high expansion foam systems 1970 handbook/nfpa 11a-1970.pdf · i ia-2 high expansion foam systems...

36
NFPA No. llA HIGH EXPANSION FOAM SYSTEMS 1970 Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Upload: others

Post on 23-Jul-2020

16 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

NFPA No.

l l A HIGH EXPANSION F O A M SYSTEMS 1970

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 2: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

Off ic ia l N F P A D e f i n i t i o n s

Adopted Jan. 23, 1964: 1Revised Dee. ~J, 1969. Where varianc~,s to these definitions are found, efforts to eliminate such conflicts are in process.

SItALL is i n t ended to ind ica te r equ i r emen t s .

SIIOULD is in t ended to indica te r eeonunenda t ions or t h a t which is adv i sed bu t no t required.

APPROVED m e a n s accep tab le to the a u t h o r i t y h a v i n g jurisdict ion. T h e Nat iona l Fire Pro tec t ion Associat ion does not approve , inspect or cer t i fy an y instal la t ions, procedures, e q u i p m e n t or ma te r i a l s nor does it a pp rove or eva lua t e tes t ing labora- tories. In de t e rm i n i ng the accep tab i l i ty of ins ta l la t ions or procedures, e q u i p m e n t or mater ia ls , the a u t h o r i t y h a v i n g jur isdict ion m a y base aeeep tanee on compl iance wi th N F P A or o ther app rop r i a t e s t andards . In the absence of sueh s tandards , said a u t h o r i t y m a y require evidence of p roper instal la t ion, p rocedure or use. T h e au tho r iW h a v i n g jurisdict ion m a y also refer to the l ist ings or label ing praet iees of na t iona l ly reeognized test ing laborator ies ,* i.e., l abora tor ies qualified an d equipped to conduc t the necessary tests, in a posi t ion to de t e rmine compl iance with ap- p ropr ia te s t anda rds for the cu r ren t p roduc t ion of l isted i tems, an d the sa t i s fac tory pe r fo rmance of sueh e q u i p m e n t or ma te r i a l s in ac tua l usage.

*Among the laboratories nationally recognized by the authorities havin~ jurisdiction in the United ~tates and Canada are the Underwriters' Laboratories, Inc., the Factory Mutual Research Corp., the Ameriean Gas Association Laboratories, the Underwriters' Laboratories of Canada, tile Canadian Standards A~soeiation Testing Laboratories, and the Canadian Gas Association Approvals Divibion.

LIST~:D: E q u i p m e n t or ma te r i a l s inc luded in a list publ ished by a na t iona l ly recognized tes t ing labora to i 'y t h a t ma in t a in s periodic inspect ion of p roduc t ion of l isted e q u i p m e n t or mater ia ls , and whose l is t ing s ta tes e i ther t h a t the e q u i p m e n t or mate r ia l mee t s na t iona l ly recognized s t a nda rds or has been tes ted and found sui table for use in a specified m a n n e r .

LABELED : E q u i p m e n t or ma te r i a l s to whieh has been a t t a e h e d a label, symbol or o ther ident i fy ing m a r k of a na t iona l ly recognized tes t ing l a b o r a t o r y t h a t ma in - tains periodic inspect ion of product ion of labeled e q u i p m e n t or mater ia l s , and by whose label ing is ind ica ted eompl ianee wi th na t iona l ly recognized s t a n d a r d s or tes ts to de t e rmine sui table usage in a specified ma nne r .

AUTHORITY HAVING JURISDICTION: T h e organizat ion, office or ind iv idua l re- sponsible for " a p p r o v i n g " equ ipmen t , an instal lat ion, or a procedure .

S t a t e m e n t o n N F P A P r o c e d u r e s This material has been developed in the interest of safety to life and property under the

published procedures of the National Fire Protection Association. These proeedures are de- signed to assure the appointment of technically eompetent Comnfittee~ havin~ balanced representation from those vitally interested and active in the areas with which the Committees are concerned. These proeedures provide that all Committee rec.ommendations shall be pub- lished prior to action on them by the Association itself and that following this publication these recommendations ~hall he presented for adoption to the Annual Meeting of the Association wtmre anyone In attendance, member or noL may present his views. While these procedures asaure the tfighest degree of care neither the National Fire Proteetion Assoeiation, its members, nor tho~e participating in its activities aeeepts any liability resulting from eompliance or non- compliance with the provisions given herein, for any restrictions imposed on materials or processes, or tot the eompletcness of t[te text.

C o p y r i g h t a n d R e p u b l i s h i n g R i g h t s

This publ iea t ion is copyr igh ted © by the Nat iona l Fire Pro tec t ion Asso- ciation. Permiss ion is g r a n t e d to republ ish in full the ma te r i a l herein in laws, ordinanees, regulat ions, a d m i n i s t r a t i v e orders or s imilar d o c u m e n t s issued by public author i t ies . .MI o thers desiring permission to reproduce this ma te r i a l in whole or in pa r t shall consul t the Nat iona l Fire Pro tec t ion Associat ion.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 3: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

IIA-I

Standard for

High Expansion Foam Systems

(Expansion Ratios from 100:1 to 1000:1)

NFPA No. 1 1 A ~ 1 9 7 0

1970 Edition of No. 11A

This Standard was developed by the NFPA Subcommittee on High Expansion Foam Systems. It was approved by the Commit- tee on Foam and submitted as a tentative standard to the members at the 1968 Annual Meeting held in Atlanta. During the year 1968 several comments and suggested amendments were received. The Committee on Foam considered all recommendations and included many of them in a revised edition. The Revised Tentative Standard NFPA No. 11A-TR, was adopted at the 1969 NFPA Annual Meeting in New York City. After one more year of tentative status the Standard was officially adopted without change at the NFPA Annual Meeting in Toronto, Ontario in May 1970.

Origin and Development of No. 11A-~I

Work on this Standard commenced in 1964. Several drafts were prepared by the Subcommittee and processed at committee meet- ings held in subsequent years. The subcommittee's draft was ap- proved by the Foam Committee at its New York meeting in December of 1967. Thereafter, the material was published in the 1968 NFPA Technical Gommittee Reports for study and evalua- tion by the NFPA membership and others interested. I t was ap- proved as a Tentative Standard at the 1968 Annual Meeting.

During 1968 it was further revised and was submitted and adopted as a revised tentative standard ~t the 1969 Annual Meet- ing. After one more year as a tentative standard, it was officially adopted without revision at the 1970 Annual Meeting.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 4: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

I IA-2 HIGH EXPANSION FOAM SYSTEMS

Committee on Foam

Thomas L. ~ C ~ ,

Eeso Resem'eh and Eng inee r ing Co., P.O. Box 101, F lorhgm Park , N.J. 079~ (rep. American Pe t ro leum Ins t i tu te )

]g. L. ~ave, S e c r e t ,

Consultant, Mater ia ls Division, U. S. Naval Research Laboratory, Code 6004, 4555 Overlook Ave., S.W. Washington, D.C. 2 ( ~ 0

Thezon Arms, Ohio Inspect ion Bu- reau

C. F. Ave~dl, National Automat ic Spr inkler & Fi re Control Assn.

Ro A. ~a rn i sh Brown, Nat ional Paint , & Lacquer Assn.

B~tt. Chief Thomas J . Burke, F i r e Marshals A ~ n . of Nor th America.

La p ~ n Campbell, Nat ional Automat ie k ler & F i re Control Assn.

J . B. Coreoran, Edison Electr ic In- s t i tu te

K. G. ] h s e y , F i re ~.xt lngulsher ~wa,- ufacturcrs Ins t i t u t e o! Canads

P. E. Johnson, Fac tory Mutual Re- search COrp.

88,muel I . K~lkstein, F i re Equipment Manufacturers Assn.

Ar thur I~ga~linos, New England In- suranec Ra t ing A ~ n .

C. H. ] [J~ l s sy , E ~ I ~ , N. Y. N o r ~ n ]g. Loelnvoo4, American

Pet ro leum Ins t i t u t e D. N. Meldrum, Nat ional Foam Sys-

tem, Inc. James O'Beg~n, O 'Regan-Gagl iardo

Associates L. E. BAvkind, The Mearl Corp. H. 8. Robinson, 011 Insurance Assn. B. M. L. Bussell , Fac tory Inmuranee

Assn. lw. ]g. 8uehomeL Underwri ters ' Lab-

oratorie~, Inc. D. H. WsT, Union Carbide Corp. I m Wilder , U. S. N&vs~I Applied Bei-

ence Laboratory.

Alternates .

A. Curl, F i re Ex t ingu i she r Mmmzfac- tu re r s Ins t i t u t e o f Canada. (Alter- nate to K. G. Easey.)

H a r r y Lein, F i re Equ ipment ~ n u - fac turer Assn. (Alternate to Samuel I. Kalkstein.)

