    MX-F Series 

    TEMPERATURE CONTROLLER

     T  E  M P  E  R  A  T 

     U  R  E 

     C  O N T  R  O L  L  E  R 

    4

    Universal Input•Output and High Accuracy 0.5 class 250ms

    ● RAMP function

    ● PID Auto-tuning

    ● Universal input

    ● ℃/℉, Reverse/Direct action selectable

    ● Remote/Local input selectable

    ■ Model and suffix code (MX-F Series)

    MODEL

    MX

    CONTROL

    OUTPUT

    SUFFIX CODE DESCRIPTION

    F

    M

    C

    S

    V

    N

    N

    P

    MX2/3/4/7/9

    Normal PID Auto-tuning

    Relay contact

    Current(4~20㎃ DC)

    SSR drive pulse voltage(0/12V DC)

    Voltage(1~5V DC)

    None

    Refer to CODE

    None

    HBA function(CT separately)

    None

    Refer to CODE

    Option is not valid in MX4-F.In current output(C), lamp signal of “OUT”does not flash.

    ① Retransmission output

    ② Heater Break Alarm(HBA)

    ③ Remote input

    O

    P

    T

    I

    ON

    CODE  ① DC 0~10㎷ ② DC 0~100㎷ ③ DC 0~1V ④ DC 0~5V

    ⑤ DC 0~10V ⑥ DC 1~5V ⑦ DC 0~20㎃ ⑧ DC 4~20㎃

    N

  • 8/18/2019 Hanyoung MX4

    2/9

    69

    MX-F Series 

    TEMPERATURE CONTROLLER

      T  E  M  P  E  R  A  T  U  R  E  C  O  N  T  R  O  L  L  E  R

    4

    ■ Functional Description

    ■ Input and Range

    ■ MX9-F

    Auto tuning(AT)

    Remote input(REM)

    Control output(OUT)

    Alarm1(AL-1)Mode(SET) key

    Setting digit shift key

    Process-value(PV)

    Set-Value(SV)

    Control loop break alarm(LBA)/Heater break alarm(HBA)

    Alarm2(AL-2)

    Set-Value increment key

    Set-Value decrement key

    MODE

    MX9

    AT

    PVC

    REM

    OUT AL-1 AL-2 H-LBA MAN

    PV

    SV

    R

    -50~1372℃

    (-50.0~999.9℃)

    -50~1100℃

    (-50.0~999.9℃)

    -199~750℃

    (-199.9~750.0℃)

    -199~400℃

    (-199.9~400.0℃)

    -199~649℃

    (-199.9~649.0℃)

    -199~649℃(-199.9~649.0℃)

    Signal Input Temperature range

    K

    J

    E

    T

    Pt 100Ω

    (DIN)

    Pt 100Ω(JIS)

    -199~3200 (1℃ Mode)

    -1999~9999 (0.1℃ Mode)

    -199~3200 (1℃ Mode)

    -1999~9999 (0.1℃ Mode)

    1~5V

    4~20mA

    0~5V

    0~20mA

    0~1760℃

    0~1760℃

    0~1760℃

    Signal Input Temperature range

    PR(R)

    PR(B)

    PR(S)

    -50~2500℉

    (-50.0~999.9)

    -50~2000℉

    (-50.0~999.9)

    -199~1400℉

    (-199.9~999.9)

    -199.9~750℉

    (-199.9~750.0)

    -199~1200℉

    (-199.9~999.9)

    -199~1200℉(-199.9~999.9)

      Cautions  for input selection

    1) When you select input mode, you must shift jump switch inside of PCB to CORRECT position first.

    2) Afterwards select each input mode by key operation.

