Geotechnical Engineering ReportPG&E TRAINING FACILITY
WKA No. 9974.01September 22, 2014
Prepared For:PG&E Corporate Real Estate, Strategy and Services
100 Montgomery Street, Suite No. 715San Francisco, California 94104
Geotechnical Engineering ReportPG&E TRAINING FACILITY
Winters, California
TABLE OF CONTENTSINTRODUCTION .......................................................................................................................... 1
Work Scope ........................................................................................................................... 1Supplemental Information ...................................................................................................... 1Figures and Attachments ....................................................................................................... 2Project Description ................................................................................................................. 2
FINDINGS..................................................................................................................................... 3Site Description...................................................................................................................... 3Historical Aerial Photograph Review ...................................................................................... 3Soil Conditions ....................................................................................................................... 4Site Geology .......................................................................................................................... 4Groundwater .......................................................................................................................... 5
CONCLUSIONS............................................................................................................................ 5Organic Content ..................................................................................................................... 5Bearing Capacity.................................................................................................................... 52013 CBC/ASCE 7-10 Seismic Design Criteria ...................................................................... 6Liquefaction............................................................................................................................ 7Soil Expansion Potential......................................................................................................... 7Excavation Conditions............................................................................................................ 7Soil Suitability for Use in Fill Construction .............................................................................. 8Pavement Subgrade Quality .................................................................................................. 8Groundwater .......................................................................................................................... 8Seasonal Water...................................................................................................................... 8Percolation Test Results ........................................................................................................ 9Preliminary Soil Corrosion Potential ....................................................................................... 9
RECOMMENDATIONS................................................................................................................10General .................................................................................................................................10Site Clearing and Preparation ...............................................................................................11Engineered Fill Construction .................................................................................................12Drainage Easement ..............................................................................................................13Utility Trench Backfill .............................................................................................................13Foundation Design ................................................................................................................14Interior Floor Slab Support ....................................................................................................17Floor Slab Moisture Penetration Resistance..........................................................................18Retaining Wall Design...........................................................................................................18Exterior Flatwork Construction ..............................................................................................19Pavement Design..................................................................................................................20Site Drainage ........................................................................................................................22Geotechnical Engineering Observation and Testing During Earthwork..................................22
LIMITATIONS ..............................................................................................................................22
Geotechnical Engineering ReportPG&E TRAINING FACILITY
Winters, California
TABLE OF CONTENTS (Continued)
FIGURESVicinity Map..........................................................................................................Figure 1Site Plan ..............................................................................................................Figure 2Logs of Borings ................................................................................ Figures 3 through 38Unified Soil Classification System.......................................................................Figure 39
APPENDIX A – General Project Information, Laboratory Testing and ResultsTriaxial Compression Test Results ...................................................... Figures A1 and A2Expansion Index Test Results ....................................................... Figures A3 through A6Resistance Value Test Results............................................................ Figures A7 and A8Corrosion Test Results ................................................................ Figures A9 through A13Particle Size Distribution............................................................ Figures A14 through A17Percolation Test Results............................................................ Figures A18 through A20
APPENDIX B – Guide Earthwork Specifications
APPENDIX C – Guide Drilled Pier Specifications
Geotechnical Engineering ReportPG&E TRAINING FACILITYEast Grant Avenue, West of I-505Winters, CaliforniaWKA No. 9974.01September 22, 2014
INTRODUCTION
We have completed a modified geotechnical engineering investigation to reflect a change in sitelayout for the proposed PG&E Training Facility to be constructed south of East Grant Avenueand west of I-505 in Winters, California. The purposes of our work have been to explore thesite, soil and groundwater conditions, and to provide geotechnical engineering conclusions andrecommendations regarding design and construction of the proposed training facility. Thisreport presents the results of our work.
The initial Geotechnical Engineering Report prepared by our firm (dated January 29, 2014) wasbased on a different site layout, which required additional borings in areas not previouslyexplored to verify the uniformity of the soil conditions and the applicability of the conclusions andrecommendations in the original report.
Work Scope
Our scope of work for this project included the following tasks:
1. two site reconnaissances;2. review of historic Unite States Geological Survey (USGS) topographic maps, aerial
photographs, and available groundwater data within the vicinity of the property;3. review of reports prepared for nearby projects;4. subsurface exploration, including the drilling and sampling of a total of 36 borings to
maximum depths of 21½ feet below existing site grades;5. bulk sampling of the subgrade soils within proposed building and pavement areas;6. laboratory testing of selected soil samples to determine engineering properties of the
soil;7. engineering analyses; and,8. preparation of this report.
Supplemental Information
Supplemental information used in the preparation of this report included review of the followingreports prepared by Wallace-Kuhl & Associates, Inc. for projects near the subject site:
Geotechnical Engineering Report Page 2PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Geotechnical Engineering Report, prepared by Wallace-Kuhl & Associates, Inc. (WKANo. 7469.03, dated July 29, 2008), prepared for the Monticello Mixed-Use Building.
Geotechnical Engineering Report, prepared by Wallace-Kuhl & Associates, Inc. (WKANo. 8274.02P, dated October 9, 2009), prepared for the Putah Creek Pedestrian Bridge,located very near the southwest corner of the subject site.
Information contained in these reports was used to assist in the analysis and preparation ofthis report.
Figures and Attachments
This report contains a Vicinity Map as Figure 1; a Site Plan showing approximate boringlocations as Figure 2; and, Logs of Soil Borings completed for this project as Figures 3 through38. An explanation of the symbols and classification system used on the logs is contained onFigure 39. Appendix A contains general information regarding project concepts, exploratorymethods used during our field investigation, and laboratory test results that are not included onthe logs. Appendix B contains Guide Earthwork Specifications that may be used in thepreparation of contract documents. Appendix C contains Guide Drilled Pier Specifications.
Project Description
The revised Winters Site Test Fit Plan, dated August 20, 2014, indicates the training facility willinvolve construction of numerous buildings containing offices, classrooms, and laboratoryspace; crane certification area; cold pits, hydro testing and pipeline inspection; equipmenttraining area; commercial driver training area; utility village; cathodic protection area; stormwater pond at the southeast side of the property; a drainage easement near the western siteboundary; and, pavement areas for autos, trucks and other heavy equipment, involving asphaltconcrete, Portland cement concrete pavements and gravel wearing surfaces.
We understand the buildings will be one-and two-story structures with interior concrete slabs-on-grade. Construction type could be steel-frame, masonry or concrete tilt-up (non-combustibleconstruction). Structural loads are anticipated to be light to moderate and consistent with thesetypes of construction. The exception to this could be the equipment training area that might becovered, which would be subject to relatively high uplift and overturning forces. We alsounderstand that the excavation areas may involve the construction of retaining walls. Thedrainage easement and storm water pond likely will be fairly shallow (less than 10 feet deep).
Geotechnical Engineering Report Page 3PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
FINDINGS
Site Description
The subject property is located south of East Grant Avenue, west of I-505 in Winters, YoloCounty, California (Figure 1). The site is bordered to the north by East Grant Avenue; to theeast by the southbound on-ramp to I-505; to the south by Putah Creek; and, to the west byresidential development. At the time of our recent site investigation, September 5, 2014, themajority of the property consisted of agricultural land, although a portion of the site adjacent to I-505 was undeveloped land. Vegetation across the agricultural portion of the property consistedof a heavy growth of weeds up to about six feet high. The undeveloped land adjacent to I-505supported a moderate growth (two to three feet high) of weeds and small shrubs. A sewer liftstation, surrounded by a chain-link fence, was observed on the undeveloped portion of the sitenear the northeast corner of the property. Three rural residential structures were observedadjacent in the northwest of the property, south of East Grant Avenue. Two above groundpressure tanks were observed adjacent to the residential structures, and a dilapidated barnsurrounded by a chain-link fence was observed south of the residences. A well was observedto the south of the barn adjacent to the western border of the site, and a power pole and a wellwere observed near the southeast corner of the property.
The topography of the site is essentially flat with a surface elevation of approximately +125 feetrelative to mean sea level (msl), based on topographic information provided on the USGS 7.5-Minute Topographic Map of the Winters Quadrangle, California, dated 1953 (photorevised1968).
Historical Aerial Photograph Review
Historical topographic maps were reviewed from the years 1993 through 2013. Review of the1993 photograph shows the approximate westernmost two-thirds of the site to be planted withrow crops. Three rural residential structures and barn are visible near the northwest corner ofthe site, south of East Grant Avenue. A portion of property adjacent to I-505 is undeveloped. Amoderate growth of vegetation and scattered shrubs are visible across this portion of theproperty. A dirt road is visible traversing northwest to southeast between the planted andundeveloped portions of the property.
Review of aerial photographs from 2003 through 2009 indicates the site to have remainedrelatively unchanged since the 1993 photograph.
Geotechnical Engineering Report Page 4PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Review of an aerial photograph from 2010 shows a disturbed portion of land approximately 70feet wide traversing across the planted portion of the property southwest to northeast, turningnorth through the undeveloped portion of the property and terminating near East Grant Avenue.
By 2012, a small structure is visible on the undeveloped portion of the site near the northeastportion of the property within the alignment of the disturbed area visible in the 2010 photograph.Review of a 2013 aerial photograph indicates the site to have remained relatively unchangedsince the prior year.
Soil Conditions
The surface and near-surface soils across the site generally consist of loose to medium densesandy silts and silty sands from the surface to depths of about 3½ to 8½ feet below existing sitegrades. Minor and variable amounts of clay were observed in the upper soils. Alternatinglayers of medium stiff to hard silty clays were encountered below the upper silts and sands tothe maximum depths of exploration of about 21½ feet below the surface. The additional sevenborings revealed relatively consistent subsurface conditions.
For detailed soil conditions at a particular location, please refer to the Logs of Soil Boringspresented as Figures 3 through 38. The initial borings are identified as borings D1 through D29.The recent borings are identified as D101 through D107.
Site Geology
The City of Winters is located in the western-central portion of the Great Valley geomorphicprovince of California adjacent to the eastern slope of the Coast Ranges. The geology in theGreat Valley is characterized by thick sequences of alluvial and flood plain deposits consistingof sedimentary material derived from the Coast Ranges to the west and the Sierra Nevadamountain range to the east.
According to Geologic Map of the Sacramento Quadrangle prepared by the CaliforniaDepartment of Mines and Geology (Wagner, 1981 et. al), the subject site is underlain by Late toMiddle Pleistocene deposits of the Modest-Riverbank Formations. The Modesto-RiverbankFormations consist of sands, silts, minor gravels, and clays. The mapping is generallyconsistent with the materials encountered in our borings.
Geotechnical Engineering Report Page 5PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Groundwater
Free groundwater was not encountered within the test borings performed between December18 through 30, 2013, or on September 5, 2014, to the maximum depth explored ofapproximately 21½ feet below existing site grades.
To supplement our groundwater information for the project site, we reviewed groundwater elevationdata obtained from a California Department of Water Resources (DWR) monitored well identifiedas #08N01W22G002M. This well is reported by DWR to be located on the project site. The DWRperiodically measured water elevations in this well from October 3, 1957 to October 6, 1971.Based on the available data, the lowest measured groundwater elevation in this well occurred onOctober 4, 1961, at an elevation of +69.1 feet msl or about 57 feet below existing grade at the well;the highest elevation occurred on January 14, 1970, at an elevation of about +93.3 feet msl orabout 33 feet below the existing grade at the well.
CONCLUSIONS
Organic Content
Three bulk samples of near-surface soil were tested to determine the organic content inaccordance with ASTM D2974. The samples selected for organic content resulted in valuesranging from 2.48% to 3.08% organics. Based on these results we conclude that the surfacesoils are suitable for use in engineered fill. A summary of these tests is presented below.
TABLE 1ORGANIC CONTENT
Test Boring Sample Depth(ft)
Soil Type OrganicContent (%)
D5 0-3 SM 2.48
D18 0-5 ML 3.15
D22 0-3 ML 3.08
Bearing Capacity
The majority of the upper two to three feet of surface soils across the site are disturbed due toagricultural activities and in a relatively loose condition. Those materials are considered
Geotechnical Engineering Report Page 6PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
unsuitable for support of the proposed structures and pavements without removal andrecompacting, although they are suitable for support of the proposed pavements.
Our work also indicates that engineered fill, properly placed and compacted in accordance withthe recommendations of this report, will be capable of supporting the proposed structures andpavement improvements. Specific recommendations to scarify, moisture condition, andrecompact the surface soils have been provided in the Site Clearing and Preparation section ofthis report.
2013 CBC/ASCE 7-10 Seismic Design Criteria
Section 1613 of the 2013 edition of the CBC references ASCE Standard 7-10 for seismicdesign. The following seismic parameters were determined based on the site latitude andlongitude using the public domain computer program developed by the USGS. The followingparameters summarized in the table below may be used for seismic design of the proposeddevelopment.
