Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 1 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
KITCHEN DRYWALL JOINT COMPOUND CRACKED AND DAMAGED WALL ADJACENT TO STOVE <1 SQ.FT P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLERESIDENCE STAFF TO ARRANGE
REMOVAL BY SPRING 2018.2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3490 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
BEDROOM A-2-H DRYWALL JOINT COMPOUND DAMAGED CEILING AT LIGHT FIXTURE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG.
278/05.RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM A-4-G DRYWALL JOINT COMPOUND WATER DAMAGED CEILING 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
A4
PHASE 1 RESIDENCE BUILDINGS
A1
A2
A3
ASPEN HALL
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 2 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
BEDROOM A-4-H DRYWALL JOINT COMPOUND CRACKING, BUBBLING AND PEELING WALL 20 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
WASHROOM DRYWALL JOINT COMPOUND DAMAGED BESIDE BATHTUB 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLERESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3498 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUNDENTRANCE VESTIBULE ADJACENT TO
THE FIRE EXTINGUISHER - WALL2 SQ.FT P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3496 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
BASEMENT DRYWALL JOINT COMPOUND WATER DAMAGED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM A-6-G DRYWALL JOINT COMPOUND DAMAGED WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
A6 INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
A7 THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
A6
A4
A5
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 3 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
DRYWALL JOINT COMPOUND DAMAGED ADJACENT TO STOVE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED ADJACENT TO KITCHEN TABLE 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND WATER DAMAGED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
BEDROOM A-7-G DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO MIRROR <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM A-7-J DRYWALL JOINT COMPOUND HOLE IN DRYWALL WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3497 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
A8
A7
KITCHEN
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 4 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3499 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
BEDROOM A-9-F DRYWALL JOINT COMPOUND DAMAGED WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
WASHROOM DRYWALL JOINT COMPOUND DAMAGED EDGING WALL ADJACENT TO SHOWER ROOM <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND WATER DAMAGED ADJACENT TO HOT WATER TANK 6 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND CRACKED ON BULKHEADSECOND FLOOR OUTSIDE BEDROOM A-
10-G6 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
DRYWALL JOINT COMPOUND DAMAGED ADJACENT TO KITCHEN TABLE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED EDGING ADJACENT TO STOVE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
A11
A10
A10
KITCHEN
A9
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 5 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
CORRIDOR DRYWALL JOINT COMPOUND HOLE IN DRYWALL ADJACENT TO BEDROOM A-11-H <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND WATER DAMAGED WALL ADJACENT TO BATHTUB 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND WATER DAMAGED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3490 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
KITCHEN DRYWALL JOINT COMPOUND CRACKING AND PEELING ADJACENT TO KITCHEN TABLE 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND WATER STAINED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND WATER STAINED WALL ADJACENT TO HOT WATER TANK 5 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
A11
BIRCH HALL
SHOWER ROOM
BASEMENT
B1
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 6 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL <1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND WATER STAINED WALL 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND WATER STAINEDBELOW STAIRS ADJACENT TO HOT
WATER TANK3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED BULKHEAD ADJACENT TO BEDROOM B-2-G 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED WALL <1SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED AT KITCHEN TABLE AND BEHIND SOFA 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND CRACKING AND DAMAGED OUTSIDE BEDROOM B-3-G 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
BASEMENT
B3
B2
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 7 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 6 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND HOLE IN DRYWALL ADJACENT TO KITCHEN TABLE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED WALL 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM B-4-F DRYWALL JOINT COMPOUND WATER DAMAGED CEILING 5 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
THIRD FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM B-4-H DRYWALL JOINT COMPOUND DAMAGED WALL 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SHOWER ROOM DRYWALL JOINT COMPOUND WATER DAMAGED WALL ADJACENT TO SHOWER <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
B4
B4
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 8 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3498 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING KITCHEN ENTRANCE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED WALL 50 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
SHOWER ROOM DRYWALL JOINT COMPOUND WATER DAMAGED WALL ADJACENT TO SHOWER 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3495 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3497 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 50 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
