handbuch
DESCRIPTION
handbuchTRANSCRIPT
Index
1
Index
PREAMBLE ___________________________________________________________________________________________________________3
1 BODY TEMPERATURE, COMFORT, HOURS AT FULL UTILISATION _____________________________________4 1.1 Comfort ___________________________________________________________________________________________________________________ 4 1.2 Hours at full utilisation for providing cooling ____________________________________________________________________ 5 2 BASES_______________________________________________________________________________________________________7 2.1 Air-conditioning, cooling and tempering _________________________________________________________________________ 7 2.2 Passive and active cooling____________________________________________________________________________________________ 7 2.2.1 Passive cooling__________________________________________________________________________________________________________ 8 2.2.2 Active cooling ___________________________________________________________________________________________________________ 8 2.3 Heat cooling sources__________________________________________________________________________________________________10 2.3.1 Ground probes _________________________________________________________________________________________________________10 2.3.2 Ground collectors______________________________________________________________________________________________________11 2.3.3 Groundwater ___________________________________________________________________________________________________________12 2.3.4 Air ________________________________________________________________________________________________________________________12 2.4 Distribution systems __________________________________________________________________________________________________12 2.4.1 Area heating (underfloor) ___________________________________________________________________________________________13 2.4.2 Area heating (ceiling) ________________________________________________________________________________________________13 2.4.3 Fan convectors and ceiling cassettes ______________________________________________________________________________14 3 H-X DIAGRAM AND DEW POINT TEMPERATURE ______________________________________________________14
4 COOLING WITH BRINE|WATER HEAT PUMPS __________________________________________________________17 4.1 Sizing ____________________________________________________________________________________________________________________17 4.2 Operating modes WPF________________________________________________________________________________________________17 4.2.1 Heating mode WPF____________________________________________________________________________________________________17 4.2.2 Passive cooling operation with WPF_______________________________________________________________________________18 4.3 Operating modes WPC cool__________________________________________________________________________________________18 4.3.1 Heating mode WPC cool______________________________________________________________________________________________18 4.3.2 Passive cooling operation with WPC cool ________________________________________________________________________18 4.4 Active cooling operation WPF and WPC___________________________________________________________________________18 4.4.1 Minimum flow rate for active cooling _____________________________________________________________________________19 4.5 Valve positions _________________________________________________________________________________________________________19 4.5.1 Passive cooling_________________________________________________________________________________________________________19 4.5.2 Active cooling __________________________________________________________________________________________________________19 4.5.3 Cooling and DHW demand___________________________________________________________________________________________20 4.6 Hydraulics WPF ________________________________________________________________________________________________________21 4.7 Hydraulics WPF with WPAC 1 _______________________________________________________________________________________22 4.8 Hydraulics WPC cool __________________________________________________________________________________________________23 4.9 Hydraulics WPF with WPAC 2 _______________________________________________________________________________________24 5 COOLNG WITH WATER|WATER HEAT PUMPS __________________________________________________________25 5.1 Sizing ____________________________________________________________________________________________________________________25 5.2 Operating modes ______________________________________________________________________________________________________25 5.2.1 Heating operation _____________________________________________________________________________________________________25 5.2.2 Passive cooling operation ___________________________________________________________________________________________26 5.2.3 Active cooling operation _____________________________________________________________________________________________26 6 COOLING WITH AIR|WATER HEAT PUMPS______________________________________________________________27
7 SETTING PARAMETERS OF AND CONTROL WITH THE WPMI _________________________________________28 7.1 Standard settings______________________________________________________________________________________________________29 7.2 Set room temperature ________________________________________________________________________________________________29 7.3 Flow temperature _____________________________________________________________________________________________________29 7.4 Flow temperature hysteresis________________________________________________________________________________________29 7.5 Dynamic (active cooling only)_______________________________________________________________________________________30 7.6 Control characteristics of the passive cooling ___________________________________________________________________30
Index
2
7.6.1 Source pump ___________________________________________________________________________________________________________30 7.7 Control characteristics of the active cooling _____________________________________________________________________31 7.7.1 Compressor _____________________________________________________________________________________________________________32 8 BRINE RESISTANCE_______________________________________________________________________________________33
9 WIRING CHANGEOVER COOLING MODE ________________________________________________________________34 9.1 Wiring diagram ________________________________________________________________________________________________________34 9.2 Distribution strip/zone valve ________________________________________________________________________________________37 10 COMPARISON COOLING WITH DIFFERENT HEAT PUMPS _____________________________________________40
11 ALTERNATIVE SYSTEMS AND COST CONSIDERATIONS _______________________________________________41 11.1 VRF systems, air-conditioning systems with direct evaporation_____________________________________________41 11.2 Free cooling ____________________________________________________________________________________________________________41 11.3 Air duct __________________________________________________________________________________________________________________41 11.4 Water wall ______________________________________________________________________________________________________________41 11.5 Cost consideration_____________________________________________________________________________________________________42 11.5.1 Recommendations ____________________________________________________________________________________________________43 12 COOLING LOAD CALCULATION FORM ___________________________________________________________________44
13 CHECK LIST ________________________________________________________________________________________________45
14 BIBLIOGRAPHY____________________________________________________________________________________________46
15 KEYWORD INDEX _________________________________________________________________________________________47
PREAMBLE
3
PREAMBLE
This manual is designed to provide an overview on the subject of cooling buildings with heat
pumps. It is designed for the trade and design engineers and represents a supplement to the
technical folder "Heat pumps".
In part I, the essential basics are explained, together with the influencing magnitudes of
ambient climate and comfort, as well as listing the differences between air-conditioning,
cooling and tempering. Furthermore, there will be a brief introduction relating to the h-x
diagram and the dew point.
The essential characteristics of passive and active cooling are explained, and diverse possible
heat sources and distribution systems are introduced.
The main part of this manual describes cooling with the various Stiebel Eltron heat pumps and
their corresponding WPMi control unit.
This overview provides information regarding possible application areas, sizing and
design/engineering. Important control variables, setting parameters and the respective
hydraulic diagrams are also illustrated.
The manual closes with an introduction of alternative systems for ambient cooling and costing
samples. The cost consideration includes a comparison of the different cooling systems by way
of an example: Active and passive cooling, room air-conditioning units and VRF air-
conditioning systems.
BODY TEMPERATURE, COMFORT, HOURS AT FULL UTILISATION
4
1 BODY TEMPERATURE, COMFORT, HOURS AT FULL UTILISATION
It is important for human beings to maintain a constant body temperature. For this to happen,
there must be balance between internal heat production and heat transfer to the ambience.
Internal heat production is primarily the result of the so-called activity level. Seated activities,
such as writing and reading, for example, represent activity level I.
On average, humans generate heat at 100 W. This exerts an influence on the heat added to the
ambient climate in much the same way as an installed device or a piece of lighting equipment.
