be doneDisplay ON displays whichever unit is selected. OFF No FAD FLOW display

Fct. 3.9.2 SUCT. TEMP. Temp at suction side.

Enter the temperature at suction side.Fct. 3.9.3 ATM PRESS. atmospheric pressure.

Enter the atmospheric pressure.

Fct. 3.9.4 FIL. P. DROP Filter Pressure drop

Enter the value of the pressure drop across the filter at the inlet of the compressor. (If there is no such filter installed thenkeep this value as zero).

Fct. 3.9.5 INLET RH Relative humidity at suction

Enter the relative humidity at the suction side (i.e. ambient air). The units are %RH

6/7

Page 40: FLOWIRL 8700(2)

Fct. 3.9.6 ACTUAL RPM actual rpm

Enter the measured speed of the compressor motor in RPM.

Fct. 3.9.7 RATED RPM rated rpm

Enter the rated speed of the compressor motor in RPM.

Fct. 3.9.8 OUTLET RH relative humidity operating

Enter the relative humidity at the meter side (i.e. compressor outlet side). Typically this value is 100%. The units are %RH

6.1.2 VFC with FAD meter

An air compressor sucks in air from the atmosphere and delivers it compressed to the required pressure. Since the atmosphericair contains water vapor, what the compressor actually sucks in is a mixture of air and water vapour. Under thse conditions theFree Air Delivery specification of the compressor is not directly and easily known. Almost all manufacturers specify FAD atstandard suction conditions only. What the user gets to use as eventual plant air or process air needs to be found out and,hence, metered with ease and a reasonable accuracy of at least +1%.

VFM FAD-METER can measure FAD online, compensated for humidity and RPM apart from its use as STD FLOWMETER.The software built into the meter evaluates the FAD automatically online. The menu-driven user-friendly software prompts theuser for information like the pressure and relative humidity, design and actual RPM, and the discharge pressure. The steamtables and the compressibility data are programmed into the memory as a standard feature. The meter is also available withan optional pressure sensor which measures the discharge pressure online eliminating the need to feed in the value manually.

6/8

Page 41: FLOWIRL 8700(2)

6.2 Program Organization and Programming Chart for SAT/SUP STEAM Ver. 6.x.y

6/9

Fct. 1.1.1 M E A S _ I N S T

Fct. 1.1.2 M A X _ F L O W

Fct. 1.1.3 M I N _ F L O W

Fct. 1.1.4 T I M E C O N S T

Fct. 1.2.6 E R R O R _ M S G

Fct. 1.2.7 C Y C L E _ D I S P

Fct. 1.3.2 R A N G E - I

Fct. 1.3.5 VARIABLE I

Fct. 1.3.7 FS. POWER

Fct. 1.4.1 F U N C T I O N _ P

Fct. 1.4.4 VARIABLE P

Fct. 2.1.2 T E S T _ I

Fct. 2.1.3 T E S T _ P

Fct. 3.1.1 N O M _ D I A

Fct. 3.1.2 K _ F A C T O R

Fct. 3.2.2 CODE 1

Fct. 3.2.4 L O C AT I O N

Fct. 3.2.5 TOT. VALUE

Fct. 3.2.6 TOT. ON/OFF

Fct. 3.2.7 POLL ADDR

Fct. 3.3.4 SET GAIN

Fct. 3.5.1 F L U I D

Fct. 3.5.2 M E D I U M

Fct. 3.5.3 SAT. P/T

Fct. 3.5.4 TEMP. OP.

Fct. 3.5.5 PRES. OP.

Fct. 3.5.7 TEMP. NORM.

Fct. 3.5.8 PRES. NORM.

Fct. 3.6.1 T _ S E N S O R

Fct. 3.6.2 P _ S E N S O R

Fct. 3.7.1 P_EXCIT. V

Fct. 3.7.2 P_SEN. P1V1

Fct. 3.7.3 P_SEN. P2V2

Fct. 3.7.4 EXT.P. RNG

Fct. 3.8.5 DRY. FACT.

Fct. 3.8.6 POWER UNIT

Fct. 3.8.8 ENERGY. UNIT

Fct. 3.8.9 E. TOT. ON

ACTUAL DISPLAY

ACCESS

TO

SETTINGS

OR

DATA

POSSIBLE

AT

THIS

LEVEL

ONLY

MEASURING MODE LEVEL FUNCTION LEVEL DATA LEVEL

MenuLevels :-

Page 42: FLOWIRL 8700(2)

6.2.1 Program function description

The program functions are given in a numeric order as follows:• Function number and title• Description of the function

When you enter any numeric value in the floating point format, the accuracy of viewing any floating point value entered is +0.003% . The precision of the measured variable depends on the choice of precision (position of decimal point) while enteringthe operating value of that parameter.

Fct. 1.1.1 MEAS. INST. measuring instrument typeSet the instrument to measure the volumetric or thenormalized volumetric or the mass flow rate as per the options:

• VOLUME • NORM.VOLUME • MASS

Usually, this function is used once initially. If you need to change the basic measurement type later on, you should check/reprogram all the flow rate and the totalizer related functions such as -

• MAX.FLOW • MIN.FLOW • TOTAL.UNITS • RANGE P • TOT. VALUE

Fct. 1.1.2 MAX.FLOW maximum flow rate

Enter the maximum flow rate desired. The max. flow should be within the measuring range for the given primary data (3.1.xfunctions) and the application data (3.5.x functions).

The current output range (4-20 mA) corresponds to the 0% flow (Q0%) and the 100% flow (Q100%) respectively.

If the flow rate exceeds the MAX FLOW, an error HIGH FLOW is annunciated on the display with an error symbol flashing atthe top left corner.

The following units are available to choose from depending on the programming of Fct.1.1.1 MEAS. INST.

for volumetric flow:• M3/HR • M3/MIN • M3/SEC• LITRE/HR • LITRE/MIN • LITRE/SEC• CUFT/HR • CUFT/MIN • CUFT/SEC• FT3/HR • FT3/MIN • FT3/SEC• CFT/HR • CFT/MIN • CFT/SEC• US GAL/HR • US GAL/MIN • US GAL/SEC• UK GAL/HR • UK GAL/MIN • UK GAL/SEC• SPECIALfor normalized volumetric flow:• NM3/HR • NM3/MIN • NM3/SEC• NORM.L/HR • NORM.L/MIN • NORM.L/SEC• SFT3/HR • SFT3/MIN • SFT3/SEC• SCFT/HR • SCFT/MIN • SCFT/SEC• SPECIALfor mass flow:• KG/HR • KG/MIN • KG/SEC• T/HR • T/MIN • T/SEC• LB/HR • LB/MIN • LB/SEC• SPECIALThe base units are m3/hr, nm3/hr and kg/hr respectively for Volume, Norm. Volume and Mass. For units other than thespecified units, replace the base unit with the user unit by changing the literal text. Also, enter the coefficient of thatparticular unit with respect to the basic unit depending on the measuring instrument type that you have selected.

6/10

Page 43: FLOWIRL 8700(2)

Refer to the formula given:

User Unit *A1 coeff.+A0 offset = Base unit

Example: If the user unit is litre/hr

A1 coeff. = Base unit/ user unit = 1/1000 = 0.001

A0 offset = 0

Fct. 1.1.3 MIN. FLOW minimum flow rate

Enter the minimum flow rate in the same units as for the max.flow above. The min. flow should be within the measuring rangefor the given primary data (3.1.X functions) and the application data (3.5.X functions). If the flow is below the min. flow then anerror LOW FLOW is annunciated on the display with an error symbol flashing at the top left corner.

Note: This value cannot be zero for Vortex flowmeters. This value is normally set to the minimum flow rate (determined fromthe sizing) for the size of the primary used.

Fct. 1.1.4 TIMECONST. time constant for flow rate

Enter a low-pass filter time constant in seconds to be applied to the flow rate. A value of zero indicates that the low-pass filteris not to be applied. With this function, it is possible to compromise between a steady indication (on the display/currentoutput) and the response time (to flow changes). It should normally be within 0-20 sec. The factory set value is 2 sec. Youmay increase it if you observe abnormal fluctuations on display.

Fct. 1.2.6 ERROR MSG. display of error messages

Choose YES so that the error messages appear between the display of parameters in the normal measuring mode, otherwiseselect NO.

Fct. 1.2.7 CYCLE DISP. cyclic/non-cyclic display

YES means the display will cycle automatically. This means a measured parameter is shown in the selected units for about6 seconds and then the next parameter in the display cycle is shown for 6 seconds and so on. NO (non-cyclic display) meansthe parameter is continuously shown on the display (to see other parameters or to change setting use the key). You may seeerror messages in between the changeover from one parameter to next if error(s) are present and Fct. 1.2.6 ERROR MSG. isYES.

