www.nexansamercable.com • e-mail: [email protected]
37-105
TYPE MMV MEDIUM POWER CABLESingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
APPLICATIONSNexans AmerCable’s Type MMVmarine medium voltage cables are foruse aboard commercial ships, mobileoffshore drilling units (MODUs), andfixed or floating offshore facilities.
FEATURESn These cables utilize flexiblestranded conductors, braided shields and a braided armor (whenarmored) which make them verysuitable for applications involvingrepeated flexing and high vibration.
n These cables have a small minimum bending radius (6xOD for unarmored cables and 8xOD for armored cables) for easyinstallation.
n Optional uninsulated groundingconductors sized per UL 1072.
n The increased flexibility of this cable allows for termination of one end and coiling on multiple module offshore platforms. Then coiling andterminating other end when modulesare mated at sea thereby reducinginstallation time.
n Passes IEC 332-3 Category A and IEEE 1202 flame tests.
Conductor ShieldA combination of semi-conducting tape and extrudedthermosetting semi-conducting material meeting UL 1309, IEEE 1580 and UL1072.
Armor (optional)(Optional) 0.0126" bronze braid providing 88%minimum coverage meeting UL 1309 and IEEEStd. 45-1998.
JacketA black, arctic grade, flame retardant, oil, abrasion,chemical and sunlight resistant thermosettingcompound meeting UL 1309, IEEE 1580 and UL 1072. Colored jackets for signifying differentvoltage levels are also available on special request (ie.yellow = 5kV, orange = 8kV and red = 15kV).
Sheath (optional)A black, arctic grade, flame retardant, oil, abrasion,chemical, and sunlight resistant thermosettingcompound meeting UL 1309, IEEE 1580 and UL 1072. Colored jackets for signifying differentvoltage levels is also available on special request (ie.yellow = 5kV, orange = 8kV and red = 15kV).
Metallic ShieldComposite shield consisting of 0.0126" tinned copper braided with nylon providing 60% copper Shieldedcoverage meeting UL 1309, IEEE Std. 1580 and UL 1072. The nylon is colored for easy phase identification (three conductor = black, blue, red) without the need toremove the shield to findan underlying colored tape.
Insulation ShieldSemi-conducting tape, with overlap, for fast and easytermination meeting UL 1309, IEEE 1580 and UL 1072.
ConductorsSoft annealed flexiblestranded tinned copperper IEEE 1580 Table 11.
InsulationExtruded thermosetting 90°C Ethylene PropyleneRubber (EPR), meeting UL 1309 (Type E), IEEE 1580 (Type E) and UL 1072.
Grounding Conductor (optional)One uninsulated soft annealed flexible strandedtinned copper conductor per ASTM B 33 and sizedaccording to Table 21.1 of UL 1072.
Ratings & Approvals� UL Listed as Marine Shipboard Cable (E111461)� American Bureau of Shipping (ABS)� Det Norske Veritas (DNV) Pending� Lloyd’s Register of Shipping (LRS) Pending� 90˚C Temperature Rating� Voltage Rating – 5kV to 15kV(25kV available on request)
Hawke Gland Types Unarmored Armored & Sheathed
Industrial & Safe Area (IP68) 121 153-X Increased Safety
501/421 501/453/U “EExe” Explosion Proof 710 753 Class I, Div. 2 Class I, Div. 1 Class I, Zone 2 Class I, Zone 1 & 2 Flameproof 501/421 501/453/U “EExd” Zone 1 & 2 (2 liter or < enclosures) ICG 653/U (2 liter or > enclosures) Zone 1 & 2
Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Inductive Voltage Inductive Voltage Single DC AC Size Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hz kcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
86421
1/02/03/04/0262313373444535646777
7.612.5213443547086
109132159189227273326394
-101-102-103-104-105-106-107-108-109-110-111-112-113-114-115-116
0.5870.6410.7230.7900.8240.9150.9911.0201.0871.1671.2101.3101.3691.4361.5351.632
205260349456522645797884
10531266129316831935222325983066
1.2820.8220.5660.3610.2960.2450.2020.2780.1410.1220.1080.0950.0860.0770.0700.065
0.0540.0500.0440.0410.0400.0390.0380.0370.0350.0340.0330.0320.0320.0310.0300.030
0.8030.9000.9811.0491.0821.1601.2401.2801.3321.3911.4691.5551.6141.7531.8521.935
398502620745826970
1171125414141645172521382407282632363728
