generator protection gers

186
Prestación de los servicios de Diseño y estudios asociados a sistemas eléctricos Certificado No. 637-1 Generator Protection Setting Criteria Juan M. Gers GERS GERS

Upload: ghk1984

Post on 01-Nov-2014

59 views

Category:

Documents


8 download

TRANSCRIPT

Page 1: Generator Protection Gers

Prestación de los servicios de Diseño y

estudios asociados a

sistemas eléctricos

Certificado No. 637-1

Generator ProtectionSetting Criteria

Juan M. Gers

GERSGERS

Page 2: Generator Protection Gers

Content

Concepts and protective relaying evolution

Functions required in the protection of generators

Types of Generator Grounding

Schemes for generator protection

Setting criteria of generator protection

Examples

Handling of alarms and oscillographs

Page 3: Generator Protection Gers

Preliminary

• Faults in power systems occur due to a high number of reasons such us:

– Lightning– Aging of insulation– Equipment failure– Animal presence– Rough environmental conditions– Branch fall– Improper design, maintenance or operation

• The occurrence of faults is not the responsibility of poor protection systems. Protective devices are essential in Power Systems to detect fault conditions, clear them and restore the healthy portion of the systems.

Page 4: Generator Protection Gers

Preliminary

• Protection relays sense any change in the signal which they are receiving, which could be of electrical or mechanical nature.

• Typical electrical protection relays include those that monitor parameters such as voltage, current, impedance, frequency, power, power direction or a ratio of any of the above.

• Typical mechanical protection relays include those that monitor parameters such as speed, temperature, pressure and flow among others.

Page 5: Generator Protection Gers

Teaching Protection Courses

Page 6: Generator Protection Gers

Teaching Protection Courses

Page 7: Generator Protection Gers

Protection requirements

• Reliability: ability to operate correctly. It has two components:

• Dependability• Security

• Speed: Minimum operating time clear a fault

• Selectivity: maintaining continuity of supply

• Cost: maximum protection at the lowest cost possible

Page 8: Generator Protection Gers

Classification of relays by construction type

– Electromagnetic– Solid state– Microprocessor– Numerical– Non-electric (thermal, pressure, etc.,)

Page 9: Generator Protection Gers

Electromagnetic

Torque

Page 10: Generator Protection Gers

Solid State

Ref

Averaged

Hysteresis

Ref

Hysteresis

Page 11: Generator Protection Gers

Microprocessor

Averaged

PA/D

Page 12: Generator Protection Gers

Numeric

Direct Samples

PA/D

Page 13: Generator Protection Gers

Advantages of numerical relays

• Reliability

• Multifunctionality

• Self-diagnosis

• Event and disturbance records

• Communication capabilities

• Adaptive protection

Page 14: Generator Protection Gers

Architecture of numerical relays

• Microprocessor

• Memory module

• Input module

• Output module

• Communication module

Page 15: Generator Protection Gers

Numerical relays

Page 16: Generator Protection Gers

Sampled Waveform

0

1

2

3

-8

-6

-4

-2

0

2

4

6

8

Sample

Cur

rent

Sine Wave4 samples/cycle0

2 4 6 8 10 12 14 16 18 20 22

Page 17: Generator Protection Gers

DFT k kI n I( ) = [Σ (cos( (sin( ))]nk ))- jI nkN-1

k=0

2πN

2πN

2N

DFT

N = # samples/cycle fundamentaln = desired harmonick = sample index

Page 18: Generator Protection Gers

For k = 0 , n=1 cos( )=1 and sin = 0

For k = 1 , n=1 =0 and = 1

For k = 2 , n=1 = -1 and = 0

For k = 3 , n=1 =0 and = -1

( )

cos( ) sin ( )

cos( ) sin ( )

cos( ) sin ( )2Nπnk 2

Nπnk

2Nπnk 2

Nπnk

2Nπnk 2

Nπnk

2Nπnk 2

NπNk

IDFT = (I0-jI1-I2+jI3)2N

DFT

Page 19: Generator Protection Gers

ANSI/IEEE device identification

No. DESCRIPTION2 Time-delay relay

21 Distance relay24 Overexcitation / Volts per Hertz25 Synchronism-check relay27 Undervoltage relay

27TN Third-Harmonic Undervoltage relay30 Annunciator device32 Reverse power relay37 Undercurrent or underpower relay40 Field excitation relay46 Negative sequence overcurrent relay47 Negative sequence overvoltage relay49 Thermal relay50 Instantaneous AC overcurrent relay

50DT Split Phase Differential50/27 Inadvertent Energizing50BF Breaker Failure

51 AC Inverse Time Overcurrent relay52 Circuit breaker59 Overvoltage relay

59D Third-Harmonic Voltage Differential Ratio

No. DESCRIPTION60 Voltage balance or loss of potential relay63 Pressure device

64F Field Ground relay64B Brush Lift-Off Detection

64S100% Stator Ground Protection by Low Frequency Injection

67 AC directional overcurrent relay68 Power Swing Blocking69 Permissive relay74 Alarm relay76 DC overcurrent relay78 Out-of-step relay79 AC reclosing relay81 Frequency relay

81R Rate of Change Frequency relay83 Transfer device85 Carrier or pilot-wire relay86 Lock out relay87 Differential relay94 Auxiliary tripping relay

Page 20: Generator Protection Gers

Review of Grounding Techniques

Why Ground?

• Safety• Ability to detect less harmful (hopefully)

phase-to-ground fault before phase-to-phase fault occurs

• Limit damage from ground faults• Stop transient overvoltages• Provide ground source for other system protection

(other zones)

Page 21: Generator Protection Gers

Types of Generator Grounds

No Impedance

• Cheap• Usually done only on small generators• Definitely a good ground source• Generator likely to get damaged on internal ground fault

G System

Page 22: Generator Protection Gers

Types of Generator Grounds

Low Impedance

• Can get expensive as resistor size increases• Usually a good ground source• Generator still likely to be damaged on internal ground

fault• Ground fault current typically 200-400 A

G System

Page 23: Generator Protection Gers

Types of Generator Grounds

High Impedance

• Moderately expensive• Used when generators are unit connected• System ground source obtained from unit xfmr• Generator damage minimized or mitigated from ground

fault• Ground fault current typically <=10A

Page 24: Generator Protection Gers

Types of Generator Grounds

Hybrid Impedance

• Combines advantages of Low Z and High Z ground• Low Z ground provides ground source for normal

conditions• If an internal ground fault (in the generator) is detected by

the 87GD element, the Low Z ground path is opened, leaving only the High Z ground path

• The High Z ground path limits fault current to approximately 10A (saves generator!)

