Historic Asbestos Containing Materials Data University of Toronto - Scarborough Campus Phase 1 and Phase 2 Residences 2017 ACM REASSESSMENT Page 1 of 31 Unit# Area Material Description Location Qty/Unit Sample Number % Type ACM (Yes, No, Suspect) Condition Accessibility Friability Comments Action Required THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4 KITCHEN DRYWALL JOINT COMPOUND CRACKED AND DAMAGED WALL ADJACENT TO STOVE <1 SQ.FT P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE RESIDENCE STAFF TO ARRANGE REMOVAL BY SPRING 2018. 2 INTERIOR - WINDOWS AND DOORS PERIMETER CAULKING VARIOUS CAULKING APPLICATIONS - INTERIOR PERIMETER OF WINDOWS AND DOORS - INTERIOR 45 L.FT. P1-2 (A-C) (2010 Report) ND GOOD A NON-FRIABLE N/A THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3490 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4 BEDROOM A-2-H DRYWALL JOINT COMPOUND DAMAGED CEILING AT LIGHT FIXTURE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE THE DAMAGED ASBESTOS-CONTAINING DRYWALL JOINT COMPOUND SHOULD BE REPAIRED FOLLOWING TYPE 1 ASBESTOS PROCEDURES, AS PRESCRIBED UNDER O. REG. 278/05. RESIDENCE STAFF TO ARRANGE REPAIR BY SPRING 2018. 2 INTERIOR - WINDOWS AND DOORS PERIMETER CAULKING VARIOUS CAULKING APPLICATIONS - INTERIOR PERIMETER OF WINDOWS AND DOORS - INTERIOR 45 L.FT. P1-2 (A-C) (2010 Report) ND GOOD A NON-FRIABLE N/A THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4 ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE THE DAMAGED ASBESTOS-CONTAINING DRYWALL JOINT COMPOUND SHOULD BE REPAIRED FOLLOWING TYPE 1 ASBESTOS PROCEDURES, AS PRESCRIBED UNDER O. REG. 278/05. RESIDENCE STAFF TO ARRANGE REPAIR BY SPRING 2018. 2 INTERIOR - WINDOWS AND DOORS PERIMETER CAULKING VARIOUS CAULKING APPLICATIONS - INTERIOR PERIMETER OF WINDOWS AND DOORS - INTERIOR 45 L.FT. P1-2 (A-C) (2010 Report) ND GOOD A NON-FRIABLE N/A THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4 ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE THE DAMAGED ASBESTOS-CONTAINING DRYWALL JOINT COMPOUND SHOULD BE REPAIRED FOLLOWING TYPE 1 ASBESTOS PROCEDURES, AS PRESCRIBED UNDER O. REG. 278/05.RESIDENCE STAFF TO ARRANGE REPAIR BY SPRING 2018. 2 KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE THE DAMAGED ASBESTOS-CONTAINING DRYWALL JOINT COMPOUND SHOULD BE REPAIRED FOLLOWING TYPE 1 ASBESTOS PROCEDURES, AS PRESCRIBED UNDER O. REG. 278/05. RESIDENCE STAFF TO ARRANGE REPAIR BY SPRING 2018. 2 BEDROOM A-4-G DRYWALL JOINT COMPOUND WATER DAMAGED CEILING 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE THE DAMAGED ASBESTOS-CONTAINING DRYWALL JOINT COMPOUND SHOULD BE REPAIRED FOLLOWING TYPE 1 ASBESTOS PROCEDURES, AS PRESCRIBED UNDER O. REG. 278/05. RESIDENCE STAFF TO ARRANGE REPAIR BY SPRING 2018. 2 A4 PHASE 1 RESIDENCE BUILDINGS A1 A2 A3 ASPEN HALL

Upload: others

Post on 03-Jul-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 1 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

KITCHEN DRYWALL JOINT COMPOUND CRACKED AND DAMAGED WALL ADJACENT TO STOVE <1 SQ.FT P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLERESIDENCE STAFF TO ARRANGE

REMOVAL BY SPRING 2018.2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3490 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

BEDROOM A-2-H DRYWALL JOINT COMPOUND DAMAGED CEILING AT LIGHT FIXTURE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG.

