generation capability curves for wind farms ieee ...site.ieee.org › ... › 2014 › 03 ›...

23
Eduardo H. Enrique Stantec Consulting Ltd. Generation Capability Curves for Wind Farms IEEE Conference on Technologies for Sustainability 2014

Upload: others

Post on 06-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

Eduardo H. Enrique

Stantec Consulting Ltd.

Generation Capability Curves for Wind Farms

IEEE Conference on Technologies for Sustainability

2014

Page 2: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

Objective of this presentation

VERIFY COMPLIANCE WITH THE REQUIREMENTS FROM THE UTILITY

AT THE POINT OF COMMON COUPLING:

REACTIVE POWER EQUAL TO ± “Q” (MVAr) AT ALL “P” (MW)

Page 3: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

Objective of this presentation

COLLECTOR

Page 4: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

Agenda

1 Wind turbines performance

2 Collector system components

3 Wind farm load flow

4 Summary

Page 5: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

Wind turbines performance 1

Page 6: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

1 Wind turbines performance

TYPE 4 WIND TURBINE P-Q DIAGRAM

ACTIVE POWER P AND REACTIVE POWER Q SIGN CONVENTIONS PER IEEE 1459

Page 7: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

1 Wind turbines performance

TYPE 4 WIND TURBINE P-Q DIAGRAM

Q

P

Page 8: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

1 Wind turbines performance

TYPE 4 WIND TURBINE P-Q DIAGRAM WITH STATCOM CAPABILITIES

Q

P

Page 9: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

1 Wind turbines performance

WIND FARM TURBINES AGGREGATE P-Q DIAGRAM

Q

P

+

Page 10: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

1 Wind turbines performance

TYPE 4 WIND TURBINE POWER-VOLTAGE (P-V) OUTPUT

&

Page 11: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

Collector system components 2

Page 12: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

2 Collector system components

TRANSMISSION LINES

UNDERGROUND CABLES

TRANSFORMERS

Page 13: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

2 Collector system components

QL ~ I2 xL

QC ~ Vr2 / xC

APPROXIMATED EQUIVALENT MODEL OF A

TRANSMISSION LINE AND UNDERGROUND CABLE

Page 14: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

2 Collector system components

APPROXIMATED EQUIVALENT MODEL

OF A TRANSFORMER

QL ~ I2 xL

Page 15: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

Wind farm load flow 3

Page 16: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

3 Wind farm load flow

UTILITY REQUIREMENTS OF REACTIVE POWER AT THE PCC

Q

P

Page 17: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

3 Wind farm load flow

WIND FARM GENERATION CAPABILITY CURVE FOR MINIMUM VOLTAGE AT THE PCC

Q

P

+ + +

Page 18: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

3 Wind farm load flow

WIND FARM GENERATION CAPABILITY CURVE FOR MINIMUM VOLTAGE AT THE PCC

Q

P

+ + +

Page 19: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

3 Wind farm load flow

VOLTAGE LIMITATIONS ON THE P-Q DIAGRAM P = 0MW, Q ≠ 0MVAr

G

V∞ VT XL

I

P,Q

ONE-LINE EQUIVALENT MODEL OF THE WIND FARM

REFERENCE CAPABILITY CURVE

90°

V

Vj I X

I

Page 20: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

I

j I XV V

3 Wind farm load flow

VOLTAGE LIMITATIONS ON THE P-Q DIAGRAM P ≠ 0MW, Q = 0MVAr

G

V∞ VT XL

I

P,Q

ONE-LINE EQUIVALENT MODEL OF THE WIND FARM

REFERENCE CAPABILITY CURVE

Page 21: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

3 Wind farm load flow

VOLTAGE LIMITATIONS ON THE P-Q DIAGRAM P = 0MW, Q ≠ 0MVAr

G

V∞ VT XL

I

P,Q

ONE-LINE EQUIVALENT MODEL OF THE WIND FARM

REFERENCE CAPABILITY CURVE V

V

j I X

I

90°

Page 22: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

Summary 4

1. The capability curves are an effective tool to evaluate

compliance with the requirements of the utility at the PCC

2. These curves provide a view of the effects of the electrical

components in the collector system and substation

3. The need for additional reactive power can be visualized

without having to resolve the system load flow each time

4. They show the limitations of the wind farm in the event of

changing conditions in the transmission system.

Page 23: Generation Capability Curves for Wind Farms IEEE ...site.ieee.org › ... › 2014 › 03 › EEnrique_Presentation-Rev-E.pdfIEEE Conference on Technologies for Sustainability 2014

Questions?

Eduardo H. Enrique

Stantec Consulting Ltd.