Fct. 1.3.2 RANGE I current output range selection

Here one selects one of the three possible range options. To set the current output as 4-20 mA with/without an errorindication on the current output. When a range with a suffix of 22E or 3.55E is selected then it means that the current outputwill give 22 mA or 3.55 mA error output if any error(s) are present in the instrument. The range options are listed below:• 4-20• 4-20/22E • 4-20/3.55E

Fct. 1.3.5 VARIABLE I Current Output selection function

Selects any one of the two options available for the current output.

Options are listed below:

• FLOW• POWER

APPEARS: If the meter type is GROSS HEAT METER

Fct. 1.3.7 FS POWER

Enter the power value at which you want the current output at its maximum 20 mA

APPEARS: If the meter type is GROSS HEAT METER

6/11

Page 44: FLOWIRL 8700(2)

Fct. 1.4.1 FUNCTION P Pulse output

Choose YES to make the pulse output active. NO makes the pulse output inactive (0 Hz).Limits: The max. frequency of the pulse output is 0.5 Hz. To ensure that the pulse output does not exceed 0.5 Hz at max.flow, the coefficient in totalizer units can be adjusted. The pulse output will be an exact replica of the integer value of theinternal totalizer. If the flow rate exceeds in such a way that the pulse rate exceeds 0.5 Hz then the pulse output will be erratic.

For Example:For a flow rate of 360 kg/hr, pulses will be 360 pulses/hr. as the pulse output is exact replica of integer totalizer. So the freq.of the pulses will be 0.1 Hz. This is within given limits. But for flowrate of 3600 kg/hr., pulses will be 3600 pulses/hr. The freq.becomes 1 Hz. This is not within the specified limits. In this case, A1 coeffecient should be adjusted in func. 3.2.5 Tot. value.This should be selected such that the freq. of the pulse o/p lies below .5 Hz. If this factor is selected as 0.1 then the frequencyof the pulse output will become 10 times less. i.e. 0.1 Hz. which lies in given limits. Please note that the same factor will getapplied to Integer totalizer also.

Fct. 1.4.4 VARIABLE P pulse output selection function.Selects any one of the two options available for the pulse output

The options are listed below:

• FLOW• POWERAPPEARS: If the meter type is GROSS HEAT METER

Fct. 2.1.2 TEST I current output test

Caution: During this test, the current output will change to the test values so appropriate actions should be taken dependingon how the current output is used.

• 4 mA • 8 mA • 12 mA

• 16 mA • 20 mA

Place the current meter in series with the current loop. Selecting any value given above will cause that current to flow so thatyou can check it on the meter. Select CONT. YES to test other current values or CONT.NO to end. When the menu functionfinishes, the normal current value depending on the flow rate and the programming of the current output function will berestored.

Fct. 2.1.3 TEST P pulse output test

Caution: When this test is initiated, the pulse output will run at the repetitive rate of 0.5003 Hz. So, appropriate actionsshould be taken depending on how the pulse output is used.When the menu function finishes, the normal frequency value depending on the flow rate and the programming of thefrequency output functions will be restored.

Connect the electromechanical counter to the pulse output. (Refer to the connection diagram.) Select CONT.YES to test thefrequency value or CONT.NO to end. Selecting CONT.YES, will cause the pulse output to run at 0.5003 Hz.

Fct. 3.1.1 NOMINAL.DIA nominal diameter

Select which DIN/ANSI size primary is used with the instrument from the options listed below. The options available are:

• 10-20 • 25 • 40-50 • 80-200

The sizes under the group are as follows:

10-20 : DN10, ANSI 3/8”DN15, ANSI 1/2”

6/12

Page 45: FLOWIRL 8700(2)

DN20, ANSI 3/4”25 : DN25, ANSI 1”40-50 : DN40, ANSI 1.5”

DN50, ANSI 2”80-200 : DN80, ANSI 3”

DN100, ANSI 4”DN150, ANSI 6”DN200, ANSI 8”

Fct. 3.1.2 K-FACTOR k-factor of the primary

Enter the primary constant k-factor value. This value is stamped on the instrument label in units of pulses/m3.

SIZE K-factorMin K-factor Max K-factor

DN 15/ANSI 1/2” 264932 314324DN 25/ANSI 1” 78394 93870DN 40/ANSI 1.5” 19841 22520DN 50/ANSI 2” 8652 9904DN 80/ANSI 3” 2660 3042DN 100/ANSI 4” 1169 1342DN 150/ANSI 6” 299 352

Fct. 3.2.2 ENTRY.CODE.1 entry code 1 password

Select YES if the password should be checked to access the menu. Use the 9-digit password to prevent configurationchanges by an unauthorized person. Answering NO means the password is not required to enter the menu. Refer to Section5.2

Fct. 3.2.4 LOCATION installation location

Enter an alphanumeric string up to 10 characters to describe the location of the installation. This input has no bearing on theperformance of the instrument in any way and it merely serves as a means of identification.

Fct. 3.2.5 TOT.VALUE totalizer value

Here the unit and coefficient of the totalizer can be set. This coeff can also be a scaling factor for the pulse output and thetotalizer value. The totalizer value can be preset using this function. The internal totalizer is an integer totalizer and has afixed roll-over value 4294967295.This function can also be used to reset the totalizer (to zero). The options available are:

• YES • NO

To reset totalizer: Select RESET YES as a double confirmation. To keep the totalizer unchanged select RESET NO.

Fct. 3.2.6 TOT. ON/OFF totalizer on/off

Select the option TOT. ON to start/restart the totalizer and select the option TOT. OFF to stop the totalizer. Stopping thetotalizer means the flow will not be accumulated till the time the totalizer is turned on again and the previous value will remainunchanged.

Fct. 3.2.7 POLL ADDR polling address

Enter the polling address from 0 to 15. This is basically required for HART communication is multidropping mode.

Fct. 3.3.4 SET GAIN Gain setting

The gain of the signal preamplifier can be changed to alter the sensitivity of the Vortex amplifier. The values available are:

• 1 • 1.5 • 2

• 3 • 6 • 11

• 16

The factory set value is 11 for gases.

6/13

Page 46: FLOWIRL 8700(2)

Fct. 3.5.1 FLUID fluid type

The only option available is STEAM.

• STEAM

Fct. 3.5.2 MEDIUM process medium

Select the medium from the options given below. For all the mediums, the instrument software calculates the density of themedium from P&T conditions that is required for meter sizing, mass flow and normalized flow computations.

Options available are

• SAT STEAM • SUP STEAM

Fct. 3.5.3 SAT. P/T, use saturation P or T

For saturated steam, only one of the operating temperature or pressure is needed for density calculation. Select whether youare going to specify the saturation temperature or the pressure from the following options:

• SAT. TEMP • SAT.PRES

The actual value of the temperature or the pressure is to be entered under Fct. 3.5.4 TEMP. OPR or Fct. 3.5.5 PRES.OPR.

Fct. 3.5.4 TEMP. OPR operating temperature

Enter the mean (average) operating temperature of the medium. This parameter is very important since it is involved in thedensity calculation.

The option available for units are.

TMEP UNITS

• DEG C • DEG F • KELVIN• SPECIAL

When the temperature sensor is not present, the value given here is used in flow computations for all mediums except NONE.The internal set unit for the temperature is DEG. C. To have some other unit, all the literal characters, coefficient and offsetmust be entered.

Example: User unit is Deg.F and base unit is Deg.C.

Referring to the formula given in Function 1.1.2,

Deg.C =0.55 Deg.F –17.77

Therefore, A1 coeff. = 0.55

A0 offset = -17.77

Here the selection of the Temperature Display can be done. The options are:

DISP ON displays whichever unit is selectedOFF No Temperature Display

Fct. 3.5.5 PRES. OPR operating pressure

Enter the mean (average) operating pressure of the medium. This parameter is very important since it is involved in thedensity calculation.

6/14

Page 47: FLOWIRL 8700(2)

The units available are :

• KG/CM2 G • KG/CM2 ABS

• IN HG G • IN HG ABS

• MM HG G • MM HG ABS

• MM WATER G • MM WAT. ABS

• PA G • PA ABS

• KPA G • KPA ABS

• ATM G • ATM ABS

• BAR G • BAR ABS

• MILLI BARG • MILLI BARA

• PSI G • PSI ABS

• LBF/FT2 G • LBF/FT2 A

• SPECIALThe internal set unit for pressure is Pascal. Enter all the characters, coefficients, and offset to obtain other units desired.Refer to the example given in Fct.3.5.4.