0.0610.0580.0510.0470.0470.0450.0430.0420.0400.0380.0370.0360.0350.0350.0340.033
1.2880.8300.5730.3670.3030.2500.2070.1730.1460.1270.1120.0990.0900.0820.0750.069
80107141186214247285328381435486544606682767865
6992
121159184212244281325371413460510570635709
6891
120158182210242279324370413462515580652735
0.6940.4360.2860.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.015
0.8850.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
Unarmored
SINGLE CONDUCTOR TYPE MMV MARINE MEDIUM VOLTAGE – 5KV, 100/133% INSULATION LEVELArmored &
Sheathed (BS) Ampacity
Inductive Voltage Inductive Voltage Single DC AC Size Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hz kcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
6421
1/02/03/04/0262313373444535646777
12.5213443547086
109132159189227273326394
-118-119-120-121-122-123-124-125-126-127-128-129-130-131-132
0.6870.7710.8740.9190.9751.0201.0691.1701.2131.2831.3381.4111.4921.5831.748
287392517594693809928
11281282149517051977229826913246
0.8240.5670.3620.2980.2460.2030.1690.1420.1230.1090.0960.0870.0780.0710.066
0.0520.0460.0430.0420.0410.0390.0380.0360.0350.0340.0330.0330.0320.0310.030
0.9461.0301.1191.1641.2331.2781.3281.4291.4711.5281.5961.6561.8091.8872.065
545667829919
10471178131415591714193821852465292633343970
0.0590.0520.0480.0470.0460.0440.0430.0410.0390.0380.0370.0360.0360.0350.034
0.8310.5740.3680.3040.2510.2080.1740.1470.1280.1130.1000.0910.0820.0750.070
107141186214247285328381435486544606682767865
92121159184212244281325371413460510570635709
91120158182210242279324370413462515580652735
0.4360.2860.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.015
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
Unarmored
SINGLE CONDUCTOR TYPE MMV MARINE MEDIUM VOLTAGE – 8KV, 100% INSULATION LEVELArmored &
Sheathed (BS) Ampacity
www.nexansamercable.com • e-mail: [email protected]
Inductive Voltage Inductive Voltage Single DC AC Size Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hz kcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
6421
1/02/03/04/0262313373444535646777
12.5213443547086
109132159189227273326394
-134-135-136-137-138-139-140-141-142-143-144-145-146-147-148
0.7390.8230.9320.9711.0171.0731.1461.1911.2651.3351.3921.4611.5891.6451.790
321419570636725856992
11571334155417682040241826763298
0.8260.5690.3650.3000.2470.2040.1710.1430.1240.1100.0970.0880.0780.0720.067
0.0540.0470.0450.0440.0420.0400.0390.0380.0360.0350.0340.0330.0320.0320.032
0.9971.0811.1911.2291.2621.3321.4041.4451.5181.5801.6511.7781.8921.9622.107
595722910989
10621243140615801525206522662906306333644035
0.0600.0530.0500.0490.0470.0450.0440.0420.0400.0390.0380.0380.0360.0360.036
0.8320.5750.3700.3050.2520.2090.1750.1480.1290.1140.1010.0930.0830.0760.071
107141186214247285328381435486544606682767865
92121159184212244281325371413460510570635709
91120158182210242279324370413462515580652735
0.4360.2860.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.015
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
Unarmored
SINGLE CONDUCTOR TYPE MMV MARINE MEDIUM VOLTAGE – 8KV, 133% INSULATION LEVELArmored &
Sheathed (BS) Ampacity
Inductive Voltage Inductive Voltage Single DC AC Size Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hz kcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
21
1/02/03/04/0262313373444535646777
3443547086
109132159189227273326394
-150-151-152-153-154-155-156-157-158-159-160-161-162
1.0041.0461.0931.1431.1921.2591.3531.4001.4531.5331.6471.7401.880
627705815925
105012331443162818642153250828253475
0.3690.3030.2510.2080.1740.1460.1280.1130.1000.0910.0820.0750.070
0.0490.0470.0450.0440.0420.0400.0390.0380.0370.0360.0360.0350.034
1.2621.3041.3511.4021.4511.5171.5981.6581.7711.8371.9642.0432.197
990108212101334147816851909212424712774318935254243
0.0530.0510.0490.0470.0460.0440.0420.0420.0410.0400.0390.0380.037
0.3730.3080.2550.2120.1780.1500.1310.1170.1040.0950.0860.0790.073
186214247284327378431481536598672754848
164189217250288332377418464514574638709
158182210241278321366409456508571641721
0.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.015
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
Unarmored