Page 25: Generator Protection Gers

Hybrid Impedance Ground

G

51 51N

51 51N

51 51N

87GD

51G

59N

52B

52F1

52F2

52F3

52G

VS

TripExcitation,

Prime Mover

Page 26: Generator Protection Gers

Generator Protection: Faults

Page 27: Generator Protection Gers

Generator Protection: Abnormal Conditions

Page 28: Generator Protection Gers

New Std C37.102-2005

Page 29: Generator Protection Gers

New Std C37.102-2005

Page 30: Generator Protection Gers

What’s new in Std C37.102-2005

• Metering of voltages, currents, power and other measurements

• Oscillography• Sequence of events capture

with time tagging• Remote setting and monitoring

through communications

Section 6 – Multifunction Generator Protection Systems • Digital technology offers several additional features which could not be obtained in one package with earlier technology• These features include:

• User configurability of tripping schemes and other control logic

• Low burden on the PT’s and CT’s

• Continuous self-checking and ease of calibration

Page 31: Generator Protection Gers

What’s new in Std C37.102-2005

6.2.1 Protective Functions• 87G – Generator Phase Differential• 87GN – Generator Ground Differential• 59G Stator Ground• 100% Stator Ground

– 27TH - Third Harmonic Neutral Undervoltage– 59TH – Third Harmonic Voltage Ratio or Differential– 64S – Sub-harmonic Voltage Injection

• 46 – Current Unbalance/Negative Sequence

Page 32: Generator Protection Gers

What’s new in Std C37.102-2005

• 24 – Overexcitation• 27 – Undervoltage• 59 – Overvoltage• 81U – Underfrequency• 81O – Overfrequency • 32 – Reverse Power or Directional Power• 49 – Thermal Protection• 51 – Overcurrent• 51VC/51VR or 21 – System Backup

Page 33: Generator Protection Gers

What’s new in Std C37.102-2005

• 60 – Loss of Voltage• 78 – Out-of-Step• 64F – Field Ground• Additional functions that may be provided include:

• Sequential Trip Logic• Accidental Energization• Open Breaker Detection

Page 34: Generator Protection Gers

What’s new in Std C37.102-2005

• 60 – Loss of Voltage• 78 – Out-of-Step• 64F – Field Ground• Additional functions that may be provided include:

– Sequential Trip Logic– Accidental Energization– Open Breaker Detection

Page 35: Generator Protection Gers

Small – up to 1 MW to 600V, 500 kVA if >600V

Small Machine Protection IEEE “Buff Book”

Page 36: Generator Protection Gers

Medium – up to 12.5 MW

Medium Machine Protection IEEE “Buff Book”

Page 37: Generator Protection Gers

Large – up to 50 MW

Large Machine Protection IEEE “Buff Book”

Page 38: Generator Protection Gers

Large Machine Protection IEEE C37.102-1995

Larger than 50 MW

Page 39: Generator Protection Gers

Large Machine Protection IEEE C37.102-2006

Page 40: Generator Protection Gers

50DT

52Gen

50BFPh

87

5050/2740 51T 4651V60FL 21 78 32

27

81R 81 27 59 24

64F 64B

M-3921+

-

CT

VT

CT

87GD 50N50

BFN 51N

R

CT

VT

59N27TN

27

32R

High-impedance Grounding with ThirdHarmonic 100% Ground Fault Protection

Low-impedance Grounding withOvercurrent Stator Ground Fault Protection

VT

VT

25

67N

59D

3Vo

This function is available as astandard protective function.

This function is available as aoptional protective function.

This function provides control forthe function to which it points.

NOTE: Some functions aremutually exclusive; seeInstruction Book for details.

Programmable I/O

LED Targets

Metering

Sequence of EventsLogging

Waveform Capture

User Interface with PC

Communications(MODBUS, Ethernet)

On Board HMI

Relay Beckwith M-3425A

Page 41: Generator Protection Gers

IEEE Devices used in Generator Protection

Negative sequence overcurrent protection46Loss of Field protection 40Overpower, Low Forward protection32F, 32LFReverse Power protection32R

100% Stator Ground Fault protection using 3rd Harmonic Undervoltage Differential27TN

Phase Undervoltage protection27Sync-check25Overexcitation / Volts per Hertz protection24Phase Distance protection21DESCRIPTIONNo.

Page 42: Generator Protection Gers

IEEE Devices used in Generator Protection

VT Fuse-loss detection and blocking60FL

100% Stator Ground Fault protection using 3rd Harmonic Voltage Comparison59D

Overvoltage protection59

Inverse Time Overcurrent protection with Voltage Control/Restraint51V

AC Inverse Time Overcurrent protection51Breaker Failure50BFInadvertent Generator Energizing protection50/27Split Phase Differential protection50DTInstantaneous AC Overcurrent protection50

DESCRIPTIONNo.

Page 43: Generator Protection Gers

IEEE Devices used in Generator Protection

Ground Differential protection87GDGenerator Phase Differential protection87Rate of Change Frequency protection81ROver/Under Frequency protection81Out-of-step protection78AC Directional Neutral Overcurrent protection67N100% Stator Ground Protection by Low Frequency Injection64SBrush Lift-Off Detection64BField Ground protection64FDESCRIPTIONNo.

Page 44: Generator Protection Gers

Distance Protection (21)Distance Protection (21)

Page 45: Generator Protection Gers

Distance ProtectionDistance Protection

Distance relaying with mho characteristics is commonly used for system phase-fault backup.

These relays are usually connected to receive currents from current transformers in the neutral ends of the generator phase windings and potential from the terminals of the generator.

If there is a delta grounded-wye step-up transformer between the generator and the system, special care must be taken in selecting the distance relay and in applying the proper currents and potentials so that these relays see correct impedances for system faults.

Page 46: Generator Protection Gers

• Phase distance backup protection may be prone to tripping on stable swings and load encroachment

- Employ three zones

• Z1 can be set to reach 80% of impedance of GSU for 87G back-up.

• Z2 can be set to reach 120% of GSU for station bus backup, or or to overreach remote bus for system fault back up protection. Load encroachment blinder provides security against high loads with long reach settings.

• Z3 may be used in conjunction with Z2 to form out-of-step blocking logic for security on power swings oror to overreach remote bus for system fault back up protection. Load encroachment blinder provides security against high loads with long reach settings.

- Current threshold provides security against loss ofpotential (machine off line)

Phase Distance (21)

Page 47: Generator Protection Gers

3-Zone 21 Function with OSB/Load Encroachment

Page 48: Generator Protection Gers

+X

-X

+R-R

XL

XT

Z1

Z2

Z3

LoadBlinder

Power Swing orLoad Encraochment

FaultImpendance

Z1, Z2 and Z3 used to tripZ1 set to 80% of GSU, Z2 set to 120% of GSUZ3 set to overreach remote bus

(for Z1, Z2, Z3)

21 – Distance element

Power Swing orLoad Encroachment

Page 49: Generator Protection Gers

21 – Distance Element

+X

-X

+R-R

XL

XT

Z1

Z2

Z3

LoadBlinder

Power Swing orLoad Encraochment

FaultImpendance

Z1 and Z2 used to tripZ1 set to 80% of GSU, Z2 set to overreach remote busZ3 used for power swing blocking; Z3 blocks Z2

(for Z1 & Z2)

Page 50: Generator Protection Gers

Distance ProtectionDistance ProtectionSettings summary per IEEE C37.102-2005

Zone-1 = the smaller of the two following criteria:1. 120% of unit transformer2. 80% of Zone 1 reach setting of the line relay on the shortest

line (neglecting in-feed); Time = 0.5 s

Zone-2 = the smaller of the three following criteria:A. 120% of longest line (with in-feed).B. 50% to 66.7% of load impedance (200% to 150% of the

generator capability curve) at the RPFC. 80% to 90% of load impedance (125% to 111% of the

generator capability curve) at the maximum torque angle; Zone-2 < 2Z maxload @ RPFTime > 60 cycles

Page 51: Generator Protection Gers

Distance ProtectionDistance Protection

Page 52: Generator Protection Gers

Overexcitation/ Volts per Hertz Overexcitation/ Volts per Hertz (24)(24)

Page 53: Generator Protection Gers

Overexcitation/VoltsOverexcitation/Volts per Hertzper Hertz

PHYSICAL INSIGHTS• As voltage rises above rating leakage flux increases• Leakage flux induces current in transformer support

structure causing rapid localized heating.