B7 INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3499 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
B8
B7
B6
B5
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 9 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
LIVING ROOM DRYWALL JOINT COMPOUND HOLE IN DRYWALL WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE <1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED WALL BELOW KITCHEN LIGHT 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND DAMAGED EDGINGBELOW STAIRS ADJACENT TO HOT
WATER TANK<1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM C-1-H DRYWALL JOINT COMPOUND HOLE IN DRYWALL WALL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
B8
C1
C1
KITCHEN
CEDAR HALL
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 10 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3485 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED WALL 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO STOVE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SHOWER ROOM DRYWALL JOINT COMPOUND WATER DAMAGED WALL ADJACENT TO SHOWER 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 6 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SHOWER ROOM DRYWALL JOINT COMPOUND MOULD IMPACTED WALL ADJACENT TO SHOWER 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 1 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
C2
C3
C3
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 11 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3496 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
KITCHEN DRYWALL JOINT COMPOUND DAMAGED EDGING WALL ADJACENT TO KITCHEN TABLE <1 SQ. FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
BEDROOM C-4-F DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3475 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED WALL 4 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED WALL OUTSIDE BEDROOM C-5-H 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
C4
C5
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 12 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN WINDOW 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 16 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL OUTSIDE BEDROOM C-6-H 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND HOLE IN DRYWALL WALL <1 SQ.FT P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM C-6-I
KITCHEN
C6
C6
C6
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 13 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
BEDROOM C-6-J DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM C-F-K DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND DAMAGED WALL AT BASE OF THE STAIRWELL <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING WALL ADJACENT TO SINK 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
C7
C6
C7
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 14 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3495 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING BULKHEAD ABOVE STAIRS 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM C-8-H DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3496 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO SLIDING DOOR 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED AND DAMAGED WALL 5 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
C8
C8
D1
D1
DOGWOOD HALL
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 15 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
BEDROOM D-1-K DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
THIRD FLOOR LANDING DRYWALL JOINT COMPOUND BUBBLING AND DAMAGED DRYWALL CEILING P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3497 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED WALL 20 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED EDGING WALL ADJACENT TO SLIDING DOOR 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM D-2-F DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM D-2-H DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING WALL OUTSIDE OF ROOM D-2-H 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
D1
D2
D2
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 16 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
BEDROOM D-2-I DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3495 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED EDGING WALL ADJACENT TO STOVE 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER
DAMAGED DRYWALLWALL 11 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
BEDROOM D-3-H DRYWALL JOINT COMPOUND CRACKED DRYWALL CEILING P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BEDROOM D-3-K DRYWALL JOINT COMPOUND DAMAGED EDGING WALL P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
D3
D2
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 17 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
LIVING ROOM DRYWALL JOINT COMPOUND DAMAGEDWALL ADJACENT TO SLIDING DOOR
ABOVE THE RADIATOR4 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED ADJACENT TO STOVE 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER
DAMAGED DRYWALLWALL 3 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 1 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
BEDROOM B-4-I DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
D4
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 18 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT SLIDING DOOR 3 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED WALL 20 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
KITCHEN DRYWALL JOINT COMPOUND HOLE IN DRYWALL ADJACENT TO KITCHEN TABLE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING WALL OUTSIDE BEDROOM D-6-G 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
D5
D6
KITCHEN
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 19 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 12 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
