Page 1: Geothermal Alliance of Illinois

Geothermal Alliance of Illinois

2012 IECC “Duct Pressure Testing”

Page 2: Geothermal Alliance of Illinois

Brian KumerThermal Imaging Services, Inc.

Peoria, IL 309-547-5000 office309-251-1719 cell

[email protected]

or www.briankumer.com

THERMAL IMAGING SERVICESof Central Illinois, Inc.

“Improving Home Performance”

Page 3: Geothermal Alliance of Illinois

3

Building Science Hot LineIllinois Home Performance Building Science

HOT LINE 866-395-1032 ext. 3

Free to homeowners, renters, contractors, anyone looking for unbiased advice on specific home

performance issues and improvements!

To learn more go to: www.illinoishomeperformance.org/hotline

Page 4: Geothermal Alliance of Illinois

Equipment Loan Program

Page 5: Geothermal Alliance of Illinois

Balanced Duct System - No Leaks

Unconditioned Crawlspace

Page 6: Geothermal Alliance of Illinois

Supply Leaks in Unconditioned Space

Unconditioned Crawlspace

Page 7: Geothermal Alliance of Illinois

Return Leaks in Unconditioned Space

Unconditioned Crawlspace

Page 8: Geothermal Alliance of Illinois

Cold Bedrooms

Page 9: Geothermal Alliance of Illinois

Tray Ceiling is a Huge Return Duct

Page 10: Geothermal Alliance of Illinois

Duct Leakage to OutsideSecond Floor Living Space

Front Porch

Porch AtticNegative Pressure

To Furnace

Page 11: Geothermal Alliance of Illinois

Two Important Tips…

1. Air seal your ducts yourself. DO NOT rely on the foam insulator to air seal your ducts with their spray foam

2. Try to pressure test your ducts in the rough-in stage of construction

Page 12: Geothermal Alliance of Illinois

Duct Blaster™ - Energy Conservatory

Page 13: Geothermal Alliance of Illinois

Flow Rings Like the Blower Door

Page 14: Geothermal Alliance of Illinois

In-Field Calibration

The flow should be between 103 cfm to 109 cfm with the calibration plate installed @ 25.0 Pascals

Page 15: Geothermal Alliance of Illinois

NEW

Page 16: Geothermal Alliance of Illinois

Ring 4 - 2.4 cfm to 25.0 cfm

Page 17: Geothermal Alliance of Illinois

Duct Blaster™ - Energy Conservatory

Page 18: Geothermal Alliance of Illinois

“Total” Duct Leakage Test

Source: The Energy Conservatory Duct Blaster Operators Manual - page 18

Ducts pressurized to +25 Pascals

Page 19: Geothermal Alliance of Illinois

2012 IECC “Total” Duct Leakage

Total duct leakage is based on 3 cfm / 100 sq’ of conditioned space with no air handler, or 4 cfm / 100 sq’ with air handler installed.

• Rough-in no air handler …………………….… 3 cfm

• Rough-in with air handler …………………… 4 cfm

• Post construction with air handler ………. 4 cfmExample:

(2,400 sq’ ÷ 100) x 3 cfm = 72 cfm of total duct leakage

(2,400 sq’ ÷ 100) x 4 cfm = 96 cfm of total duct leakage

Page 20: Geothermal Alliance of Illinois

System 2Second Floor

System 1Main Floor & Basement

4 cfm / 100 sq’ of living space

Page 21: Geothermal Alliance of Illinois

Basement /Floor Cavity

Living Space

Supply Duct

Source of Duct Leakage

Page 22: Geothermal Alliance of Illinois

Attic Space

Living Space

Supply Duct

Source of Duct Leakage

Page 23: Geothermal Alliance of Illinois

Duct Pressure Testing

Page 24: Geothermal Alliance of Illinois

House Set-up…

• Open a window to prevent pressurizing the home during the test

• Turn off air handler(s)

• Cover all supply & return registers with tape or mask. Seal between the floor or wall and the register

• Remove air filter

• DO NOT tape air filter slot (it’s part of the system)

Page 25: Geothermal Alliance of Illinois

Connect to the Duct System

Connected to return grille Connected to blower compartment

Page 26: Geothermal Alliance of Illinois

Direct Mount to Blower Compartment

Connected to blower compartment Need to add clearance for blower

Page 27: Geothermal Alliance of Illinois

Air Filter Slot Cover Leakage

Page 28: Geothermal Alliance of Illinois

Pressure Drop Across the CoilReturn Ducts

Negative PressureSupply Ducts

Positive Pressure

Return Ducts.1 iwc

Air Filter.1 iwc

A-coil.2 iwc

Supply Ducts.1 iwc

(fan)

Page 29: Geothermal Alliance of Illinois

Pressure Drop Across the Coil55.0 Pascal's 25.0 Pascal’s

(fan)

Return Ducts Supply Ducts

Duct Blaster

Page 30: Geothermal Alliance of Illinois

Duct Testing Adaptors

Page 31: Geothermal Alliance of Illinois

Duct Testing Adaptors

Seal much better and are much faster!

Page 32: Geothermal Alliance of Illinois

Portable Power for Testing

Page 33: Geothermal Alliance of Illinois

Pressure Pan

Page 34: Geothermal Alliance of Illinois

Using a Theatrical Fogger With Fan

Page 35: Geothermal Alliance of Illinois

TrueFlow Air Handler Flow Meter

Page 36: Geothermal Alliance of Illinois