SINGLE CONDUCTOR TYPE MMV MARINE MEDIUM VOLTAGE – 15KV, 100% INSULATION LEVELArmored &
Sheathed (BS) Ampacity
Ordering Type MMV Medium VoltageCablesExample: • 3 conductor power cable • 8kV 100% • #2 AWG • ground • bronze armored & sheathed
Nexans AmerCableType MMV Prefix
Specific CableNumber
(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
Ground ConductorG – with groundBlank – no ground
37–105 – 319 BS G
37-105
TYPE MMV MEDIUM VOLTAGE CABLESingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Inductive Voltage Inductive Voltage Single DC AC Size Part Nominal Weight Reactance Drop Nominal Weight Reactance Drop In Free Triangular Banked Resistance ResistanceAWG/ No. Diameter (Lbs./ (ohms/ (Volts/amp/ Diameter (Lbs./ (ohms/ (Volts/amp/ Air Configuration in Tray at 25°C at 90°C, 60 Hz kcmil mm2 37-105 (inches) 1000 ft.) 1000 ft.) 1000 ft.) (inches) 1000 ft.) 1000 ft.) 1000 ft.) (amps) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.)
21
1/02/03/04/0262313373444535646777
3443547086
109132159189227273326394
-164-165-166-167-168-169-170-171-172-173-174-175-176
1.0891.1251.1781.2301.2911.3571.4341.4901.5431.6151.7551.8471.969
701779886
1022116213401535174319602250267530683608
0.3700.3050.2520.2090.1760.1480.1290.1140.1010.0930.0840.0770.071
0.0500.0490.0470.0450.0440.0420.0400.0390.0380.0380.0370.0360.035
1.3471.3841.4371.4881.5361.6161.7511.8071.8601.9322.0722.1642.286
1095118513121463161418182132236125992916339838164410
0.0550.0530.0510.0490.0470.0460.0440.0430.0420.0410.0400.0390.038
0.3750.3090.2560.2130.1790.1510.1330.1180.1050.0960.0870.0800.074
186214247284327378431481536598672754848
164189217250288332377418464514574638709
158182210241278321366409456508571641721
0.1750.1400.1110.0890.0700.0560.0460.0380.0320.0270.0220.0190.015
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
Unarmored
SINGLE CONDUCTOR TYPE MMV MARINE MEDIUM VOLTAGE – 15KV, 133% INSULATION LEVELArmored &
Sheathed (BS) Ampacity
Single Inductive Size Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding kcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
86421
1/02/03/04/0262313373444535646777
7.612.5213443547086
109132159189227273326394
-301-302-303-304-305-306-307-308-309-310-311-312-313-314-315-316
1.1761.2941.4691.6151.7461.8451.9962.0812.2222.4102.4882.6592.8923.0363.2493.458
722918
1252162019422257274431103714448645995825694679619274
10902
13561371184722992646299435403966461456145760706182979317
1078912471
1.4341.5391.7731.9352.0452.1492.3002.3982.5392.7892.8673.0383.2704.4153.6273.823
6688
116152175201232266306348386429455528584647
567599
129149171197226260296328365387449496550
0.7080.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.0240.0200.016
0.8850.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
0.0480.0440.0390.0360.0350.0340.0330.0320.0310.0300.0290.0290.0280.0280.0270.027
1.2750.8150.5600.3560.2910.2390.1960.1630.1360.1180.1040.0920.0830.0740.0670.062
866644433322111
1/0
Unarmored
THREE CONDUCTOR TYPE MMV MARINE MEDIUM VOLTAGE – 5KV, 100/133% INSULATION LEVELArmored &
Sheathed (BS) Ampacity
www.nexansamercable.com • e-mail: [email protected]
Single Inductive Size Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding kcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
6421
1/02/03/04/0262313373444535646
12.5213443547086
109132159189227273326
-332-333-334-335-336-337-338-339-340-341-342-343-344-345
1.5041.7431.8891.9722.0712.1922.3032.4472.6202.8192.9423.0903.3653.486
11661629207523012636308835244169485457366502743688699753
179623472854311034643982444252956055701278048863
1041811361
1.8212.0602.2062.2892.3752.5092.6062.8122.9873.1983.2863.4693.7443.864
88116152175201232266306348386429455528584
7599
129149171197226260296328365387449496
0.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.0240.020
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.028
0.0480.0430.0400.0380.0370.0360.0350.0330.0320.0320.0310.0300.0300.029
0.8200.5640.3590.2940.2420.1990.1660.1390.1210.1060.0940.0850.0760.069
66644433322111
Unarmored
THREE CONDUCTOR TYPE MMV MARINE MEDIUM VOLTAGE – 8KV, 133% INSULATION LEVELArmored &
Sheathed (BS) Ampacity