Table 1 Heat production subject to activity in accordance with DIN 1946-2
Activity
level
Activity Heat production
per person [W]
Specific heat production
[W/m²]
- Basic metabolic rate 79 44
I Seated activity, such as
writing or reading
100 56
II Light work whilst standing
up, such as laboratory work,
typing
150 83
III Moderately heavy physical
activity
200 111
IV Heavy physical activity >250 >140
The heat transfer to ambience is subject to the climatic conditions of the surroundings and the
level of clothing. In the latter case, transfer is effected through radiation, convection, conduction
and water vapour diffusion. /2/
To maintain the heat balance, humans possess an effective temperature control system. For
example, an increase in blood circulation and dissipation of sweat can substantially increase
heat transfer to the ambience. /2/
Humans are able to store chemical energy, for example in the form of fat deposits. However,
humans have hardly any thermal storage capacity. Heat is produced constantly and transferred
to the ambience.
1.1 Comfort
The conditions at which humans perceive their thermal ambience as pleasant, in other words
when there is an equilibrium between the internal heat production and heat transfer, is
described as comfortable. Thermal comfort is a subjective perception variable that depends on
the ambience and the individual person.
BODY TEMPERATURE, COMFORT, HOURS AT FULL UTILISATION
5
Human comfort decreases with ambient temperatures that are too low or too high. Excessive
temperatures can also severely reduce human output/capacity. Consequently, living and
working environments should provide a comfortable climate.
The following terms are summarised under the comfort influencing variables:
- Activity level
- Clothing
- Air temperature
- Temperature of the surface areas enclosing the ambient space
- Relative humidity
- Air velocity
- Air purity
These different variables have lead to the assessment and evaluation of the ambient climate
being generally based on the comfort field developed by Leusden and Freymark, see diagram 1.
/2/ /4/
The following comfort diagram by Leusden and
Freymark illustrates the relationship between two
factors: Relative humidity and ambient
temperature.
For example, one person may not discern any
substantial loss in comfort at an ambient
temperature of 22 °C and a relative humidity
between 30 % and 70 %. He/she would perceive
both air conditions as equally pleasant.
Figure 1 Comfort field according to Leusden and Freymark
1.2 Hours at full utilisation for providing cooling
Buildings that require a higher cooling demand include offices, buildings for wholesalers and
retailers, hospitals, theatres, cinemas, as well as hotels and apartments. Generally, with
cooling, the internal temperature should only be reduced by approx. 3 to 6 K below the outside
temperature. Where higher temperature differentials persist there would be a risk of catching a
cold, as summer clothing would generally not be suitable for such ambient conditions.
For the annual hours at full utilisation in cooling operation, see the following tables.
BODY TEMPERATURE, COMFORT, HOURS AT FULL UTILISATION
6
Table 2 Hours at full utilisation /7/
Type of building Hours at full utilisation [h/p.a.]
cooling operation
Office building 300 - 400
Hospitals 800
Department stores 600 - 800
Trade fairs 500 - 600
Theatre/Cinema 200 - 300
Hotels 400 - 500
Apartments 100 - 200
BASES
7
2 BASES
The increasing demand for comfort has resulted in an increasing number of apartments being
equipped with cooling systems. At low energy consumption, these provide excellent ambient
comfort in most cases.
2.1 Air-conditioning, cooling and tempering
Air-conditioning of rooms means that the air temperature, as well as the relative humidity, is
regulated. Controlling the relative humidity requires a humidifying/de-humidifying system,
where the air is regulated to the required parameters using a cooler, a humidifier and a heater.
Conventionally, this is only done in centralised air-conditioning systems, where air acts as heat
transfer medium. Systems for the cooling of rooms to a specified temperature level generally
only require the air to be dehumidified. For this, fan convectors and ceiling cassettes with
condensate drain are used, where the water contained in the air condenses on the cooling
surfaces. Tempering describes the lowering or raising of the ambient temperature by a few
Kelvin. However, this does not result in any dehumidification. That is possible with heat transfer
above the dew point temperatures, for example via wall or underfloor heating systems or
cooling ceilings. In apartment buildings and smaller commercial operations, cooling and
tempering are the conventional method for increasing comfort levels.
Heat pumps enable both heating and cooling. In heating mode, heat pumps extract the heat
stored in the environment (underground, air, groundwater or surface water) and raise that
energy by means of a compressor to a higher temperature level that makes it useful for DHW
heating or for heating the building. In cooling mode, the heat transfer operates in reverse. Heat
is extracted from the building and transferred to the environment.
2.2 Passive and active cooling
When cooling a building with heat pumps, we differentiate between passive and active cooling.
The main difference between these methods is the operation with (active) or without (passive) a
compressor. In addition, refrigerant distribution systems are generally filled with antifreeze.
Where there is no risk of frost with passive cooling, water flows through the refrigerant
distribution systems, i.e. area heating, cooling ceiling or fan convectors. With active cooling, the
heating circuit contains a water:glycol mixture (brine).
Passive cooling is only possible when the heat source temperature lies below the required
cooling temperature. This can be assumed to be approx. 18 °C for underfloor heating systems
and 7 to 13 °C with fan convectors.
BASES
8
Active cooling is required when the heat source temperature lies above the required cooling
temperature.
Table 3 Main characteristics of passive and active cooling
Passive cooling Active cooling Compressor OFF Compressor ON Water in the distribution system Water:glycol mixture (brine) in
the distribution system
Heat source temperature lower than
the required cooling temperature
Passive cooling is also referred to as quiet or natural cooling; active cooling as dynamic cooling.
2.2.1 Passive cooling
With passive cooling, heat is transferred from the cool source via heat exchanger to the area
heating system or the fan convectors. The flow temperature is approx. 15 to 20 °C, and the
possible cooling capacity is limited to approx. 25 to 50 W/m². With area cooling, the cooling
water temperature must be above the dew point temperature. Otherwise condensate may form
on the heat exchanger surfaces.
Only pipes and fittings made from corrosion-resistant materials may be used. All supply lines
entering the house must be insulated in a vapour diffusion-proof manner to prevent the
formation of condensate.
2.2.2 Active cooling
The active cooling operates according to a principle similar to air-conditioning systems, where
the heat from within a building is extracted via the active refrigerant circuit and is then
transferred to low temperature "heat sink". Active cooling can be brought about by two different
means:
Method 1: Swapping the connections of the heating and heat source circuit at the heat pump
evaporator and condenser via suitable hydraulic equipment.
The heating circuit is routed to the heat pump evaporator and the source circuit to the heat
pump condenser. The heat pump compressor will be started, i.e. it is "active". The heat pump
can be changed over between heating and cooling via corresponding diverter valves. In
practical applications, this can only be brought about with brine|water heat pumps.