    Input T.C./Voltage RTD Current

    Switch position

    TC RPT

    32~3200℉

    32~3200℉

    32~3200℉

  • 8/18/2019 Hanyoung MX4

    3/9

    70

    MX-F Series 

    TEMPERATURE CONTROLLER

     T  E  M P  E  R  A  T 

     U  R  E 

     C  O N T  R  O L  L  E  R 

    4

    MODEL

     Appearance

    Externaldimension

    Input

     Accuracy

    Power supply

    Control action

    Control output

     Alarm output

     Ambient

    temperature

    Net weight

    Connection

    MX9-F MX7-F

    10

    9

    8

    7

    20

    19

    18

    17

    16

    15

    14

    13

    6

    5

    4

    3

    2

    1

    12

    11

    AL-2

    100-

    240VAC50/60Hz

    12VA

    B

    B

    A

    LBA/HBA

    COM

    TRANSMIT

    4 - 20mADC

          R      T      D

    4 - 20mA DC 12VDC

    C.T

    REM+

    -

    +

    -

    T.C

    +

    -

    H

    C

    L

    ++

    19

    18

    17

    16

    15

    14

    13

    5

    4

    3

    6

    100 240VAC

    50/60Hz

    12VA

    AL 1

         M     A     I     N

    H

    L

    C

    LBA/ 

    COM

    A

    B

    B

         T .     C

         R     T     D

    2

    1 12VDC

    4 20mADC

    7

    12

    11

    10

    9

    8

    C.T

     4 20mADC

    TRANSMIT

     VOLTAGE

    CURRENT

    +

    HBA

    +

    REM

    AL 2

    96X96mm(1/4 DIN), mounting depth:100mm 72X72mm, mounting depth:100mm

    11 Kinds of input (See input range)

    [Setting accuracy] T/C: Within±(0.3% of SV + 1 digit) or ±2℃(Whichever is larger)R.S: ±4℃ + 1 digitR.T.D: Within±(0.3% of SV + 1 digit) or ± 0.8℃(Whichever is larger)

    [Display accuracy] Same as setting accuracy.

    100 to 240V AC (Common to 50/60Hz) (Excluding power supply voltage variation)

    PID (Auto-tuning function), ON/OFF, P.PI.PD

    Relay contact: AC 250V 3A (Resistive load) 1C(NO/NC) contactSSR driving:12V DC (Constant voltage pulse) [load resistance more than 800Ω]Current: 4-20mA DC [load resistance less than 600Ω]Voltage: 0-10V DC [load resistance less than 1㏀]

    Deviation or process settingRelay contact output: AC 250V 0.5A (AL-2), 3A (AL-1)

    0 ~ 50℃(32 ~ 122℉) ※Ambient humidity:35 ~ 85% RH

    Approx 375g Approx 300g

  • 8/18/2019 Hanyoung MX4

    4/9

    71

    MX-F Series 

    TEMPERATURE CONTROLLER

      T  E  M  P  E  R  A  T  U  R  E  C  O  N  T  R  O  L  L  E  R

    4

    Relay contact:AC 250V 3A(Resistive load) 1C(NO/NC) contactSSR driving :12V DC(Constant voltage pulse)〔load resistance more than 800Ω〕Current :4-20mA DC〔load resistance less than 600Ω〕Voltage :0-10V DC〔load resistance less than 1 KΩ〕

    〔Setting accuracy〕T/C :Within±(0.3% of SV+1 digit) or±2℃(Whichever is larger)R.S :±4℃ + 1 digitR.T.D :Within±(0.3% of SV+1 digit) or±0.8℃(Whichever is larger)

    〔Display accuracy〕 Same as setting accuracy

    100 to 240V AC(Common to 50/60Hz)(Excluding power supply voltage variation)

    PID (Auto-tuning function), ON/OFF, P.PI.PD

    11 Kinds of input (See input range)

    Deviation or process settingRelay contact output:AC 250 0.5A (AL-2), 3A (AL-1)

    Deviation or process settingRelay contact output:AC 250V 3A (Resistive load)

    A

    AL-1H

    CL

    +

          A      L   -      2

          L      B      A      /      H      B      A

    C.T

    B B T.C

    RTD

    +

    +

      CURRENT

    SOLIDSTATE

    10 9 8 7

    20 18 17 16 15

    6 5

    19 14 13

    4 3 2 1

    12 11

    TRANSMIT

    4-20mA/DC

    REM

    100-240VAC

    50/60Hz

    12VA

    +

    +

    MAIN

          C      O      M   CURRENT

      VOLTATE

    H

    C

    L

    10

    9

    8

    7

    20

    19

    18

    17

    16

    15

    14

    13

    6

    5

    4

    3

    2

    1

    12

    11

    +

    LBA/HBA

    MAIN

    AL 2

    AL 1

    TRANSMIT

    4 20mA DC

    COM

    +

    C.T

    REM

          R      T      D

    B

    B

    A

    +

    T.CCURRENT

      SOLIDSTATE

    +

    100 240VAC

    50/60Hz

    12VA

    CURRENT

    VOLTAGE

    MX4-F

    1

    2

    6

    7

    3 8

    4 9

    5 10

    ALM

    MAIN   T  .       C

    +

    100 240 VAC

    50/60Hz 12VA

    3A250VAC

    3A250VAC

           T  .       C

    +

    7

    9

    10

    RTD

    B

    B

    A

    8

    4

    5

    CURRENT

    SOLIDSTATE

    +

    MX2-F MX3-F

    Approx 310g

    0~50℃(32~122℉) ※Ambient humidity : 35~85% RH

    Approx 310g Approx 235g

    48×96mm(1/8 DIN), mounting depth : 100mm   96×48mm(Horizontal), mounting depth : 100mm 48×48mm(1/16 DIN)