Here the selection of the Pressure Display can be done. The options are:

DISP ON displays whichever unit is selectedOFF No Pressure Display

Fct. 3.5.7 TEMP. NORM normal temperature

Enter the value for the normal/base/reference temperature.

This value is usually 00C or 200C. The unit options for this value are the same as in FCT. 3.5.4

Fct. 3.5.8 PRES. NORM normal pressure

Enter the value for the normal/base/reference pressure. This value is usually 1 atm. The unit options for this value are thesame as in Fct. 3.5.5

Fct. 3.6.1 T-SENSOR temperature sensor

Select YES if the temperature sensor is present elseselect NO.

Fct. 3.6.2 P-SENSOR pressure sensor

Select any of the the three option.

• INTERNAL • EXTERNAL • NONE

Fct. 3.7.1 P_EXCIT.V

Enter the excitation voltage given to the pressure sensor bridge. This is to make calibration data independent of electronics.

Fct. 3.7.2 P_SEN P1V1 calibration point 1

Enter the pressure value (in one of the units same as in Fct. 3.5.5) and the corresponding millivolt value.

Fct. 3.7.3 P_SEN P2V2 calibration point 2

Enter the pressure value (the same unit assumed as in Fct. 3.7.2) and the corresponding millivolt value.

Fct. 3.7.4 EXT. P. RNG external pressure sensor range

Enter the external pressure range for 4 mA & 20 mA

Fct. 3.8.5 DRY. FACT dryness factorEnter the dryness factors for saturated steam. It is in the limits 0.85 to 1.0

6/15

Page 48: FLOWIRL 8700(2)

Fct. 3.8.6 PWR UNITS thermal power units.

Thermal power can be displayed in any one of the following units:

• KJ/hr • MJ/hr • GJ/hr• MW • BTU/hr • kCal/hr• KW• SPECIAL

APPEARS: If the meter is GROSS HEAT METER

Here the selection of the Thermal Power Display can be done. The options are :

DISP ON displays whichever unit is selected

OFF No Thermal Power Display

Fct. 3.8.8 ENERGY UNITS thermal energy units.

Thermal energy can be displayed in any one of the following units:

• KJ • MJ • GJ• BTU • kCal • KWH• MWH • SPECIAL

APPEARS: If the meter type is GROSS HEAT METER

Here the selection of the Thermal Energy Display can be done. The options are :

DISP ON displays whichever unit is selected

OFF No Thermal Energy Display

Fct. 3.8.9 E.TOT.ON energy totalizer on/off

Select the option TOT.ON/OFF to start/restart the totalizer and select TOT.OFF to stop the totalizer, This means the powerwill not be accumulated till the time the totalizer is turned on again.

APPEARS: If the meter is GROSS HEAT METER

6/16

Page 49: FLOWIRL 8700(2)

6/17

6.2.2 Heat Meter

Forbes Marshall, support thermal power and energy calculations for steam and water. Thermal power is calculated onlinefrom the mass flow and the specific enthalpy at the operating P&T and the thermal energy is calculated by time integrating(totalizing) thermal power. As energy totalizer is provided to accumulate the thermal energy.

The thermal power can be displayed in one of the following units.

KJ/hr, MJ/hr, GJ/hr, BTU/hr, kCal/hr, KW and MW

The corresponding units for the energy display are : KJ, MJ, GJ, BTU, kCal, KWh and MWh

Page 50: FLOWIRL 8700(2)

6.3 Program Organization and Programming Chart for COMPENSATED LIQUID

ver 4.x.y.

6/18

Fct. 1.1.1 MEAS_INST

Fct. 1.1.2 MAX_FLOW

Fct. 1.1.3 MIN_FLOW

Fct. 1.1.4 TIMECONST

Fct. 1.2.6 ERROR_MSG

Fct. 1.2.7 CYCLE_DISP

Fct. 1.3.2 RANxGE-I

Fct. 1.3.5. VARIABLE I

Fct. 1.3.7 FS.N. POWER

Fct. 1.4.1 FUNCTION_P

Fct. 1.4.4 VARIABLE P

Fct. 2.1.2 TEST_I

Fct. 2.1.3 TEST_P

Fct. 3.1.1 NOM_DIA

Fct. 3.1.2 K_FACTOR

Fct. 3.2.2 CODE 1

Fct. 3.2.4 LOCATION

Fct. 3.2.5 TOT. VALUE

Fct. 3.2.6 TOT. ON/OFF

Fct. 3.2.7 POLL ADDR

Fct. 3.3.4 SET GAIN

Fct. 3.5.1 FLUID

Fct. 3.5.2 MEDIUM

Fct. 3.5.4 TEMP. OP.

Fct. 3.5.6 DENS. OP.

Fct. 3.6.1 T_SENSOR

Fct. 3.8.6 N.PWR. UNIT

Fct. 3.8.8. N. EN. UNIT

Fct. 3.8.9 NE. TOT. ON

Fct. 3.8.11 EXT. T. RANGE

Fct. 3.8.14 HIGHER T

Fct. 3.8.15 NULL TEMP

ACTUAL DISPLAY

ACCESS

TO

SETTINGS

OR

DATA

POSSIBLE

AT

THIS

LEVEL

ONLY

MEASURING MODE LEVEL FUNCTION LEVEL DATA LEVEL

Menu

Levels :-

Page 51: FLOWIRL 8700(2)

6.3.1 Program function description

The program functions are given in a numeric order as follows:

• Function number and title

• Description of the function

When you enter any numeric value in the floating point format, the accuracy of viewing any floating point value entered is +0.003% . The precision of the measured variable depends on the choice of precision (position of decimal point) while enteringthe operating value of that parameter.

Fct. 1.1.1 MEAS. INST. measuring instrument typeSet the instrument to measure the volumetric or the mass flow rate as per the options:

• VOLUME • MASS

Usually, this function is used once initially. If you need to change the basic measurement type later on, you should check/reprogram all the flow rate and the totalizer related functions such as -

• MAX.FLOW • MIN.FLOW • FLOW UNITS• TOTAL.UNITS • TOT. VALUE

Fct. 1.1.2 MAX.FLOW maximum flow rate

Enter the maximum flow rate desired. The max. flow should be within the measuring range for the given primary data (3.1.xfunctions) and the application data (3.5.x functions).

The current output range (4-20 mA) corresponds to the 0% flow (Q0%) and the 100% flow (Q100%) respectively.

If the flow rate exceeds the MAX FLOW, an error HIGH FLOW is annunciated on the display with an error symbol flashing atthe top left corner.

The following units are available to choose from depend on the programming in fun 1.1.1

FOR VOLUMETRIC FLOW

• M3/HR • M3/MIN • M3/SEC• LITRE/HR • LITRE/MIN • LITRE/SEC• CUFT/HR • CUFT/MIN • CUFT/SEC• FT3/HR • FT3/MIN • FT3/SEC• CFT/HR • CFT/MIN • CFT/SEC• US GAL/HR • US GAL/MIN • US GAL/SEC• UK GAL/HR • UK GAL/MIN • UK GAL/SEC• SPECIAL

FOR MASS FLOW

• KG/HR • KG/MIN • KG/SEC• T/HR • T/MIN • T/SEC• LB/HR • LB/MIN • LB/SEC• SPECIALFor units other than the specified units, select unit “SPECIAL”, replace the base unit with the user unit by changing the literaltext. Also, enter the coefficient of that particular unit with respect to the basic unit depending on the measuring instrumenttype that you have selected.

Refer to the formula given:

User Unit *A1 coeff.+A0 offset = Base unit

Example: If the user unit is litre/hr

A1 coeff. = Base unit/ user unit = 1/1000 = 0.001

A0 offset = 0

6/19

Page 52: FLOWIRL 8700(2)

In this function only the flow display unit can be selected. The options available are.

• Unit displays the unit selected

• % Max Flow displays the % flow.

Fct. 1.1.3 MIN. FLOW minimum flow rate

Enter the minimum flow rate in the same units as for the max.flow above. The min. flow should be within the measuring rangefor the given primary data (3.1.X functions) and the application data (3.5.X functions). If the flow is below the min. flow then anerror LOW FLOW is annunciated on the display with an error symbol flashing at the top left corner.

Note: This value cannot be zero for Vortex flowmeters. This value is normally set to the minimum flow rate (determined fromthe sizing) for the size of the primary used.

Fct. 1.1.4 TIMECONST. time constant for flow rate

Enter a low-pass filter time constant in seconds to be applied to the flow rate. A value of zero indicates that the low-pass filteris not to be applied. With this function, it is possible to compromise between a steady indication (on the display/currentoutput) and the response time (to flow changes). It should normally be within 0-20 sec. The factory set value is 2 sec. Youmay increase it if you observe abnormal fluctuations on display.