H. B. P e n n o n , U. S. Naval Research Laboratory. (Al ternate t o It . L. Tuve. )

B. E. 8herwood, 0 i l Inmzrance Assn. (Al ternate to H. S. Robinson.)

W. J. 8wingler , l~actorY Insurance Assn. (Alternate to R. M. L. Rus- sell. )

Sco~: The instal lat ion, maintenance and use of foam sys tems for fire protection, inc luding foam hose streams.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 5: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

CONTENTS l l A - 3

T a b l e o f C o n t e n t s

Page

Foreword ................................................................................................ I IA-5 Introduction .......................................................................................... I I A - 7

1. Pu rpose ........................................................................................ I I A - 7 2. Scope ............................................................................................ U A - 7 5. Defini t ions .................................................................................. I I A - 7

Chapter 1. Gene ra l Information and R e q u i r e m e n t s ........................ I 1A-8

11. Genera l I n f o r m a t i o n .................................................................. I I A - 8 I11. Scope ............................................................................ U A - 8 112. M e c h a n i s m s of E x t i n g u i s h m e n t .................................. I IA-8 113. Use a n d Limi ta t ions .................................................... I I A - 8 114. Types of Systems .......................................................... 11A-8 115. Systems Pro tec t ing O n e or M o r e Haza rds ................ l l A - 9

12. Personnel Safety ........................................................................ I I A - 9 121. Haza rds to Personne l .................................................. I 1A-9 122. Electr ical Clearances .................................................... l l A - 9

15. Specifications, P lans a n d Approval .......................................... I I A - 9 131. P u r c h a s i n g Specificat ions ............................................ I I A - 9 132. P lans .............................................................................. I l A - 1 0 133. Approva l of Plans ........................................................ I 1A-10 134. Approva l of Ins ta l la t ions ............................................ 1,1A-10

14. Ope ra t i on a n d Cont ro l of Systems ............................................ I IA-11 141. Me thods of Ac tua t ion .................................................. I IA-11 142. De tec t ion of Fires ........................................................ I I A - I 1 142. O p e r a t i n g Devices ........................................................ I I A - 1 2 144. Supervis ion .................................................................... 11A-13 145. A la rms a n d Ind ica tors ................................................ I1A-13

15. Water , F o a m Concen t r a t e a n d Air Supply .............................. l l A - 1 3 151. W a t e r Q u a n t i t y ............................................................ I I A - 1 3 152. W a t e r Qua l i t y .............................................................. I I A - 1 3 153. W a t e r Storage .............................................................. I .IA-13 154. F o a m C o n c e n t r a t e Q u a n t i t y ........................................ l l A - 1 3 155. F o a m Conc en t r a t e Qua l i t y .......................................... I 1A-14 156. F o a m Concen t r a t e Reserve Supply ............................ I 1A-14 157. F o a m Conc en t r a t e Storage .......................................... I I A - 1 4 158. F o a m Concen t r a t e Storage T a n k ................................ I I A - 1 4 159. Ai r Supp ly .................................................................... 11A-14

16. F o a m Gene ra t i ng A p p a r a t u s Locat ion ...................................... I I A - 1 4 161. F o a m Gene ra t i ng A p p a r a t u s Loca t ion ........................ I I A - 1 4 162. Pro tec t ion Aga ins t Exposure ...................................... I 1A-14

17. Dis t r ibut ion Systems .................................................................. I I A - 1 5 171. Pipe a n d Fi t t ings .......................................................... I I A - 1 5 172. A r r a n g e m e n t and Ins ta l la t ion of Pip ing and Fi t t ings l l A - 1 5 173. Valves ............................................................................ I I A - 1 5 174. D u c t s .............................................................................. l l A - 1 5

18. M a i n t e n a n c e and Ins t ruc t ions .................................................. l l A - 1 6 181. Inspec t ion a n d Tes ts .................................................... I 1A-16 182. M a i n t e n a n c e .................................................................. l l A - 1 6 183. Ins t ruc t ions .................................................................... I I A - 1 6

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 6: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

I1A-4 H I G H E X P A N S I O N FOAM S Y S T E M S

Chap te r 2. Tota l Flooding Systems .................................................... I I A- 17

21. General Informat ion .................................................................. 11A-17 211. Descript ion .................................................................... I IA-17 212. Uses .............................................................................. I IA-17 213. General Requirements ................................................ I1A-17

22. Enclosure Specifications ............................................................ I I A- 17 221. Leakage and Ventilat ion .............................................. I IA-17

23. Foam Requirements .................................................................... I I A- 18 231. General .......................................................................... l lA - 18 232. Foam Dep th .................................................................. l lA - 18 233. Submergence Volume .................................................. I I A- 18 234. Submergence T'Lme ...................................................... I I A - 1 8 235. Rate of Discharge ........................................................ IIA-19 236. Quan t i t y ........................................................................ l lA - 20

24. Maintenance of Submergence Volume .................................... I IA-21 241. Method .......................................................................... I1A-21

25. Overhaul ...................................................................................... l lA-21

26. Distr ibut ion ................................................................................ I IA-21

Chapter $. Local Applicat ion Systems .............................................. I IA-21

31. General In format ion .................................................................. I1A-21 311. Descript ion .................................................................... I1A-21 312. Uses ................................................................................ I IA-21 313. General Requirements .................................................. 11A-22

32. Hazard Specifications ................................................................ I1A-22 321. Extent of Hazard .......................................................... 1 IA-22 322. Location of Hazard ...................................................... 11A-22

33. Foam Requirements .................................................................... 11A-22 331. General .......................................................................... 11A-22 332. Quan t i ty ........................................................................ 11A-22

34. Method ........................................................................................ 11A-22

Chap te r 4. Portable Foam Genera t ing Devices ................................ 11A-23

41. General In format ion .................................................................. 11A-23 411. Descript ion .................................................................... 11A-23 412. General Requirements .................................................. 11A-23

42. Hazard Specifications .................................................................. !1A-23 43. Location and Spacing ................................................................ 11A-23

431. Location ........................................................................ 11A-23

44. Foam Requirements .................................................................... 11A-23 441. Rate and Dura t ion of Discharge ................................ 11A-23 442. Simultaneous Use of Portable Foam Generat ing De-

vices ................................................................................ 11A-24

45. Equ ipmen t Specifications .......................................................... 11A-24 451. Hose .............................................................................. 11A-24 452. Electric Power Supply and Connections .................... 11A-24

46. Tra in ing ...................................................................................... 1 IA-24

Appendix ................................................................................................ 11A-25

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 7: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

FOREWORD 1 IA-5

Standard for

High Expansion Foam Systems

(Expansion Ratios From 100:1 to 1000:1) NFPA No. 11A~1970

FOREWORD

High expansion foam is a relatively new agent for control and extinguishment of Class A and Class B fires and is particularly suited as a flooding agent for use in confined spaces. The develop- ment of the use of high expansion foams for fire-fighting purposes started with the work of the Safety in Mines Research Establish- ment of Buxtou, England, upon the difficult problem of fires in coal mines. It was found that by expanding an aqueous surface active agent solution to a semi-stable foam of about 1000 times the volume of the original solution, it was possible to force the foam down relatively long corridors thus providing a means for transporting water to a fire inaccessible to ordinary hose streams.

This work has led to the development of specialized high ex- pansion foam generating equipment for fighting fires in mines, for application in municipal and industrial fire-fighting, and for the protection of special hazard occupancies.

High expansion foam is an aggregation of bubbles mechanically generated by the passage of air or other gases through a net, screen or other porous medium which is wetted by an aqueous solution of surface active foaming agents. Under proper conditions, fire fighting foams of expansions from 100:1 to 1000:1 can be generated. Such foams provide a unique agent for transporting water to inaccessible places, for total flooding of confined spaces, and for volumetric displacement of vapor, heat and smoke. Tests have shown that under certain circumstances high expansion foam when used in conjunction with water sprinklers will provide more positive con- trol and extinguishment than either extinguishment system by it- self. High-piled storage of rolled paper stock is an example. Op- t imum efficiency in any one type of hazard is dependent to some extent on the rate of application and also the foam expansion and stability.

High expansion foam is particularly suited for indoor fires in confined spaces. Its use outdoors may be limited because of the

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 8: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

l lA-6 H I G H EXPANSION FOAM SYSTEMS

effects of weather. f i r e s :

High expansion foam has several effects on

1. When generated in sufficient volume, it can prevent air, neces- sary for continued combustion, from reaching the fire.

2. When forced into the heat of a fire the water in the foam is converted to steam, reducing the oxygen concentration by dilu- tion of the air. For example, the water in a foam having an expansion ratio of 1000:1 can provide enough steam to reduce the oxygen concentration of the resultant air-steam mix to about 7.5 per cent by volume.

3. The conversion of the water to steam absorbs heat from the burning fuel. Any hot object exposed to the foam will con- tinue the process of breaking the foam, converting the water to steam, and of being cooled.

4. Because of its relatively low surface tension, solution from the foam, which is not converted to steam, will tend to penetrate Class A materials. However, deep-seated fires may require overhaul.

5. When accumulated in depth, high expansion foam can provide an insulating barrier for protection of exposed materials or structures not involved in a fire and can thus prevent fire spread.

Class A fires are controlled when the foam completely covers the fire and burning material. If the foam is sufficiently wet and is maintained long enough, the fire may be extinguished.

Class B fires involving high flash point liquids can be extin- guished when the surface is cooled below the flash point. Class B fires of low flash point liquids can be extinguished when a foam blanket of sufficient depth is established over the liquid surface.

This Standard is based on test data and design experience so far developed for use of high expansion foam. The intent of this standard is to indicate general rules applicable to any system. The limited field experience of approved systems makes it difficult to prepare specific recommendations covering the many potential uses. This Standard is issued to outline some of the factors which should be given consideration in judging the acceptability of specific installations.

Asterisks (*) indicate additional information in Appendix in correspondingly numbered paragraphs.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 9: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

XNTRODUCTXON 1 IA-7

INTRODUCTION

1. Purpose

This Standard is prepared for use and guidance of those charged with the purchasing, designing, installing, testing, inspecting, ap- proving, listing, operating or maintaining high expansion foam systems, in order that such equipment will function as intended throughout its life.