Method 2: Reversing the refrigerant circuit (reversible heat pumps).
The refrigerant circuit can be reversed. For this, the flow direction of the refrigerant is crucial.
The position of a 4-2-way valve determines the order of the components through which the flow
BASES
9
is routed. By changing the valve position, the evaporator and condenser functions are swapped,
and the operating mode changed between generating heat and cooling.
Figure 2 Operating mode of a brine|water heat pump with passive and active cooling function
Possible cooling distribution systems are fan convectors and ceiling cassettes.
Cooling ceilings and area heating systems are unsuitable for active cooling due to the low flow
temperatures. For example, cooling ceilings should not be operated with flow temperatures
below 15 °C.
The cooling capacity will not be rated at more than 60 W per m² heat transfer surface due to
considerations of personal comfort.
2.2.2.1 Comparison between active cooling using hydraulic changeover and a reversible
heat pump
The advantages and disadvantages of these two types of active cooling with heat pumps are
compared in the following table.
BASES
10
Table 4 Advantages and disadvantages - Hydraulic changeover and reversible heat pump
Cooling via hydraulic changeover Reversible heat pump
Advantages - Passive cooling is also possible, higher
efficiency
- Simultaneous cooling and DHW heating
possible
- Marginally better efficiency in the
refrigerant circuit
- Standard device can be used; optional
retrofitting (do not forget the thermal
insulation of existing pipe runs!)
- Lower pressure drop in the
heating circuit
- Lower investment outlay
Disadvantages - More material required (four diverter
valves); consequently more susceptible
- Higher pressure drop in the heating circuit
- Significantly higher installation effort and
space requirement
- Only active cooling is possible
- Either cooling or DHW heating
2.3 Heat cooling sources
Groundwater and ground probes are likely heat sources/heat sinks for passive cooling. Sources
for active cooling are ground probes, ground collectors and, to a limited extent, groundwater.
When cooling with reversible heat pumps, air or groundwater can be used as heat source/sink.
Table 5 Conventional natural heat sink systems for cooling with heat pumps [4]
Passive cooling Active cooling
Ground probe 8 – 12 °C Ground probe 8 – 12 °C
Groundwater 8 – 12 °C Ground
collector
0 – 15 °C
Outside air -20 - +35 °C
2.3.1 Ground probes
Passive cooling with ground probes utilises the constant temperature (approx. 10 °C) of the
ground at greater depths. The cooling capacity is sufficient for conventional residential
buildings and the assumption of a few cooling days per annum. Where high cooling loads are
present, the temperature underground gradually rises, resulting in a drop of the available
cooling capacity. Ground probes are suitable for passive and active cooling. For passive cooling,
the probes will be sized for 80% of the cooling extract capacity. For cooling operation it is
recommended to drill for shorter probes (max. 100 m).
Subject to application, size the probe for the heating or cooling case. In particular with high
internal cooling loads that may, for example, result from the presence of many occupants in the
BASES
11
building, the cooling demand may be greater than the heating energy demand. Cooling with
ground probes in summer also regenerates the heat source for winter.
Table 6 Average temperatures underground
Drilling depth
[m]
Average temperatures underground [°C]
Exposed site Urban area Height
0 9.5 9.5 3.2
25 11.3 12.5 8.0
50 12.0 13.5 8.7
75 12.8 14.5 9.5
100 13.5 15.5 10.2
125 14.3 16.5 11.0
150 15.0 17.5 11.7
175 15.8 18.5 12.5
200 16.5 19.5 13.2
2.3.2 Ground collectors
Ground collectors have only a limited use for passive cooling. Active cooling is possible.
With passive cooling, the ground heats up quickly reducing the temperature differential
between the ground temperature and the room temperature to an unacceptable level. In
addition, the ground temperature near the surface is substantially dependent on the outside
temperature. Should the temperature there exceed 15 °C, passive cooling could no longer be
achieved (see Figure 3).
The collector is well suited to active cooling, as in cooling mode; the ground has a substantially
lower temperature than the ambient air, thereby enabling the limit temperatures (10 - 60 °C) to
be maintained without difficulties. Furthermore, the CoP is higher than with systems using air
as heat sink. The drying out of the ground would be one disadvantage when using ground
collectors for active cooling.
The collector will be sized only for the heating operation.
BASES
12
Figure 3 Temperature progression underground
2.3.3 Groundwater
Both passive and active cooling are possible with groundwater as heat source.
Observe that the groundwater returned underground must not exceed a temperature of 20 °C. A
water analysis should also verify that the water is compatible with the heat exchanger material.
The average groundwater temperature in cooling mode is approx. 10 to 15 °C. Active cooling is
generally not required because of the low and stable temperature.
2.3.4 Air
With a reversible air|water heat pump, the outside air can be used as heat sink.
For this, the cooled air is transferred to the rooms to be cooled via fan convectors. There are no
further requirements of the source side. The heat source temperature determines the limits.
Table 7 Application limits reversible air|water heat pump
Outside air temp. Flow temp.
Min. Max. Min. Max.
Heating –20 °C 35 °C 18 °C 60 °C
Cooling 15 °C 40 °C 7 °C 20 °C
2.4 Distribution systems
The cooling operation is possible via an area (underfloor heating system, ceiling) or via fan
convectors (with condensate drain).
Heat is dissipated via an additional heat exchanger that, in cooling mode, receives a flow of
brine via a three-way valve. In heating mode, this is generally supplied constantly in series with
the condenser whilst the pump is running.
BASES
13
Apart from selecting the distribution system it requires careful consideration which rooms
actually require cooling in summer. It is, for example, conventional not to include the
bathroom, toilet and kitchen into the cooling cycle. Rooms requiring cooling include: Working,
living and bedrooms.
2.4.1 Area heating (underfloor)
The cooling capacity for cooling with area heating systems can be up to 25 W/m². However, this
may be significantly higher if the area heating system is subject to direct solar irradiation.
The cooling capacity is limited since, according to DIN 1946-2, a room temperature should not
exceed 21 °C at 0.1 m height when operating an underfloor heating system in cooling mode. /6/
When sizing the underfloor heating system for cooling, select a smaller pipe spacing than
would be conventional for heating purposes. The following applies to both heating and cooling
cases: The better the thermal insulation of the building the higher the pipe spacing can be with
identical flow temperatures.
The following summarises a number of climatic, economic and architectural benefits of area
cooling:
- High comfort level
- No draughts
- Quiet operation
- Low investment outlay
- Low operating costs
- Unrestricted interior design
Monitoring the relative humidity is beneficial, to prevent the formation of condensate on the
cooling surfaces. Check with the respective parquet manufacturer, whether this kind of floor
surface is compatible with a cooling operation.