Fct. 1.2.6 ERROR MSG. display of error messages

Choose YES so that the error messages appear between the display of parameters in the normal measuring mode, otherwiseselect NO.

Fct. 1.2.7 CYCLE DISP. cyclic/non-cyclic display

YES means the display will cycle automatically. This means a measured parameter is shown in the selected units for about6 seconds and then the next parameter in the display cycle is shown for 6 seconds and so on. NO (non-cyclic display) meansthe parameter is continuously shown on the display (to see other parameters or to change setting use the key). You may seeerror messages in between the changeover from one parameter to next if error(s) are present and Fct. 1.2.6 ERROR MSG.is YES.

Fct. 1.3.2 RANGE I current output range selection

Here one selects one of the three possible range options. To set the current output as 0-20 mA or 4-20 mA with/without anerror indication on the current output. When a range with a suffix of 22E or 3.55E is selected then it means that the currentoutput will give 22 mA or 3.55 mA error output if any error(s) are present in the instrument. The range options are listedbelow:• 4-20 • 4-20/22E • 4-20/3.55E

Fct. 1.3.5 VARIABLE I Current Output selection function

Selects any one of the two options available for the current output.

Options are listed below:

• FLOW• NET POWER

APPEARS: If the meter type is NET HEAT METER.

Fct. 1.3.7 FS.N.PWR

Enter the power value at which you want the current output at its maximum 20 mA.

APPEARS: If the meter type is NET HEAT METER &

6/20

Page 53: FLOWIRL 8700(2)

fct 1.3.5. VARIABLE I is NET POWER.

Fct. 1.4.1 FUNCTION P Pulse outputChoose YES to make the pulse output active. NO makes the pulse output inactive (0 Hz).

Limits: The max. frequency of the pulse output is 0.5 Hz. To ensure that the pulse output does not exceed 0.5 Hz at max.flow, the coefficient in totalizer units can be adjusted. The pulse output will be an exact replica of the integer value of theinternal totalizer. If the flow rate exceeds in such a way that the pulse rate exceeds 0.5 Hz then the pulse output will beerratic.

For Example:

For a flow rate of 360 kg/hr, pulses will be 360 pulses/hr. as the pulse output is exact replica of integer totalizer. So the freq.of the pulses will be 0.1 Hz. This is within given limits. But for flowrate of 3600 kg/hr., pulses will be 3600 pulses/hr. The freq.becomes 1 Hz. This is not within the specified limits. In this case, A1 coeffecient should be adjusted in func. 3.2.5 Tot. value.This should be selected such that the freq. of the pulse o/p lies below .5 Hz. If this factor is selected as 0.1 then thefrequency of the pulse output will become 10 times less. i.e. 0.1 Hz. which lies in given limits. Please note that the samefactor will get applied to Integer totalizer also.

Fct. 1.4.4 VARIABLE PAssign pulse output to either of following options

• FLOW • NET ENERGYFct. 2.1.2 TEST I current output test

Caution: During this test, the current output will change to the test values so appropriate actions should be takendepending on how the current output is used.

• 4 mA • 8 mA • 12 mA

• 16 mA • 20 mA

Place the current meter in series with the current loop. Selecting any value given above will cause that current to flow so thatyou can check it on the meter. Select CONT. YES to test other current values or CONT.NO to end. When the menu functionfinishes, the normal current value depending on the flow rate and the programming of the current output function will berestored.

Fct. 2.1.3 TEST P pulse output test

Caution: When this test is initiated, the pulse output will run at the repetitive rate of 0.5003 Hz. So, appropriate actionsshould be taken depending on how the pulse output is used.

When the menu function finishes, the normal frequency value depending on the flow rate and the programming of thefrequency output functions will be restored.

Connect the electromechanical counter to the pulse output. (Refer to the connection diagram.) Select CONT.YES to test thefrequency value or CONT.NO to end. Selecting CONT.YES, will cause the pulse output to run at 0.5003 Hz.

Fct. 3.1.1 NOMINAL.DIA nominal diameter

Select which DIN/ANSI size primary is used with the instrument from the options listed below. The options available are:

• 10-20 • 25 • 40-50 • 80-200The sizes under the group are as follows:

10-20 : DN10, ANSI 3/8”DN15, ANSI 1/2”DN20, ANSI 3/4”

25 : DN25, ANSI 1”

40-50 : DN40, ANSI 1.5”DN50, ANSI 2”

80-200 : DN80, ANSI 3”DN100, ANSI 4”DN150, ANSI 6”DN200, ANSI 8”

6/21

Page 54: FLOWIRL 8700(2)

Fct. 3.1.2 K-FACTOR k-factor of the primary

Enter the primary constant k-factor value. This value is stamped on the instrument label in units of pulses/m3.

SIZE K-factorMin K-factor Max K-factor

DN 15/ANSI 1/2” 264932 314324DN 25/ANSI 1” 78394 93870DN 40/ANSI 1.5” 19841 22520DN 50/ANSI 2” 8652 9904DN 80/ANSI 3” 2660 3042DN 100/ANSI 4” 1169 1342DN 150/ANSI 6” 299 352

Fct. 3.2.2 ENTRY.CODE.1 entry code 1 password

Select YES if the password should be checked to access the menu. Use the 9-digit password to prevent configurationchanges by an unauthorized person. Answering NO means the password is not required to enter the menu. Refer to Section5.2

Fct. 3.2.4 LOCATION installation location

Enter an alphanumeric string up to 10 characters to describe the location of the installation. This input has no bearing on theperformance of the instrument in any way and it merely serves as a means of identification.

Fct. 3.2.5 TOT.VALUE totalizer value

Here the unit and coefficient of the totalizer can be set. This coeff can also be a scaling factor for the pulse output and thetotalizer value. The totalizer value can be preset using this function. The internal totalizer is an integer totalizer and has afixed roll-over value 4294967295.

The units available are

• M3• LITRE• FT3 • CFT• CUFT • US GAL• UK GAL • SPECIALThis function can also be used to reset the totalizer (to zero). The options available are:

• YES • NO

To reset totalizer: Select RESET YES as a double confirmation. To keep the totalizer unchanged select RESET NO.

Here the selection of the Totalizer Display can be done. The options are :

DISP ON displays whichever unit is selected

OFF No Totalizer Display

Fct. 3.2.6 TOT. ON/OFF totalizer on/off

Select the option TOT. ON to start/restart the totalizer and select the option TOT. OFF to stop the totalizer. Stopping thetotalizer means the flow will not be accumulated till the time the totalizer is turned on again and the previous value will remainunchanged.

6/22

Page 55: FLOWIRL 8700(2)

Fct. 3.2.7 POLL ADDR polling address

Enter the polling address from 0 to 15. This is basically required for HART communication in multidropping mode.

Fct. 3.3.4 SET GAIN Gain setting

The gain of the signal preamplifier can be changed to alter the sensitivity of the Vortex amplifier. The values available are:

• 1 • 1.5 • 2

• 3 • 6 • 11

• 16

The factory set value is 3 for Liquids.

Fct. 3.5.1 FLUID fluid type

Select fluid type which is always LIQUID in this case.

• LIQUID

The operating density should be entered for LIQUID and where the medium selected is NONE.

Fct. 3.5.2 MEDIUM process medium

Select the medium from the options given below. If the medium used is not included in the option list, select -NONE-.Forall the mediums except -NONE-, the instrument software calculates the density of the medium from conditions that isrequired for meter sizing, mass flow computations. However, for unsupported medium, the user has to supply the density atthe operating P&T and the density at the normal P&T

Options for fluid LIQUID:

• WATER • NONE

Fct. 3.5.4 TEMP. OPR operating temperature

Enter the mean (average) operating temperature of the medium. This parameter is very important since it is involved in thedensity calculation.

When the temperature sensor is not present, the value given here is used in flow computations for all mediums except NONE.The option available for units are.

TEMP UNITS

• DEG C • DEG F • KELVIN

• SPECIAL

To have some SPECIAL unit other than listed, all the literal characters, coefficient and offset must be entered.

Example: User unit is Deg.F and base unit is Deg.C.

Referring to the formula given in Function 1.1.2,

Deg.C =0.55 Deg.F –17.77

Therefore, A1 coeff. = 0.55

A0 offset = -17.77

Here the selection of the Temperature Display can be done. The options are :

DISP ON displays whichever unit is selected

OFF No Temeperature Display

6/23

Page 56: FLOWIRL 8700(2)

Fct. 3.5.6 DENS. OPR. density at operating P&T

Enter the density of the medium at the operating pressure and temperature conditions. The units available are:

• KG/M3 • KG/LITRE

• LB/FT3 • LB/CFT

• SP. GR. WAT • SPECIAL

Fct. 3.6.1 T-SENSOR temperature sensor

Select YES if the temperature sensor is present elseselect NO.