TABLE 2CBC/ASCE 7-10 SEISMIC DESIGN PARAMETERS
Latitude: 38.5275° NLongitude: -121.9565° W
ASCE 7-10Table/Figure
2013 CBCTable/Figure
Factor/Coefficient Value
Short-Period MCE at0.2s Figure 22-1 Figure
1613.3.1(1) SS 1.650 g
1.0s Period MCE Figure 22-2 Figure1613.3.1(2) S1 0.560 g
Soil Class Table 20.3-1 Section 1613.3.2 Site Class D
Site Coefficient Table 11.4-1 Table 1613.3.3(1) Fa 1.000
Site Coefficient Table 11.4-2 Table 1613.3.3(2) Fv 1.500
Equation 11.4-1 Equation 16-37 SMS 1.650 gAdjusted MCE SpectralResponse Parameters Equation 11.4-2 Equation 16-38 SM1 0.840 g
Equation 11.4-3 Equation 16-39 SDS 1.100 gDesign SpectralAcceleration Parameters Equation 11.4-4 Equation 16-40 SD1 0.560 g
Table 11.6-1 Section1613.3.5(1)
Risk CategoryI to IV D
Seismic Design CategoryTable 11.6-2 Section
1613.3.5(2)Risk Category
I to IV D
Geotechnical Engineering Report Page 7PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Liquefaction
The soil conditions encountered at the borings and our review of geologic information in theWinters area indicates the site is underlain by silty clay or mixtures of sands, silts, clays, anddense gravels, which typically decrease the potential for liquefaction. To our knowledge, therehave been no reported instances of liquefaction having occurred in the vicinity of the project siteor within the Winters area during major earthquake events. Therefore, it is our opinion thatloose cohesionless soils below groundwater do not exist in significant thickness beneath the siteand the potential for liquefaction of the soils beneath the site during a seismic event is very low.
Soil Expansion Potential
Laboratory test results on the near-surface silts indicate these materials possess a lowexpansion potential when tested in accordance with ASTM D4829 test method (see Figures A3,A5 and A6). Additional laboratory tests performed on samples of the underlying silty claysencountered below the near-surface silts and sands indicate that these materials possess amedium expansion potential (see Figures A4 and A7). Based on the laboratory test results andthe depth to the clays, we conclude mitigation measures to reduce the detrimental effects ofexpansion pressures caused by moisture variations within the clay soils will not be necessaryfor development at this site.
Excavation Conditions
The on-site soils should be readily excavatable with conventional construction equipment. Inour opinion, shallow excavations less than five feet in depth will stand at a near-verticalinclination for the short periods of time required for utility construction. However, minorsloughing and "running" conditions could occur if the soils are saturated, or where zones ofclean (cohesionless) sands are encountered, especially when subjected to constructionvibrations or allowed to dry significantly.
Excavations deeper than five feet that will be entered by workers should be sloped, braced orshored in accordance with current OSHA regulations. The contractor must provide anadequately constructed and braced shoring system in accordance with federal, state and localsafety regulations for individuals working in an excavation that may expose them to the dangerof moving ground.
Geotechnical Engineering Report Page 8PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Excavated materials should not be stockpiled directly adjacent to open trenches to preventsurcharge loading of the trench sidewalls. Excessive truck and equipment traffic should also beavoided near open trenches. If material is stored or heavy equipment is operated near anexcavation, stronger shoring (or flatter slopes) would be required to resist the additionalpressure due to the surcharged loads.
Soil Suitability for Use in Fill Construction
The on-site soils encountered in our test borings are considered suitable for use as engineeredfill, provided these materials are free of organics, rubble and other deleterious material, and areat moisture contents capable of achieving the desired degree of compaction.
Pavement Subgrade Quality
Laboratory testing of the surface and near-surface soils indicates the soils across the site arevariable with respect to their support qualities for pavements. Resistance (“R”) value testingwas performed on three representative samples of the anticipated subgrade soils collectedduring our subsurface investigation. Laboratory testing indicates the on-site materials testedpossess Resistance ("R") values ranging from 12 to 28, as shown on Figures A8 through A10.Based on the laboratory test results and our experience with similar soil types, and theanticipated mixing of soils during earthwork construction, we consider an R-value of 20appropriate for design.
Groundwater
Groundwater was not encountered to the explored 20 foot depth of the test borings performedfor this investigation, and we conclude that a permanent groundwater table should not be asignificant factor in site development. However, groundwater levels should be expected tofluctuate throughout the year based on variations in precipitation, temperature, evaporation, run-off, and other factors. The groundwater levels discussed herein represent the conditions at thetime the measurements were obtained. The actual groundwater levels at the time ofconstruction may vary. However, standard sump pit and pumping procedures should beadequate to control localized groundwater seepage into excavations.
Seasonal Water
During the wet season, infiltrating surface water will create saturated surface soil conditions dueto the relatively impermeable nature of the underlying clays. Grading operations attempted
Geotechnical Engineering Report Page 9PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
following the on-set of winter rains and prior to prolonged drying periods will be hampered byhigh soil moisture contents. Such soils, intended for use as engineered fill, will requireconsiderable drying and aeration to reach a moisture content that will permit the specifieddegree of compaction to be achieved.
Percolation Test Results
At the approximate locations indicated on Figure 2, three percolation tests (P1 through P3) wereperformed at the site on December 20, 2013. The percolation tests were prepared by drillingfour-inch diameter holes approximately 10 feet below the existing ground surface. Followingdrilling, 2-inch diameter perforated pipes were placed in the test holes and the annular spacefilled with gravel. The percolation test holes were pre-soaked by filling the holes with water upto the existing ground surface and the test holes were allowed to soak overnight.
Percolation tests were performed the following day by refilling the percolation holes to within afoot or two of the surface. The drop in water was measured initially in 5 minute increments,followed by readings every 10 minutes for the next four hours. Percolation rates werecalculated for each time interval and for overall rates (total drop vs. total time). The overall ratesfor the three tests, based on the last hour range from 0.11 to 0.19 inches per minute(approximately 5 to 9 minutes per inch). Due to the presence of stiff silty clays at a depth of 8feet, the percolation rates likely relate primarily to horizontal percolation and not verticalpercolation. The field data for the percolation tests is contained on Figures A21 through A23 inAppendix A.
The new storm water basin is north and east of the initial basin locations. Due to the relativeconsistent soil conditions the data from the initial percolations testing is appropriate for therevised basin location.
Preliminary Soil Corrosion Potential
Six samples of near-surface soil were submitted to Sunland Analytical Lab for testing to determinepH, chloride and sulfate concentrations, and minimum resistivity to help evaluate the potential forcorrosive attack upon buried concrete. The results of the corrosivity testing are summarized inthe following table. Copies of the test reports are presented on Figures A11 through A16.
Geotechnical Engineering Report Page 10PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
TABLE 3SOIL CORROSIVITY TESTING
Bulk Sample Identification
Analyte Test Method D4(0’ - 3')
D9(4½’-7’)
D15(0’ - 3')
D20(0’ - 3')
D24(0’ - 3')
D103(0’ - 3')
pHCA DOT 643
Modified*7.78 7.92 7.79 7.53 7.21 7.18
MinimumResistivity
CA DOT 643Modified*
1260-cm
1150-cm
990-cm
800-cm
1930-cm
1130-cm
Chloride CA DOT 41746.8ppm
32.8ppm
59.6ppm
59.8ppm
30.3ppm
17.1ppm
Sulfate CA DOT 42251.1ppm
41.2ppm
69.9ppm
74.9ppm
2.9ppm
41.2ppm
* = Small cell method; -cm = Ohm-centimeters; ppm = Parts per million
Table 4.2.1 Exposure Categories and Classes of the American Concrete Institute (ACI) Manualof Concrete Practice Part 3 - 2010, indicates the severity of sulfate exposure for the samplestested is Not Applicable. However, the minimum resistivity test results suggest that the nativesoils may be moderately to highly corrosive to unprotected buried metal, but not excessivelycorrosive to steel reinforcement properly embedded within Portland cement concrete.
Wallace-Kuhl & Associates are not corrosion engineers. Therefore, if it is desired to furtherdefine the soil corrosion potential at the site, a corrosion engineer should be consulted.
RECOMMENDATIONS
General
The site is essentially level with little topographic relief across the property; therefore, we haveassumed maximum excavations and fills on the order of one to three feet for development of theproperty (excluding the drainage canal and detention basins). The recommendations in thisreport are based upon this assumption.
Geotechnical Engineering Report Page 11PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
In addition, the recommendations presented below are appropriate for typical construction in thelate spring through fall months. The on-site soils likely will be saturated by rainfall in the winterand early spring months, and will not be compactable without drying by aeration or the additionof quicklime (or a similar product) to dry the soils. Should the construction schedule requirework to continue during the wet months, additional recommendations can be provided, asconditions warrant.
Site Clearing and Preparation
Initially, the site should be cleared of existing structures designated for removal, including butnot limited to, concrete slabs, foundations, underground structures and any septic tanks;resulting demolition debris; trees and bushes, including root systems; and, any utilities to berelocated or abandoned within areas to be developed. Tree removal should include the rootballand all surface roots larger than ½-inch in diameter. Domestic and agricultural wells should beidentified and removed in conformance with the requirements of the governing agency. Septictanks should be removed and wasted off-site, and leach fields should be excavated.
Following removal of foundations, slabs, leach fields and existing structural improvements, alldisturbed soil from the operations should be excavated to expose firm native soils and gradesrestored with engineered fill placed in accordance with the recommendations in this report.
Following clearing operations, any remaining surface vegetation and organically contaminatedtopsoil should be removed by stripping. A stripping depth of three inches should be assumedfor removal of the surface organics and shallow root systems. Strippings may be stockpiled forlater use or disposed of off-site. Strippings should not be used in general fill construction, butmay be used in landscaped areas, provided they are kept at least five feet from any structure,including adjacent flatwork and pavements, are moisture conditioned and receive compactiveeffort. Due to the height and moderate to heavy concentrations of weeds at the site discing ofthe organics is not recommended.
The surface and near-surface soils are relatively loose, and clearing operations likely will resultin disturbance of the upper few feet of soil. Therefore, all building pads, including adjacentexterior flatwork, should be sub-excavated to a depth of at least 24 inches below the existinggrade. The sub-excavations should extend at least five feet beyond the proposed footprint ofthe buildings and adjacent flatwork. The exposed subgrade then should be thoroughly scarifiedto a depth of at least 12 inches, brought to a uniform moisture content of at least the optimummoisture content, and compacted to not less than 90 percent of the maximum dry density per
Geotechnical Engineering Report Page 12PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
ASTM D1557 specifications. Compaction should be performed using a Cat 825 or anequivalent-sized sheepsfoot compactor.
Based on the relatively flat topography of the site we anticipate a majority of pavementsubgrades will be at-grade or achieved by excavations up to one foot in depth. Once thepavement areas are at rough subgrade elevation, the soils should be thoroughly scarified to adepth of about 18 inches and all unsuitable materials removed. The soils should then bemoisture conditioned to at least the optimum moisture and compacted to at least 90 percent ofthe maximum dry density per ASTM D1557 using a Cat 825 or equivalent compactor. Finalsubgrade preparation should be accomplished after all underground utility construction iscomplete.
Due to the loose soils at this site it is crucial that a Cat 825 compactor be used for compaction.Smaller compactors are not acceptable for compaction during mass grading for this project.
Compaction of the existing grade must be performed in the presence of our representative whowill evaluate the performance of the subgrade under compactive loads and identify any loose orunstable soil conditions that could require removal and replacement.
Engineered Fill Construction
Engineered fill should be placed in lifts that do not exceed six inches in compacted thickness.Native materials should be uniformly moisture conditioned to at least the optimum moisturecontent and compacted to at least 90 percent of the ASTM D1557 maximum dry density.
On-site soils are considered suitable for use in engineered fill construction, if free of significantconcentrations of organics, rubble or debris. Imported fill materials, if required, should begranular materials with non-plastic fines with an Expansion Index of 20 or less, and free ofparticles greater than three-inches in maximum dimension. Additionally, import fill materials thatwill be used within pavement areas should have a minimum Resistance value of 20 when testedin accordance with California Test 301. Imported fill should be approved by the GeotechnicalEngineer prior to being transported to the site. Additionally the contractor must provideadequate documentation that the imported materials are free of known contaminants and withinacceptable corrosion limits.
The upper six inches of final pavement subgrade should be uniformly compacted to at least95 percent of the ASTM D1557 maximum dry density at a moisture content of at least theoptimum moisture, and must be stable under construction traffic prior to placement of aggregate
Geotechnical Engineering Report Page 13PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
base. Final pavement subgrade processing and compaction should be performed just prior toplacement of aggregate base, after construction of underground utilities is complete. Themoisture content of the subgrade soils should be maintained until covered by aggregate base.