278/05.RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM A-4-G DRYWALL JOINT COMPOUND WATER DAMAGED CEILING 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

A4

PHASE 1 RESIDENCE BUILDINGS

A1

A2

A3

ASPEN HALL

Page 2: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 2 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

BEDROOM A-4-H DRYWALL JOINT COMPOUND CRACKING, BUBBLING AND PEELING WALL 20 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

WASHROOM DRYWALL JOINT COMPOUND DAMAGED BESIDE BATHTUB 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLERESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3498 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUNDENTRANCE VESTIBULE ADJACENT TO

THE FIRE EXTINGUISHER - WALL2 SQ.FT P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3496 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

BASEMENT DRYWALL JOINT COMPOUND WATER DAMAGED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM A-6-G DRYWALL JOINT COMPOUND DAMAGED WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

A6 INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

A7 THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

A6

A4

A5

Page 3: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 3 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

DRYWALL JOINT COMPOUND DAMAGED ADJACENT TO STOVE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED ADJACENT TO KITCHEN TABLE 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND WATER DAMAGED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

BEDROOM A-7-G DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO MIRROR <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM A-7-J DRYWALL JOINT COMPOUND HOLE IN DRYWALL WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3497 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

A8

A7

KITCHEN

Page 4: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 4 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3499 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

BEDROOM A-9-F DRYWALL JOINT COMPOUND DAMAGED WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

WASHROOM DRYWALL JOINT COMPOUND DAMAGED EDGING WALL ADJACENT TO SHOWER ROOM <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND WATER DAMAGED ADJACENT TO HOT WATER TANK 6 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND CRACKED ON BULKHEADSECOND FLOOR OUTSIDE BEDROOM A-

10-G6 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

DRYWALL JOINT COMPOUND DAMAGED ADJACENT TO KITCHEN TABLE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED EDGING ADJACENT TO STOVE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

A11

A10

A10

KITCHEN

A9

Page 5: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 5 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

CORRIDOR DRYWALL JOINT COMPOUND HOLE IN DRYWALL ADJACENT TO BEDROOM A-11-H <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND WATER DAMAGED WALL ADJACENT TO BATHTUB 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND WATER DAMAGED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3490 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

KITCHEN DRYWALL JOINT COMPOUND CRACKING AND PEELING ADJACENT TO KITCHEN TABLE 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND WATER STAINED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND WATER STAINED WALL ADJACENT TO HOT WATER TANK 5 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

A11

BIRCH HALL

SHOWER ROOM

BASEMENT

B1

Page 6: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 6 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL <1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND WATER STAINED WALL 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND WATER STAINEDBELOW STAIRS ADJACENT TO HOT

WATER TANK3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED BULKHEAD ADJACENT TO BEDROOM B-2-G 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED WALL <1SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED AT KITCHEN TABLE AND BEHIND SOFA 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND CRACKING AND DAMAGED OUTSIDE BEDROOM B-3-G 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

BASEMENT

B3

B2

Page 7: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 7 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 6 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND HOLE IN DRYWALL ADJACENT TO KITCHEN TABLE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED WALL 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM B-4-F DRYWALL JOINT COMPOUND WATER DAMAGED CEILING 5 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

THIRD FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM B-4-H DRYWALL JOINT COMPOUND DAMAGED WALL 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SHOWER ROOM DRYWALL JOINT COMPOUND WATER DAMAGED WALL ADJACENT TO SHOWER <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

B4

B4

Page 8: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 8 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3498 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING KITCHEN ENTRANCE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED WALL 50 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

SHOWER ROOM DRYWALL JOINT COMPOUND WATER DAMAGED WALL ADJACENT TO SHOWER 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3495 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3497 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 50 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