Page 54: Generator Protection Gers

Overexcitation/ Volts per HertzOverexcitation/ Volts per Hertz

GENERATORTRANSFORMER ≈EXCITATION

Voltage V

Freq. Hz

GENERATOR LIMITS (ANSI C 50.13)Full Load V/Hz = 1.05 puNo Load V/Hz = 1.05 pu

TRANSFORMER LIMITSFull Load V/Hz = 1.05 pu (HVTerminals)No Load V/Hz = 1.10 pu (HV Terminals)

Page 55: Generator Protection Gers

Overexcitation/Volts per HertzOverexcitation/Volts per HertzTypical Curves

Page 56: Generator Protection Gers

Overexcitation/Volts per HertzOverexcitation/Volts per Hertz

Example of inverse volts/hertz setting

Page 57: Generator Protection Gers

Overexcitation/ Volts per HertzOverexcitation/ Volts per Hertz

Settings summary per IEEE C37.102

Single relay: PU = 110% p.u. time = 6 sTwo stages relay: alarm pu = 110%; 45< t < 60 s

trip pu = 118% - 120%, 2< t < 6s

Page 58: Generator Protection Gers

Overexcitation/Volts per HertzOverexcitation/Volts per Hertz

Overfluxing Capability, Diagram 3Siemens V84.3 165 MW Generator 12/1/94 MET-ED, FPC

Page 59: Generator Protection Gers

SynchronizingSynchronizing(25)(25)

Page 60: Generator Protection Gers

SynchronizingSynchronizing

Improper synchronizing of a generator to a system may result in damage to the generator step-up transformer and any type of generating unit.

The damage incurred may be slipped couplings, increased shaft vibration, a change in bearing alignment, loosened stator windings, loosened stator laminations and fatigue damage to shafts and other mechanical parts.

In order to avoid damaging a generator during synchronizing, the generator manufacturer will generally provide synchronizing limits in terms of breaker closing angle and voltage matching.

Page 61: Generator Protection Gers

Settings summary per IEEE C37.102

Breaker closing angle: within ± 10 elect. degreesVoltage matching: 0 to +5%Frequency difference < 0.067 Hz

SynchronizingSynchronizing

Page 62: Generator Protection Gers

UndervoltageUndervoltage(27)(27)

Page 63: Generator Protection Gers

UndervoltageUndervoltage

Generators are usually designed to operate continuously at a minimum voltage of 95% of its rated voltage, while delivering rated power at rated frequency.

Operating generator with terminal voltage lower than 95% of its rated voltage may result in undesirable effects such as reduction in stability limit, import of excessive reactive power from the grid to which it is connected, and malfunctioning of voltage sensitive devices and equipment.

Page 64: Generator Protection Gers

Settings summary per IEEE C37.102Relays with inverse time characteristic and instantaneous

PU : 90%Vn; t= 9.0 s at 90% of PU settingInst : 80% Vn

Relays with definite time characteristic and two stages

Alarm PU : 90%Vn; 10< t < 15 sTrip PU : 80% Vn; time: 2s

UndervoltageUndervoltage

Page 65: Generator Protection Gers

Reverse PowerReverse Power(32)(32)

Page 66: Generator Protection Gers

Reverse PowerReverse Power

Prevents generator from motoring on loss of prime moverFrom a system standpoint, motoring is defined as the flow of real power into the generator acting as a motor. With current in the field winding, the generator will remain in synchronism with the system and act as a synchronous motor. If the field breaker is opened, the generator will act as an induction motor.A power relay set to look into the machine is therefore used on most units. The sensitivity and setting of the relay is dependent upon the type of prime mover involved.

Page 67: Generator Protection Gers

Settings summary per IEEE C37.102

Pickup setting should be below the following motoring limits:

Gas : 50% rated power; time < 60 sDiesel : 25% rated power; time < 60 sHydro turbines : 0.2% - 2% rated power; time < 60 sSteam turbines : 0.5% - 3% rated power; time < 30 s

Reverse PowerReverse Power

Page 68: Generator Protection Gers

Sequential TrippingSequential Tripping

Used on steam turbine generators to prevent overspeed

Recommended by manufacturers of steam turbine generators as a result of field experience

This trip mode used only for boiler/reactor or turbine mechanical problems

Electrical protection should not trip through this mode

Page 69: Generator Protection Gers

Sequential TrippingSequential Tripping

STEP 1Abnormal turbine/boiler/reactor condition is detected

STEP 2Turbine valves are closed; generator allowed to briefly “motor” (I.e., take in power)

STEP 3A reverse power (32) relay in series with turbine valves position switches confirms all valves have closed

STEP 4Generator is separated from power system

Page 70: Generator Protection Gers

Sequential Tripping LogicSequential Tripping Logic

Page 71: Generator Protection Gers

Sequential Tripping ProblemSequential Tripping Problem

CONSIDER

High MVArs (out)

Low MW (in)

E-M relay can be fooled

Page 72: Generator Protection Gers

LossLoss--ofof--Field Field (40)(40)

Page 73: Generator Protection Gers

Loss of FieldLoss of Field

CAUSES

• Field open circuit

• Field short circuit

• Accidental tripping of field breaker

• Regulator control failure

• Loss of main exciter

Page 74: Generator Protection Gers

Loss of FieldLoss of Field

Page 75: Generator Protection Gers

Transformation from KWTransformation from KW--KVARKVARplot to Rplot to R--X PlotX Plot

Machine Capability Curve R-X Plot

Page 76: Generator Protection Gers

Loss of FieldLoss of Field

Loss of Field Impedance Characteristics

Page 77: Generator Protection Gers

Settings summary per IEEE C37.102

UNIT 1Offset: X'd/2; Diameter: 1.0 pu; time: 0.1 s

UNIT 2Offset: X'd/2; Diameter: Xd; time: 0.5 to 0.6 s

Loss of FieldLoss of Field

Page 78: Generator Protection Gers

Loss of FieldLoss of Field

Protective Approach # 1

Page 79: Generator Protection Gers

Loss of FieldLoss of Field

Protective Approach # 2

Page 80: Generator Protection Gers

Graphical Method For SteadyGraphical Method For Steady--state state StabilityStability

The Steady-State Stability limit can be a significant limit that should be related to both the machine capability curve (MW-MVAR Plot) and the loss-of-field (40) relay operating characteristics (R-X Diagram Plot). In the figures below, V is the per-unit terminal generator voltage, XT and Xs the per-unit Generator Step Up (GSU) transformer and system impedances respectively as viewed from the generator terminals. Xd is the per-unit unsaturated synchronous reactance of the generator. All reactances should be placed on the generator MVA base.