Permanent excavation and fill slopes should be constructed no steeper than two horizontal toone vertical (2:1), and should be vegetated as soon as practical following grading to minimizeerosion. Slopes should be over-built and trimmed to design lines and grades.
Site preparation should be accomplished in accordance with the recommendations of thissection and the Guide Earthwork Specifications provided in Appendix B. A representative of theGeotechnical Engineer should be present during site preparation and all grading operations toobserve and test the fill to verify compliance with our recommendations and the projectspecifications.
Drainage Easement
A drainage easement is planned near the western boundary of the subject site. We understandthe bottom of the easement will be approximately 10 feet below existing grades. Excavation forthe canal will likely encounter the relatively granular soils, although clay soils could beencountered near the bottom of the canal, depending on final design depth. Conventionalexcavation equipment will be suitable for excavation and construction of the canal.
Due to the relatively loose condition of the soils within the upper 10 feet, we recommend theside slopes for the easement be constructed no steeper that three horizontal to one vertical(3:1). Following excavation, the slopes should be track-walked with a dozer to improve thedensity of the soil and help reduce the erosion potential.
Unless the bottom of the easement extends into the underlying silty clays, there is a potential forerosion of the easement bottom, depending on flow volume and velocity.
Utility Trench Backfill
Bedding of utilities and initial backfill around and over the pipe should be in accordance with themanufacturer’s recommendations for the pipe materials selected, and applicable City of WintersStandards.
We recommend that native soil be used to backfill utility trenches, especially within buildingareas. Utility trench backfill should be placed in maximum 12-inch lifts (compacted thickness),
Geotechnical Engineering Report Page 14PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
moisture conditioned to at least the optimum moisture content, and mechanically compacted toat least 90 percent of the maximum dry density as determined by ASTM D1557. Within theupper six inches of pavement areas the minimum compaction should be increased to 95 percentof ASTM D1557.
We recommend that underground utility trenches that are aligned nearly parallel withfoundations be at least three feet from the outer edge of foundations, wherever possible. As ageneral rule, trenches should not encroach into the zone extending outward at a horizontal toone vertical (1:1) inclination below the bottom of the foundations. Additionally, trenches parallelto existing foundations should not remain open longer than 72 hours. The intent of theserecommendations is to prevent loss of both lateral and vertical support of foundations, resultingin possible settlement.
Foundation Design
Conventional Foundations
The proposed office and classroom buildings may be supported upon continuous and/orisolated spread foundations that extend at least 18 inches into the compacted building pad, asmeasured from lowest adjacent soil grade. For this project, the building pad subgrade isdefined as the soil surface on which capillary break gravel is placed. A continuous, reinforcedfoundation should be utilized for the perimeter of the structures to act as a “cut-off” to helpminimize moisture infiltration and variations beneath the interior slab-on-grade areas of thestructures. Continuous foundations should be at least 12 inches wide; isolated spreadfoundations should maintain a minimum 24-inch dimension.
We recommend that all foundations be adequately reinforced to provide structural continuity,mitigate cracking and permit spanning of local soil irregularities. As a minimum, we recommendthat continuous foundations be reinforced with at least two No. 4 steel reinforcing bars, placedone each near the top and bottom of the foundations. The structural engineer should determinefinal foundation dimensions and reinforcing requirements.
Foundations bearing on recompacted native soils, engineered fill, or a combination of thesematerials may be sized utilizing a maximum allowable soil pressure of 3000 psf for dead loadplus live loads, or 4000 psf for all loads, including wind or seismic forces. The weight offoundation concrete extending below lowest adjacent soil grade may be disregarded in sizingcomputations.
Geotechnical Engineering Report Page 15PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Lateral resistance of foundations may be computed using an allowable friction factor of 0.30which may be multiplied by the vertical load on the foundation. Additional lateral resistance maybe assumed to develop against the vertical face of the foundations and may be computed usinga "passive" equivalent fluid pressure of 300 psf per foot of depth. These two modes ofresistance should not be added unless the frictional component is reduced by 50 percent sincefull mobilization of the passive resistance requires some horizontal movement, whichsignificantly diminishes the frictional resistance.
Based on local experience, shallow foundations constructed in accordance with therecommendations of this report could experience maximum total settlements on the order of 1-inch and maximum differential settlements on the order of ½-inch.
Drilled Concrete Piers
The equipment training structures may be supported on shallow spread foundations, although itis likely these foundations will not provide adequate uplift and overturning resistance. Thereforethe future covered excavation structures may be supported on drilled, cast-in-place concretepiers extending at least 10 feet below the lowest adjacent soil grade. Piers should have aminimum shaft diameter of 24 inches. Drilled piers may be designed using an allowable endbearing capacity of 6000 pounds per square foot (psf) for dead and dead plus live loads with a1/3 increase to include the short-term effects of wind or seismic forces.
For constructability purposes, a minimum shaft diameter of 24 inches is recommended. Toavoid potential group effects between adjacent caissons when considering either axial or lateralloads, we recommend a minimum spacing of three pier diameters (center-to-center). Due to thegranular nature of the upper 8 to 10 feet of soil, belled piers likely would not hold their shape inthe upper granular soils, and therefore are not recommended for this project.
Uplift resistance of piers can be evaluated based upon an average skin friction of 400 psf inaddition to the weight of the pier. Lateral resistance of pier foundations may be evaluated byapplying a passive earth pressure equivalent to a fluid pressure of 300 psf per foot of depth,acting over an area equal to 1½ times the pier diameter times the depth of the pier. If the pier issurrounded by slab-on-grade concrete, a constrained condition may be assumed for design.Reinforcement and concrete should be placed in the pier excavations as soon as possible afterthe drilling is completed to minimize the chances of sidewall caving into the excavations. Thenear-surface silts and sands could slough during pier construction; therefore, we recommendthat the pier contractor be prepared to case the pier holes.
Geotechnical Engineering Report Page 16PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
The bottom of the pier excavations should be free of loose or disturbed soils prior to placementof the concrete. Cleaning of the bearing surface may be done mechanically with the auger, andshould be verified by the geotechnical engineer prior to concrete placement.
If the drilled piers are constructed in the "dry" (with dry being less than six inches of water at thebase of the excavation), the concrete may be placed by the free-fall method, using a shorthopper or back-chute to direct the concrete flow out of the truck into a vertical stream of flowingconcrete with a relatively small diameter. The stream must be directed to avoid hitting the sidesof the excavation or reinforcing cages.
In general, we anticipate the drilled pier excavations will be relatively dry. However, ifgroundwater is encountered which cannot be controlled such that more than six inches of wateraccumulates at the bottom of the pier excavation, concrete should be placed using a tremie,after it is confirmed that the excess water cannot be removed from the caisson excavation bybailing or with sump pumps.
When extracting temporary casings or tremie methods from the excavation, care should betaken to maintain a head of concrete to prevent infiltration of water and soil into the shaft area.
To reduce lateral movement of the drilled shafts, the concrete for the drilled shafts must be indirect contact with the surrounding soil. Any voids or enlargements in the shafts due to over-excavation or temporary casing installation should be filled with concrete at the time the shaftconcrete is placed.
The design parameters recommended above assume the geotechnical engineer is be presentto observe foundation drilling to verify that the materials encountered at the drilled pier locationsare as anticipated. The geotechnical engineer can verify the bearing materials and conditionsfrom the surface using cuttings from augers. Either observation by the field engineer from theground surface or a down-hole camera can be used to visually observe the bearing surfaceswhere necessary to determine if the surface has been adequately cleaned or if standing water ispresent.
Drilled piers should be constructed in accordance with the recommendations of this report andthe Guide Drilled Pier Specifications provided in Appendix C.
Geotechnical Engineering Report Page 17PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Interior Floor Slab Support
Interior concrete slab-on-grade floors can be suitably supported upon the soil subgradeprepared in accordance with the recommendations in this report and maintained in thatcondition (optimum moisture). As a minimum, slabs should be at least 4 inches thick in officeand classroom areas (lightly loaded floors) and at least 6 inches thick in warehouse or industrialareas and should contain at least chaired No. 3 steel reinforcing bars placed on 24-inch centers,each way throughout the slab located at mid-slab depth. This slab reinforcement is suggestedas a guide "minimum" only. Final slab thickness and reinforcement should be provided by thestructural engineer based upon the anticipated floor loads. Temporary loads exerted duringconstruction also should be considered in the design thickness and reinforcement of interiorslabs. Proper and consistent location of the reinforcement at mid-slab is essential to itsperformance. The risk of uncontrolled shrinkage cracking is increased if the reinforcement isnot properly located within the slab.
Lightly loaded floor slabs (office and classroom areas) may be underlain by a layer of free-draining crushed rock, serving as a deterrent to migration of capillary moisture. The rock layershould be at least four inches thick and graded such that 100 percent passes a one-inch sieveand none passes a No. 4 sieve. Additional moisture protection may be provided by placing awater vapor retarder membrane (at least 10-mils thick) directly over the crushed rock. Theplastic water vapor retarder should meet or exceed the minimum specifications outlined inASTM E1745, and be installed in strict conformance with the manufacture’s recommendations.
Floor slab construction over the past 25 years or more has included placement of a thin layer ofsand over the vapor retarder membrane. The intent of the sand is to aid in the proper curing ofthe slab concrete. However, recent debate over excessive moisture vapor emissions from floorslabs includes concern for water trapped within the sand. As a consequence, we consider theuse of the sand layer as optional. The concrete curing benefits should be weighed againstefforts to reduce slab moisture vapor transmission.
For increased support for heavily loaded slab-on-grade floors or slabs subjected to fork lifttraffic, slabs may be underlain by at least six inches of Class 2 aggregate base compacted to 95percent of the maximum dry density as determined by ASTM D1557 test method. A durablevapor barrier (minimum 10-mil) could be placed beneath the aggregate base, if desired tominimize moisture vapor migration through the slab. Slab thickness and reinforcement shouldbe determined by the structural engineer based on anticipated slab loads.
Geotechnical Engineering Report Page 18PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Floor Slab Moisture Penetration Resistance
It is considered likely that floor slab subgrade soils will become saturated at some time duringthe life of the structure. This is a certainty when slabs are constructed during the wet season,when the subgrade soils are saturated prior to slab construction and when constantly wetground or poor drainage conditions exist adjacent to structures. For this reason, it should beassumed that interior slabs, particularly those intended for moisture-sensitive floor coverings ormaterials, require protection against moisture or moisture vapor penetration. Standard practiceincludes the rock, plastic membrane and sand as suggested above. However, the rock andplastic membrane offer only a limited, first line of defense against soil-related moisture.Recommendations contained in this report concerning foundation and floor slab design arepresented as minimum requirements only from the geotechnical engineering standpoint.
It is emphasized that the use of sub-slab gravel or aggregate base and sheet plastic membranewill not "moisture proof" the slab, nor does it assure that slab moisture transmission levels willprevent damage to floor coverings or other building components. They simply offer a first line ofdefense against soil related moisture. If increased protection against moisture vaporpenetration of slabs is desired, a concrete moisture protection specialist should be consulted.The design team should consider all available measures for slab moisture protection. It iscommonly accepted that maintaining the lowest practical water-cement ratio in the slab concreteis one of the most effective ways to reduce future moisture vapor penetration of the completedslabs.
Retaining Wall Design
Retaining walls may be supported upon continuous and/or isolated spread foundations bearingupon undisturbed native surface soils, engineered fill, or a combination of these materials.Retaining walls capable of slight rotation about their base (unrestrained at the top or sides)should be capable of resisting an "active" lateral earth pressure equal to an equivalent fluidpressure of 40 psf per foot of wall backfill for horizontal backfill conditions. Retaining walls thatare fixed at the top should be capable of resisting an "at-rest" lateral earth pressure equal to anequivalent fluid pressure of 60 psf per foot for horizontal backfill conditions.
Retaining walls could experience additional surcharge loading if vehicles are parked or at-gradefoundations are constructed within a one horizontal to one vertical (1:1) projection from thebottom of the retaining wall. Surcharge loading under these circumstances should be evaluatedon a case-by-case basis.
Geotechnical Engineering Report Page 19PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Retaining wall foundations should extend at least 18 inches below lowest adjacent soil grade,and may be designed utilizing the parameters provided in the Foundation Design section of thisreport.
Retaining walls should be fully drained to prevent the build-up of hydrostatic pressure behindthe wall. Retaining walls should be provided with a drainage blanket (Class 2 permeablematerial, Caltrans Specification Section 68-202F(3)) at least one foot wide extending from thebase of wall to within one foot of the top of the wall. The top foot above the drainage layershould consist of compacted aggregate base. Weep holes or perforated rigid pipe should beprovided near the base of the wall to allow drainage of accumulated water. Drain pipes, if used,should slope to discharge at no less than a one percent fall to suitable drainage facilities. Open-graded ½- to ¾-inch crushed rock may be used in lieu of the Class 2 permeable material, if therock and drain pipe are completely enveloped in an approved non-woven geotextile filter fabric.Detailing of wall drainage should be provided by the designer of the retaining wall.