B7 INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3499 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

B8

B7

B6

B5

Page 9: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 9 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

LIVING ROOM DRYWALL JOINT COMPOUND HOLE IN DRYWALL WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE <1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED WALL BELOW KITCHEN LIGHT 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND DAMAGED EDGINGBELOW STAIRS ADJACENT TO HOT

WATER TANK<1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM C-1-H DRYWALL JOINT COMPOUND HOLE IN DRYWALL WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

B8

C1

C1

KITCHEN

CEDAR HALL

Page 10: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 10 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3485 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED WALL 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO STOVE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SHOWER ROOM DRYWALL JOINT COMPOUND WATER DAMAGED WALL ADJACENT TO SHOWER 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 6 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SHOWER ROOM DRYWALL JOINT COMPOUND MOULD IMPACTED WALL ADJACENT TO SHOWER 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 1 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

C2

C3

C3

Page 11: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 11 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3496 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

KITCHEN DRYWALL JOINT COMPOUND DAMAGED EDGING WALL ADJACENT TO KITCHEN TABLE <1 SQ. FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

BEDROOM C-4-F DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3475 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED WALL 4 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED WALL OUTSIDE BEDROOM C-5-H 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

C4

C5

Page 12: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 12 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN WINDOW 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 16 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL OUTSIDE BEDROOM C-6-H 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND HOLE IN DRYWALL WALL <1 SQ.FT P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM C-6-I

KITCHEN

C6

C6

C6

Page 13: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 13 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

BEDROOM C-6-J DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM C-F-K DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND DAMAGED WALL AT BASE OF THE STAIRWELL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING WALL ADJACENT TO SINK 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

C7

C6

C7

Page 14: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 14 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3495 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING BULKHEAD ABOVE STAIRS 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM C-8-H DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3496 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO SLIDING DOOR 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 5 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

C8

C8

D1

D1

DOGWOOD HALL

Page 15: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 15 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

BEDROOM D-1-K DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

THIRD FLOOR LANDING DRYWALL JOINT COMPOUND BUBBLING AND DAMAGED DRYWALL CEILING P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3497 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED WALL 20 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED EDGING WALL ADJACENT TO SLIDING DOOR 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM D-2-F DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM D-2-H DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING WALL OUTSIDE OF ROOM D-2-H 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

D1

D2

D2

Page 16: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 16 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

BEDROOM D-2-I DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3495 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED EDGING WALL ADJACENT TO STOVE 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER

DAMAGED DRYWALLWALL 11 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

BEDROOM D-3-H DRYWALL JOINT COMPOUND CRACKED DRYWALL CEILING P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BEDROOM D-3-K DRYWALL JOINT COMPOUND DAMAGED EDGING WALL P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

D3

D2

Page 17: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 17 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

LIVING ROOM DRYWALL JOINT COMPOUND DAMAGEDWALL ADJACENT TO SLIDING DOOR

ABOVE THE RADIATOR4 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED ADJACENT TO STOVE 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER

DAMAGED DRYWALLWALL 3 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 1 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

BEDROOM B-4-I DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

D4

Page 18: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 18 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT SLIDING DOOR 3 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED WALL 20 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

KITCHEN DRYWALL JOINT COMPOUND HOLE IN DRYWALL ADJACENT TO KITCHEN TABLE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING WALL OUTSIDE BEDROOM D-6-G 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

D5

D6

KITCHEN

Page 19: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 19 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 12 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

BEDROOM D-7-F DRYWALL JOINT COMPOUND DAMAGED WALL IN CLOSET 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED WALL OUTSIDE BEDROOM D-7-G 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SHOWER ROOM DRYWALL JOINT COMPOUND WATER DAMAGED WALL ADJACENT TO SHOWER 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 6 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO SLIDING DOOR 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

D8

D7

Page 20: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 20 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING BULKHEAD ABOVE STAIRS 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND CRACKED DRYWALL BULKHEAD ABOVE STAIRS 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND HOLE IN DRYWALL WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