2. Scope

This Standard includes minimum requirements for high expan- sion foam systems.

Only those skilled in this field are competent to design and in- stall this equipment. It may be necessary for many of those charged with the purchasing, inspecting, testing, approving, operating, and maintaining this equipment to consult with an experienced and competent fire protection engineer in order to effectively discharge their respective duties.

3. Definitions. For purposes of clarification, the following gen- eral terms used with special technical meanings, in this Standard, are defined:

AUTHORITY HAVINO JURISDICTION is usually the purchaser or the competent engineer or organization appointed by him to interpret and make decisions as set forth in this Standard. Where insurance is involved, the inspection department representing the insurance carrier generally becomes the authority having jurisdiction. In some cases, civil or military authorities may have final jurisdiction.

HIOH EXPANSION FOAM is an aggregation of bubbles resulting from the mechanical expansion of a foam solution by air or other gases with a foam-to-solution volume ratio of 100:1 to approxi- mately 1000:1 (see Section A-143).

FOAM CONCZN~aATB is a concentrated liquid foaming agent as received from the manufacturer.

FOAM SOLUTION is water into which foam concentrate has been introduced in the proper proportion.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 10: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

I1A-8 H I G H E X P A N S I O N FOAM S Y S T E M S

CHAPTER 1. GENERAL INFORMATION AND REQUIREMENTS

11. General Information

111. Scope. Chapter 1 contains general information, and file design and installation requirements for features that are generally common to all high expansion foam systems.

112. Mechanisms of Extinguishment. High expansion foam extinguishes fire by reducing the concentration of oxygen at the seat of the fire, by cooling, by halting convection, and by excluding additional air from the fire.

113. Use and Limitations. While high expansion foam is find- ing application for a broad range of fire fighting problems, this standard is presently limited to considering specific types of hazards.

1131. Some important types of hazards that high expansion foam systems may satisfactorily protect include:

1. Ordinary combustibles 2. Flammable liquids 3. Combinations of each

NOTE: Under certain circumstances it may be possible to utilize high expansion foam systems at fires involving flammable liquids o r gases issuing under pressure, but no general recommendations can be m a d e in this Standard due to the infinite variety of particular situations which can be encountered in actual practice.

1132. High expansion foam systems should not be used on fires in the following hazards unless competent evaluation, which may include tests, indicates acceptability:

1. Chemicals, such as cellulose nitrate, which release sufficient oxygen or other oxidizing agents to sustain combustion.

2. Energized unenclosed electrical equipment (see Sub-Section 1215.)

3. Water-reactive metals such as sodium, potassium, NaK. 4. Hazardous water-reactive materials, such as triethylaluminum

and phosphorous pentoxide.

114. Types of Systems. The types of systems recognized in this Standard include:

Total Flooding Systems Local Application Systems Portable Foam Generating Devices

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 11: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

GENERAL INFORMATION I I A - 9

115. Systems Protecting One or More Hazards. Systems may be used to protect one or more hazards or groups of hazards using the same supply of foam concentrate and water, except as provided in Sub-Section 1151.

1151. Where, in the opinion of the authority having juris- diction, two or more hazards may be simultaneously involved in fire by reason of their proximity, each hazard shall be protected with an individual system or the system shall be arranged to dis- charge on all potentially involved hazards simultaneously.

12. Personnd Safety

121. Hazards to Personnel: The discharge of large amounts of high expansion foam may inundate personnel, blocking vision, making hearing difficult, and creating some discomfort in breath- ing. This breathing discomfort will increase with a reduction in expansion ra t io of the foam and also under the effect of sprinkler discharge.

1211. Personnel working in a hazard area and with no respon- sibility for fire fighting should be instructed to immediately vacate the area in the event of fire, if possible. If personnel are unable to vacate and are trapped so that their lives are endangered by smoke

.or heat, they may.enter the foam. Instructions should be given to move the hand over the nose and mouth to minimize discomfort in breathing within the foam.

1212. Where possible the relative location of foam discharge points to building exits shall be arranged to facilitate evacuation of personnel.

1213. To re-enter a foam-filled building, a coarse water spray should be used to cut a path in the foam. Personnel should not enter the foam. The foam is opaque, and it is impossible to see when one is submerged. I t is dangerous to enter a building in which there was a fire if one cannot see.

1214. CAU~ON. A canister type gas mask shall not be worn in the foam. The chemicals of the canister will react with the water of the foam and cause suffocation. If emergency re-entry is essential, self-contained breathing apparatus shall be used in con- junction with a life line.

1215. Unenclosed electrical apparatus shall be de-energized upon system actuation unless by competent evaluation it has been deemed unnecessary.

"122. Electrical Clearances. All foam system components such as piping, duct work, and generators, shall be located so as to

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 12: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

IIA-10 H I G H E X P A N S I O N FOAM S Y S T E M S

maintain standard clearances from live electrical parts in the oc- cupancy (see Appendix for a table of clearances).

13. Specifications, Plans and Approval 131. Purchasing Specifications. Specifications for high expan-

sion foam systems shall be drawn up with care under the super- vision of a competent engineer, and with the advice of the authority having jurisdiction. To ensure a satisfactory system, the following items shall be in the specifications.

1311. The specifications shall designate the authority having jurisdiction and indicate whether submittal of plans is required.

1312. The specifications shall state that the installation shall conform to this Standard and meet the approval of the authority having jurisdiction.

1313. The specifications shall include the specific tests that may be required to meet the approval of the authority having jurisdiction, and indicate how cost of testing is to be borne.

132. Plans. Where plans are required, their preparation shall be entrusted only to fully experienced and responsible persons.

1321. These plans shall be drawn to an indicated scale or be suitably dimensioned, and shall be made so that they can be easily reproduced.

1322. These plans shall contain sufficient detail of the hazard to enable the authority having jurisdiction to evaluate the effective- ness of the system. The details on the hazard shall include the specific materials involved, the location and arrangement and the immediate exposure to the hazard. The detail on the system shall include sufficient information and calculations on the required amount of foam concentrate; water requirements; hydraulic cal- culations on the size, length and arrangement of connected piping and hose; and the size and location of foam generators so that the adequacy of the quantity, flow rate and distribution of the high ex- pansion foam generated can be determined. Detailed information shall be submitted pertaining to the location and function of de- tection devices, operating devices, auxiliary equipment including stand-by power and electrical circuitry, if used. Sufficient informa- tion shall be indicated to identify properly the apparatus and de- vices used. Any special features shall be adequately explained.

No-rE: See Chapter 7 of NFPA No. 13 for hydraulic calculation proce- dures.

133. Approval of Plans. Where plans are required, they shall

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 13: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

0ENERAL INFORMATION llA-11

be submitted to the authority having jurisdiction for approval be- fore work starts.

1331. Where field conditions necessitate any significant change from the approved plan, corrected "as installed" plans shall be supplied for approval to the authority having jurisdiction.

134. Approval of Installations. The completed system shall be tested by qualified personnel to meet the approval of the authori- ty having jurisdiction. These tests shall be adequate to determine that the system has been properly installed, and will function as intended. Only listed or approved equipment and devices shall be used in these systems.

1341. Such tests should include a discharge of foam if possible. This foam should be checked visually for desired quality. If actual discharge is not permitted, the supplier or installer should check air flow and liquid flow in a manner satisfactory to authority having jurisdiction. All piping up to each foam generator shall be sub- jected to a 2-hour hydrostatic pressure test at 200 psi or 50 psi in excess of the maximum pressure anticipated, whichever is greater, in general conformity with the NFPA Standard for the Installation of Sprinkler Systems (No. 13). Operating instructions provided by the supplier and the proper identification of devices shall be checked.

14. Operation and Control of Systems

141. Methods of Actuation. Systems shall be classified as manual or automatic in accordance with the method of actuation. An automatic system is one which is actuated by automatic detec- tion equipment. Such systems also shall have means for manual actuation.

142. Detection of Fires. Fires or conditions likely to produce fire may be detected by human senses or by automatic means.

1421. Automatic detection shall be used except when other- wise approved by the authority having jurisdiction.

1422. Automatic detection shall be by listed or approved method or devices capable of detecting and indicating heat, smoke, flame, combustible vapors, or any abnormal condition in the hazard, such as process trouble likely to produce fire.

1423. An adequate and reliable source of energy shall be used in detection systems. The need for an alternate power supply shall be determined by the authority having jurisdiction.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 14: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

l lA-12 H I G H E X P A N S I O N FOAM S Y S T E M S

"143. Operating Devices. Operating devices include foam generators, valves, proportioners, eductors, discharge controls, and shutdown equipment.

1431. Operation shall be controlled by listed or approved mechanical, electrical, hydraulic or pneumatic means. An ade- quate and reliable source of energy shall be used. The need for an alternate power supply shall be determined by the authority having jurisdiction.

1432. All operating devices shall be suitable for the service they will encounter, and shall not be readily rendered inoperative or susceptible to accidental operation. Provision shall be made to protect piping normally filled with liquid from freezing.

1433. All devices shall be located, installed, or suitably pro- tected so that they are not subject to mechanical, chemical, climatic or other conditions that will render them inoperative.

1434. Manual controls for actuation and shutdown shall be located so as to be conveniently and easily accessible at all times including the time of fire and system operation. Remote control stations for manual actuation may be required where the area is large, egress difficult or when required by the authority having jurisdiction. Manual controls for actuation shall operate the sys- tem to the same extent as the automatic control.