Figure 4 Method of laying an underfloor heating system
2.4.2 Area heating (ceiling)
No minimum air temperatures need to be taken into consideration. Consequently, the cooling
capacity of a cooling ceiling can be substantially higher than that of an underfloor heating
system used for cooling. As a result, specific cooling capacities between 40 and 100 W/m² are
H-X DIAGRAM AND DEW POINT TEMPERATURE
14
possible, whereby the flow temperature represents the limiting variable. The minimum flow
temperature for cooling ceilings is 15 °C (manufacturer's details).
Figure 5 System image, cooling ceilings
2.4.3 Fan convectors and ceiling cassettes
The cooling capacity of fan convectors and ceiling cassettes is subject to the size of the building,
the air flow rate and the cooling water temperature. The larger and more powerful the device,
the higher its cooling capacity, but also the air flow rate and the air velocity. To prevent the
comfort limits specified by the DIN 1946 being exceeded, the cooling capacity should be
between 30 and 60 W per m² heat transfer surface of the fan convector.
The pipelines for the fan convectors and ceiling cassettes must be installed vapour diffusion-
proof. Pipelines embedded into walls cannot be used for connection to fan convectors as they
are not vapour diffusion-proof.
Figure 5 Fan convector and ceiling cassette
The distribution system for active cooling with fan convectors or ceiling cassettes is filled with
water:glycol mixture (brine). Consequently, the resistance of the individual components to brine
must be checked out. Brine can only be topped up as ready-mixed solution.
Please note: It is prohibited that the heating circuit is filled with potassium carbonate.
3 H-X DIAGRAM AND DEW POINT TEMPERATURE
Mollier best depicts the change in condition non-cooled rooms/cooled rooms in the so-called
h-x diagram.
In the following simplified diagram, temperature, relative humidity and absolute humidity are
depicted.
H-X DIAGRAM AND DEW POINT TEMPERATURE
15
It is assumed that the non-cooled room has a temperature of 26 °C and a relative humidity of
65 % (point 1).
If the room is cooled by, for example 4 K by passive or active cooling (cooling to above the dew
point = above the saturation line), draw a vertical line down from point 1 to the 22 °C
isothermal line1 (point 2). Now the temperature of the cooled room is 22 °C with a relative
humidity of 80 %. This demonstrates clearly that the relative humidity increases when the room
is cooled.
If the cooling reaches below the saturation line, a different condition occurs and condensate is
produced.
Figure 6 Change of condition room cooling /3/
1 Isothermal lines: Lines of constant temperature
H-X DIAGRAM AND DEW POINT TEMPERATURE
16
The dew point temperature subject to the air temperature and relative humidity can also be
checked in the h-x diagram. The dew point temperature for condition 2 can be checked on the
Y-axis, if the vertical line from point 1 to point 2 is extended to the saturation line. In that case it
is 18.4 °C.
Working with the following table enables a precise and more convenient determination of the
dew point temperature.
Table 8 Dew point temperature
COOLING WITH BRINE|WATER HEAT PUMPS
17
4 COOLING WITH BRINE|WATER HEAT PUMPS
4.1 Sizing
The ground probes are sized according to the heat pump heating output. The resulting cooling
capacity is illustrated in the following table. Where higher cooling capacities are required,
install a correspondingly greater number of probes.
Table 9 Sizing table ground probe
Heat pump type Heating
output
(0/35) [kW]
Refrigeration
capacity
[kW]
Ground
probe
32 x 2.9
No.
Ground
probe2
32 x 2.9
Depth [m]
Cooling
capacity
[kW]
WPC 5 cool 5.8 4.5 1 pce. 82 3.2
WPC 7 cool 7.8 6.0 1 pce. 109 4.2
WPC 10 cool 9.9 7.7 2 pce. 70 5.4
WPC 13 cool 13.4 10.3 2 pce. 94 7.2
WPF 5 5.8 4.5 1 pce. 82 3.2
WPF 7 7.8 6.0 1 pce. 109 4.2
WPF 10 9.9 7.7 2 pce. 70 5.4
WPF 13 13.4 10.3 2 pce. 94 7.2
WPF 16 16.1 12.5 3 pce. 84 9.6
4.2 WPF operating modes
4.2.1 Heating mode WPF
Environmental energy is extracted from the ground via the heat exchanger on the heat source
side. The absorbed energy together with the energy used to drive the compressor is transferred
to the heating water by the heat exchanger on the heating water side. The domestic hot water is
heated via the indirect coil integrated into the DHW cylinder.
2 Condition: Approx. 55 W/m extraction capacity.
COOLING WITH BRINE|WATER HEAT PUMPS
18
4.2.2 Passive cooling operation with WPF
The brine circulates in cooling mode via the additional heat exchanger. Consequently, heat is
transferred from the hotter to the colder medium. The heating water of the area heating system
or the cooling ceiling cooled by this method flows through the floor/ceiling of the rooms to be
cooled and thereby lowers the area temperature of the floor/ceiling. The compressor will only
be started if DHW is required. The water at the higher temperature level flows directly into the
indirect coil of the DHW cylinder.
The cooling operation remains switched off during DHW heating.
4.3 WPC cool operating modes
4.3.1 Heating mode WPC cool
Environmental heat is extracted from the ground via the heat exchanger on the heat source
side. Any energy extracted is transferred, together with the energy drawn by the compressor
drive, to the heating water by the heat exchanger on the heating water side. The DHW is heated
via the internal indirect coil inside the DHW cylinder. The DHW cylinder is integrated into the
WPC cool.
4.3.2 Passive cooling operation with WPC cool
The brine circulates in cooling mode via the additional heat exchanger. Heat is transferred from
the hot to the cold medium. The heating water of the area heating system or cooling ceiling
cooled by this process flows through the floor/ceiling of the rooms to be cooled, thereby
lowering the temperature of the floor/ceiling. The compressor will only be started if DHW is
required. The water at the higher temperature flows directly into the indirect coil of the DHW
cylinder.
The cooling operation remains switched off during DHW heating.
4.4 Active cooling operation WPF and WPC
Active cooling requires the cooling module WPAC 1 (with integral brine circulation pump) or
WPAC 2 (without integral brine circulation pump). The modules are comprised of the following:
Four 3-2-way valves switch the circulation over between heating, passive and active cooling
subject to demand.
Cooling with the WPAC is controlled in two stages from passive to active cooling.
1. Stage: Cooling through running source pump.
2. Stage: Cooling though running source pump and running compressor.
Stage 2 will be added if, after cooling at stage 1 for 30 minutes, the actual flow temperature is
still higher than the required flow temperature.
COOLING WITH BRINE|WATER HEAT PUMPS
19
Figure 6 WPAC 1 layout for WPF (l.h.) and WPAC 2 for WPC (r.h.)
The WPMi heat pump manager controls the system.