LIVING ROOM DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL ADJACENT SLIDING DOOR 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

ELM HALL

E1

D8

D9

Page 21: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 21 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

KITCHEN DRYWALL JOINT COMPOUND BUBBLING AND DAMAGED DRYWALL CEILING IN THE CORNER 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER

DAMAGED DRYWALLWALL 15 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3490 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

LIVING ROOM DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL ADJACENT TO SLIDING DOOR 6 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED DRYWALL WALL ADJACENT TO KITCHEN TABLE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND DAMAGED DRYWALL WALL ADJACENT TO STOVE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

E3

E2

KITCHEN

ENTRANCE

Page 22: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 22 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

BASEMENT DRYWALL JOINT COMPOUND WATER STAINED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

SHOWER ROOM DRYWALL JOINT COMPOUND MOULD IMPACTED WALL ADJACENT TO SHOWER 6 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 1 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

BEDROOM E-3-J DRYWALL JOINT COMPOUND DAMAGED EDGING WALL P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3497 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER

DAMAGED DRYWALLWALL 4 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 1 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

E3

E4

E5

E6

E7

Page 23: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 23 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER

DAMAGED DRYWALLWALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 2

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 2 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

BEDROOM E-7-G DRYWALL JOINT COMPOUND DAMAGED WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3494 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

KITCHEN DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUNDMOULD AND WATER DAMAGED

DRYWALL WALL 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 1 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

SECOND FLOOR LANDING DRYWALL JOINT COMPOUND CRACKED DRYWALL BULKHEAD ABOVE STAIRS 8 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

THIRD FLOOR LANDING DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL OUTSIDE BEDROOM E-8-H 8 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

E7

E8

Page 24: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 24 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4

ENTRANCE DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL ADJACENT TO SLIDING DOOR 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER

DAMAGED DRYWALLWALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE

THE DAMAGED ASBESTOS-CONTAINING

DRYWALL JOINT COMPOUND SHOULD

BE REPAIRED FOLLOWING TYPE 1

ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05,

AND LEVEL 1 MOULD REMEDIATION

PROCEDURES. RESIDENCE STAFF TO

ARRANGE REPAIR BY SPRING 2018.

2

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND NO GOOD A NON-FRIABLE N/A

GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC

12"X12" TAN VINYL FLOOR TILES WITH

BROWN STREAKS AND YELLOW

MASTIC

SMALL CLOSET 6 SQ.FT.02 (A-C) (2013 RE-

ASSESSMENT1.0-1.2 CHRYSOTILE YES GOOD A NON-FRIABLE

THE MASTIC WAS ALSO ANALYZED AND

DETERMINED TO BE NON-ASBESTOS.

THESE TILES MAY BE PRESENT IN

OTHER PHASE 2 RESIDENCE

BUILDINGS IN CONCEALED AREAS (I.E.,

BENEATH CARPETS AND NEWER

FLOORING LAYERS).

4

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ. FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

PHASE 2 RESIDENCE BUILDINGS

FIR HALL

F1

LIVING ROOM

E9

Page 25: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 25 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC

12"X12" TAN VINYL FLOOR TILES WITH

BROWN STREAKS AND YELLOW

MASTIC

SMALL CLOSET 6 SQ.FT.02 (A-C) (2013 RE-

ASSESSMENT1.0-1.2 CHRYSOTILE YES GOOD A NON-FRIABLE

THE MASTIC WAS ALSO ANALYZED AND

DETERMINED TO BE NON-ASBESTOS.

THESE TILES MAY BE PRESENT IN

OTHER PHASE 2 RESIDENCE

BUILDINGS IN CONCEALED AREAS (I.E.,

BENEATH CARPETS AND NEWER

FLOORING LAYERS).