1435. All automatically operated equipment controlling the generation and distribution of foam shall be provided with ap- proved independent means for emergency manual operation. If the means for manual actuation of the system required in Section 141 provides approved positive operation independent of the automatic actuation, it may be used as the emergency means. The emergency means, preferably mechanical, shall be easily accessible and located close to the equipment controlled. If possible, the system should be designed so that complete emergency actuation can be accom- plished from one location.

1436. All required door and window closers, vent openers, and electrical equipment shutdown devices shall be considered in- tegral parts of the system and shall function with the system opera- tion.

1437. All manual operating devices shall be identified as to the hazards they protect.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 15: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

GENERAL INFORMATION l l A - 1 3

144. Supervision. Supervision of automatic detection and actuation equipment is advisable where the possible loss may be high because of any delay of actuation and/or where the detection or control systems are so extensive and complex that they cannot be readily checked by visual or other inspection. Where supervision is provided it should be so arranged that there will be immediate indication of failure. The extent and type of supervision shall be approved by the authority having jurisdiction.

145. Alarms and Indicators. Alarms and/or indicators shall be installed to indicate the operation of the system, alert personnel and indicate failure of any sprinkler device or equipment. They may be audible or visual. Such devices shall be of such a type and should be provided in such numbers and such locations as are necessary to accomplish satisfactorily their purpose subject to ap- proval of the authority having jurisdiction.

1451. An alarm or indicator shall be provided to show that the system has operated, personnel response may be needed, and the system shall be reserviced.

1452. Alarms should be provided to give ample warning of discharge where hazard to personnel may exist.

1453. Alarms indicating failure of supervised devices or equipment shall give prompt and positive indication of any failure and shall be distinctive from alarms indicating operation or hazard- ous conditions.

15. Water, Foam Concentrate and Air Supply.

151. Water Quantity. Water shall be available in sufficient quantity and pressure to supply the maximum number of high expansion foam generators likely to operate simultaneously in addi- tion to the demands of other fire protection equipment.

152. Water Quality. Consideration should be given to the suitability of the water for production of high expansion foam. The presence of corrosion inhibitors, antifreeze agents, marine growths, oil, or other contaminants may result in reduction of foam volume or stability. If the quality of the water is questionable, the manu- facturer of the foam equipment shall be consulted.

153. Water Storage. Water supply shall be protected against freezing.

154. Foam Concentrate Quantity. The amount of foam con- centrate in the system shall be at least sufficient for the largest

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 16: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

l lA-14 H I G H E X P A N S I O N FOAM S Y S T E M S

single hazard protected or a group of hazards which are to be pro- tected simultaneously (see Section 236 and 332).

155. Foam Concentrate Quality. The foam concentrate sup- plied with the system shall be that listed for use with the equip- ment. The performance of the system is dependent upon the com- position of the foam concentrate as well as other factors. The quality of the concentrate for proper performance under the instal- lation requirements of this Standard shall be determined by suit- able tests. One such suitable test based on fire performance, is de- scribed in A-165.

156. Foam Concentrate Reserve Supply. Sufficient foam con- centrate should be kept on hand for at least one complete recharge of the system based on desired requirements. This reserve supply shall be stored in separate tanks, compartments, original shipping containers or by other approved methods. To prevent accidental use and depletion of this reserve supply, it shall be available to the system only by intentional manual operation.

157. Foam Concentrate Storage. In-service and reserve sup- plies of foam concentrate should be stored where the temperature is maintained between 35°F and 110°F, or within such other tem- perature range for which the concentrate has been listed. The reserve supply containers should be kept tightly closed in a clean dry area to prevent contamination or deterioration.

158. Foam Concentrate Storage Tank. The tank shall be of corrosion-resisting materials and construction compatible with the foam concentrate. Consult the foam equipment manufacturer.

159. Air Supply. Air from outside the hazard area shall be used for foam generation unless the calculated foam generation rate using inside air is increased to compensate for foam loss be- cause of heat, smoke, and chemical effects during a fire. The degree of loss from such effects shall be determined by test.

1591. Vents shall be located to avoid recirculation of com- bustion products into the air inlets of the foam generators.

16. Foam Generating Apparatus Location.

161. Foam Generating Apparatus Location. Accessibility for Inspection and Maintenance. Foam generating apparatus shall be so located and arranged that inspection, testing, recharging, and other maintenance is facilitated and interruption to protection is held to a minimum.

162. Protection Against Exposure. Foam generating equip-

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 17: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

OENERAL INFORMATION tlA-15

ment should be located as near as possible to the hazard or hazards it protects, but not where it will be unduly exposed to a fire or explosion. Foam generators installed inside the hazard area shall be constructed or protected against fire exposure. Such protection may be by insulation, fire retardant paint, water spray, or sprin- klers, etc. In certain applications additional generators may be substituted for fire exposure protection with the approval of the authority having jurisdiction.

17. Distribution Systems

171. Pipe and Fittings. The piping and fittings in continuous contact with foam concentrate shall be of corrosion-resisting mate- rials compatible with the foam concentrate used. The remainder of the piping and fittings should be standard weight (Schedule 40) black or galvanized steel pipe and standard weight black or gal-

vanized steel, ductile, or malleable iron fittings. Consideration should be given to possible galvanic effects when dissimilar metals are joined, especially in piping which carries foam concentrate.

172. Arrangement and Installation of Piping and Fittings. Piping shall be installed in accordance with practices outlined in NFPA No. 13.

1721. All piping systems shall be designed using hydraulic calculations to assume the desired rate of flow at the foam genera- tors. Care shall be taken to avoid possible restrictions due to foreign matter, faulty fabrication, and improper installation.

1722. A listed strainer shall be provided in the water line up- stream of the water valve suitable for use with the proportloner and foam generator. Supplemental strainers may be used as recom- mended by the foam equipment manufacturer.

173. Valves. All valves shall be suitable for the intended use, particularly in regard to flow capacity and operation. Valves shall be of a listed type or deemed suitable for such use as a part of the system.

1731. Valves shall not be easily subject to mechanical, chemi- cal, or other damage.

174. Ducts. Foam distribution and air inlet ducts shall be designed, located, installed and suitably protected so that they are not subject to undue mechanical, chemical or other damage.

1741. Duct closures such as selector valves, gates, or doors shall be of the quick-opening type, allowing free passage of the foam. When located where they may be subjected to fire or heat

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 18: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

IIA-16 H I G H EXP ANS ION FOAM S YS TEM S

exposure, either inside or outside the area to be protected, special care should be taken to ensure positive operation.

1742. Ducts shall be designed and installed so that undue turbulence is avoided and the foam discharge rate is in accord with the design requirements. Bends and excessive lengths should be avoided.

18. Maintenance and Instructions.

181. Inspection and Tests. At least annually, all high expan- sion foam systems shall be thoroughly inspected and checked for proper operation by a competent engineer or inspector. This should include determination of any changes in physical properties of the foam concentrate which indicate any deterioration in quality. Regular service contracts with the manufacturer or installing company are recommended.

1811. The goal of this inspection and testing shall be to en- sure that the system is in full operating condition and to indicate the probable continuance of that condition until the next in- spection.

1812. Suitable discharge tests should be made when any in- spection indicates their advisability.

1813. The inspection report, with recommendations, shall be filed with the owner.

1814. Between the regular service contract inspection or tests, the system shall be inspected by competent personnel, follow- ing an approved schedule.

1815. Strainers should be inspected and cleaned after each use and test.

182. Maintenance. These systems shall be maintained in full operating condition at all times. Use, impairment, and restoration of this protection shall be reported promptly to the authority having jurisdiction.

1821. Any troubles or impairments shall be corrected at once by competent personnel.

183. Instructions. All persons who may be expected to inspect, test, maintain, or operate foam generating apparatus shall be thoroughly trained and kept thoroughly trained in the functions they are expected to perform.

1831. Training programs approved by authority having juris- diction shall be established.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 19: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

TOTAL I~LOODING SYSTEMS IIA-17

CHAPTER 2.

TOTAL FLOODING SYSTEMS

21. General Information

211. Description. A total flooding system consists of fixed foam generating apparatus complete with a piped supply of foam concentrate and water, arranged to discharge into an enclosed space or enclosure about the hazard.

212. Uses. This type of system may be used where there is a permanent enclosure about the hazard that is adequate to enable the required amount of fire extinguishing medium to be built up and to be maintained for the required period of time to ensure the control or extinguishment of the fire in the specific combustible material or materials involved.

2121. Examples of hazards that may be successfully, protected by total flooding systems include rooms, vaults, storage areas, ware- housing facilities and buildings containing Class A and Class B combustibles either singly or in combination. Three dimensional fires in flammable liquids (falling or flowing under pressure) having flash points below 100°F generally will not be extinguished by total coverage. Although this fire may continue in the foam, heat radiation will be reduced and kept under control with continued foam application.

2122. Fires which can be controlled or extinguished by total flooding methods can be divided into two categories: namely (1) surface fires involving flammable or combustible liquids and solids and (2) deep seated fires involving solids subject to smoldering.

213. General Requirements. Total flooding systems shall be designed, installed, tested and maintained in accordance with the applicable requirements in the previous chapter and with the ad- ditional requirements set forth in this chapter. Only listed or ap- proved equipment and devices shall be used in these systems.

22. Enclosure Specifications

221. Leakage and Ventilation. Since the efficiency of the high expansion foam system depends upon the development and mainte- nance of a suitable quantity of foam within the particular en- closure to be protected, leakage of foam from the enclosure shall be avoided.