  • 8/18/2019 Hanyoung MX4

    5/9

    72

    MX-F Series 

    TEMPERATURE CONTROLLER

     T  E  M P  E  R  A  T 

     U  R  E 

     C  O N T  R  O L  L  E  R 

    4

    ■ Setting of constants in display

    ■ Alarm mode

    Signal onPV display Name Description Setting range Initial set

    Temp. range

    Ramp

    Proportional band

    Anti-reset windup

    Integral time

    Derivative time

    Hysteresis(in ON/OFF action)

    Proportioning cycle

    Temperature range in ramp

    Ramp(Rate) time setting

    Set when proportional controlis performed.

    Prevents overshoot and/orundershoot caused by integral

    action effect.Eliminates offset occurring inproportional control. Integralaction turns OFF with thisaction set to“O”.

    Prevents ripples by predictingoutput change therebyimproving control stability.Derivative action turns OFFwith this action set to“O”.

    Displays hysteresis Set-Valuefor main output.

    Displays manipulated outputcycle(sec.).

    -199~3200(-199.9~999.9)

    0~540 minutes

    1 to span ℃(℉)0.1~999.9 ℃(℉)

    0~100℃(℉)

    0 to 3600 sec.

    0 to 3600 sec.

    0.1~100.0

    1 to 100 sec.(0.1 to 100.0 sec.)

    -

    -

    20 ℃(℉)

    100℃(℉)

    240 sec.

    60 sec.

    1℃(℉)

    Relay contactoutput : 20 sec.Voltage pulseoutput : 2sec.

    *Automatically set by Auto-tuning

    None

    Deviation high alarm

    Deviation low alarm

    Hold function of high alarm

    Hold function of low alarm

    Band alarm

    High and low alarm

    Low alarm hold function of high/lowalarm

    High alarm hold function of high/lowalarm

    Hold function of high/low alarm

    Process high alarm

    Hold function of process high alarm

    Process low alarm

    Hold function of process low alarm

    *

    *

    *

  • 8/18/2019 Hanyoung MX4

    6/9

    73

    MX-F Series 

    TEMPERATURE CONTROLLER

      T  E  M  P  E  R  A  T  U  R  E  C  O  N  T  R  O  L  L  E  R

    4

    ■ Operation Manual

    MODE

    MODE

    (Power ON)

    Display in Ramp function

    Display in HBAfunction only

    ✽ P,A,I,D,C: No display in ON/OFF mode

    Temp. high limit

    Temp. low limit

    Output limit range:0~100%

    Manual output set (Select in SL-3 mode to display this mode)

    range:0~100%

    Remote function mode(Select inSL-3 mode to display this mode)Set 1 for operation

    3sec. 3sec.

    3sec.

    3sec.

    (PV)

    (SV)

    (Input type)   (Temp. range)

    Power supply

    MODE

    MODE

    MODE MODEMODE

    MODEMODE

    MODE

    Operates only in :1000 position.When flickers, Press to stop.Press and key simultaneously for

    3 sec. to enter

    SYSTEM SET MODE

    Display inON/OFF mode

    Note

    In case of Current and Voltageoutput, PID Auto-tuning does notoperate by Auto-tuning key. Initial values of P.I and Dare Programmed and you may usethe unit in ordinary applications. Ifyou are not satisfied with givenvalues, you can change values of Iand D slightly in normal mode bymanual adjustment.

    ■ Normal mode

  • 8/18/2019 Hanyoung MX4

    7/9

    74

    MX-F Series 

    TEMPERATURE CONTROLLER

     T  E  M P  E  R  A  T 

     U  R  E 

     C  O N T  R  O L  L  E  R 

    4

    (System mode)   (HBA mode)(Alarm mode)(Retransmission output mode)

    MODE 3sec.   MODE 3sec.   MODE 3sec.

    MODEMODEMODE

    MODE

    MODE

    Note : Press and key simultaneously for 3 sec.

    and return to initial PV/SV mode in every step.

    ※ Press key for 3 sec. in and return

    to .

    MODE

    MODE MODE

    3sec.

    MODE

    MODE

    3sec.   3sec.