4

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC

12"X12" TAN VINYL FLOOR TILES WITH

BROWN STREAKS AND YELLOW

MASTIC

SMALL CLOSET 2 SQ.FT.02 (A-C) (2013 RE-

ASSESSMENT1.0-1.2 CHRYSOTILE YES GOOD A NON-FRIABLE

THE MASTIC WAS ALSO ANALYZED AND

DETERMINED TO BE NON-ASBESTOS.

THESE TILES MAY BE PRESENT IN

OTHER PHASE 2 RESIDENCE

BUILDINGS IN CONCEALED AREAS (I.E.,

BENEATH CARPETS AND NEWER

FLOORING LAYERS).

4

F2

F3

F4

F5

F6

Page 26: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 26 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

F6 GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC

12"X12" TAN VINYL FLOOR TILES WITH

BROWN STREAKS AND YELLOW

MASTIC

SMALL CLOSET 4 SQ.FT.02 (A-C) (2013 RE-

ASSESSMENT1.0-1.2 CHRYSOTILE YES POOR A NON-FRIABLE

THE MASTIC WAS ALSO ANALYZED AND

DETERMINED TO BE NON-ASBESTOS.

THE DAMAGED ASBESTOS-CONTAINING

VINYL FLOOR TILES SHOULD BE

REMOVED AND REPLACED FOLLOWING

TYPE 1 ASBESTOS PROCEDURES, AS

PRESCRIBED UNDER O. REG. 278/05.

RESIDENCE STAFF TO ARRANGE

REPAIR BY SPRING 2018.

2

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC

12"X12" TAN VINYL FLOOR TILES WITH

BROWN STREAKS AND YELLOW

MASTIC

SMALL CLOSET 6 SQ.FT.02 (A-C) (2013 RE-

ASSESSMENT1.0-1.2 CHRYSOTILE YES GOOD A NON-FRIABLE

THE MASTIC WAS ALSO ANALYZED AND

DETERMINED TO BE NON-ASBESTOS.

THESE TILES MAY BE PRESENT IN

OTHER PHASE 2 RESIDENCE

BUILDINGS IN CONCEALED AREAS (I.E.,

BENEATH CARPETS AND NEWER

FLOORING LAYERS).

4

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC

12"X12" TAN VINYL FLOOR TILES WITH

BROWN STREAKS AND YELLOW

MASTIC

SMALL CLOSET 6 SQ.FT.02 (A-C) (2013 RE-

ASSESSMENT1.0-1.2 CHRYSOTILE YES GOOD A NON-FRIABLE

THE MASTIC WAS ALSO ANALYZED AND

DETERMINED TO BE NON-ASBESTOS.

THESE TILES MAY BE PRESENT IN

OTHER PHASE 2 RESIDENCE

BUILDINGS IN CONCEALED AREAS (I.E.,

BENEATH CARPETS AND NEWER

FLOORING LAYERS).

4

F10

F11

F7

F8

F9

Page 27: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 27 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

G1

G2

G3

G4

GREY PINE HALL

Page 28: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 28 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

G5

G8

G9

G6

G7

Page 29: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 29 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

H4

H5

H1

HICKORY HALL

H2

H3

H6

H7

Page 30: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 30 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

H9

H10

IRONWOOD HALL

I1

I2

I3

H8

Page 31: Historic Asbestos Containing Materials Data ... - University of Toronto€¦ · interior - windows and doors perimeter caulking various caulking applications - interior perimeter

Historic Asbestos Containing Materials Data

University of Toronto - Scarborough Campus

Phase 1 and Phase 2 Residences

2017 ACM REASSESSMENT

Page 31 of 31

Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,

Suspect)Condition Accessibility Friability Comments

Action

Required

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010

Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE

TRACE ASBESTOS DETECTED.

MATERIAL NOT CONSIDERED TO B E

ASBESTOS-CONTAINING.

N/A

INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -

INTERIOR

PERIMETER OF WINDOWS AND DOORS -

INTERIOR45 L.FT.

P2-2(A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010

Report)ND GOOD A NON-FRIABLE N/A

THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM

RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A

I4

I5

I6