Fct. 3.8.6 PWR UNITS Net thermal power units.

Thermal power can be displayed in any one of the following units:

• KJ/hr • MJ/hr • GJ/hr• MW • BTU/hr • kCal/hr• KW • TR• SPECIAL

APPEARS: If the meter is NET HEAT METER

Here the selection of the Thermal Power Display can be done. The options are :

DISP ON displays whichever unit is selected

OFF No Thermal Power Display

Fct. 3.8.8 EN UNITS Net thermal energy units.

Thermal energy can be displayed in any one of the following units:

• KJ • MJ • GJ• BTU • kCal • KWH• MWH • SPECIAL

APPEARS: If the meter type is NET HEAT METER

Here the selection of the Thermal Energy Display can be done. The options are :

DISP ON displays whichever unit is selected

OFF No Thermal Energy Display

Fct. 3.8.9 NE.TOT.ON/OFF Net energy totalizer on/off

Select the option TOT.ON/OFF to start/restart the totalizer and select TOT.OFF to stop the totalizer, This means the netpower will not be accumulated till the time the totalizer is turned on again.

APPEARS: If the meter is NET HEAT METER

Fct. 3.8.11 EXT. T. RANGE External temperature full scale value

This function is used to enter the Range value of the external temperature sensor. Enter values of external temp at 4 mA & 20mA.

APPEARS: If the meter type is NET HEAT METER.

Here the selection of the External Temperature Display can be done. The options are :

DISP ON displays whichever unit is selected

OFF No External Temperature Display

6/25

Page 57: FLOWIRL 8700(2)

Fct. 3.8.14 HIGHER T Select Process

The function is used to select the process. Options available are:

• T1>T2• T2>T1• NO CHOICE

APPEARS: If the meter type is NET HEAT METER

Fct. 3.8.15 NULL TEMP.

This function is used to null the difference between the temperature sensors, T1 and T2, in the plant when the plant is notrunning. This eliminates the error in the calculation due to an offset in the same temperature reading if measured by twodifferent temperature sensors.

APPEARS: If the meter type is NET HEAT METER

6.3.2 VFC with Net Heat Meter

VFM supports net thermal power and net energy calculations for water. Thermal power is calculated online from the mass flowand the specific enthalpy both at the inlet of the process and at the outlet. The difference between these two values is the netthermal power. The net thermal energy is calculated by time integrating (totalizing) the net thermal power. The mass flow ismeasured by the VFM along with the temperature at that point. The temperature at the exit of the process is also measuredand transmitted (4 to 20 mA) to the VFM through an additional junction box. The mass flow rate at the inlet and the outlet ofthe process is assumed to be the same.

The net thermal power can be displayed in any one of the following units:

KJ/hr, MJ/hr, GJ/hr, BTU/hr, kCal/hr, KW, MW, TR.

The net thermal energy units may be displayed in one of the following units:KJ, MJ, GJ, BTU, kCal, KWH, MWH

For both thermal power and energy user defined unit can be set. For details see sect 3.1.1

For external temperature sensing, a 2-wire RTD transmitter can be used. This should have a current output 4 to 20mA andan accuracy better than + 0.25% of the full scale.

6/25

Page 58: FLOWIRL 8700(2)

7. Description of Program Menu Functions

7.1 Numerical format

• Display of numerical values

Real (i.e. fractional) values are displayed in the first line of the display consisting of 8 digits. The number is displayedin the floating point format except the totalizer which is in an integer format (max. value... 4294967295) otherwisean exponent notation is used. See the examples given below.

Floating format: 1234.5678, 100.00

Exponent format: 1234E-10, 12345E12

In most practical applications, it is very rare that the parameters need be displayed in the exponent format.

• Input of numerical values

Entering a numeric value is very flexible. Enter a positive or a negative number in the floating point format orthe exponent format as required or as convenient.

Example: 1.2345678, -1234.567, 0.0001234

123456E1, -12345E4, 1234E-4

7/1

Page 59: FLOWIRL 8700(2)

7/2

7.2 Display

Organization: The display consists of the following two fields.

Field 1: 10-character, 5x7 dot matrix alphanumeric display used primarily for showing numeric values and also for messages.

Field 2: 10-character, 5x7 dot matrix alphanumeric display used for showing units, messages, etc.

Programming: The measurement mode settings are as follows:

- To allow the selection of the units for all the measured parametersRefer to Fct. 1.1.2, 3.2.5, 3.5.4 and 3.5.5

- Select display mode (cyclic/non-cyclic) and the error messages to/not to appear in the display cycle.Refer to Sect. Fct. 1.2.6 to 1.2.7

Measurement mode: The display shows the measured parameter(s) in its selected unit. The parameter is displayedcontinuously in the non-cyclic mode. [Fct. 1.2.7]. To select other parameter(s) of the display cycle, if any, use the key. Inthe cyclic mode, all the parameters selected in the display cycle are displayed in a sequence one after another every 6seconds.

Programming mode: The numeric line indicates the menu/functions level such as Fct. 1.1.1 [current menu level digitblinks] and the alpha-numeric line indicates the menu/function title such as MEAS_INST.

Error indications: A blinking bar at the upper left corner in the measurement mode indicates that error(s) are present. Errormessages are displayed interleaved between changing from one display parameter to another, if Fct. 1.2.6 ERROR.MSG isYES. For description of the error messages, refer to Sect. 4.1.5.

7.3 Flow range and meter size

The flow rate (min. flow to max. flow) that the flowmeter will be able to measure depends on the primary data (3.1.x functions)and the application data (3.5.x functions). Thus, the flow range specified under the Fct. 1.1.2 MAX. FLOW and Fct. 1.1.3MIN. FLOW must be within the measuring range.

The flow range for any given application is determined by the sizing of the meter for that application.

When the flow rate exceeds the max flow, an error condition -HIGH FLOW- is generated. When the flow rate falls below themin. flow, an error condition -LOW FLOW- is generated. The Vortex sensor signal is weak at this condition and if the flowrate reduces further, Vortex signal related errors such as CHECK INST., LOW SIGNAL will occur.

7.4 Primary information

The primary data gives VORTEX FLOW METER the basic information about the Vortex primary sensor. Use Fct. 3.1.1NOMINAL.DIA for specification of the nominal DN/ANSI size and Fct. 3.1.2 K-FACTOR for the calibration factor of theprimary.

Depending on whether the primary has temperature sensor, the settings need be done inFct. 3.6.1 T-SENSOR. These sensors enable the VORTEX FLOW METER to provide an online T compensation.

Depending on whether the primary has Pressure Sensor, the settings need be done in Fct. 3.6.2 P-SENSOR. Thesesensors enable the VORTEX FLOW METER to provide an online P compensation.

Page 60: FLOWIRL 8700(2)

7/3

7.5 Application information

This is the data of the process medium, its operating conditions and physical properties. It consists of:

– Process medium Fct. 3.5.1 FLUID and Fct. 3.5.2 MEDIUM

– Operating temperature and pressure conditions. Refer Fct. 3.5.6 TEMP. OPR and Fct. 3.5.7 PRES. OPR.

– Density of the medium at the operating conditions. This is required only if the software within the instrumentdoes not support the medium (Fct. 3.5.1 is selected as OTHER GAS OR OTHER LIQUID). Refer to

Fct. 3.5.6 DENS.OPR.

– Normal or reference P&T values required for normalized flow measurements only (depending on Fct.1.1.1).

The usual values are temp.norm = 0oC or 20oC and pres.norm = 1 atm.

– Density under normal conditions. This is required only for normalized volumetric flow and if the softwarewithin the

instrument does not support the medium (Fct. 3.5.2 is selected as OTHER GAS OR OTHER LIQUID).Refer to Fct. 3.5.9 DENS.NORM.

Not all of the above data needs to be given for any given application. Only the relevant data should bepunched during the actual programming.

7.6 Internal Electronic Totalizer

– The internal electronic totalizer counts volume, normalized volume or mass. The totalizer value is saved inthe non-volatile memory continuously. The totalizer can be displayed in the unit desired as per the programmingof Fct. 3.2.5 TOT.VAL. The totalizer counting is interrupted for the duration of a power failure. Counting mayoptionally be stopped and thereafter restarted by the use of Fct. 3.2.6 TOT. ON/OFF

– Resetting [to 0] or presetting of the totalizer is possible by using Fct. 3.2.5 TOT. VALUE.