2211. Openings below design filling depth, such as doorways, windows, etc., shall be arranged to close automatically before, or

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 20: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

ilA-18 m o l l E x P A N s I O N FOAM SYSTEMS

simultaneously with the start of the foam discharge, with due consideration for evacuation of personnel. They shall be designed to maintain a closure during a fire and be capable of withstanding pressures of foam and sprinkler water discharge. If any unclosable openings exist, the system shall be designed to compensate for the probable loss of foam, and should be tested to assure proper performance.

2212. When outside air is used for foam generation, high level venting shall he provided for air which is displaced by the foam. If possible, venting velocity should not exceed 1000 feet per minute in free air. The venting so required shall oonsist of suitable openings, either normally open, or normally closed and arranged to open automatically when the system operates. When design criteria demand exhaust fans, they shall be approved for high temperature operation and installed with due consideration for protection of switches, wiring, etc., to assure equal reliability of exhaust fan performance as for the foam generators. Where forced air ventilating systems interfere with the proper build-up of foam, they shall be shut down or closed off automatically.

23. Foam Requirements 231. General. For adequate protection, sufficient high expan-

sion foam shall be discharged at a rate to fill the enclosure to an effective depth above the hazard before an unacceptable degree of damage occurs.

232. Foam Depth. The minimum total depth of foam shall be not less than 1.1 times the height of the highest hazard, but in no case less than 2 feet over this hazard. For flammable or com- bustible liquids, the required depth over the hazard may be con- siderably greater and shall be detemined by tests~

233. Submergence Volume. Submergence volume is detined as (1) the depth as specified in Section 232 multiplied by the

,floor area of the space to be protected or (2) in the case of un- sprinklered rooms of internal combustible construction or finish, the entire volume including concealed spaces. The volume occupied by vessels, machinery or other permanently located equipment may be deducted when determining the submerged volume. The volume occupied by stored material shall not be deducted when determin- ing the submergence volume unless approved by the authority having jurisdiction.

~234. Submergence Time. Recommended times to achieve sub- mergence volume for various types of hazards and building con- struction are shown in Table I. Shorter submergence times may be required depending on the factors included in Section 235.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 21: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

TOTAL FLOODING SYSTEMS I 1 A - 1 9

Hazard

TABLE I

Mmdmum submergence time for High Expansion Foam Measured

from start of Foam Dischar~e* (Minutes)

Heavy or Protected Light or Unprotected or Fire Resistive

Steel Construction Construction

Not Not Sprinklemd Sprinldered Sprinklered Sprinklered

Flammable Liquids (Flash Points below 14001:) * * 3 2 5 3

Combustible Liquids (Flash Points of 140°F end above)** 4 3 6 4

Low Density Combustibles 4 3*** 6 d*** i.e., Foam Rubber

Foam Plastics Rolled Tissue or Crepe Paper

High Density Combustibles 7 5*** 8 6*** i.e., Rolled Paper

-Kraft or Coated-Banded

High Density Combustibles 5 4*** 6 5*** i.e., Rolled Paper

-Kraft or Coated-Unhanded

Rubber Tires 7 5*** 8 6***

Combustibles, in cartons, bags, 7 5*** 8 6*** fiber drums

* This is based on a maximum of 30 sec. delay between fire detection and start of foam discharge. Any delays in excess of 30 sec. shall be deducted from the submergence times in Table I.

** Polar solvents are not included in this table. Flammable liquids having boiling points less than IO0°F may require higher application rates. Where use of high expansion foam is contemplated on these materials, the foam equipment supplier shall substantiate suitability for the intended use.

*** These submergence times may not be directly applicable to high-piled storage above 15 ft. or where fire spread through combustible contents is very rapid.

235. Rate of Discharge. The rate of foam discharge necessary for extinguishment or sufficient control to permit overhaul depends upon the strength of sprinkler protection, nature and configuration of the hazard, vulnerability of the structure and contents to fire, and the loss potential to life, property and production. The rate also depends upon foam properties, such as expansion ratio, water retention, effect of water contaminants, temperature effects on water retention, etc. The foam discharge rate shall be sufficient

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 22: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

IIA-20 H I G H E X P A N S I O N FOAM S YS TEM S

to satisfy the foam depth requirements and submergence times of Table I, making compensation for normal foam shrinkage, foam leakage, and breakdown effects of sprinkler discharge.

"2351. The minimum rate of discharge or total generator capacity shall be calculated from the following formula:

R = ( T + Rs ) X CNX CL where:

R = rate of discharge - - cfm V = submergence volume

cubic feet T = submergence t i m e -

minutes Rs = rate of foam breakdown

by sprinklers - - elm CN = compensation for normal

foam shrinkage CI~ = compensation for leakage

2352. The factor (R~) for compensation for breakdown by sprinkler discharge should be determined by test. In the absence of specific test data, the following formula shall be used:

R~ = S X Q where: S = Foam breakdown in cfm per gpm of sprinkler discharge.

S shall be 10 cfm/gpm. Q = Estimated total discharge from maximum number of

sprinklers expected to operate--gpm.

2353. The factor (CN) for compensation for normal foam shrinkage shall be 1.15. This is an empirical factor based on aver- age reduction in foam quantity from solution drainage, fire, wetting of surfaces, absorbency of stock, etc.

2354. The factor (CL) for compensation for loss of foam due to leakage around doors and windows and through unclosable openings shall be determined by the design engineer after proper evaluation of the structure. Obviously this factor cannot be less than 1.0 even for a structure completely tight below the design filling depth. This factor could be as high as 1.2 for a building with all openings normally closed depending upon foam expansion ratio, sprinkler operation, and foam depth.

236. Quantity. Sufficient foam concentrate and water shall be provided to permit continuous operation of the entire system for at least 25 minutes or to generate four times the submergence vol- ume, whichever is less, but in no ease less than enough for 15 minutes of full operation (see Section 154).

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 23: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

LOCAL APPLICATION SYSTEMS I1A-21

2361. Reserve supplies shall be provided in accordance with Section 156.

~24. Maintenance of Submergence Volume. To ensure adequate control or extinguishment, the submergence volume shall be main- tained for at least 60 minutes for unsprinklered locations and 30 minutes for sprinklered locations. Where only flammable or com- bustible liquids are involved, this period may be reduced.

241. Method. The submergence volume may be maintained by continuous or intermittent operation of any or all of the generators provided.

2411. Arrangements and procedures shall be provided to maintain the submergence volume without waste of foam concen- trate which may be needed in case of re-ignition.

**25. Overhaul. As is true with other total flooding extinguish- ing systems, control established by the system may be lost by im- proper overhaul procedures.

26. Distribution. The discharge arrangements should be such that a relatively even build-up of high expansion foam will take place during the discharge period.

CHAPTER 3. LOCAL APPLICATION SYSTEMS

31. General Information

311. Description. A local application system consists of fixed foam generating apparatus complete with a piped supply of foam concentrate and water and arranged to discharge foam directly onto the fire.

312. Uses. Local application systems may be used for the extinguishment of fires in flammable or combustible liquids, and ordinary Class A combustibles where the hazard is not totally enclosed. These systems are best adapted to the protection of essentially flat surfaces such as confined spills, open tanks, drain- boards, curbed areas, pits, trenches, etc. For multiple level or three dimensional fire hazards where total building flooding is not practical, the individual hazard shall be provided with suitable containment facilities acceptable to the authority having juris- diction.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 24: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

11A-22 m G H E X P A N S I O N FOAM S Y S T E M S

313. General Requirements. Local application systems shall be designed, installed, tested and maintained in accordance with the applicable requirements in previous chapters and with the ad- ditional requirements set forth in this chapter. Only listed or ap- proved equipment and devices shall be used in these systems.

32. Hazard Specifications 321. Extent of Hazard. The hazard shall include all areas to

which or from which fire may spread.

322. Location of Hazard. The hazard may be indoors, partly sheltered, or completely out-of-doors. Foam should be protected from strong winds or air currents.

33. Foam Requirements

331. General. General sufficient foam shall be discharged at a rate to cover the hazard to a depth of at least two feet.

332. Quantity. Sufficient foam concentrate and water shall be provided to permit continuous operation of the entire system for at least 12 minutes (see Section 154).

3321. Reserve supplies shall be provided in accordance with Section 156.

34. Method. Discharge outlets shall be arranged to ensure that foam is delivered over all areas which constitute the hazard. Where parts of the hazard are elevated or raised up from the ground or floor llne, the arrangement of the system shall be such that foam will be delivered to, and retained on, such parts in sufficient depth to ensure prompt and final extinguishment.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 25: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

PORTABLE OENERATINO DEVICES 11A-23

CHAPTER 4. PORTABLE FOAM GENERATING DEVICES

41. General Information

411. Description. Portable foam generating devices consist of a high expansion foam generator, manually operable and trans- portable, connected by means of hose, or piping and hose, to a supply of water and foam concentrate. The proportioning equip- ment may be integral with or separate from the foam generator. A separate foam concentrate supply may he provided for each unit, or solution may be piped from central proportioning equip- ment.

412. General Requirements. Portable foam generating de- vices and associated equipment shall be used and maintained in accordance with the applicable requirements in the preceding chapters and with the additional requirements set forth in this chapter. Only listed or approved equipment and devices shall be used.

42. Hazard Specifications

421. Portable foam generating devices may be used to combat fires in all hazards covered under Chapters 2 and 3.

43. Location and Spacing

431. Location. Portable foam generating devices which are preconnected to a water or solution supply shall be placed where they are easily accessible and with enough hose to reach the most distant hazard which they are expected to protect. Foam concen- trate shall be available for immediate use. These devices shall be located such that they are not exposed to the hazard. Those not preconnected to a water or solution supply and their associated equipment shall be located and arranged for immediate transport to all designated hazards.