    ■ Function set mode

  • 8/18/2019 Hanyoung MX4

    8/9

    75

    MX-F Series 

    TEMPERATURE CONTROLLER

      T  E  M  P  E  R  A  T  U  R  E  C  O  N  T  R  O  L  L  E  R

    4

    : Input mode

    : Input shift valuerange: within free scale range

    : Decimal point selectionrange : 0 ~ 3(0001 → 000.0 in PV mode)

    0: Indicator1: Controller0: ON/OFF1: PID

    0: Direct control action for cooling1: Reverse control action for heatingMX-F Normal type

    0: ℉1: ℃0: 0.1℃ resolution1: 1℃ resolutionNo function key (Do not modify)0: Current output1: Relay or Voltage, Pulse

    0: None1: AL-1 output → AL-1 terminal(Initial value)2: AL-1 output → AL-2 terminal3: AL-1 output → LBA/HBA terminal

    : Span of free scalerange: -199~3200 -1/1 MODE

    (-1999~9999) -1/10 MODE

    : Zero of free scalerange: -199~3200 -1/1 MODE

    (-1999~9999) -1/10 MODE

    : Alarm-1 (Refer to alarm mode)

    initial value : Deviation high alarm

    : Dead band of AL-1initial value : 1

    : Alarm-2 (Refer to alarm mode)initial value: Hold function of low alarm

    : Dead band of AL-2

    initial value : 1.0

    : Output terminal of AL-2

    : LBA/HBA function

    : Dead band of HBA(A)

    : Output terminal of LBA/HBA

    : Retransmission display

    : Span of retransmission outputrange : 0~4095 initial value :3500(Do not modify)

    : Zero of retransmission outputrange : 0~4095 initial value :500(Do not modify)

    : Remote input calibration(Do not modify)

    (None) (PV) (SV)

    (None) (LBA)  (25A HBA)(50A HBA)

    : Output terminal of AL-1

    0: Remote input function1: No remote input function0: Manual output function1: No manual output functionNo function key (Do not modify)0: Ramp function1: No ramp function

    0: None1: AL-2 output → AL-1 terminal(Initial value)2: AL-2 output → AL-2 terminal3: AL-2 output → LBA/HBA terminal

    0: None1: LBA/HBA output → AL-1 terminal2: LBA/HBA output → AL-2 terminal3: LBA/HBA output → LBA/HBA terminal

  • 8/18/2019 Hanyoung MX4

    9/9

    76

    MX-F Series 

    TEMPERATURE CONTROLLER

     T  E  M P  E  R  A  T 

     U  R  E 

     C  O N T  R  O L  L  E  R 

    4

    Ramp rate can be adjusted.

    (0~540 minutes)

    Model CT-25 Model CT-50

    Time

    Set ▶

    MODE

    MODE

    MODE

    RAMP RATE

          2      5

          2      2      9

          9

          1      3

          3      1

          3      4 .      5

          1      6

    ■ Ramp function

    ■ CT(Current Transformer)

    ■ PID Auto-Tuning (Valid in Relay and SSR output only)

    • Press the key and key at the same time. Then,

    AT indication lamp flashes to start the Auto-tuning

    function.

    • If Auto-tuning function ends, the AT indication lamp

    stops flashing automatically.

    When checking the auto-tuned value, press the key

    and conform in turn.

    • When you want Auto-tuning function to be suspended,

    press the key and key simultaneously, then the

    AT indication lamp stops flashing to release Auto-tuning

    function. In this case P.I.D and ARW values are not

    changed (Maintain the value before the Auto-tuningstarts).

    • When you want to change the SV(set-value) during Auto-

    tuning, suspend it and perform PID control using the

    values before Auto-tuning starts.

    ■ Control loop break alarm(LBA)LBA function starts to measure time from the moment

    that the PID Computed Value (Output ON time/cycle)

    become 0% or 100%, and detects the amount of Process

    Value change at each LBA setting time, and determines by

    the amount of change whether LBA is to be ON or OFF.

    • When the status at a 100% PID computed value

    continues beyond the LBA setting time, the LBA turns

    ON if the measured-value(PV) does not rise by 2℃(℉)

    or more.

    (In direct action, the above alarm turns ON if the

    measured-value does not fall by 2℃(℉) or more.

    • When the status at 0% PID computed value continuesbeyond the LBA setting time, the LBA turns ON if the

    measured-value(PV) does not fall by 2℃(℉) or more.

    ■ Remote input

    Set-value of controller can be set or changed from outside

    of the controller by direct voltage/current signal.

    But the external signal should be input continuously.

    (Auto-tuning function is not operated while the external

    signal is set)

    ■ Heater break alarm(HBA)Set-value of HBA to be set about 85% to input of CT but

    the set-value should be less in case that the ratio of

    voltage variation is high.

    If several heaters are connected in parallel, the alarm may

    be turned ON even though one circuit is broken.

    In such a case, set the value of HBA to be slightly high.

    No HBA operates at “O” setting, but HBA operates at

    “25.0”or“50.0”setting.