Single Inductive Size Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding kcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
6421
1/02/03/04/0262313373444535646777
12.5213443547086
109132159189227273326394
-317-318-319-320-321-322-323-324-325-326-327-328-329-330-331
1.3831.5741.7631.8611.9602.0772.1842.3372.4932.6452.8242.9813.1563.3543.583
10361378184021192442288033013943456853186195715082789660
11307
1534203525632883324237294192488957316525751085279715
1120612971
1.6511.8912.0802.1782.2772.3942.5012.6542.8723.0103.2033.3603.5213.7323.962
88116152175201232266306348386429455528584647
7599
129149171197226260296328365387449496550
0.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.0240.0200.016
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.0330.0280.025
0.0460.0410.0380.0370.0360.0340.0330.0320.0310.0300.0300.0290.0290.0280.028
0.8180.5620.3570.2930.2410.1980.1650.1380.1190.1050.0930.0840.0750.0680.063
66644433322111
1/0
Unarmored
THREE CONDUCTOR TYPE MMV MARINE MEDIUM VOLTAGE – 8KV, 100% INSULATION LEVELArmored &
Sheathed (BS) Ampacity
37-105
TYPE MMV MEDIUM VOLTAGE CABLESingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
Ordering Type MMV Medium VoltageCablesExample: • 3 conductor power cable • 8kV 100% • #2 AWG • ground • bronze armored & sheathed
Nexans AmerCableType MMV Prefix
Specific CableNumber
(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
Ground ConductorG – with groundBlank – no ground
37–105 – 319 BS G
Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
Single Inductive Size Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding kcmil mm2 37-105 (inches) 1000 ft.) (inches 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
21
1/02/03/04/0262313373444535
3443547086
109132159189227273
-346-347-348-349-350-351-352-353-354-355-356
2.0432.1332.2352.3432.4492.5922.8312.9583.0743.2453.491
23142599299233923838449054496078689279289248
3147346939044339498857086765744883149442
10858
2.3602.4502.5522.6602.8282.9713.2103.3373.4533.6243.869
156178205234269309352389432456528
133151174199229263299331367388449
0.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.024
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033
0.0420.0400.0390.0370.0360.0350.0340.0330.0320.0310.031
0.3610.2960.2440.2010.1680.1410.1220.1070.0950.0860.077
64443332211
Unarmored
THREE CONDUCTOR TYPE MMV MARINE MEDIUM VOLTAGE – 15KV, 100% INSULATION LEVELArmored &
Sheathed (BS) Ampacity
Single Inductive Size Nominal Weight Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Voltage Drop OptionalAWG/ Part No. Diameter (Lbs./ Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (ohms/ (Volts per amp Grounding kcmil mm2 37-105 (inches) 1000 ft.) (inches) 1000 ft.) (amps) (amps) (ohms/1000 ft.) (ohms/1000 ft.) 1000 ft.) per 1000 ft.) Conductor
21
1/02/03/04/0262313373444535
3443547086
109132159189227273
-357-358-359-360-361-362-363-364-365-366-367
2.2262.3042.4192.5292.6632.8673.0333.1533.2673.4233.598
26552927332438094329513158636602736784009594
3556386644544995556664587273806788889991
11262
2.5432.6212.7982.9083.0413.2453.4113.5323.6463.8013.976
156178205234269309352389432456528
133151174199229263299331367388449
0.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.024
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033
0.0440.0430.0410.0390.0380.0370.0350.0340.0340.0330.033
0.3640.2990.2460.2030.1700.1420.1240.1090.0970.0880.079
64443332211
Unarmored
THREE CONDUCTOR TYPE MMV MARINE MEDIUM VOLTAGE – 15KV, 133% INSULATION LEVELArmored &
Sheathed (BS) Ampacity
Ordering Type MMV Medium VoltageCablesExample: • 3 conductor power cable • 8kV 100% • #2 AWG • ground • bronze armored & sheathed
Nexans AmerCableType MMV Prefix
Specific CableNumber
(from charts)
Armor RequirementBS – armored &
sheathedBlank – no armor
Ground ConductorG – with groundBlank – no ground
37–105 – 319 BS G
www.nexansamercable.com • e-mail: [email protected]
37-105VFD
TYPE MMV-VFDPOWER CABLEThree Conductor: 8kV –15kV • 133% Insulation Level • Rated 90°C
APPLICATIONSA flexible, braid and foil shielded,power cable specifically engineered for use in medium voltage variable frequency AC drive (VFD) applications.