44. Foam Requirements

441. Rate and Duration of Discharge. The rate and duration of discharge and consequently the quantity of foam concentrate and water shall be determined by the type and potential size of hazard. To the extent that the specific hazards can be identihed, the applicable requirements of Chapters 2 or 3 shall apply.

442. Simultaneous Use of Portable Foam Generating Devices. Where simultaneous use of two or more devices is possible, suffi-

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 26: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

1 1 A - 2 4 HIGH EXPANSION FOAM SYSTEMS

cient supplies of foam concentrate and water shall be available to supply the maximum number of devices that are likely to be used at any one time.

45. Equipment Specifications

451. Hose. Hose used to connect the generator to the water or solution supplies shall be listed lined hose. Unlined fabric hose shall not be used. The hose size and length shall be selected with consideration to the hydraulics of the entire system. Such hose should be stored in an arrangement that will permit immediate use and be protected against the weather.

452. Electric Power Supply and Connections. Power supply and connections needed for operation of the generator shall be adequate to transmit the required power, and shall be selected with consideration to the intended use. All power cables shall be sufficiently rugged to withstand abuse in service, be impervious to water and shall contain a ground wire. Unless electric con° nectors are waterproof, care should be taken to prevent them from being immersed in water.

46. Training

461. Successful extinguishment of fire with portable foam gen- erating devices is dependent upon the individual ability and tech- nique of the operator. All personnel likely to use this equipment shall be properly trained in its operation and in the necessary fire- fighting techniques.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 27: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

APPENDIX 11A-25

APPENDIX

A-122. Clearance to Live Electrical Apparatus General As used in this Standard, "clearance" is the air distance between

high expansion foam equipment, including piping and nozzles, and unenclosed or uninsulated live electrical components at other than ground potential.

The clearances given are for altitudes of 3,300 ft. or leu. At alti- tudes in excess of 3,300 ft., the clearance shall be increased at the rate of I percent for each 330 ft. increase in altitude above 3,300 ft.

Clearance. Clearance shall not be le-~ than that given in the following Table.

The clearances are based upon minimum general practices related to design Basic Insuladon Level (BIL) values. To coordinate the required clearance with the electrical design, the design BIL of the equipment being protected should be used as a basis, although ~ is not material at nominal line volt- ages of 161 kv or len.

Up to electrical system voltages of 161 kv the design BIL kv and corre- sponding minimum clearances, phase to ground, have been established through long mmge.

At voltages higher than 161 kv, uniformity in the relationship between design BIIJ kv and the various ~lectrical system voltages has not been estab- liahed in practice and is dependent upon several variables so that the re- tqhuired clearances to ground should be based upon the design BIL used rather

an on the nominal line or ground voltage.

Table A-122 Clearance From High Expansion Foam Equipment

To Live Uninsulated Electrical Components

Nominal Une Nominal Voltage Design BIL Minimum Voltage To Ground Clearance

kv kv kv inches

15 9 110 6 23 13 150 8 34.5 20 200 12 46 27 250 15 69 40 350 23

115 66 550 37 138 80 650 44 161 93 750 52

196-230 114-132 $ 900 $ 63 ~1050 | 76

287-380 166-220 (1175 (8_7 11300 i98 ~1550 ~120

500 290 $1675 $131 |1800 ~142

500-700 290-400 ( 1925 ( 153 ]2100 |168 2300 t 184

Possible design variations in the clearance required at higher voltages axe evident in the Table, where a range of voltages is indicated opposite the vari-

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 28: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

11A-26 HIGH EXPANSION FOAM SYSTEMS

ous BIL test values in the high voltage portion of the Table. However, the clearance between uninsulated energized parts of the electrical system equip- ment and any portion of the high expansion foam system shall not be less than the minimum clearance provided elsewhere for electrical system insula- tions on any individual component.

NOT~: BIL values are expressed as kilovolts (kv), the number being the crest value of the full wave impulse test that the electrical equip- ment is designed to withstand.

A-143. Operating Devices. A block diagram of typical automatic high expansion foam system is shown in Fig. A-143-1.

Foam generators. At the present time foam generators for high expan- sion foam are of two types depending on the means for introducing air, namely by aspirator or blower. In either case, the properly proportioned foam solution is made to impinge at appropriate velocity on a screen or porous or perforated membrane or series of screens in a moving air stream. The liquid films formed on the screen are distended by the moving air stream to form a mass of bubbles or high expansion foam. The foam volume varies from about 100 to 1000 times t h e liquid volume depending on the design of the generator. The capacity of foam generators is gen- erally determined by the time required to fill an enclosure of known volume by top application within 1 to 5 minutes.

Foam Genera tors - -Aspi ra tor Type. These may be fixed or portable. Jet streams of foam solution aspirate sufficient amounts of air which is then entrained on the screens to produce foam. (See Fig. A-143-2). These usually produce foam with expansion ratios ~ot over 250:1.

Foam Genera tors - -Blower Type. These may be fixed or portable. The foam solutkm is discharged as a spray onto screens through which an air stream developed by a fan or blower is passing. The blower may be powered by electric motors, internal combustion engines, air, gas, or hydraulic motors or water motors. The water motors are usually powered by foam solution. (See Fig. A-143-3.)

{ • DETECTOR

MANUAL OVERRIDE -7

I ' H t . . . . CON,ROLl C A I

Fig. A.14~1. Block Diagram of Automatic High Expansion Foam System.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 29: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

APPEND= 11A-27

FOAM SCREEN ~ FOAM

Fig. A-14,11-2. Aspirating Type Foam Generator.

L_ BLOWER

FAN

PRIME MOVER

SCREEN-~ ~ooO~ /AOo o

!i \ - - !~OoO;; , 0 0 ~ ,I \ Noo~ ,11 ~°°0

FOAM SOLUTION

Fig. A-14S~I. Blower Type Foam Generator.

L)oO ~o oo o ~o oo ,g o 0

~o o 0 o

o

• %-155. Fire Pedormance Test. The purpose of this test is to provide a reproducible fire situation where foam shall be required to move a sub- stantial distance at a slow rate to the fire. The time to move this distance and to fill to the top of the test combustibles is the FOAM TRANSIT TIME. The effect of the transit time is to give age to the foam during the period of its slow movement from foam generator to fire.

The test shall be conducted in an open top pen or buildlng of suitable construction and suitable dimensions. To prevent the velocity of foam movement from being too high, the width of the pen or building times I00

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 30: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

11A-28 HIGH EXPANSION FOAM SYSTEM~;

should give a figure not smaller than the capacity in cfm of the foan~ generator used in the test. The height of the size of the pen or building should be about 10 ft. If the fluidity of the foam permits, the height may be less. However, the foam shall not flow over the sides of the pen nor contact the ceiling of the building during the test. The foam generator shall be set at one end of the pen or building, and the fire shall be set 10 feet from the opposite end. The distance between the foam generator and the fire shall be as required to give the foam transit time desired.

Foam shall be produced by a generator in which the expansion ratio is equal to or greater than that produced by the generator proposed for installation.

The test fire shall be a stack of eight standards 4 ft. x 4 ft. hardwood pal- lets dried to a moisture content between 5 and 8 percent, set on suitable non- combustible supports not over 24 in. above the floor. Beneath the pallets shall be a 10 sq. ft. pan containing 1 gal. of heptane or naph tha floating on water. The surface of the flammable liquid shall be approximately 12 in. below the bottom boards of the bottom pallet.

The first test of each series shall be a timed fill without a fire to determine the foam transit time. The location of the leading edge of the foam as it progresses across the floor of the pen or building shall be timed at suitable intervals. Also, the time shall be noted when the foam reaches the edge of the pan. This data will permit estimating, with reasonable accuracy, the location of the leading edge of the foam 3 minutes before the foam should reach the edge of the pan. Thereafter, during each fire test, the heptane shall be ignited when the foam reaches that point corresponding to 3 minutes in advance of reaching the pan. In this manner, the fire is given a reproducible 3 minute preburn. This fill test can be terminated when the foam has filled to the top of the wood pallets, and the time determined as the foam transit time.

The minimum foam transit time shall be 12 minutes (150 percent of maximum submergence time, 8 minutes, from Table I ) . To be considered successful under the foam transit time condition, the foam shall give adequate control of the test fire. The foam generator shall be run for a maximum of 30 minutes. Adequate control shall be interpreted as the absence of active burning within the test stack while the stack is covered with foam.

Foam Concentrate Proportioning Systems. Some typical proportioning systems are shown in NFPA Standard for Foam Extinguishing Systems (No. l l ) .

A-162. Resistance of Foam Generators to Fire Exposure. To determine its ability to withstand fire exposure from the hazard area a generator, its associated piping and electrical wiring, protected in accordance with the manufacturer 's recommendations, shall be started and operated after a 5 minute exposure 10 feet above a 50 square foot gasoline fire using 100 gallons of fuel. The test fire should be shielded to ensure flame impinge- ment on the generator.

A-234. Submergence Time - - Vulnerabil i ty of Structure. I t is impera- tive that the integrity of primary structural members be maintained under fire exposure (which in sprinklered structures normally support the sprin- kler system). Light unprotected bar joist and other similar types of sup- ports are especially vulnerable to damage by fast developing fires as com- pared to that of heavy steel construction. So also is heavy unprotected

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 31: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

APPENDIX I I A - 2 9

steel framing more vulnerable than fire resistive (concrete) or protected structural members.