Structural backfill materials for retaining walls, other than the drainage layer, should consist ofgranular soils free of significant quantities of rubbish, rubble, organics and rock over threeinches in size. Structural backfill should be placed in lifts not exceeding 12 inches in compactedthickness, and should be mechanically compacted to at least 90 percent relative compaction.The top 12 inches of backfill (aggregate base) should be compacted to at least 90 percent of theASTM D1557 maximum dry density.
Exterior Flatwork Construction
Soil subgrades supporting exterior concrete flatwork (i.e., sidewalks, patios, etc.) should bemoisture conditioned to the optimum moisture content and uniformly compacted to not less than90 percent of the ASTM D1557 maximum dry density, prior to the placement of the concrete.Proper moisture conditioning of the subgrade soils is considered essential to the performance ofexterior flatwork. Expansion joints should be provided to allow for minor vertical movement ofthe flatwork. Exterior flatwork should be constructed independent of the perimeter buildingfoundation and isolated column foundations by the placement of a layer of felt material betweenthe flatwork and the foundation.
Areas adjacent to new exterior flatwork should be landscaped to maintain more uniform soilmoisture conditions adjacent to and under the flatwork. We recommend final landscaping plansnot allow fallow ground adjacent to exterior concrete flatwork.
Geotechnical Engineering Report Page 20PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Practices recommended by the Portland Cement Association for proper placement, curing, jointdepth and spacing, construction, and placement of concrete should be followed during exteriorconcrete flatwork construction.
Pavement Design
Traffic indices were not specified for the project; therefore, we have assumed typical trafficindices of 4.0 through 10.0. The following pavement sections have been calculated based onthe assumed traffic indices and the procedures contained within Chapter 600 to 670 of the SixthEdition of the of the California Highway Design Manual. The project civil engineer shoulddetermine the appropriate traffic index based on anticipated traffic conditions.
TABLE 4PAVEMENT DESIGN ALTERNATIVES
R-value = 20
Traffic IndexType B
Asphalt Concrete(inches)
Class 2Aggregate Base
(inches)
2½ 74.03* 6
2½ 95.03* 8
2½ 126.03½* 10
3 147.04* 12
4 158.04½* 14
4 199.05½* 16
5 2010.06* 18
* = Asphalt thickness includes Caltrans Factor of Safety
We emphasize that the performance of a pavement is critically dependent upon uniformcompaction of the subgrade soils, as well as all engineered fill and utility trench backfill withinthe limits of the pavements. The upper six inches of pavement subgrades should be compacted
Geotechnical Engineering Report Page 21PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
to at least 95 percent of the ASTM D1557 maximum dry density at no less than the optimummoisture content. We recommend that pavement subgrade preparation, i.e. scarification,moisture conditioning and compaction, be performed just prior to aggregate base placement.Class 2 aggregate base should be uniformly moisture conditioned to the optimum moisturecontent and compacted to at least 95 percent of the ASTM D1557 maximum dry density.Subgrade preparation should conform to the recommendations in the previous paragraph.Proofrolling also should be performed on the completed aggregate base section prior to pavingoperations.
We understand that Portland cement concrete pavements will be used in some of the trainingareas. Portland cement concrete pavements should be at least 6 inches thick and underlain by6 inches of Class 2 aggregate base compacted to not less than 95 percent of ASTM D1557.Subgrade preparation and compaction should conform to the recommendations in the previousparagraph. Reinforcing for crack control, if desired, should consist of at least No. 3 reinforcingbars placed on maximum 24-inch centers each way throughout the slab. Reinforcement mustbe located at mid-slab depth to be effective. Joint spacing and details should conform with thecurrent PCA or ACI guidelines. Portland cement concrete should achieve a minimumcompressive strength of 3500 pounds per square inch at 28 days.
We also understand that some training areas will utilize a gravel surface, without an asphaltconcrete or Portland cement concrete wearing surface. To provide reasonable year roundsupport we recommend using a geogrid, such as Tensor BX1100 or the equivalent, coveredwith at least 12 inches of Class 2 aggregate base compacted in lifts to at least 95 percent of theASTM D1557 maximum dry density. Prior to placement of the geogrid, the soil subgrade shouldbe scarified to at least six inches, moisture conditioned to at least the optimum moisture content,and compacted to not less than 95 percent of ASTM D1557. Without an asphalt or concretewearing surface there is an increased potential for the underlying subgrade to become saturatedand unstable. This likely would increase maintenance costs and should be considered in thedesign.
Efficient drainage of all surface water to avoid infiltration and saturation of the supportingaggregate base and subgrade soils is important to pavement performance. We suggestconsidering the use of full-depth curbs where pavements abut landscaped areas to serve as acut-off against water migrating into the pavement base and subgrade materials. Weep holesalso could be provided at drop inlets, located at or slightly below the subgrade-base interface, toallow accumulated water to drain from beneath the pavements.
Geotechnical Engineering Report Page 22PG&E TRAINING FACILITYWKA No. 9974.01September 22, 2014
Materials quality and construction within the structural sections of the pavement should conformto the applicable provisions of the latest editions of the Caltrans Standard Specifications andYolo County Improvement Standards, latest editions.
Site Drainage
Site drainage should be accomplished to provide positive drainage of surface water away fromthe structures and prevent ponding of water adjacent to foundations. The grades adjacent tothe structures should be sloped away from foundations at a minimum two percent for a distanceof at least five feet. We suggest consideration be given to connecting all roof downspouts tosolid drainage pipes that convey water away from the buildings to available drainage features,or discharging downspouts onto concrete or asphalt surfaces that slope away from structures.
Geotechnical Engineering Observation and Testing During Earthwork
Site preparation should be accomplished in accordance with the recommendations of thisreport. Geotechnical testing and observation during construction is considered a continuation ofour geotechnical engineering investigation. Wallace-Kuhl & Associates should be retained toprovide testing and observation services during site preparation, earthwork, and foundationconstruction at the project to verify compliance with this geotechnical report and the projectplans and specifications, and to provide consultation as required during construction. Theseservices are beyond the scope of work authorized for this investigation.
In the event that Wallace-Kuhl & Associates is not retained to provide geotechnical engineeringobservation and testing services during construction, the Geotechnical Engineer retained toprovide these services should indicate in writing that they agree with the recommendations ofthis report, or prepare supplemental recommendations as necessary. A final report by the“Geotechnical Engineer” should be prepared upon completion of the project.
LIMITATIONS
Our recommendations are based upon the information provided regarding the proposed project,combined with our analysis of site conditions revealed by the field exploration and laboratorytesting programs. We have used our engineering judgment based upon the informationprovided and the data generated from our investigation. This report has been prepared insubstantial compliance with generally accepted geotechnical engineering practices that exist in
SITE
PUTAH CREEK RD
BUCK
EYE
RD
MAIN ST
BAKER ST
ABBEY ST4TH ST
EAST STRAILROAD AVE
MORGAN ST
COUN
TY R
OAD
89
COUN
TY R
OAD
90
COUNTY ROAD 33
Putah Creek
Dry Slough
Willow Canal
Dry Creek
High
land C
anal
ROAD 90A
BOYCE RD
GADDINI RD
WINTERS RD
EDWARDS ST
MAIN ST
3RD ST
1ST ST
2ND ST
RUSSELL ST
THORPE RD
ABBEY ST
WALN
UT LN
ANDERSON AVE
HEME
NWAY
ST
BOWMAN RD
WALNUT
BAKER ST
RACE COURSE LN
FEEDRANCHS DR
IVY LOOP
MOODY SLOUGH RD
DUTT
ON S
T
CREEKSIDE WAYMAPLE LN
COLBY LN
WINTU WAY
VILLAGE CIR
ALMOND DR
JOHNSON RD
LUPINE WAY
RAILROAD AVE
WILDROSE LN
MARTINEZ WAY
WOLFSKILL ST
APRICOT AVE
CARR
ION
CIR
CEMETERY DR
DRY CREEK LN
ELLIOTT ST
OWINGS DR
ORCHARD LNGRIFFIN WAY
ALMERIA PL
MYRTLE CIR
GATEWAY CT
BETTY CT
NIEMANN ST
BAKER ST
MAIN
ST
!"#$505
WKA NO. 9974.01
FIGUREDRAWN BYCHECKED BYPROJECT MGRDATE
1TJCGJFSLF9/14
VICINITY MAPPG&E TRAINING FACILITY
Winters, California
±0 1,000 2,000
Feet
Street data courtesy of ESRI, 2010.Hydrography courtesy of the U.S. Geological Surveyacquired from the GIS Data Depot, December, 2007.Projection: NAD 83, California State Plane, Zone II
Í!
Í!
Í!
Í!Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!
Í!
"DC
"DC
"DC
Í!Í!
Í!
Í! Í!
Í!
Í!
P3
P2P1
D9
D8
D7
D6
D5D4
D3
D2
D1
D29
D28
D27
D26
D25
D24
D23
D22
D21
D20D19
D18
D17
D16
D15
D14D13
D12
D11
D10
D107
D106
D105D104
D103D102
D101
WKA NO. 9974.01
FIGUREDRAWN BYCHECKED BYPROJECT MGRDATE
2TJCGJFSLF9/14
SITE PLANPG&E TRAINING FACILITY
Winters, California
±0 150 300
Feet
Adapted from a drawing prepared by Dreyfuss &Blackford Architects, dated August 20, 2014.Projection: NAD 83, California State Plane, Zone II
LegendÍ! Approximate soil boring location"DC Approximate percolation test location
Project PG&E Training Facility
Projec't Location: Vllinters, Califomia
WKANumber: 9974.01
LOG OF SOIL BORING DI
Sheet 1 of 1
ff'.¿,Jjiåt, 4- sotid Ftishr Augers Blll',?3"- Hins¡deDrining Ii$J,,'ofiBjl s.o reet
D¡amete(s)of Hole, inches
Approx. SurfaceElevation. ft MSL
Driving Method 140 lb automatic
o@
¿F
UlJLil
ENGINEERING CLASSIFICATION AND DESCRIPTIONJ
ztr.g'¡ãt:<F
Bor¡ng terminated at 5 feet below existing site grade
FIGURE 3
Project: PG&E Training FacilityProject Location: Wnters, Califomiaþ1ll(ANumber: 9974.01
LOG OF SOIL BORING D2
Sheet 1 of 1
BfiF"(å) rzgol1g LooqedBV-_ tr\rF Checked
By SLF
il!','jjåt, 4- sotid Ftisht Ausers | 3äll,?3"., Hirlside Dririns Ii$l,''oÊåj: 5.0 reer
Drill RioI VDE B.24 Diameter(s)
of Hole. inchesApprox. SurfaceElevation. ft MSL
G_roundwate-r Depth Groundwate.r was not I p_ampli¡g Open drive sampler with GinchlElevationl, feet encountered I Method(é) slêeve Bå'lnllfr'" Gunínss
Remarks Driving Method 140 lb automaticand Drop hammer, 30 inch droo
o,o
¿oF
uJ
ut
o_o
:Êt-(Itilo
(9oJo-ÀÉ.(,
ENGINEERING CLASSIFICATION AND DESCRIPTION
SAMPLE DATA TEST DATA
UIL
U)
rr ff;H<lu>z
U)
x.7UJO
>ozo
su.-trpr2==õ
>=tuõÈ
zoF9õ6c}U<t'-
J
Brown, moist, loose, clayey, sandy silt (ML) D2 (0-5)
Boring terminated at 5 feet below existing s¡te grade.
Wallace F(uhl FIGURE 4& asS0ctaTES\\f
Proiect: PG&E Training FacilityProject Location: Winters, Galifornia
WKA Number: 9974.01
LOG OF SOIL BORING D3
Sheet 1 of 1
liFJ,Pfifll! s.oreer
Approx. SurfaceElevation. ft MSL
$.a4pling. Open drive sampler with GinchMethod(s) sléeve Båtf]fl'" cuttinss
o¿tr
ulJul
ENGINEERING CLASSIFICATION AND DESCRIPTION
TEST DATA
U)
uÈr.u O>dlzO
Boring terminated at 5 feet below existing site grade
FIGURE 5
Project PG&E Training Facility
Project Location: Wnters, Galifornia
WKANumber: 9974.01
LOG OF SOIL BORING D4
Sheet 1 of 1
BîlË$) 1z3ot1s I Loqoedlei- GJF CheckedBy SLF
DrillinoMethoI 4" Solid Flight Augers 8!ll,?å"", HirsideDririns IiBl,?ÊBT! 15.0 reer
Drill RigTvpe B.24
Diamete(s)of Hole. inches
Approx. SurfaceElevation, ft MSL
Groundwater Depth Groundwater was not I Sampling Open drive sampler with Ginch[Elevation], feet encountered I Method(s) sléeve B:[f|fl'" Guttinss
Remarks Bulk D4 (0-3') Driving Method 140 lb automaticand Drop hammer, 30 inch drop
o.o
¿F-
uJ
t
o_o
rFùUo
oJ
=Àt
ENGINEERING CLASSIFICATION AND DESCRIPTION
SAMPLE DATA TEST DATA
UJÈ
(t
,,tÉ.