Page 81: Generator Protection Gers

Negative SequenceNegative Sequence(46)(46)

Page 82: Generator Protection Gers

• Unbalanced phase currents create negative sequence current in generator stator

• Negative sequence current interacts with normal positive sequence current to induce a double frequency current (120 Hz)

• Current (120 Hz) is induced into rotor causing surface heating• Generator has established short-time rating,

l22t=Kwhere K=Manufacturer Factor (the larger the

generator the smaller the K value)

Negative SequenceNegative Sequence

Page 83: Generator Protection Gers

Negative SequenceNegative Sequence

TYPE OF GENERATORPERMISSIBLE l2

PERCENT OF STATOR RATING

Salient Pole

With connected amortisseur windings 10

With non-connected amortisseur windings 5

Cylindrical Rotor

Indirectly cooled 10

Directly cooled to 960 MVA 8

961 to 1200 MVA 6

1200 to 1500 MVA 5

†These values also express the negative-phase –sequence current capability at reduced generator KVA capabilities.

‡ The short time (unbalanced fault) negative sequence capability of a generator is also defined in ANSI C50.13.

Settings summary per IEEE C37.102

Page 84: Generator Protection Gers

Negative SequenceNegative SequenceType of Generator Permissible l22t

Salient pole generator 40

Synchronous condenser 30

Cylindrical rotor generators

Indirectly cooled 30

Directly cooled (0-800 MVA) 10

Directly cooled (801-1600 MVA) see curve below

(VALUES TAKENFROM ANSI C50.13-1989)

Page 85: Generator Protection Gers

Split PhaseSplit PhaseDifferentialDifferential

(50DT)(50DT)

Page 86: Generator Protection Gers

• Most turbine generators have single turn stator windings. If a generator has stator windings with multiturn coils and with two or more circuits per phase, the split-phase relaying scheme may be used to provide turn fault protection.

• In this scheme, the circuits in each phase of the stator windingare split into two equal groups and the currents of each group are compared.

• A difference in these currents indicates an unbalance caused by a single turn fault.

SplitSplit--Phase DifferentialPhase Differential

Page 87: Generator Protection Gers

SplitSplit--Phase DifferentialPhase Differential

• Scheme detects turn to turn fault not involving ground.

• Generator must have two or more windings per phase to apply scheme.

• Used widely on salient-pole hydro generators. Used on some steam generators.

• Difference between current on each phase indicates a turn to turn fault.

• Need to have separate pick-up levels on each phase to accommodate practice of removal of shorted terms.

Page 88: Generator Protection Gers

Typical SplitTypical Split--Phase Differential Using Window Phase Differential Using Window CTCT’’ss

Page 89: Generator Protection Gers

SplitSplit--phase protection using a single window phase protection using a single window current transformercurrent transformer

Settings summary per IEEE C37.102

The pickup of the instantaneous unit must be set above CT error currents that may occur during external faults.

Page 90: Generator Protection Gers

Inadvertent OffInadvertent Off--Line Generator Line Generator ProtectionProtection

(50/27)(50/27)

Page 91: Generator Protection Gers

Why Inadvertent Energizing OccursWhy Inadvertent Energizing Occurs

• Operating errors• Breaker head flashover• Control circuit malfunctions• Combination of above

Page 92: Generator Protection Gers

Inadvertent Energizing ProtectionInadvertent Energizing Protection

Inadvertent energizing is a serious industry problem

Damage occurs within seconds

Conventional generator protection will not provide protection

- marginal in detecting the event

- disabled when machine is inadvertently energized

- operates too slowly to prevent damage

Need to install dedicated protection scheme

Page 93: Generator Protection Gers

Generator Response and Damage to Generator Response and Damage to ThreeThree--Phase EnergizingPhase Energizing

Generator behaves as an induction motor

Rotating flux induced into the generator rotor

Resulting rotor current is forced into negative sequence path in rotor body

Machine impedance during initial energizing is equivalent to its negative sequence impedance

Rapid rotor heating occurs l2t = K

Page 94: Generator Protection Gers

Inadvertent Energizing Equivalent CircuitInadvertent Energizing Equivalent Circuit

Page 95: Generator Protection Gers

Response of Conventional Generator Response of Conventional Generator Protection to Inadvertent EnergizingProtection to Inadvertent Energizing

Some relays may detect inadvertent generator energizing but can:

Be marginal in their ability to detect the condition

Operate too slowly to prevent damage

Many times conventional protection is disabled when the unit is off-line

Removal of AC potential transformer fuses or links

Removal of D.C. control power

Auxiliary contact (52a) of breaker of switches can disable tripping

Page 96: Generator Protection Gers

Dedicated Protection Schemes toDedicated Protection Schemes toDetect Inadvertent EnergizingDetect Inadvertent Energizing

Frequency supervised overcurrent scheme

Voltage supervised overcurrent scheme

Directional overcurrent scheme

Impedance relays scheme

Auxiliary contact enabled overcurrent scheme

Page 97: Generator Protection Gers

Inadvertent Energizing ProtectionInadvertent Energizing Protection

*Positive Sequence Voltage

Page 98: Generator Protection Gers

Settings summary per IEEE C37.102

50: P.U ≤ 50% of the worst-case current value and should be < 125% generator rated current.

27: 70% Vn, time: 1.5 s

Inadvertent Energizing ProtectionInadvertent Energizing Protection

Page 99: Generator Protection Gers

Generator Circuit Breaker Generator Circuit Breaker FailureFailure(50BF)(50BF)

Page 100: Generator Protection Gers

Generator Circuit Breaker FailureGenerator Circuit Breaker FailureIf a breaker does not clear the fault or abnormal condition in aspecified time, the timer will trip the necessary breakers to remove the generator from the system. To initiate the breaker-failure timer, a protective relay must operate and a current detector or a breaker "a" switch must indicate that the breaker has failed to open, as shown in the Figure.

Page 101: Generator Protection Gers

Generator Circuit Breaker FailureGenerator Circuit Breaker Failure

Functional diagram of alternate generator breaker failure scheme

Page 102: Generator Protection Gers

Settings summary per IEEE C37.102

Current detector PU: should be more sensitive than the lowest current present during fault involving currents.

Timer: > Gen breaker interrupting time + Current detector dropout time + safety margin

Generator Circuit Breaker FailureGenerator Circuit Breaker Failure

Page 103: Generator Protection Gers

Overcurrent Protection Overcurrent Protection (50/51)(50/51)

Page 104: Generator Protection Gers

Overcurrent ProtectionOvercurrent Protection

In some instances, generator overload protection may be provided through the use of a torque controlled overcurrent relay that is coordinated with the ANSI C50.13-2004 short-time capability curve

This relay consists of an instantaneous overcurrent unit and a time overcurrent unit having an extremely inverse characteristic.

An overload alarm may be desirable to give the operator an opportunity to reduce load in an orderly manner.

This alarm should not give nuisance alarms for external faults and should coordinate with the generator overload protection if this protection is provided.

Page 105: Generator Protection Gers

Overcurrent ProtectionOvercurrent Protection

Turbine-generator short-time thermal capability for balanced3-phase loading (From ANSI C50.13-2004)

Page 106: Generator Protection Gers

Settings summary per IEEE C37.102

51PU: 75-100% FLC, time: 7 s at 226% FLC. Where FLC: full load current.

50PU: 115% FLC, time: instantaneousDropout: 95% of 50PU or higher

Overcurrent ProtectionOvercurrent Protection

Page 107: Generator Protection Gers

Voltage Controlled or Voltage Voltage Controlled or Voltage Restrained Time OvercurrentRestrained Time Overcurrent

(51 V)(51 V)

Page 108: Generator Protection Gers

Voltage Controlled or Voltage Voltage Controlled or Voltage Restrained Time OvercurrentRestrained Time Overcurrent

Faults close to generator terminals may result in voltage drop and fault current reduction, especially if the generators are isolated and the faults are severe.