Active cooling is currently only possible with fan convectors or ceiling cassettes.
4.4.1 Minimum flow rate for active cooling
The minimum flow rate on the side to be cooled corresponds to the minimum flow rate in
heating mode. The minimum flow rate on the source side in cooling mode must be halved,
relative to the minimum flow rate on the source side in heating mode.
The following applies: Cooling side (inside the building): heatingcooling VV min,min,&& =
Source side: heatingcooling VV min,min, 5,0 && ⋅=
4.5 Valve positions
4.5.1 Passive cooling
During passive cooling, brine is routed via changing the valve positions so that the brine cooled
by the ground flows directly into the fan convector. The evaporator must receive a volume flow
on account of the pipework, without the compressor running. The return from the fan
convectors is routed through the condenser back outside again into the ground probes.
4.5.2 Active cooling
With active cooling, the valves are positioned so that the heating water leaving the fan
convector is routed through the evaporator and the brine circuit of the ground probes through
the condenser.
The heating water leaving the fan convector must be routed through the evaporator to extract
the heat from the heat transfer medium. The compressor will be running.
The source pump is adequate for cooling operation up to the brine|water heat pump WPF 13.
For heat pumps with a higher output range, a second, additional source pump or a low loss
header is required.
COOLING WITH BRINE|WATER HEAT PUMPS
20
4.5.3 Cooling and DHW demand
For active cooling, we need to differentiate between the two possible cooling stages. The
cooling output is immediately switched off in case of DHW demand, and DHW heating is
activated if the system is in cooling mode stage 1 (source pump ON, compressor OFF).
In cooling mode stage 2 (source pump ON, compressor ON), cooling and DHW heating can
operate in parallel. The cooling output is, in that case, only switched off if the required flow
temperature and the set room temperature are achieved.
Figure 7 Operating mode of a brine|water heat pump with passive and active cooling function
COOLING WITH BRINE|WATER HEAT PUMPS
21
4.6 Hydraulics WPF
Figure 8 Hydraulic diagram - Heating with WPF without WPAC 1
Figure 9 Hydraulic diagram - Passive cooling with WPF without WPAC 1
Legend:
TA = Temperature sensor
outside
TA = Temperature sensor
flow
TA = Temperature sensor
return
TW = Temperature sensor
DHW
FEK = remote control with
room temperature and
humidity sensor
COOLING WITH BRINE|WATER HEAT PUMPS
22
4.7 Hydraulics WPF with WPAC 1
Figure 10 Hydraulic diagram - Heating with WPF and WPAC 1
Figure 11 Hydraulic diagram - Passive cooling with WPF and WPAC 1
Figure 12 Hydraulic diagram - Active cooling with WPF and WPAC 1
Legend:
TA = Temperature sensor outside
TM = Temperature sensor mixer
TR = Temperature sensor return
TW = Temperature sensor DHW
FE7 = Remote control with room
temperature sensor
FEK = Remote control with room
temperature and humidity sensor
COOLING WITH BRINE|WATER HEAT PUMPS
23
4.8 Hydraulics WPC cool
Figure 13 Hydraulic diagram - Heating and cooling with WPC cool without WPAC 2 Key:
TA = Temperature sensor outside
FEK = Remote control with room
temperature and humidity sensor
COOLING WITH BRINE|WATER HEAT PUMPS
24
4.9 Hydraulics WPF with WPAC 2
Figure 14 Hydraulic diagram - Heating with WPC and WPAC 2
Figure 15 Hydraulic diagram - Passive cooling with WPC and WPAC 2
Figure 16 Hydraulic diagram - Active cooling with WPC and WPAC 2
Key:
TA = Temperature sensor outside
TM = Temperature sensor mixer
TR = Temperature sensor return
TW = Temperature sensor DHW
FE7 = Remote control with room
temperature sensor
FEK = Remote control with room
temperature and humidity sensor
COOLNG WITH WATER|WATER HEAT PUMPS
25
5 COOLNG WITH WATER|WATER HEAT PUMPS
5.1 Sizing
The volume of groundwater that can be utilised to remove heat is determined in accordance
with the volume of groundwater required by the heat pump.
The temperature differential between the groundwater and the cooling water is approx. 5 K.
The average groundwater temperature in cooling mode is approx. 15 °C.
Table 9 Sizing table groundwater
Heat pump type Cooling output Groundwater
volume3
WPW 7 5.9 kW 1.5 m³/h
WPW 10 8.2 kW 2.1 m³/h
WPW 13 10.2 kW 2.6 m³/h
WPW 18 14.1 kW 3.4 m³/h
WPW 22 M 18.2 kW 4.4 m³/h
5.2 Operating modes
5.2.1 Heating operation
Heat is extracted from the groundwater via the heat pump heat exchanger on the heat source
side. Any energy extracted is transferred, together with the energy drawn by the compressor
drive, to the heating water by the heat exchanger on the heating water side. The heating water
is routed via the buffer cylinder into the underfloor heating system and the indirect coil in the
DHW cylinder.
3 The system will be sized for heating operation. If required, a higher cooling capacity can be achieved with a
larger well pump.
COOLNG WITH WATER|WATER HEAT PUMPS
26
5.2.2 Passive cooling operation
The cool groundwater is routed through the additional heat exchanger when cooling is
required. Heat is transferred from the hotter to the colder medium. The heating water of the
area heating system or cooling ceiling cooled by this process flows through the floor/ceiling of
the rooms to be cooled, thereby lowering the temperature of the floor/ceiling. The cooled
heating water can also be routed through a fan convector or ceiling cassettes. The compressor
will only be started if DHW is required. The water at the higher temperature flows directly into
the indirect coil of the DHW cylinder.
The cooling operation is switched off during DHW heating.
5.2.3 Active cooling operation
Theoretically at least, active cooling is possible with a reversible water|water heat pump. Active
cooling using hydraulic changeover is not feasible.
COOLING WITH AIR|WATER HEAT PUMPS
27
6 COOLING WITH AIR|WATER HEAT PUMPS
Information regarding the sizing, operating modes and the hydraulic layout for active cooling
with reversible air|water heat pumps will be available mid 2007.
SETTING PARAMETERS OF AND CONTROL WITH THE WPMi
28
7 SETTING PARAMETERS OF AND CONTROL WITH THE WPMi
The cooling operation can only be regulated with the heat pump manager WPMi. The WPMi is
fitted as standard to the following heat pumps: WPC, WPC cool, WPF with integral controller
and WPW with integral controller. Currently, the WPM II offers no cooling function.
In addition, the operation requires the analog remote control unit with room temperature
sensor FE 7 or the digital remote control unit FEK with room temperature sensor and humidity
sensor.
A separate remote control unit is required for each circuit in systems with two heating circuits.
Cooling via heating surfaces is only possible with the FEK.