;H<fa2
U)øìruO>d]zO
sU,.q2
*z=õ
2+>=õì
zty)^^õüi< t--
f,
10
15
Brown, moist, loose, fìne sandy silt (ML)
very roose
D+11
D4-21
D4-31
D4-41
7
5
33
tl
'12.3
17.5
89
89
EITRIAX
Brown, moist, very stiff, silty clay (CL)
stiff
Boring terminated at 15 feet below existing site grade.
Wællace l(uhl FIGURE 6GASSOCIATES\\f
Project: PG&E Training FacilityProject Location: Wnters, CalifomiaWKANumben 9974.01
LOG OF SOIL BORING D5
BiTi"f) ntsons
il'¿','ül% 4'sorid Frisht Augers],"$J,,o, ÊB,|! 25.0 reer
Approx. SurfaceElevat¡on. ft MSL
Groundwater Deoth Groundwater was not
Remarks Bulk D5 (0-3') Driving Method 140 lb automaticand Drop hammer, 30 inch
q).0)
¿t-
tilú
ENGINEERING CLASSIFICATION AND DESCRIPTION)zo=9oul<F
Brown, moist, loose, fìne sandy silt (ML
row-nlmãstmeãiumìense,ãtty,ãanoy,[eãg-raGt(c-Na)
Organic
2.48%
Brown, moist, stiff, silty clay (CL)
Boring terminated at 20 feet below existing site grade
FIGURE 7
LOG OF SOIL BORING D6
Sheet I of 1
Project PG&E Training Facility
Project Location: Wnters, California
WKANumber: 9974.01
B'¿','ißT 4- sorid Frighr Ausers li$l,?fi3|! 16.5 reer
Approx. SurfaceElevation. ft MSL
Sampling Open drive samplerwith GinchMettiod(õ) sl'eeve
Remarks Bulk D6 (0-3')
ENGINEERING CLASSIFICATION AND DESCRIPTION
TEST DATAo.o
¿F
ulJul
, moist, loose, sandy silt (ML)
É rown lmo¡st, tooselsãovãlt t n¡-t-l
1? 2
Boring terminated at 16.5 feet below existing site grade.
FIGURE 8
Project: PG&E Training FacilityProject Location: Wnters, CaliforniaW(ANumber: 9974.01
LOG OF SOIL BORING D7
Sheet 1 of 1
ffË'lji¡% 4' sorid Frisht Ausers],"F1,o, fig,|! 5.0 reet
Approx. SurfaceElevation. ft MSL
feet encountered$_ampli¡1g. Open drive samplerwith GínchMethod(s) slèeve
oo
¿o
ulú
ENGINEERING CLASSIFICATION AND DESCRIPTION
Brown, moist, loose, slightly clayey, sandy
Boring terminated at 5.5 feet below existing site grade.
FIGURE 9
Project: PG&E Training FacilityProject Location: Winterc, CaliforniaWI(A Number: 9974.01
LOG OF SOIL BORING D8
Sheet 1 of 1
ff!','üåt, 4'sorid Frisht Ausers
Approx. SurfaceElevation. ft MSL
$ampling. Open drive sampler with 6-inchMethod(s) sléeve
ENGINEERING CLASSIFICATION AND DESCRIPTION
Brown, moist, loose, slightly clayey, silty fine sand
morst, verv mn, siltv-clav-tcl-l -
Boring terminated at 20 feet below ex¡sting site grade.
FIGURE 1O
LOG OF SOIL BORING D9
Sheet 1 of 1
Project: PG&E Training Facility
Project Location: Wnters, California
WKA Number: 9974.01
ffËiJijl% 4'sorid Frisht Ausers
Diamete(s)of Hole, inches
Groundwater Deoth Groundwater was not Sampling Open drive samplerwith 6-inchMethod(s) sleeve
Remarks Bulk D9 (4%'-7'l
ENGINEERING CLASSIFICATION AND DESCRIPTION
Dark brown, moist, very stiff, silty clay (CL)
Borlng terminated at 15 feet below exist¡ng site grade
FIGURE 11
Project PG&E Training Facility
Project Location: Wnters, Galifornia
V1[(ANumber: 9W4.01
LOG OF SOIL BORING DIO
RË','Ài% 4" sorid Frishr Ausers ]i$J,uofio"l! 5.0 reer
Diamete(s)of Hole. inches
Approx. SurfaceElevation. ft MSL
Groundwater Deoth Groundwater was not[Elevatíonl. feet encountered
Dr¡ving Method 140 lb automaticand Drop hammer,30 inch
oe¿F
utJtIJ
ENGINEERING CLASSIFICATION AND DESCRIPTION z
=?)ãt;õüi<t-
loose, fine sandy silt (ML)
Boring terminated at 5 feet below existing site grade.
FIGURE 12
Project: PG&E Training FacilityProject Location: Winters, Galifornia
WKA Number: 9974.01
LOG OF SOIL BORING DII
ilËïijl% 4'sorid Frisht Ausers"Ir"F|,o,
fioo!! 2o.o reet
Approx. SurfaceElevation. ft MSL
Groundwater Depth Groundwater was not[Elevation]. feet encountered
Sampling. Open drive samplerwith GinchMethod(s) slêeve
Remarks Bulk D11 (0-3')
oe¿oF
utJtiJ
ENGINEERING CLASSIFICATION AND DESCRIPTION
rown, mãsf tooê, sin-vlne sanA-tSVl-
D11-ll
Dl 1-3t
D11-51
Óã¡<-¡rowi¡nãst _verv
mn, s¡¡ty-clay-(cl)- -
Boring terminated at 20 feet below existing site grade
FIGURE 13
ProjecÍ PG&E Training Facility
Project Location: Winters, Califomia\lì/l(ANumber: 9974.01
LOG OF SOIL BORING D12
Bil¡"f) lnrsotl3
li$j,,| Ê[1|3 rs.o reet
Diameter(s) 'iof Hole. inches + Approx. SurfaceElevation. ft MSL
Groundwater Depth Sampling. Qpen drive sampler with 6-inchMethod(s) slêeve
@.o
2t-
tU
ú
ENGINEERING CLASSIFICATION AND DESCRIPTIONo.o
zl>=egõ=
D12-11
D12-31
D12-41
Boring terminated at 15 feet below existing site grade.
FIGURE I4
LOG OF SOIL BORING DI3Project PG&E Training FacilitY
Project Location: Winters, California
WKANumber: 9974.01
Ii$l,,?fi3l! 2o.o reetilË'lülT 4'sotidFtishtAugers
Aoprox. SurfaceEleivation. ft MSL
Diamete(s)of Hole, inches
Sampling Open drive sampler with 6-inchMethod(s) sleeve
Method 140 lb automaticRemarks Bulk D13 (0-3')
ENGINEERING CLASSIFICATION AND DESCRIPTION
oo
¿É
UJJul
ttt3ruO>dlzo
Dl3-l I
D13-31
D13-41
D13-51
Boring terminated at 20 feet below existing site grade
FIGURE 15
Project: PG&E Training Facility
Project Location: Winters, Galifornia
V1fr(A Number: 9974.01
LOG OF SOIL BORING D14
BîTËr;) 1zsot13
]iBJ,',oÊBT! 16.5 reerffËiül% 4'sorid Frishr Ausers
Approx. SurfaceElevation. ft MSL
Sampling Open drive samplerwith 6-inchMethod(s) sleeve
Remarks Bulk D14 (0-3')
ENGINEERING CLASSIFICATION AND DESCRIPTION
rown, moist, loose, silty fine sand (SM)
-¡rownlmãst very st¡tt, s¡lty-clay-tCt-f - - -
eõw-n,-mã;I st¡n, cøGv-s¡lt @Ll
D14-21
D14-31
D14-41
Boring terminated at 16.5 feet below existing site grade
FIGURE 16
Project: PG&E Training Facility
Project Location: Winters, Galifornia
WKANumber: 9974.01
LOG OF SOIL BORING D15
Sheet 1 of 1
BilË$) lntßr1s
lifj'| fiåT! 2o.o reetff'¿','ül% 4- sorid Frishr Ausers
Approx. SurfaceElevation, ft MSL
Groundwater Deoth Groundwater was not$BET"or*"
sampler with 6-inch
Remarks Bulk Dl5 (0-3')
ENGINEERING CLASSIFICATION AND DESCRIPTION
@C)
¿t-
tiJJuJ
õr(L
É.
moist, loose, , silty fine sand (SM)
medium dense
õw-n¡nãst Grv st¡tt, s¡lt[clavJcTf - - - -
Boring terminated at 20 feet below existing site grade.
D15-21
FIGURE 17
Project PG&E Training Facility
Project Location: Winters, California
WKANumber: 9974.01
LOG OF SOIL BORING D16
Sheet 1 of 1
BiTi.$) 1zr1st13
flË'Jißt, 4'sorid Frishr Ausers
Groundwater Depth Groundwater was notlElevation]. feet encountered $B:l"on*
sampler with 6-inch
ENGINEERING CLASSIFICATION AND DESCRIPTION
õ.g)
¿F
IUJuJ
oJo-ÈÉ.
fìne sand (SM)
medium dense
Brown, mãst, verv mf, srtty ctav-tCTl-
Boring terminated at 15 feet below existing site grade.
D16-l I
D1 6-31
D16-41
FIGURE 18
Project: PG&E Training FacilityProject Location: Wnters, Galifornia
WKA Number: 9974.01
LOG OF SOIL BORING DI7
ilË','iå% 4'sorid Frishr Ausers
Approx. SurfaceElevation. ft MSL
Groundwater Depth Groundwater was notBål*Tfl'" cutrinss
Method 140 lb automatic'p hammer.30 inch
oo
¿l-
uJ
[i
ooõI(L
t(9
ENGINEERING CLASSIFICATION AND DESCRIPTION
TEST DATA
t7UJO
>dlzo
Brown, moist, stiff, silty clay (CL)
Brown, moist, loose, clayey sand (SC)
rowr,-mo¡sf very st¡f , s¡ lty-clay-tC l- I
D17-'ll
D17-21
D17-31
D17-41
Boring terminated at 16.5 feet below existing site grade.
FIGURE 19
Project PG&E Training Facility
Project Location: Winters, California
WKA Number: 9974.01
LOG OF SOIL BORING D18
Sheet I of I
Bili.$) lntsotl3 [ïsseo cJF CheckedBv SLF
ff'¿','jlåI 4" sorid Frishr Ausers 3å11,?3"- HinsideDririns L"$J,,?fiBl! 5.0 reer
frillRio 824 Diameterls)of Hole. inches + Approx. Surface
Elevation, ft MSL
Groundwater Deoth Groundwater was notlElevationl, feet encountered
Sampling Open drive sampler with ÈinchMethodls) sleeve BåI*Tfr* cuninss
Remarks Drivinq Method 140 lb automaticand Diop hammer. 30 inch drop
oo¿F
tUJIU
.o
-ÈuJo
(,JIIÈÍ.
ENGINEERING CLASSIFICATION AND DESCRIPTION lrJ
(t)
;AMPLE D/
¡ttTHã=u)z
TA
U)tÈH9>dìzo
TE
sx2ts-2Z
=õ
iST DI
E
,TA
)zoF?a6c)u<F.
-5
Brown, moist, Ioose, sandy silt (ML) Dr8 (0-5) urganrccontent3.15%
Boring terminated at 5 feet below ex¡sting s¡te grade.
Wallace Kuh FIGURE 20\\f ASSOCIATES
Project PG&E Training Facility
Project Location: Wnters, California
WKANumber: 9974.01
LOG OF SOIL BORING D19
RËiijlt, 4- sorid Frishr Ausers
Diameter(s)of Hole, inches
Approx. SurfaceElevation. ft MSL
Groundwater Depth Groundwater was notIElevationl. feet encountered
Remarks Bulk Dl9 (0-3') Driving Method 140 lb automaticand Drop hammer. 30 inch
ENGINEERING CLASSIFICATION AND DESCRIPTION
õ.0)
¿Ë
uJJLIJ
(,oõrÈúo
D19-1 |
D19-21
Dl9-31
D19-51
Boring terminated at 20 feet below existing site grade.