FEATURESn Flexible stranded conductors and
braided shields. Suitable for applications involving repeated flexing and high vibration.
n Small minimum bending radius (8x OD) for easy installation.
n Insulation has a very low dielectricconstant. This allows for longeroutput cable distances andminimizes common mode current.
n Overall braid plus foil shield is engineered with 100% coverage anda surface transfer impedance <50milliohms at 10MHz to contain EMI.
n Symmetrical insulated ground conductors reduce induced voltageimbalances and carry common mode noise back to the drive.
n High strand count conductors andbraid shield design is much more flexible, easier to install and moreresistant to vibration than Type MC cable.
n Severe cold durability: exceeds CSA cold bend/cold impact (-40˚C/-35˚C).
n Flame retardant: IEC 332-3 Category A and IEEE 1202.
n Suitable for use in Class I, Division 1, and Zone 1 environments.
Conductors (3)Soft annealed flexible strandedtinned copper per IEEE 1580 Table 11.
Conductor ShieldA combination of semi-conducting tape and extrudedthermosetting semi-conducting material meeting UL1309, IEEE 1580 and UL1072.
Armor/EMI ShieldOverall tinned copper braid plus aluminum/polyester tape provides 100% coverage. This braid serves as both an armor and EMI shield meeting both IEEE 1580 and UL 1307/CSA 245.
JacketA black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 245, IEEE 1580, and UL 1072. This jacket allows for isolation between the insulation shields and overall shield. Shields can then be terminated on opposite ends tominimize circulating currents.
Sheath (optional)A black, arctic grade, flame retardant, oil,abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 245, IEEE 1580, and UL 1072.Colored jackets for signifying different voltage levels are also available on specialrequest (orange = 8kV and red = 15kV).
Insulation ShieldComposite shieldconsisting of 0.0126"tinned copper braidedwith nylon providing60% copper Shieldedcoverage meeting UL 1309, IEEE Std.1580, and UL 1072.The nylon is coloredfor easy phase identification (three conductor = black,blue, red) without the need to removethe shield to find an underlying colored tape.
Insulation ShieldSemi-conducting layer meeting UL 1309, IEEE 1580 and UL 1072.
InsulationExtruded thermosetting90°C Ethylene PropyleneRubber (EPR), meetingUL 1309 (Type E), IEEE 1580 (Type E)and UL 1072.
Symmetrical InsulatedGrounding Conductors (3)Soft annealed flexible stranded tinned copper conductor per IEEE 1580 Table 11. GexolInsulation sized per Table 23.2 of UL1072.Color: Green
Ratings & Approvalsn UL Listed as Marine Shipboard Cable (E111461)n American Bureau of Shipping (ABS)n Det Norske Veritas (DNV) Pendingn Lloyd’s Register of Shipping (LRS) Pendingn 90˚C Temperature Ratingn Voltage Rating – 8kV to 15kV
(25kV available on request)
Low smokehalogen-free
jacket available
on request.