BEDROOM D-7-F DRYWALL JOINT COMPOUND DAMAGED WALL IN CLOSET 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED WALL OUTSIDE BEDROOM D-7-G 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SHOWER ROOM DRYWALL JOINT COMPOUND WATER DAMAGED WALL ADJACENT TO SHOWER 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 6 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
LIVING ROOM DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO SLIDING DOOR 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
D8
D7
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 20 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND DAMAGED EDGING BULKHEAD ABOVE STAIRS 3 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND CRACKED DRYWALL BULKHEAD ABOVE STAIRS 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND HOLE IN DRYWALL WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
LIVING ROOM DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL ADJACENT SLIDING DOOR 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
ELM HALL
E1
D8
D9
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 21 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
KITCHEN DRYWALL JOINT COMPOUND BUBBLING AND DAMAGED DRYWALL CEILING IN THE CORNER 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER
DAMAGED DRYWALLWALL 15 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3490 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 5 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
LIVING ROOM DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL ADJACENT TO SLIDING DOOR 6 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED DRYWALL WALL ADJACENT TO KITCHEN TABLE <1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND DAMAGED DRYWALL WALL ADJACENT TO STOVE 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
E3
E2
KITCHEN
ENTRANCE
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 22 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
BASEMENT DRYWALL JOINT COMPOUND WATER STAINED WALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
SHOWER ROOM DRYWALL JOINT COMPOUND MOULD IMPACTED WALL ADJACENT TO SHOWER 6 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 1 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
BEDROOM E-3-J DRYWALL JOINT COMPOUND DAMAGED EDGING WALL P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3497 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER
DAMAGED DRYWALLWALL 4 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 1 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
E3
E4
E5
E6
E7
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 23 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
KITCHEN DRYWALL JOINT COMPOUND DAMAGED WALL ADJACENT TO KITCHEN TABLE 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER
DAMAGED DRYWALLWALL 10 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 2
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 2 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
BEDROOM E-7-G DRYWALL JOINT COMPOUND DAMAGED WALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3494 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
KITCHEN DRYWALL JOINT COMPOUND DAMAGED EDGING WALL 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUNDMOULD AND WATER DAMAGED
DRYWALL WALL 2 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 1 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
SECOND FLOOR LANDING DRYWALL JOINT COMPOUND CRACKED DRYWALL BULKHEAD ABOVE STAIRS 8 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
THIRD FLOOR LANDING DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL OUTSIDE BEDROOM E-8-H 8 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
E7
E8
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 24 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES GOOD A NON-FRIABLE 4
ENTRANCE DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL 2 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL ADJACENT TO SLIDING DOOR 1 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
DRYWALL JOINT COMPOUND CRACKED DRYWALL WALL 4 L.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES FAIR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
BASEMENT DRYWALL JOINT COMPOUNDMOULD IMPACTED AND WATER
DAMAGED DRYWALLWALL 1 SQ.FT. P1-1a (2010 Report) 1.5 CHRYSOTILE YES POOR A NON-FRIABLE
THE DAMAGED ASBESTOS-CONTAINING
DRYWALL JOINT COMPOUND SHOULD
BE REPAIRED FOLLOWING TYPE 1
ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05,
AND LEVEL 1 MOULD REMEDIATION
PROCEDURES. RESIDENCE STAFF TO
ARRANGE REPAIR BY SPRING 2018.
2
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND NO GOOD A NON-FRIABLE N/A
GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC
12"X12" TAN VINYL FLOOR TILES WITH
BROWN STREAKS AND YELLOW
MASTIC
SMALL CLOSET 6 SQ.FT.02 (A-C) (2013 RE-
ASSESSMENT1.0-1.2 CHRYSOTILE YES GOOD A NON-FRIABLE
THE MASTIC WAS ALSO ANALYZED AND
DETERMINED TO BE NON-ASBESTOS.
THESE TILES MAY BE PRESENT IN
OTHER PHASE 2 RESIDENCE
BUILDINGS IN CONCEALED AREAS (I.E.,
BENEATH CARPETS AND NEWER
FLOORING LAYERS).
4
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ. FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
PHASE 2 RESIDENCE BUILDINGS
FIR HALL
F1
LIVING ROOM
E9
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 25 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC
12"X12" TAN VINYL FLOOR TILES WITH
BROWN STREAKS AND YELLOW
MASTIC
SMALL CLOSET 6 SQ.FT.02 (A-C) (2013 RE-
ASSESSMENT1.0-1.2 CHRYSOTILE YES GOOD A NON-FRIABLE
THE MASTIC WAS ALSO ANALYZED AND
DETERMINED TO BE NON-ASBESTOS.
THESE TILES MAY BE PRESENT IN
OTHER PHASE 2 RESIDENCE
BUILDINGS IN CONCEALED AREAS (I.E.,
BENEATH CARPETS AND NEWER
FLOORING LAYERS).
4
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC
12"X12" TAN VINYL FLOOR TILES WITH
BROWN STREAKS AND YELLOW
MASTIC
SMALL CLOSET 2 SQ.FT.02 (A-C) (2013 RE-
ASSESSMENT1.0-1.2 CHRYSOTILE YES GOOD A NON-FRIABLE
THE MASTIC WAS ALSO ANALYZED AND
DETERMINED TO BE NON-ASBESTOS.