Figure 17 FE 7 and FEK (from left to right)
For cooling, the heat pump manager WPMi must be in Summer mode. The changeover from
heating mode to summer mode is subject to the outside temperature.
Three adjustable parameters are available for the summer mode. Summer mode 1 for lightly
built constructions. In this mode, the average outside temperature is calculated over a period of
24 hours. In this mode, the average outside temperature is calculated over a period of 48 hours.
In this mode, the average outside temperature is calculated over a period of 72 hours.
The heat pump automatically changes over to summer mode if the average outside temperature
is higher than 20 °C. The freely selectable standard setting was factory-set to summer mode 1
and a changeover at 20 °C.
The outside temperature from which the changeover from heating to summer mode occurs, can
be reduced by up to 1 °C. For this, the outside temperature must be higher than the selected
value.
The heat pump manager is in summer mode, if the heat pump stops and restarts again straight
away after the outside temperature value has been changed. This enables a check during
commissioning whether the changeover from winter to summer mode functions correctly.
SETTING PARAMETERS OF AND CONTROL WITH THE WPMi
29
7.1 Standard settings
Control unit setting parameters for cooling:
- Set room temperature
- Flow temperature
- Flow temperature hysteresis (in this case a "+ hysteresis")
- Dynamic
Table 10 Standard setting and setting ranges for the WPMi
Standard setting Setting range
Set room temperature 25 °C 20 °C - 30 °C
Flow temperature 15 °C 10 °C – 25 °C
Flow temperature hysteresis 5 K +1 K – +5 K
Dynamic 10 1 - 10
7.2 Set room temperature
For cooling, the set room temperature should be changed subject to the outside temperature.
Generally, with cooling, the internal temperatures should only be approx. 3 to 6 K below the
outside temperature (relative to a setting range of 22 - 26 °C).
7.3 Flow temperature
Apart from the set room temperature, the customer can also change the flow temperature.
Recommendation:
- Floor tiles, flow temperature 20 °C,
- Carpet, flow temperature 15 °C,
A lower flow temperature must be selected for fitted carpets, as the heat transfer coefficient of
carpeted floors is lower than that of tiles.
7.4 Flow temperature hysteresis
The control circuit requires a hysteresis to prevent a counter-action when minute control
deviations occur. The hysteresis specifies the possible deviation from the set value.
For a system with slow responses, the recommended setting of the hysteresis subject to the heat
transfer coefficient is: Small hysteresis (2 K), and large hysteresis (5 K) for a system with quicker
responses.
The heat transfer coefficient describes the resistance of a material to thermal conduction and is
therefore a measure for the speed of the heat transfer, in this example of heating water to the
floor surface.
SETTING PARAMETERS OF AND CONTROL WITH THE WPMi
30
Table 11 Recommended values for flow temperature and flow temperature hysteresis
Flow temp. [°C] Hysteresis [K]
Parquet 15 2
Laminate 15 2
Natural
stone
20 4
Carpet 15 2
Cork 15 1
Marble 20 5
Clay 20 4
7.5 Dynamic (active cooling only)
The dynamic parameter enables a choice to be made as to how quickly the compressor is
started in case of active cooling. Values between 1 and 10 can be selected.
Quick reacting system
The dynamic, set to 1, switches the compressor ON as soon as the source pump has been running
for 10 minutes and the current flow temperature is higher than the selected flow temperature
plus the flow temperature hysteresis plus 0.5 K (hysteresis for the dynamic of value 1).
Slow reacting system
The dynamic set to 10 switches the compressor ON after the source pump has been running for
30 minutes and the current flow temperature is higher than the selected flow temperature plus
the flow temperature hysteresis plus 2 K (hysteresis for the dynamic of value 10).
Interpolation is applied between the values 1 and 10.
7.6 Control characteristics of the passive cooling
The cooling mode is started when the actual room temperature is ≥ 25 °C. The heating circuit
pump and the control unit cooling output are switched ON. For the first 60 seconds, only the
heating circuit pump is enabled.
7.6.1 Source pump
The source pumps starts when the control variable is smaller than the actual flow temperature.
The control variable is different for each distribution system.
SETTING PARAMETERS OF AND CONTROL WITH THE WPMi
31
7.6.1.1 Fan convectors
For fan convectors, the control variable is equal to the selected flow temperature. The following
applies: Control variable = selected flow temperature
7.6.1.2 Heating surfaces
The dew point of the heating surfaces is also monitored.
Control variable = selected flow temperature if the selected flow temperature + hysteresis >
dew point temperature + 2 K (see example case 1)
Control variable = dew point temperature + 2 K if the selected flow temperature + hysteresis
< dew point temperature + 2 K (see example case 2)
Here is an example by way of an explanation:
The user has selected a flow temperature of 15 °C plus a flow temperature hysteresis of 5 K. As
a result a flow temperature of 20 °C is calculated.
Case 1: Relative humidity in the room: 75 %
The dew point temperature at 20 °C and a relative humidity of 75 % is 15.4 °C (see Table 8);
15.4 °C + 2 K = 16.4 °C
16.4 °C < 20 °C: Control variable = selected flow temperature + hysteresis = 20 °C
Case 2: Relative humidity in the room: 90 %
This results in a dew point temperature at 20 °C and 90 % relative humidity of 18.3 °C.
18.3 °C + 2 K = 20.3 °C
20.3 °C > 20 °C: Control variable = dew point temperature + 2 K + hysteresis = 18.3 °C + 2 K
+ 5 K = 25.3 °C
Independent of the flow temperature, the source pump must run for at least 5 minutes. This
ensures that at least once, only cool water enters the cooling system to achieve a cooling effect
at all.
At a flow temperature < 15 °C, the source pump switches OFF subject to the standard settings.
If, during this minimum runtime of 5 minutes, DHW heating is demanded, the cooling mode
immediately switches over to DHW heating.
7.7 Control characteristics of the active cooling
The active cooling is controlled in the same way as passive cooling and is only supplemented by
starting of the compressor and a simultaneous changeover of the valves.
SETTING PARAMETERS OF AND CONTROL WITH THE WPMi
32
7.7.1 Compressor
If, after 30 minutes of passive cooling (the source pump has been running for 30 minutes), the
actual flow temperature is still higher than the control variable plus hysteresis, the compressor
starts and the valves change over.
The compressor switches OFF if the room temperature is lower than the set room temperature –
2 K.
In this case, the 2 K is a fixed control hysteresis that should not be confused with the flow
temperature hysteresis.
BRINE RESISTANCE
33
8 BRINE RESISTANCE
With active cooling, fill the distribution system with a water:glycol mixture (brine). Therefore
ensure that the individual components concerned are resistant to brine. Brine must only be
topped up with a ready-mixed solution.
If the system is run with brine expect a 1.5-fold pressure drop.