A-235. Tests with foams of above 400:1 expansion ratio have shown that extinguishment times for flammable liquid fires increased significantly at rates of foam rise less than 3 feet per minute. I t is expected that at some expansion ratio below 400:1 lower rates of foam rise would be adequate, hut insufficient tests have been conducted to identify this ratio.

A-2351. Sample Calculation of Total Generator Capacity

GxvEN: Building Size - - 100 feet x 200 feet x 30 feet high

Building Construction - - Light bar joist, Class I steel deck roof, adequately vented. Masonry walls with all openings closable.

Sprinkler Protection - - Wet system, 10 feet x 10 feet spacing. 0.25 gpm/sq ft density.

Occupancy - - Vertically stacked unbanded rolled Kraft paper 25 feet high.

A s s v ~ : Fire will open 50 sprinkler heads. Foam leakage around closed doors, drains, etc., hence, CL = 1.2

CALCULATION : Foam Depth

Depth = 25 × 1.1 = 27.5 feet (This is greater than minimum cover of 2 feet)

Submergence Volume V = 100 x 200 x 27.5 = 550,000 cubic feet

Submergence Time T = 5 minutes (from Table I)

Rate of Foam Breakdown by Sprinklers S -- 10 c fm/gpm (from Section 2352)

Q = No. of heads x a rea /head × density. = 50 × (10 × 10) x 0.25 = 1250gpm

R~ = S X Q = 10 × 1250 = 12,500 cfm

Normal Foam Shrinkage Cs = 1.15 (from Section 2353)

Leakage CT. = 1.2 (assumption)

Total Generator Capacity (v ) R = - ~ - + R.~ × C.,,r × Cr,

R = (55o,000__g__ + 12,500) × 1.15 × 1.2

R = 169,000 cfm

The number of generators required will depend upon the capacity of the generators available.

A-2352. Rate of Breakdown by Sprinklers. Where sprinklers are present in an area to be protected by high expansion foam, simultaneous operation will cause breakdown of the foam. The rate of breakdown will depend

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 32: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

llA-30 HIGH EXPANSION FOAM SYSTEMS

upon the number of sprinklers operating and the subsequent total rate of water discharge. The number of sprinklers expected to operate will depend upon various factors as outlined in NFPA Standard for Installation of Sprinkler Systems (No. 13).

A-2354. Foam Leakage. I t is essential tha t uncontrolled leakage be re- duced to an absolute minimum through the use of foam-tight barriers at all openings below the effective hazard control level or depth, contemplating the increased rate of foam escape as its fluidity is increased by anticipated sprinkler discharge.

Such leakage through drains, trenches, under doors, around windows, etc. can be minimized by use of suitable automatic closures, sealing agents, or mechanisms. Additional generator capacity should be added to corn= pensate for the aggregate losses where foam escapement cannot be effective- ly controlled.

A-24. Maintenance of Submergence Volume. The choice of a total flood- ing foam system for protection of a hazard, does not necessarily imply that it is expected that the system will completely extinguish the fire, or even so nearly extinguish it as to render the fire incapable of regaining the offensive. Rather, the effect sought might often be speedy control with minimum damage to contents not involved in the fire.

When high expansion foam is establishing or has established control of a fire, care must be exercised that control is not lost. The following points should be kept in mind. Depending upon the particular fire, some or all might be vital.

I. All should be aware of the necessity for t ight closure. Employees, brigade members, and the fire depar tment should move rapidly to close any openings through which foam is being lost. Improvised closures can be made of practically any available material such as screening, plastic, plywood, hardboard.

2. If the material involved is liable to deep-seated fires, such as fur- niture, packaged material, fibers, rolls of paper, etc., p.articular care must be exercised in opening up the areas and remowng the foam. Even where only surface fire is thought possible as in flammable liquids, smoldering Class A material may cause reignltion.

3. A "soaking" period should elapse before foam is removed. This may be as long as an hour and should be predetermined based upon the fuel in the area.

A-25. Overhaul. haul operations:

The following points should be considered during over-

1. All foam and sprinkler systems which are shut off should have men standing by valves to turn them back on if this should be- come necessary.

2. Foam supplies should be replenished if depleted.

3. Hand hose lines should be charged and manned. Personal protec- tive equipment should be donned, self-contained breathing apparatus should be worn in the "ready" position so there will be no delay in put t ing it in service.

4. Foam should be removed first from the /ire area and foam removal should be coordinated with overhaul and salvage operations. The

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 33: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

APPSNDXX 1 IA-31

total loss will be kept to a minimum if thoughtless operations are avoided. The fire is under control; undue haste to extinguish the last ember may greatly increase the loss.

5. Caution should be taken in entering previously foam-filled areas, particularly in structures with pits or openings in the floor.

6. The area should be well ventilated but openings through which foam might be lost should be kept to a minimum and manned for closing if this should become necessary.

7. Consideration shall be given to disposal of the foam to prevent any undue hazard to adjacent areas.

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 34: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 35: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

National Fire Protection Association In ternat ional

60 Batterymarch Street, Boston, Mass. 02110

The National Fire Protection Association was organized in 1896 to promote the science and improve the meth,,ds of fire protection. Anyone interested may become an Associate Member; the annual dues are 830.00. National and regional societies and associations are eligible to be Organiza- tion Members; annual dues are 8225. Full membership information is available on request.

This is one of a large number of publications on fire safety issued by the Association. All NFPA codes, standards, and recommended practices are prepared by NFPA Technical Committees and adopted at an Annual Meeting of the Association. They are intended to prescribe reasonable measures for minimizing losses of life and property by fire.

This and other NFPA codes, standards, and recommended practices are published in the Nat iona l Fire Codes, a ten-volume compilation of NFPA's official technical material. Following are the titles of the ten- volume set:

Vol. 1 Flammable Liquids, Ovens, Boiler-Furnaces

Vol. 2 Gases

Vol. 3 Combustible Solids, Dusts and Explosives

Vol. 4 Building Construction and Facilities

Vol. 5 Electrical

Vol. 6 Sprinklers, Fire Pumps and Water Tanks

Vol. 7 Alarm and Special Extinguishing Systems

Vol. 8 Portable and Manual Fire Control Equipment

Vol. 9 Occupancy Standards and Process Hazards

Vol. 10 Transportation

Write the Association for full information.

D i s c o u n t Prices on this P a m p h l e t

The following schedule of discount prices for multiple copies of this pamphlet have been established:

1 to 4 copies: Unit price 25 copies and over: 25% 5 copies and over: 15~ 50 copies and over: 30%

10 copies and over: 20~ 75 copies and over: 35G 100 and over: Special quote

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.

Page 36: HIGH EXPANSION FOAM SYSTEMS 1970 handbook/NFPA 11A-1970.pdf · I IA-2 HIGH EXPANSION FOAM SYSTEMS Committee on Foam Thomas L. ~ C~, Eeso Resem'eh and Engineering Co., P.O. Box 101,

TYPICAL POCKET EDITIONS OF NFPA List revised as of June, 1970 . Titles are abbreviated, For ¢omglete l lst of

2M Model Legislation "67 . . . . SO 4A Fire Dept. Organization '69 -~ . .7~ 4B Fire Dept. Management "6B , . 2.S0 6 industrial Loss Prevent. ~67 , .S0 7 Controlling Fire Emerg '67 . " , .50 8 Management Resaonsibility "67 . ,50 9 Tralnin~ kegOrtS, Records '70 . .50

10 Extinguishers, lustnl. ' 7 0 . . 1,00 ]OA Extinguishers, Maiot. '70 . 1.00 IOL Model Enabling Act '69 . . .50 ]1 Foam Ext. Systems '70 . . . 2.00 1 iA High Expansion Foam Syst. '70 .75 12 CarLon Dioxide Systems '68 . 1.50 I2A Halon 1301 Systems ' 7 0 . . 1.2~ 13 Sprinkler Systems "69 . . 2.00 13A Sprinkler Maintenance "69 75 13E Sprlnklered Prop., F.D.

Opera t ions at '66 . . . . 60 14 Standnioe, Hose Systems '70 • .75 15 Water Spray Fixed Syst. "69 1.25 t6 Foam.Water Systems '68 . . 1.00 17 Dry Chem. EXt. Systems ' 69 . . 75 18 Wetting Agents '66 . . . . . 50 ]82M Vaporizing Linuid '65 . 40 19 Fire Anoa ra tus Sores. '70 . . 1.50 191 Portable PumP. Units ' 59 , .35 193 Ladders. Ground-Aerial '$9 . .50 194 Hose Coupling Threads '68 . .75 196 Fire Hose "69 . . . . . . .50 197 ~nitial Fire Attach "66 . , ,,SO 198 Fire Hose, Care of "69 . . , 1.00

20 Centrifugal Fire Pumps '70 . 2.00 21 Steam F i re Puma MainS. ~63 . .60 22 Water Tanks ' 70 . . . . . . 2.00 24 Outside Protection '70 . • . 1.25 25 Rural Water Systems ' 69 . . . 75 26 Supervisior Valves '$8 . . . . 40 27 Private Fire Brigades '67 . . .$0 292M Water Charges, Private '61 . .40 295 Forest F i re ContraJ '65 , . .75

30 Flare. Liuuids Code ' 69 . . 1 . 00 31 Oil Burning Eouinment ' 6 8 . 1.25 32 Drycieoning Plants '70 . . . . 7S 321 Cta>s. F/am. Liquids '69 . . .50 325A 71ashpoint Index of Trade

Name Liouids "68 . . . . 2.50 325M Pron. Flare. Liquids ' 69 . . . 3 . 00 326 Warning Labels '51 . . ~" .2S 327 Cleaning Smalt Tanks '70 .S0 328 Manholes, Sewers, Flare.