THESE TILES MAY BE PRESENT IN
OTHER PHASE 2 RESIDENCE
BUILDINGS IN CONCEALED AREAS (I.E.,
BENEATH CARPETS AND NEWER
FLOORING LAYERS).
4
F2
F3
F4
F5
F6
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 26 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
F6 GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC
12"X12" TAN VINYL FLOOR TILES WITH
BROWN STREAKS AND YELLOW
MASTIC
SMALL CLOSET 4 SQ.FT.02 (A-C) (2013 RE-
ASSESSMENT1.0-1.2 CHRYSOTILE YES POOR A NON-FRIABLE
THE MASTIC WAS ALSO ANALYZED AND
DETERMINED TO BE NON-ASBESTOS.
THE DAMAGED ASBESTOS-CONTAINING
VINYL FLOOR TILES SHOULD BE
REMOVED AND REPLACED FOLLOWING
TYPE 1 ASBESTOS PROCEDURES, AS
PRESCRIBED UNDER O. REG. 278/05.
RESIDENCE STAFF TO ARRANGE
REPAIR BY SPRING 2018.
2
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC
12"X12" TAN VINYL FLOOR TILES WITH
BROWN STREAKS AND YELLOW
MASTIC
SMALL CLOSET 6 SQ.FT.02 (A-C) (2013 RE-
ASSESSMENT1.0-1.2 CHRYSOTILE YES GOOD A NON-FRIABLE
THE MASTIC WAS ALSO ANALYZED AND
DETERMINED TO BE NON-ASBESTOS.
THESE TILES MAY BE PRESENT IN
OTHER PHASE 2 RESIDENCE
BUILDINGS IN CONCEALED AREAS (I.E.,
BENEATH CARPETS AND NEWER
FLOORING LAYERS).
4
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
GROUND FLOOR - ENTRANCE CORRIDOR VINYL FLOOR TILES WITH YELLOW MASTIC
12"X12" TAN VINYL FLOOR TILES WITH
BROWN STREAKS AND YELLOW
MASTIC
SMALL CLOSET 6 SQ.FT.02 (A-C) (2013 RE-
ASSESSMENT1.0-1.2 CHRYSOTILE YES GOOD A NON-FRIABLE
THE MASTIC WAS ALSO ANALYZED AND
DETERMINED TO BE NON-ASBESTOS.
THESE TILES MAY BE PRESENT IN
OTHER PHASE 2 RESIDENCE
BUILDINGS IN CONCEALED AREAS (I.E.,
BENEATH CARPETS AND NEWER
FLOORING LAYERS).
4
F10
F11
F7
F8
F9
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 27 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
G1
G2
G3
G4
GREY PINE HALL
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 28 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
G5
G8
G9
G6
G7
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 29 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
H4
H5
H1
HICKORY HALL
H2
H3
H6
H7
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 30 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
H9
H10
IRONWOOD HALL
I1
I2
I3
H8
Historic Asbestos Containing Materials Data
University of Toronto - Scarborough Campus
Phase 1 and Phase 2 Residences
2017 ACM REASSESSMENT
Page 31 of 31
Unit# Area Material Description Location Qty/Unit Sample Number % TypeACM (Yes, No,
Suspect)Condition Accessibility Friability Comments
Action
Required
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
EXTERIOR CAULKING BROWN CAULKING EXTERIOR WINDOWS, DOORS & TRIM 45 L.FT.P2-3(A-C) (2010
Report)0.25 CHRYSOTILE NO GOOD A NON-FRIABLE
TRACE ASBESTOS DETECTED.
MATERIAL NOT CONSIDERED TO B E
ASBESTOS-CONTAINING.
N/A
INTERIOR - WINDOWS AND DOORS PERIMETER CAULKINGVARIOUS CAULKING APPLICATIONS -
INTERIOR
PERIMETER OF WINDOWS AND DOORS -
INTERIOR45 L.FT.
P2-2(A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS 3500 SQ.FT.P1-2 (A-C) (2010
Report)ND GOOD A NON-FRIABLE N/A
THROUGHOUT DRYWALL JOINT COMPOUND WHITE DRYWALL JOINT COMPOUND WALLS AND CEILINGS SEE ABOVE01 (A-D) (2013 ACM
RE-ASSESSMENT)ND GOOD A NON-FRIABLE N/A
I4
I5
I6