Manufactured by Nexans AmerCable • 800-506-9473 • 713-896-5800 • Fax: 713-849-9009
THREE CONDUCTOR TYPE MMV-VFD MARINE MEDIUM VOLTAGE8KV • 133% INSULATION LEVEL
Ampacity
Ampacity
THREE CONDUCTOR TYPE MMV-VFD MARINE MEDIUM VOLTAGE15KV • 133% INSULATION LEVEL
Ordering Type MMV-VFD Medium Voltage CablesExample: • 3 conductor MMV-VFD power cable • 15kV • #2 AWG
Nexans AmerCableType MMV-VFD
PrefixSpecific Cable
Number (from charts)
37–105 – 357TSVFD
Single Inductive Voltage Green Insulated Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Drop GroundingAWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (Ohms/ (Volts/Amp/ Conductor (3x) kcmil mm2 37-105 (Inches) 1000 Ft.) (Amps) (Amps) (Ohms/1000 Ft.)(Ohms/1000 Ft.) 1000 Ft.) 1000 Ft.) Size (AWG)
6421
1/02/03/04/0262313373444535
12.5213443547086
109132159189227273
-332TSVFD-333TSVFD-334TSVFD-335TSVFD-336TSVFD-337TSVFD-338TSVFD-339TSVFD-340TSVFD-341TSVFD-342TSVFD-343TSVFD-344TSVFD
181423912879338735514053460953936218712681219035
10585
1.8152.0282.1742.2902.3562.4772.5882.8152.9683.1663.2893.4373.735
88116152175201232266306348386429455528
7599
129149171197226260296328365387449
0.4450.3000.1840.1470.1170.0930.0740.0580.0480.0400.0340.0280.024
0.5560.3760.2300.1840.1470.1170.0940.0750.0630.0530.0450.0390.033
0.0480.0430.0400.0380.0370.0360.0350.0330.0320.0320.0310.0300.030
0.8200.5640.3590.2940.2420.1990.1660.1390.1210.1060.0940.0850.076
1010108886666444
Single Inductive Voltage Green Insulated Size Nominal Weight In Free Banked DC Resistance AC Resistance Reactance Drop GroundingAWG/ Part No. Diameter (Lbs./ Air in Trays at 25°C at 90°C, 60Hz (Ohms/ (Volts/Amp/ Conductor (3x) kcmil mm2 37-105 (Inches) 1000 Ft.) (Amps) (Amps) (Ohms/1000 Ft.)(Ohms/1000 Ft.) 1000 Ft.) 1000 Ft.) Size (AWG)
21
1/02/03/04/0262313373444
3443547086
109132159189227
-357TSVFD-358TSVFD-359TSVFD-360TSVFD-361TSVFD-362TSVFD-363TSVFD-364TSVFD-365TSVFD-366TSVFD
359139354368505957046592740481969135
10236
2.5112.5892.7042.8763.0093.2133.3793.5003.6143.769
156178205234269309352389432456
133151174199229263299331367388
0.1840.1470.1170.0930.0740.0580.0480.0400.0340.028
0.2300.1840.1470.1170.0940.0750.0630.0530.0450.039
0.0440.0430.0410.0390.0380.0370.0350.0340.0340.033
0.3640.2990.2460.2030.1700.1420.1240.1090.0970.080
10888666644
www.nexansamercable.com • e-mail: [email protected]_16
Ampacities are based on API RP 14F (June 1999)Table 4 or 5 for single conductor cables and Table 3for multi-conductor cables. The notes to these tablesare also applicable. Ampacities are also based on a90°C conductor temperature and a 45°C ambienttemperature.
Inductive reactance and voltage drop values are based on a 90°C conductor temperature and 60 Hz operation. Values for single conductor cables are based on a symmetrical triangular configuration.
Please consult Nexans AmerCable on values for other configurations.
MMV AMPACITIES & ELECTRICAL DATA
Individual Closest Equivalent Uninsulated Size Number Strand Dia. IEEE 45 Metric Size ConductorAWG/kcmil of Strands (inches) Std. Size (mm2) Dia. (inches)
86421
1/02/03/04/0262313373444535646777
1111
3761
133133209266342418532646777925
11101332159119242745
0.0201 0.0201 0.0177 0.0223 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201 0.0201
1626416683
106133168212262313373444535646777
1111
7.57 12.49 21.11 33.51 42.79 54.45 70.01 85.57
108.91 132.25 159.06 189.36 227.23 272.68 325.70 393.87 561.94
0.136 0.175 0.258 0.324 0.361 0.407 0.461 0.510 0.575 0.654 0.720 0.785 0.860 0.941 1.029 1.132 1.354
MMV Bend Radius Unarmored Armored Armored & Sheathed
IEEE 45 6X Diameter 8X Diameter 8X Diameter
IEC 92 <1" (25mm) 6X Diameter 8X Diameter 4 x Diameter >1" (25mm) 6X Diameter
Transport <1" (25mm) 6X Diameter 6X Diameter Canada 4X Diameter >1" (25mm) 6X Diameter
37-105
TYPE MMV MEDIUM VOLTAGE CABLESingle Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°CMulti-Conductor: 5kV – 15kV, 100% & 133% Insulation Levels. Rated 90°C
MMV Stranding Profile