Page 61: FLOWIRL 8700(2)

7.7 Current (analog) output I

The current output gives an analog representation of the flow rate. An output of 20 mA always corresponds to Q100% and thatof 4 mA to Q0%. The current output between Q0% & Qmin is 4 mA.

FOR Qmin Programmed > = Qmin from Sizing

TESTING OF CURRENT OUTPUT IFct. 2.2 TEST I can be used to check the current output. Integer values between 4 and 20 mA are possible to be monitoredon a current meter. During the test, the current output changes to the test value(s). The normal current value is restoredautomatically (as per programming of the current output) when the measurement mode is resumed.

7/4

QminP

QminSDisplayed Q

QminS = QminFROM SIZING

QminP = QminPROGRAMMED

QminS = QminFROM SIZING

QminP = QminPROGRAMMED

Displayed Q

QminP

QminS

FOR Qmin Programmed > = Qmin from Sizing

Page 62: FLOWIRL 8700(2)

7.8 Pulse output P

The pulse output value is an exact replica of the internal integer totalizer. Every time the totalizer is incremented by one, thepulse output will give a pulse. For programming of the pulse rate, set the coefficient in Fct.3.2.5 TOT.VAL.

The pulse output is generated by tracking the totalized flow and, thus, provides a true reflection of the internal totalizer value.The totalizer value is saved, continuously.

7.9 Coding desired for entry into programming mode

Fct. 3.2.2 ENTRY.CODE.1 set to YES for the coding. The entry code consists of 9 key strokes of 3 keys in the givensequence, Refer to Section 3.2.1, functionality of the keys.

7.10 Behavior of outputs during programming

Programming of the VORTEX FLOW METER is “offline” meaning that the instrument stops working when it is in the programmingmode. This means that the VORTEX FLOW METER will stop measuring the flow rate and temperature; the totalizing flow andthe control outputs (current and pulse) as per the programmed configuration. Thus, this means that the VORTEX FLOWMETER will keep the totalizer value and the current pulse output as per the last value before entering into the programmingmode.

EXCEPTION: Test functions TEST I and TEST P will affect the current and the pulse outputs respectively only for theduration of the testing.

7/5

Page 63: FLOWIRL 8700(2)

8. Technical Data

8.1 Measuring range saturated steam

Overpressure [bar] 1 3.5 5.2 7

Density [kg/m3] 1.12482 2.39175 3.22667 4.10067

Flow rate [kg/h] min max min max min max min max

DN to EN DN to

1092-1 ASME B16.5

15 1/2 5.23 65.13 7.63 138.5 8.86 186.84 9.99 237.45

25 1 11.77 146.55 17.16 311.62 19.93 420.4 22.47 534.26

40 11/2 29.51 367.39 43.03 781.2 49.98 1053.91 56.34 1339.38

50 2 51.08 636.07 74.5 1352.5 86.52 1824.84 97.55 2318.87

80 3 111.9 1393.25 163.18 2962.52 189.53 3996.69 213.66 5079.26

100 4 192.27 2393.91 280.38 5090.27 325.66 6867.21 367.12 8727.32

150 6 435.59 5423.39 635.19 11531.97 737.77 15557.6 831.71 19771.65

200 8 761.19 9477.2 1109.97 20151.75 1289.22 27186.37 1453.38 34550.3

250 10 1177.07 14655.07 1716.4 31161.66 1993.6 42039.68 2247.44 53426.86

300 12 1659.85 20665.94 2420.39 43942.81 2811.29 59282.52 3169.24 75340.22

8.2 Measuring range saturated steam

Overpressure [bar] 10.5 14 17.5 20

Density [kg/m3] 5.78855 7.47056 9.15131 0.3542

Flow rate [kg/h] min max min max min max min max

DN to DN to

EN 1092-1 ASME B16.5

15 1/2 12.57 293.62 16.22 336.12 19.87 374.28 22.48 399.6

25 1 26.7 660.65 30.33 756.27 33.57 842.14 35.71 899.1

40 1 1/2 66.94 1656.22 76.05 1895.92 84.17 2111.2 89.53 2254

50 2 115.9 2867.41 131.66 3282.41 145.72 3655.12 155 3902.36

80 3 253.86 6280.78 288.39 7189.79 319.19 8006.18 339.52 8547.74

100 4 436.19 10791.79 495.52 12353.69 548.43 13756.42 583.36 14686.93

150 6 988.19 24448.7 1122.59 27987.16 1242.47 31165.04 1321.61 33273.11

200 8 1726.83 42723.28 1961.69 48906.62 2171.17 54459.88 2309.46 58143.65

250 10 2670.28 66065.16 3033.45 75626.77 3357.4 84214.04 3571.24 89910.45

300 12 3765.52 93162.2 4277.65 106645.56 4737.45 118754.96 5036.01 126787.78

8/1

Page 64: FLOWIRL 8700(2)

Technical Data

8.3 Measuring range saturated steam

Overpressure [psigr] 15 50 75 100

Density [lbs/ft3] 0.072 0.1498 0.2036 0.2569

Flow rate [lbs/h] min max min max min max min max

DN to EN DN to

1092-1 ASME B16.5

15 1/2 11.39 143.59 16.79 305.33 19.43 411.92 21.98 523.49

25 1 25.63 323.09 37.78 687 43.72 926.82 49.46 1177.86

40 11/2 64.25 809.97 94.71 1722.26 109.6 2323.47 123.99 2952.83

50 2 111.23 1402.29 163.97 2981.75 189.74 4022.64 214.67 5112.24

80 3 243.64 3071.59 359.16 6531.24 415.61 8811.18 470.22 11197.84

100 4 418.62 5277.67 617.11 11222.13 714.12 15139.59 807.94 19240.41

150 6 948.38 11956.52 1398.07 25423.63 1617.83 34298.6 1830.38 43588.97

200 8 1657.27 20893.62 2443.07 44426.95 2827.11 59935.66 3198.52 76170.28

250 10 2562.72 32308.86 3777.85 68699.63 4371.7 92681.52 4946.03 117785.93

300 12 3613.84 45560.54 5327.35 96877.61 6164.78 130695.42 6974.68 166096.57

8.4 Measuring range saturated steam

Overpressure[psig] 150 200 250 300

Density [lbs/ft3] 0.3627 0.4682 0.5736 0.6793

Flow rate [lbs/h] min max min max min max min max

DN to DN to

EN 1092-1 ASME B16.5

15 1/2 27.71 647.32 35.76 741.01 43.81 825.16 49.57 880.97

25 1 58.76 1456.48 66.75 1667.28 73.87 1856.6 76.8 1982.18

40 1 1/2 147.31 3651.32 167.33 4179.78 185.19 4654.39 192.54 4969.22

50 2 255.05 6321.55 289.69 7236.47 320.61 8058.16 333.34 8603.23

80 3 558.66 13846.72 634.55 15850.77 702.27 17650.59 730.15 18844.51

100 4 959.9 23791.79 1090.29 27235.18 1206.66 30327.68 1254.56 32379.11

150 6 2174.63 53900.08 2470.04 61701.05 2733.67 68707.08 2842.2 73354.56

200 8 3800.1 94188.6 4316.32 107820.52 4777 120063.33 4966.64 128184.65

250 10 5876.29 145648.57 6674.55 166728.29 7386.91 185659.96 7680.16 198218.37

300 12 8286.49 205387.25 9412.15 235112.94 10416.7 261809.55 10830.22 279518.87

8/2

Page 65: FLOWIRL 8700(2)

8.5 Flow table

Measuring range limits

Size Qmin Qmax

DN to EN 1092-1 DN to ASME B16.5 [m3/h] [m3/h]

Water

15 1/2 0.36 5.07

25 1 0.81 11.4

40 1 1/2 2.04 28.58

50 2 3.53 49.48

80 3 7.74 108.38

100 4 13.3 186.22

150 6 30.13 421.89

200 8 52.66 737.23

250 10 81.43 1140.02

300 12 114.83 1607.61

Values based on water at 20°C

Air

15 1/2 4.34 57.91

25 1 9.77 130.29

40 1 1/2 24.5 326.63

50 2 42.41 565.49

80 3 92.9 1238.64

100 4 159.62 2128.27

150 6 361.62 4821.57

200 8 631.91 8425.53

250 10 977.16 13028.81

300 12 1377.95 18372.66

Values based on air at 20°C and 1,013 bar abs

Flow rate limits

Product Nominal diameters Minimum flow rates Maximum flow rates

to EN to ASME [m/s] [m/s]

Liquids DN15… N300 DN1/2“…DN12“ 0.5 x ( 998 / p ) 0.5 or 0.4 1 7 x ( 998 / p )0.47 or 10 2

Gas, vapor DN15… N300 DN1/2“…DN12“ 6 x ( 1.29 / p )0.5 or 2 2 7 x ( 998 / p )0.47 or 80 2

