generator protection .pdf

5
Home Articles Add Article Civil & Structure All Electrical Power Systems Electrical Motor Transformer Protection Wiring Design Solar Wind Others Blog Topics Entries My Entries Write Topic Seismic Structure Design Concrete Soil Test Moment & Shearwall Power Systems Substations Transformer Power Protection Transmission Line Power Distribution Motors Forum Electrical Discussion Post New Discussion Civil Discussion Post New Discussion Mechanical Discussion Search... 60

Upload: mohamed-ahmed-fawzy

Post on 17-Sep-2015

226 views

Category:

Documents


8 download

TRANSCRIPT

  • 5/14/2015 Zone4info.comDieselgeneratorprotectionrelay

    http://zone4info.com/forums/topic/6603/dieselgeneratorprotectionrela#.VVOWbmqpHw 1/5

    HomeArticles

    AddArticleCivil&StructureAllElectricalPowerSystemsElectricalMotorTransformerProtectionWiringDesignSolarWindOthers

    BlogTopicsEntriesMyEntriesWriteTopicSeismicStructureDesignConcreteSoilTestMoment&ShearwallPowerSystemsSubstationsTransformerPowerProtectionTransmissionLinePowerDistributionMotors

    ForumElectricalDiscussion

    PostNewDiscussionCivilDiscussion

    PostNewDiscussionMechanicalDiscussion

    Search...

    60

  • 5/14/2015 Zone4info.comDieselgeneratorprotectionrelay

    http://zone4info.com/forums/topic/6603/dieselgeneratorprotectionrela#.VVOWbmqpHw 2/5

    PostNewDiscussionGeneral

    PostNewDiscussionGroups

    BrowseGroupsMyGroupsCreateNewGroup

    JobsBrowseJobsPostNewJob

    CoursesBrowseChannelsMyChannelsDiaryCreateNewChannel

    AlbumsNewAlbumsMyAlbumsAddNewPhotosAddNewPhotosEngineeringAlbumsAlbumsPinboardCategories

    FollowFacebookLinkedinGoogle+PinterestTwitterYoutube

    PagesCreateNewPageBrowsePagesBrowsePagePinboardViewBrowsePagesAlbumsBrowsePagesVideos

    MoreLikesCompanyVideos

    Search...

    ForumsElectricalengineering

    LikeSuggesttoFriendsBackToTopicsPostReplyWatchTopic

    Dieselgeneratorprotectionrelay

  • 5/14/2015 Zone4info.comDieselgeneratorprotectionrelay

    http://zone4info.com/forums/topic/6603/dieselgeneratorprotectionrela#.VVOWbmqpHw 3/5

    SarahOkwuosa

    5postsApril30,201512:13AMEESTReply&attachImageQuoteReport

    Iamdoingadieselgeneratorprotectionrelaysetting.Wenormallysetthe51Vto1.4xFullloadcurrent.Onthegeneratornameplate,themaximumoverloadis10%for2hours.Isthe1.4Fullloadsettingtoohigh?

    AlexdeMoura

    267postsMay1,20156:59PMEESTReply&attachImageQuoteReport

    Sarah,greetings,Ican'tsaymuchwiththelittleinformationyougave,butlet'strytohelpyouonthis.

    ThefrontlineovercurrentprotectionismadebytheInstantaneous50orTimed51relays/functions,meanwhilethe51VistheVoltageSupervised(Timed)Overcurrent.ItisabackuprelaythatworksonlyatGeneratorundervoltageconditions,usuallyinLVandMVGenerators.The51Vcanbe:

    1.VoltageRestrainedOvercurrent:sometimescalled51VR,theovercurrentsetting

    Ease guaranteedWall hung electric Water heaters

  • 5/14/2015 Zone4info.comDieselgeneratorprotectionrelay

    http://zone4info.com/forums/topic/6603/dieselgeneratorprotectionrela#.VVOWbmqpHw 4/5

    CHANGESasthevoltagechanges,allowingittorespondtoovercurrentsatallreducedvoltages,thereisSetPointCurve(%SPx%Vr),itisacontinuous/analogrelay.Atratedvoltage(Vr)thesettingis125175%FLC,verycommon,but125150%FLAisalsousual.TheSetPointof140%FLCofyoursisinsideofbothoptions,ifweassumeVrcondition.Forothervoltages,the51VRSetPointcurvetypicallystarts25%SP@0%Vr(inyourcase25%SP=25%x140%FLC=35%FLC)butIprefertoadjust30%SP@20%Vr(inyourcase30%SP=30%x140%FLC=42%FLC),inamorelinearpartofthecurve

    2.VoltageControlledOvercurrent:sometimescalled51VCor51C,theovercurrentsettingisENABLEDwhenthevoltageisbelowapresetvalue.Ifthevoltageisabovetheundervoltageelementsettingtherelayisnotfunctional,soitisadiscreterelay.Theundervoltagesettingtoenablethe51VCis70%90%Vr,75%Vrisveryusual,or5%morethantheUndervoltageProtectionRelaysettingisalsocommon

    SomeEngineersliketouse8090%Idovercurrentsetting,mainlyfor51VCtype,beingId=1/XdSynchronousUnsaturated.ButIsupposethisaddsmorecomplications.IfyouhaveIdavailableyoucanuseittocheckiftheovercurrentsettingisinthe8090%Idrange.

    Thetimesettingfor51Vcanbe0.52.0secondsnormally,beingthe1.0secondthemostusualvalue,orthesametimesettingtobeappliedon51TimedOvercurrentrelay.

    Ifyouarereallyuncomfortablewith140%FLC,youcanreducetosomethinglike135%FLC,butIwouldnotsuggestthatbecausetheGeneratorhasacontinuousoperation(morethan1hour)capabilityof110%FLC,asyoudescribed.ThatiswhysomeEngineersuseFLA(practical,measured)insteadofFLC(theoretical,rated)for51Vsettingcalculationsas125150%FLA.YourGeneratorhasaFLA=110%FLC.Areducedsettingforabackup51Vrelaycouldmakeitoperatetoooftenandinconvenientlybeforeotherfrontlineovercurrentprotections.

    Ithink140%FLCisOK,andIwoulddaretosaythatmaybeyouwillincreasethisvalueabitduringprojectCommissioningafterthetestsindicatesomeunwantedtripsbyovercurrent,mainlyatoverloadoperations.Pleaseletusknowaboutit.

    ThispostwaseditedbyAlexdeMouraatMay3,201511:31PMEEST

    QuickReply

    Jobs in QatarAll New Jobs in Qatar. Apply Today!

    & % 7 !

    FontFamily FontSizes 2 1 0 /

    + * ( ) '

  • 5/14/2015 Zone4info.comDieselgeneratorprotectionrelay

    http://zone4info.com/forums/topic/6603/dieselgeneratorprotectionrela#.VVOWbmqpHw 5/5

    Sendmenotificationswhenothermembersreplytothistopic.PostReply

    Copyright2015PrivacyTermsofServiceContactPowerSystemsTransformersMotorsWiringDesignSolarEnergySoilTestingConcreteStructureSeismicCivilCoursesMech.CoursesElectricalJobsCivilJobsMech.JobsElectricalCoursesCivilBooksHVACMoment&ShearwallPowerDistributionPowersystemguidesPowerprotectionguidesElectricalBooksExcelSheetCalculatorsWindEnergySubstationTransformersguidesSolarguidesWindguidesMotorguidesTransmissionLinesHydro