Air System Sizing Summary for Meeting Room - 02Project Name: Coca - Cola Plant at Bangaluru 09-22-2012 Prepared by: ANA Design Consultancy 04:22PM
Air System Information Air System Name Meeting Room - 02 Equipment Class SPLT AHU Air System Type SZCAV
Number of zones 1Floor Area 130.0 ft²Location Bangalore, India
Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads
Calculation Months Jan to DecSizing Data Calculated
Central Cooling Coil Sizing Data Total coil load 1.2 Tons Total coil load 13.9 MBH Sensible coil load 11.5 MBH Coil CFM at Nov 1600 559 CFM Max block CFM 599 CFM Sum of peak zone CFM 599 CFM Sensible heat ratio 0.832 ft²/Ton 112.4 BTU/(hr-ft²) 106.7 Water flow @ 10.0 °F rise N/A
Load occurs at Nov 1600OA DB / WB 92.8 / 79.9 °FEntering DB / WB 74.3 / 59.9 °FLeaving DB / WB 53.0 / 50.2 °FCoil ADP 47.3 °FBypass Factor 0.210Resulting RH 43 %Design supply temp. 56.0 °FZone T-stat Check 1 of 1 OKMax zone temperature deviation 0.0 °F
Supply Fan Sizing Data Actual max CFM 599 CFM Standard CFM 537 CFM Actual max CFM/ft² 4.61 CFM/ft²
Fan motor BHP n/aFan motor kW 0.51 kW
Outdoor Ventilation Air Data Design airflow CFM 28 CFM CFM/ft² 0.21 CFM/ft²
CFM/person 6.95 CFM/person
Hourly Analysis Program v4.51 Page 1 of 4
System Psychrometrics for Meeting Room - 02Project Name: Coca - Cola Plant at Bangaluru 09-22-2012 Prepared by: ANA Design Consultancy 04:22PM
November DESIGN COOLING DAY, 1600
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 92.8 0.02173 26 400 486 1480Vent - Return Mixing Outlet 74.3 0.00894 559 1636 - -Central Cooling Coil Outlet 53.0 0.00796 559 1636 11550 2327Supply Fan Outlet 56.0 0.00796 559 1636 1622 -Cold Supply Duct Outlet 56.0 0.00796 559 1636 - -Zone Air - 73.0 0.00832 559 1696 9193 845Return Plenum Outlet 73.5 0.00832 559 1696 266 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft
TABLE 2: ZONE DATA
Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)Zone 1 8980 Cooling 9193 73.0 559 1696 0 0
Hourly Analysis Program v4.51 Page 2 of 4
System Psychrometrics for Meeting Room - 02Project Name: Coca - Cola Plant at Bangaluru 09-22-2012 Prepared by: ANA Design Consultancy 04:22PM
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible LatentTemp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)Ventilation Air Inlet 59.0 0.00588 0 400 0 0Vent - Return Mixing Outlet 0.0 0.00000 0 0 - -Central Cooling Coil Outlet 0.0 0.00000 0 0 0 0Supply Fan Outlet 0.0 0.00000 0 0 0 -Zone Air - 0.0 0.00000 0 0 0 0Return Plenum Outlet 79.1 0.00000 0 0 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft
TABLE 2: ZONE DATA
Zone Terminal ZoneSensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil UnitZone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)Zone 1 -43 Deadband 0 59.2 0 0 0 0
Hourly Analysis Program v4.51 Page 3 of 4
Psychrometric Analysis for Meeting Room - 02Project Name: Coca - Cola Plant at Bangaluru 09-22-2012 Prepared by: ANA Design Consultancy 04:22PM
1. Outdoor Air 2. Mixed Air 3. Central Cooling Coil Outlet 4. Supply Fan Outlet 5. Room Air 6. Return Plenum Outlet 1
23 4 5
6
0.0000.0020.0040.0060.0080.0100.0120.0140.0160.0180.0200.0220.024
30 40 50 60 70 80 90 100
Location: Bangalore, IndiaAltitude: 3021.0 ft.Data for: November DESIGN COOLING DAY, 1600
Specific H
umidity ( lb/lb )
Temperature ( °F )
Hourly Analysis Program v4.51 Page 4 of 4