F¡GURE 21
Project: PG&E Training Facility
Project Location: Winters, Galifomia
WKA Number: 9974.01
LOG OF SOIL BORING D2O
Drilled
flËiJlßt, 4- sorid Frisht Augers L"$J,,o,Ên"1|! 2o.o reer
?[|'"*'n e,24 Diameter(s)of Hole. inches
Approx. SurfaceElevation. ft MSL
Dr¡v¡ng Method 140 lb automatic
o).lD
¿ot-
LrJJuJ
õe-t!ulo
ENGINEERING CLASSIFICATION AND DESCRIPTION
Brown, moist, loose, silty fine sand
, moist, loose, clayey, sandy silt (ML)
row-n, mõðf mø¡umiense,Tme san¿v, s¡ltv cøvTcTl- - -
-gõw-nlmãst" lt¡n, c-nvev s¡lt tlt¡Ð - - - - -
irown, moist, very stiff, silty clay (CL)
D20-11
D20-31
D20-51
17.8
Boring terminated at 20 feet below existing grade
FIGURE 22
Project: PG&E Training Facility
Project Location: Winters, Galifomia
l/ìll(ANumber: 9974.01
LOG OF SOIL BORING D21
Bil¡"f) nt1urt3
],"Bl,Pfin"T! 2o.o reer
Approx. SurfaceËlevation. ft MSL
Groundwater Deoth Groundwater was notfElevationl. feet encountered
Drivinq Method 140 lb automaticand Diop hammer, 30 inch
ENGINEERING CLASSIFICATION AND DESCRIPTION
, moist, loose, clayey fine sand (SC)
moist, stiff, s¡lty clay (CL)
b rown ,_mã st na ø, ã nv -d aV tõt-T
D21-11
Bor¡ng terminated at 2O feet below existing site grade.
FIGURE 23
LOG OF SOIL BORING D22Project: PG&E Training Facility
Project Location: Wnters, Califomia
WKANumber: 9974.01
fl,jllå% 4- sorid Frishr Ausers
Aoorox. SurfaceEleivation. ft MSL
Groundwater Depth Groundwater was not
ENGINEERING CLASSIFICATION AND DESCRIPTION
õe¿oF
I,IJ
ú
U)r.ÈUJO
>drzO
zF9
<FBrown, mo¡st, loose, slightly clayey, sandy silt
Boring terminated at 5 feet below existing site grade.
FIGURE 24
ProjecÍ PG&E Training FacilityProject Location: Winters, CaliforniaV1[(ANumben 9974.01
LOG OF SOIL BORING D23
BiT¡"f) enu13
li$J,,?ÊB[ 2o.o reer
Diameter(s)of Hole, inches
Approx. SurfaceElevation. ft MSL
Groundwater Depth Groundwater was not[Elevationl, feet encountered
o.c)
¿F
UJJttl
ENGINEERING CLASSIFICATION AND DESCRIPTION
Brown, mo¡st, very stiff, silty clay (CL)
D23-'tl
D23-21
D23-5t
Boring terminated at 20 feet below existing site grade.
FIGURE 25
Project: PG&E Training FacilityProject Location: Vlfinters, CalifomiaWKA Number: 9974.01
LOG OF SOIL BORING D24
Bil¡"f) pr,tsr3
ff'¿','liàT 4'sorid Frishr Ausers ]i$l,",ÊBì: is.oreer
D¡ameter(s)of Hole, inches
Approx. SurfaceElevation. ft MSL
Sampling Open drive sampler with GinchMettiod(õ) sl'eeve
Remarks Bulk D24 (0-3') Driving Method 140 lb automaticand Drop hammer, 30 inch
ENGINEERING CLASSIFICATION AND DESCRIPTION .o
=+>=õl
-eõwn$ãst, Tery mff;eyeysilt (fli
D24-21
D24-41
Boring terminated at 15 feet below existing s¡te grade.
FIGURE 26
Project: PG&E Training Facility
Project Location: Wnters, CalifomiaW](ANumber: 9974.01
LOG OF SOIL BORING D25
BiTÊ(å) pnsn3
ffËiüåT 4' sorid Frishr Ausers J¡BJ,,?ÊBÌ! 16.s reer
Diamete(s)of Hole, inches
Approx. SurfaceElevation. ft MSL
Sampling. Open drive samplerwith &inchMethod(s) sléeve
Dr¡ving Method 140 lb automaticand Drop hammer,30 ínch
ENGINEERING CLASSIFICATION AND DESCRIPTIONJ
zo+9õ6OU<F
rown,-mor-st very st¡tf, s¡lty claVJCTi-
D25-11
Boring terminated at 16.5 feet below existing site grade
FIGURE 27
Project: PG&E Training FacilityProject Location: Winters, CalifomiaWKANumber: 9974.01
LOG OF SOIL BORING D26
ilËilllt, 4'sorid Frisht Ausers
Diamete(s)of Hole. inches
Approx. SurfaceElevation, ft MSL
Drivino Method 140 lb automaticand Diop hammer, 30 inch
o.o
¿F
Lu
uJ
ENGINEERING CLASSIFICATION AND DESCRIPTION t,tú.fuJÀ(I¡
==cDZ
Brown, mo¡st, slightly clayey, silty fine sand (SM)
Brown, moist, very stiff, silty clay (CL)
Bor¡ng terminated at 16.5 feet below existing site grade.
FIGURE 28
Project PG&E Training Facility
Project Location: Winters, California
WKANumber: 9974.01
LOG OF SOIL BORING D27
BiTË$) nßotls
il'jiillft 4- sorid Frishr Ausers
Approx. SurfaceElevation, ft MSL
Groundwater Depth Groundwater was not[Elevation], feet encountered
Sampling Open drive sampler with 6-inchMethod(s) slèeve
Drivinq Method 140 lb automaticand Diop hammer. 30 inch
ENGINEERING CLASSIFICATION AND DESCRIPTION
ooõ-ùú
tìrJJ O>dlzo
Boring terminated at 5 feet below ex¡sting s¡te grade.
FIGURE 29
LOG OF SOIL BORING D28Project: PG&E Training FacilitY
Project Location: \Mnte¡s, California
WKANumber: 9974.01
"I,"8J,,?fiBT! 5.0 reerD"Ë'Jijlt, 4' sotid Frisht Ausers
Aoprox. SurfaceEleivation. ft MSL
ENGINEERING CLASSIFICATION AND DESCRIPTION
o
2F
uúi
moist, Ioose, sandy s¡lt (ML
Boring terminated at 5 feet below ex¡sting s¡te grade'
FIGURE 30
Project: PG&E Training FacilityProject Location: Winters, Galifornia
ìlì/l(ANumbe¡: 9974.01
LOG OF SOIL BORING D29
il[',',li]% 4- sorid Frishr Ausers
Approx. SurfaceElevation. ft MSL
Groundwater Deplh Groundwater was not$E:l"ot""
sampler with Èinch
o_o
¿o
tIlJ¡.IJ
ENGINEERING CLASSIFICATION AND DESCRIPTION e.3ruO>d]zO
,-mãst, st¡f, s¡ltñtay tCTi
D29-21
Brown, moist, medium st¡ff, silt cl
Bor¡ng terminatated at 16.5 feet below exist¡ng s¡te grade.
FIGURE 31
Projecf PG&E Training FacilityProject Location: Winters, GaliforniaWKANumber: 9974.01
LOG OF SOIL BORING D1O1
3äll|?å"",. v&wDririns, rnc. ]i$j,,PÊn",|: 1s.o reer
Approx. SurfaceElevation. ft MSL
Groundwater Depth Groundwater was not
Driving Method 140 lb automaticand Drop hammer, 30 inch
o
¿F
tU
ú
o
õI(L
Í.o
ENGINEERING CLASSIFICATION AND DESCRIPTION
moist, sand (
medium dense
Brown, mo¡st, very stiff, silty clay (CL)
very hard
Boring terminated at 15 feet below existing site grade. Groundwater was not encountered.
D10l-11
D101-21
D101-31
D101-41
FIGURE 32
Project: PG&E Training FacilityProject Location: lMnters, Galifornia
WKANumber: 9974.01
LOG OF SOIL BORING D1O2
Sheet 1 of I
Båll',?3..,. v&wDririns, rnc. li$j,,?fi3!! 21.steet
Approx. SurfaceElevation. ft MSL
Groundwater Depth Groundwater was notfElevationl, feet ' encountered Bål*!fr'" soirGutrings
Driving Method 140 lb automaticand Drop hammer,30 inch
o.o
¿F
ulJul
ENGINEERING CLASSIFICATION AND DESCRIPTION
rownlmor-õI GrV st¡ff, s-¡nv-clav-(Ct-)- - -
D102-11
D102-41
D102-51
Boring terminated at 21.5 feet below existing site grade. Groundwater was not encountered.
FIGURE 33
Project PG&E Training FacilityProject Location: Winters, Galifomia
WKA Number: 9974.01
LOG OF SOIL BORING D1O3
8åll',?å."' V&wDririns, Inc. #$},PÊB1|: 16.oreet
Diamete(s) ^rof Hole. inches s Approx. Surface
Elevation. ft MSLGroundwater Depth Groundwater was not
o.o
¿F
ulJUJ
ENGINEERING CLASSIFICATION AND DESCRIPTION zoF9qU<F
medium dense, silty fine sand (SM)
Brown, moist, very hard, silty clay (CL)
D103-41
Boring terminated at 16 feet below ex¡sting site grade. Groundwater was not encountered.
allaceKuhl FIGURE 34
Project: PG&E Training FacilityProject Location: Winters, GaliforniaVlll(ANumber: 9974.01
LOG OF SOIL BORING D1O4
fi'¿','ijl? sorid stem Augers Slll',?å"- v &wDririns, rnc. JiB/,,| ÊBÌ! 14.5 reer
Diamete(s)of Hole, inches
Approx. SurfaceElevation. ft MSL
Groundwater Depth Groundwater was not
oo
¿t-
Uú
ENGINEERING CLASSIFICATION AND DESCRIPTION
med¡um dense, silty f¡ne sand (SM)
-e rown,-mã st, GrV st¡rf , s i lt[c I ay-t C t- )- - - - - -
very hard
Boring terminated at 14.5 feet below existing site grade. Groundwater was not encountered.
D104-21
D1 04-31
FIGURE 35
Project: PG&E Training FacilityProject Location: Wnters, GaliforniaW(ANumber: 9974.01
LOG OF SOIL BORING DIOs
BiT¡"!') sH14
8ãll',?3"", v&wDrilins, Inc.
Diamete(s)of Hole, inches
Approx. SurfaceElevation. ft MSL
o.tD
¿F
Lu
ú
ENGINEERING CLASSIFICATION AND DESCRIPTION
Boring terminated at 5 feet below existing site grade.
FIGURE 36
Project: PG&E Training FacilityProject Location: Winters, CaliforniaWKANumber: 9974.01
LOG OF SOIL BORING D1O6
3åll',?å"". v&wDr¡uins,lnc. Ii$J,PfrBl! 5.0 reer
Diamete(s)of Hole, inches
Approx. SurfaceElevation. ft MSL
Groundwater Depth Groundwater was notlElevationl, feet encountered
Driving Method 140 lb automatic
og¿o
I,IJ
ú
ENGINEERING CLASSIFICATION AND DESCRIPTION
Boring terminated at 5 feet below existing s¡te grade.
FIGURE 37
Project: PG&E Training FacilityProject Location: Winters, CaliforniaWl(ANumber: 9974.01
LOG OF SOIL BORING Ð107
Sheet 1 of I
8ll1',?å"", v&wDriuins, rnc.
Diameterls)of Hole. inches o
Groundwater Depth Groundwater was not
Driving Method 140 lb automaticand Drop hammer.30 inch
ENGINEERING CLASSIFICATION AND DESCRIPTION
Dl07-l I
D107-21
D1 07-3t
D107-41
Brown, moist, very st¡ff, silty clay (CL)
Boring terminated at 15 feet below existing s¡te grade. Groundwater was not encountered
FIGURE 38
APPENDIX A
A. GENERAL INFORMATION
The performance of a geotechnical engineering investigation for the proposed PG&ETraining Facility to be constructed on the south side of East Grand Avenue, west ofHighway I-505, in Winters, California, was authorized by Alfa Tech ConsultingEnterprises, Inc. on August 22, 2014. Authorization was for an investigation asdescribed in our proposal letter dated August 22, 2014, sent to our client PG&ECorporate Real Estate, Strategy & Services, whose address is 245 Market Street, SanFrancisco, California; telephone (415) 403-3048.
The project civil engineering consultant is BKF Engineers, whose mailing address is 9809th Street, Suite 1770, Sacramento, California 95814; telephone (916) 556-5826.
The project structural engineering consultant is Buehler and Buehler StructuralEngineers, Inc., whose mailing address is 600 Q Street, Suite 200, Sacramento,California 95811; telephone (916) 443-0303; facsimile (916) 443-0313.
The project architectural consultant is Dreyfuss & Blackford, whose mailing address is3540 Folsom Boulevard, Folsom, California 95816; telephone (916) 453-1234.