Therefore, in generation protection it is important to have voltage control on the overcurrent time-delay units to ensure proper operation and co-ordination.

These devices are used to improve the reliability of the relay by ensuring that it operates before the generator current becomes too low.

There are two types of overcurrent relays with this feature –voltage-controlled and voltage-restrained, which are generally referred to as type 51V relays.

Page 109: Generator Protection Gers

Voltage Controlled or Voltage Voltage Controlled or Voltage Restrained Time OvercurrentRestrained Time Overcurrent

The voltage-controlled (51/27C) feature allows the relays to be set below rated current, and operation is blocked until the voltage falls well below normal voltage.

The voltage-controlled approach typically inhibits operation until the voltage drops below a pre-set value.

It should be set to function below about 80% of rated voltage with a current pick-up of about 50% of generator rated current.

Page 110: Generator Protection Gers

Voltage Controlled or Voltage Voltage Controlled or Voltage Restrained Time OvercurrentRestrained Time Overcurrent

The voltage-restrained (51/27R) feature causes the pick-up to decrease with reducing voltage, as shown in Figure.

For example, the relay can be set for 175% of generator rated current with rated voltage applied. At 25% voltage the relay picks up at 25% of the relay setting (1.75 × 0.25 = 0.44 times rated).

The varying pick-up level makes it more difficult to co-ordinate the relay with other fixed pick-up overcurrent relays.

Page 111: Generator Protection Gers

Settings summary per IEEE C37.102Voltage Controlled:

Overcurrent PU: 50% FLCControl voltage: 75%VNOM.Inverse time curve and dial settings should be set to coordinate with system line relays for close-in faults on the transmission lines at the plant.

Voltage Restrained:Overcurrent PU: 150% FLC at rated voltageInverse time curve and dial settings should be set to coordinate with system line relays for close-in faults on the transmission lines at the plant.

Voltage Controlled or Voltage Voltage Controlled or Voltage Restrained Time OvercurrentRestrained Time Overcurrent

Page 112: Generator Protection Gers

Overvoltage (59)Overvoltage (59)

Page 113: Generator Protection Gers

Generator overvoltage may occur without necessarily exceeding the V/Hz limits of the machine.

Protection for generator overvoltage is provided with a frequency-compensated (or frequency insensitive) overvoltage relay.

The relay should have both an instantaneous unit and a time delay unit with an inverse time characteristic.

Two definite time delay relays can also be applied.

OvervoltageOvervoltage

Page 114: Generator Protection Gers

Settings summary per IEEE C37.102

Relays with inverse time characteristic and instantaneousPU : 110%Vn; t= 2.5 s at 140% of PU settingInst : 130 - 150% Vn

Relays with definite time characteristic and two stagesAlarm PU : 110%Vn; 10< t < 15 sTrip PU : 150% Vn; time: 2s

OvervoltageOvervoltage

Page 115: Generator Protection Gers

100% Stator Ground100% Stator Ground(59N/27TH)(59N/27TH)

Page 116: Generator Protection Gers

Stator Ground ProtectionStator Ground ProtectionProvides protection for stator ground fault on generators which are high impedance groundedUsed on unit connected generatorsGround current limited to about 10A primary

Provides 100% stator ground protection (entire winding)

High Impedance Grounding

Page 117: Generator Protection Gers

3rd Harmonic Comparator for 100% 3rd Harmonic Comparator for 100% Stator Ground Fault ProtectionStator Ground Fault Protection

• 3rd harmonic levels change with position of ground fault and loading

• Using a comparator technique of 3rd harmonic voltages at line and neutral ends allows an overvoltage element to be applied

Page 118: Generator Protection Gers

Third-Harmonic Undervoltage Ground-Fault Protection Scheme

100% Stator Ground Fault (59N/27TN)

Page 119: Generator Protection Gers

Settings summary per IEEE C37.102

59G element: Pickup = 5 V; t = 5 s Note: Time setting must be selected to provide coordination with other system protective devices.

27TH element: Pickup = 50% of minimum normal generator 3rd harmonic. t = 5 s

Stator GroundStator Ground

Page 120: Generator Protection Gers

Field GroundField Ground(64F)(64F)

Page 121: Generator Protection Gers

Field (Rotor) Ground Fault ProtectionField (Rotor) Ground Fault Protection

The field circuit of a generator is an ungrounded system. As such, a single ground fault will not generally affect the operation of a generator.

However, if a second ground fault occurs, a portion of the field winding will be short circuited, thereby producing unbalanced air gap fluxes in the machine.

These unbalanced fluxes may cause rotor vibration that may quickly damage the machine; also, unbalanced rotor winding and rotor body temperatures caused by uneven rotor winding currents may cause similar damaging vibrations.

Page 122: Generator Protection Gers

Field (Rotor) Ground Fault ProtectionField (Rotor) Ground Fault ProtectionThe probability of the second ground occurring is greater than the first, since the first ground establishes a ground reference for voltages induced in the field by stator transients, thereby increasing the stress to ground at other points on the field winding.

On a brushless excitation system continuous monitoring for field ground is not possible with conventional field ground relays since the generator field connections are contained in the rotating element.

Insurance companies consider this is the most frequent internal generator fault

Review existing 64F voltage protection methods

Page 123: Generator Protection Gers

Typical Generator Field CircuitTypical Generator Field Circuit

A single field ground fault will not:affect the operation of a generatorproduce any immediate damaging effects

Page 124: Generator Protection Gers

Typical Generator Field CircuitTypical Generator Field Circuit

The first ground fault will:establish a ground reference making a second ground fault more likelyincrease stress to ground at other points in field winding

Ground #1

Page 125: Generator Protection Gers

Typical Generator Field CircuitTypical Generator Field Circuit

The second ground fault will:short out part of field winding causing unit vibrationscause rotor heating from unbalanced currentscause arc damage at the points of fault

Ground #2

Ground #1

Page 126: Generator Protection Gers

Detection Using a DC SourceDetection Using a DC Source

A dc voltage source in series with an overvoltage relay coil is connected between the negative side of the generator field winding and ground.

A ground anywhere in the field will cause the relay to operate.

Page 127: Generator Protection Gers

Detection Using a Voltage DividerDetection Using a Voltage Divider

This method uses a voltage divider and a sensitive overvoltagerelay between the divider midpoint and ground.

A maximum voltageis impressed on the relay by a ground on either the positive or negative side of the field circuit.

This generator field ground relay is designed to overcome the null problem by using a nonlinear resistor (varistor) in series with one of the two linear resistors in the voltage divider.

Page 128: Generator Protection Gers

Detection Using Pilot BrushesDetection Using Pilot Brushes

The addition of a pilot brush or brushes is to gain access to the rotating field parts.

Normally this is not done since eliminating the brushes is one of the advantages of a brushless system.

A ground fault shorts out the field winding to rotor capacitance, CR, which unbalances the bridge circuit.

If a voltage is read across the 64F relay, then a ground exists

Detection systems may be used to detect field grounds if a collector ring is provided on the rotating shaft along with a pilot brush that may be periodically dropped to monitor the system.

Page 129: Generator Protection Gers

Detection Using Pilot BrushesDetection Using Pilot Brushes

The brushes used in this scheme are not suitable for continuouscontact with the collector rings.