Liquids and Gases in '70 ~ ".75 329 Leakage, Underground

F~am. Liouid Tanks ' 65 . . 50 33 Spray Finishing " 69 , . , 1 .2S 34 Dip Tanks " 66 . . . . . . 50 35 Mf9, Organic Coatings *70 . - ~ 1.O0 36 Solvent Extraction " 67 . . . . 60 37 Combustion Engines '70 . . . . 7S 385 Tank Vehicles "66 . . . . . 60 386 Portable Shippmg Tanks '70 . .S0 393 Gasotine Blow Torches " 69 . . 50 395 Fa rm Storage Flam. Lip. "65 . .40

• ~0 Motior Picture Fi lm "67 . . .60 41L Model Rocketry Code "68 . . .50 42 Pyroxylin Plastic Factories '67 .60 43 Pyroxylin Warehouses '67 , . .40 46 Timh~, OutdOor Storage '6| , .50 46A Wood Chips, Storage '65 , . .40 47 Lumber Storage Yards ~61 . . .50 48 Magnesium s67 ". . . . . 60 481 Titanium "61 . . . . . : . . 6 0 482M Zirconium "61 . . . . . . " 2 "50.50 49 Hazarqous Chem. Data ' 69 ; . .

STANDARDS ~:

490 Ammonium Nitrate ~70 , - . . .75 49tM Chem. Reactions '68 , . . 2.50 492 Ammon, Nitrate, Sop. Oi~t, " 68 .SO 493 Process Control Eguip. "69 , .75 494L:State Fireworks Law "64 . ,40 495 Explosives, Stge,, Use '70 . 1.25 496 Purged Enclosures " 67 . . . . 50 498 Explosives,. Motor Term, ' 7 0 , .50

50A Gaseous Hydrogen Syst, " 69 . .50 $1 Welding and Cutting " 69 . . 75 50B LH-Syst,, Consumer Sites ~68 ~ .50 S]B Welding Processes "62 . . . . 4O 54 Gas APPliances, Piping "69 . . 1.25 S4A Indust. Gas Plpln~ "69 1.00 56A Inhalation Anesthetics '7"0 i t.50 56B inhalation Therapy ~68 . . . . 75 56C Honpital La~oratorles '70 . ~ .75 56D Hyperbaric Facilities '70 . 1.00 S6F NomSam, Med. Gases '70 ; . • .75 ,566 Bulk 0xyget~ Systems.'65 .; , .S0 57 Fumigation ~68 . . . . . . 7.5 58 LP-Gas Storage, Use " 69 . . 1.25 59 LP-Gas~ Uti l i ty Plaots'68 . . 1.25 S9A LN-Gas, Ut i l i ty Plants '67 . .60

60 Pulverized Fuel Systs. '61 . . .60 61A Starch Factories '62 . . . . S0 6 iB Grain Elevators '70 . . . . 75 61C Flour and Feed Mil ls '62 . . .60 62 Sugar amd Cocoa '67 . . . . . 50 63 Exp Deigns indus. Plants " 64 .50 65 Alumln~m Processing '70 ; , , .S0 651 Aluminum Powder ' 6 7 . , " . .50 652 Magnesium Powder "68 . , .50 653 Coal Preoaration Plants ' 59 . .5G 654 Plastics. Expi. Fre~ent, aTO , 1.25 655 Sulfur Fires '68 . . . . . . 35 656 Spice Grinding Plants iS9 ' : : ; .40 657 Confectionery Plants "67 . . .$0 66 Pneumatic Conveying " 70 , . . 75 664 Woodworking, Woncl Flour "62 .60 68 Explosion Venting ~54 . . . . . 75 69 ExPlosion Prey. Syst, *70 • . ,1.25

70 Natfl Electrical Code "68 . . 2.00 70A Dwelling Electrical Code ~69 1.75 71 Central Statian Sig. "70 . . 1.00 72A Local Protective Syst. '67 . ,60 72B AuxiliarY Stg. Syst. "67 . . .60 72C Remote Station Sys tem '67 , . 60 72D Proprietary Sin. Syst. " 67 , . . 60 73 Municipal Alarm SysL./67 : . , . 50 74 Household Warning SYst" ' 67 '. ,50 75 Electronic Computer Syst~ '68 ,75 76A Hospital Eles. Systems *70 . .75 77 Static Electricity "66 ,,- ~ • 1.00 78 Lightning Prot. Code ' 6 8 . ; 1.2S 79 Electrical Metalworking

Mac~in~ Tools '70 . . . . I.O0

80 Fire Doors , Windows ~70 2.00 80A Exposure Fires, Prof. '7"0 ~ .75 R1 Fur Storage, Cleaning " 69 , . .7S R2 Incinerators, Rubbish '70 . . ,7S 85 Watertube Boiler-Furnanes " 67 . .7S RSB Gas-Fired Multiple Burner

Rol let-Furnaces '70 . . . . 1.25 85D Fuel Oil-Fired Mutt~ole

Burner Boiler-Furneces '70 ." 1.$0 86A Ovens and Furnaces '69 , . 2.00 87 Piers and Wharves '68 . . . . 75 88 Garages '68 . . . . . . . 7,5 BgM Heat Eqgip.' Clearances '70 . ' .50

S~0A A i r Conditioning Syst, / 69 . ,75

pobtir,~tlons write NFPA. : : : " ,.

90B Residence Warm A i r Hnattng .75 i;,; • 91 Blower and Exhaust Syst. "61 .50 96 Vaonr Remona~ Cooking Eouip-

ment '70 . . . . . . . . 50 97M Glossary , Heating Terms "68 . .SO

101 Life Safety Code t 70 , , , 2 . 00 , 102 Tents, Grandstands, Air-

Subported Structures '67 . . .60

203M Roof Coverings eTO . . . . SO 204 Smoke, Heat Venting " 68 . : , . 50 206M Building Areas ~70 . . . . SO 21f Chimneys, Venting Syst. sTO 1 .00 : ' 214 Water Cooling Towers *68 . .75 220 Std. Types Bldg. Const,,'61 224 Homes Forest Areas " 69 . , . 75 231 Indoor General Storage '7(J . 75 , 231A Outdoor Gen'l. Sto rage J7O . .50 23tO Cellular Ruble,,r, Storage '68 .73 232 Protection of Records '70 ~ I..SO "" 241 Bldg. Constr, Ooera~.iofl '68 . . . . 50 251 Fire Tests Oldg, Mall. '69 . .75 252 Fire Tests Door Assem, ' 69 . .$0 255 Flamesoreod Tests *69 . . . . SO 25~ Tests Roof Coverings '70 . . . . $0 257 Window Assemblies '70 , ". ,50

302 Motor Craft '68 , . . . . 1.25 303 Marinas and Boatyards ' 69 r 1 . 00 306 Gas Hazards on Vessels " 69 . ,75 307 Marine Terminals "67 . , . .60 312 Vessels, Constr.-Repair 170 o .~iO

402 Aircraft Rescue Proced. ' 69 . 2.00 : " 403 Aircraft Rescue Services 170 . 1.2,5 406M Handling Crash Fires '68 . 1.00 :i: 407 Aircraft Fuel Servicing " 70 . 1 . 50 , 408 Aircraft Extinguishers ~70 . .SO 409 Aircraft Hangars '70 1.25 410A Elec. Syst. MainS, "68 . . .50 41OB Oxygen Syst. MainS. '66 .50 410C Fuel Syst. MainS. "68 . . . 1.00 410D Aircraft Painting "66 _ . .50 410E Aircraft Welding '70 . . . . 50 41DE Aircraft Cabin Clean. '70 . .50 41] Aircraft Ramp Hazard '70 . .50 412 Testingr Foam Vehicles ' 69 . . 75 414 Rescue Vehicles '70 . . . . 2.00 4 ,5 Fuel ng Ramp Dra nape "66 . .50 4]6 Airport Terminals '67 . . . . 50 417 Loading Walkways "68 . . . . SO 418 Roof-Top Heliports ' 68 . . .SO 4f9 Airport Water Systems "69 . .75

S01A Trailer Courts ~64 . . . . S0 ! 501O Mobile Homes " 68 . . . 2 , 00 501C Recreational Vehicles '70 , 2.00 505 Power Industrial Trucks " 69 ~ ,75 512 Tr~ck Fire Protection *70 . • .75 513 Motor Freight Terminals '59 ~ .40

601 Guard Seruice "68 . . . . . 50 601A Guard Oaerations '68 . . .SO 602 Community Dumps "64 . . . . 50 604 Salvaging Operations "64 . . ,50

701 Fire Tests, Textiles, Films '69 .75 702 Wearing Apparel "68 . . . . 75 703 Fire Retardonts Bldg. M o l l . . .40 704M Identification of Materials .75

801 Radioactive Mat t FaclL ' 7 0 . .75 802 Nuclear Reactors ' 60 . . . . 75

901 Fire Reporting Sys tem- ' 69 . 3 . 00 910 Llbrar7 Collections '70 . . . 75 911 Museum Golfectioos " 69 , . . 75

Licensed to U.S. Dept. of Labor, MSHA, Dist. 3, Morgantown, WV. Only one paper copy may be printed. Networking not permitted.