In performing this investigation, we referenced the Winters Site Test Fit Plan preparedby Dreyfuss and Blackford Architects, dated August 20, 2014.
B. FIELD EXPLORATION
Twenty-nine borings were drilled on December 18, 2013 and seven additional boringswere drilled on September 5, 2014, utilizing a CME-55 truck-mounted drill rig at theapproximate locations shown in Figure 2. The borings were drilled to a maximum depthof approximately 21½ feet below existing site grades using six-inch diameter, solid flighthelical augers. At various intervals, relatively undisturbed soil samples were recoveredwith a 2½-inch O.D., 2-inch I.D., Modified California sampler driven by a 140-poundhammer freely falling 30 inches. The number of blows of the hammer required to drivethe 18-inch long sampler each 6-inch interval was recorded. The sum of the blowsrequired to drive the sampler the lower 12-inch interval, or portion thereof, is designatedthe penetration resistance or "blow count" for that particular drive.
The samples were retained in two-inch (2”) diameter by six-inch (6”) long thin-walledbrass tubes contained within the sampler. Immediately after recovery, the soils in the
WKA No. 9974.01 Page A2
tubes were visually classified by the field engineer and the ends of the tubes weresealed to preserve the natural moisture contents. All samples were taken to ourlaboratory for soil classification and selection of samples for testing.
The Logs of Soil Borings, Figures 32 through 38, contain descriptions of the soilsencountered at each boring location. A Boring Legend explaining the Unified SoilClassification System and the symbols used on the logs is contained on Figure 39.
C. LABORATORY TESTING
Selected undisturbed samples of the soils were tested to determine dry unit weight(ASTM D2937), natural moisture content (ASTM D2216), and shear strength by triaxialstrength testing (ASTM D4767). The results of the moisture content and unit weighttests are included on the Logs of Borings. The results of the triaxial shear strengthtesting are presented on Figures A1 and A2.
Five bulk samples of near-surface soil were subjected to Expansion Index testing(ASTM D4829); the results of the test are presented on Figures A3 through A7.
Four bulk samples of anticipated pavement subgrade soil were subjected to Resistance-value ("R-value") testing in accordance with California Test 301. The results of the R-value test, which were used in the pavement design, are presented on Figures A8through A10.
Six near-surface soil samples were submitted to Sunland Analytical to determine the soilpH and minimum resistivity (California Test 643), Sulfate concentration (California Test417) and Chloride concentration (California Test 422). The results of these tests arepresented on Figures A11 through A16.
Four hydrometer tests were performed on near-surface clays to determine thepercentage passing the No. 200 sieve (ASTM D422). The results of the hydrometertests are presented on Figures A17 through A20.
GRAVEL SANDSILT CLAY
COARSE FINE UUAKJtr MEDIUM FINE
I u s srlUlDARD srEVE | ,.r. sTANDARD srEVE NUMBERS II OPENING3' 1.5" 3t4" 3/8' t4 #10 #20 t40 f60 #',100 #200
t--otrA.'ts
d¡É.lur 50zl!t-zIIJ 4ñ(JÉ.t¡Jo-
10
1 0.1
PARTICLE SIZE IN MILLIMETERS
PARTICLE SIZE DISTR¡BUTIONProject: PG&E Training Facility
WKA No. 9974.01
l-(uhl t'*
¡
\\
\
BoringNumber
SampleNumber USCS
Depth(feet) Symbol LL PI Classification
D5 ML 0-3' a Brown, fine sandy silt
GRAVEL SANDSILT CLAY
COARSE FINE COARSE MEDIUM FINE
I ussrÁNDARDsrEVE | ,,.TANDARD',EVENUMBERS I I I¡ OPENING3" 1.5' 314" 318" i4 #10 t20 i40 #60 #1 00 #200
t-:Eou¡ Ants
oú.luJ 50ztrFzuJ 40C)ú.u¡È
10
'1 0.1
PARTICLE SIZE IN MILLIMETERS
PARTICLE SIZE DISTRIBUTIONProject PoGftS tJãä:s,FaciritY
l-(ur, I t'*
\
I -l
\a ----{
BoringNumber
SampleNumber USCS
Depth(feet) Symbol LL PI Classification
D19 D19 ML 0-3' o Brown, fine sandy silt
GRAVEL SANDSILT CLAY
COARSE FINE COARSE MEDIUM FINE
II
3"
U.S, STANDARD SIEVEOPENING'1.5' 3/4" 3/8"
I U.S. STANDARD SIEVE NUMBERS
#10 t20 #40 #60 #100
PARTICLE SIZE IN MILLIMETERS
BoringNumber
SampleNumber USCS
Depth(feet) Symbol LL PI Classification
D26 D26-l ñl 10' o Brown, silty clay
PARTICLE SIZE DISTRIBUTIONProject: PG&E Training Facility
WKA No. 9974.01
\\f w?=r l::e Kuhr FIGURE A19
GRAVEL SANDSILT CLAY
COARSE FINE COARSE NIEDIUM FINE
U.S. STANDARD SIEVEOPENING
1.5" 314" 3/8"
U.S, STANDARD SIEVE NUMBERS
#10 i20 t40 f60 i
PARTICLE SIZE IN MILLIMETERS
PARTICLE SIZE DISTRIBUTIONProject: PG&E Training Facility
WKA No. 9974.01
t-:EoUJ
=00
É.tIJzLLFzuJ()ú.lrJfL
N
ö
otsô(9
È
BoringNumber
SampleNumber USCS
Depth(feet) Symbol LL PI Classification
D27 D27 ML o Brown, fine sandy silt
\\f w:Jt=:e r(uhl FIGURE A2O
PERCOLATION TEST LOCATION P1
Time Interval (minutes) Water Drop (inches)
Incremental Percolation
Rate (inches/minute)
Percolation Rate
(inches/minute)
0 -- -- -- 5 5 1.0 1.0 15 1 0.10 0.43 25 3 0.30 0.38 35 1 0.10 0.30 45 1.5 0.15 0.26 55 1 0.10 0.23 65 1.5 0.15 0.22 75 1 0.10 0.20 85 2 0.20 0.20 95 0 -- 0.18 105 0.5 0.05 0.17 115 1.5 0.15 0.17 125 0.5 0.05 0.16 135 1 0.10 0.15 145 0.5 0.05 0.14 155 1 0.10 0.14 165 0.5 0.05 0.14 175 1 0.10 0.14 185 0.25 0.025 0.13 195 0.25 0.025 0.13 205 0.25 0.025 0.12 215 0.25 0.025 0.12 225 0.25 0.025 0.11 235 0.25 0.025 0.11
PERCOLATION TEST LOCATION P2
Time Interval (minutes) Water Drop (inches)
Incremental Percolation
Rate (inches/minute)
Percolat ion Rate
(inches/minute)
0 -- -- -- 5 7 1.4 1.4 15 6.5 0.65 0.9 25 5.5 0.55 0.76 35 3 0.30 0.62 45 3 0.30 0.55 55 2 0.20 0.49 65 1.5 0.15 0.43 75 1 0.10 0.39 85 2 0.20 0.37 95 0 -- 0.33 105 1 0.10 0.31 115 1 0.10 0.29 125 0.75 0.075 0.27 135 0.25 0.025 0.25 145 1 0.10 0.24 155 1 0.10 0.23 165 0.5 0.05 0.18 175 0.5 0.05 0.17 185 0 -- 0.16 195 0.5 0.05 0.16 205 0.5 0.05 0.15 215 0.5 0.05 0.15 225 0.5 0.05 0.13 235 0.5 0.05 0.13
PERCOLATION TEST LOCATION P3
Time Interval (minutes) Water Drop (inches)
Incremental Percolation
Rate (inches/minute)
Percolat ion Rate
(inches/minute)
0 -- -- -- 5 13 2.6 2.6 15 8.5 0.85 1.43 25 4 0.40 1.02 35 2.5 0.25 0.80 45 1.5 0.15 0.65 55 1.5 0.15 0.56 65 1 0.10 0.49 75 2 0.20 0.45 85 2 0.20 0.42 95 0.25 0.025 0.38 105 0.75 0.075 0.35 115 1 0.10 0.33 125 0 -- 0.30 135 0.25 0.025 0.28 145 0.25 0.025 0.26 155 0.75 0.075 0.25 165 0.5 0.05 0.19 175 0.5 0.05 0.18 185 0.5 0.05 0.18 195 0 -- 0.17 205 0.25 0.025 0.16 215 0.25 0.025 0.16 225 0.50 0.05 0.13 235 0.25 0.025 0.13
APPENDIX BGUIDE EARTHWORK SPECIFICATIONS
PG&E TRAINING FACILITYEast Grant Avenue, West of I-505
Winters, CaliforniaWKA No. 9974.01
PART 1: GENERAL
1.1 SCOPEA. General Description
This item shall include clearing of all surface and subsurface structuresassociated with current development on site, remnants of former structures,including all foundations, surface debris, trees, vineyards and associated items;below grade irrigation systems; preparation of surfaces to be filled, filling,spreading, compaction, observation and testing of the fill; and all subsidiary worknecessary to complete the grading to conform with the lines, grades and slopesas shown on the accepted Drawings.
B. Related Work Specified Elsewhere1. Trenching and backfilling for sanitary sewer system: Section ______.2. Trenching and backfilling for storm drain system: Section ______.3. Trenching and backfilling for underground water, natural gas, and electric
supplies: Section ______.C. Geotechnical Engineer
Where specific reference is made to "Geotechnical Engineer" this designationshall be understood to include either him or his representative.
1.2 PROTECTIONA. Adequate protection measures shall be provided to protect workers and passers-
by at the site. Streets and adjacent property shall be fully protected throughoutthe operations.
B. In accordance with generally accepted construction practices, the Contractorshall be solely and completely responsible for working conditions at the job site,including safety of all persons and property during performance of the work.This requirement shall apply continuously and shall not be limited to normalworking hours.
C. Any construction review of the Contractor's performance conducted by theGeotechnical Engineer is not intended to include review of the adequacy of theContractor's safety measures, in, on or near the construction site.
WKA No. 9974.01 Page B2
D. Adjacent streets and sidewalks shall be kept free of mud, dirt or similarnuisances resulting from earthwork operations.
E. Surface drainage provisions shall be made during the period of construction in amanner to avoid creating a nuisance to adjacent areas.
F. The site and adjacent influenced areas shall be watered as required to suppressdust nuisance.
1.3 GEOTECHNICAL REPORTA. A Geotechnical Engineering Report (WKA No. 9974.01; dated September 22,
2014) has been prepared for this site by Wallace - Kuhl & Associates,Geotechnical Engineers of West Sacramento, California. A copy is available forreview at the office of Wallace - Kuhl & Associates.
B. The information contained in this report was obtained for design purposes only.The Contractor is responsible for any conclusions they may draw from thisreport. Should the Contractor prefer not to assume such risk, they should employtheir own experts to analyze available information and/or to make additionalborings upon which to base their conclusions, all at no cost to the Owner.
1.4 EXISTING SITE CONDITIONSThe Contractor shall be acquainted with all site conditions. If unshown active utilities areencountered during the work, the Architect shall be promptly notified for instructions.Failure to notify will make the Contractor liable for damage to these utilities arising fromContractor's operations subsequent to the discovery of such unshown utilities.
1.5 SEASONAL LIMITSFill material shall not be placed, spread or rolled during unfavorable weather conditions. When the work is interrupted by heavy rains, fill operations shall not be resumed untilfield tests indicate that the moisture contents of the subgrade and fill materials aresatisfactory.
PART 2: PRODUCTS
2.1 MATERIALSA. All fill shall be of approved local materials from required excavations,
supplemented by imported fill, if necessary. Approved local materials aredefined as local granular soils, which are free from significant quantities ofrubble, rubbish and vegetation, and having been tested and approved by theGeotechnical Engineer prior to use. Clods, rocks or hard lumps exceeding sixinches (6") in final size shall not be allowed in the upper two feet (2') of any fillsupporting pavements and the buildings.
WKA No. 9974.01 Page B3
B. Imported fill materials shall be approved by the Geotechnical Engineer; they shallmeet the above requirements; shall have a maximum expansion index notexceeding twenty (20) when tested in accordance with ASTM D4829; and, shallbe of three-inch (3") maximum particle size. Imported fill materials used withinpavement limits shall possess a minimum Resistance value of twenty (20) whentested in accordance with California Test 301.
C. Capillary barrier material under floor slabs shall be provided to the thicknessshown on the Drawings. This material shall be clean gravel or crushed rock ofone-inch (1") maximum size, with no material passing a Number four (#4) sieve.
D. Asphalt concrete, aggregate base, aggregate subbase, and other pavingproducts shall comply with the appropriate provisions of the State of California(Caltrans) Standard Specifications and Yolo County Improvement Standards,latest editions.