Page 130: Generator Protection Gers

Field Ground Detection for Brushless Field Ground Detection for Brushless Machines LED CommunicationsMachines LED Communications

Page 131: Generator Protection Gers

Field Ground Detection for Brushless Field Ground Detection for Brushless Machines with Infrared LED Machines with Infrared LED

CommunicationsCommunicationsThe relay's transmitter is mounted on the generator fielddiode wheel.

Its source of power is the ac brushless exciter system. Twoleads are connected to the diode bridge circuit of the rotatingrectifier to provide this power.

Ground detection is obtained by connecting one lead of thetransmitter to thenegative bus of the field rectifier and theground lead to the rotor shaft.

Sensing current is determined by the field ground resistanceand the location of a fault with respect to the positive andnegative bus.

Page 132: Generator Protection Gers

Field Ground Detection for Brushless Field Ground Detection for Brushless Machines with Infrared LED Machines with Infrared LED

CommunicationsCommunications

The transmitter Light Emitting Diodes (LEDs) emit light for normal conditions.

The receiver's infrared detectors sense the light signal from the LED across the air gap.

Upon detection of a fault, the LED's are turned off. Loss of LED light to the receiver will actuate the ground relay and initiate a trip or alarm

Page 133: Generator Protection Gers

Using Injection Voltage SignalUsing Injection Voltage Signal

Page 134: Generator Protection Gers

Using Injection Voltage SignalUsing Injection Voltage Signal

In addition, digital relays may provide real-time monitoring of actual insulation resistance so deterioration with time may be monitored.

The passive coupling network is used to isolate high dc field voltages from the relay.

Backup protection for the above described schemes usually consists of vibration detecting equipment.

Contacts are provided to trip the main and field breakers if vibration is above that associated with normal short circuit transients for faults external to the unit.

Page 135: Generator Protection Gers

Settings summary per IEEE C37.102

Field ground detection using DC a source: 1< t <3 s

Field ground detection for Brushless Machines with infrared LED communications: time up to 10 s

Field ground detection using low frequency square wave voltage injection: ALARM = 20 kΩ

TRIP = 5 kΩ

Field (Rotor) Ground Fault ProtectionField (Rotor) Ground Fault Protection

Page 136: Generator Protection Gers

Generator OutGenerator Out--OfOf--StepStepProtection (OSP)Protection (OSP)

(78)(78)

Page 137: Generator Protection Gers

When is OSP needed?When is OSP needed?

1. When critical switching times are short enough to warrant concern that backup clearing of a system fault could exceed critical switching time.

2. This swing locus passes through the generator or GSU

3. Credible loss of transmission lines could result in high transfer reactance between the generator and the power system

Page 138: Generator Protection Gers

Power system stability enables the synchronous machines of a system to respond to a disturbance such as transmission system faults, sudden load changes, loss of generating units or line switching.

Loss of synchronism is produced when the angle of the EMF of a machine increases to a level that does not allow any recovery of the plant when the machine is said to have reached a slip.

Transient stability studies allow to determine if the system will remain in synchronism following major disturbance

BackgroundBackground

Page 139: Generator Protection Gers

• During power system disturbances, the voltage and current which feed the relays vary with time and, as a result, the relays will also see an impedance that is varying with time.

• Certain power system disturbances may cause loss of synchronism between a generator and the rest of the utility system, or between neighboring utility interconnected power systems.

• If such a loss of synchronism occurs, it is imperative that the generator or system areas operating asynchronously are separated immediately through controlled islanding of the power system using out-of-step protection systems-OST.

• OST systems must be complemented with Power Swing Blocking (PSB) of distance relay elements prone to operate during unstable power swings. PSB prevents system separation from occurring at any locations other than the pre-selected ones.

OST & PSB Functions

Page 140: Generator Protection Gers

Power Transfer Equation

VS x VRP =

XSinδ

Page 141: Generator Protection Gers

Two-Machine System

P

VSVS VR90° &Constant

δ

VS x VRP =

XSinδ

Page 142: Generator Protection Gers

Effect of Faults on Power Transfer

Angular D isplacem ent in Degrees

Pe

rU

nit

To

r qu

eo

rP

ow

er

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180

T

L-L Fault

L-G Fault

Faulty Lin eSw itched O u t

Before Fau lt

L-L-G F ault0

3 ø Fau lt

Page 143: Generator Protection Gers

Network with Three Phase Fault

S

S'S

A

Fault

BV ‘

R

R'RV '

Pn

3∅

Page 144: Generator Protection Gers

Power Transfer Curve

Angle m

PD

45 90 135 180

Steady State LoadRequirements andMechanical InputTo Generators

U

Before Fault

InitialOperatingPoint

Tran

smitt

edPo

wer

E

A and BBreakers Closed

H

G

F

A Breaker OpenB Breaker Closed

During 3 Fault∅

N

Line A-B Open

J

I

L

K

FinalOperatingPoint

II

Page 145: Generator Protection Gers

• Ways the protection system can mitigate the affect of the fault on power swings.

• Fast clearing• Pilot systems• Breaker failure systems• Single pole tripping• High speed reclosing • Load shedding

Power Transfer Curve

Page 146: Generator Protection Gers

Impedances Seen by Relays

Page 147: Generator Protection Gers

Impedances Seen by Relays

δ

Page 148: Generator Protection Gers

Impedances Seen by Relays

δ

Page 149: Generator Protection Gers

Basics of Power Swing Blocking

V

Increase in when

R

LZ

S

S

A

SS

ISAV /

IV

S

by the relayImpedance seen

O

SI

Q

X

R

V

S R

R

V = VS

δ

δ

B

V

Increase in when

R

LZ

S

S

A

SS

ISAV /

IV

S

by the relayImpedance seen

O

SI

Q

X

R

V

S R

R

V = VS

δ

δ

B

Page 150: Generator Protection Gers

Basics of Power Swing Blocking

Power oscillation

Blocking relaycharacteristic

s rwith V >V

Load characteristic

Zone 2

Zone 3Measuring unit

Page 151: Generator Protection Gers

Basics of Out of Step Protection

• The Out-of-Step function (78) is used to protect the generator from out-of-step or pole slip conditions.

• There are different ways to implement Out of Step Protection.

• One of the commonest types uses one set of blinders, along with a supervisory MHO element.

Page 152: Generator Protection Gers

Basics of Out of Step Protection

•The pickup area is restricted to the shaded area, defined by theinner region of the MHO circle, the region to the right of the blinder A and the region to the left of blinder B.

Page 153: Generator Protection Gers

For operation of the blinder scheme :

The positive sequence impedance must originate outside either blinder A or B,

It should swing through the pickup area and progress to the opposite blinder from where the swing had originated.

The swing time should be greater than the time delay setting

When this scenario happens, the tripping circuit is complete. The contact will remain closed for the amount of time set by the seal-in timer delay.

Basics of Out of Step Protection

Page 154: Generator Protection Gers

Unstable

Stable

Generator Out-of-Step Protection (OSP)

X’d XT XS

Page 155: Generator Protection Gers

A B

D

P

MR

Swing Locus

ELEMENTMHO

X

d

δ

C

ELEMENTSBLINDER

ELEMENTPICK-UP

ELEMENTPICK-UP

A B

1.5 XTG

2X d

X maxSG1

SYSTEM

O

TRANSTGX

O

GENdX´

Setting of 78 Relays

Page 156: Generator Protection Gers

Settings summary per IEEE C37.102-2005Mho Diameter : 2X'd + 1.5 XTG

d = ((X'd + XTG + XmaxSG1)/2) x tan (90-(δ/2))where d: Blinder distance

δ: angular separation between generator and the system which the relay determines instability. If there is not stability study available δ = 120º

t = as per transient stability study typically 40 < t < 100 ms

Setting of 78 Relays

Page 157: Generator Protection Gers

Frequency (81)

Page 158: Generator Protection Gers

The operation of generators at abnormal frequencies (either overfrequency or underfrequency) generally results from full or partial load rejection or from overloading of the generator.