If the correct glycol:water concentration was filled into the system and the brine contains
corrosion inhibitors (25 to 33 %), then the following components from the Stiebel Eltron product
range are brine resistant:
- Pumps
- Valves
- Expansion vessels
- Safety valves
Overflow valves, the seals of which are made from PTFE, are suitable for water:glycol mixtures
without restrictions.
When selecting the pump, ensure that only cast pumps (condensate forming between the casing
and the stator) or rotary pumps are used.
The expansion vessel on the brine side may possibly be sized larger in brine|water heat pumps
in cooling mode on account of the temperature differentials.
Table 12 Possible temperature differentials during heating and cooling
Temperature
differentials
Heating 5 – 15 °C
Passive cooling 5 – 25 °C
Active cooling 5 – 50 °C
WIRING CHANGEOVER COOLING MODE
34
9 WIRING CHANGEOVER COOLING MODE
9.1 Wiring diagram
Figure 18 Hydraulic diagram WPF
Figure 19 Connection diagram WPF
WIRING CHANGEOVER COOLING MODE
35
Figure 20 Hydraulic diagram WPC cool
Figure 21 Connection diagram WPC cool
WIRING CHANGEOVER COOLING MODE
36
Figure 22 Hydraulic diagram - Cooling WPF with WPAC 1
Figure 23 Connection diagram - WPF with WPAC 1
WIRING CHANGEOVER COOLING MODE
37
9.2 Distribution strip/zone valve
For the changeover from heating to cooling mode with area heating systems and the associated
opening of actuator valves in the heating circuits in the rooms to be cooled, special distribution
strips are available.
Such distribution strips enable the connection of room temperature controllers and actuators in
the individual rooms. In addition, they are equipped with an input for changing over between
cooling and heating mode.
Figure 24 Distribution strip heating/cooling
The following overviews explain how the wiring of the rooms that require cooling and those
that do not should be carried out.
WIRING CHANGEOVER COOLING MODE
38
Figure 25 Connection diagram for the wiring of the distribution strip with room thermostat
1 Room thermostat, heating only 2 Room thermostat, heating and cooling 3 Valves, room 1 K Cooling H Heating L Phase N Neutral conductor
WIRING CHANGEOVER COOLING MODE
39
Figure 26 Example of a connection diagram for the wiring of the distribution strip
1 SP cool distributor strip 2 Room 1, heating and cooling 3 Room 2, heating and cooling 4 Room 3, heating only 5 Single room thermostat (on site) 6 FEK digital remote control 7 Heating circuit distributor 8 WPMi heat pump manager
COMPARISON COOLING WITH DIFFERENT HEAT PUMPS
40
10 COMPARISON COOLING WITH DIFFERENT HEAT PUMPS
The advantages and disadvantages of the heat pump types for use in passive and active cooling
are compared in the following table.
Table 13 Overview of the advantages and disadvantages
Brine|Water heat pump Water|Water heat pump Reversible Air|Water heat
pump
Advantages - Passive and active
cooling are possible
- Low flow temperature
possible (active cooling)
- Low operating costs as
only the brine
circulation pump
operates (in passive
cooling)
- Passive cooling adequate
due to constant heat
source temperature
- Constant flow
temperature
- Low operating costs as
only the well pump
operates (in passive
cooling)
- Low installation costs
for the heat source
- Flow temperatures up
to 7 °C possible
Disadvantages - High installation costs
for the heat source
- Flow temperature
subject to the ground
probe temperature (in
passive cooling)
- High installation costs for
the heat source
- Check the heat
exchanger compatibility
with groundwater
- Cooling only possible
from outside
temperatures of 15 °C
- Only active cooling is
possible
- High operating costs as
pumps and compressor
operate
In summary it can be said that, with a brine|water heat pump passive and active cooling is
feasibly. With a water|water heat pump, passive cooling may frequently be adequate. With
reversible air|water heat pumps, only active cooling is technically feasible.
ALTERNATIVE SYSTEMS AND COST CONSIDERATIONS
41
11 ALTERNATIVE SYSTEMS AND COST CONSIDERATIONS
11.1 VRF systems, air-conditioning systems with direct evaporation
Split air-conditioning units are an alternative to the extraction of cooling loads. In such
equipment, condensate is created when cooling the air; this must be drained away. One
disadvantage is the additional installation effort (internal and external equipment, wall outlets),
which is not required for cooling with an existing area heating system.
11.2 Free cooling
Free cooling represents an alternative that requires no mechanical drive for cooling the
buildings. This can be easily realised if the room to be cooled is equipped with ventilation
openings in opposing walls (windows, ventilation flaps). This enables effective night ventilation
by cross venting. The cooling capacity is hampered by the low temperature differential between
day and night temperatures, particularly on hot days. The specific cooling capacity is approx. 1.5
to 2.5 W/(m³/h). /5/
Free ventilation is easily achieved with domestic ventilation systems.
11.3 Air duct
Apart from fan convectors or area heating systems there is the possibility of utilising air ducts in
existing domestic ventilation systems as an alternative distribution system for cooling purposes.
For this, a corresponding heat exchanger can be integrated into the central ventilation unit. One
problem, however, is that pure cooling raises the relative humidity, resulting in the
temperature falling below the dew point and consequently in condensation. Cooling/tempering
is therefore unacceptable for hygienic reasons. However, air-conditioning with dehumidification
would be feasible.
A classic office air-conditioning system, where the offices are air-conditioned with treated air,
contains several banks for treating the air. There are units for humidifying and dehumidifying
the air as well as those for boosting the heating. In other words, these units do not provide a
simple cooling of the air. Also, these units are serviced regularly.
11.4 Water wall
Water walls represent a simple option for reducing the room temperature in summer. If the
circulating water is cooled below the dew point, condensate is created on the water surface,
making the water wall suitable for dehumidification and cooling.
ALTERNATIVE SYSTEMS AND COST CONSIDERATIONS
42
11.5 Cost consideration
Today, buildings are almost always cooled with split air-conditioning units, chillers or VRF
systems (variable refrigerant flow). The alternative, i.e. the use of heat pumps for cooling
purposes, has come to be considered recently as heat pumps have found increasing favour as
heating system. The heat pump has become a favourite heating system since oil and gas prices
have constantly risen in cost. The additional use for cooling or tempering is attractive because
of the low level of addition costs for the cooling systems and the very low costs for generating
the cooling capacity. The combined use for cooling and heating improves the efficiency of heat
pumps with ground probes in heating mode, as the ground probe significantly regenerates the
ground in summer.
The following cost consideration compares three typical application examples for cooling; these
are also shown in Table 14.
