gauss siedel method of load flow

14
Gauss Siedel method of Load flow studies Presenter: Abdul Azeem M. Tech (Power System & Drives) Department of Electrical Engineering Z.H.C.E.T. Aligarh Muslim University Aligarh UP

Upload: abdul-azeem

Post on 20-Mar-2017

33 views

Category:

Engineering


4 download

TRANSCRIPT

Page 1: Gauss Siedel method of Load Flow

Gauss Siedel method of Load

flow studiesPresenter:

Abdul AzeemM. Tech (Power System & Drives)

Department of Electrical Engineering Z.H.C.E.T.

Aligarh Muslim UniversityAligarh UP

Page 2: Gauss Siedel method of Load Flow

Load/Power Flow studies Load-flow studies are performed to determine the steady-state

operation of an electric power system. It calculates the voltage drop on each feeder, the voltage at each bus, and the power flow in all branch and feeder circuits.

Determine if system voltages remain within specified limits under various contingency conditions, and whether equipment such as transformers and conductors are overloaded.

Load-flow studies are often used to identify the need for additional generation, capacitive, or inductive VAR support, or the placement of capacitors and/or reactors to maintain system voltages within specified limits.

Losses in each branch and total system power losses are also calculated.

Necessary for planning, economic scheduling, and control of an existing system as well as planning its future expansion of system.

Page 3: Gauss Siedel method of Load Flow

Power Flow Equation

Note: Transmission lines are represented by their equivalent pi models (impedance in p.u.)

Applying KCL to this bus results in

(1)

Fig. 1. A typical bus of the power system.

Page 4: Gauss Siedel method of Load Flow

(2)

The real and reactive power at bus i is

Substituting for Ii in (2) yields

Equation (5) is an algebraic non linear equation which must be solved by iterative techniques

Page 5: Gauss Siedel method of Load Flow

Gauss-Seidel methodEquation (5) is solved for Vi solved

iteratively

Where yij is the actual admittance in p.u. Pi

sch and Qisch are the net real and reactive powers in p.u.

In writing the KCL, current entering bus I was assumed positive. Thus for: Generator buses (where real and reactive powers are injected), Pi

sch and Qisch have positive values.

Load buses (real and reactive powers flow away from the bus), Pi

sch and Qisch have negative values.

Page 6: Gauss Siedel method of Load Flow

Eqn.5 can be solved for Pi and Qi

The power flow equation is usually expressed in terms of the elements of the bus admittance matrix, Ybus , shown by upper case letters, are Yij = -yij, and the diagonal elements are Yii = ∑ yij. Hence eqn. 6 can be written as

Page 7: Gauss Siedel method of Load Flow

Iterative steps:•Slack bus: both components of the voltage are specified. 2(n-1) equations to be solved iteratively.• Flat voltage start: initial voltage of 1.0+j0 for unknown voltages.• PQ buses: Pi and Qi are known. with flat voltage start, Eqn. 9 is solved for real and imaginary components of Voltage.•PV buses: Pi

sch and [Vi] are known. Eqn. 11 is solved for Qik+1

which is then substituted in Eqn. 9 to solve for Vik+1

Page 8: Gauss Siedel method of Load Flow

ExampleA three bus system are shown in figure. The

relevent per unit values of admittences on 100 MVA base are indicated on the diagram and bus data are given in table-

Form Ybus and determine the voltage at bus 2 and bus bus 3 after the first iteration using Gauss-Siedel method.Take the acceleration factor 1.6.

(Power System Analysis by Ashfaq Hussain, page no. 380)

Page 9: Gauss Siedel method of Load Flow
Page 10: Gauss Siedel method of Load Flow

We first calculate the element of the Ybus

Y11 =sum of admittences of all elements connected to node 1=-j3-j4=-j7

Y22 =sum of all admiteneces connected to bus 2=-j3-j4=-j8

Y33=sum of all the admittences connected to bus 3=-j4-j5=-j9

Y12=Y21=-(-j3)=j3Y23=Y32=-(j5)=j5Y31=Y13=-(-j4)=j4

Page 11: Gauss Siedel method of Load Flow
Page 12: Gauss Siedel method of Load Flow
Page 13: Gauss Siedel method of Load Flow
Page 14: Gauss Siedel method of Load Flow

THANKS