Load rejection will cause the generator to overspeed and operate at some frequency above normal

Steam and gas turbines are more limited or restrictive to abnormal frequency than hydrogenerators.

At some point abnormal frequency may impact turbine blades and result in damage to the bearings due to vibration.

Frequency

Page 159: Generator Protection Gers

Settings summary per IEEE C37.102It is important to consult turbine manufacturer and get turbine off frequency operating curves or limitsUnder frequency:

81U ALARM: 59.5 Hz time: 10 s81U TRIP :

The generator 81U relay should be set below the pick-up of under frequency load shedding relay set-point and above the off frequency operating limits of steam turbine.

Over frequency:81O ALARM

Pick-up: 60.6 Hz, Time Delay 5 sec.

FrequencyFrequency

Page 160: Generator Protection Gers

Phase DifferentialPhase Differential(87)(87)

Page 161: Generator Protection Gers

Phase DifferentialPhase DifferentialFast response time (under 1 – ½ cycle)Percentage differential with adjustable slope

Page 162: Generator Protection Gers

Settings summary per IEEE C37.102

PU : 0.3 A

Slope1 : 10%

time: Instantaneous

Phase DifferentialPhase Differential

Page 163: Generator Protection Gers

Typical Settings of Generator Relays

Relays with inverse time charac and instantaneousPU : 90%Vn; t= 9.0 s at 90% of PU settingInst : 80% VnRelays with definite time charac and 2 stagesAlarm PU : 90%Vn; 10< t < 15 sTrip PU : 80% Vn; time: 2s

A.2.13Undervoltage27

Breaker closing angle: within ± 10 elect. DegreesVoltage matching: 0 to +5%Frequency difference < 0.067 Hz

5.7Sync-check25

Single relay: PU = 110% p.u. time = 6 sTwo stages relay: alarm pu = 110%; 45< t < 60 s

trip pu = 118% - 120%, 2< t < 6s4.5.4.2Overexcitation24

Zone-1 = smaller of the two following criteria:1. 120% of unit transformer2. 80% of Zone 1 reach setting of the line relay on the shortest line (neglecting in-feed); time = 0.5 s Zone-2 = the smaller of the three following criteria:A. 120% of longest line (with in-feed). If the unit is connected to a breaker and a half bus, thiswould be the length of the adjacent line.B. 50% to 66.7% of load impedance (200% to 150% of the generator capability curve) at the RPFAC. 80% to 90% of load impedance (125% to 111% of the generator capability curve) at themaximum torque angle; time > 60 cyclesZone-2 < 2Z maxload @ RPF

A.2.3Distance 21

DESCRIPTIONSECTION

Per IEEE C37.102FUNCTIONIEEE No.

Table 1 - Recommended Settings

Page 164: Generator Protection Gers

Typical Settings of Generator Relays

Pickup setting should be below the permissible I2percent expressed in percent of rated current, which are indicated below:Salient pole w/connected amortisseur windings: 10%Salient pole non-connected amortisseur windings: 5%Cylindrical rotor indirectly cooled: 10%Directly cooled up to 960 MVA: 8%Directly cooled 961 to 1200 MVA: 6%Directly cooled 961 to 1200 MVA: 6%Directly cooled 1201 to 1500 MVA: 5%Permissible K (I22 x t)Salient pole generator: 40Synchronous condenser: 30Cylindrical rotor indirectly cooled: 30Directly cooled: 10

4.5.2Negative Sequence Overcurrent46

UNIT 1Offset: X'd/2; Diameter: 1.0 pu; time: 0.1 sUNIT 2Offset: X'd/2; Diameter: Xd; time: 0.5 to 0.6 s

4.5.1.3Loss-of-field40

Pickup setting should be below the following motoring limits:Gas : 50% rated power; time < 60 sDiesel : 25% rated power; time < 60 sHydro turbines : 0.2% - 2% rated power; time < 60 sSteam turbines : 0.5% - 3% rated power; time < 30 s

4.5.5.3 & A.2.9Reverse Power32

DESCRIPTIONSECTION

Per IEEE C37.102FUNCTIONIEEE No.

Table 1 - Recommended Settings

Page 165: Generator Protection Gers

Typical Settings of Generator Relays

Stator Ground Over-current(High Z Gnd)51GN, 51N

Stator Ground Over-current(Low, Med Z Gnd, Neutral CT or Flux Summation CT)

50/51N

Stator Ground Over-current (Low,Med Z Gnd,Phase CT Residual)51N

Current detector PU: should be more sensitive than the lowest current present during fault involving currents.Timer > Gen breaker int time + Curr det. dropout time + safety margin

A.2.11Generator Breaker Failure Protection50 BF

50: P.U ≤ 50% of the worst-case current value andshould be < 125% generator rated current.

27: 70% Vn, time: 1.5 sA.2.4

Inadvertent EnergizationOvercurrent with 27, 81 Supervision

50/27

The pickup of the instantaneous unit must be set above CT error currents that may occur during external faults.4.3.2.5.1Differential via flux summation

CTs or split-phase protection50/87

DESCRIPTIONSECTION

Per IEEE C37.102FUNCTIONIEEE No.

Table 1 - Recommended Settings

Page 166: Generator Protection Gers

Typical Settings of Generator Relays

59G element: Pickup = 5 V; t = 5 sTime setting must be selected to provide coordination with other system protective devices.27TH element: Pickup = 50% of minimum normal generator 3rd harmonic, time = 5 s

4.3.3.1.1 & A.2.7

100% Stator Gound protection(for high impedance grounding generators)

59N,27-TH, 59P

Relays with inverse time charac and instantaneousPU : 110%Vn; t= 2.5 s at 140% of PU settingInst : 130 - 150% VnRelays with definite time charac and 2 stagesAlarm PU : 110%Vn; 10< t < 15 sTrip PU : 150% Vn; time: 2s

4.5.6. & A.2.12Overvoltage59

Overcurrent PU: 150% FLC at rated voltageInverse time curve and dial settings should be set to coordinate with system line relays for close-in faults on the transmission lines at the plant.

A.2.6Voltage Restrained Overcurrent51VR

Overcurrent PU: 50% FLCControl voltage: 75%VNOM.Inverse time curve and dial settings should be set to coordinate with system line relays for close-in faults on the transmission lines at the plant.

A.2.6Voltage Controlled Overcurrent51VC

51PU: 75-100% FLC, time: 7 s at 226% FLC. FLC means full load current.50PU: 115% FLC, time: instantaneous

4.1.1.2Time overcurrent protection(against overloads)50/51

DESCRIPTIONSECTION

Per IEEE C37.102FUNCTIONIEEE No.

Table 1 - Recommended Settings

Page 167: Generator Protection Gers

Typical Settings of Generator Relays

81U ALARM: 59.5 Hz time: 10 s81U TRIP:The generator 81U relay should be set below the pick-up of underfrequency load shedding relay set-point and above the off frequency operating limits of steam turbine.81O ALARM:Pick-up: 60.6 Hz, Time Delay 5 sec.