1 Use the larger value!

2 Use the smaller value!

8/3

Page 66: FLOWIRL 8700(2)

8.6 Technical data

Measuring system

Field of application Flow measurement of liquids, gases and vapors

Operating method / measuring

principle Karman vortex street

Measured value

Primary measured value: Vortex shedding frequency

Secondary measured value: Operating and standard volumetric flow, mass flow

Measuring accuracy

Accuracy Re >20000 ± 0.75% for liquids

Re > 20000 ± 1% for gases and vapors

10000 < Re < 20000 ± 2% for liquids, gases and vapors 1

Repeatability ± 0.1%

Stability ± 0.1% over a period of 1 year

Operating conditions

Ambient temperature -40…+65°C (Ex version)

-40…+85°C (non-Ex version)

Storage temperature -50…+85°C

Product temperature -20…+240°C

Process products Liquids, gases, vapors

Density is taken into consideration when rating

Viscosity < 10 cP

Reynolds’ number 10000...2300000

Product pressure limit max. 100 bar, higher pressures on request

Installation requirements

Inlet run > 20 x DN

Outlet run: > 5 x DN

Dimensions and Weights see table 9/1, 9/2

Materials

Sensor 1.4404/316L; 1.4539/904L in preparation; Hastelloy C-2000 in

preparation

Electronics casing Aluminum

Sensor gasket 1.4435/316L / FPM

1 Accuracy pressure- and temperature-compensated Re > 20000 +/- 1.5% for gases and vapors;

10000 < Re < 20000 +/- 2.5% for gases and vapors

8/4

Page 67: FLOWIRL 8700(2)

Power supplyNon-Ex version 12 VDC…36 VDC

Protection category IP66/67

Current outputMeasuring range 4...20mA

Over Range 20.8 mA +/- 1 % (105 % +/- 1%)

Load: minimum 100 ohms; maximum R = ((Ub - 14 V) / 22.4 mA)

Error signal NAMUR NE43

Maximum 22.0 mA (112.5%)

Multidrop mode 4.0 mA

Digital outputHART Compatible

Pulse outputPulse output Pulse frequency max. 0.5 Hz

Power supply non-Ex 24 VDC as NAMUR, or open < 1 mA, maximum 36 V,

closed 100 mA, U < 2 V

Display and operating interfaceLocal display 2 lines, 10 characters

Operating and display languages English

Process connectionsProcess connection EN or ASME flanges

Flange version DN 15...DN 150

Sandwich version DN 15...DN 100

Protection categoryProtection category IP 66/67

8/5

Page 68: FLOWIRL 8700(2)

8.7 Signal Convertor VORTEX FLOW METER-- Technical Data

Full-scale range Units text of 10-characters freely programmable. Conversion factor coefficientand intercept (offset) programmable for accepting any unit required.

Power supply UB (2-wire) 12-36 V DC

Current output terminals, 4-20 mA, DC, 2-wire

Maximum load resistanceRB =

UB - 12 V

20 mA

Ambient temperature Tu

Local display (optional) 2-line dot matrix 10-characters per line LCD with3-button keypad/magnetic pin programming.Programming through a user-friendly menu interface.

Display functions Actual flow rate, sum integer totalizer (10-digit),operating temperature, Vortex frequency each programmable for continuous orsequential display of the measuredparameters and error messages

Display units Units text (10-characters) freely programmable along with conversion factors

8/6

12

1200

Page 69: FLOWIRL 8700(2)

Actual flow rate Units text (10-characters) freely programmable along with conversion factors

Totalizer Units text (10-characters) freely programmable along with conversion factors

Language of plain texts English. German and French available upon request.

Display

1st field (top) 10-character, 5x7 dot matrix alphanumeric display

2nd field (bottom) 10-character, 5x7 dot matrix alphanumeric display

Mass flow measurement Online for saturated steam or water (liquid state) up to 240 deg. C. Temperature sensorstandard built-in with VORTEX FLOW SENSOR primary.Offline operating and standard density programmable.

Temp measurement Accuracy + 0.3 degree

Pressure measurement Accuracy + 0.3% of F.S.+ 1 LSB

Current output (same as the Operating data programmable, galvanically isolated from power terminals 12/11)the sensors and the pulse output

Current 4-20 mA corresponding to zero and the maximum flow value programmed

Accuracy ± 0.2% of full-scale

Temperature coefficient 100 ppm of full-scale range per 10 C

Power influence + 0.05% of full-scale range for 12-36 V variation in the voltage supply

Pulse output (passive) Optional. Galvanically isolated from the sensors and the current output. The incrementis identical to the internal integer totalizer. Maximum pulse rate is 0.5 Hz.

Power supply 5-30 V DC

Load current Max. 100 mA

Power Internal power dissipation is 250 mW

Self diagnostics Built-in for amplifier circuits witherror annunciation.

8/7

Page 70: FLOWIRL 8700(2)

9. Dimensions & Weight

9.1 FLANGED Version WEIGHT (Kg) WEIGHT (Kg)(WITH PR.SNSR.) (W/O PR.SNSR.)

NB CLASS d D L H INB 1/2" 150 16 90 200 269 140 5.1 4,5NB 1/2" 300 16 95 200 269 140 5.5 4.9NB 1/2" 600 16 95 200 269 140 5.7 5.1 NB 1" 150 24 110 200 268 148 6.8 6.2 NB 1" 300 24 125 200 268 148 7.8 7.2 NB 1" 600 24 125 200 268 148 8.1 7.5 NB 1.5" 150 38 125 200 274 148 8.9 8.3 NB 1.5" 300 38 155 200 274 148 11 10.4 NB 1.5" 600 38 155 200 274 148 12 11.4 NB 2" 150 50 150 200 278 148 11.6 11 NB 2" 300 50 165 200 278 148 13 12.4 NB 2" 600 50 165 200 278 148 14.5 13.9 NB 3" 150 74 190 200 292 158 20.4 19.8 NB 3" 300 74 210 200 292 158 23.4 22.8 NB 3" 600 74 210 200 292 158 24.4 23.8 NB 4" 150 97 230 250 308 170 24 23.8 NB 4" 300 97 255 250 308 170 32 31.4 NB 4" 600 97 275 250 308 170 41 40.4 NB 6" 150 146 280 300 327 197 36.8 36.2 NB 6" 300 146 320 300 327 197 51.8 51.2 NB 6" 600 146 355 300 327 197 76.8 76.2DN PN d D L H I WT.(P) WT.(T)DN15 40 16 95 200 269 140 6.1 5.5DN15 100 16 105 200 269 140 7.1 6.5DN25 40 24 115 200 268 148 7.9 7.3DN25 100 24 140 200 268 148 9.9 9.3DN40 40 38 150 200 274 148 10.8 10.2DN40 100 38 170 200 274 148 14.8 14.2DN50 16 50 165 200 278 148 12.7 12.1DN50 40 50 165 200 278 148 12.9 12.3DN50 63 50 180 200 278 148 16.9 16.3DN50 100 50 195 200 278 148 18.4 17.8DN80 16 74 200 200 292 158 17.4 16.8DN80 40 74 200 200 292 158 19.4 18.8DN80 63 74 215 200 292 158 23.4 22.8DN80 100 74 230 200 292 158 27.4 26.8DN100 16 97 220 250 308 170 22 21.4DN100 40 97 235 250 308 170 25 24.4DN100 63 97 250 250 308 170 30 29.4DN100 100 97 265 250 308 170 36 35.4DN150 16 146 285 300 327 197 35.8 35.2DN150 40 146 300 300 327 197 41.8 41.2DN150 63 146 345 300 327 197 59.8 59.2DN150 100 146 355 300 327 197 67.8 67.2

9.2 SANDWICH Version WEIGHT.(Kg) WEIGHT.(Kg)(WITH PR.SNSR.) (W/O PR.SNSR.)

N B CLASS d D L H INB 1/2" 150 16 45 65 269 140 4.1 3.5NB 1/2" 300 16 45 65 269 140 4.1 3.5NB 1/2" 600 16 45 65 269 140 4.1 3.5 NB 1" 150 24 65 65 268 148 4.9 4.3 NB 1" 300 24 65 65 268 148 4.9 4.3 NB 1" 600 24 65 65 268 148 4.9 4.3 NB 1.5" 150 38 82 65 274 148 5.5 4.9 NB 1.5" 300 38 82 65 274 148 5.5 4.9 NB 1.5" 600 38 82 65 274 148 5.5 4.9 NB 2" 150 50 102 65 278 148 6.6 6 NB 2" 300 50 102 65 278 148 6.6 6 NB 2" 600 50 102 65 278 148 6.6 6 NB 3" 150 74 135 65 292 158 8.8 8.2 NB 3" 300 74 135 65 292 158 8.8 8.2 NB 3" 600 74 135 65 292 158 8.8 8.2 NB 4" 150 97 158 65 308 170 10.1 9.5 NB 4" 300 97 158 65 308 170 10.1 9.5 NB 4" 600 97 158 65 308 170 10.1 9.5DN PN d D L H I WT.(P) WT.(T)DN15 100 16 45 65 269 140 4.1 3.5DN25 100 24 65 65 268 148 4.9 4.3DN40 100 38 82 65 274 148 5.5 4.9DN50 100 50 102 65 278 148 6.6 6DN80 100 74 135 65 292 158 8.8 8.2DN100 100 97 158 65 308 170 10.1 9.5

9/1

Page 71: FLOWIRL 8700(2)

9/2

DN 80-DN100, SW

DN 15-DN50, SW

DN 15-DN50, FL

DN 80-DN150, FL

Page 72: FLOWIRL 8700(2)

10. Function Checks

This section describes some functional checks that can be performed without using any special equipment. It must benoted that these checks are very preliminary and do not check the total functionality of the primary head or the signalconverter.