Example 1: Residential building 150 m² (cooling load 6 kW, 4 rooms, 150 hours at full cooling
utilisation)
Example 2: Office building 300 m² (cooling load 25 kW, 15 rooms, 400 hours at full cooling
utilisation)
Example 3: Shop 500 m² (cooling 45 kW, 700 hours full cooling utilisation)
Cooling foodstuffs with active or passive cooling is not feasible due to the limits of use, off
periods and control equipment.
ALTERNATIVE SYSTEMS AND COST CONSIDERATIONS
43
Table 14 Cost comparison for different cooling systems using the examples of a residential building, an office building and a shop /1/
Heat pump
Passive cooling Active cooling
Room air-
conditioning
units
VRF-controlled
air-conditioning
systems
Performance factors in cooling mode 15.0 4 5.0 3.0 3.8
Example: Residential building 150 m² (cooling load 6 kW, 4 rooms, 150 hours at full cooling
utilisation)
Additional investment, cooling €2.000 €7.000 €9.000
Energy costs €9.0/p.a. €19.8/p.a. €45.0/p.a.
Annual cooling costs €268.0/p.a. €926.3/p.a. €1210.5/p.a.
Unusual
Example: Office building 300 m² (cooling load 25 kW, 15 rooms, 400 hours at full cooling utilisation)
Additional investment, cooling €4.000 €25.000 €30.000 €45.000
Energy costs €100.0/p.a. €220.0/p.a. €500.0/p.a. €395.0/p.a.
Annual cooling costs €618.0/p.a. €3457.5/p.a. €4385.0/p.a. €6222.5/p.a.
Example: Shop 500 m² (cooling 45 kW, 700 hours full cooling utilisation)
Additional investment, cooling €5.000 €27.000 €40.000
Energy costs €315.0/p.a. €693.0/p.a. €1243.0/p.a.
Annual cooling costs €962.5/p.a. €4189.5/p.a.
Unusual
€6423.0/p.a.
Assumptions for the cost consideration
- The investment outlay for the devices is based on manufacturer's details plus conventional installation
costs.
- For the additional costs in connection with the cooling with heat pumps it is assumed that a heat pump
heating systems with ground probes is already installed.
- The electricity tariff for active cooling with heat pump is €0.11/kWh.
- The electricity tariff for passive cooling with heat pump and cooling with room air-conditioning units and
VRF systems is €0.15/kWh.
- The annuity with an annuity factor of 12.95 % is based on an amortisation period of 10 years with an
interest rate of 5 %.
11.5.1 Recommendations
Given the energy and annual cooling costs, as well as the different cooling loads, we
recommend the use primarily of passive cooling in detached houses. In office buildings, passive
and active cooling and in small businesses primarily the active cooling is recommended.
4 Only the pump operation for the brine and heating circuit are taken into account, as the compressor operation is not
required.
COOLING LOAD CALCULATION FORM
44
Table 15 Overview application options passive/active cooling
Passive cooling Active cooling
Detached house Office building
Office building Small business
12 COOLING LOAD CALCULATION FORM
The cooling load activation form enables an estimate of the cooling load for one room
respectively to be made. The following influencing factors are taken into consideration:
- Cooling load due to solar irradiation through windows, skylights and doors
- Cooling load due to external and internal walls and floors
- Cooling load due to the ceiling
- Cooling load due to electrical devices
- Cooling load due to occupants
CHECK LIST
45
13 CHECK LIST
- What is the purpose of the heat pump?
- What heat source is to be used with the heat pump?
- What is the required cooling capacity? Carry out a cooling load calculation.
- What cooling source is available?
- Check the compatibility of the heat exchanger when cooling with a water|water heat
pump.
- All lines and fittings must be made from corrosion resistant material.
- Are all components resistant to brine?
- Are all pipe runs insulated in a vapour diffusion-proof manner?
- Must application limits be taken into consideration?
- The brine increases the pressure drop. This must be taken into account when sizing the
pumps; allow for a 1.5-fold pressure drop.
- Topping up with brine only as ready-mixed solution.
- The expansion vessel on the brine side may need to be sized larger for cooling since the
temperature differentials are greater.
- Use only a circulation pumps that are resistant to brine and condensate.
- Minimum flow rates, active cooling: On the cooling side: The same minimum flow rate as
for heating; on the source side: ½ the minimum flow rate as for heating.
The following applies: Cooling side (inside the building): heatingcooling VV min,min,&& =
Source side: heatingcooling VV min,min, 5,0 && ⋅=
BIBLIOGRAPHY
46
14 BIBLIOGRAPHY
/1/ Brugmann, Krone; Technische, energetische und wirtschaftliche Bewertung passiver und
aktiver Kühlsysteme mit Sole/Wasser-Wärmepumpen, published 4th Forum Wärmepumpen
2006, Berlin
/2/ Handbuch der Klimatechnik, vol. 1 Grundlagen, publisher C.F. Müller GmbH, Karlsruhe 1989,
chapter 3 Physiologische Grundlagen p. 62
/3/ h-x diagram, http://www.bosy-online.de/hx-diag.pdf (11/06)
/4/ Leusden, Freymark, Behaglichkeitsfeld; Der Gesundheitsingenieur, No. 72, 1951
/5/ Pfluger, Rainer; Technologien zur energieeffizienten Raumkühlung: passiv-hybrid-aktiv,
Energieeffiziente Raumkühlung, Protokollband 31
/6/ Recknagel, Sprenger, Schramek; Taschenbuch für Heizung und Klimatechnik, 2005/2006
72nd issue, Oldenbourg Industrieverlag Munich 2005, p. 1134 3.2.3-7 Kombinierter Kühl- und
Heizboden
/7/ Sponsel, Christian, Hilligweg, Arnd; Wirtschaftlichkeit von Eisspeichern, TGA Fachplaner
4-2003
KEYWORD INDEX
47
15 KEYWORD INDEX
Active cooling, 8
Air, 12
Air-conditioning, cooling and tempering, 7
Area heating (ceiling), 13
Area heating (underfloor), 13
Brine resistance, 34
Ceiling cassettes, 14
Comfort, 4
Comparison of cooling with different heat
pumps, 40
Cooling load calculation form, 44
Cooling via hydraulic changeover, 10
Cooling with air|water heat pumps, 28
Cooling with brine|water heat pumps, 17
Cooling with water|water heat pumps, 26
Distribution strip/zone valve, 38
Dynamic, 31
Fan convectors, 14
Ground collectors, 11
Ground probes, 10
Groundwater, 12
Hours at full utilisation for providing
cooling, 5
h-x diagram and dew point temperature, 14
Hydraulics WPC cool, 24
Hydraulics WPF, 22
Hydraulics WPF with WPAC 1, 23
Hydraulics WPF with WPAC 2, 25
Operating modes WPC cool, 18
Operating modes WPF, 17
Passive cooling, 8
Reversible heat pump, 10
WPMi, 29