A.2.14Over/under frequency(60 Hz systems)81

Mho Diameter : 2X'd + 1.5 XTGBlinder distance (d) = ((X'd + XTG + XmaxSG1)/2) x tan (90-(d/2));d: angular separation between generator and the system which the relay determines instability.If there is not stability study availabled = 120ºt = as per transient stability study Typically 40 < t < 100 ms

A.2.2Out of Step78

Directional O/C for Inadvertent Energization67IE

Field ground detection using DC a source: 1< t <3 sField ground detection for Brushless Machines with infrared LED communications: time up to 10 sField ground detection using low frequency suare wave voltage injection: ALARM = 20 kOhm

TRIP = 5 kOhm

4.4Generator Rotor Field protection(rotor ground faults)

64F

DESCRIPTIONSECTION

Per IEEE C37.102FUNCTIONIEEE No.

Table 1 - Recommended Settings

Page 168: Generator Protection Gers

Typical Settings of Generator Relays

Unit Differential87UD

Generator Ground Differential87GN

PU : 0.3 ASlope : 10%time: instantaneous

A.2.5Generator Phase Differential87G

DESCRIPTIONSECTION

Per IEEE C37.102FUNCTIONIEEE No.

Table 1 - Recommended Settings

Page 169: Generator Protection Gers

Types Of Data

• Metering• Function Status• Breaker Monitoring• Fault Reporting• Oscillography• Testing

Page 170: Generator Protection Gers

Metering

Page 171: Generator Protection Gers

Function Status

Page 172: Generator Protection Gers

Phase Distance Monitor

Page 173: Generator Protection Gers

Breaker Monitoring

Page 174: Generator Protection Gers

Fault Reporting

Page 175: Generator Protection Gers

Fault Reporting

Page 176: Generator Protection Gers

Fault Reporting

Page 177: Generator Protection Gers

Oscillography

B C D

K NMLIG H

J

A

E

F

Page 178: Generator Protection Gers

A. All analog traces. This view shows peak values. RMS values mayalso be displayed.

B. Controls for going to the beginning or end of a record, as well as nudging forward or backward in time in a record

C. Zoom controlsD. Display controls for analog traces, RMS traces, fundamental

waveform display, frequency trace, power trace, power factor trace, phasor diagram, impedance diagram and power diagram

E. Marker #1F. Marker #2G. Time at Marker #1H. Time at Marker #2I. Control status input and contact output traces (discrete I/O)J. Scaling for each analog trace. This can be set automatically or

manually adjusted.K. Date and timestamp for recordL. Time of trip commandM. Time at Marker #1N. Time at Marker #2

Page 179: Generator Protection Gers

Oscillography

PQ

R

O

S

Page 180: Generator Protection Gers

O. Drop down window for view selection, diagram selection and zoom

P. Delta value between Marker #1 and Marker #2Q. Value at Marker #1R. Value at Marker #2S. Scaling for each analog trace. This can be set

automatically or manually adjusted.

Page 181: Generator Protection Gers

Waveform Capture: PQ Plot

Page 182: Generator Protection Gers

Communications

Page 183: Generator Protection Gers

Test Report

DATE

TESTED BY:

PROJECT : Meter and relay APROVED BY:

1. GENERAL SETTINGSValue Value1203.98 30050 200

ABC 1005 2600

Enable 25

2. READINGS CHECK

Note: IR, IY, IB = line side currents / Ir, Iy, Ib = generator side currents

0.10%

-0.35%1.85%-1.15%0.00%

C.T. Secundary Rating [A]Delta - Y Transformer

0.08%0.04%0.16%0.10%0.14%

FEBRUARY 26 / 2004

13018

V.T. Phase Ratio

Description Injected Theoretical Value

V YB [V] 120.0

% ErrorObtained Read-0.17%-0.25%24000 23940

V RY [V] 120.0 24000 23960

I R [A] 5.0 13000 13005V BR [V] 120.0 24000 24020

I Y [A] 5.0 13000 13021I B [A] 5.0 13000 13013

13013I r [A] 5.0 13000I y [A] 5.0 13000

0.00%I b [A] 5.0 13000 13000Active Power [W/MW] 900.0 468.00 466.36

Power Factor 0.87 0.87 0.86Reactive Power [VAr/MVAr] 519.6 270.20 275.21

Frequency [Hz] 50.000 50.00 50.00

C.T. Neutral Ratio

Parameter ParameterNominal Voltage [V]Nominal Current [A]

V.T. ConfigurationRelay Seal-in Time [Cycles]

L-G to L-L

Nominal Frequency [Hz]Phase Rotation

GERS BECHTEL LIMITEDTEST REPORT

CONSULTING ENGINEERS R. Bravo - C. Quintero

GENERATOR PROTECTIONtest at Spalding Energy Project A.Tasama - G. WilliamsMANUFACTURER : BECKWITH PANEL TAG: LOCATION : SERIAL NUMBER : CIRCUIT : STG PROT. A

SYSTEM: AC01TYPE: M-3425 GPR STG ELECT BUILDING 1815

V.T. Neutral RatioC.T. Phase Ratio

Page 184: Generator Protection Gers

Test Report

16. FUNCTION 87. PHASE DIFFERENTIAL PROTECTION16.1. Settings

0.3Slope 10%

1

16.2 Function Test% Error

IR 3.33%IY 3.33%IB 3.33%

Slope 1 0.53%Slope 2 0.00%Operation Time [ms] -5.00%

Line current [A] - Fixed IR 0.29 3.00 5.00 7.00 10.50 13.00 15.00Theoretical Values Ir 0.00 2.70 4.52 6.33 7.00 8.67 10.00

Idiff = (IR-Ir) Idiff 0.29 0.30 0.48 0.67 3.50 4.33 5.00Ibias = (IR+Ir)/2 Ibias 0.15 2.85 4.76 6.67 8.75 10.83 12.50

Obtained values Ir 0.00 2.70 4.50 6.30 7.00 8.60 10.00Idiff = (IR-Ir) Idiff 0.29 0.30 0.50 0.70 3.50 4.40 5.00Ibias = (IR+Ir)/2 Ibias 0.15 2.85 4.75 6.65 8.75 10.80 12.50

10.00% 10.53%

Result0.29

Trip output 1Blocking input -

0.290.29

Parameter Theoretical Value

Minimum current for operation [A] 0.30

Parameter ValueMinimum Operation current [A]

Time Delay [Cycles]

40.00% 40.00%20.00 19.00

Differential Characteristic Test

0.0

1.0

2.0

3.0

4.0

5.0

6.0

0 2 4 6 8 10 12 14Bias Current [A]

Diff

eren

tial C

urre

nt [A

]

Obtained Theoretical

Page 185: Generator Protection Gers

Test Report

3. FUNCTION 21. DISTANCE PROTECTION3.1. Settings

3.2 Function Test

Voltage [V LN] FixedCurrent [A] VariedImpedance [Ohms] Calculated

Trip output 1Blocking input 1 & FL

1.18%1.17%

Parameter ValueDiameter [Ohms] 8.50Offset [Ohms] -5.2Impedance Angle [Degrees] 85Time delay [cycles] 50

Parameter Theoretical Value Result % Error20 - -

6.06 5.993.30 3.34

Operation time [s] 1.00 1.01 0.50%