10.1 Current output check

Fct. 2.1.2 TEST I can be used to test the current output function of VORTEX FLOW CONVERTER. With thisfunction, it is possible to generate following test values: 0/2/4/10/20/22 mA. Refer to section 1.2 for the connectiondiagram.

The current output electronics is factory-calibrated and should be within + 0.02 mA. Otherwise re-calibration ofthe current output is necessary by Forbes Marshall Service.

10.2 Pulse output check

Fct. 2.1.3 TEST P is meant for checking the pulse output. 0.50607 Hz will be generated at pulse output. This canbe checked by connecting the electromechanical counter between the pulse output terminals.

10/1

Page 73: FLOWIRL 8700(2)

10/2

10.3 Primary head functional checks

10.3.1 Vortex sensor

To perform the preliminary testing of the Vortex piezo sensor, the signal cable of the piezo sensor should be disconnectedfrom the signal converter electronics. To do this: always switch OFF the power source before commencing work!

1. remove the cover from the electronic compartment. Ensure that the screw threads of the electronic compartment coverare well greased at all times!

Do the following tests

Capacitance between the centre pin and each outer pin is from 3 nano farad to 9.52 nano farad

Resistance between the centre pin and each outer pin >200 M ohm. Also, the resistance betweeneach sensor wire pin and the earth should be >200 M ohm.5. Reassemble the converter in the reverse order

Temp Sensor I/P

Pressure sensor I/P

Piezo sensor I/p

Connector fordisplay

10.3.2 Temperature sensor

The PT-1000 temperature sensor can be checked by measuring its resistance.

Always switch OFF power source beforecommencing work!

Follow the steps 1 and 2 i.e. the same as in the above

3. Remove the temperature sensor cable at the location Y of the preamplifier board. Pull the cable by its end connector andnot by the cable itself!

4. Resistance between the 2 pins should be within 1K [0ºC] – 1.193k [50ºC] depending on the ambient temperature. Forother temperatures resistance values as per DIN43760.

5. Reassemble the converter in the reverse order.

Page 74: FLOWIRL 8700(2)

11. Trouble-shooting

It is assumed in this section that the convertor has already been installed. (for installation details, refer to Sections2 and 3 in the Sensor Manual).

Given below are some trouble-shooting hints.

SYMPTOM: The display is blank.

• Supply voltage (between terminals 1/2) is not available.

• Electronics faulty

SYMPTOM: The current output is not correct.

• Check the current output electronics (refer to Sect.7.7)

• Check that the current output loop is not overloaded [1200 ohm max.]

SYMPTOM: The pulse output is incorrect.

• Check the pulse output electronics (refer to Sect. 7.8)

• Check the programming of the pulse output (Functions Fct. 1.4.1.)

• Check that the pulse output is not overloaded. For load ratings of the pulse output, refer to specifications on Page 3/2

SYMPTOM: INV.CONFIG (invalid configuration)

• Configuration data in the non-volatile memory is inadvertently corrupted. Go to the programming mode and recheck

(reprogram, if necessary) all the settings. If the error persists contact Forbes Marshall Service.

SYMPTOM: Display contrast is progressively fading.

• Never expose the display directly to the sunlight! Install a sunshade if necessary.

11/1

Page 75: FLOWIRL 8700(2)

11.1 Trouble-shooting hints

It is assumed in this section that the flowmeter has already been installed. (for installation details, refer to Sections 2 and 3).

Given below are some trouble-shooting hints.

SYMPTOM: A non-zero flow indicated when no actual flow in the pipe.• Mains interference due to improper earthing.

The protective earth PE terminal should be properly grounded.

• Excessive mechanical vibration in the pipe. If so, support the pipeline near the flowmeter perpendicular to both the axis ofthe pipe and the axis of the bluff body.

• This problem can be solved by reducing the factory set gain.

For e.g. Factory set gain for Gas/Steam is 11 and for liquid it is 3. This can be reduced to 6 for Gas/Steam and 2 for liquid.

Caution: By reducing the gain, the minimum measurable flow rate will go up by the factor which is approx. equal to squareroot of ratio of the gains. (old gains/ new gain). If the min. flow with reduced gain is above the min. flow which is required tobe measured, then reducing the gain is not the permanent solution. Then the installation should be corrected and also thevibrations should be eliminated.

SYMPTOM: ‘CHECK INST.’ error is displayed when no flow in the pipe.

The display should normally indicate 0.0 flow rate, LOW FLOW and LOW SIGNAL errors when there is no flow in the pipe.The additional CHECK INSTALL error (flow rate = 0.0 or some steady or fluctuating value) is an indication of:

• Improper/inadequate earthing

• Excessive pipe vibration

SYMPTOM: Flow rate indicated is 0.0 even with flow in the pipe.

• The Vortex sensor cable disconnected or is not properly connected.

• Flow sensor faulty – some checks are given inSect. 10.1

SYMPTOM: The flow indicated responds to changes in the flow but the indicated value does not correspond tothe actual flow rate. Also ‘CHECK INST.’ error may appear intermittantly.

• Check the programming of Fct. 3.1.2 K-Factor which should be same as that on the name plate

• The meter is not properly centered on the pipeline. The axis of the meter bore should be aligned with that of the pipe.

• Gaskets at the meter are protruding into the pipe bore. The gaskets must not project into the effective cross-section of thepipe.

• Irregularities on the surface of the pipe bore. The pipe bore should be free from irregularities at the welded joints, dirt,deposits and excessive surface roughness.

• The Vortex signal is falsified due to a bi-phase medium. Bi-phase media are not permitted. Use a moisture separator for wetsteam applications to remove the moisture droplets from the steam. Use suitable filters in gas applications to remove solidparticles from the flowing gas.

• Incorrect angular position of the meter.Refer to Sect. 2.10 for the allowable mounting positions.

• Insufficient upstream/downstream pipe lengths. Check that the upstream/downstream pipe lengths are of the correctminimum length as given in Sect. 2.11.

• Check the flow direction and the direction of the arrow on the primary.

11/2

Page 76: FLOWIRL 8700(2)

Addendum to Installation and Operating Instructions

Precautions for “Safe and Desired” operation of VFS 8000with VFC 700 signal converter

Do

Ensure that sufficient Upstream and Downstream straight lengths are provided

Check that the housing of the primary head is perfectly centred between the process flanges

Provide proper supports to the pipeline at both ends of the meter to keep the pipe vibration level wellbelow the maximum limit specified

Ensure that the unit is installed in the process pipeline with fasteners securely and firmly tightenedcausing no leakage of the process fluid through the gaskets

Check the chemical compatibility of the material of the wetted parts with the process fluid

Maintain proper Downstream pressure to avoid cavitation

Degrease the meter properly in case the process fluid is hazardous like Oxygen

Ensure that the controlled valve is opened slowly not allowing the start-up velocity from being veryhigh in case the process fluid is hazardous like Oxygen

DO NOT

Use the meter with the process fluid being bi-phase like Gases-Vapours with liquid droplets or solidparticles and gas bubbles in liquids

Install the meter where the process medium is pulsating with fluctuations in the process pressure Allow any of the parameters like Flow-Density-Pressure-Temperature- Reynolds Number beyond the

limit value specified for the meter on the Nameplate and the Test and Guarantee Certificate Tamper with any parts of the primary head of the meter Replace the fasteners with any other make or brand without the consent of the manufacturer Allow the process pressure to exceed the flange rating.

12

Page 77: FLOWIRL 8700(2)