PART 3: EXECUTION
3.1 LAYOUT AND PREPARATIONLay out all work, establish grades, locate existing underground utilities, set markers andstakes, set up and maintain barricades and protection of utilities--all prior to beginningactual earthwork operations.
3.2 CLEARING, GRUBBING AND PREPARING BUILDING PADS AND PAVEMENT AREASA. The site shall be cleared of all surface rubble and debris, existing and remnants
of former structures designated for removal including, but not limited to,foundations, slabs, irrigation systems, concrete rubble, and debris. Existingutilities designated to be removed or abandoned shall include all trench backfill.The ends of abandoned pipes shall be plugged. Trees and shrubs shall includethe entire rootball and all roots larger than one-half inch (½") in diameter. On-sitewells, septic tanks, and leach fields shall be properly abandoned in accordancewith Yolo County Environmental Health Department requirements.
B. Remaining surface organics shall be removed by stripping. For bid purposes thestripping shall be three inches (3”). Strippings shall be removed from the site orreused in landscape areas. If reused on-site the strippings shall not extendwithin five feet (5’) of any building or pavement areas. Strippings shall bemoisture conditioned and receive compactive effort.
C. The upper twenty-four (24") of soil within building areas shall be sub-excavated.The sub-excavations shall extend at least five feet (5’) beyond the proposedfootprint of the buildings, including adjacent flatwork. The exposed soils shall bescarified to a depth of twelve inches (12”). After scarification the soils shall beuniformly moisture conditioned to at least the optimum moisture and compacted
WKA No. 9974.01 Page B4
to at least ninety percent (90%) of the ASTM D1557 Compaction Test.Compaction shall be accomplished with a Caterpillar 825 or equivalent sizedcompactor.
D. Horizontal and vertical control of the limits of over-excavation, scarification andcompaction shall be responsibility of the Contractor and/or Project Civil Engineer.
E. After rough subgrade elevation has been achieved in pavement areas an othernon-building areas, the exposed soils shall be scarified to a depth of at leasteighteen inches (18”) and all exposed unsuitable materials removed and hauledoff site. The scarified soils shall then be moisture conditioned to at least theoptimum moisture content and be compacted to at least ninety percent (90%) ofthe ASTM D1557 Compaction Test.
F. The Contractors bid shall include a cost per cubic yard for removal of unsuitablematerials from building or pavement areas, and replacement with engineered fillas required.
3.3 PLACING, SPREADING AND COMPACTING FILL MATERIALA. The selected soil fill material shall be placed in layers which when compacted
shall not exceed six inches (6") in thickness. Each layer shall be spread evenlyand shall be thoroughly mixed during the spreading to promote uniformity ofmaterial in each layer.
B. When the moisture content of the fill material is below the optimum moisturecontent, water shall be added until the proper moisture content is achieved.Soils shall be thoroughly moisture conditioned to at least the optimum moisturecontent.
C. When the moisture content of the fill material is too high to permit the specifieddegree of compaction to be achieved, the fill material shall be aerated by bladingor other methods until the moisture content is satisfactory.
D. After each layer has been placed, mixed and spread evenly, it shall bethoroughly compacted to at least ninety percent (90%) as determined by theASTM D1557 Test Method. Compaction shall be undertaken with a self-propelled sheepsfoot compactor capable of achieving the specified density(Caterpillar 825 or equivalent compactor). Compaction shall be accomplishedwhile the fill material is at the required moisture content, and the moisturecontent shall be uniform throughout each layer. Each layer shall be compactedover its entire area until the desired density has been obtained.
E. The filling operations shall be continued until the fills have been brought to thefinished slopes and grades as shown on the accepted Drawings.
WKA No. 9974.01 Page B5
3.4 FINAL SUBGRADE PREPARATIONThe upper twelve inches (12") of all final building pad subgrades and the uppersix inches (6") of all pavement subgrades and subgrades supporting flatworkshall be properly scarified, brought to a uniform moisture content, and shall beuniformly compacted to not less than:
building pad 90%flatwork 90%pavement 95%
as determined by the ASTM D1557 Test Method, regardless of whether finalsubgrade elevations are attained by filling, excavation or are left at existinggrades. The moisture content of the subgrade soils shall be maintained untilcovered by slabs or pavements.
3.5 TESTING AND OBSERVATIONA. Grading operations shall be observed by the Geotechnical Engineer, serving as
the representative of the Owner.B. Field density tests shall be made by the Geotechnical Engineer after compaction
of each layer of fill. Additional layers of fill shall not be spread until the fielddensity tests indicate that the minimum specified density has been obtained.
C. Earthwork shall not be performed without the notification or approval of theGeotechnical Engineer. The Contractor shall notify the Geotechnical Engineer atleast two (2) working days prior to commencement of any aspect of the siteearthwork.
D. If the Contractor should fail to meet the technical or design requirementsembodied in this document and on the applicable plans, the Contractor shallmake the necessary readjustments until all work is deemed satisfactory, asdetermined by the Geotechnical Engineer and the Architect/Engineer. Nodeviation from the specifications shall be made except upon written approval ofthe Geotechnical Engineer or Architect/Engineer.
APPENDIX CGUIDE DRILLED PIER SPECIFICATIONS
PG&E TRAINING FACILITYWinters, CaliforniaWKA No. 9974.01
PART I: GENERAL1.1 SCOPE
Furnish all labor, equipment, tools and materials, and perform all operations inconnection with the installation of cast-in-place piers in accordance with thesespecifications and the applicable Drawings, and subject to the terms and conditions ofthe contract.
1.2 QUALIFICATIONSAll piers shall be installed by a Foundation Contractor qualified to install the type of pierto be constructed in accordance with the Drawings and Specifications, and underconditions existing at the site. The minimum requirements for qualification shall be five(5) years experience and evidence of satisfactory completion of pier installationscomparable in scope to the work specified hereunder and under the subsurfaceconditions anticipated at this site.
1.3 PROTECTIONa. Adequate protection measures shall be provided to protect workmen and passers-by the
site. Streets and adjacent property shall be fully protected throughout the operations.b. In accordance with generally accepted construction practices, the Contractor shall be
solely and completely responsible for working conditions at the job site, including safetyof all persons and property during performance of the work. This requirement shallapply continuously and shall not be limited to normal working hours.
c. Any construction review of the Contractor's performance conducted by the Architect,Structural Engineer or Geotechnical Engineer is not intended to include review of theadequacy of the Contractor's safety measures, in, on, or near the construction site.
d. Adjacent streets and sidewalks shall be kept free of mud, dirt, or similar nuisancesresulting from pier drilling operations.
e. Provide for surface drainage during the period of construction in a manner to avoidcreating a nuisance to adjacent areas. Keep all surface excavations free of water duringthe entire progress of the work, regardless of the cause, source or nature of the water.
f. Stored materials and construction equipment shall be kept at least ten feet (10') awayfrom the vertical axes of all open drilled pier shafts, at all times.
g. Water as required to suppress dust nuisance.
h. Work shall comply with all Municipal, State, and Federal regulations regarding safety,including the requirements of the Williams-Steiger Occupational Safety and Health Actof 1970.
1.4 GEOTECHNICAL REPORTa. A Geotechnical Engineering Report (WKA No. 9974.01; dated September 22, 2014) has
been prepared for this site by Wallace - Kuhl & Associates, Geotechnical Engineers ofWest Sacramento, California [(916) 372-1434]. A copy is available for review at theoffice of Wallace - Kuhl & Associates.
b. The information contained in this report was obtained for design purposes only. TheContractor is responsible for any conclusions he may draw from this report; should heprefer not to assume such risk, he may employ his own experts to analyze availableinformation and/or to make additional borings upon which to base his conclusions, all atno cost to the Owner.
1.5 EXISTING SITE CONDITIONSThe Contractor shall acquaint himself with all site conditions. If unshown active utilitiesare encountered during the work, the Architect shall be promptly notified for instructions.Failure to notify will make the Contractor liable for damage to these utilities arising fromContractor's operations subsequent to his discovery of such unshown utilities.
PART II: PRODUCTS2.1 MATERIALS
a. Reinforcing steel shall be as specified in Section ___. The reinforcing steel cage shallbe assembled, including centering guides, as shown on the Drawings and approved bythe Engineer or his representative in sufficient time prior to completion of drillingoperations to permit the assembled cage to be inserted in the completed drill holewithout delay.
b. Concrete shall be as specified in Section ___. The Contractor shall make provisions fora supply of concrete that is adequate to complete placement of any given pier in onecontinuous, uninterrupted operation, so as to form a monolithic concrete structuralelement.
2.2 EQUIPMENT, TOOLS AND LABORa. The Foundation Contractor shall provide a combination of power-driven rotary type rig,
and bits and/or augers of the proper size to drill pier excavations to the dimensionsshown on the plans; and, shall provide temporary casing as necessary.
b. All other materials, labor, tools and equipment necessary for the construction of anygiven pier in one continuous operation, shall be furnished by the Contractor.
PART III: EXECUTION3.1 LAYOUT AND PREPARATION
Lay out all work, establish grades, locate existing underground utilities, set markers andstakes, set up and maintain barricades and protection of utilities; all prior to beginningactual drilling operations.
3.2 TOLERANCESPier drilling equipment shall be positioned so that the center of any pier as drilled shallbe not more than three inches (3") from the required location, and no pier shall be out ofplumb more than two percent (2%) as measured over the total length of the shaft. Thedrilled shaft diameter of each pier shall be no smaller than shown on the Drawings. Thebottom elevation of the pier excavation shall not be less than the elevation shown on theDrawings.
3.3 PIER DRILLINGa. Helical or bucket auger drilling shall be used to excavate each pier.b. Each pier shall be extended to the depths shown on the approved drawings.c. Temporary casing may be installed to facilitate drilling, subject to the approval of the
Geotechnical Engineer.d. Every pier excavation shall be inspected for cleanliness and acceptability by the
Geotechnical Engineer or his representative. Reinforcing steel and concrete shall notbe placed in any pier excavation until the Geotechnical Engineer or his representativehas given express approval of its suitability.
e. No pier excavations shall be permitted to stand open for more than two (2) hours aftercompletion.
3.4 REINFORCING STEEL PLACEMENTUpon completion of drilling, the reinforcing steel cage shall be positioned in the piershaft as shown on the Drawings and shall be suspended above the bottom ofexcavation before any concrete is placed in the shaft. In the event that difficulties areencountered in positioning the reinforcing steel cage, or if it cannot be freely rotated(after suspension) indicating caving of the excavation sides, the cage shall be removedand the hole shall be reamed sufficiently to permit the final positioning of the cagewithout difficulty. The top of the cage shall be braced or supported to assure that itremains concentrically aligned in the shaft excavation during placement of concrete.
3.5 GROUNDWATER PUMPING a. Pumping of groundwater immediately prior to concrete placement will be acceptable
only if a coordinated procedure of drilling, steel placement, pumping and concreteplacement can be achieved whereby appreciable caving of the lower soils does not
occur. Determination of an acceptable procedure will be solely the responsibility of theGeotechnical Engineer.
b. If pumping cannot be used to remove the groundwater, as determined by theGeotechnical Engineer, then tremie concrete placement methods shall be used.
3.6 CONCRETE PLACEMENTConcrete shall be deposited by the use of an elephant trunk or other approved devicewhen the free fall is in excess of six feet (6') and only if there is less than six inches (6")of water in the excavation. If more than six inches (6") of water exists in the pierexcavation immediately prior to concrete placement, either (1) dewatering shall beaccomplished subject to the limitations of Section 3.5 above, or (2) concrete shall beplaced by means of tremie concrete placement methods, using a tremie pipe andassociated equipment and materials approved by the Geotechnical Engineer and theStructural Engineer. Additional costs for materials, equipment and labor to use tremieconcrete placement methods shall be borne by the Contractor. Concrete shall bevibrated during placement operations so as to provide a dense, monolithic concretesection throughout the full length and diameter of the pier. During and after the vibratingoperation, the top of the freshly placed concrete shall be observed to see that it remainsconstant and that there is no appreciable drop in elevation that would signify loss ofconcrete through hidden voids.
3.7 TESTINGIf the Geotechnical Engineer has reason to suspect that any pier may containextraneous material or otherwise fail to meet specifications, he may order testing of thepier by coring or other methods. The Contractor shall bear the expense of theinvestigation and/or testing and shall also, at no cost to the Owner, install properadditional construction as required by the Engineer.
3.8 CLEANUPThe Contractor at all times shall keep the area adjacent to pier drilling operations free ofaccumulations of excavated material and/or rubbish and trash caused by his employeesor work. At the completion of work, he shall remove all excavated materials, trash, andrubbish from and about the area of the premises and all his tools, scaffolding, andsurplus materials, and shall leave the site with a clean finished appearance.
3.9 CHANGE OR SUBSTITUTIONSNo changes in any material, equipment or method of installation, or deviation fromDrawings or Specifications, will be permitted without written approval of the Engineer orhis representative.